Product Models<br />

Sizes 125, 160, 200 and 250 are available integrated in<br />

a steel panel for installation in modular 600x600 mm<br />

suspended ceilings.<br />

The external dimensions of the front panel are<br />

595 mm x 595 mm.<br />

20/<strong>TCA</strong>/3500/0106/EN<br />

ACCESSORIES<br />

ACCESSORY CODE DESCRIPTION<br />

Balancing plenum with airflow<br />

measurement and adjustment unit<br />

TRI/N<br />

For balancing, equalizing the airflow<br />

Plenum PLC Plenum for duct connection (with or without insulation)<br />

Sound attenuation IN Polyester fiber as sound attenuation material in the TRI plenum. Mineral wool as<br />

sound attenuation material in the PLC.<br />

Airflow measurement and<br />

adjustment unit<br />

MSM<br />

For supply installation<br />

Airflow adjustment unit LD Circular galvanised steel unit for flow adjustment (inside the coupling sleeve)<br />

Airflow adjustment damper DC Circular galvanised steel blade damper for flow adjustment (inside the coupling<br />

sleeve)<br />

Airflow adjustment unit CU1 Circular galvanised steel unit for flow adjustment in the plenum<br />

Electrical actuator M1 Adjustment of the position of the conical central core<br />

Wax-bulb actuator M2 Adjustment of the position of the conical central core<br />

Wax-bulb actuator<br />

The <strong>TCA</strong> (D355…630mm) can be equipped with a waxbulb<br />

actuator. Neither auxiliary energy nor dedicated<br />

control system are needed.<br />

The actuator position changes according to the<br />

temperature of supply air.<br />

When warm air is supplied at a temperature up<br />

to 18°C, the wax bulb actuator piston moves<br />

progressively until the conical central core is at the<br />

low position. The supply air pattern is vertical compact<br />

jet.<br />

The cycle for movement between extreme positions<br />

takes 10 to 20 minutes.<br />

When cold air is supplied, the conical central cone<br />

is returned back by springs to the upper position for<br />

horizontal radial jet function.<br />

The operation range of the wax-bulb actuator is<br />

between 18°C and 32°C.<br />

No maintenance is required for the wax-bulb actuator.<br />

<strong>TCA</strong> - Conical Ceiling Diffuser<br />