Options:<br />

Hydronic module (if required)<br />

■ The hydronic module shall be integrated in the chiller chassis<br />

without increasing its dimensions and include the following<br />

elements: removable screen filter, membrane type expansion<br />

tank, centrifugal single-cell water pump with three-phase<br />

motor equipped with internal over-temperature protection,<br />

electronic water flow switch without paddle, safety relief<br />

valve calibrated to 4 bar, long-stroke flow control valve. A<br />

pressure gauge and a valve set permit differential pressure<br />

measurements: water pump, evaporator pressure loss, filter<br />

pressure loss.<br />

■ To limit vibration and noise transmission the water pump<br />

shall be isolated from the chiller structure.<br />

■ The water piping shall be protected against corrosion and<br />

equipped with drain and purge plugs. The customer<br />

connections shall be Victaulic connections. The piping and<br />

the water pump shall be fully insulated by polyurethane<br />

foam, and aluminium cladding to prevent condensation.<br />

Emergency frost protection by starting up of the water pump<br />

in case of a risk of frost formation.<br />

■ A choice of four pump types shall be available:<br />

- Single high-pressure pump<br />

- Dual high-pressure pump<br />

- Single low-pressure pump<br />

- Dual low-pressure pump<br />

34