TCA - Halton
TCA - Halton
TCA - Halton
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Product Models<br />
Sizes 125, 160, 200 and 250 are available integrated in<br />
a steel panel for installation in modular 600x600 mm<br />
suspended ceilings.<br />
The external dimensions of the front panel are<br />
595 mm x 595 mm.<br />
20/<strong>TCA</strong>/3500/0106/EN<br />
ACCESSORIES<br />
ACCESSORY CODE DESCRIPTION<br />
Balancing plenum with airflow<br />
measurement and adjustment unit<br />
TRI/N<br />
For balancing, equalizing the airflow<br />
Plenum PLC Plenum for duct connection (with or without insulation)<br />
Sound attenuation IN Polyester fiber as sound attenuation material in the TRI plenum. Mineral wool as<br />
sound attenuation material in the PLC.<br />
Airflow measurement and<br />
adjustment unit<br />
MSM<br />
For supply installation<br />
Airflow adjustment unit LD Circular galvanised steel unit for flow adjustment (inside the coupling sleeve)<br />
Airflow adjustment damper DC Circular galvanised steel blade damper for flow adjustment (inside the coupling<br />
sleeve)<br />
Airflow adjustment unit CU1 Circular galvanised steel unit for flow adjustment in the plenum<br />
Electrical actuator M1 Adjustment of the position of the conical central core<br />
Wax-bulb actuator M2 Adjustment of the position of the conical central core<br />
Wax-bulb actuator<br />
The <strong>TCA</strong> (D355…630mm) can be equipped with a waxbulb<br />
actuator. Neither auxiliary energy nor dedicated<br />
control system are needed.<br />
The actuator position changes according to the<br />
temperature of supply air.<br />
When warm air is supplied at a temperature up<br />
to 18°C, the wax bulb actuator piston moves<br />
progressively until the conical central core is at the<br />
low position. The supply air pattern is vertical compact<br />
jet.<br />
The cycle for movement between extreme positions<br />
takes 10 to 20 minutes.<br />
When cold air is supplied, the conical central cone<br />
is returned back by springs to the upper position for<br />
horizontal radial jet function.<br />
The operation range of the wax-bulb actuator is<br />
between 18°C and 32°C.<br />
No maintenance is required for the wax-bulb actuator.<br />
<strong>TCA</strong> - Conical Ceiling Diffuser<br />