30XA 252-1702
30XA 252-1702
30XA 252-1702
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Options:<br />
Hydronic module (if required)<br />
■ The hydronic module shall be integrated in the chiller chassis<br />
without increasing its dimensions and include the following<br />
elements: removable screen filter, membrane type expansion<br />
tank, centrifugal single-cell water pump with three-phase<br />
motor equipped with internal over-temperature protection,<br />
electronic water flow switch without paddle, safety relief<br />
valve calibrated to 4 bar, long-stroke flow control valve. A<br />
pressure gauge and a valve set permit differential pressure<br />
measurements: water pump, evaporator pressure loss, filter<br />
pressure loss.<br />
■ To limit vibration and noise transmission the water pump<br />
shall be isolated from the chiller structure.<br />
■ The water piping shall be protected against corrosion and<br />
equipped with drain and purge plugs. The customer<br />
connections shall be Victaulic connections. The piping and<br />
the water pump shall be fully insulated by polyurethane<br />
foam, and aluminium cladding to prevent condensation.<br />
Emergency frost protection by starting up of the water pump<br />
in case of a risk of frost formation.<br />
■ A choice of four pump types shall be available:<br />
- Single high-pressure pump<br />
- Dual high-pressure pump<br />
- Single low-pressure pump<br />
- Dual low-pressure pump<br />
34