TACO <strong>ZONE</strong> <strong>CONTROLS</strong> WIRING <strong>GUIDE</strong><br />

Pages<br />

Switching Relays – Single Zone Wiring 2 – 2<br />

Switching Relays – Oil Boiler Wiring Safety Notice 2 3 – 4<br />

Switching Relays – NON EXP Connected Together with Priority 5 – 11<br />

Switching Relays – EXP Connected Together with Priority 12 – 14<br />

Switching Relays – Multiple Indirect Hot Water Heaters 15 – 16<br />

Switching Relays – EXP Connected To Reset Controls (PC700, 702 & 705) 17 – 28<br />

Zone Valve Controls – NON EXP Connected Together with Priority 29 – 34<br />

Zone Valve Controls – EXP Connected Together with Priority 35 – 38<br />

Zone Valve Controls – Connected To Reset Controls (PC700, 702 & 705) 39 – 46<br />

Hydro Air Fan Controls (HAFC 101 & 201) 47 – 51<br />

Specialty Thermostat and Zone Valve Wiring 52 – 56<br />

Radiant Mixing Block 57 – 58<br />

X-Pump Block 59 – 61<br />

iSeries Mixing Valves 62 – 63<br />

Low Water Cutoffs and Electric Water Feeders 64 – 79<br />

Aquastat Wiring 80 – 86<br />

Instruction Sheets 87 – 97<br />

Standard Terms and Definitions – 98<br />

Cross Reference 99 – 100<br />

Do it once.<br />

Do it right.<br />

© <strong>Taco</strong> Catalog No. 100-9.0 Effective Date: July 1, 2010<br />

Supersedes Date: July 1, 2007


TACO Zone Control Product Information<br />

Switching Relays<br />

Product No.<br />

SR501<br />

SR501-845RP<br />

SR502<br />

SR503<br />

SR504<br />

SR506<br />

Description<br />

1 Zone Switching Relay<br />

1 Zone Switching Relay Replacement PC Board for<br />

Honeywell R845, RA89A, RA832 or Comparable Relay<br />

2 Zone Switching Relay with Priority<br />

3 Zone Switching Relay with Priority<br />

4 Zone Switching Relay with Priority<br />

6 Zone Switching Relay with Priority<br />

Switching Relays with PowerPort Options and Expandable to 20 Zones<br />

Product No.<br />

Description<br />

SR501-EXP<br />

1 Zone Switching Relay<br />

SR503-EXP<br />

3 Zone Switching Relay with Priority and 3 PowerPorts<br />

SR504-EXP<br />

4 Zone Switching Relay with Priority and 3 PowerPorts<br />

SR506-EXP<br />

6 Zone Switching Relay with Priority and 3 PowerPorts<br />

Zone Valve Controls<br />

Product No.<br />

ZVC403<br />

ZVC404<br />

ZVC405<br />

ZVC406<br />

Description<br />

3 Zone Valve Control<br />

4 Zone Valve Control with Priority<br />

5 Zone Valve Control<br />

6 Zone Valve Control with Priority<br />

Zone Valve Controls with PowerPort Options and Expandable to 20 Zones<br />

Product No.<br />

Description<br />

ZVC404-EXP<br />

4 Zone Valve Control with Priority and 2 PowerPorts<br />

ZVC406-EXP<br />

6 Zone Valve Control with Priority and 2 PowerPorts<br />

Plug-In PowerPort Cards (For use with all -EXP controls)<br />

Product No.<br />

Description<br />

PC600<br />

Post Purge Timer Plug-In Card<br />

PC605<br />

Priority Protection Plug-In Card<br />

PC610<br />

Universal Timer/Pump Exercise Plug-In Card<br />

Add-On Power Controls (For use with all -EXP controls)<br />

Product No.<br />

Description<br />

PC700<br />

Boiler Reset Control<br />

PC702<br />

2-Stage Boiler Reset Control<br />

PC705<br />

Variable Speed Pump Injection Mixing Control<br />

Fan Controls<br />

Product No.<br />

HAFC101<br />

HAFC201<br />

Description<br />

Hydro Air Fan Control<br />

Hydro Air Fan Control with Optional Time Delays<br />

Do it once.<br />

Do it right.


SR501 Switching Relay Wiring<br />

ALTERNATIVE WIRING<br />

(TANKLESS COIL)<br />

THERMOST<br />

AT<br />

T<br />

SR501<br />

1 <strong>ZONE</strong><br />

SWITCHING RELAY<br />

24<br />

R W VAC<br />

T T COM<br />

POWER<br />

T STAT<br />

120 VAC<br />

INPUT<br />

N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />

TO: ZC<br />

TO: ZR<br />

TO: 120 VAC POWER<br />

CIRCULATOR<br />

Note: When using Alternative Wiring diagram, the boiler operating<br />

control’s ZC terminal will see the load of the circulator(s).<br />

Warning: When using Alternative Wiring diagram, wiring<br />

instructions must be followed so power originates from the boiler<br />

aquastat. Failure to follow these wiring instructions may result in<br />

a secondary source of power being connected to the boiler that<br />

may activate it under certain circumstances, causing injury or death.<br />

ALTERNATIVE WIRING<br />

(24 VAC POWERED INPUT SIGNAL)<br />

24 VAC<br />

SIGNAL<br />

SR501<br />

1 <strong>ZONE</strong><br />

SWITCHING RELAY<br />

24<br />

R W VAC<br />

T T COM<br />

POWER *<br />

T STAT *<br />

N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />

H<br />

N<br />

TO: TT ON BOILER<br />

TO: 120 VAC POWER<br />

CIRCULATOR<br />

REMOVE JUMPER.<br />

DO NOT CONNECT POWER<br />

TO N AND H TERMINALS.<br />

* T STAT LIGHT WILL GO<br />

ON AND OFF WITH 24 VAC<br />

SIGNAL. POWER LIGHT<br />

WILL ALWAYS BE OFF.<br />

2<br />

TYPICAL WIRING<br />

(COLD START)<br />

AT<br />

THERMOST<br />

T<br />

24<br />

R W VAC<br />

T T COM<br />

SR501<br />

1 <strong>ZONE</strong><br />

SWITCHING RELAY<br />

POWER<br />

T STAT<br />

120 VAC<br />

INPUT<br />

N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />

JUMPER<br />

TO: TT ON BOILER<br />

CIRCULATOR<br />

TO: 120 VAC<br />

POWER


NOTE: No tankless coil priority.<br />

3


(cont.)<br />

(HOT)<br />

L1<br />

L2<br />

(NEUTRAL)<br />

THERMOSTATS<br />

CIRCUIT<br />

BREAKER<br />

CUSTOMER<br />

EMERGENCY<br />

SWITCH<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

THERMOSTAT<br />

L1 L2 T T<br />

HONEYWELL L8124<br />

OR EQUAL<br />

THERMAL<br />

FUSE<br />

(FIROMATIC)<br />

SERVICE<br />

SWITCH<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

B2<br />

C1<br />

C2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

ZR<br />

ZC<br />

B1<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

LOW<br />

WATER<br />

CUTOFF<br />

120 VAC INPUT<br />

NOTE: Tankless coil has priority.<br />

(HOT)<br />

L1<br />

L2<br />

(NEUTRAL)<br />

THERMOSTAT<br />

CIRCUIT<br />

BREAKER<br />

24 VAC<br />

POWER<br />

SR 503<br />

THERMOSTAT<br />

CUSTOMER<br />

EMERGENCY<br />

SWITCH<br />

FUSE 1 AMP<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

POWER<br />

<strong>ZONE</strong> 1<br />

L1 L2 T T<br />

HONEYWELL L8124<br />

OR EQUAL<br />

THERMAL<br />

FUSE<br />

(FIROMATIC)<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

B2<br />

C1<br />

C2<br />

ZR<br />

ZC<br />

B1<br />

SERVICE<br />

SWITCH<br />

N P ZC H<br />

X1<br />

X2<br />

ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

120 VOLT CIRCULATORS<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

LOW<br />

WATER<br />

CUTOFF<br />

120 VAC INPUT<br />

NOTE: The boiler operating control’s ZC terminal will see the load of the circulator(s).<br />

4


SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay<br />

MASTER<br />

AQUASTAT<br />

ON DHW<br />

HEATER<br />

A<br />

T<br />

T<br />

PRIORITY ON<br />

VIA JUMPER<br />

PLACEMENT<br />

24 VAC<br />

POWER<br />

SR 503<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

N P ZC H<br />

JUMPER<br />

X 2<br />

X 1 ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

N<br />

H<br />

120 VAC POWER<br />

DHW<br />

HEATER<br />

CIRCULATOR<br />

120 VOLT<br />

CIRCULATORS<br />

SLAVE<br />

T<br />

T<br />

T<br />

PRIORITY OFF<br />

VIA JUMPER<br />

PLACEMENT<br />

24 VAC<br />

POWER<br />

SR 503<br />

FUSE 1 AMP<br />

N P ZC H<br />

JUMPER<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

X ZR 1<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

X 2<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

POWER<br />

BOILER<br />

120 VOLT CIRCULATORS<br />

TO: "TT" ON AQUASTAT CONTROL<br />

5


SR502/503 Switching Relay Controlling Another SR504/506 Switching Relay<br />

MASTER<br />

AQUASTAT<br />

ON DHW<br />

HEATER<br />

A<br />

T<br />

T<br />

24 VAC<br />

POWER<br />

SR 503<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

FUSE 1 AMP<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

PRIORITY ON<br />

VIA JUMPER<br />

PLACEMENT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

N P ZC H<br />

JUMPERS<br />

X 2<br />

X 1 ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

120 VOLT<br />

CIRCULATORS<br />

24 VAC<br />

POWER<br />

SLAVE<br />

SR 506<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

THERMOSTATS<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

T<br />

POWER<br />

INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

REMOVE<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

TO: "TT" ON BOILER<br />

BOILER<br />

6


Two SR504/506 Switching Relays Connected Together<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

T<br />

T<br />

T<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

ON<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

DHW<br />

HEATER<br />

CIRCULATOR<br />

BOILER<br />

T<br />

T<br />

T<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

ON<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

OUTPUT<br />

NOT<br />

USED<br />

120 VAC INPUT<br />

H<br />

N<br />

7


Priority Zoning Circulator Controlling SR504/506 Switching Relay<br />

MASTER<br />

PRIORITY ZONING CIRCULATOR<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

ON<br />

THERMOSTAT BOILER PRIORITY POWER IN<br />

1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />

A<br />

120 VAC INPUT<br />

AQUASTAT ON<br />

DHW HEATER<br />

THERMOSTATS<br />

SLAVE<br />

T<br />

PRIORITY<br />

OFF<br />

24 VAC<br />

POWER<br />

SR 506<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

REMOVE<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

TO: "TT" ON BOILER<br />

BOILER<br />

8


FUSE 1 AMP<br />

BOILER<br />

Priority Zoning Circulator Controlling 2 SR504/506 Switching Relays<br />

SR 504<br />

T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

T<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

120V RELAY<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

120V RELAY<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

PRIORITY ZONING CIRCULATOR<br />

OFF<br />

PRIORITY<br />

ON<br />

PRIORITY<br />

ON<br />

THERMOSTAT BOILER PRIORITY POWER IN<br />

1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

120 VAC INPUT<br />

T T T T T<br />

PRIORITY<br />

OFF<br />

SLAVE<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

FUSE 1 AMP<br />

REMOVE<br />

REMOVE<br />

JUMPER<br />

JUMPER<br />

TO: "TT" ON BOILER<br />

PRIORITY<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

120 VAC INPUT<br />

H<br />

N<br />

24 VAC<br />

POWER<br />

9


FUSE 1 AMP<br />

BOILER<br />

SR502/503 Switching Relay Controlling 2 SR504/506 Switching Relays<br />

SR 504<br />

T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

T<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

120V RELAY<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

120V RELAY<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T<br />

24 VAC<br />

POWER<br />

SR 503 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

PRIORITY<br />

ON<br />

TWO <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

X 2<br />

N P ZC H X ZR<br />

1<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

JUMPER<br />

T T T T T<br />

PRIORITY<br />

OFF<br />

SLAVE<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

FUSE 1 AMP<br />

REMOVE<br />

REMOVE<br />

JUMPER<br />

JUMPER<br />

TO: "TT" ON BOILER<br />

120 VAC INPUT<br />

PRIORITY<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

H<br />

N<br />

24 VAC<br />

POWER<br />

10


SLAVE<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

BOILER<br />

SR 504<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

REMOVE<br />

JUMPER<br />

TO: "TT" ON BOILER<br />

SR501 Switching Relay Controlling 2 SR504/506 Switching Relays<br />

MASTER<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

SR501<br />

24<br />

R W VAC<br />

T T COM<br />

1 <strong>ZONE</strong> SWITCHING RELAY<br />

POWER<br />

T STAT<br />

N H 3 4 4 6 6<br />

N/O N/C N/C N/O 5<br />

JUMPER<br />

120 VAC INPUT<br />

DHW<br />

CIRCULATOR<br />

T T T T<br />

SLAVE<br />

T T T T<br />

PRIORITY OFF PRIORITY OFF<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

REMOVE<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

H<br />

N<br />

11


SR501-EXP Switching Relay Controlling Another SR504/506 Switching Relay<br />

AQUASTAT ON<br />

DHW HEATER<br />

TO: "TT" ON BOILER<br />

A<br />

TO: OPTIONAL <strong>ZONE</strong> VALVE<br />

OR iSeries MIXING VALVE<br />

MASTER<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET<br />

FUSE<br />

1 AMP<br />

NORMAL<br />

SLAVE<br />

MASTER<br />

END<br />

SWITCH<br />

X<br />

EXPANSION<br />

<strong>ZONE</strong><br />

THERMOSTAT<br />

VALVE<br />

X 1 3 4 T/R T/W COM 1<br />

2 2<br />

SR 501-EXP<br />

FUSE<br />

5 AMP<br />

POWER<br />

T STAT<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

120VAC CIRC<br />

OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

JUMPER<br />

DHW CIRCULATOR<br />

24 VAC<br />

POWER<br />

SLAVE<br />

SR 506<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

THERMOSTATS<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

T<br />

POWER<br />

INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

REMOVE<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

TO: "TT" ON BOILER<br />

BOILER<br />

12


SR501-EXP Switching Relay Controlling a ZVC404/406 Zone Valve Control<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

TO: OPTIONAL <strong>ZONE</strong> VALVE<br />

OR iSeries MIXING VALVE<br />

<strong>ZONE</strong><br />

VALVE<br />

X 1 2 1 2<br />

END<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

X 3 4 T/R T/W COM<br />

SR 501-EXP<br />

POWER<br />

T STAT<br />

FUSE<br />

5 AMP<br />

N H ZC ZR H H<br />

PRIORITY<br />

OUTPUT<br />

CIRC<br />

OUTPUT<br />

120VAC<br />

OUTPUT<br />

120VAC<br />

INPUT<br />

POWER<br />

INPUT<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

T T T<br />

DHW<br />

HEATER<br />

CIRCULATOR<br />

JUMPER<br />

24 VAC<br />

SLAVE<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

POWER IN<br />

120 VAC<br />

INPUT<br />

BLACK<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

MAIN N/C<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

TO BOILER AQUASTAT RELAY<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

MOTOR END<br />

SWITCH<br />

SYSTEM<br />

PUMP<br />

1<br />

2<br />

3<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

SYSTEM PUMP TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS<br />

EXCEPT WHEN THE DHW HEATER (SR501-EXP) CALLS.<br />

MASTER<br />

TO BOILER AQUASTAT RELAY<br />

MODE<br />

POWER<br />

<strong>CONTROLS</strong> RESET<br />

NORMAL<br />

SLAVE<br />

FUSE<br />

1 AMP<br />

MASTER<br />

N<br />

120 VAC<br />

INPUT<br />

H<br />

BOILER<br />

13


2 Expandable Switching Relays Connected Together<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T<br />

THERMOSTATS<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504-EXP<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

MASTER<br />

THERMOSTATS<br />

T<br />

A<br />

AQUASTAT<br />

ON DHW<br />

HEATER<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

PLUG-IN CARDS<br />

RESET<br />

NORMAL<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SR 506-EXP<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

BOILER<br />

DHW<br />

CIRCULATOR<br />

14


2 Indirect Water Heaters with Priority Connected to Standard Switching Relays<br />

AQUASTATS ON<br />

DHW HEATERS<br />

A<br />

A<br />

MASTER<br />

24 VAC<br />

POWER<br />

SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

PRIORITY<br />

OFF<br />

TWO <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

N P ZC H X ZR<br />

1<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

JUMPERS<br />

SR 504<br />

T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

T<br />

SLAVE SLAVE<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

PRIORITY<br />

ON<br />

SR 504<br />

T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

T<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

24 V AC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

FUSE 1 AMP<br />

FUSE 1 AMP<br />

JUMPER<br />

<strong>ZONE</strong><br />

NOT<br />

USED<br />

JUMPER<br />

<strong>ZONE</strong><br />

NOT<br />

USED<br />

BOILER<br />

TO: "TT" ON BOILER<br />

120 VAC INPUT<br />

PRIORITY<br />

ON<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

H<br />

N<br />

X 2<br />

<strong>ZONE</strong> 2<br />

15


2 Indirect Water Heaters with Priority Connected to EXP Switching Relays<br />

A<br />

A<br />

AQUASTATS ON<br />

DHW HEATERS<br />

24 VAC<br />

POWER<br />

SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

PRIORITY<br />

OFF<br />

TWO <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

N P ZC H X ZR<br />

1<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

T<br />

JUMPERS<br />

DHW<br />

CIRCULATORS<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

MASTER SLAVE<br />

T<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504-EXP<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

SR 504-EXP<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

FUSE 1 AMP<br />

FUSE 1 AMP<br />

JUMPER<br />

JUMPER<br />

BOILER<br />

TO: "TT" ON BOILER<br />

<strong>ZONE</strong><br />

NOT<br />

USED<br />

120 VAC INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

H<br />

N<br />

X 2<br />

<strong>ZONE</strong> 2<br />

16


PC700 Boiler Reset Control Connected to SR501-EXP Switching Relay<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

PC700<br />

THERMOSTAT<br />

BOIL OUT<br />

SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

TO: "TT" ON BOILER<br />

T<br />

TO: OPTIONAL <strong>ZONE</strong> VALVE<br />

OR iSeries MIXING VALVE<br />

BOILER SENSOR<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET<br />

FUSE<br />

1 AMP<br />

NORMAL<br />

SLAVE<br />

MASTER<br />

END<br />

<strong>ZONE</strong><br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

VALVE<br />

X 1 3 4 T/R T/W COM 1<br />

X<br />

2 2<br />

SR 501-EXP<br />

FUSE<br />

5 AMP<br />

POWER<br />

T STAT<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

120VAC CIRC<br />

OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

BOILER<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

SYSTEM<br />

CIRCULATOR<br />

17


SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Switching Relay<br />

OUTDOOR<br />

SENSOR<br />

TO: "TT" ON BOILER<br />

Note: If Zone Control comes on without a call for heat,<br />

reverse Reset Override input (1 & 2) wires on SR501-EXP.<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

FUSE<br />

1 AMP<br />

POWER<br />

<strong>CONTROLS</strong><br />

END<br />

RESET<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

SR 501-EXP<br />

K1 K2<br />

MODE<br />

RESET<br />

NORMAL<br />

POWER<br />

T STAT<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

THERMOSTATS<br />

SR 504<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

120V RELAY<br />

T<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

120VAC<br />

OUTPUT<br />

K1-B K2-A K2-A<br />

CIRC<br />

OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

JUMPER<br />

MASTER<br />

JUMPER<br />

BOILER<br />

PRIMARY<br />

SYSTEM<br />

CIRCULATOR<br />

(Optional)<br />

DHW<br />

HEATER<br />

CIRCULATOR<br />

120 VAC<br />

INPUT<br />

H<br />

N<br />

OUTDOOR<br />

SENSOR<br />

Connecting a DHW Heater to an Existing Heating Only Switching Relay<br />

Using an SR501-EXP and PC700 Boiler Reset Control<br />

TO: "TT" ON BOILER<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

MASTER<br />

FUSE<br />

1 AMP<br />

POWER<br />

<strong>CONTROLS</strong><br />

END<br />

RESET<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

SR 501-EXP<br />

K1 K2<br />

MODE<br />

RESET<br />

NORMAL<br />

POWER<br />

T STAT<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

SLAVE<br />

SR 504<br />

120V RELAY<br />

T<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

THERMOSTATS<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

120VAC<br />

OUTPUT<br />

K1-B K2-A K2-A<br />

CIRC<br />

OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

BOILER<br />

JUMPER<br />

DHW<br />

HEATER<br />

CIRCULATOR<br />

REMOVE<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

H<br />

N<br />

18


SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Zone Valve Control<br />

OUTDOOR<br />

SENSOR<br />

TO: "TT" ON BOILER<br />

Note: If Zone Control comes on without a call for heat,<br />

reverse Reset Override input (1 & 2) wires on SR501-EXP.<br />

THERMOSTATS<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

POWER<br />

<strong>CONTROLS</strong><br />

FUSE<br />

1 AMP<br />

END<br />

RESET MODE<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE RESET<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SR 501-EXP NORMAL<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

K1<br />

K2<br />

POWER<br />

T STAT<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24<br />

VAC<br />

POWER IN<br />

MAIN EXTRA<br />

END END<br />

SWITCH SWITCH<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

MODE<br />

NORMAL RESET<br />

FUSE<br />

(3 AMP MAX)<br />

T<br />

24 VAC<br />

T<br />

T T T T T T T T<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />

N/O COM N/C<br />

<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />

ZVC 404<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

OFF<br />

ON<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

POWER<br />

K1-B K2-A K2-A<br />

N H ZC ZR H H<br />

POWER 120VAC 120VAC CIRC<br />

INPUT INPUT OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

JUMPER<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE TACO<br />

(NO END SWITCH) 3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

BOILER<br />

PRIMARY<br />

SYSTEM<br />

CIRCULATOR<br />

(Optional)<br />

DHW HEATER<br />

CIRCULATOR<br />

<strong>ZONE</strong> VALVE SYSTEM<br />

CIRCULATOR<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

H<br />

N<br />

120 VAC<br />

INPUT<br />

Connecting a DHW Heater to an Existing Heating Only Zone Valve Control<br />

Using an SR501-EXP and PC700 Boiler Reset Control<br />

OUTDOOR<br />

SENSOR<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

TO: "TT" ON BOILER<br />

THERMOSTATS<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

MASTER<br />

POWER<br />

<strong>CONTROLS</strong><br />

FUSE<br />

1 AMP<br />

END<br />

RESET MODE<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE RESET<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SR 501-EXP NORMAL<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

K1<br />

K2<br />

POWER<br />

T STAT<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24<br />

VAC<br />

POWER IN<br />

MAIN EXTRA<br />

END END<br />

SWITCH SWITCH<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

MODE<br />

NORMAL RESET<br />

FUSE<br />

(3 AMP MAX)<br />

T<br />

24 VAC<br />

T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />

N/O COM N/C<br />

<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

OFF<br />

T T T T T T T T<br />

ON<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

ZVC 404<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

SLAVE<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

POWER<br />

K1-B K2-A K2-A<br />

N H ZC ZR H H<br />

POWER 120VAC 120VAC CIRC<br />

INPUT INPUT OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

JUMPER<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE TACO<br />

(NO END SWITCH) 3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

BOILER<br />

DHW HEATER<br />

CIRCULATOR<br />

<strong>ZONE</strong> VALVE SYSTEM<br />

CIRCULATOR<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

H<br />

N<br />

120 VAC<br />

INPUT<br />

19


SR501-EXP and PC700 Boiler Reset Control Connected to an Existing<br />

Tankless Coil Boiler – Zoning with Circulators<br />

OUTDOOR<br />

SENSOR<br />

T<br />

THERMOSTATS<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

FUSE<br />

1 AMP<br />

POWER<br />

<strong>CONTROLS</strong><br />

END<br />

RESET<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

SR 501-EXP<br />

K1 K2<br />

MODE<br />

RESET<br />

NORMAL<br />

POWER<br />

T STAT<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

SR 504<br />

120V RELAY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

120VAC<br />

OUTPUT<br />

K1-B K2-A K2-A<br />

CIRC<br />

OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

JUMPER<br />

BOILER<br />

TO: "ZR" ON BOILER CONTROL<br />

TO: "ZC" ON BOILER CONTROL<br />

PRIMARY<br />

SYSTEM<br />

CIRCULATOR<br />

(Optional)<br />

REMOVE<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

H<br />

N<br />

Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).<br />

OUTDOOR<br />

SENSOR<br />

SR501-EXP and PC700 Boiler Reset Control Connected to an Existing<br />

Tankless Coil Boiler – Zoning with Zone Valves<br />

THERMOSTATS<br />

PC700<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

MASTER<br />

FUSE<br />

1 AMP<br />

POWER<br />

<strong>CONTROLS</strong><br />

END<br />

RESET MODE<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE RESET<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

K1-A<br />

MASTER<br />

SR 501-EXP NORMAL<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

K1<br />

K2<br />

POWER<br />

T STAT<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24<br />

VAC<br />

POWER IN<br />

MAIN EXTRA<br />

END END<br />

SWITCH SWITCH<br />

EXISTING<br />

<strong>ZONE</strong><br />

CONTROL<br />

MODE<br />

NORMAL RESET<br />

FUSE<br />

(3 AMP MAX)<br />

T<br />

24 VAC<br />

T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />

N/O COM N/C<br />

<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

OFF<br />

T T T T T T T T<br />

ON<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

ZVC 404<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

SLAVE<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

POWER<br />

K1-B K2-A K2-A<br />

N H ZC ZR H H<br />

POWER 120VAC 120VAC CIRC<br />

INPUT INPUT OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

TO: "ZR" ON BOILER CONTROL<br />

TO: "ZC" ON BOILER CONTROL<br />

JUMPER<br />

PRIMARY<br />

SYSTEM<br />

CIRCULATOR<br />

(Optional)<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

<strong>ZONE</strong> VALVE SYSTEM<br />

CIRCULATOR<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

BOILER<br />

H<br />

N<br />

120 VAC<br />

INPUT<br />

Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).<br />

20


OUTDOOR<br />

SENSOR<br />

BOIL<br />

SEN<br />

PC700<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

BOILER SENSOR<br />

BOILER<br />

PC700 Boiler Reset Control Connected to EXP Switching Relay<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

T<br />

THERMOSTATS<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1234 PLUG-IN CARDS<br />

RESET NORMAL<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

TO: "TT" ON BOILER<br />

H<br />

N<br />

21


STAGE<br />

1<br />

PC702 2–Stage Boiler Reset Control Connected to EXP Switching Relay<br />

OUTDOOR<br />

SENSOR<br />

DHW<br />

DEMAND<br />

SWITCH SETTINGS<br />

PC702<br />

STAGE<br />

2<br />

BOIL<br />

SEN<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

T<br />

THERMOSTATS<br />

BOILER<br />

#1<br />

BOILER SENSOR<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1234 PLUG-IN CARDS<br />

RESET NORMAL<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

BOILER<br />

#2<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

SYSTEM<br />

CIRCULATOR<br />

(OPTIONAL)<br />

22


OUTDOOR<br />

SENSOR<br />

PC705-2<br />

BOIL<br />

SEN<br />

SUP<br />

SEN<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

BOILER<br />

PC705 Variable Speed Pump Injection Control Connected to EXP Switching Relay<br />

GREEN/GROUND<br />

(SEE NOTE B)<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

T<br />

THERMOSTATS<br />

RED<br />

BLUE<br />

BLACK<br />

SYSTEM<br />

CIRCULATOR<br />

AND/OR BOILER<br />

INJECTION<br />

CIRCULATOR<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1234 PLUG-IN CARDS<br />

RESET NORMAL<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

SYSTEM<br />

CIRCULATOR<br />

AND/OR BOILER<br />

(SEE NOTE A)<br />

120 VAC INPUT<br />

N<br />

H<br />

NOTE A: WHEN SYSTEM CIRCULATOR IS CONNECTED TO ZR TERMINAL ON SWITCHING RELAY, THE MODE SWITCH MUST BE SET TO NORMAL.<br />

THE PC705-2 WILL NOT RESET THE BOILER WHEN IN THE NORMAL MODE.<br />

NOTE B: WHEN SYSTEM CIRCULATOR IS CONNECTED TO RED <strong>WIRE</strong> ON PC705-2, THE CIRCULATOR WILL OPERATE ONLY WHEN THERMOSTAT CALLS FOR HEAT<br />

AND THE OUTDOOR TEMPERATURE IS BELOW THE WARM WEATHER SHUT DOWN (WWSD) TEMPERATURE. THE WWSD CAN BE ADJUSTED OR TURNED<br />

OFF SO THAT THE CIRCULATOR IS NOT AFFECTED BY OUTDOOR TEMPERATURE.<br />

23


PC700 Boiler Reset Control Connected to 2 EXP Switching Relays<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

BOIL OUT<br />

SEN SEN<br />

PC700<br />

<strong>ZONE</strong><br />

CONTROL<br />

BOILER SENSOR<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

MASTER<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

BOILER<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: No Priority<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

SLAVE<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

SYSTEM<br />

CIRCULATOR<br />

(OPTIONAL)<br />

24


PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays<br />

STAGE<br />

1<br />

PC702<br />

STAGE<br />

2<br />

BOIL OUT <strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER<br />

#1<br />

BOILER SENSOR<br />

DHW<br />

DEMAND<br />

OUTDOOR<br />

SENSOR<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

MASTER<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

BOILER<br />

#2<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: No Priority<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

SLAVE<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

SYSTEM<br />

CIRCULATOR<br />

(OPTIONAL)<br />

JUMPER<br />

H<br />

N<br />

120 VAC INPUT<br />

25


PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays<br />

SWITCH SETTINGS<br />

OUTDOOR<br />

SENSOR<br />

GREEN/GROUND<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

T<br />

THERMOSTATS<br />

MASTER<br />

BOIL<br />

SEN<br />

PC705-2<br />

SUP OUT<br />

SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

RED<br />

BLUE<br />

BLACK<br />

(SEE NOTE B<br />

ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

INJECTION<br />

CIRCULATOR<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

BOILER<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: No Priority<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

SLAVE<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

H<br />

N<br />

SYSTEM<br />

CIRCULATOR<br />

(OPTIONAL)<br />

(SEE NOTE A ON PAGE 23)<br />

120 VAC INPUT<br />

26


PC700 and PC705 Controls Connected to 2 EXP Switching Relays<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

BOIL OUT<br />

SEN SEN<br />

PC700<br />

<strong>ZONE</strong><br />

CONTROL<br />

BOILER SENSOR<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

MASTER<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC INPUT<br />

BOILER<br />

OUTDOOR<br />

SENSOR<br />

BOIL<br />

SEN<br />

PC705-2<br />

SUP OUT<br />

SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

GREEN/GROUND<br />

RED<br />

BLUE<br />

BLACK<br />

(SEE NOTE B<br />

ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

INJECTION<br />

CIRCULATOR<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: No Priority<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

SLAVE<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

SYSTEM CIRCULATOR<br />

(OPTIONAL LOCATION)<br />

(SEE NOTE A ON PAGE 23)<br />

H<br />

N<br />

120 VAC INPUT<br />

27


PC702 and PC705 Controls Connected to 2 EXP Switching Relays<br />

STAGE<br />

1<br />

PC702<br />

STAGE<br />

2<br />

BOIL OUT <strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER<br />

#1<br />

BOILER SENSOR<br />

DHW<br />

DEMAND<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

FUSE 1 AMP<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

MASTER<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

JUMPER<br />

120 VAC INPUT<br />

BOILER<br />

#2<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

OUTDOOR<br />

SENSOR<br />

BOIL<br />

SEN<br />

PC705-2<br />

SUP OUT<br />

SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

GREEN/GROUND<br />

RED<br />

BLUE<br />

BLACK<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: No Priority<br />

(SEE NOTE B<br />

ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

INJECTION<br />

CIRCULATOR<br />

24 VAC<br />

POWER<br />

SLAVE<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

120V RELAY<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

T<br />

THERMOSTATS<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

SR 504-EXP<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

SLAVE<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

FUSE 1 AMP<br />

JUMPER<br />

28<br />

SYSTEM CIRCULATOR<br />

(OPTIONAL LOCATION)<br />

(SEE NOTE A ON PAGE 23)<br />

120 VAC INPUT<br />

H<br />

N


THERMOSTAT THERMOSTAT THERMOSTAT<br />

24 VAC<br />

T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

ZVC 405<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

ZVC403/405 with System Pump<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

T T T<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

POWER<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

POWER IN<br />

FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

FUSE (5 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

N/O COM N/C<br />

BOILER<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

TO BOILER AQUASTAT RELAY<br />

MOTOR END<br />

SWITCH<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

SYSTEM<br />

PUMP<br />

N<br />

H<br />

SYSTEM PUMP AND BOILER TURN ON<br />

WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

29


ZVC404/406 with System Pump<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T T<br />

24 VAC<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

N<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

H<br />

MAIN N/C<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

TO BOILER AQUASTAT RELAY<br />

MOTOR END<br />

SWITCH<br />

DRY<br />

CONTACTS<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

BOILER<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SYSTEM<br />

PUMP<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SYSTEM PUMP AND BOILER TURN ON<br />

WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

30


ZVC404/406 with Domestic Hot Water (DHW) Pump<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T T<br />

24 VAC<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

MAIN N/C<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

N<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

TO BOILER AQUASTAT RELAY<br />

MOTOR END<br />

SWITCH<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

H<br />

BOILER<br />

DHW<br />

PUMP<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

31


ZVC404/406 with System and DHW Pumps<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T T<br />

24 VAC<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

MAIN N/C<br />

N<br />

JUMPER<br />

3 & 4<br />

H<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

TO BOILER AQUASTAT RELAY<br />

MOTOR END<br />

SWITCH<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

BOILER<br />

SYSTEM<br />

PUMP<br />

DHW<br />

PUMP<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

32


ZVC404/406 with System, DHW and Secondary Pumps<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T T<br />

24 VAC<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

N<br />

MAIN N/C<br />

H<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

TO BOILER AQUASTAT RELAY<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

MOTOR END<br />

SWITCH<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

BOILER<br />

SYSTEM<br />

PUMP<br />

DHW<br />

PUMP<br />

SECONDARY<br />

PUMP<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

SECONDARY PUMP COMES ON WHEN ANY <strong>ZONE</strong> CALLS EXCEPT PRIORITY <strong>ZONE</strong>.<br />

33


2 ZVC404/406 Connected Together with Priority<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

T T T<br />

24 VAC<br />

N<br />

H<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24<br />

VAC<br />

POWER IN<br />

MAIN<br />

END<br />

SWITCH<br />

EXTRA<br />

END<br />

SWITCH<br />

MODE<br />

NORMAL RESET<br />

N/O COM N/C<br />

<strong>ZONE</strong> 4 RELAY<br />

FUSE (3 AMP MAX)<br />

<strong>ZONE</strong> 4 PRIORITY<br />

OFF<br />

ON<br />

T T T T T T T T<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />

1 2 3 4 1 2 3 4<br />

ZVC 404<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

PRIORITY<br />

ON<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

POWER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

T T T<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

24 VAC<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24<br />

VAC<br />

POWER IN<br />

MAIN<br />

END<br />

SWITCH<br />

EXTRA<br />

END<br />

SWITCH<br />

MODE<br />

NORMAL RESET<br />

N/O COM N/C<br />

<strong>ZONE</strong> 4 RELAY<br />

FUSE (3 AMP MAX)<br />

<strong>ZONE</strong> 4 PRIORITY<br />

OFF<br />

ON<br />

T T T T T T T T<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />

1 2 3 4 1 2 3 4<br />

ZVC 404<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

PRIORITY<br />

ON<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

POWER<br />

BOILER<br />

TO BOILER AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

34


2 EXP Zone Valve Controls Connected Together with System Pump<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER AQUASTAT RELAY<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

SYSTEM<br />

PUMP<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

N<br />

H<br />

120 VAC<br />

INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

35


2 EXP Zone Valve Controls Connected Together with DHW Pump<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

DHW<br />

PUMP<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

N<br />

H<br />

120 VAC<br />

INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

36


2 EXP Zone Valve Controls Connected Together with System and DHW Pumps<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DHW<br />

PUMP<br />

SYSTEM<br />

PUMP<br />

JUMPER<br />

3 & 4<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

1<br />

2<br />

3<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

MOTOR<br />

END<br />

SWITCH<br />

PRIORITY<br />

<strong>ZONE</strong><br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

JUMPER<br />

3 & 4<br />

SEE NOTE<br />

SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

N<br />

H<br />

120 VAC<br />

INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

37


2 EXP Zone Valve Controls Connected Together with System, DHW and Secondary Pumps<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

A<br />

AQUASTAT ON<br />

DHW HEATER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DHW<br />

PUMP<br />

SYSTEM<br />

PUMP<br />

SECONDARY<br />

PUMP<br />

JUMPER<br />

3 & 4<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

1<br />

2<br />

3<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

MOTOR<br />

END<br />

SWITCH<br />

PRIORITY<br />

<strong>ZONE</strong><br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

JUMPER<br />

3 & 4<br />

SEE NOTE<br />

SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

SECONDARY PUMP TURNS ON WHEN ANY <strong>ZONE</strong> CALLS, EXCEPT PRIORITY <strong>ZONE</strong>.<br />

N<br />

H<br />

120 VAC<br />

INPUT<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

38


PC700 Boiler Reset Control Connected To EXP Zone Valve Control<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

24 VAC<br />

POWER<br />

<strong>CONTROLS</strong><br />

RESET<br />

MODE<br />

SLAVE<br />

NORMAL<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

JUMPER<br />

3 & 4<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

1<br />

2<br />

3<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

MOTOR END<br />

SWITCH<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

INDIRECT<br />

WATER HEATER<br />

AQUASTAT<br />

OR THERMOSTAT<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SEE NOTE<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

BOILER<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

PC700<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

BOIL<br />

SEN<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

BOILER SENSOR<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

24 VAC<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

SYSTEM<br />

CIRCULATOR<br />

H<br />

N<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

39


PC702 2–Stage Boiler Reset Control Connected To EXP Zone Valve Control<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

24 VAC<br />

POWER<br />

<strong>CONTROLS</strong><br />

RESET<br />

MODE<br />

SLAVE<br />

NORMAL<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

INDIRECT<br />

WATER HEATER<br />

AQUASTAT<br />

OR THERMOSTAT<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SEE NOTE<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

STAGE<br />

1<br />

OUTDOOR<br />

SENSOR<br />

DHW<br />

DEMAND<br />

PC702<br />

STAGE<br />

2<br />

BOIL<br />

SEN<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

BOILER SENSOR<br />

BOILER<br />

#1<br />

BOILER<br />

#2<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

24 VAC<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

SYSTEM<br />

CIRCULATOR<br />

H<br />

N<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

DHW<br />

CIRCULATOR<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

40


PC705 Variable Speed Pump Injection Control Connected To EXP Zone Valve Control<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

24 VAC<br />

POWER<br />

<strong>CONTROLS</strong><br />

RESET<br />

MODE<br />

SLAVE<br />

NORMAL<br />

MASTER<br />

1 2 3 4<br />

EXPANSION<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

INDIRECT<br />

WATER HEATER<br />

AQUASTAT<br />

OR THERMOSTAT<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SEE NOTE<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

BOILER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

24 VAC<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

H<br />

N<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

OUTDOOR<br />

SENSOR<br />

BOIL<br />

SEN<br />

GREEN/GROUND<br />

PC705-2<br />

SUP<br />

SEN<br />

OUT<br />

SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

RED<br />

BLUE<br />

BLACK<br />

SYSTEM<br />

CIRCULATOR<br />

(SEE NOTE B ON PAGE 23)<br />

INJECTION<br />

CIRCULATOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

T T T<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

SYSTEM CIRCULATOR<br />

(OPTIONAL LOCATION)<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

41


PC700 Boiler Reset Control Connected To 2 EXP Zone Valve Controls<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

PC700<br />

INDIRECT WATER HEATER<br />

AQUASTAT OR THERMOSTAT<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

SYSTEM<br />

CIRCULATOR<br />

DHW<br />

CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

H<br />

N<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

T<br />

24 VAC<br />

T<br />

T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

42


PC702 2–Stage Boiler Reset Control Connected To 2 EXP Zone Valve Controls<br />

OUTDOOR<br />

SENSOR<br />

DHW<br />

DEMAND<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

PC702<br />

STAGE STAGE BOIL OUT <strong>ZONE</strong><br />

1 2 SEN SEN CONTROL<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

INDIRECT WATER HEATER<br />

AQUASTAT OR THERMOSTAT<br />

BOILER SENSOR<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

#1<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

SYSTEM<br />

CIRCULATOR<br />

DHW<br />

CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

H<br />

N<br />

BOILER<br />

#2<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

SLAVE<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

T<br />

24 VAC<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

43


PC705 Variable Speed Pump Injection Control Connected To 2 EXP Zone Valve Controls<br />

OUTDOOR<br />

SENSOR<br />

GREEN/GROUND<br />

RED<br />

(SEE NOTE B ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

PC705-2<br />

BOIL SUP OUT <strong>ZONE</strong><br />

SEN SEN SEN CONTROL<br />

BLUE<br />

BLACK<br />

INJECTION<br />

CIRCULATOR<br />

INDIRECT WATER HEATER<br />

AQUASTAT OR THERMOSTAT<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

MASTER<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

T<br />

24 VAC<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

SYSTEM CIRCULATOR<br />

(OPTIONAL LOCATION)<br />

JUMPER<br />

3 & 4<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

1<br />

2<br />

3<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

MOTOR<br />

END<br />

SWITCH<br />

PRIORITY<br />

<strong>ZONE</strong><br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

JUMPER<br />

3 & 4<br />

SEE NOTE<br />

H<br />

N<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

SLAVE<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

T<br />

24 VAC<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

44


PC700 and PC705 Connected To 2 EXP Zone Valve Controls<br />

OUTDOOR<br />

SENSOR<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Reset<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

PC700<br />

INDIRECT WATER HEATER<br />

AQUASTAT OR THERMOSTAT<br />

BOIL OUT<br />

<strong>ZONE</strong><br />

SEN SEN CONTROL<br />

BOILER SENSOR<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

TO BOILER<br />

AQUASTAT RELAY<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

SYSTEM<br />

CIRCULATOR<br />

DHW<br />

CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

H<br />

OUTDOOR<br />

SENSOR<br />

GREEN/GROUND<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

N<br />

RED<br />

(SEE NOTE B ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

PC705-2<br />

BLUE<br />

INJECTION<br />

CIRCULATOR<br />

BOIL SUP OUT<br />

SEN SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

BLACK<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

SLAVE<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

T<br />

24 VAC<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

T<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

45


PC702 and PC705 Connected To 2 EXP Zone Valve Controls<br />

OUTDOOR<br />

SENSOR<br />

DHW<br />

DEMAND<br />

SWITCH SETTINGS<br />

Master/Slave: Master<br />

Reset/Normal: Normal<br />

Priority Zone: On or Off<br />

Note: When a circulator is used on the<br />

priority zone instead of a zone valve,<br />

jumper 3 and 4 of the priority zone.<br />

PC702<br />

STAGE STAGE BOIL OUT <strong>ZONE</strong><br />

1 2 SEN SEN CONTROL<br />

WIRING NEEDED ONLY IF<br />

PRIORITY <strong>ZONE</strong> IS DHW<br />

INDIRECT WATER HEATER<br />

AQUASTAT OR THERMOSTAT<br />

BOILER SENSOR<br />

MASTER<br />

T<br />

24 VAC<br />

T<br />

T<br />

BOILER<br />

#1<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

BOILER<br />

#2<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

SYSTEM<br />

CIRCULATOR<br />

DHW<br />

CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

H<br />

OUTDOOR<br />

SENSOR<br />

GREEN/GROUND<br />

SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />

N<br />

RED<br />

(SEE NOTE B ON PAGE 23)<br />

SYSTEM<br />

CIRCULATOR<br />

PC705-2<br />

BLUE<br />

BLACK<br />

INJECTION<br />

CIRCULATOR<br />

BOIL SUP OUT<br />

SEN SEN SEN<br />

<strong>ZONE</strong><br />

CONTROL<br />

SUPPLY SENSOR<br />

BOILER SENSOR<br />

SLAVE<br />

T<br />

24 VAC<br />

T<br />

T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

RESET NORMAL<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SWITCH SETTINGS<br />

Master/Slave: Slave<br />

Reset/Normal: Normal<br />

Priority Zone: Off<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

46


HAFC101 with 1 Speed Air Handler<br />

THERMOSTAT<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

T<br />

To: Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

C R W Y<br />

THERMOSTAT<br />

G<br />

T T<br />

AQUASTAT<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

BOILER<br />

AIR HANDLER<br />

X X C R Y<br />

G G<br />

LOW HIGH<br />

Jumper<br />

Dry Contacts To:<br />

“T T” on Boiler<br />

or Switching Relay<br />

Line 24 VAC<br />

Fan<br />

Relay<br />

M<br />

Outdoor<br />

Condenser<br />

Unit<br />

HAFC 101 WITH 1 SPEED AIR HANDLER<br />

(Both HFC 101 and HAFC 201 are<br />

capable of 1 and 2 speed applications.)<br />

47


HAFC101 with 2 Speed Air Handler<br />

THERMOSTAT<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

T<br />

To: Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

C R W Y<br />

THERMOSTAT<br />

G<br />

T T<br />

AQUASTAT<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

BOILER<br />

AIR HANDLER<br />

X X C R Y<br />

G G<br />

LOW HIGH<br />

Dry Contacts To:<br />

“T T” on Boiler<br />

or Switching Relay<br />

Line 24 VAC<br />

Low<br />

High<br />

M<br />

Fan Relays<br />

Outdoor<br />

Condenser<br />

Unit<br />

HAFC 101 WITH 2 SPEED AIR HANDLER<br />

(Both HFC 101 and HAFC 201 are<br />

capable of 1 and 2 speed applications.)<br />

48


HAFC201 with 1 Speed Air Handler<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

THERMOSTAT<br />

T<br />

To: Optional<br />

Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

To: Optional Aquastat<br />

or Thermostat to sense<br />

low ambient<br />

temperature<br />

C R W Y<br />

THERMOSTAT<br />

G<br />

T<br />

T<br />

T<br />

T<br />

WATER COIL FREEZE PR<br />

AQUASTATS<br />

NOTE: For 4 minute<br />

on delay of Heating Fan,<br />

switch 1 and 3 MIN ON<br />

DELAY to ON position.<br />

OFF ON<br />

1 MIN ON DELAY - FAN<br />

3 MIN ON DELAY - FAN<br />

2 MIN @ 24 HR - PUMP<br />

30 SEC @ 2 WK - PUMP<br />

HAFC201<br />

HYDRO AIR FAN CONTROL<br />

DRY CONTACTS<br />

5 AMP 1/6 HP RATED<br />

PUMP<br />

X<br />

X<br />

BOILER<br />

AIR HANDLER<br />

XXCRY<br />

G G<br />

LOW HIGH<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

Jumper<br />

Hot<br />

Neutral<br />

(or to “T T” on<br />

switching relay)<br />

Circulator<br />

Dry Contacts To:<br />

“T T” on Boiler<br />

or Switching<br />

Relay<br />

Line 24 VAC<br />

Fan<br />

Relay<br />

M<br />

Outdoor<br />

Condenser<br />

Unit<br />

HAFC 201 WITH 1 SPEED AIR HANDLER<br />

(Both HFC 101 and HAFC 201 are<br />

capable of 1 and 2 speed applications.)<br />

49


HAFC201 with 2 Speed Air Handler<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

THERMOSTAT<br />

T<br />

To: Optional<br />

Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

To: Optional Aquastat<br />

or Thermostat to sense<br />

low ambient<br />

temperature<br />

C R W Y<br />

THERMOSTAT<br />

G<br />

T<br />

T<br />

T<br />

T<br />

WATER COIL FREEZE PR<br />

AQUASTATS<br />

NOTE: For 4 minute<br />

on delay of Heating Fan,<br />

switch 1 and 3 MIN ON<br />

DELAY to ON position.<br />

OFF ON<br />

1 MIN ON DELAY - FAN<br />

3 MIN ON DELAY - FAN<br />

2 MIN @ 24 HR - PUMP<br />

30 SEC @ 2 WK - PUMP<br />

HAFC201<br />

HYDRO AIR FAN CONTROL<br />

DRY CONTACTS<br />

5 AMP 1/6 HP RATED<br />

PUMP<br />

X<br />

X<br />

BOILER<br />

AIR HANDLER<br />

XXCRY<br />

G G<br />

LOW HIGH<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

Hot<br />

Neutral<br />

(or to “T T” on<br />

switching relay)<br />

Circulator<br />

“T T” on Boiler<br />

or Switching<br />

Relay<br />

Line 24 VAC<br />

Low<br />

High<br />

M<br />

Fan Relays<br />

Outdoor<br />

Condenser<br />

Unit<br />

HAFC 201 WITH 2 SPEED AIR HANDLER<br />

(Both HFC 101 and HAFC 201 are<br />

capable of 1 and 2 speed applications.)<br />

50


Multiple HAFC’s and Switching Relay<br />

THERMOSTAT<br />

THERMOSTAT<br />

THERMOSTAT<br />

C R W Y G T T<br />

THERMOSTAT AQUASTAT<br />

C R W Y G T T<br />

THERMOSTAT AQUASTAT<br />

C R W Y G T T<br />

THERMOSTAT AQUASTAT<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

POWER PM<br />

CALL FOR HEAT<br />

FAN, COOLING<br />

FAN, HEATING<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

BOILER AIR HANDLER<br />

X X C R Y G G<br />

LOW HIGH<br />

BOILER AIR HANDLER<br />

X X C R Y G G<br />

LOW HIGH<br />

BOILER AIR HANDLER<br />

X X C R Y G G<br />

M<br />

OUTDOOR<br />

CONDENSER<br />

UNIT<br />

Line 24 VAC<br />

Low<br />

High<br />

Fan Relays<br />

M<br />

Line 24 VAC<br />

Low<br />

High<br />

Fan Relays<br />

M<br />

Line 24 VAC<br />

Low<br />

High<br />

Fan Relays<br />

OPTIONAL POWER <strong>WIRE</strong><br />

TO THERMOSTAT<br />

THAT REQUIRES 24VAC<br />

T T T<br />

TO: AQUASTAT ON<br />

RETURN LINE OF<br />

HYDRO COIL<br />

OPTIONAL POWER <strong>WIRE</strong><br />

TO THERMOSTAT<br />

THAT REQUIRES 24VAC<br />

TO: AQUASTAT ON<br />

RETURN LINE OF<br />

HYDRO COIL<br />

OPTIONAL POWER <strong>WIRE</strong><br />

TO THERMOSTAT<br />

THAT REQUIRES 24VAC<br />

TO: AQUASTAT ON<br />

RETURN LINE OF<br />

HYDRO COIL<br />

POWER PM<br />

CALL FOR HEAT<br />

FAN, COOLING<br />

FAN, HEATING<br />

POWER PM<br />

CALL FOR HEAT<br />

FAN, COOLING<br />

FAN, HEATING<br />

LOW HIGH<br />

OUTDOOR<br />

CONDENSER<br />

UNIT<br />

OUTDOOR<br />

CONDENSER<br />

UNIT<br />

2 SPEED AIR HANDLER<br />

2 SPEED AIR HANDLER<br />

2 SPEED AIR HANDLER<br />

SR 504<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

DHW<br />

HEATER<br />

AQUASTAT<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

TO: "TT" ON BOILER<br />

BOILER<br />

H<br />

N<br />

51


3 Wire Thermostat Connected to TACO Switching Relay<br />

3 <strong>WIRE</strong><br />

THERMOSTAT<br />

SR 504<br />

COM T<br />

T T T<br />

W R<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 4<br />

PRIORITY<br />

ON<br />

OFF<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

FOUR <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

X X<br />

END ZC ZR<br />

SWITCH<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

FUSE 1 AMP<br />

JUMPER<br />

120 VAC INPUT<br />

H<br />

N<br />

TO: "TT" ON BOILER<br />

BOILER<br />

3 Wire Thermostat Connected to TACO Zone Valve Control<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

T T T<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

C<br />

W R<br />

WH<br />

RED<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

END<br />

SWITCH<br />

POWER IN<br />

COMMON<br />

T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

ZVC 405<br />

FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

POWER<br />

T<br />

T<br />

TO T&T ON BOILER<br />

OR PUMP RELAY<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

BLACK<br />

BLACK<br />

RED<br />

RED<br />

MOTOR<br />

END<br />

SWITCH<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(TACO TYPE)<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(HONEYWELL TYPE)<br />

52


White-Rogers 1361 Hydronic Zone Valve with TACO Zone Valve Control<br />

NOTE: WHEN USING ZVC 404 OR ZVC 406,<br />

CONNECT <strong>WIRE</strong> #2 OF <strong>ZONE</strong> VALVE<br />

TO PRIORITY <strong>ZONE</strong> RIGHT TT SCREW<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

T T T<br />

24 VAC<br />

T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

ZVC 405<br />

FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

3<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

WHITE-ROGERS 1361<br />

HYDRONIC <strong>ZONE</strong> VALVE<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(TACO TYPE)<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(HONEYWELL TYPE)<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

POWER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

RIGHT TT<br />

SCREW<br />

(SEE NOTE)<br />

POWER IN<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

END<br />

SWITCH<br />

BLACK<br />

BLACK<br />

RED<br />

RED<br />

T<br />

T<br />

TO T&T ON BOILER<br />

OR PUMP RELAY<br />

2<br />

1<br />

4<br />

TERMINAL ASSIGNMENT<br />

<strong>ZONE</strong> VALVE CONTROL<br />

1 1<br />

2<br />

TT (Rt)<br />

3<br />

3<br />

4 2<br />

53


Honeywell VC 40 & 80 (spdt) Hydronic Zone Valve with TACO Zone Valve Control<br />

24 VAC<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

NOTE: WHEN USING ZVC 404 OR ZVC 406,<br />

CONNECT <strong>WIRE</strong> #3 OF <strong>ZONE</strong> VALVE<br />

TO PRIORITY <strong>ZONE</strong> RIGHT TT SCREW<br />

T T T<br />

RIGHT TT<br />

SCREW<br />

(SEE NOTE)<br />

TERMINAL ASSIGNMENT<br />

<strong>ZONE</strong> VALVE CONTROL<br />

ORANGE 1 3<br />

BLUE 2 1<br />

BROWN 3 TT (Rt)<br />

GRAY 4 4<br />

BLACK 6 2<br />

END<br />

SWITCH<br />

T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

ZVC 405<br />

FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

24 VAC<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

POWER<br />

BLACK<br />

BLACK<br />

RED<br />

RED<br />

T<br />

T<br />

TO T&T ON BOILER<br />

OR PUMP RELAY<br />

3<br />

2<br />

6<br />

4<br />

1<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

HONEYWELL VC (SPST)<br />

HYDRONIC <strong>ZONE</strong> VALVE<br />

SERIES 40 & 80<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(TACO TYPE)<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(HONEYWELL TYPE)<br />

54


570 Zone Valve to Switching Relay<br />

T<br />

THERMOSTAT<br />

24 VAC<br />

TRANSFORMER<br />

1<br />

2<br />

3<br />

24 VAC<br />

POWER<br />

SR 503<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

N P ZC H<br />

JUMPERS<br />

X 2<br />

X 1 ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

120 VOLT<br />

CIRCULATORS<br />

TO: 120 VAC POWER (NEUTRAL)<br />

TO: 120 VAC POWER (HOT)<br />

TO: "TT" ON AQUASTAT CONTROL<br />

TO: "TT" ON AQUASTAT CONTROL<br />

55


Zone Valve Control with 1 Low Temperature Zone Using Priority Zoning Circulator<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

AQUASTAT ON<br />

DHW HEATER<br />

A<br />

T T T<br />

24 VAC<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

N<br />

120 VAC<br />

INPUT<br />

BLACK<br />

H<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

MODE<br />

NORMAL RESET<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

POWER IN<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

ZVC 406<br />

FUSE (7 AMP MAX)<br />

24 VAC<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

MAIN N/C<br />

N/O COM<br />

<strong>ZONE</strong> 6 RELAY<br />

EXTRA<br />

END<br />

SWITCH<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

SEE NOTE<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

TO BOILER AQUASTAT RELAY<br />

END<br />

SWITCH<br />

MOTOR<br />

MOTOR END<br />

SWITCH<br />

DRY<br />

CONTACTS<br />

Note: When a circulator is<br />

used on the priority zone<br />

instead of a zone valve,<br />

jumper 3 and 4 of the<br />

priority zone.<br />

BOILER<br />

1<br />

2<br />

3<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

TACO<br />

3 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong><br />

<strong>ZONE</strong> VALVE<br />

(POWER OPEN,<br />

SELF CLOSING)<br />

SYSTEM<br />

PUMP<br />

PRIORITY<br />

ON<br />

PRIORITY ZONING CIRCULATOR<br />

PRIORITY<br />

ON<br />

OFF<br />

THERMOSTAT BOILER PRIORITY POWER IN<br />

1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />

SYSTEM PUMP AND BOILER TURN ON<br />

WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />

120 VAC INPUT<br />

56


Radiant Mixing Block (RMB)<br />

Back of<br />

Control<br />

Front of<br />

Control<br />

R<br />

Power: 120 V + 10%<br />

C US 50/60 Hz, 750 VA<br />

158033 Var. Speed: 120 V<br />

(ac) 1 A<br />

Pmp Relay: 120 V<br />

(ac) 5 A, 1/6 hp<br />

Use copper<br />

conductors only<br />

Com SupSys<br />

ComBoil Out ComHeat<br />

Ret<br />

Dem<br />

Boiler<br />

MENU ITEM<br />

RADIANT MIXING BLOCK<br />

PATENT PENDING<br />

U L RMB-1<br />

Boiler<br />

Meets Class B:<br />

Canadian ICES<br />

FCC Part 15<br />

Sys<br />

Y R B<br />

Var<br />

Boiler Operation<br />

Off-Enable On-Control<br />

Fuse<br />

Pump<br />

Man<br />

H<br />

N<br />

Line Cord<br />

Supply<br />

Sensor<br />

Boiler<br />

Sensor<br />

Outdoor<br />

Sensor<br />

To<br />

Zone<br />

Control<br />

End<br />

Switch<br />

or<br />

Thermostat<br />

Injection<br />

Circulator<br />

Radiant<br />

Circulator<br />

Radiant Mixing Block, Single Zone<br />

Boiler<br />

RMB<br />

Back of Control<br />

Boiler Operation<br />

Off-Enable On-Control<br />

T<br />

Thermostat<br />

(Dry Contact)<br />

Pump<br />

ComSupSysComBoil Out ComHeat<br />

Ret<br />

Dem<br />

H<br />

N<br />

H<br />

N<br />

Power<br />

Input<br />

Outdoor<br />

Sensor<br />

N<br />

Boiler<br />

Sensor<br />

Supply<br />

Sensor<br />

High Mass Boiler<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />

57


Radiant Mixing Block Connected to Zone Valve Control with System Pump Wired off the RMB<br />

Outdoor<br />

Sensor<br />

Power<br />

Input<br />

H<br />

N<br />

Factory<br />

Installed<br />

Transformer<br />

T<br />

T<br />

Thermostats<br />

Boiler<br />

RMB<br />

Back of Control<br />

Boiler Operation<br />

Off-Enable On-Control<br />

POWER IN<br />

FUSE<br />

(5 AMP MAX)<br />

T T<br />

<strong>ZONE</strong> 1<br />

T T<br />

<strong>ZONE</strong> 2<br />

ZVC 403<br />

T T<br />

<strong>ZONE</strong> 3<br />

THREE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

Pump<br />

END<br />

SWITCH<br />

N/O COM N/C<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

Com Sup Sys Com Boil Out Com Heat<br />

Ret<br />

Dem<br />

H<br />

N<br />

N<br />

Motor<br />

M<br />

End Switch<br />

Motor<br />

M<br />

End Switch<br />

Boiler<br />

Sensor<br />

Supply<br />

Sensor<br />

Radiant Mixing Block Connected to 2 EXP Switching Relays with DHW Pump<br />

SLAVE<br />

MASTER<br />

POWER CONTROL<br />

INTERFACE<br />

1 2 3 4<br />

EXPANSION<br />

RESET<br />

Thermostats<br />

T<br />

PLUG-IN CARDS<br />

NORMAL<br />

<strong>ZONE</strong>1<br />

T<br />

<strong>ZONE</strong>2<br />

A<br />

<strong>ZONE</strong>3<br />

DHW<br />

Aquastat<br />

<strong>ZONE</strong> 3<br />

PRIORITY<br />

ON<br />

OFF<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY SR503-EXP<br />

Outdoor<br />

Sensor<br />

Boiler<br />

RMB<br />

Back of Control<br />

Boiler Operation<br />

Off-Enable On-Control<br />

Power Cord<br />

SLAVE<br />

MASTER<br />

POWER CONTROL<br />

INTERFACE<br />

1 2 3 4<br />

EXPANSION<br />

PLUG-IN CARDS<br />

RESET NORMAL<br />

T<br />

T<br />

Thermostats<br />

<strong>ZONE</strong> 3<br />

PRIORITY<br />

ON<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

OFF<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

SR503-EXP<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

Sys Com<br />

ComSup Boil Out ComHeat<br />

Ret<br />

Dem<br />

Pump<br />

H<br />

N<br />

24 VAC<br />

POWER<br />

FUSE 1 AMP<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

H<br />

N<br />

Power<br />

Input<br />

DHW<br />

Circ.<br />

N<br />

Boiler<br />

Sensor<br />

Supply<br />

Sensor<br />

58<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard


X - Pump Block (XPB)<br />

Back of<br />

Control<br />

Front of<br />

Control<br />

R<br />

Power: 120 V + 10%<br />

C US 50/60 Hz, 750 VA<br />

158033 Var. Speed: 120 V<br />

(ac) 1 A<br />

Pmp Relay: 120 V<br />

(ac) 5 A, 1/6 hp<br />

Use copper<br />

conductors only<br />

MENU ITEM<br />

Com Sup SysCom<br />

Boil Out Com Heat<br />

Ret<br />

Dem<br />

Heat Source<br />

X – PUMP BLOCK<br />

PATENT PENDING<br />

U L XPB-1<br />

System<br />

Supply<br />

Sensor<br />

Heat<br />

Source<br />

Sensor<br />

Outdoor<br />

Sensor<br />

Boiler<br />

To<br />

Zone<br />

Control<br />

End Switch<br />

or<br />

Thermostat<br />

(Relay or<br />

Mechanical<br />

Type)<br />

Meets Class B:<br />

Canadian ICES<br />

FCC Part 15<br />

Sys<br />

Y R B<br />

Var<br />

Boiler Operation<br />

Off-Enable On-Control<br />

Fuse<br />

Pump<br />

Man<br />

H<br />

N<br />

Manual<br />

Operation<br />

Switch<br />

Line Cord<br />

Variable Speed Circulator<br />

Heating: Heat Source Circulator<br />

Snowmelt: System Circulator<br />

Constant Speed Circulator<br />

Heating: System Circulator<br />

Snowmelt: Heat Source Circulator<br />

X - Pump Block, Single Zone<br />

Outdoor<br />

Sensor<br />

Boiler<br />

XPB<br />

Back of Control<br />

Boiler Operation<br />

Off-Enable On-Control<br />

Power<br />

Cord<br />

Pump<br />

Thermostat<br />

(Relay or Mechanical Type)<br />

ComSupSysComBoil Out Com Heat<br />

Ret<br />

Dem<br />

H<br />

N<br />

T<br />

Pressure<br />

Relief<br />

HEAT<br />

SOURCE<br />

Input from<br />

Heat Source<br />

Exp<br />

Tank<br />

Output to<br />

System<br />

Supply<br />

Sensor<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />

59


X - Pump Block Connected to Zone Valve Control<br />

Outdoor<br />

Sensor<br />

Power<br />

Cord<br />

Power<br />

Input<br />

H<br />

N<br />

Factory<br />

Installed<br />

Transformer<br />

T<br />

T<br />

T<br />

Boiler<br />

Boiler Operation<br />

XPB Off-Enable On-Control<br />

Back of Control<br />

NORMAL<br />

POWER IN<br />

T T<br />

<strong>ZONE</strong> 1<br />

T T<br />

<strong>ZONE</strong> 2<br />

T T<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4 PRIORITY<br />

OFF<br />

T T<br />

ON<br />

<strong>ZONE</strong> 4<br />

ComSupSysComBoil Out Com Heat<br />

Ret<br />

Dem<br />

H<br />

Pump<br />

MAIN EXTRA<br />

END END<br />

SWITCH SWITCH<br />

FUSE<br />

(3 AMP MAX)<br />

N/O COMN/C<br />

<strong>ZONE</strong> 4 RELAY<br />

MODE<br />

RESET<br />

ZVC 404<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

N<br />

Pressure<br />

Relief<br />

HEAT<br />

SOURCE<br />

Input from<br />

Heat Source<br />

Exp<br />

Tank<br />

Output to<br />

System<br />

Supply<br />

Sensor<br />

Radiant Manifold - Return<br />

Radiant Manifold - Supply<br />

X - Pump Block Connected to 2 SR502/503 Switching Relays<br />

T<br />

Power<br />

Input<br />

24 VAC<br />

POWER<br />

H<br />

N<br />

SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2<br />

TWO <strong>ZONE</strong> SWITCHING RELAY<br />

FUSE 1 AMP<br />

X2<br />

N P ZC H X1 ZR<br />

T<br />

<strong>ZONE</strong>1<br />

<strong>ZONE</strong>2<br />

Outdoor<br />

Sensor<br />

Boiler<br />

ComSupSysComBoil Out Com Heat<br />

Ret<br />

Dem<br />

H<br />

N<br />

Power<br />

Cord<br />

Boiler Operation<br />

Off-Enable On-Control<br />

XPB<br />

Back of Control<br />

Pump<br />

Power<br />

Input<br />

24 VAC<br />

POWER<br />

H<br />

N<br />

SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2<br />

TWO <strong>ZONE</strong> SWITCHING RELAY<br />

FUSE 1 AMP<br />

T<br />

X2<br />

N P ZC H X1 ZR<br />

T<br />

<strong>ZONE</strong>1<br />

<strong>ZONE</strong>2<br />

Pressure<br />

Relief<br />

Return<br />

Sensor<br />

Input from<br />

Heat Source<br />

Exp<br />

Tank<br />

Output to<br />

System<br />

Supply<br />

Sensor<br />

60<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard


Typical Radiant Floor to Water Heater Installation<br />

ASSE 1017<br />

Tempering<br />

Valve<br />

Domestic<br />

Hot<br />

Supply<br />

C<br />

MIX<br />

H<br />

Hot<br />

Cold<br />

Cold<br />

Supply<br />

Check<br />

Valve<br />

X-PUMP<br />

BLOCK<br />

Air<br />

Separator<br />

Exp.<br />

Tank<br />

Supply<br />

Relief<br />

Valve<br />

Return<br />

RADIANT<br />

SYSTEM<br />

(Secondary Side<br />

of the System)<br />

WATER<br />

HEATER<br />

WARNING! A pressure relief valve and expansion tank must be installed on the secondary<br />

side in addition to any pressure relief valve and expansion tank which is installed on primary<br />

side of system. Use dedicated supply and return piping to the X-Pump Block from the water<br />

heater so as not to add heated water into the house’s cold water piping.<br />

Typical Snow Melt Installation<br />

Separator<br />

(Tb)<br />

Exp.<br />

Tank<br />

Note 3<br />

{<br />

Note 1 Note 2<br />

{<br />

Note 3<br />

{<br />

{<br />

X-PUMP<br />

BLOCK<br />

SYSTEM<br />

RETURN<br />

SENSOR<br />

Note 2<br />

{<br />

}<br />

Note 1<br />

(Ts)<br />

Air<br />

Separator<br />

Exp.<br />

Tank<br />

SYSTEM<br />

SUPPLY<br />

SENSOR<br />

Relief<br />

Valve<br />

Return<br />

(ΔTs)<br />

HEAT<br />

SOURCE<br />

HEAT SOURCE<br />

RETURN SENSOR<br />

(OPTIONAL)<br />

FIXED SPEED<br />

CIRCULATOR<br />

(4 PIN PLUG)<br />

VARIABLE SPEED<br />

CIRCULATOR<br />

(3 PIN PLUG)<br />

Supply<br />

SNOW MELT<br />

SYSTEM<br />

Tb = Boiler Supply Temperature<br />

Ts = System Supply Temperature<br />

ΔTs = System Temperature Drop<br />

(typically 20°F for convectors<br />

and 10°F for radiant floor heating)<br />

Note 1: There must be no more than 4 pipe diameters between the tees in the boiler and<br />

system loops in order to prevent ghost flow when the variable speed injection<br />

pump is off and either the boiler pump or system pump is on.<br />

Note 2: There must be at least 6 pipe diameters of straight pipe on either side of the tees in<br />

order to prevent the momentum of water in the boiler and system loops from pushing<br />

flow through the injection loop.<br />

Note 3: There should be a minimum 1 foot drop to create a thermal trap in order to prevent<br />

convective heat transfer through the injection loop.<br />

61


iSeries Mixing Valve<br />

Boiler<br />

Return<br />

Sensor<br />

(optional)<br />

System<br />

Supply<br />

Sensor<br />

Back of<br />

Control<br />

Boiler<br />

Return<br />

Sensor<br />

System<br />

Supply<br />

Sensor<br />

Back of<br />

Control<br />

BOILER<br />

SUPPLY<br />

SETBACK<br />

POWER<br />

GREEN<br />

SENSOR<br />

ERROR<br />

RED<br />

C<br />

R<br />

24 VAC<br />

POWER INPUT<br />

BOILER<br />

SUPPLY<br />

OUTDOOR<br />

POWER<br />

GREEN<br />

SENSOR<br />

ERROR<br />

RED<br />

C<br />

R<br />

24 VAC<br />

POWER INPUT<br />

SENSOR COMMON<br />

SENSOR COMMON<br />

Setback<br />

Input<br />

24 V (ac)<br />

Transformer<br />

or<br />

End<br />

Switch<br />

Outdoor<br />

Sensor<br />

24 V (ac)<br />

Transformer<br />

or<br />

End<br />

Switch<br />

iValve-S<br />

iValve-R<br />

iValve, 2-Way Injection, Single Zone<br />

Outdoor<br />

Sensor<br />

T<br />

Thermostat<br />

BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />

BOILER<br />

POWER<br />

SUPPLY GREEN<br />

OUTDOOR<br />

SENSOR<br />

ERROR<br />

RED<br />

SENSOR<br />

COMMON<br />

24 VAC<br />

POWER INPUT<br />

C R<br />

SR501<br />

1 Z ONE<br />

SWITCHING RELAY<br />

R<br />

T<br />

W<br />

T<br />

120 VAC<br />

INPUT<br />

N 4 N/O N/C<br />

6 N/C<br />

24<br />

VAC<br />

COM<br />

H 3 4 6 5<br />

N/O<br />

24 Volt<br />

Transformer<br />

H<br />

N<br />

Power<br />

Input<br />

iSeries-R<br />

Supply<br />

Sensor<br />

A<br />

B<br />

Boiler<br />

Sensor<br />

62<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard


iValve, 3-Way Mixing Working with SR502/503 Switching Relay with DHW Priority<br />

T<br />

Thermostats<br />

Outdoor<br />

Sensor<br />

BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />

Power<br />

Input<br />

H N<br />

24 VAC<br />

POWER<br />

DHW Aquastat<br />

SR 503<br />

FUSE 1 AMP<br />

A<br />

T<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

BOILER<br />

POWER<br />

SUPPLY GREEN<br />

OUTDOOR<br />

SENSOR<br />

COMMON<br />

24 VAC<br />

POWER INPUT<br />

C R<br />

Transformer<br />

24 Volt<br />

X2<br />

N P ZC H X1 ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

SENSOR<br />

ERROR<br />

RED<br />

DHW<br />

Circ.<br />

Supply<br />

Sensor<br />

B<br />

C<br />

A<br />

C<br />

A<br />

iSeries-R<br />

Boiler<br />

Sensor<br />

iValve, 4-Way Mixing Working with Zone Valve Control<br />

Outdoor<br />

Sensor<br />

BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />

T<br />

T<br />

Thermostats<br />

BOILER<br />

SUPPLY<br />

OUTDOOR<br />

POWER<br />

GREEN<br />

SENSOR<br />

ERROR<br />

RED<br />

SENSOR 24 VAC<br />

COMMON POWER INPUT<br />

C R<br />

24 Volt<br />

Transformer<br />

Power<br />

Input<br />

H<br />

N<br />

Factory<br />

Installed<br />

Transformer<br />

POWER IN<br />

FUSE<br />

(5 AMP MAX)<br />

END N/O COM N/C<br />

SWITCH<br />

TT<br />

<strong>ZONE</strong> 1<br />

ZVC 403<br />

THREE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

<strong>ZONE</strong> 1<br />

1234<br />

TT<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 2<br />

1234<br />

TT<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 3<br />

1234<br />

Motor<br />

M<br />

End Switch<br />

Motor<br />

M<br />

End<br />

Switch<br />

Supply<br />

Sensor<br />

iSeries-R<br />

Boiler<br />

Sensor<br />

FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />

63


Wiring for Boilers with Honeywell Control Center Model R8285 or Equivalent<br />

TACO LTR0243T-1<br />

FEMALE<br />

CONNECTOR<br />

FACTORY<br />

WIRING<br />

WH<br />

RED<br />

YEL<br />

GRN<br />

YEL<br />

MALE<br />

CONNECTOR<br />

GROUND<br />

CONNECTION<br />

Alternate<br />

Wiring<br />

TACO LTR0243T-1<br />

WH RED YEL GRN<br />

YEL<br />

24 VAC<br />

CLASS 2<br />

TRANSFORMER<br />

HOT<br />

LIMIT<br />

<strong>CONTROLS</strong><br />

120<br />

VAC<br />

24 VAC<br />

GAS<br />

VALVE<br />

COMMON<br />

64


Wiring Boilers with a United Technologies Integrated Control Module and a <strong>Taco</strong> LTR0243U-1<br />

INTEGRATED BOILER<br />

CONTROL<br />

MALE<br />

CONNECTOR<br />

FACTORY WIRING<br />

FEMALE<br />

CONNECTOR<br />

BOILER MODULE<br />

WIRING HARNESS<br />

Wiring Boilers with a United Technologies Ucontrol or other Integrated Control Modules<br />

which accept a 4-pin harness and a <strong>Taco</strong> LTR0243L-1<br />

4-PIN CONNECTOR (#1)<br />

4-PIN CONNECTOR (#2)<br />

WIRING HARNESS<br />

INTEGRATED<br />

CONTROL<br />

MODULE<br />

Wiring Instructions<br />

1. Plug the 4-pin connector on the wiring harness (#1 as<br />

shown) into the integrated control module.<br />

2. Plug the 4-pin connector on the wiring harness (#2 as<br />

shown) into the LTR.<br />

65


Wiring <strong>Taco</strong> LN and LTA-2 Series Low Water Cutoffs<br />

Using Burner Circuit Power Source<br />

*<br />

*Factory Installed<br />

NOTE: For 24 VAC models, LNA024xx and LTA0243S-2, 24 VAC to<br />

be supplied by an EXTERNAL Class 2 power source to terminals<br />

H and N. For 120 VAC models, LNA120xx and LTA1203S-2, 120 VAC<br />

is supplied by an external circuit to terminals H and N.<br />

Wiring <strong>Taco</strong> LN and LTA-2 Series Low Water Cutoffs<br />

Using Power Source Other Than Burner Circuit<br />

NOTE: For 24 VAC models, LNA024xx and LTA0243S-2, 24 VAC to<br />

be supplied by an EXTERNAL Class 2 power source to terminals<br />

H and N. For 120 VAC models, LNA120xx and LTA1203S-2, 120 VAC<br />

is supplied by an external circuit to terminals H and N.<br />

66


Wiring <strong>Taco</strong> LT Series (1st generation, -1) Low Water Cutoffs<br />

Using Burner Circuit Power Source<br />

*<br />

*Factory Installed<br />

NOTE: For 24 VAC models, LTx024xx-1, 24 VAC to be supplied<br />

by an EXTERNAL Class 2 power source to terminals H and N.<br />

For 120 VAC models, LTx120xx-1, 120 VAC is supplied by an<br />

external circuit to terminals H and N.<br />

Wiring <strong>Taco</strong> LT Series (1st generation, -1) Low Water Cutoffs<br />

Using Power Source Other Than Burner Circuit<br />

NOTE: For 24 VAC models, LTx024xx-1, 24 VAC to be supplied<br />

by an EXTERNAL Class 2 power source to terminals H and N.<br />

For 120 VAC models, LTx120xx-1, 120 VAC is supplied by an<br />

external circuit to terminals H and N.<br />

67


Wiring <strong>Taco</strong> LF Series Low Water Cutoffs Using Burner Circuit Power Source<br />

NOTE: Remote probe available on remote probe models only.<br />

NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.<br />

For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.<br />

Wiring <strong>Taco</strong> LF Series Low Water Cutoffs Using Power Source Other Than Burner Circuit<br />

NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.<br />

For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.<br />

68


<strong>Taco</strong> Low Water Cutoff Replacement Guide<br />

<strong>Taco</strong> McDonnell & Miller Hydrolevel Honeywell<br />

LFA1203S-1<br />

LTA1203N-1<br />

LTA1203S-1<br />

LFM1203S-1<br />

LTM1203N-1<br />

LTM1203S-1<br />

LFA0243S-1<br />

LTA0243N-1<br />

LTA0243S-1<br />

LFM0243S-1<br />

LTM0243N-1<br />

LTM0243S-1<br />

LFA1203R-1<br />

LTA1203R-1<br />

LFM1203R-1<br />

LTM1203R-1<br />

LFA1202R-1<br />

LTA1202R-1<br />

LFM1202R-1<br />

LTM1202R-1<br />

LFA0242R-1<br />

LTA0242R-1<br />

LTA0243S-2<br />

LNA0243S-1<br />

LTA1203S-2<br />

LNA1203S-1<br />

LTR0243T-1<br />

P3R-1<br />

EWF120<br />

EWF024<br />

PS-801-120<br />

PSE-801-120<br />

PS-800-120<br />

PS-850-120<br />

900<br />

900C<br />

PS-801-M-120<br />

PS-851-M-120<br />

PS-851-SP-M-120<br />

PS-850-M-120<br />

900M<br />

901M<br />

902M<br />

PS-802-24<br />

PSE-802-24<br />

PS-800-24<br />

PS-850-24<br />

PS-802-M-24<br />

PS-852-M-24<br />

PS-852-SP-M-24<br />

PS-850-M-24<br />

750-T-120<br />

750-120<br />

750-MT-120<br />

750-M-120<br />

PS-851-RX2-120<br />

PS-851-M-RX2-120<br />

PS-802-RX2-24<br />

PS-852-24<br />

PS-852-SP-24<br />

750-MT-SP-24<br />

750P-MT-24<br />

750P-MT-U-24<br />

RB-120<br />

RB-122E<br />

PS-851-120<br />

PS-851-SP-120<br />

750P-MT-120<br />

750P-MT-SP-120<br />

750P-MT-U-120<br />

901<br />

RB-120II<br />

RB-122<br />

RB-24E<br />

RB-24<br />

RS-1-BR-1<br />

RS-1-LP<br />

RS-1-LP-S<br />

WFE-120<br />

WF2-U-120V<br />

WF-2-120<br />

WF-4-120<br />

WFE-24<br />

WF2-U-24V<br />

WF-2-24<br />

WF-4-24<br />

Bold / Italics Indicates Discontinued Part Number<br />

450<br />

CG450<br />

CGT450<br />

OEM170TD<br />

550<br />

550SV<br />

750<br />

OEM170MC<br />

OEM170M<br />

400<br />

CG400<br />

OEM24TD<br />

500<br />

500SV<br />

700<br />

OEM24MC<br />

650R<br />

550R<br />

650R<br />

550R<br />

400R<br />

24<br />

24SV<br />

600<br />

600SV<br />

OEM24C<br />

170<br />

170SV<br />

1150<br />

650<br />

650SV<br />

OEM170C<br />

OEM170<br />

1100<br />

EL1214-R<br />

VRTX-120<br />

V-120-1&2<br />

VRTX-24<br />

V-24-1&2<br />

RW700A1031<br />

RW700A1056<br />

RW700A1080<br />

RW700B1054<br />

RW700B1039<br />

RW700B1021<br />

RW700A1098<br />

RW700A1007<br />

RW700A1006<br />

VW400A1004<br />

VW800A1004<br />

69


<strong>Taco</strong> LF Series 120 Volt LWCO Competitive Wiring Cross Reference<br />

120 VAC Models with 120 VAC Burner Circuits<br />

NC<br />

TACO LFx120x<br />

NO COM H N GND P<br />

McDONNELL & MILLER<br />

PS-801/851-120<br />

w/Red & Amber LEDs<br />

Series 750<br />

1 2 3 4 5<br />

BURNER<br />

CIRCUIT<br />

FACTORY<br />

INSTALLED<br />

JUMPER<br />

120 VAC<br />

CIRCUIT<br />

HOT<br />

NEUTRAL<br />

HOT<br />

NEUTRAL<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HYDROLEVEL<br />

450, 550, 650 & 750<br />

McDONNELL & MILLER<br />

PS-801/851-120<br />

w/Red & Green LEDs<br />

2 1 P1 P2 A<br />

N H C W B<br />

HOT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

NEUTRAL<br />

120 VAC Models with 24 VAC Burner Circuits<br />

NC<br />

TACO LFx120x<br />

NO COM H N GND P<br />

McDONNELL & MILLER<br />

PS-801/851-120<br />

w/Red & Amber LEDs<br />

Series 750<br />

1 2 3 4 5<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

HOT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

24 VAC<br />

TRANSFORMER<br />

NEUTRAL<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

HYDROLEVEL<br />

450, 550, 650 & 750<br />

McDONNELL & MILLER<br />

PS-801/851-120<br />

w/Red & Green LEDs<br />

2 1 P1 P2 A<br />

N H C W B<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

70


<strong>Taco</strong> LF Series 24 Volt LWCO Competitive Wiring Cross Reference<br />

24 VAC Models with 24 VAC Burner Circuits<br />

TACO LFx024x<br />

NC<br />

NO COM H N GND P<br />

BURNER<br />

CIRCUIT<br />

FACTORY<br />

INSTALLED<br />

JUMPER<br />

24 VAC<br />

CIRCUIT<br />

HOT<br />

NEUTRAL<br />

HYDROLEVEL<br />

400, 500, 600 & 700<br />

McDONNELL & MILLER<br />

PS-802/852-24<br />

2 1 P1 P2 A<br />

N H C W B<br />

HOT<br />

HOT<br />

24 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

24 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

NEUTRAL<br />

24 VAC Models with 120 VAC Burner Circuits<br />

TACO LFx024x<br />

NC<br />

NO COM H N GND P<br />

BURNER<br />

CIRCUIT<br />

24 VAC<br />

TRANSFORMER<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

NEUTRAL<br />

HYDROLEVEL<br />

400, 500, 600 & 700<br />

2 1 P1 P2 A<br />

McDONNELL & MILLER<br />

PS-802/852-24<br />

N H C W B<br />

HOT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

BURNER<br />

CIRCUIT<br />

71


<strong>Taco</strong> LTA-2 Series 120 Volt LWCO Competitive Wiring Cross Reference<br />

120 VAC Models with 120 VAC Burner Circuits<br />

TACO LTA1203S-2<br />

N H COM NC NO<br />

McDONNELL & MILLER<br />

RB-120<br />

1 2 3 4 5<br />

HOT<br />

HOT<br />

NEUTRAL<br />

120 VAC<br />

CIRCUIT<br />

FACTORY<br />

INSTALLED<br />

JUMPER<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

McDONNELL & MILLER<br />

RB-122E<br />

N H B C<br />

HYDROLEVEL 1150<br />

CUT-OFF<br />

H N<br />

HYDROLEVEL 170<br />

GN H P1 P2 A<br />

HOT<br />

HOT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

NEUTRAL<br />

NEUTRAL<br />

120 VAC Models with 24 VAC Burner Circuits<br />

TACO LTA1203S-2<br />

McDONNELL & MILLER<br />

RB-120<br />

N H COM NC NO<br />

1 2 3 4 5<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

McDONNELL & MILLER<br />

RB-122E<br />

HYDROLEVEL 1150<br />

HYDROLEVEL 170SV<br />

N H B C H N<br />

CUT-OFF<br />

GN H P1 P2 A<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

NEUTRAL<br />

24 VAC<br />

TRANSFORMER<br />

72


<strong>Taco</strong> LTR and LTA-2 Series 24 Volt LWCO Competitive Wiring Cross Reference<br />

24 VAC Models with 24 VAC Burner Circuits<br />

TACO LTA0243S-2<br />

N H COM NC NO<br />

McDONNELL & MILLER<br />

RB-24E<br />

Red<br />

Wire<br />

White<br />

Wire<br />

Yellow<br />

Wire<br />

Yellow<br />

Wire<br />

HOT<br />

HOT<br />

NEUTRAL<br />

24 VAC<br />

CIRCUIT<br />

FACTORY<br />

INSTALLED<br />

JUMPER<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

24 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

Red<br />

Wire<br />

TACO LTR0243T-1<br />

White<br />

Wire<br />

Yellow<br />

Wire<br />

Yellow<br />

Wire<br />

HYDROLEVEL 1100<br />

Red<br />

Wire<br />

White<br />

Wire<br />

Yellow<br />

Wire<br />

Yellow<br />

Wire<br />

HYDROLEVEL 24<br />

2 1 P1 P2 A<br />

HOT<br />

24 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

24 VAC<br />

CIRCUIT<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

24 VAC<br />

CIRCUIT<br />

JUMPER<br />

BURNER<br />

CIRCUIT<br />

NEUTRAL<br />

NEUTRAL<br />

NEUTRAL<br />

24 VAC Models with 120 VAC Burner Circuits<br />

TACO LTA0243S-2<br />

HYDROLEVEL 24<br />

N H COM NC NO<br />

2 1 P1 P2 A<br />

HOT<br />

HOT<br />

120 VAC<br />

CIRCUIT<br />

NEUTRAL<br />

BURNER<br />

CIRCUIT<br />

120 VAC<br />

CIRCUIT<br />

NEUTRAL<br />

BURNER<br />

CIRCUIT<br />

24 VAC<br />

TRANSFORMER<br />

24 VAC<br />

TRANSFORMER<br />

73


Wiring <strong>Taco</strong> LF Series Low Water Cutoffs<br />

to <strong>Taco</strong> Electric Water Feeder with the Same Voltages<br />

EWF Standard Wiring<br />

<strong>Taco</strong> LFx120x / LFx024x<br />

NC NO COM H N<br />

GND<br />

P<br />

HOT<br />

BURNER<br />

CIRCUIT<br />

FACTORY<br />

INSTALLED<br />

JUMPER<br />

120 V AC / 24 V AC<br />

CIRCUIT<br />

NEUTRAL<br />

LW<br />

N<br />

H<br />

<strong>Taco</strong> E W F120 / E W F024<br />

Wiring <strong>Taco</strong> LF Series Low Water Cutoffs<br />

to <strong>Taco</strong> Electric Water Feeder with Different Burner Voltages<br />

EWF Alternate Wiring<br />

<strong>Taco</strong> LFx120x<br />

<strong>Taco</strong> LFx024x<br />

NC NO COM H N<br />

GND<br />

P<br />

NC<br />

NO COM H N GND P<br />

BURNER<br />

CIRCUIT<br />

HOT<br />

* *<br />

BURNER<br />

120 VAC<br />

CIRCUIT<br />

CIRCUIT<br />

NEUTRAL<br />

HOT<br />

24 V AC<br />

CIRCUIT<br />

NEUTRAL<br />

HOT<br />

HOT<br />

H<br />

N<br />

LW<br />

24 V AC<br />

CIRCUIT<br />

H<br />

N<br />

LW<br />

120 VAC<br />

CIRCUIT<br />

<strong>Taco</strong> EW F024<br />

NEUTRAL<br />

<strong>Taco</strong> EW F120<br />

NEUTRAL<br />

* NOTE: Remove factory installed<br />

jumper between H and COM terminals<br />

74


Wiring <strong>Taco</strong> 24VAC Electric Water Feeder to <strong>Taco</strong> LF Series 24VAC Low Water Cutoff<br />

or 24VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs<br />

McDonnell & Miller<br />

PS-802/852-24<br />

B<br />

W<br />

C<br />

H<br />

N<br />

Hydrolevel<br />

400, 500, 600, & 700<br />

P2<br />

A<br />

P1<br />

1<br />

2<br />

<strong>Taco</strong> LFx024x<br />

NC NO COM H N GND P<br />

BURNER<br />

CIRCUIT<br />

INSTALLED<br />

JUMPER **<br />

HOT<br />

24 V AC<br />

CIRCUIT<br />

** May be factory installed on<br />

some LW COs<br />

LW<br />

N<br />

<strong>Taco</strong> EWF024<br />

H<br />

NEUTRAL<br />

NOTE: Wiring shown only for control<br />

and burner circuits of the same<br />

voltage. Some terminal designations<br />

are not in their actual order on the<br />

LW COs.<br />

Wiring <strong>Taco</strong> 120VAC Electric Water Feeder to <strong>Taco</strong> LF Series 120VAC Low Water Cutoff<br />

or 120VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs<br />

McDonnell & Miller<br />

PS-801/851-120 w/Red &<br />

Am ber LE Ds, Series 750<br />

5<br />

4<br />

3<br />

1 2<br />

McDonnell & Miller<br />

PS-801/851-120<br />

w/Red & Green LEDs<br />

B<br />

W<br />

C<br />

H<br />

N<br />

Hydrolevel<br />

450, 550, 650, & 750<br />

P2<br />

A<br />

P1<br />

1<br />

2<br />

<strong>Taco</strong> LFx120x<br />

NC NO COM H N GND P<br />

HOT<br />

** May be factory installed on<br />

some LW COs<br />

BURNER<br />

CIRCUIT<br />

INSTALLED<br />

JUMPER **<br />

120 V AC<br />

CIRCUIT<br />

NEUTRAL<br />

NOTE: Wiring shown only for control<br />

and burner circuits of the same<br />

voltage. Some terminal designations<br />

are not in their actual order on the<br />

LW COs.<br />

LW<br />

N<br />

H<br />

<strong>Taco</strong> EWF120<br />

75


Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to<br />

McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder<br />

UNI-MATCH<br />

WATER FEEDER<br />

MODEL WF2-U-24<br />

1 2 3<br />

0R<br />

W N H<br />

SWITCH POSITION #2<br />

M&M<br />

2<br />

3<br />

24VAC<br />

SUPPLY<br />

50/60 Hz<br />

N<br />

H<br />

BURNER<br />

Note on switch position:<br />

Switch setting 1 (M&M), the feed cycle repeats<br />

indefinitely. Position 2 and 3 gives one feed cycle.<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

24 VAC LWCO Using Burner Circuit Power Source<br />

Remove jumper between H and COM if using power source<br />

other than burner circuit or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

If using the LTA-2 series, choose whichever position<br />

best matches the application:<br />

WF-2 switch to position 1<br />

- 60 sec. delay, 90 sec. feed, repeats<br />

WF-2 switch to position 2<br />

- 90 sec. delay, 90 sec. feed<br />

WF-2 switch to position 3<br />

- 100 sec. delay, 90 sec. feed<br />

Wiring TACO LTA-2 or LF Series 120VAC Low Water Cutoff to<br />

McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder<br />

UNI-MATCH<br />

WATER FEEDER<br />

MODEL WF2-U-120<br />

1 2 3<br />

0R<br />

W N H<br />

SWITCH POSITION #2<br />

M&M<br />

2<br />

3<br />

120VAC N<br />

SUPPLY<br />

50/60 Hz H<br />

BURNER<br />

Note on switch position:<br />

Switch setting 1 (M&M), the feed cycle repeats<br />

indefinitely. Position 2 and 3 gives one feed cycle.<br />

76<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

120 VAC LWCO Using Burner Circuit Power Source<br />

Remove jumper between H and COM if using power source<br />

other than burner circuit or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

If using the LTA-2 series, choose whichever position<br />

best matches the application:<br />

WF-2 switch to position 1<br />

- 60 sec. delay, 90 sec. feed, repeats<br />

WF-2 switch to position 2<br />

- 90 sec. delay, 90 sec. feed<br />

WF-2 switch to position 3<br />

- 100 sec. delay, 90 sec. feed


Wiring TACO LF Series 24VAC Low Water Cutoff to<br />

Hydrolevel VXT-24 Water Feeder (Non-Display Model)<br />

SAFGARD VXT-24<br />

WATER FEEDER<br />

Set Safgard as desired.<br />

WHITE<br />

BLACK<br />

24VAC N<br />

SUPPLY<br />

50/60 Hz H<br />

BURNER<br />

Remove jumper between H and COM if using<br />

power source other than burner circuit<br />

or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

24 VAC LWCO Using Burner Circuit Power Source<br />

Wiring TACO LF Series 120VAC Low Water Cutoff to<br />

Hydrolevel VXT-120 Water Feeder (Non-Display Model)<br />

SAFGARD VXT-120<br />

WATER FEEDER<br />

Set Safgard as desired.<br />

WHITE<br />

BLACK<br />

120VAC N<br />

SUPPLY<br />

50/60 Hz H<br />

BURNER<br />

Remove jumper between H and COM if using<br />

power source other than burner circuit<br />

or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

120 VAC LWCO Using Burner Circuit Power Source<br />

77


Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to<br />

Hydrolevel VXT-24 Programmable Water Feeder (Model with Display)<br />

SAFGARD VRTX-24<br />

WATER FEEDER<br />

Set Safgard as desired.<br />

WHITE<br />

BLACK<br />

RED<br />

24VAC N<br />

SUPPLY<br />

50/60 Hz H<br />

BURNER<br />

Remove jumper between H and COM if using<br />

power source other than burner circuit<br />

or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

24 VAC LWCO Using Burner Circuit Power Source<br />

Wiring TACO LTA-2 or LF Series 120VAC Low Water Cutoff to<br />

Hydrolevel VXT-120 Programmable Water Feeder (Model with Display)<br />

SAFGARD VRTX-120<br />

WATER FEEDER<br />

Set Safgard as desired.<br />

WHITE<br />

BLACK<br />

RED<br />

120VAC N<br />

SUPPLY<br />

50/60 Hz H<br />

BURNER<br />

Remove jumper between H and COM if using<br />

power source other than burner circuit<br />

or when using mixed voltages.<br />

Do not connect feeder to a manual reset LWCO.<br />

N H COM NC NO<br />

AC POWER OUTPUT CONTACTS<br />

120 VAC LWCO Using Burner Circuit Power Source<br />

78


<strong>Taco</strong> LTR, LN, LT-1, LTA-2 & LF Series Low Water Cutoff and <strong>Taco</strong> Electric Water Feeder Wiring Cross Reference<br />

Power Connections Output Contacts Remote Probes<br />

Probe<br />

Preference<br />

To EWF’s LW<br />

Terminal/Alarm<br />

To Burner<br />

Circuit<br />

Manufacturer Device or Series<br />

Probe<br />

Hot Neutral Common<br />

<strong>Taco</strong> LF & LT-1 Series H N COM NC NO P GND<br />

<strong>Taco</strong> LTA-2 & LN Series H N COM NC NO — —<br />

<strong>Taco</strong> LTR Series Red Wire White Wire Yellow Wire Yellow Wire — — —<br />

PS-801/851 (Older Models<br />

w/Red & Amber LEDs)<br />

1 2 3 5 4 P or J2 Chassis GND<br />

PS-801/851 (New Models<br />

w/Red & Green LEDs)<br />

H N C B W J2 Chassis GND<br />

PS-802/852 (Older Models<br />

w/Red & Amber LEDs)<br />

H N C B W J7 Chassis GND<br />

PS-802/852 (Older Models<br />

w/Red & Green LEDs)<br />

H N C B W J3 Chassis GND<br />

McDonnell & Miller<br />

McDonnell & Miller<br />

McDonnell & Miller<br />

McDonnell & Miller<br />

McDonnell & Miller Series 750 1 2 3 5 4 P Chassis GND<br />

— — —<br />

B<br />

(Yellow Wire)<br />

C<br />

(Yellow Wire)<br />

N<br />

(White Wire)<br />

H<br />

(Black Wire)<br />

McDonnell & Miller RB-122<br />

McDonnell & Miller RB-120 1 2 3 4 5 — —<br />

McDonnell & Miller RB-24 Red Wire White Wire Yellow Wire Yellow Wire — — —<br />

Hydrolevel 24 1 2 P1 P2 A — —<br />

Hydrolevel 170 H GN P1 P2 A — —<br />

Hydrolevel 1100 Red Wire White Wire Yellow Wire Yellow Wire — — —<br />

— — —<br />

CUT-OFF<br />

(Yellow Wire)<br />

CUT-OFF<br />

(Yellow Wire)<br />

N<br />

(White Wire)<br />

H<br />

(Black Wire)<br />

Hydrolevel 1150<br />

1 2 P1 P2 A H3 Chassis GND<br />

400, 500, 600, 700, 450,<br />

550, 650, 750<br />

RW700 Series<br />

(Except RW700A1098)<br />

Hydrolevel<br />

Green Wire<br />

2 Red Wires,<br />

White Wire<br />

L1 L2 — B A<br />

Hydrolevel<br />

Green Wire<br />

2 Red Wires,<br />

White Wire<br />

Hydrolevel RW700A1098 T1 T2 — B A<br />

79


Aquastat Wiring<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1 L2 T T<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C1<br />

ZC<br />

B2 C2 ZR B1<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8124A & C OR EQUAL<br />

MILLI-VOLTAGE<br />

GAS VALVE<br />

B1 B2 T T<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C<br />

L1<br />

L2<br />

C2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

HONEYWELL L8124B OR EQUAL<br />

TV T Z<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C1<br />

C2<br />

B1<br />

B2<br />

L1<br />

L2<br />

LOW VOLTAGE<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

HONEYWELL L8124E OR EQUAL<br />

80


Aquastat Wiring<br />

TV T Z<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

L1<br />

ZC<br />

L2<br />

ZR<br />

B2<br />

C2<br />

B1<br />

C1<br />

LINE<br />

VOLTAGE<br />

OIL BURNER<br />

RELAY OR<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

HONEYWELL L8124G & L OR EQUAL<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1 L2 T T<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C1<br />

ZC<br />

B2<br />

C2<br />

ZR<br />

B1<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8124M OR EQUAL<br />

L1<br />

(HOT)<br />

L1 L2 T T<br />

3<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C1<br />

C2<br />

B1<br />

B2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8148A OR EQUAL<br />

81


Aquastat Wiring<br />

TV W T<br />

Z<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

C1<br />

C2<br />

B1<br />

B2<br />

L1<br />

L2<br />

LOW VOLTAGE<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

HONEYWELL L8148E OR EQUAL<br />

TV W T<br />

TP<br />

Z<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

MILLI-<br />

VOLTAGE<br />

GAS<br />

VALVE<br />

B1<br />

B2<br />

B3<br />

C1<br />

L1<br />

C2<br />

L2<br />

OR<br />

LOW VOLTAGE<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

HONEYWELL L8148J OR EQUAL<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1<br />

L2<br />

B1<br />

B2<br />

C2<br />

C1<br />

OIL BURNER<br />

AND<br />

IGNITION<br />

END SWITCH<br />

TACO<br />

<strong>ZONE</strong><br />

CONTROL<br />

ZC<br />

ZR<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

T<br />

T<br />

F<br />

F<br />

CAD CELL<br />

HONEYWELL L8182D OR EQUAL<br />

82


Aquastat Wiring<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1 L2 T T<br />

T<br />

THERMOSTAT<br />

(IF INDEPENDENT <strong>ZONE</strong>)<br />

END SWITCH<br />

X X<br />

TACO<br />

SWITCHING<br />

RELAY<br />

ZC ZR N H<br />

C1<br />

ZC<br />

B2 C2 ZR B1<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8124A & C OR EQUAL<br />

T<br />

THERMOSTAT<br />

(IF INDEPENDENT <strong>ZONE</strong>)<br />

TV T Z<br />

END SWITCH<br />

X X<br />

TACO<br />

SWITCHING<br />

RELAY<br />

ZC ZR N H<br />

ZC<br />

ZR<br />

B1<br />

L1<br />

(HOT)<br />

L1<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L2<br />

B2<br />

C2<br />

C1<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE<br />

VOLTAGE<br />

OIL BURNER<br />

RELAY OR<br />

GAS VALVE<br />

HONEYWELL L8124G & L OR EQUAL<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1 L2 T T<br />

T<br />

THERMOSTAT<br />

(IF INDEPENDENT <strong>ZONE</strong>)<br />

END SWITCH<br />

X X<br />

TACO<br />

SWITCHING<br />

RELAY<br />

ZC ZR N H<br />

C1<br />

ZC<br />

B2 C2 ZR B1<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8124M OR EQUAL<br />

83


Aquastat Wiring<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

R<br />

W<br />

B<br />

L1 L2 T T<br />

3<br />

B2<br />

B<br />

T<br />

THERMOSTAT<br />

(IF INDEPENDENT <strong>ZONE</strong>)<br />

END SWITCH<br />

X X<br />

TACO<br />

SWITCHING<br />

RELAY<br />

ZC ZR N H<br />

L6006<br />

LOW<br />

LIMIT<br />

CONTROLER<br />

C1<br />

C2<br />

R<br />

B1<br />

B2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

LINE VOLTAGE<br />

OIL BURNER RELAY<br />

OR GAS VALVE<br />

HONEYWELL L8148A OR EQUAL<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

L1<br />

L2<br />

B1<br />

B2<br />

C2<br />

C1<br />

ZC<br />

OIL BURNER<br />

AND<br />

IGNITION<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

END SWITCH<br />

X X<br />

TACO<br />

SWITCHING<br />

RELAY<br />

ZC ZR N H<br />

ZR<br />

T<br />

T<br />

F<br />

F<br />

T<br />

THERMOSTAT<br />

(IF INDEPENDENT<br />

<strong>ZONE</strong>)<br />

CAD CELL<br />

HONEYWELL L8182D OR EQUAL<br />

84


Wiring for Boilers with Honeywell Aquastat Model L8124E or Equivalent<br />

FACTORY WIRING<br />

(unplug from B1 terminal)<br />

TACO LTR0243T-1<br />

WH RED YEL GRN YEL<br />

TV T Z<br />

HONEYWELL<br />

L8124E<br />

C1<br />

C2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

MALE<br />

CONNECTOR<br />

B1<br />

G<br />

B2<br />

L1<br />

L2<br />

FEMALE<br />

CONNECTOR<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

NOTE: The green wire must be connected to a ground source<br />

electrically common to the boiler ground.<br />

Wiring for Boilers with Honeywell Aquastat Model L8148E or Equivalent<br />

FACTORY WIRING<br />

(unplug from B1 terminal)<br />

TACO LTR0243T-1<br />

WH RED YEL GRN<br />

YEL<br />

TV W T<br />

Z<br />

HONEYWELL<br />

L8148E<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

MALE<br />

CONNECTOR<br />

B1<br />

B2<br />

C1<br />

C2<br />

G<br />

L1<br />

L2<br />

FEMALE<br />

CONNECTOR<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

NOTE: The green wire must be connected to a ground source<br />

electrically common to the boiler ground.<br />

85


Aquastat Wiring to 24VAC Low Water Cutoff<br />

TO<br />

THERMOSTAT<br />

TACO LNA024 or LTA024-2<br />

N H COM NC NO<br />

TV W T<br />

HONEYWELL<br />

L8148E<br />

Z<br />

B<br />

R<br />

C1<br />

C2<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

B1<br />

B2<br />

L1<br />

L2<br />

G<br />

SPILL<br />

SWITCH<br />

LOW VOLTAGE<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)<br />

Aquastat Wiring to 120VAC Low Water Cutoff<br />

TO<br />

THERMOSTAT<br />

TACO LNA120 OR LTA120-2<br />

N H COM NC NO<br />

TV W T<br />

Z<br />

B<br />

HONEYWELL<br />

L8148E<br />

CIRCULATOR<br />

ON BOILER<br />

(IF ATTACHED)<br />

R<br />

C1<br />

C2<br />

B1<br />

B2<br />

L1<br />

L2<br />

G<br />

SPILL<br />

SWITCH<br />

86<br />

LOW VOLTAGE<br />

GAS VALVE<br />

L1<br />

(HOT)<br />

120 VAC<br />

INPUT<br />

L2<br />

(NEUTRAL)


Instruction Sheet<br />

SR501 Switching Relay<br />

Features:<br />

External Indicator Lights<br />

Universal Replaceability<br />

Snap-in PC Board<br />

Simplified Wiring<br />

Fully Enclosed Snap-Out Relays<br />

100% Factory Tested<br />

Contractor Friendly PC Board Layout<br />

Universal Thermostat Compatibility<br />

UL Approved<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Typical<br />

Wiring<br />

SR501<br />

1 <strong>ZONE</strong> SWITCHING RELAY<br />

THERMOSTAT<br />

24<br />

R W VAC<br />

T T COM<br />

POWER<br />

T STAT<br />

Alternative<br />

Wiring<br />

SR501<br />

1 <strong>ZONE</strong> SWITCHING RELAY<br />

THERMOSTAT<br />

24<br />

R W VAC<br />

T T COM<br />

POWER<br />

T STAT<br />

Operation:<br />

Connect a thermostat to the “T T” terminals on<br />

the switching relay. When the thermostat calls for<br />

heat, the relay is energized and power is given to the<br />

circulator.<br />

120 VAC<br />

INPUT<br />

N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />

JUMPER<br />

120 VAC<br />

INPUT<br />

N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />

Power Input:<br />

Connect 120 volt ac power to terminals N and H.<br />

TO: 120 VAC POWER<br />

TO: TT ON BOILER<br />

CIRCULATOR<br />

TO: ZC<br />

TO: ZR<br />

TO: 120 VAC POWER<br />

CIRCULATOR<br />

Jumper Placement:<br />

The jumper is factory installed between terminals H<br />

and 3 to switch power on terminals 4 n/o and 4 n/c.<br />

External Diagnostics:<br />

The External lights show full functionality of the<br />

switching relay. The green light should always be on,<br />

indicating that power is connected. When the thermostat<br />

calls for heat, both the appropriate circulator<br />

and red indicating light is energized.<br />

The <strong>Taco</strong> Connection:<br />

Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />

Priority Zoning Circulators, Thermostats, and the “00”<br />

family of circulators with the advanced features of the<br />

<strong>Taco</strong> Zone Controls to achieve total system integration.<br />

No matter the application, <strong>Taco</strong> now provides<br />

the products to maximize system performance while<br />

simplifying both installation and service.<br />

Note: When using Alternative Wiring diagram, the boiler operating control’s<br />

ZC terminal will see the load of the circulator(s).<br />

Warning: When using Alternative Wiring diagram, wiring instructions<br />

must be followed so power originates from the boiler aquastat. Failure to<br />

follow these wiring instructions may result in a secondary source of power<br />

being connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Terminal Description:<br />

T & T Thermostat Connection<br />

COM Common side of transformer, to power some setback thermostats<br />

N Neutral wire of power input<br />

H Hot wire of power input<br />

3 Common terminal for 4 n/o and 4 n/c<br />

4 n/o Normally open terminal<br />

4 n/c Normally closed terminal<br />

6 n/c Normally closed terminal<br />

6 n/o Normally open terminal<br />

5 Common terminal for 6 n/o and 6 n/c<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR501 1 Zone 120 VAC Input 7.2 amps 4 1/4" 5 1/4" 2 3/4"<br />

All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single<br />

phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />

Warning: Wiring connections must be made in accordance with all applicable electrical<br />

codes and these instructions. Use copper wire only. Failure to follow this<br />

instruction can result in personal injury or death and/or property damage. 10-18<br />

gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22<br />

gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />

wire for 24 VAC source with 5 in.lbs. max torque.<br />

TACO SR501 REPLACEMNENT CROSS-REFERENCE<br />

MANUFACTURER MODEL CONNECTIONS<br />

<strong>Taco</strong> SR501 H N 3 4 NO 4 NC 5 6 NO 6 NC R/T W/T C<br />

Argo AR821 1 2 3 4 5 6 T<br />

AR822 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />

Colombus MR10 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />

Erie SR100 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />

Honeywell RA89A 1 2 3 4 T T<br />

RA832A 1 2 3 4 X X T T<br />

R845A 1 2 3 4 5 6 T T<br />

White-Rogers 889-189 1 2 3 4 T T<br />

829-845 1 2 3 4 5 6 T T<br />

Do it Once. Do it Right. ®<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.<br />

87


Instruction Sheet<br />

SR501-845RP Universal Replacement Relay<br />

Features:<br />

Universal Replaceability<br />

Indicator Lights<br />

Snap-in PC Board to Existing Enclosure<br />

Simplified Wiring<br />

Fully Enclosed Snap-Out Relay<br />

100% Factory Tested<br />

Universal Thermostat Compatibility<br />

UL Approved<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Operation:<br />

Connect a thermostat to the “T T” terminals on<br />

the switching relay. When the thermostat calls for<br />

heat, the relay is energized and power is given to<br />

the circulator.<br />

Power Input:<br />

Connect 120 volt ac power to terminals L1 and L2.<br />

Typical<br />

Wiring<br />

REPLACES HONEYWELL<br />

R845, RA89A & RA832<br />

OR COMPARABLE RELAY<br />

TO: 120 VAC POWER<br />

JUMPER<br />

R W<br />

T T<br />

UNIVERSAL REPLACEMENT RELAY<br />

MODEL: SR501-845RP<br />

120 VAC<br />

INPUT<br />

L2 L1 3 4 5 6<br />

CIRCULATOR<br />

THERMOSTAT<br />

POWER<br />

T STAT<br />

TO: TT ON BOILER<br />

Alternative<br />

Wiring<br />

REPLACES HONEYWELL<br />

R845, RA89A & RA832<br />

OR COMPARABLE RELAY<br />

TO: ZC<br />

TO: ZR<br />

TO: 120 VAC POWER<br />

120 VAC<br />

INPUT<br />

R W<br />

T T<br />

UNIVERSAL REPLACEMENT RELAY<br />

MODEL: SR501-845RP<br />

L2 L1 3 4 5 6<br />

THERMOSTAT<br />

POWER<br />

T STAT<br />

CIRCULATOR<br />

Jumper Placement:<br />

The jumper is factory installed between terminals<br />

L1 and 3 to switch power on terminal 4.<br />

Diagnostics:<br />

The Indicator lights show full functionality of the<br />

switching relay. The green light should always be<br />

on, indicating that power is connected. When the<br />

thermostat calls for heat, both the appropriate circulator<br />

and red indicating light is energized.<br />

The <strong>Taco</strong> Connection:<br />

Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />

Priority Zoning Circulators, Thermostats, and the<br />

“00” family of circulators with the advanced features<br />

of the <strong>Taco</strong> Zone Controls to achieve total system<br />

integration. No matter the application, <strong>Taco</strong> now provides<br />

the products to maximize system performance<br />

while simplifying both installation and service.<br />

Terminal Description:<br />

T & T Thermostat Connection<br />

L2 Neutral wire of power input<br />

L1 Hot wire of power input<br />

3 Common terminal for 4<br />

4 Normally open terminal<br />

6 Normally open terminal<br />

5 Common terminal for 6<br />

Note: When using Alternative Wiring diagram, the boiler operating control’s<br />

ZC terminal will see the load of the circulator(s).<br />

Warning: When using Alternative Wiring diagram, wiring instructions must<br />

be followed so power originates from the boiler aquastat. Failure to follow<br />

these wiring instructions may result in a secondary source of power being<br />

connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR501-845RP 1 Zone 120 VAC Input 7.2 amps 4 1/4" 5 1/4" 2 3/4"<br />

All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single phase<br />

motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />

TACO SR501-845RP REPLACEMENT CROSS-REFERENCE<br />

MANUFACTURER MODEL CONNECTIONS<br />

<strong>Taco</strong> SR501-845RP L1 L2 3 4 5 6 R/T W/T<br />

Argo AR821 1 2 3 4 5 6 T<br />

AR822 L1 L2 3 4 NO 5 6 NO R/T G/T<br />

Colombus MR10 L1 L2 3 4 NO 5 6 NO R/T G/T<br />

Erie SR100 L1 L2 3 4 NO 5 6 NO R/T G/T<br />

Honeywell RA89A 1 2 3 4 T T<br />

RA832A 1 2 3 4 X X T T<br />

R845A 1 2 3 4 5 6 T T<br />

White-Rogers 889-189 1 2 3 4 T T<br />

829-845 1 2 3 4 5 6 T T<br />

Warning: Wiring connections must be made in accordance with all applicable electrical<br />

codes and these instructions. Use copper wire only. Failure to follow this<br />

instruction can result in personal injury or death and/or property damage. 10-18<br />

gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22<br />

gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />

wire for 24 VAC source with 5 in.lbs. max torque.<br />

88<br />

Do it Once. Do it Right. ®<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.


Instruction Sheet<br />

SR502 & SR503 Switching Relay<br />

Cold Start Boiler<br />

Application<br />

THERMOSTATS<br />

Tankless Coil Boiler<br />

Application<br />

THERMOSTATS<br />

24 VAC<br />

POWER<br />

24 VAC<br />

POWER<br />

SR 503<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

SR 503<br />

FUSE 1 AMP<br />

N P ZC H<br />

JUMPERS<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

X 2<br />

X 1 ZR <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

X<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

THREE <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

FUSE 1 AMP<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

2<br />

N P ZC H X 1 ZR <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />

JUMPERS<br />

TO: 120 VAC POWER (NEUTRAL)<br />

TO: 120 VAC POWER (NEUTRAL)<br />

TO: 120 VAC POWER (HOT)<br />

TO: "TT" ON AQUASTAT CONTROL<br />

120 VOLT<br />

CIRCULATORS<br />

TO: 120 VAC POWER (HOT)<br />

TO: "ZC" ON AQUASTAT CONTROL<br />

120 VOLT<br />

CIRCULATORS<br />

TO: "TT" ON AQUASTAT CONTROL<br />

TO: "ZR" ON AQUASTAT CONTROL<br />

Note: When using Alternative Wiring diagram, the boiler operating control’s ZC terminal will see the load of the circulator(s).<br />

Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />

follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Operation: When the thermostat calls for heat, the appropriate circulator<br />

is energized and the isolated end switch (X 1 and X 2 ) will start the<br />

boiler.<br />

Jumper Placement: The jumper should be placed between terminals<br />

ZC and H. Connect the isolated end switch, X 1 and X 2 to the boiler<br />

aquastat control. For zone 1 priority, remove jumper between<br />

terminals P and ZC.<br />

Power Input: Connect 120 volt ac power input to terminals N and H.<br />

Neutral wire to terminal N. Hot wire to terminal H.<br />

Operation: When any thermostat calls for heat, the boiler and appropriate<br />

circulator are energized when the boiler temperature is above the<br />

set low limit.<br />

Jumper Placement: A jumper should be placed between terminals ZC<br />

and X 1 . Connect terminal ZC to ZC terminal on the aquastat control.<br />

Connect terminal ZR to ZR terminal on the aquastat control. Confirm<br />

polarity is consistent between boiler aquastat and switching relay. For<br />

zone 1 priority, remove jumper between terminals<br />

P and ZC.<br />

Power Input: Connect 120 volt ac power input to terminals N and H.<br />

Neutral wire to terminal N. Hot wire to terminal H.<br />

The <strong>Taco</strong> Connection:<br />

Combine the reliability of the <strong>Taco</strong> Zone Valves, Priority Zoning<br />

Circulators, Thermostats, and the “00” family of circulators with the<br />

advanced features of the <strong>Taco</strong> Zone Controls to achieve total system<br />

integration. No matter the application, <strong>Taco</strong> now provides the products<br />

to maximize system performance while simplifying both installation<br />

and service.<br />

External Diagnostics:<br />

Externally visible lights show full functionality of the switching relay.<br />

The green light should always be on, indicating that power is connected.<br />

When the thermostat calls for heat, both the appropriate circulator<br />

and red indicating light is energized.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR502 2 with Priority 120 VAC Input 15 amps 10 1/4" 6 3/4" 2 3/4"<br />

SR503 3 with Priority 120 VAC Input 15 amps 10 1/4" 6 3/4" 2 3/4"<br />

All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />

motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />

Do it Once. Do it Right. ®<br />

Features:<br />

External Indicator Lights<br />

Priority<br />

Simplified Wiring<br />

Fully Enclosed Snap-Out Relays<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Contractor Friendly PC Board Layout<br />

Universal Thermostat Compatibility<br />

UL Approved<br />

24 volt Power Input or Output Terminal<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes and these<br />

instructions. Use copper wire only. Failure to follow this instruction can result in personal injury or<br />

death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs.<br />

max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />

wire for 24 VAC source with 5 in.lbs. max torque.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.<br />

89


Instruction Sheet<br />

SR504 & SR506 Switching Relay<br />

Cold Start Boiler<br />

Application<br />

THERMOSTATS<br />

Tankless Coil Boiler<br />

Application<br />

THERMOSTATS<br />

24 VAC<br />

POWER<br />

SR 506<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

ZC ZR<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6 POWER<br />

120 VOLT CIRCULATORS INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

24 VAC<br />

POWER<br />

SR 506<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

POWER<br />

INPUT<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

FUSE 1 AMP<br />

TO: "ZR" ON AQUASTAT<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC INPUT<br />

TO: "ZC" ON AQUASTAT<br />

JUMPER<br />

120 VAC INPUT<br />

Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />

follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Operation: When any thermostat calls for heat, the appropriate circulator<br />

is energized and the isolated end switch (X and X) will start the<br />

boiler.<br />

Priority Operation: When zone 6 is switched to the priority setting<br />

and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />

When zone 6 is not switched to priority, all zones will operate<br />

independently.<br />

Jumper Placement: The jumper should be placed between terminals<br />

ZC and ZR. Connect the isolated end switch to the aquastat control on<br />

the boiler.<br />

Power Input: Connect 120 volt ac power input to terminals N and H.<br />

Neutral wire to terminal N. Hot wire to terminal H.<br />

Operation: When any thermostat calls for heat, the boiler and appropriate<br />

circulator are energized when the boiler temperature is above the<br />

set low limit.<br />

Priority Operation: When zone 6 is switched to the priority setting<br />

and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />

When zone 6 is not switched to priority, all zones will operate<br />

independently.<br />

Jumper Placement: MOVE the jumper between terminals ZC and ZR<br />

to end switch X and ZC. Connect terminal ZC to ZC terminal on the<br />

aquastat control. Connect the other end switch X to ZR terminal on the<br />

aquastat control. Confirm polarity is consistent between boiler aquastat<br />

and switching relay.<br />

Power Input: Connect 120 volt ac power input to terminals N and H.<br />

Neutral wire to terminal N. Hot wire to terminal H.<br />

The <strong>Taco</strong> Connection:<br />

Combine the reliability of the <strong>Taco</strong> Zone Valves, Priority Zoning<br />

Circulators, Thermostats, and the “00” family of circulators with the<br />

advanced features of the <strong>Taco</strong> Zone Controls to achieve total system<br />

integration. No matter the application, <strong>Taco</strong> now provides the products<br />

to maximize system performance while simplifying both installation<br />

and service.<br />

External Diagnostics:<br />

Externally visible lights show full functionality of the switching relay.<br />

The green light should always be on, indicating that power is connected.<br />

When the thermostat calls for heat, both the appropriate circulator and<br />

red indicating light is energized.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR504 4 with Priority 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />

SR506 6 with Priority 120 VAC Input 20 amps 11 3/4" 7 1/2" 3"<br />

All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />

motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />

Do it Once. Do it Right. ®<br />

Visit our web site at: http://www.taco-hvac.com<br />

90<br />

Features:<br />

External Indicator Lights<br />

Switchable Priority<br />

Simplified Wiring<br />

Fully Enclosed Snap-Out Relays<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Contractor Friendly PC Board Layout<br />

Universal Thermostat Compatibility<br />

UL Approved<br />

24 volt Power Input or Output Terminal<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes<br />

and these instructions. Use copper wire only. Failure to follow this instruction can result in personal<br />

injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections<br />

with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs.<br />

max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.


Instruction Sheet<br />

SR501-EXP Switching Relay<br />

Cold Start Boiler<br />

Application<br />

TO: "TT" on Boiler Aquastat<br />

THERMOSTAT<br />

T<br />

TO: DHW Aquastat if PC700<br />

Boiler Reset is installed.<br />

Tankless Coil Boiler<br />

Application<br />

THERMOSTAT<br />

T<br />

TO: DHW Aquastat if PC700<br />

Boiler Reset is installed.<br />

POWER<br />

<strong>CONTROLS</strong><br />

POWER<br />

<strong>CONTROLS</strong><br />

MODE<br />

MODE<br />

END<br />

RESET<br />

END<br />

RESET<br />

EXPANSION THERMOSTAT<br />

EXPANSION THERMOSTAT<br />

SWITCH<br />

OVERRIDE RESET<br />

SWITCH<br />

OVERRIDE RESET<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

X X 1 2 3 4 T/R T/W COM 1 2<br />

FUSE<br />

K1-A<br />

FUSE<br />

K1-A<br />

MASTER<br />

1 AMP NORMAL<br />

1 AMP MASTER<br />

NORMAL<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

K1<br />

K2<br />

POWER<br />

T STAT<br />

SLAVE<br />

FUSE<br />

5 AMP<br />

K1<br />

K2<br />

POWER<br />

T STAT<br />

SR 501-EXP<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

K1-B K2-A K2-A<br />

120VAC CIRC<br />

OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

SR 501-EXP<br />

N<br />

POWER<br />

INPUT<br />

H ZC ZR H H<br />

120VAC<br />

INPUT<br />

K1-B K2-A K2-A<br />

120VAC CIRC<br />

OUTPUT OUTPUT<br />

PRIORITY<br />

OUTPUT<br />

JUMPER<br />

TO: ZC on Boiler Control<br />

TO: 120 VAC POWER<br />

CIRCULATOR<br />

TO: ZR on Boiler Control<br />

TO: 120 VAC POWER<br />

CIRCULATOR<br />

Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />

follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Operation: When the thermostat calls for heat, the appropriate circulator is energized<br />

and the isolated end switch (X and X) will start the boiler. Priority Output<br />

has power all the time, except when the thermostat is calling.<br />

Mode Operation: When the mode switch is set to NORMAL, the end switch<br />

relay will be energized if any zone is in operation. When the switch is set to<br />

RESET, the end switch relay will only be energized through the operation of a<br />

plug-in reset control or closure of Priority Input.<br />

Jumper Placement: The jumper should be placed between terminals ZC and H.<br />

Connect the isolated end switch to the aquastat control on the boiler.<br />

Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />

wire to terminal N. Hot wire to terminal H.<br />

Expansion Connections: Set the expansion switch to MASTER on the switching<br />

relay that has the designated priority zone or is utilizing the PowerPort options.<br />

Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />

gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />

1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />

using any combination of -EXP controls.<br />

Operation: When the thermostat calls for heat, the appropriate circulator is energized<br />

when the boiler’s aquastat is above the set low limit. The ZR (120VAC) output<br />

will signal the boiler to start. Priority Output has power all the time, except<br />

when the thermostat is calling.<br />

Mode Operation: When the mode switch is set to NORMAL, the end switch<br />

relay will be energized if any zone is in operation. When the switch is set to<br />

RESET, the end switch relay will only be energized through the operation of a<br />

plug-in reset control or closure of Priority Input.<br />

Jumper Placement: REMOVE the jumper between terminals ZC and H. Connect<br />

terminal ZC to ZC terminal on the aquastat control. Connect terminal ZR to ZR<br />

terminal on the aquastat control. Confirm polarity is consistent between boiler<br />

aquastat and switching relay.<br />

Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />

wire to terminal N. Hot wire to terminal H.<br />

Expansion Connections: Set the expansion switch to MASTER on the switching<br />

relay that has the designated priority zone or is utilizing the PowerPort options.<br />

Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />

gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />

1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />

using any combination of -EXP controls.<br />

Features: External Indicator Lights<br />

Ideal for Retrofitting<br />

Priority Output<br />

Simplified Wiring<br />

Add-On Power Controls<br />

Sealed Relays<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Expandable to 20 Zones<br />

Contractor Friendly PC Board<br />

Layout<br />

Universal Thermostat<br />

Compatibility<br />

UL Approved<br />

24 volt Power Input or Output<br />

Terminal<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

External Diagnostics: Externally visible lights show full functionality of the<br />

switching relay. The green light should always be on, indicating that power is<br />

connected. When the thermostat calls for heat, both the appropriate circulator<br />

and red indicating light are energized.<br />

Specifications:<br />

PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S <strong>CONTROLS</strong> VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR501-EXP 1 1 120 VAC Input 5.0 amps 4 1/4" 5 1/4" 2 3/4"<br />

All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a<br />

single phase motor rating per zone of 1/3 hp (5.0A) @ 120 VAC.<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only with a minimum temperature rating of 60/75°C. Failure to follow this instruction can<br />

result in personal injury or death and/or property damage. 12-18 gauge wire recommended for 120 VAC connections, 14-22 gauge wire for thermostat connections, and 14-22 gauge wire for 24 VAC source<br />

connections.<br />

Do it Once. Do it Right. ®<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.<br />

91


Instruction Sheet<br />

SR503-EXP, SR504-EXP & SR506-EXP Switching Relay<br />

Cold Start Boiler<br />

Application<br />

THERMOSTATS<br />

Tankless Coil Boiler<br />

Application<br />

THERMOSTATS<br />

EXPANSION<br />

CONNECTIONS<br />

EXPANSION<br />

CONNECTIONS<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

SLAVE<br />

1234<br />

MASTER<br />

PLUG-IN CARDS<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

POWER<br />

CONTROL<br />

INTERFACE<br />

SLAVE<br />

1234<br />

MASTER<br />

PLUG-IN CARDS<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

<strong>ZONE</strong> 6<br />

PRIORITY<br />

ON<br />

OFF<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

RESET<br />

NORMAL<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

SR 506-EXP<br />

POWER<br />

INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

24 VAC<br />

POWER<br />

120V RELAY<br />

X X<br />

END<br />

SWITCH<br />

RESET<br />

NORMAL<br />

SIX <strong>ZONE</strong> SWITCHING RELAY<br />

WITH OPTIONAL PRIORITY<br />

SR 506-EXP<br />

<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6 POWER<br />

ZC ZR<br />

120 VOLT CIRCULATORS<br />

INPUT<br />

POWER<br />

<strong>ZONE</strong> 1<br />

<strong>ZONE</strong> 2<br />

<strong>ZONE</strong> 3<br />

<strong>ZONE</strong> 4<br />

<strong>ZONE</strong> 5<br />

<strong>ZONE</strong> 6<br />

FUSE 1 AMP<br />

FUSE 1 AMP<br />

TO: "TT" ON BOILER<br />

JUMPER<br />

120 VAC INPUT<br />

TO: "ZR" ON AQUASTAT<br />

TO: "ZC" ON AQUASTAT<br />

JUMPER<br />

120 VAC INPUT<br />

Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />

follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />

causing injury or death.<br />

Operation: When any thermostat calls for heat, the appropriate circulator is<br />

energized and the isolated end switch (X and X) will start the boiler.<br />

Priority Operation: When zone 6 is switched to the priority setting and is actuated,<br />

all other zones will stop operation until zone 6 is satisfied. When zone 6 is<br />

not switched to priority, all zones will operate independently.<br />

Mode Operation: When the mode switch is set to NORMAL, the end switch<br />

relay will be energized if any zone is in operation. When the switch is set to<br />

RESET, the end switch relay will only be energized if priority zone is in operation,<br />

or through the operation of a plug-in reset control.<br />

Jumper Placement: The jumper should be placed between terminals ZC and ZR.<br />

Connect the isolated end switch to the aquastat control on the boiler.<br />

Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />

wire to terminal N. Hot wire to terminal H.<br />

Expansion Connections: Set the expansion switch to MASTER on the switching<br />

relay that has the designated priority zone or is utilizing the PowerPort options.<br />

Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />

gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />

1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />

using any combination of -EXP controls.<br />

Operation: When any thermostat calls for heat, the boiler and appropriate circulator<br />

are energized when the boiler temperature is above the set low limit.<br />

Priority Operation: When zone 6 is switched to the priority setting and is actuated,<br />

all other zones will stop operation until zone 6 is satisfied. When zone 6 is<br />

not switched to priority, all zones will operate independently.<br />

Mode Operation: When the mode switch is set to NORMAL, the end switch<br />

relay will be energized if any zone is in operation. When the switch is set to<br />

RESET, the end switch relay will only be energized if priority zone is in operation,<br />

or through the operation of a plug-in reset control.<br />

Jumper Placement: MOVE the jumper between terminals ZC and ZR to end<br />

switch X and ZC. Connect terminal ZC to ZC terminal on the aquastat control.<br />

Connect the other end switch X to ZR terminal on the aquastat control. Confirm<br />

polarity is consistent between boiler aquastat and switching relay.<br />

Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />

wire to terminal N. Hot wire to terminal H.<br />

Expansion Connections: Set the expansion switch to MASTER on the switching<br />

relay that has the designated priority zone or is utilizing the PowerPort options.<br />

Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />

gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />

1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />

using any combination of -EXP controls.<br />

Features: External Indicator<br />

Lights<br />

Plug-In PowerPort Cards<br />

Switchable Priority<br />

Simplified Wiring<br />

Add-On Power Controls<br />

Fully Enclosed Snap-Out<br />

Relays<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Expandable to 20 Zones<br />

Contractor Friendly PC Board<br />

Layout<br />

Universal Thermostat<br />

Compatibility<br />

UL Approved<br />

24 volt Power Input or Output<br />

Terminal<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

External Diagnostics: Externally visible lights show full functionality of the<br />

switching relay. The green light should always be on, indicating that power is<br />

connected. When the thermostat calls for heat, both the appropriate circulator<br />

and red indicating light is energized.<br />

Specifications:<br />

PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S PORTS VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />

SR503-EXP 3 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />

SR504-EXP 4 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />

SR506-EXP 6 with Priority 3 120 VAC Input 20 amps 11 3/4" 7 1/2" 3"<br />

All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />

motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes and these instructions. Use copper wire only. Failure to follow this instruction can result in personal injury or<br />

death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire<br />

for 24 VAC source with 5 in.lbs. max torque.<br />

92<br />

Do it Once. Do it Right. ®<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2005<br />

TACO, Inc.


Instruction Sheet<br />

ZVC403 & ZVC405 Zone Valve Control<br />

Wiring<br />

Diagram<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

24 VAC<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

Installation of<br />

Optional System<br />

Circulator<br />

END<br />

SWITCH<br />

N/O COM N/C<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

24 VAC<br />

T<br />

T<br />

END<br />

SWITCH<br />

TO CIRCULATOR<br />

OR BOILER<br />

AQUASTAT RELAY<br />

POWER IN<br />

N/O COM N/C<br />

DRY<br />

CONTACTS<br />

FUSE (5 AMP MAX)<br />

T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

ZVC 405<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

JUMPER<br />

3 & 4<br />

FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

1<br />

2<br />

3<br />

MOTOR END<br />

SWITCH<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

POWER<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

T<br />

T<br />

BOILER<br />

120 VAC<br />

HOT<br />

NEUTRAL<br />

Operation/External Diagnostics: When any thermostat<br />

calls for heat, the appropriate zone valve is energized and<br />

the yellow light goes on. When the zone valve is fully<br />

open, the red light goes on and energizes the end switch<br />

relay. The green light should always be on, indicating that<br />

power is connected.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />

ZVC403 3 Zone 120 VAC Input 40 VA 10 1 ⁄ 4" 6 3 ⁄ 4" 2 3 ⁄ 4"<br />

ZVC405 5 Zone 120 VAC Input 80 VA 11 3 ⁄ 4" 7 1 ⁄ 2" 3"<br />

All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of<br />

1 ⁄ 6 hp (5A) @ 120 VAC.<br />

The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong><br />

Zone Valves, Priority Zoning Circulators, Thermostats, and<br />

the “00” family of circulators with the advanced features of<br />

the <strong>Taco</strong> Zone Controls to achieve total system integration.<br />

No matter the application, <strong>Taco</strong> now provides the<br />

products to maximize system performance while simplifying<br />

both installation and service.<br />

Warning: Wiring connections must be made in accordance with all applicable<br />

electrical codes. Use copper wire only. Failure to follow this instruction can result<br />

in personal injury or death and/or property damage. 10-18 gauge wire recommended<br />

for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for<br />

thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24<br />

VAC source with 5 in.lbs. max torque.<br />

Do it Once. Do it Right.<br />

Features:<br />

External Indicator<br />

Lights<br />

Simplified Wiring<br />

Works with 2, 3, or 4-<br />

Wire Zone Valves<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Extra Set of Dry Contacts<br />

Contractor Friendly PC<br />

Board Layout<br />

Universal Thermostat<br />

Compatibility<br />

UL Approved<br />

Sturdy Screw Connections<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.<br />

93


Instruction Sheet<br />

ZVC404 & ZVC406 Zone Valve Control<br />

Wiring<br />

Diagram<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

INDIRECT<br />

WATER HEATER<br />

AQUASTAT<br />

OR THERMOSTAT<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

Installation of<br />

Optional System<br />

and/or DHW Circulator<br />

24 VAC<br />

24 VAC<br />

MAIN<br />

END<br />

SWITCH<br />

POWER IN<br />

EXTRA<br />

END<br />

SWITCH<br />

MODE<br />

NORMAL RESET<br />

FUSE (7 AMP MAX)<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

24 VAC<br />

<strong>ZONE</strong> 6 PRIORITY<br />

OFF<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

ZVC 406<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER<br />

MAIN<br />

END<br />

SWITCH<br />

EXTRA<br />

END<br />

SWITCH<br />

N/O COM N/C<br />

T<br />

T<br />

TO CIRCULATOR<br />

OR BOILER<br />

AQUASTAT RELAY<br />

DRY<br />

CONTACTS<br />

JUMPER<br />

3 & 4<br />

1<br />

2<br />

3<br />

MOTOR<br />

END<br />

SWITCH<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

SEE NOTE<br />

T<br />

T<br />

BOILER<br />

SYSTEM CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

DHW CIRCULATOR (See Note)<br />

120 VAC<br />

NEUTRAL<br />

HOT<br />

Operation/External Diagnostics: When any thermostat<br />

calls for heat, the appropriate zone valve is energized and the<br />

yellow light goes on. When the zone valve is fully open, the<br />

red light goes on and energizes the end switch relay. The green<br />

light should always be on, indicating that power is connected.<br />

Priority Operation: When zone 6 is switched to the priority<br />

setting and is actuated, all other zones will stop operation until<br />

zone 6 is satisfied. When zone 6 is not switched to priority, all<br />

zones will operate independently. Note: When a circulator is<br />

used on the priority zone instead of a zone valve, jumper 3 and<br />

4 of the priority zone.<br />

Mode Operation: When the mode switch is set to NORMAL,<br />

the end switch relay will be energized if any zone is in operation.<br />

When the switch is set to RESET, the end switch relay<br />

will only be energized if priority zone is in operation.<br />

The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong><br />

Zone Valves, Priority Zoning Circulators, Thermostats, and the<br />

“00” family of circulators with the advanced features of the<br />

<strong>Taco</strong> Zone Controls to achieve total system integration. No<br />

matter the application, <strong>Taco</strong> now provides the products to<br />

maximize system performance while simplifying both installation<br />

and service.<br />

94<br />

Do it Once. Do it Right.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />

ZVC404 4 with Priority 120 VAC Input 40 VA 10 1 ⁄ 4" 6 3 ⁄ 4" 2 3 ⁄ 4"<br />

ZVC406 6 with Priority 120 VAC Input 80 VA 11 3 ⁄ 4" 7 1 ⁄ 2" 3"<br />

All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of<br />

1 ⁄ 6 hp (5A) @ 120 VAC.<br />

Features: External Indicator Lights<br />

Switchable Priority<br />

Simplified Wiring<br />

Works with 2, 3, or 4-Wire Zone Valves<br />

Compact Design<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Extra Set of Dry Contacts<br />

Contractor Friendly PC Board Layout<br />

Universal Thermostat Compatibility<br />

UL Approved<br />

Sturdy Screw Connections<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper<br />

wire only. Failure to follow this instruction can result in personal injury or death and/or property damage.<br />

10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for<br />

thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs.<br />

max torque.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.


Instruction Sheet<br />

ZVC404-EXP & ZVC406-EXP Zone Valve Control<br />

Wiring<br />

Diagram<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

WHITE<br />

120 VAC<br />

INPUT<br />

BLACK<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

FACTORY<br />

INSTALLED<br />

TRANSFORMER<br />

Installation of<br />

Optional System<br />

and/or DHW Circulator<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

N/O COM N/C<br />

24 VAC<br />

24 VAC<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

TACO, INC ZVC406-EXP<br />

POWER IN<br />

POWER<br />

<strong>CONTROLS</strong><br />

RESET<br />

END<br />

SWITCH<br />

B<br />

PUMP<br />

TO CIRCULATOR<br />

OR BOILER<br />

AQUASTAT RELAY<br />

SLAVE 1 2 3 4<br />

EXPANSION<br />

MASTER<br />

MODE<br />

NORMAL<br />

N/O COM N/C<br />

<strong>ZONE</strong> 6 RELAY<br />

DRY<br />

CONTACTS<br />

END<br />

SWITCH<br />

A<br />

BOILER<br />

TO CIRCULATOR<br />

OR BOILER<br />

AQUASTAT RELAY<br />

PLUG-IN<br />

<strong>ZONE</strong> 6<br />

CARDS PRIORITY<br />

ON<br />

T T T T T T T T T T T T<br />

<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />

OFF<br />

FUSE 7 AMP MAX<br />

<strong>ZONE</strong> 1<br />

1 2 3 4<br />

THERMOSTAT THERMOSTAT THERMOSTAT<br />

JUMPER<br />

3 & 4<br />

24 VAC<br />

ZVC 406-EXP<br />

SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTOL<br />

WITH OPTIONAL PRIORITY<br />

<strong>ZONE</strong> 2<br />

1 2 3 4<br />

1<br />

2<br />

3<br />

<strong>ZONE</strong> 3<br />

1 2 3 4<br />

<strong>ZONE</strong> 4<br />

1 2 3 4<br />

<strong>ZONE</strong> 5<br />

1 2 3 4<br />

MOTOR<br />

END<br />

SWITCH<br />

<strong>ZONE</strong> 6<br />

1 2 3 4<br />

JUMPER<br />

3 & 4<br />

PRIORITY<br />

<strong>ZONE</strong><br />

INDIRECT<br />

WATER HEATER<br />

AQUASTAT<br />

OR THERMOSTAT<br />

T STAT 1<br />

VALVE 1<br />

T STAT 2<br />

VALVE 2<br />

T STAT 3<br />

VALVE 3<br />

T STAT 4<br />

VALVE 4<br />

T STAT 5<br />

VALVE 5<br />

T STAT 6<br />

VALVE 6<br />

POWER ON<br />

SEE NOTE<br />

SYSTEM<br />

CIRCULATOR<br />

2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(NO END SWITCH)<br />

TACO<br />

3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />

(POWER OPEN, SELF CLOSING)<br />

DHW<br />

120 VAC<br />

CIRCULATOR<br />

(See Note)<br />

NEUTRAL HOT<br />

T T<br />

BOILER<br />

Operation/External Diagnostics: When any thermostat calls for<br />

heat, the appropriate zone valve is energized and the yellow light goes<br />

on. When the zone valve is fully open, the red light goes on and energizes<br />

the end switch relays. The green light should always be on, indicating<br />

that power is connected.<br />

Priority Operation: When zone 6 is switched to the priority setting<br />

and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />

When zone 6 is not switched to priority, all zones will operate<br />

independently. Note: When a circulator is used on the priority zone<br />

instead of a zone valve, jumper 3 and 4 of the priority zone.<br />

Mode Operation: When the mode switch is set to NORMAL, both end<br />

switch relays will be energized if any zone is in operation. When the<br />

mode switch is set to RESET, the end switch relay “A” will only be energized<br />

when the priority zone is in operation. The end switch relay “B”<br />

will be energized when any zone is in operation<br />

Power Input: Connect 120 volt ac power input to leads on transformer.<br />

Neutral to white wire. Hot to black wire.<br />

Expansion Connections: Set the expansion switch to MASTER on the<br />

zone valve control that has the designated priority zone or is utilizing<br />

the PowerPort options. Set all other daisy chained controls to SLAVE.<br />

Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on<br />

the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s).<br />

Controls may be daisy chained up to 20 zones using any combination<br />

of Switching Relay -EXP or Zone Valve -EXP controls.<br />

The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />

Priority Zoning Circulators, Thermostats, and the “00” family of circulators<br />

with the advanced features of the <strong>Taco</strong> Zone Controls to achieve<br />

total system integration. No matter the application, <strong>Taco</strong> now provides<br />

the products to maximize system performance while simplifying both<br />

installation and service.<br />

Specifications:<br />

PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />

NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />

ZVC404-EXP 4 with Priority 120 VAC Input 80 VA 11 3 ⁄4" 7 1 ⁄2" 3"<br />

ZVC406-EXP 6 with Priority 120 VAC Input 80 VA 11 3 ⁄4" 7 1 ⁄2" 3"<br />

All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone<br />

of 1 ⁄ 6 hp (5A) @ 120 VAC.<br />

Features:<br />

External Indicator Lights<br />

Plug-In PowerPort Cards<br />

Switchable Priority<br />

Simplified Wiring<br />

Add-On Power Controls<br />

Works with 2, 3, or 4-Wire<br />

Zone Valves<br />

UL Approved<br />

Fuse Protected<br />

100% Factory Tested<br />

Isolated End Switch<br />

Expandable to 20 Zones<br />

Extra Set of Dry Contacts<br />

Contractor Friendly PC<br />

Board Layout<br />

Universal Thermostat<br />

Compatibility<br />

Sturdy Screw Connections<br />

Extended 3 Year Warranty<br />

Made in the USA<br />

Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property<br />

damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with<br />

5 in.lbs. max torque.<br />

Do it Once. Do it Right.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.<br />

95


Instruction Sheet<br />

Hydro Air Fan Controls<br />

Operation HAFC101 and 201:<br />

The Hydro Air Fan Control is an interface<br />

between the thermostat and air handler. It<br />

also has an isolated end switch to start the<br />

boiler and/or pump. When the thermostat<br />

calls for heat, the Fan Control energizes the<br />

end switch relay and allows the fan to operate<br />

at low speed when the water is above the<br />

optional aquastat setting. When the thermostat<br />

calls for cooling, the Fan Control energizes<br />

the condenser and operates on high speed.<br />

Additional HAFC201 Operations:<br />

Selectable one, three or four minute delay on<br />

fan operation in heating mode. Selectable<br />

pump exercise activates circulator but does<br />

not enable boiler contacts. Two minutes every<br />

24 hours minimizes the chance of bacteria<br />

build-up in an open loop system. Thirty seconds<br />

every two weeks minimizes seasonal<br />

start-up problems generally associated with<br />

harsh water conditions. Optional aquastat or<br />

thermostat can be connected to Freeze<br />

Protection TT terminals to reduce the chance<br />

of pipes freezing by energizing the pump dry<br />

contacts (boiler contacts not activated.)<br />

Switch Settings (HAFC201):<br />

1 1 minute on fan delay, in heating mode<br />

2 3 minute on fan delay, in heating mode<br />

1&2 4 minute on fan delay, in heating mode<br />

3 Pump dry contact activated for 2 minutes<br />

every 24 hours (boiler contacts not<br />

activated)<br />

4 Pump dry contacts activated for 30 seconds<br />

every two weeks (boiler contacts<br />

not activated)<br />

External Diagnostics:<br />

The external lights show full functionality of<br />

the Hydro Air Fan Control. The green light<br />

should always be on, indicating that power is<br />

connected. Red lights indicate fan operation<br />

for heating and cooling modes.<br />

Warning:<br />

Wiring connections must be made in accordance with<br />

all applicable electrical codes. Use copper wire only.<br />

Failure to follow this instruction can result in personal<br />

injury or death and/or property damage. 10-18 gauge<br />

wire recommended for 120 VAC connections with<br />

9 in.lbs. max torque, 12-22 gauge wire for thermostat<br />

connections with 9 in.lbs. max torque, and 12-22 gauge<br />

wire for 24 VAC source with 5 in.lbs. max torque.<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

THERMOSTAT<br />

C R W Y<br />

1 MIN ON DELAY - FAN<br />

3 MIN ON DELAY - FAN<br />

2 MIN @ 24 HR - PUMP<br />

30 SEC @ 2 WK - PUMP<br />

OFF ON<br />

THERMOSTAT<br />

Hot<br />

Neutral<br />

(or to “T T” on<br />

switching relay)<br />

Circulator<br />

Dry Contacts<br />

To: “T T” on<br />

Boiler or<br />

Switching<br />

Relay<br />

G T<br />

DRY CONTACTS<br />

5 AMP 1/6 HP RATED<br />

PUMP BOILER<br />

Line 24 VAC<br />

T T T<br />

WATER COIL FREEZE PR<br />

AQUASTATS<br />

HAFC201<br />

HYDRO AIR FAN CONTROL<br />

X X XXCRY<br />

To: Optional<br />

Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

AIR HANDLER<br />

G G<br />

Fan<br />

Relay<br />

M<br />

To: Optional Aquastat<br />

or Thermostat to sense<br />

low ambient<br />

temperature<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

Jumper<br />

Outdoor<br />

Condenser<br />

Unit<br />

Optional Power Wire<br />

to Thermostat<br />

that Requires 24VAC<br />

Dry Contacts<br />

To: “T T” on Boiler<br />

or Switching Relay<br />

THERMOSTAT<br />

C R W Y<br />

THERMOSTAT<br />

G T T<br />

AQUASTAT<br />

HAFC101<br />

HYDRO AIR FAN CONTROL<br />

BOILER AIR HANDLER<br />

X X C R Y G G<br />

To: Aquastat on<br />

Return Line of<br />

Hydro Coil<br />

1 Speed Air Handler*<br />

2 Speed Air Handler*<br />

* Both HAFC101 and 201 capable of 1 and 2 speed applications<br />

Terminal Description:<br />

Thermostat:<br />

C Optional: Common side of transformer W White - Heating signal<br />

to power some styles of thermostats Y Yellow - Condenser signal<br />

R Red - Hot side of transformer used to G Green - Fan signal<br />

switch all functions<br />

Water Coil Aquastat:<br />

TT Connect to aquastat at air handler to control operation of the fan when<br />

in the heating mode. Install a jumper if the aquastat is not used<br />

Freeze Protection Aquastat:<br />

TT Connect to aquastat or thermostat to sense low ambient temperature.<br />

Reduces the chance of pipes freezing by energizing the pump dry contacts.<br />

Pump Dry Contacts:<br />

XX May switch pump directly by bringing in external line voltage or connect<br />

to “T T” on a switching relay.<br />

Boiler Dry Contacts:<br />

XX Connect to the boiler or “T T” terminals on a switching relay.<br />

Air Handler:<br />

C Common side of transformer to power the Fan Control<br />

R Red - Hot side of transformer used to switch all functions<br />

Y Yellow - Condenser signal<br />

One Speed Motor:<br />

G low Connect the fan to the relay. Keep the jumper installed between G high and G low.<br />

Two Speed Motor:<br />

G high Remove jumper and connect G high to the high speed fan relay and<br />

connect G low to the low speed fan relay.<br />

Line 24 VAC<br />

Low<br />

High<br />

M<br />

Fan Relays<br />

Power On<br />

Call for Heat<br />

Fan, Cooling<br />

Fan, Heating<br />

Outdoor<br />

Condenser<br />

Unit<br />

Specifications:<br />

** Model number changed from SR501-F<br />

PRODUCT<br />

NUMBER<br />

NUMBER<br />

OF <strong>ZONE</strong>S<br />

POWER INPUT<br />

VOLTAGE<br />

MAXIMUM<br />

COMBINED LOAD<br />

RELAY<br />

TYPE<br />

THERMOSTAT<br />

CURRENT<br />

SINGLE PHAZE MOTOR<br />

RATING (RELAY)<br />

DIMENSIONS OF ENCLOSURE<br />

WIDTH HEIGHT DEPTH<br />

HAFC101** 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC 4 1/4" 5 1/4" 2 3/4"<br />

HAFC201•• 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC 4 1/4" 5 1/4" 2 3/4"<br />

The Hydro Air Fan Controls are relay type DPDT, have a thermostat current of .18 and a single phase motor rating per zone of 1/6 HP (5A) @ 120 VAC.<br />

Do it Once. Do it Right.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

96<br />

Printed in USA<br />

Copyright 1999<br />

TACO, Inc.


Instruction Sheet<br />

PC600 Post Purge Timer Plug-In PowerPort Card<br />

102-094<br />

SUPERSEDES: August 1, 1997 EFFECTIVE: May 1, 2000<br />

Plant ID No. 9300-867<br />

Operation:<br />

Once the priority zone is satisfied, the PC600 maintains power to the circulator, but does not fire the boiler. The circulator purges excess heat into the priority zone,<br />

minimizing standby loss during warm weather months and optimizing boiler operation when used with a boiler reset control. Power can be maintained to the circulator<br />

from a minimum of 10 seconds to a maximum of 420 seconds. The power LED light is energized when the priority zone or the post purge card is in operation.<br />

Installation:<br />

The PC600 can be installed in any one of the PowerPort terminals located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Remove the shunt/jumper between pins 9<br />

& 10 on the PowerPort terminal before installing the PC600. Align the connector on the base of the post purge card with the PowerPort terminal on the Expandable<br />

Control and push until the two mate.<br />

XX Terminals (Optional):<br />

The XX terminals on the post purge card can be wired to TT on the boiler to fire only when the priority zone is calling for heat. If using a boiler with an internal<br />

reset control, wire the XX terminals in parallel with the TT connections of the internal reset control.<br />

Do it Once. Do it Right.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.<br />

Instruction Sheet<br />

PC605 Priority Protection Plug-In PowerPort Card<br />

102-095<br />

SUPERSEDES: MAY 1, 1998 EFFECTIVE: MAY 1, 2000<br />

PLANT ID NO. 9300-1012<br />

Operation:<br />

The PC605 Priority Protection Plug-In Card is a solid state control that helps prevent freeze-ups in the event of a priority zone failure. If the priority zone calls for heat<br />

continuously for more than one hour, power is returned to the space heating (non-priority) zones, allowing all zones to function independently. Once the priority zone is<br />

satisfied, the PC605’s auto-reset is activated and the priority zone is again allowed to have priority for up to one hour the next time it calls. The one hour time frame is<br />

not adjustable. The red LED light is energized only when the Priority Protection Card is operating in priority override mode.<br />

Installation:<br />

The PC605 can be installed in any unoccupied PowerPort terminal located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 &<br />

10 on the Expandable Control unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the<br />

Expandable Control and push until the two mate. The PC605 can be used in conjunction with any other <strong>Taco</strong> PC style PowerPort Cards or Add-on Controls.<br />

Do it Once. Do it Right.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.<br />

Instruction Sheet<br />

PC610 Pump Exercise and Timer Plug-In PowerPort Card<br />

102-096<br />

SUPERSEDES: May 31, 1998 EFFECTIVE: May 1, 2000<br />

Plant ID No. 9300-1025<br />

Operation:<br />

The PC610 Pump Exercise and Timer Plug-In Card is a solid state universal timer designed to cycle all the pumps that are attached to the Expandable Control(s)<br />

at selected time intervals. This minimizes seasonal start-up problems generally associated with harsh water conditions. The control can be configured to reduce<br />

the chance of freeze-ups by cycling the pumps more often during cold weather months. Bacteria can be minimized in heating systems that utilize domestic hot<br />

water heaters as their heat source by systematically circulating the water.<br />

Installation:<br />

The PC610 can be installed in any unoccupied PowerPort terminal located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on<br />

the Expandable Switching Relay unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the<br />

Expandable Switching Relay and push until the two mate. The PC610 can be used in conjunction with any other <strong>Taco</strong> PC style PowerPort Cards or Add-on Controls.<br />

Typical Settings:<br />

Application On Time Off Time<br />

Pump Exercise 30 sec. 2 weeks<br />

Bacteria Minimization 4 min. 12 hours<br />

Freeze Protection 4 min. 1 hour<br />

Do it Once. Do it Right.<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Printed in USA<br />

Copyright 2000<br />

TACO, Inc.<br />

97


Standard Terms and Definitions<br />

Switching Relay: Transformer and relay in one box, which allows a low voltage thermostat to control a line voltage load (circulator),<br />

with an isolated end switch that can energize the boiler.<br />

Zone Valve Control: Transformer and relay in one box, which allows a low voltage thermostat to control a low voltage zone valve, with<br />

an isolated end switch that can energize the boiler and/or circulators.<br />

Dry Contacts: Set of relay contacts that make and beak, where no voltage is present. Usually can switch 24 or 120 VAC.<br />

Isolated End Set Switch: Set of dry contacts that make when a zone calls for heat. Usually connected to a boiler’s aquastat TT.<br />

Mode Switch: Switch set to NORMAL – When any zone calls for heat, the end switch will make and fire the boiler.<br />

Switch set to RESET – When any zone calls for heat, a heat demand signal is given to external add-on reset control and it controls<br />

boiler operation.Also when the priority zone calls for heat and is switched to priority, the end switch will override reset control and<br />

fire boiler to high limit.<br />

TT: Where thermostat or aquastat connects on a heating control.<br />

XX: Denotes Isolated End Switch.<br />

Low Voltage: 24 VAC for most HVAC systems.<br />

Line Voltage: Normally 120 VAC relative to ground.<br />

H or L1: Hot side of line voltage.<br />

N or L2: Neutral side of line voltage.<br />

ZR: 120 VAC (Hot) signal from switching relay to boiler’s operating aquastat to fire the burner to high limit when any zone calls for<br />

heat. Also ideal for controlling primary circulator.<br />

ZC: 120 VAC (Hot) signal from boiler’s operating aquastat to switching relay allowing circulator(s) to run when aquastat is above the<br />

set low limit.<br />

Cold Start: A boiler that fires only when there is a call for heat.<br />

Tankless Coil: A method of heating domestic water utilizing a heat exchanger inside a boiler.The boiler also maintains heat year round<br />

to deliver hot water on demand.<br />

DHW Heater: A method of heating domestic water utilizing a heat exchanger and storage tank.<br />

Transformer: A component for increasing or reducing AC voltage. Rated in VA (volts x amps).<br />

OHMS Law: Example: A 24 volt, 40 VA transformer can produce how much current?<br />

Current = VA / Voltage<br />

40 / 24 = 1.6 Amps<br />

I = E/R where I = Current in Amps<br />

R = E/I<br />

R = Resistance in Ohms<br />

E = I x R<br />

E = Volts<br />

W = E x I<br />

W = Watts or VA<br />

I = W(VA)/E<br />

RELAY CONTACTS:<br />

N/C: Normally closed connection of a relay, when not energized.<br />

N/O: Normally open connection of a relay, when not energized.<br />

Com: The common terminal for normally open and normally closed.<br />

Pole: The number of independent circuits of a switch or relay.<br />

Throw: The number of settings which a switch or relay can have.<br />

3 4 4 6 6 5<br />

COM N/O N/C N/C N/O COM<br />

DPDT = Double Pole Double Throw<br />

98


TACO Zone Controls Cross-Reference<br />

TACO ARGO ERIE HONEYWELL WHITE-ROGERS<br />

SWITCHING RELAYS<br />

1 Zone Switching Relay (DPDT) SR501 AR821 (1), AR822 SR100 RA89A (2), RA845A (1), RA832A (1) 889-189 (2), 829-845 (1)<br />

1 Zone Switching Relay Replacement PC Board (DTSP) SR501-845RP<br />

2 Zone Switching Relay with Priority SR502 AR-861-2 (3) SR201<br />

3 Zone Switching Relay with Priority SR503 AR-861-3 (3) SR301 R8888A1007<br />

4 Zone Switching Relay with Priority SR504 AR-842 SR601 R8888B1005<br />

6 Zone Switching Relay with Priority SR506 AR-866 SR601 (4)<br />

SWITCHING RELAYS<br />

WITH POWERPORT OPTIONS<br />

3 Zone Switching Relay with Priority and 3 Power Ports SR503-EXP ARM-861-DP (5,6),ARM-3P<br />

4 Zone Switching Relay with Priority and 3 Power Ports SR504-EXP ARM-842-DP (5,6),ARM-4P<br />

6 Zone Switching Relay with Priority and 3 Power Ports SR506-EXP ARM-866-DP (5,6),ARM-6P<br />

<strong>ZONE</strong> VALVE <strong>CONTROLS</strong><br />

3 Zone Valve Control ZVC403 (7) AZ-3 R8889A1014<br />

4 Zone Valve Control with Priority ZVC404 (7) AZ-4P R8889B1012<br />

5 Zone Valve Control ZVC405 (7) AZ-5 VL500 (8)<br />

6 Zone Valve Control with Priority ZVC406 (7) AZ-6P VL500 (8)<br />

<strong>ZONE</strong> VALVE <strong>CONTROLS</strong><br />

WITH POWERPORT OPTIONS<br />

4 Zone Valve Control with Priority and 2 Power Ports ZVC404-EXP<br />

6 Zone Valve Control with Priority and 2 Power Ports ZVC406-EXP<br />

PLUG IN POWERPORT CARDS<br />

Post Purge Timer Plug-In Card PC600<br />

Priority Protection Plug-In Card PC605 DPM-1<br />

Universal Timer/Pump Exercize Plug-In Card PC610<br />

99


TACO Zone Controls Cross-Reference (Continued)<br />

100<br />

TACO ARGO ERIE HONEYWELL WHITE-ROGERS<br />

ADD-ON POWER <strong>CONTROLS</strong><br />

Boiler Reset Control PC700 DPM-2 BB1200<br />

2-Stage Boiler Reset Control PC702<br />

Variable Speed Pump Injection Mixing Control PC705 BB3000<br />

FAN <strong>CONTROLS</strong><br />

1 Zone Hydro Air Fan Control (1 or 2 Speed) HAFC101 ARH-1,ARH-2,ARH-3 WA300<br />

1 Zone Hydro Air Fan Control with Time Delays (1 or 2 Speed) HAFC201<br />

REPLACEMENT PARTS<br />

24 Volt Replacement Relay SR024-001RP R-35 EXP10<br />

120 Volt Replacement Relay SR120-001RP R-49<br />

NOTES:<br />

1. Does not have both normally open and normally closed contacts.<br />

2. Has only one set of normally open contacts (SPST).<br />

3. Does not have optional priority.<br />

4. Can be expanded to five and six zones with the addition of EXP10 relays.<br />

5. Argo ARM units are expandable to 10 zones using special controls (ARM-1,ARM-4) with a phone jack.<br />

TACO switching relays can be expanded up to 20 zones using any combination of -EXP models with no special connections.<br />

6. Includes only one data port for adding data port modules.<br />

7. All TACO zone valve controls include an extra set of dry contacts (N/O, Common, N/C).<br />

8. VL500 is only 5 zones, 4 normal and 1 priority.


<strong>CONTROLS</strong> MADE EASY. ®<br />

TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />

TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.<br />

Visit our web site at: http://www.taco-hvac.com<br />

Printed in USA<br />