<strong>AC</strong> <strong>voltage</strong> <strong>transducer</strong><br />

<strong>UW</strong> <strong>13.01</strong> G<br />

FEATURES<br />

Input:<br />

<strong>AC</strong> <strong>voltage</strong> up to 500 V <strong>AC</strong>,<br />

True RMS value recording<br />

Output, simultaneous:<br />

Current 0(4)…20 mA and<br />

Voltage 0(2)…10 V<br />

Galvanic 3-way isolation<br />

of 4 kV<br />

FUNCTION<br />

The <strong>UW</strong> <strong>13.01</strong> G is being used to convert a <strong>AC</strong> <strong>voltage</strong><br />

signal into a standard signal.<br />

It has an <strong>AC</strong> <strong>voltage</strong> input and an output for current<br />

and <strong>voltage</strong> simultaneous.<br />

Indication of operating state is displayed by LED on<br />

front side.<br />

Auxiliary power: 230 V <strong>AC</strong>/ 24 V UC/ wide range<br />

99<br />

1 2<br />

Power supply<br />

Input<br />

~ U[V]<br />

~ U[V]<br />

10<br />

uP<br />

6<br />

5<br />

9 8<br />

7<br />

Output<br />

+ I [mA]<br />

GND<br />

+ U [V]<br />

GND<br />

114,5<br />

Status<br />

22,5<br />

07-7


1 2 3 4<br />

5 6 7 8<br />

<strong>UW</strong> <strong>13.01</strong> G<br />

~<br />

~<br />

- I<br />

+ I<br />

- U<br />

+ U<br />

Auxiliary power<br />

Output<br />

simultaneous<br />

Status LED<br />

Input:<br />

U: <strong>AC</strong> <strong>voltage</strong>: max. 500 V <strong>AC</strong>, 50 Hz<br />

True RMS value recording<br />

Customer specification of and input setting, e.g.<br />

input:<br />

or input:<br />

or input:<br />

0...20 V <strong>AC</strong><br />

0...100 V <strong>AC</strong><br />

0...400 V <strong>AC</strong><br />

connection: terminal 9, 10<br />

Output:<br />

Customer specification, factory setting: 0...20 mA<br />

I: load-independent <strong>AC</strong> current: 0(4)...20 mA permissible load max. 500 Ω<br />

U: load-independent <strong>AC</strong> <strong>voltage</strong>: 0(2)...10 V permissible load ≥ 5 kΩ<br />

9 10 11 12<br />

Input<br />

~ U<br />

~ U<br />

Display:<br />

LED Status: green, active input signal within range, ready for operation<br />

13 14 15 16<br />

Environmental conditions:<br />

Storage temperature: -20...+70 °C<br />

Operating temperature: 0...55 °C<br />

Isolation <strong>voltage</strong>: 4 kV eff. 1 sec.<br />

input/ output/ auxiliary <strong>voltage</strong><br />

Auxiliary power:<br />

230 V <strong>AC</strong>: 200...250 V <strong>AC</strong><br />

approx. 9 mA<br />

24 V UC: 20...30 V <strong>AC</strong>/ DC<br />

approx. 50 mA<br />

Wide range:<br />

20...253 V <strong>AC</strong>/ DC<br />

approx. 10...50 mA<br />

Infl. of auxiliary power: < 0,1 %<br />

Characteristics of transmission:<br />

Transmission error: < 1 % of final value<br />

Linearity error: ± 0,1 %<br />

Resolution:<br />

10 bit<br />

Temperature error: < 100 ppm/ K<br />

Load influence I: < 50 ppm<br />

of final value<br />

Load influence U: < 0,2%<br />

at 1 kΩ load<br />

Set time:<br />

4 sec. factory set<br />

(0,5...64 sec. possible)<br />

Directive:<br />

EMC Directive:<br />

2004/108/EC*<br />

Low Voltage Directive: 2006/95/EC<br />

*minimum deviations possible during<br />

HF-radiation influence<br />

Mounting details:<br />

Housing for top hat rail<br />

Type of protection:<br />

IP 40 housing<br />

IP 20 clamps<br />

Mounting rail fixed according to<br />

EN 50022-35 x 6,2 mm<br />

Width:<br />

22,5 mm<br />

Weight:<br />

170 g<br />

Material:<br />

Polyamide PA<br />

Flammability class: V0 (UL94)<br />

Approval:<br />

CE<br />

Connection:<br />

pluggable<br />

screw clamps<br />

0,2...2,5 mm2<br />

For safety reasons we recommend to<br />

mount the housing for top hat rail with a<br />

distance of approx. 5 mm to each other.<br />

Please check switch position before initial<br />

operation!<br />

<strong>Schuhmann</strong> GmbH & Co. KG<br />

Kleingartacher Str. 21<br />

D-74363 Güglingen<br />

Tel. + 49 71 35 50 56<br />

Fax + 49 71 35 53 55<br />

www.schuhmann-messtechnik.de<br />

Ordering information:<br />

Please specify input- and output signal in<br />

clear text, e.g.:<br />

Input: 0…10 V <strong>AC</strong>, output: 4…20 mA<br />

Type: <strong>UW</strong> <strong>13.01</strong> G 230 V <strong>AC</strong><br />

<strong>UW</strong> <strong>13.01</strong> GUC<br />

24 V UC<br />

<strong>UW</strong> <strong>13.01</strong> GW<br />

wide range<br />

08.02.2013<br />

07-8