TACO <strong>ZONE</strong> <strong>CONTROLS</strong> WIRING <strong>GUIDE</strong><br />
Pages<br />
Switching Relays – Single Zone Wiring 2 – 2<br />
Switching Relays – Oil Boiler Wiring Safety Notice 2 3 – 4<br />
Switching Relays – NON EXP Connected Together with Priority 5 – 11<br />
Switching Relays – EXP Connected Together with Priority 12 – 14<br />
Switching Relays – Multiple Indirect Hot Water Heaters 15 – 16<br />
Switching Relays – EXP Connected To Reset Controls (PC700, 702 & 705) 17 – 28<br />
Zone Valve Controls – NON EXP Connected Together with Priority 29 – 34<br />
Zone Valve Controls – EXP Connected Together with Priority 35 – 38<br />
Zone Valve Controls – Connected To Reset Controls (PC700, 702 & 705) 39 – 46<br />
Hydro Air Fan Controls (HAFC 101 & 201) 47 – 51<br />
Specialty Thermostat and Zone Valve Wiring 52 – 56<br />
Radiant Mixing Block 57 – 58<br />
X-Pump Block 59 – 61<br />
iSeries Mixing Valves 62 – 63<br />
Low Water Cutoffs and Electric Water Feeders 64 – 79<br />
Aquastat Wiring 80 – 86<br />
Instruction Sheets 87 – 97<br />
Standard Terms and Definitions – 98<br />
Cross Reference 99 – 100<br />
Do it once.<br />
Do it right.<br />
© <strong>Taco</strong> Catalog No. 100-9.0 Effective Date: July 1, 2010<br />
Supersedes Date: July 1, 2007
TACO Zone Control Product Information<br />
Switching Relays<br />
Product No.<br />
SR501<br />
SR501-845RP<br />
SR502<br />
SR503<br />
SR504<br />
SR506<br />
Description<br />
1 Zone Switching Relay<br />
1 Zone Switching Relay Replacement PC Board for<br />
Honeywell R845, RA89A, RA832 or Comparable Relay<br />
2 Zone Switching Relay with Priority<br />
3 Zone Switching Relay with Priority<br />
4 Zone Switching Relay with Priority<br />
6 Zone Switching Relay with Priority<br />
Switching Relays with PowerPort Options and Expandable to 20 Zones<br />
Product No.<br />
Description<br />
SR501-EXP<br />
1 Zone Switching Relay<br />
SR503-EXP<br />
3 Zone Switching Relay with Priority and 3 PowerPorts<br />
SR504-EXP<br />
4 Zone Switching Relay with Priority and 3 PowerPorts<br />
SR506-EXP<br />
6 Zone Switching Relay with Priority and 3 PowerPorts<br />
Zone Valve Controls<br />
Product No.<br />
ZVC403<br />
ZVC404<br />
ZVC405<br />
ZVC406<br />
Description<br />
3 Zone Valve Control<br />
4 Zone Valve Control with Priority<br />
5 Zone Valve Control<br />
6 Zone Valve Control with Priority<br />
Zone Valve Controls with PowerPort Options and Expandable to 20 Zones<br />
Product No.<br />
Description<br />
ZVC404-EXP<br />
4 Zone Valve Control with Priority and 2 PowerPorts<br />
ZVC406-EXP<br />
6 Zone Valve Control with Priority and 2 PowerPorts<br />
Plug-In PowerPort Cards (For use with all -EXP controls)<br />
Product No.<br />
Description<br />
PC600<br />
Post Purge Timer Plug-In Card<br />
PC605<br />
Priority Protection Plug-In Card<br />
PC610<br />
Universal Timer/Pump Exercise Plug-In Card<br />
Add-On Power Controls (For use with all -EXP controls)<br />
Product No.<br />
Description<br />
PC700<br />
Boiler Reset Control<br />
PC702<br />
2-Stage Boiler Reset Control<br />
PC705<br />
Variable Speed Pump Injection Mixing Control<br />
Fan Controls<br />
Product No.<br />
HAFC101<br />
HAFC201<br />
Description<br />
Hydro Air Fan Control<br />
Hydro Air Fan Control with Optional Time Delays<br />
Do it once.<br />
Do it right.
SR501 Switching Relay Wiring<br />
ALTERNATIVE WIRING<br />
(TANKLESS COIL)<br />
THERMOST<br />
AT<br />
T<br />
SR501<br />
1 <strong>ZONE</strong><br />
SWITCHING RELAY<br />
24<br />
R W VAC<br />
T T COM<br />
POWER<br />
T STAT<br />
120 VAC<br />
INPUT<br />
N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />
TO: ZC<br />
TO: ZR<br />
TO: 120 VAC POWER<br />
CIRCULATOR<br />
Note: When using Alternative Wiring diagram, the boiler operating<br />
control’s ZC terminal will see the load of the circulator(s).<br />
Warning: When using Alternative Wiring diagram, wiring<br />
instructions must be followed so power originates from the boiler<br />
aquastat. Failure to follow these wiring instructions may result in<br />
a secondary source of power being connected to the boiler that<br />
may activate it under certain circumstances, causing injury or death.<br />
ALTERNATIVE WIRING<br />
(24 VAC POWERED INPUT SIGNAL)<br />
24 VAC<br />
SIGNAL<br />
SR501<br />
1 <strong>ZONE</strong><br />
SWITCHING RELAY<br />
24<br />
R W VAC<br />
T T COM<br />
POWER *<br />
T STAT *<br />
N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />
H<br />
N<br />
TO: TT ON BOILER<br />
TO: 120 VAC POWER<br />
CIRCULATOR<br />
REMOVE JUMPER.<br />
DO NOT CONNECT POWER<br />
TO N AND H TERMINALS.<br />
* T STAT LIGHT WILL GO<br />
ON AND OFF WITH 24 VAC<br />
SIGNAL. POWER LIGHT<br />
WILL ALWAYS BE OFF.<br />
2<br />
TYPICAL WIRING<br />
(COLD START)<br />
AT<br />
THERMOST<br />
T<br />
24<br />
R W VAC<br />
T T COM<br />
SR501<br />
1 <strong>ZONE</strong><br />
SWITCHING RELAY<br />
POWER<br />
T STAT<br />
120 VAC<br />
INPUT<br />
N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />
JUMPER<br />
TO: TT ON BOILER<br />
CIRCULATOR<br />
TO: 120 VAC<br />
POWER
NOTE: No tankless coil priority.<br />
3
(cont.)<br />
(HOT)<br />
L1<br />
L2<br />
(NEUTRAL)<br />
THERMOSTATS<br />
CIRCUIT<br />
BREAKER<br />
CUSTOMER<br />
EMERGENCY<br />
SWITCH<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
THERMOSTAT<br />
L1 L2 T T<br />
HONEYWELL L8124<br />
OR EQUAL<br />
THERMAL<br />
FUSE<br />
(FIROMATIC)<br />
SERVICE<br />
SWITCH<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
B2<br />
C1<br />
C2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
ZR<br />
ZC<br />
B1<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
LOW<br />
WATER<br />
CUTOFF<br />
120 VAC INPUT<br />
NOTE: Tankless coil has priority.<br />
(HOT)<br />
L1<br />
L2<br />
(NEUTRAL)<br />
THERMOSTAT<br />
CIRCUIT<br />
BREAKER<br />
24 VAC<br />
POWER<br />
SR 503<br />
THERMOSTAT<br />
CUSTOMER<br />
EMERGENCY<br />
SWITCH<br />
FUSE 1 AMP<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
POWER<br />
<strong>ZONE</strong> 1<br />
L1 L2 T T<br />
HONEYWELL L8124<br />
OR EQUAL<br />
THERMAL<br />
FUSE<br />
(FIROMATIC)<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
B2<br />
C1<br />
C2<br />
ZR<br />
ZC<br />
B1<br />
SERVICE<br />
SWITCH<br />
N P ZC H<br />
X1<br />
X2<br />
ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
120 VOLT CIRCULATORS<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
LOW<br />
WATER<br />
CUTOFF<br />
120 VAC INPUT<br />
NOTE: The boiler operating control’s ZC terminal will see the load of the circulator(s).<br />
4
SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay<br />
MASTER<br />
AQUASTAT<br />
ON DHW<br />
HEATER<br />
A<br />
T<br />
T<br />
PRIORITY ON<br />
VIA JUMPER<br />
PLACEMENT<br />
24 VAC<br />
POWER<br />
SR 503<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
N P ZC H<br />
JUMPER<br />
X 2<br />
X 1 ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
N<br />
H<br />
120 VAC POWER<br />
DHW<br />
HEATER<br />
CIRCULATOR<br />
120 VOLT<br />
CIRCULATORS<br />
SLAVE<br />
T<br />
T<br />
T<br />
PRIORITY OFF<br />
VIA JUMPER<br />
PLACEMENT<br />
24 VAC<br />
POWER<br />
SR 503<br />
FUSE 1 AMP<br />
N P ZC H<br />
JUMPER<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
X ZR 1<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
X 2<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
POWER<br />
BOILER<br />
120 VOLT CIRCULATORS<br />
TO: "TT" ON AQUASTAT CONTROL<br />
5
SR502/503 Switching Relay Controlling Another SR504/506 Switching Relay<br />
MASTER<br />
AQUASTAT<br />
ON DHW<br />
HEATER<br />
A<br />
T<br />
T<br />
24 VAC<br />
POWER<br />
SR 503<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
FUSE 1 AMP<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
PRIORITY ON<br />
VIA JUMPER<br />
PLACEMENT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
N P ZC H<br />
JUMPERS<br />
X 2<br />
X 1 ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
120 VOLT<br />
CIRCULATORS<br />
24 VAC<br />
POWER<br />
SLAVE<br />
SR 506<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
THERMOSTATS<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
T<br />
POWER<br />
INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
REMOVE<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
TO: "TT" ON BOILER<br />
BOILER<br />
6
Two SR504/506 Switching Relays Connected Together<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
T<br />
T<br />
T<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
ON<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
DHW<br />
HEATER<br />
CIRCULATOR<br />
BOILER<br />
T<br />
T<br />
T<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
ON<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
OUTPUT<br />
NOT<br />
USED<br />
120 VAC INPUT<br />
H<br />
N<br />
7
Priority Zoning Circulator Controlling SR504/506 Switching Relay<br />
MASTER<br />
PRIORITY ZONING CIRCULATOR<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
ON<br />
THERMOSTAT BOILER PRIORITY POWER IN<br />
1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />
A<br />
120 VAC INPUT<br />
AQUASTAT ON<br />
DHW HEATER<br />
THERMOSTATS<br />
SLAVE<br />
T<br />
PRIORITY<br />
OFF<br />
24 VAC<br />
POWER<br />
SR 506<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
REMOVE<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
TO: "TT" ON BOILER<br />
BOILER<br />
8
FUSE 1 AMP<br />
BOILER<br />
Priority Zoning Circulator Controlling 2 SR504/506 Switching Relays<br />
SR 504<br />
T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
T<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
120V RELAY<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
120V RELAY<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
PRIORITY ZONING CIRCULATOR<br />
OFF<br />
PRIORITY<br />
ON<br />
PRIORITY<br />
ON<br />
THERMOSTAT BOILER PRIORITY POWER IN<br />
1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
120 VAC INPUT<br />
T T T T T<br />
PRIORITY<br />
OFF<br />
SLAVE<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
FUSE 1 AMP<br />
REMOVE<br />
REMOVE<br />
JUMPER<br />
JUMPER<br />
TO: "TT" ON BOILER<br />
PRIORITY<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
120 VAC INPUT<br />
H<br />
N<br />
24 VAC<br />
POWER<br />
9
FUSE 1 AMP<br />
BOILER<br />
SR502/503 Switching Relay Controlling 2 SR504/506 Switching Relays<br />
SR 504<br />
T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
T<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
120V RELAY<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
120V RELAY<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T<br />
24 VAC<br />
POWER<br />
SR 503 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
PRIORITY<br />
ON<br />
TWO <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
X 2<br />
N P ZC H X ZR<br />
1<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
JUMPER<br />
T T T T T<br />
PRIORITY<br />
OFF<br />
SLAVE<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
FUSE 1 AMP<br />
REMOVE<br />
REMOVE<br />
JUMPER<br />
JUMPER<br />
TO: "TT" ON BOILER<br />
120 VAC INPUT<br />
PRIORITY<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
H<br />
N<br />
24 VAC<br />
POWER<br />
10
SLAVE<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
BOILER<br />
SR 504<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
REMOVE<br />
JUMPER<br />
TO: "TT" ON BOILER<br />
SR501 Switching Relay Controlling 2 SR504/506 Switching Relays<br />
MASTER<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
SR501<br />
24<br />
R W VAC<br />
T T COM<br />
1 <strong>ZONE</strong> SWITCHING RELAY<br />
POWER<br />
T STAT<br />
N H 3 4 4 6 6<br />
N/O N/C N/C N/O 5<br />
JUMPER<br />
120 VAC INPUT<br />
DHW<br />
CIRCULATOR<br />
T T T T<br />
SLAVE<br />
T T T T<br />
PRIORITY OFF PRIORITY OFF<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
REMOVE<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
H<br />
N<br />
11
SR501-EXP Switching Relay Controlling Another SR504/506 Switching Relay<br />
AQUASTAT ON<br />
DHW HEATER<br />
TO: "TT" ON BOILER<br />
A<br />
TO: OPTIONAL <strong>ZONE</strong> VALVE<br />
OR iSeries MIXING VALVE<br />
MASTER<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET<br />
FUSE<br />
1 AMP<br />
NORMAL<br />
SLAVE<br />
MASTER<br />
END<br />
SWITCH<br />
X<br />
EXPANSION<br />
<strong>ZONE</strong><br />
THERMOSTAT<br />
VALVE<br />
X 1 3 4 T/R T/W COM 1<br />
2 2<br />
SR 501-EXP<br />
FUSE<br />
5 AMP<br />
POWER<br />
T STAT<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
120VAC CIRC<br />
OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
JUMPER<br />
DHW CIRCULATOR<br />
24 VAC<br />
POWER<br />
SLAVE<br />
SR 506<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
THERMOSTATS<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
T<br />
POWER<br />
INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
REMOVE<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
TO: "TT" ON BOILER<br />
BOILER<br />
12
SR501-EXP Switching Relay Controlling a ZVC404/406 Zone Valve Control<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
TO: OPTIONAL <strong>ZONE</strong> VALVE<br />
OR iSeries MIXING VALVE<br />
<strong>ZONE</strong><br />
VALVE<br />
X 1 2 1 2<br />
END<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
X 3 4 T/R T/W COM<br />
SR 501-EXP<br />
POWER<br />
T STAT<br />
FUSE<br />
5 AMP<br />
N H ZC ZR H H<br />
PRIORITY<br />
OUTPUT<br />
CIRC<br />
OUTPUT<br />
120VAC<br />
OUTPUT<br />
120VAC<br />
INPUT<br />
POWER<br />
INPUT<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
T T T<br />
DHW<br />
HEATER<br />
CIRCULATOR<br />
JUMPER<br />
24 VAC<br />
SLAVE<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
POWER IN<br />
120 VAC<br />
INPUT<br />
BLACK<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
MAIN N/C<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
TO BOILER AQUASTAT RELAY<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
MOTOR END<br />
SWITCH<br />
SYSTEM<br />
PUMP<br />
1<br />
2<br />
3<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
SYSTEM PUMP TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS<br />
EXCEPT WHEN THE DHW HEATER (SR501-EXP) CALLS.<br />
MASTER<br />
TO BOILER AQUASTAT RELAY<br />
MODE<br />
POWER<br />
<strong>CONTROLS</strong> RESET<br />
NORMAL<br />
SLAVE<br />
FUSE<br />
1 AMP<br />
MASTER<br />
N<br />
120 VAC<br />
INPUT<br />
H<br />
BOILER<br />
13
2 Expandable Switching Relays Connected Together<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T<br />
THERMOSTATS<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504-EXP<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
MASTER<br />
THERMOSTATS<br />
T<br />
A<br />
AQUASTAT<br />
ON DHW<br />
HEATER<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
PLUG-IN CARDS<br />
RESET<br />
NORMAL<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SR 506-EXP<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
BOILER<br />
DHW<br />
CIRCULATOR<br />
14
2 Indirect Water Heaters with Priority Connected to Standard Switching Relays<br />
AQUASTATS ON<br />
DHW HEATERS<br />
A<br />
A<br />
MASTER<br />
24 VAC<br />
POWER<br />
SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
PRIORITY<br />
OFF<br />
TWO <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
N P ZC H X ZR<br />
1<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
JUMPERS<br />
SR 504<br />
T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
T<br />
SLAVE SLAVE<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
PRIORITY<br />
ON<br />
SR 504<br />
T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
T<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
24 V AC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
FUSE 1 AMP<br />
FUSE 1 AMP<br />
JUMPER<br />
<strong>ZONE</strong><br />
NOT<br />
USED<br />
JUMPER<br />
<strong>ZONE</strong><br />
NOT<br />
USED<br />
BOILER<br />
TO: "TT" ON BOILER<br />
120 VAC INPUT<br />
PRIORITY<br />
ON<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
H<br />
N<br />
X 2<br />
<strong>ZONE</strong> 2<br />
15
2 Indirect Water Heaters with Priority Connected to EXP Switching Relays<br />
A<br />
A<br />
AQUASTATS ON<br />
DHW HEATERS<br />
24 VAC<br />
POWER<br />
SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
PRIORITY<br />
OFF<br />
TWO <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
N P ZC H X ZR<br />
1<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
T<br />
JUMPERS<br />
DHW<br />
CIRCULATORS<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
MASTER SLAVE<br />
T<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504-EXP<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
SR 504-EXP<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
FUSE 1 AMP<br />
FUSE 1 AMP<br />
JUMPER<br />
JUMPER<br />
BOILER<br />
TO: "TT" ON BOILER<br />
<strong>ZONE</strong><br />
NOT<br />
USED<br />
120 VAC INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
H<br />
N<br />
X 2<br />
<strong>ZONE</strong> 2<br />
16
PC700 Boiler Reset Control Connected to SR501-EXP Switching Relay<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
PC700<br />
THERMOSTAT<br />
BOIL OUT<br />
SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
TO: "TT" ON BOILER<br />
T<br />
TO: OPTIONAL <strong>ZONE</strong> VALVE<br />
OR iSeries MIXING VALVE<br />
BOILER SENSOR<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET<br />
FUSE<br />
1 AMP<br />
NORMAL<br />
SLAVE<br />
MASTER<br />
END<br />
<strong>ZONE</strong><br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
VALVE<br />
X 1 3 4 T/R T/W COM 1<br />
X<br />
2 2<br />
SR 501-EXP<br />
FUSE<br />
5 AMP<br />
POWER<br />
T STAT<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
120VAC CIRC<br />
OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
BOILER<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
SYSTEM<br />
CIRCULATOR<br />
17
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Switching Relay<br />
OUTDOOR<br />
SENSOR<br />
TO: "TT" ON BOILER<br />
Note: If Zone Control comes on without a call for heat,<br />
reverse Reset Override input (1 & 2) wires on SR501-EXP.<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
FUSE<br />
1 AMP<br />
POWER<br />
<strong>CONTROLS</strong><br />
END<br />
RESET<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
SR 501-EXP<br />
K1 K2<br />
MODE<br />
RESET<br />
NORMAL<br />
POWER<br />
T STAT<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
THERMOSTATS<br />
SR 504<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
120V RELAY<br />
T<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
120VAC<br />
OUTPUT<br />
K1-B K2-A K2-A<br />
CIRC<br />
OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
JUMPER<br />
MASTER<br />
JUMPER<br />
BOILER<br />
PRIMARY<br />
SYSTEM<br />
CIRCULATOR<br />
(Optional)<br />
DHW<br />
HEATER<br />
CIRCULATOR<br />
120 VAC<br />
INPUT<br />
H<br />
N<br />
OUTDOOR<br />
SENSOR<br />
Connecting a DHW Heater to an Existing Heating Only Switching Relay<br />
Using an SR501-EXP and PC700 Boiler Reset Control<br />
TO: "TT" ON BOILER<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
MASTER<br />
FUSE<br />
1 AMP<br />
POWER<br />
<strong>CONTROLS</strong><br />
END<br />
RESET<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
SR 501-EXP<br />
K1 K2<br />
MODE<br />
RESET<br />
NORMAL<br />
POWER<br />
T STAT<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
SLAVE<br />
SR 504<br />
120V RELAY<br />
T<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
THERMOSTATS<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
120VAC<br />
OUTPUT<br />
K1-B K2-A K2-A<br />
CIRC<br />
OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
BOILER<br />
JUMPER<br />
DHW<br />
HEATER<br />
CIRCULATOR<br />
REMOVE<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
H<br />
N<br />
18
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Zone Valve Control<br />
OUTDOOR<br />
SENSOR<br />
TO: "TT" ON BOILER<br />
Note: If Zone Control comes on without a call for heat,<br />
reverse Reset Override input (1 & 2) wires on SR501-EXP.<br />
THERMOSTATS<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
POWER<br />
<strong>CONTROLS</strong><br />
FUSE<br />
1 AMP<br />
END<br />
RESET MODE<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE RESET<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SR 501-EXP NORMAL<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
K1<br />
K2<br />
POWER<br />
T STAT<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24<br />
VAC<br />
POWER IN<br />
MAIN EXTRA<br />
END END<br />
SWITCH SWITCH<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
MODE<br />
NORMAL RESET<br />
FUSE<br />
(3 AMP MAX)<br />
T<br />
24 VAC<br />
T<br />
T T T T T T T T<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />
N/O COM N/C<br />
<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />
ZVC 404<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
OFF<br />
ON<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
POWER<br />
K1-B K2-A K2-A<br />
N H ZC ZR H H<br />
POWER 120VAC 120VAC CIRC<br />
INPUT INPUT OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
JUMPER<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE TACO<br />
(NO END SWITCH) 3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
BOILER<br />
PRIMARY<br />
SYSTEM<br />
CIRCULATOR<br />
(Optional)<br />
DHW HEATER<br />
CIRCULATOR<br />
<strong>ZONE</strong> VALVE SYSTEM<br />
CIRCULATOR<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
H<br />
N<br />
120 VAC<br />
INPUT<br />
Connecting a DHW Heater to an Existing Heating Only Zone Valve Control<br />
Using an SR501-EXP and PC700 Boiler Reset Control<br />
OUTDOOR<br />
SENSOR<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
TO: "TT" ON BOILER<br />
THERMOSTATS<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
MASTER<br />
POWER<br />
<strong>CONTROLS</strong><br />
FUSE<br />
1 AMP<br />
END<br />
RESET MODE<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE RESET<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SR 501-EXP NORMAL<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
K1<br />
K2<br />
POWER<br />
T STAT<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24<br />
VAC<br />
POWER IN<br />
MAIN EXTRA<br />
END END<br />
SWITCH SWITCH<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
MODE<br />
NORMAL RESET<br />
FUSE<br />
(3 AMP MAX)<br />
T<br />
24 VAC<br />
T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />
N/O COM N/C<br />
<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
OFF<br />
T T T T T T T T<br />
ON<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
ZVC 404<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
SLAVE<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
POWER<br />
K1-B K2-A K2-A<br />
N H ZC ZR H H<br />
POWER 120VAC 120VAC CIRC<br />
INPUT INPUT OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
JUMPER<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE TACO<br />
(NO END SWITCH) 3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
BOILER<br />
DHW HEATER<br />
CIRCULATOR<br />
<strong>ZONE</strong> VALVE SYSTEM<br />
CIRCULATOR<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
H<br />
N<br />
120 VAC<br />
INPUT<br />
19
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing<br />
Tankless Coil Boiler – Zoning with Circulators<br />
OUTDOOR<br />
SENSOR<br />
T<br />
THERMOSTATS<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
FUSE<br />
1 AMP<br />
POWER<br />
<strong>CONTROLS</strong><br />
END<br />
RESET<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
SR 501-EXP<br />
K1 K2<br />
MODE<br />
RESET<br />
NORMAL<br />
POWER<br />
T STAT<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
SR 504<br />
120V RELAY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
120VAC<br />
OUTPUT<br />
K1-B K2-A K2-A<br />
CIRC<br />
OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
JUMPER<br />
BOILER<br />
TO: "ZR" ON BOILER CONTROL<br />
TO: "ZC" ON BOILER CONTROL<br />
PRIMARY<br />
SYSTEM<br />
CIRCULATOR<br />
(Optional)<br />
REMOVE<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
H<br />
N<br />
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).<br />
OUTDOOR<br />
SENSOR<br />
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing<br />
Tankless Coil Boiler – Zoning with Zone Valves<br />
THERMOSTATS<br />
PC700<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
MASTER<br />
FUSE<br />
1 AMP<br />
POWER<br />
<strong>CONTROLS</strong><br />
END<br />
RESET MODE<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE RESET<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
K1-A<br />
MASTER<br />
SR 501-EXP NORMAL<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
K1<br />
K2<br />
POWER<br />
T STAT<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24<br />
VAC<br />
POWER IN<br />
MAIN EXTRA<br />
END END<br />
SWITCH SWITCH<br />
EXISTING<br />
<strong>ZONE</strong><br />
CONTROL<br />
MODE<br />
NORMAL RESET<br />
FUSE<br />
(3 AMP MAX)<br />
T<br />
24 VAC<br />
T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />
N/O COM N/C<br />
<strong>ZONE</strong> 4 RELAY 1 2 3 4 1 2 3 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
OFF<br />
T T T T T T T T<br />
ON<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
ZVC 404<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
SLAVE<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
POWER<br />
K1-B K2-A K2-A<br />
N H ZC ZR H H<br />
POWER 120VAC 120VAC CIRC<br />
INPUT INPUT OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
TO: "ZR" ON BOILER CONTROL<br />
TO: "ZC" ON BOILER CONTROL<br />
JUMPER<br />
PRIMARY<br />
SYSTEM<br />
CIRCULATOR<br />
(Optional)<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
<strong>ZONE</strong> VALVE SYSTEM<br />
CIRCULATOR<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
BOILER<br />
H<br />
N<br />
120 VAC<br />
INPUT<br />
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker).<br />
20
OUTDOOR<br />
SENSOR<br />
BOIL<br />
SEN<br />
PC700<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
BOILER SENSOR<br />
BOILER<br />
PC700 Boiler Reset Control Connected to EXP Switching Relay<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
T<br />
THERMOSTATS<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1234 PLUG-IN CARDS<br />
RESET NORMAL<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
TO: "TT" ON BOILER<br />
H<br />
N<br />
21
STAGE<br />
1<br />
PC702 2–Stage Boiler Reset Control Connected to EXP Switching Relay<br />
OUTDOOR<br />
SENSOR<br />
DHW<br />
DEMAND<br />
SWITCH SETTINGS<br />
PC702<br />
STAGE<br />
2<br />
BOIL<br />
SEN<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
T<br />
THERMOSTATS<br />
BOILER<br />
#1<br />
BOILER SENSOR<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1234 PLUG-IN CARDS<br />
RESET NORMAL<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
BOILER<br />
#2<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
SYSTEM<br />
CIRCULATOR<br />
(OPTIONAL)<br />
22
OUTDOOR<br />
SENSOR<br />
PC705-2<br />
BOIL<br />
SEN<br />
SUP<br />
SEN<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
BOILER<br />
PC705 Variable Speed Pump Injection Control Connected to EXP Switching Relay<br />
GREEN/GROUND<br />
(SEE NOTE B)<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
T<br />
THERMOSTATS<br />
RED<br />
BLUE<br />
BLACK<br />
SYSTEM<br />
CIRCULATOR<br />
AND/OR BOILER<br />
INJECTION<br />
CIRCULATOR<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1234 PLUG-IN CARDS<br />
RESET NORMAL<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
SYSTEM<br />
CIRCULATOR<br />
AND/OR BOILER<br />
(SEE NOTE A)<br />
120 VAC INPUT<br />
N<br />
H<br />
NOTE A: WHEN SYSTEM CIRCULATOR IS CONNECTED TO ZR TERMINAL ON SWITCHING RELAY, THE MODE SWITCH MUST BE SET TO NORMAL.<br />
THE PC705-2 WILL NOT RESET THE BOILER WHEN IN THE NORMAL MODE.<br />
NOTE B: WHEN SYSTEM CIRCULATOR IS CONNECTED TO RED <strong>WIRE</strong> ON PC705-2, THE CIRCULATOR WILL OPERATE ONLY WHEN THERMOSTAT CALLS FOR HEAT<br />
AND THE OUTDOOR TEMPERATURE IS BELOW THE WARM WEATHER SHUT DOWN (WWSD) TEMPERATURE. THE WWSD CAN BE ADJUSTED OR TURNED<br />
OFF SO THAT THE CIRCULATOR IS NOT AFFECTED BY OUTDOOR TEMPERATURE.<br />
23
PC700 Boiler Reset Control Connected to 2 EXP Switching Relays<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
BOIL OUT<br />
SEN SEN<br />
PC700<br />
<strong>ZONE</strong><br />
CONTROL<br />
BOILER SENSOR<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
MASTER<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
BOILER<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: No Priority<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
SLAVE<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
SYSTEM<br />
CIRCULATOR<br />
(OPTIONAL)<br />
24
PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays<br />
STAGE<br />
1<br />
PC702<br />
STAGE<br />
2<br />
BOIL OUT <strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER<br />
#1<br />
BOILER SENSOR<br />
DHW<br />
DEMAND<br />
OUTDOOR<br />
SENSOR<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
MASTER<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
BOILER<br />
#2<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: No Priority<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
SLAVE<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
SYSTEM<br />
CIRCULATOR<br />
(OPTIONAL)<br />
JUMPER<br />
H<br />
N<br />
120 VAC INPUT<br />
25
PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays<br />
SWITCH SETTINGS<br />
OUTDOOR<br />
SENSOR<br />
GREEN/GROUND<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
T<br />
THERMOSTATS<br />
MASTER<br />
BOIL<br />
SEN<br />
PC705-2<br />
SUP OUT<br />
SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
RED<br />
BLUE<br />
BLACK<br />
(SEE NOTE B<br />
ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
INJECTION<br />
CIRCULATOR<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
BOILER<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: No Priority<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
SLAVE<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
H<br />
N<br />
SYSTEM<br />
CIRCULATOR<br />
(OPTIONAL)<br />
(SEE NOTE A ON PAGE 23)<br />
120 VAC INPUT<br />
26
PC700 and PC705 Controls Connected to 2 EXP Switching Relays<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
BOIL OUT<br />
SEN SEN<br />
PC700<br />
<strong>ZONE</strong><br />
CONTROL<br />
BOILER SENSOR<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
MASTER<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC INPUT<br />
BOILER<br />
OUTDOOR<br />
SENSOR<br />
BOIL<br />
SEN<br />
PC705-2<br />
SUP OUT<br />
SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
GREEN/GROUND<br />
RED<br />
BLUE<br />
BLACK<br />
(SEE NOTE B<br />
ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
INJECTION<br />
CIRCULATOR<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: No Priority<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
SLAVE<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
SYSTEM CIRCULATOR<br />
(OPTIONAL LOCATION)<br />
(SEE NOTE A ON PAGE 23)<br />
H<br />
N<br />
120 VAC INPUT<br />
27
PC702 and PC705 Controls Connected to 2 EXP Switching Relays<br />
STAGE<br />
1<br />
PC702<br />
STAGE<br />
2<br />
BOIL OUT <strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER<br />
#1<br />
BOILER SENSOR<br />
DHW<br />
DEMAND<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
FUSE 1 AMP<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
MASTER<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
JUMPER<br />
120 VAC INPUT<br />
BOILER<br />
#2<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
OUTDOOR<br />
SENSOR<br />
BOIL<br />
SEN<br />
PC705-2<br />
SUP OUT<br />
SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
GREEN/GROUND<br />
RED<br />
BLUE<br />
BLACK<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: No Priority<br />
(SEE NOTE B<br />
ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
INJECTION<br />
CIRCULATOR<br />
24 VAC<br />
POWER<br />
SLAVE<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
120V RELAY<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
T<br />
THERMOSTATS<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
SR 504-EXP<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
SLAVE<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
FUSE 1 AMP<br />
JUMPER<br />
28<br />
SYSTEM CIRCULATOR<br />
(OPTIONAL LOCATION)<br />
(SEE NOTE A ON PAGE 23)<br />
120 VAC INPUT<br />
H<br />
N
THERMOSTAT THERMOSTAT THERMOSTAT<br />
24 VAC<br />
T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
ZVC 405<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
ZVC403/405 with System Pump<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
T T T<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
POWER<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
POWER IN<br />
FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
FUSE (5 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
N/O COM N/C<br />
BOILER<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
TO BOILER AQUASTAT RELAY<br />
MOTOR END<br />
SWITCH<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
SYSTEM<br />
PUMP<br />
N<br />
H<br />
SYSTEM PUMP AND BOILER TURN ON<br />
WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
29
ZVC404/406 with System Pump<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T T<br />
24 VAC<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
N<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
H<br />
MAIN N/C<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
TO BOILER AQUASTAT RELAY<br />
MOTOR END<br />
SWITCH<br />
DRY<br />
CONTACTS<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
BOILER<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SYSTEM<br />
PUMP<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SYSTEM PUMP AND BOILER TURN ON<br />
WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
30
ZVC404/406 with Domestic Hot Water (DHW) Pump<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T T<br />
24 VAC<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
MAIN N/C<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
N<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
TO BOILER AQUASTAT RELAY<br />
MOTOR END<br />
SWITCH<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
H<br />
BOILER<br />
DHW<br />
PUMP<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
31
ZVC404/406 with System and DHW Pumps<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T T<br />
24 VAC<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
MAIN N/C<br />
N<br />
JUMPER<br />
3 & 4<br />
H<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
TO BOILER AQUASTAT RELAY<br />
MOTOR END<br />
SWITCH<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
BOILER<br />
SYSTEM<br />
PUMP<br />
DHW<br />
PUMP<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
32
ZVC404/406 with System, DHW and Secondary Pumps<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T T<br />
24 VAC<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
N<br />
MAIN N/C<br />
H<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
TO BOILER AQUASTAT RELAY<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
MOTOR END<br />
SWITCH<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
BOILER<br />
SYSTEM<br />
PUMP<br />
DHW<br />
PUMP<br />
SECONDARY<br />
PUMP<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
SECONDARY PUMP COMES ON WHEN ANY <strong>ZONE</strong> CALLS EXCEPT PRIORITY <strong>ZONE</strong>.<br />
33
2 ZVC404/406 Connected Together with Priority<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
T T T<br />
24 VAC<br />
N<br />
H<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24<br />
VAC<br />
POWER IN<br />
MAIN<br />
END<br />
SWITCH<br />
EXTRA<br />
END<br />
SWITCH<br />
MODE<br />
NORMAL RESET<br />
N/O COM N/C<br />
<strong>ZONE</strong> 4 RELAY<br />
FUSE (3 AMP MAX)<br />
<strong>ZONE</strong> 4 PRIORITY<br />
OFF<br />
ON<br />
T T T T T T T T<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />
1 2 3 4 1 2 3 4<br />
ZVC 404<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
PRIORITY<br />
ON<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
POWER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
T T T<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
24 VAC<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24<br />
VAC<br />
POWER IN<br />
MAIN<br />
END<br />
SWITCH<br />
EXTRA<br />
END<br />
SWITCH<br />
MODE<br />
NORMAL RESET<br />
N/O COM N/C<br />
<strong>ZONE</strong> 4 RELAY<br />
FUSE (3 AMP MAX)<br />
<strong>ZONE</strong> 4 PRIORITY<br />
OFF<br />
ON<br />
T T T T T T T T<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2<br />
1 2 3 4 1 2 3 4<br />
ZVC 404<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
PRIORITY<br />
ON<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
POWER<br />
BOILER<br />
TO BOILER AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
34
2 EXP Zone Valve Controls Connected Together with System Pump<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER AQUASTAT RELAY<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
SYSTEM<br />
PUMP<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
N<br />
H<br />
120 VAC<br />
INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
35
2 EXP Zone Valve Controls Connected Together with DHW Pump<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
DHW<br />
PUMP<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
BOILER TURNS ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
N<br />
H<br />
120 VAC<br />
INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
36
2 EXP Zone Valve Controls Connected Together with System and DHW Pumps<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DHW<br />
PUMP<br />
SYSTEM<br />
PUMP<br />
JUMPER<br />
3 & 4<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
1<br />
2<br />
3<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
MOTOR<br />
END<br />
SWITCH<br />
PRIORITY<br />
<strong>ZONE</strong><br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
JUMPER<br />
3 & 4<br />
SEE NOTE<br />
SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
N<br />
H<br />
120 VAC<br />
INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
37
2 EXP Zone Valve Controls Connected Together with System, DHW and Secondary Pumps<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
A<br />
AQUASTAT ON<br />
DHW HEATER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DHW<br />
PUMP<br />
SYSTEM<br />
PUMP<br />
SECONDARY<br />
PUMP<br />
JUMPER<br />
3 & 4<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
1<br />
2<br />
3<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
MOTOR<br />
END<br />
SWITCH<br />
PRIORITY<br />
<strong>ZONE</strong><br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
JUMPER<br />
3 & 4<br />
SEE NOTE<br />
SYSTEM PUMP AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW PUMP TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
SECONDARY PUMP TURNS ON WHEN ANY <strong>ZONE</strong> CALLS, EXCEPT PRIORITY <strong>ZONE</strong>.<br />
N<br />
H<br />
120 VAC<br />
INPUT<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
38
PC700 Boiler Reset Control Connected To EXP Zone Valve Control<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
24 VAC<br />
POWER<br />
<strong>CONTROLS</strong><br />
RESET<br />
MODE<br />
SLAVE<br />
NORMAL<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
JUMPER<br />
3 & 4<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
1<br />
2<br />
3<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
MOTOR END<br />
SWITCH<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
INDIRECT<br />
WATER HEATER<br />
AQUASTAT<br />
OR THERMOSTAT<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SEE NOTE<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
BOILER<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
PC700<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
BOIL<br />
SEN<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
BOILER SENSOR<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
24 VAC<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
SYSTEM<br />
CIRCULATOR<br />
H<br />
N<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
39
PC702 2–Stage Boiler Reset Control Connected To EXP Zone Valve Control<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
24 VAC<br />
POWER<br />
<strong>CONTROLS</strong><br />
RESET<br />
MODE<br />
SLAVE<br />
NORMAL<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
INDIRECT<br />
WATER HEATER<br />
AQUASTAT<br />
OR THERMOSTAT<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SEE NOTE<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
STAGE<br />
1<br />
OUTDOOR<br />
SENSOR<br />
DHW<br />
DEMAND<br />
PC702<br />
STAGE<br />
2<br />
BOIL<br />
SEN<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
BOILER SENSOR<br />
BOILER<br />
#1<br />
BOILER<br />
#2<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
24 VAC<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
SYSTEM<br />
CIRCULATOR<br />
H<br />
N<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
DHW<br />
CIRCULATOR<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
40
PC705 Variable Speed Pump Injection Control Connected To EXP Zone Valve Control<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
24 VAC<br />
POWER<br />
<strong>CONTROLS</strong><br />
RESET<br />
MODE<br />
SLAVE<br />
NORMAL<br />
MASTER<br />
1 2 3 4<br />
EXPANSION<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
INDIRECT<br />
WATER HEATER<br />
AQUASTAT<br />
OR THERMOSTAT<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SEE NOTE<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
BOILER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
24 VAC<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
H<br />
N<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
OUTDOOR<br />
SENSOR<br />
BOIL<br />
SEN<br />
GREEN/GROUND<br />
PC705-2<br />
SUP<br />
SEN<br />
OUT<br />
SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
RED<br />
BLUE<br />
BLACK<br />
SYSTEM<br />
CIRCULATOR<br />
(SEE NOTE B ON PAGE 23)<br />
INJECTION<br />
CIRCULATOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
T T T<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
SYSTEM CIRCULATOR<br />
(OPTIONAL LOCATION)<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
41
PC700 Boiler Reset Control Connected To 2 EXP Zone Valve Controls<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
PC700<br />
INDIRECT WATER HEATER<br />
AQUASTAT OR THERMOSTAT<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
SYSTEM<br />
CIRCULATOR<br />
DHW<br />
CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
H<br />
N<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
T<br />
24 VAC<br />
T<br />
T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
42
PC702 2–Stage Boiler Reset Control Connected To 2 EXP Zone Valve Controls<br />
OUTDOOR<br />
SENSOR<br />
DHW<br />
DEMAND<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
PC702<br />
STAGE STAGE BOIL OUT <strong>ZONE</strong><br />
1 2 SEN SEN CONTROL<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
INDIRECT WATER HEATER<br />
AQUASTAT OR THERMOSTAT<br />
BOILER SENSOR<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
#1<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
SYSTEM<br />
CIRCULATOR<br />
DHW<br />
CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
H<br />
N<br />
BOILER<br />
#2<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
SLAVE<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
T<br />
24 VAC<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
43
PC705 Variable Speed Pump Injection Control Connected To 2 EXP Zone Valve Controls<br />
OUTDOOR<br />
SENSOR<br />
GREEN/GROUND<br />
RED<br />
(SEE NOTE B ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
PC705-2<br />
BOIL SUP OUT <strong>ZONE</strong><br />
SEN SEN SEN CONTROL<br />
BLUE<br />
BLACK<br />
INJECTION<br />
CIRCULATOR<br />
INDIRECT WATER HEATER<br />
AQUASTAT OR THERMOSTAT<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
MASTER<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
T<br />
24 VAC<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
SYSTEM CIRCULATOR<br />
(OPTIONAL LOCATION)<br />
JUMPER<br />
3 & 4<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
1<br />
2<br />
3<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
MOTOR<br />
END<br />
SWITCH<br />
PRIORITY<br />
<strong>ZONE</strong><br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
JUMPER<br />
3 & 4<br />
SEE NOTE<br />
H<br />
N<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
SLAVE<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
T<br />
24 VAC<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
44
PC700 and PC705 Connected To 2 EXP Zone Valve Controls<br />
OUTDOOR<br />
SENSOR<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Reset<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
PC700<br />
INDIRECT WATER HEATER<br />
AQUASTAT OR THERMOSTAT<br />
BOIL OUT<br />
<strong>ZONE</strong><br />
SEN SEN CONTROL<br />
BOILER SENSOR<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
TO BOILER<br />
AQUASTAT RELAY<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
SYSTEM<br />
CIRCULATOR<br />
DHW<br />
CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
H<br />
OUTDOOR<br />
SENSOR<br />
GREEN/GROUND<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
N<br />
RED<br />
(SEE NOTE B ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
PC705-2<br />
BLUE<br />
INJECTION<br />
CIRCULATOR<br />
BOIL SUP OUT<br />
SEN SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
BLACK<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
SLAVE<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
T<br />
24 VAC<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
T<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
45
PC702 and PC705 Connected To 2 EXP Zone Valve Controls<br />
OUTDOOR<br />
SENSOR<br />
DHW<br />
DEMAND<br />
SWITCH SETTINGS<br />
Master/Slave: Master<br />
Reset/Normal: Normal<br />
Priority Zone: On or Off<br />
Note: When a circulator is used on the<br />
priority zone instead of a zone valve,<br />
jumper 3 and 4 of the priority zone.<br />
PC702<br />
STAGE STAGE BOIL OUT <strong>ZONE</strong><br />
1 2 SEN SEN CONTROL<br />
WIRING NEEDED ONLY IF<br />
PRIORITY <strong>ZONE</strong> IS DHW<br />
INDIRECT WATER HEATER<br />
AQUASTAT OR THERMOSTAT<br />
BOILER SENSOR<br />
MASTER<br />
T<br />
24 VAC<br />
T<br />
T<br />
BOILER<br />
#1<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
BOILER<br />
#2<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
SYSTEM<br />
CIRCULATOR<br />
DHW<br />
CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
H<br />
OUTDOOR<br />
SENSOR<br />
GREEN/GROUND<br />
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY <strong>ZONE</strong> CALLS.<br />
N<br />
RED<br />
(SEE NOTE B ON PAGE 23)<br />
SYSTEM<br />
CIRCULATOR<br />
PC705-2<br />
BLUE<br />
BLACK<br />
INJECTION<br />
CIRCULATOR<br />
BOIL SUP OUT<br />
SEN SEN SEN<br />
<strong>ZONE</strong><br />
CONTROL<br />
SUPPLY SENSOR<br />
BOILER SENSOR<br />
SLAVE<br />
T<br />
24 VAC<br />
T<br />
T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
RESET NORMAL<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SWITCH SETTINGS<br />
Master/Slave: Slave<br />
Reset/Normal: Normal<br />
Priority Zone: Off<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
46
HAFC101 with 1 Speed Air Handler<br />
THERMOSTAT<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
T<br />
To: Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
C R W Y<br />
THERMOSTAT<br />
G<br />
T T<br />
AQUASTAT<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
BOILER<br />
AIR HANDLER<br />
X X C R Y<br />
G G<br />
LOW HIGH<br />
Jumper<br />
Dry Contacts To:<br />
“T T” on Boiler<br />
or Switching Relay<br />
Line 24 VAC<br />
Fan<br />
Relay<br />
M<br />
Outdoor<br />
Condenser<br />
Unit<br />
HAFC 101 WITH 1 SPEED AIR HANDLER<br />
(Both HFC 101 and HAFC 201 are<br />
capable of 1 and 2 speed applications.)<br />
47
HAFC101 with 2 Speed Air Handler<br />
THERMOSTAT<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
T<br />
To: Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
C R W Y<br />
THERMOSTAT<br />
G<br />
T T<br />
AQUASTAT<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
BOILER<br />
AIR HANDLER<br />
X X C R Y<br />
G G<br />
LOW HIGH<br />
Dry Contacts To:<br />
“T T” on Boiler<br />
or Switching Relay<br />
Line 24 VAC<br />
Low<br />
High<br />
M<br />
Fan Relays<br />
Outdoor<br />
Condenser<br />
Unit<br />
HAFC 101 WITH 2 SPEED AIR HANDLER<br />
(Both HFC 101 and HAFC 201 are<br />
capable of 1 and 2 speed applications.)<br />
48
HAFC201 with 1 Speed Air Handler<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
THERMOSTAT<br />
T<br />
To: Optional<br />
Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
To: Optional Aquastat<br />
or Thermostat to sense<br />
low ambient<br />
temperature<br />
C R W Y<br />
THERMOSTAT<br />
G<br />
T<br />
T<br />
T<br />
T<br />
WATER COIL FREEZE PR<br />
AQUASTATS<br />
NOTE: For 4 minute<br />
on delay of Heating Fan,<br />
switch 1 and 3 MIN ON<br />
DELAY to ON position.<br />
OFF ON<br />
1 MIN ON DELAY - FAN<br />
3 MIN ON DELAY - FAN<br />
2 MIN @ 24 HR - PUMP<br />
30 SEC @ 2 WK - PUMP<br />
HAFC201<br />
HYDRO AIR FAN CONTROL<br />
DRY CONTACTS<br />
5 AMP 1/6 HP RATED<br />
PUMP<br />
X<br />
X<br />
BOILER<br />
AIR HANDLER<br />
XXCRY<br />
G G<br />
LOW HIGH<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
Jumper<br />
Hot<br />
Neutral<br />
(or to “T T” on<br />
switching relay)<br />
Circulator<br />
Dry Contacts To:<br />
“T T” on Boiler<br />
or Switching<br />
Relay<br />
Line 24 VAC<br />
Fan<br />
Relay<br />
M<br />
Outdoor<br />
Condenser<br />
Unit<br />
HAFC 201 WITH 1 SPEED AIR HANDLER<br />
(Both HFC 101 and HAFC 201 are<br />
capable of 1 and 2 speed applications.)<br />
49
HAFC201 with 2 Speed Air Handler<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
THERMOSTAT<br />
T<br />
To: Optional<br />
Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
To: Optional Aquastat<br />
or Thermostat to sense<br />
low ambient<br />
temperature<br />
C R W Y<br />
THERMOSTAT<br />
G<br />
T<br />
T<br />
T<br />
T<br />
WATER COIL FREEZE PR<br />
AQUASTATS<br />
NOTE: For 4 minute<br />
on delay of Heating Fan,<br />
switch 1 and 3 MIN ON<br />
DELAY to ON position.<br />
OFF ON<br />
1 MIN ON DELAY - FAN<br />
3 MIN ON DELAY - FAN<br />
2 MIN @ 24 HR - PUMP<br />
30 SEC @ 2 WK - PUMP<br />
HAFC201<br />
HYDRO AIR FAN CONTROL<br />
DRY CONTACTS<br />
5 AMP 1/6 HP RATED<br />
PUMP<br />
X<br />
X<br />
BOILER<br />
AIR HANDLER<br />
XXCRY<br />
G G<br />
LOW HIGH<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
Hot<br />
Neutral<br />
(or to “T T” on<br />
switching relay)<br />
Circulator<br />
“T T” on Boiler<br />
or Switching<br />
Relay<br />
Line 24 VAC<br />
Low<br />
High<br />
M<br />
Fan Relays<br />
Outdoor<br />
Condenser<br />
Unit<br />
HAFC 201 WITH 2 SPEED AIR HANDLER<br />
(Both HFC 101 and HAFC 201 are<br />
capable of 1 and 2 speed applications.)<br />
50
Multiple HAFC’s and Switching Relay<br />
THERMOSTAT<br />
THERMOSTAT<br />
THERMOSTAT<br />
C R W Y G T T<br />
THERMOSTAT AQUASTAT<br />
C R W Y G T T<br />
THERMOSTAT AQUASTAT<br />
C R W Y G T T<br />
THERMOSTAT AQUASTAT<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
POWER PM<br />
CALL FOR HEAT<br />
FAN, COOLING<br />
FAN, HEATING<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
BOILER AIR HANDLER<br />
X X C R Y G G<br />
LOW HIGH<br />
BOILER AIR HANDLER<br />
X X C R Y G G<br />
LOW HIGH<br />
BOILER AIR HANDLER<br />
X X C R Y G G<br />
M<br />
OUTDOOR<br />
CONDENSER<br />
UNIT<br />
Line 24 VAC<br />
Low<br />
High<br />
Fan Relays<br />
M<br />
Line 24 VAC<br />
Low<br />
High<br />
Fan Relays<br />
M<br />
Line 24 VAC<br />
Low<br />
High<br />
Fan Relays<br />
OPTIONAL POWER <strong>WIRE</strong><br />
TO THERMOSTAT<br />
THAT REQUIRES 24VAC<br />
T T T<br />
TO: AQUASTAT ON<br />
RETURN LINE OF<br />
HYDRO COIL<br />
OPTIONAL POWER <strong>WIRE</strong><br />
TO THERMOSTAT<br />
THAT REQUIRES 24VAC<br />
TO: AQUASTAT ON<br />
RETURN LINE OF<br />
HYDRO COIL<br />
OPTIONAL POWER <strong>WIRE</strong><br />
TO THERMOSTAT<br />
THAT REQUIRES 24VAC<br />
TO: AQUASTAT ON<br />
RETURN LINE OF<br />
HYDRO COIL<br />
POWER PM<br />
CALL FOR HEAT<br />
FAN, COOLING<br />
FAN, HEATING<br />
POWER PM<br />
CALL FOR HEAT<br />
FAN, COOLING<br />
FAN, HEATING<br />
LOW HIGH<br />
OUTDOOR<br />
CONDENSER<br />
UNIT<br />
OUTDOOR<br />
CONDENSER<br />
UNIT<br />
2 SPEED AIR HANDLER<br />
2 SPEED AIR HANDLER<br />
2 SPEED AIR HANDLER<br />
SR 504<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
DHW<br />
HEATER<br />
AQUASTAT<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
TO: "TT" ON BOILER<br />
BOILER<br />
H<br />
N<br />
51
3 Wire Thermostat Connected to TACO Switching Relay<br />
3 <strong>WIRE</strong><br />
THERMOSTAT<br />
SR 504<br />
COM T<br />
T T T<br />
W R<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 4<br />
PRIORITY<br />
ON<br />
OFF<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
FOUR <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
X X<br />
END ZC ZR<br />
SWITCH<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
FUSE 1 AMP<br />
JUMPER<br />
120 VAC INPUT<br />
H<br />
N<br />
TO: "TT" ON BOILER<br />
BOILER<br />
3 Wire Thermostat Connected to TACO Zone Valve Control<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
T T T<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
C<br />
W R<br />
WH<br />
RED<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
END<br />
SWITCH<br />
POWER IN<br />
COMMON<br />
T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
ZVC 405<br />
FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
POWER<br />
T<br />
T<br />
TO T&T ON BOILER<br />
OR PUMP RELAY<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
BLACK<br />
BLACK<br />
RED<br />
RED<br />
MOTOR<br />
END<br />
SWITCH<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(TACO TYPE)<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(HONEYWELL TYPE)<br />
52
White-Rogers 1361 Hydronic Zone Valve with TACO Zone Valve Control<br />
NOTE: WHEN USING ZVC 404 OR ZVC 406,<br />
CONNECT <strong>WIRE</strong> #2 OF <strong>ZONE</strong> VALVE<br />
TO PRIORITY <strong>ZONE</strong> RIGHT TT SCREW<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
T T T<br />
24 VAC<br />
T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
ZVC 405<br />
FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
3<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
WHITE-ROGERS 1361<br />
HYDRONIC <strong>ZONE</strong> VALVE<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(TACO TYPE)<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(HONEYWELL TYPE)<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
POWER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
RIGHT TT<br />
SCREW<br />
(SEE NOTE)<br />
POWER IN<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
END<br />
SWITCH<br />
BLACK<br />
BLACK<br />
RED<br />
RED<br />
T<br />
T<br />
TO T&T ON BOILER<br />
OR PUMP RELAY<br />
2<br />
1<br />
4<br />
TERMINAL ASSIGNMENT<br />
<strong>ZONE</strong> VALVE CONTROL<br />
1 1<br />
2<br />
TT (Rt)<br />
3<br />
3<br />
4 2<br />
53
Honeywell VC 40 & 80 (spdt) Hydronic Zone Valve with TACO Zone Valve Control<br />
24 VAC<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
NOTE: WHEN USING ZVC 404 OR ZVC 406,<br />
CONNECT <strong>WIRE</strong> #3 OF <strong>ZONE</strong> VALVE<br />
TO PRIORITY <strong>ZONE</strong> RIGHT TT SCREW<br />
T T T<br />
RIGHT TT<br />
SCREW<br />
(SEE NOTE)<br />
TERMINAL ASSIGNMENT<br />
<strong>ZONE</strong> VALVE CONTROL<br />
ORANGE 1 3<br />
BLUE 2 1<br />
BROWN 3 TT (Rt)<br />
GRAY 4 4<br />
BLACK 6 2<br />
END<br />
SWITCH<br />
T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
ZVC 405<br />
FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
24 VAC<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
POWER<br />
BLACK<br />
BLACK<br />
RED<br />
RED<br />
T<br />
T<br />
TO T&T ON BOILER<br />
OR PUMP RELAY<br />
3<br />
2<br />
6<br />
4<br />
1<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
HONEYWELL VC (SPST)<br />
HYDRONIC <strong>ZONE</strong> VALVE<br />
SERIES 40 & 80<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(TACO TYPE)<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(HONEYWELL TYPE)<br />
54
570 Zone Valve to Switching Relay<br />
T<br />
THERMOSTAT<br />
24 VAC<br />
TRANSFORMER<br />
1<br />
2<br />
3<br />
24 VAC<br />
POWER<br />
SR 503<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
N P ZC H<br />
JUMPERS<br />
X 2<br />
X 1 ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
120 VOLT<br />
CIRCULATORS<br />
TO: 120 VAC POWER (NEUTRAL)<br />
TO: 120 VAC POWER (HOT)<br />
TO: "TT" ON AQUASTAT CONTROL<br />
TO: "TT" ON AQUASTAT CONTROL<br />
55
Zone Valve Control with 1 Low Temperature Zone Using Priority Zoning Circulator<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
AQUASTAT ON<br />
DHW HEATER<br />
A<br />
T T T<br />
24 VAC<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
N<br />
120 VAC<br />
INPUT<br />
BLACK<br />
H<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
MODE<br />
NORMAL RESET<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
POWER IN<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
ZVC 406<br />
FUSE (7 AMP MAX)<br />
24 VAC<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
MAIN N/C<br />
N/O COM<br />
<strong>ZONE</strong> 6 RELAY<br />
EXTRA<br />
END<br />
SWITCH<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
SEE NOTE<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
TO BOILER AQUASTAT RELAY<br />
END<br />
SWITCH<br />
MOTOR<br />
MOTOR END<br />
SWITCH<br />
DRY<br />
CONTACTS<br />
Note: When a circulator is<br />
used on the priority zone<br />
instead of a zone valve,<br />
jumper 3 and 4 of the<br />
priority zone.<br />
BOILER<br />
1<br />
2<br />
3<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
TACO<br />
3 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong><br />
<strong>ZONE</strong> VALVE<br />
(POWER OPEN,<br />
SELF CLOSING)<br />
SYSTEM<br />
PUMP<br />
PRIORITY<br />
ON<br />
PRIORITY ZONING CIRCULATOR<br />
PRIORITY<br />
ON<br />
OFF<br />
THERMOSTAT BOILER PRIORITY POWER IN<br />
1 2 3 4 PR-IN PR-OUT LIVE NEUT<br />
SYSTEM PUMP AND BOILER TURN ON<br />
WHEN ANY <strong>ZONE</strong> VALVE OPENS.<br />
120 VAC INPUT<br />
56
Radiant Mixing Block (RMB)<br />
Back of<br />
Control<br />
Front of<br />
Control<br />
R<br />
Power: 120 V + 10%<br />
C US 50/60 Hz, 750 VA<br />
158033 Var. Speed: 120 V<br />
(ac) 1 A<br />
Pmp Relay: 120 V<br />
(ac) 5 A, 1/6 hp<br />
Use copper<br />
conductors only<br />
Com SupSys<br />
ComBoil Out ComHeat<br />
Ret<br />
Dem<br />
Boiler<br />
MENU ITEM<br />
RADIANT MIXING BLOCK<br />
PATENT PENDING<br />
U L RMB-1<br />
Boiler<br />
Meets Class B:<br />
Canadian ICES<br />
FCC Part 15<br />
Sys<br />
Y R B<br />
Var<br />
Boiler Operation<br />
Off-Enable On-Control<br />
Fuse<br />
Pump<br />
Man<br />
H<br />
N<br />
Line Cord<br />
Supply<br />
Sensor<br />
Boiler<br />
Sensor<br />
Outdoor<br />
Sensor<br />
To<br />
Zone<br />
Control<br />
End<br />
Switch<br />
or<br />
Thermostat<br />
Injection<br />
Circulator<br />
Radiant<br />
Circulator<br />
Radiant Mixing Block, Single Zone<br />
Boiler<br />
RMB<br />
Back of Control<br />
Boiler Operation<br />
Off-Enable On-Control<br />
T<br />
Thermostat<br />
(Dry Contact)<br />
Pump<br />
ComSupSysComBoil Out ComHeat<br />
Ret<br />
Dem<br />
H<br />
N<br />
H<br />
N<br />
Power<br />
Input<br />
Outdoor<br />
Sensor<br />
N<br />
Boiler<br />
Sensor<br />
Supply<br />
Sensor<br />
High Mass Boiler<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />
57
Radiant Mixing Block Connected to Zone Valve Control with System Pump Wired off the RMB<br />
Outdoor<br />
Sensor<br />
Power<br />
Input<br />
H<br />
N<br />
Factory<br />
Installed<br />
Transformer<br />
T<br />
T<br />
Thermostats<br />
Boiler<br />
RMB<br />
Back of Control<br />
Boiler Operation<br />
Off-Enable On-Control<br />
POWER IN<br />
FUSE<br />
(5 AMP MAX)<br />
T T<br />
<strong>ZONE</strong> 1<br />
T T<br />
<strong>ZONE</strong> 2<br />
ZVC 403<br />
T T<br />
<strong>ZONE</strong> 3<br />
THREE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
Pump<br />
END<br />
SWITCH<br />
N/O COM N/C<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
Com Sup Sys Com Boil Out Com Heat<br />
Ret<br />
Dem<br />
H<br />
N<br />
N<br />
Motor<br />
M<br />
End Switch<br />
Motor<br />
M<br />
End Switch<br />
Boiler<br />
Sensor<br />
Supply<br />
Sensor<br />
Radiant Mixing Block Connected to 2 EXP Switching Relays with DHW Pump<br />
SLAVE<br />
MASTER<br />
POWER CONTROL<br />
INTERFACE<br />
1 2 3 4<br />
EXPANSION<br />
RESET<br />
Thermostats<br />
T<br />
PLUG-IN CARDS<br />
NORMAL<br />
<strong>ZONE</strong>1<br />
T<br />
<strong>ZONE</strong>2<br />
A<br />
<strong>ZONE</strong>3<br />
DHW<br />
Aquastat<br />
<strong>ZONE</strong> 3<br />
PRIORITY<br />
ON<br />
OFF<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY SR503-EXP<br />
Outdoor<br />
Sensor<br />
Boiler<br />
RMB<br />
Back of Control<br />
Boiler Operation<br />
Off-Enable On-Control<br />
Power Cord<br />
SLAVE<br />
MASTER<br />
POWER CONTROL<br />
INTERFACE<br />
1 2 3 4<br />
EXPANSION<br />
PLUG-IN CARDS<br />
RESET NORMAL<br />
T<br />
T<br />
Thermostats<br />
<strong>ZONE</strong> 3<br />
PRIORITY<br />
ON<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
OFF<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
SR503-EXP<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
Sys Com<br />
ComSup Boil Out ComHeat<br />
Ret<br />
Dem<br />
Pump<br />
H<br />
N<br />
24 VAC<br />
POWER<br />
FUSE 1 AMP<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
H<br />
N<br />
Power<br />
Input<br />
DHW<br />
Circ.<br />
N<br />
Boiler<br />
Sensor<br />
Supply<br />
Sensor<br />
58<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard
X - Pump Block (XPB)<br />
Back of<br />
Control<br />
Front of<br />
Control<br />
R<br />
Power: 120 V + 10%<br />
C US 50/60 Hz, 750 VA<br />
158033 Var. Speed: 120 V<br />
(ac) 1 A<br />
Pmp Relay: 120 V<br />
(ac) 5 A, 1/6 hp<br />
Use copper<br />
conductors only<br />
MENU ITEM<br />
Com Sup SysCom<br />
Boil Out Com Heat<br />
Ret<br />
Dem<br />
Heat Source<br />
X – PUMP BLOCK<br />
PATENT PENDING<br />
U L XPB-1<br />
System<br />
Supply<br />
Sensor<br />
Heat<br />
Source<br />
Sensor<br />
Outdoor<br />
Sensor<br />
Boiler<br />
To<br />
Zone<br />
Control<br />
End Switch<br />
or<br />
Thermostat<br />
(Relay or<br />
Mechanical<br />
Type)<br />
Meets Class B:<br />
Canadian ICES<br />
FCC Part 15<br />
Sys<br />
Y R B<br />
Var<br />
Boiler Operation<br />
Off-Enable On-Control<br />
Fuse<br />
Pump<br />
Man<br />
H<br />
N<br />
Manual<br />
Operation<br />
Switch<br />
Line Cord<br />
Variable Speed Circulator<br />
Heating: Heat Source Circulator<br />
Snowmelt: System Circulator<br />
Constant Speed Circulator<br />
Heating: System Circulator<br />
Snowmelt: Heat Source Circulator<br />
X - Pump Block, Single Zone<br />
Outdoor<br />
Sensor<br />
Boiler<br />
XPB<br />
Back of Control<br />
Boiler Operation<br />
Off-Enable On-Control<br />
Power<br />
Cord<br />
Pump<br />
Thermostat<br />
(Relay or Mechanical Type)<br />
ComSupSysComBoil Out Com Heat<br />
Ret<br />
Dem<br />
H<br />
N<br />
T<br />
Pressure<br />
Relief<br />
HEAT<br />
SOURCE<br />
Input from<br />
Heat Source<br />
Exp<br />
Tank<br />
Output to<br />
System<br />
Supply<br />
Sensor<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />
59
X - Pump Block Connected to Zone Valve Control<br />
Outdoor<br />
Sensor<br />
Power<br />
Cord<br />
Power<br />
Input<br />
H<br />
N<br />
Factory<br />
Installed<br />
Transformer<br />
T<br />
T<br />
T<br />
Boiler<br />
Boiler Operation<br />
XPB Off-Enable On-Control<br />
Back of Control<br />
NORMAL<br />
POWER IN<br />
T T<br />
<strong>ZONE</strong> 1<br />
T T<br />
<strong>ZONE</strong> 2<br />
T T<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4 PRIORITY<br />
OFF<br />
T T<br />
ON<br />
<strong>ZONE</strong> 4<br />
ComSupSysComBoil Out Com Heat<br />
Ret<br />
Dem<br />
H<br />
Pump<br />
MAIN EXTRA<br />
END END<br />
SWITCH SWITCH<br />
FUSE<br />
(3 AMP MAX)<br />
N/O COMN/C<br />
<strong>ZONE</strong> 4 RELAY<br />
MODE<br />
RESET<br />
ZVC 404<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
FOUR <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
N<br />
Pressure<br />
Relief<br />
HEAT<br />
SOURCE<br />
Input from<br />
Heat Source<br />
Exp<br />
Tank<br />
Output to<br />
System<br />
Supply<br />
Sensor<br />
Radiant Manifold - Return<br />
Radiant Manifold - Supply<br />
X - Pump Block Connected to 2 SR502/503 Switching Relays<br />
T<br />
Power<br />
Input<br />
24 VAC<br />
POWER<br />
H<br />
N<br />
SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2<br />
TWO <strong>ZONE</strong> SWITCHING RELAY<br />
FUSE 1 AMP<br />
X2<br />
N P ZC H X1 ZR<br />
T<br />
<strong>ZONE</strong>1<br />
<strong>ZONE</strong>2<br />
Outdoor<br />
Sensor<br />
Boiler<br />
ComSupSysComBoil Out Com Heat<br />
Ret<br />
Dem<br />
H<br />
N<br />
Power<br />
Cord<br />
Boiler Operation<br />
Off-Enable On-Control<br />
XPB<br />
Back of Control<br />
Pump<br />
Power<br />
Input<br />
24 VAC<br />
POWER<br />
H<br />
N<br />
SR 502 <strong>ZONE</strong>1 <strong>ZONE</strong>2<br />
TWO <strong>ZONE</strong> SWITCHING RELAY<br />
FUSE 1 AMP<br />
T<br />
X2<br />
N P ZC H X1 ZR<br />
T<br />
<strong>ZONE</strong>1<br />
<strong>ZONE</strong>2<br />
Pressure<br />
Relief<br />
Return<br />
Sensor<br />
Input from<br />
Heat Source<br />
Exp<br />
Tank<br />
Output to<br />
System<br />
Supply<br />
Sensor<br />
60<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard
Typical Radiant Floor to Water Heater Installation<br />
ASSE 1017<br />
Tempering<br />
Valve<br />
Domestic<br />
Hot<br />
Supply<br />
C<br />
MIX<br />
H<br />
Hot<br />
Cold<br />
Cold<br />
Supply<br />
Check<br />
Valve<br />
X-PUMP<br />
BLOCK<br />
Air<br />
Separator<br />
Exp.<br />
Tank<br />
Supply<br />
Relief<br />
Valve<br />
Return<br />
RADIANT<br />
SYSTEM<br />
(Secondary Side<br />
of the System)<br />
WATER<br />
HEATER<br />
WARNING! A pressure relief valve and expansion tank must be installed on the secondary<br />
side in addition to any pressure relief valve and expansion tank which is installed on primary<br />
side of system. Use dedicated supply and return piping to the X-Pump Block from the water<br />
heater so as not to add heated water into the house’s cold water piping.<br />
Typical Snow Melt Installation<br />
Separator<br />
(Tb)<br />
Exp.<br />
Tank<br />
Note 3<br />
{<br />
Note 1 Note 2<br />
{<br />
Note 3<br />
{<br />
{<br />
X-PUMP<br />
BLOCK<br />
SYSTEM<br />
RETURN<br />
SENSOR<br />
Note 2<br />
{<br />
}<br />
Note 1<br />
(Ts)<br />
Air<br />
Separator<br />
Exp.<br />
Tank<br />
SYSTEM<br />
SUPPLY<br />
SENSOR<br />
Relief<br />
Valve<br />
Return<br />
(ΔTs)<br />
HEAT<br />
SOURCE<br />
HEAT SOURCE<br />
RETURN SENSOR<br />
(OPTIONAL)<br />
FIXED SPEED<br />
CIRCULATOR<br />
(4 PIN PLUG)<br />
VARIABLE SPEED<br />
CIRCULATOR<br />
(3 PIN PLUG)<br />
Supply<br />
SNOW MELT<br />
SYSTEM<br />
Tb = Boiler Supply Temperature<br />
Ts = System Supply Temperature<br />
ΔTs = System Temperature Drop<br />
(typically 20°F for convectors<br />
and 10°F for radiant floor heating)<br />
Note 1: There must be no more than 4 pipe diameters between the tees in the boiler and<br />
system loops in order to prevent ghost flow when the variable speed injection<br />
pump is off and either the boiler pump or system pump is on.<br />
Note 2: There must be at least 6 pipe diameters of straight pipe on either side of the tees in<br />
order to prevent the momentum of water in the boiler and system loops from pushing<br />
flow through the injection loop.<br />
Note 3: There should be a minimum 1 foot drop to create a thermal trap in order to prevent<br />
convective heat transfer through the injection loop.<br />
61
iSeries Mixing Valve<br />
Boiler<br />
Return<br />
Sensor<br />
(optional)<br />
System<br />
Supply<br />
Sensor<br />
Back of<br />
Control<br />
Boiler<br />
Return<br />
Sensor<br />
System<br />
Supply<br />
Sensor<br />
Back of<br />
Control<br />
BOILER<br />
SUPPLY<br />
SETBACK<br />
POWER<br />
GREEN<br />
SENSOR<br />
ERROR<br />
RED<br />
C<br />
R<br />
24 VAC<br />
POWER INPUT<br />
BOILER<br />
SUPPLY<br />
OUTDOOR<br />
POWER<br />
GREEN<br />
SENSOR<br />
ERROR<br />
RED<br />
C<br />
R<br />
24 VAC<br />
POWER INPUT<br />
SENSOR COMMON<br />
SENSOR COMMON<br />
Setback<br />
Input<br />
24 V (ac)<br />
Transformer<br />
or<br />
End<br />
Switch<br />
Outdoor<br />
Sensor<br />
24 V (ac)<br />
Transformer<br />
or<br />
End<br />
Switch<br />
iValve-S<br />
iValve-R<br />
iValve, 2-Way Injection, Single Zone<br />
Outdoor<br />
Sensor<br />
T<br />
Thermostat<br />
BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />
BOILER<br />
POWER<br />
SUPPLY GREEN<br />
OUTDOOR<br />
SENSOR<br />
ERROR<br />
RED<br />
SENSOR<br />
COMMON<br />
24 VAC<br />
POWER INPUT<br />
C R<br />
SR501<br />
1 Z ONE<br />
SWITCHING RELAY<br />
R<br />
T<br />
W<br />
T<br />
120 VAC<br />
INPUT<br />
N 4 N/O N/C<br />
6 N/C<br />
24<br />
VAC<br />
COM<br />
H 3 4 6 5<br />
N/O<br />
24 Volt<br />
Transformer<br />
H<br />
N<br />
Power<br />
Input<br />
iSeries-R<br />
Supply<br />
Sensor<br />
A<br />
B<br />
Boiler<br />
Sensor<br />
62<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard
iValve, 3-Way Mixing Working with SR502/503 Switching Relay with DHW Priority<br />
T<br />
Thermostats<br />
Outdoor<br />
Sensor<br />
BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />
Power<br />
Input<br />
H N<br />
24 VAC<br />
POWER<br />
DHW Aquastat<br />
SR 503<br />
FUSE 1 AMP<br />
A<br />
T<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
BOILER<br />
POWER<br />
SUPPLY GREEN<br />
OUTDOOR<br />
SENSOR<br />
COMMON<br />
24 VAC<br />
POWER INPUT<br />
C R<br />
Transformer<br />
24 Volt<br />
X2<br />
N P ZC H X1 ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
SENSOR<br />
ERROR<br />
RED<br />
DHW<br />
Circ.<br />
Supply<br />
Sensor<br />
B<br />
C<br />
A<br />
C<br />
A<br />
iSeries-R<br />
Boiler<br />
Sensor<br />
iValve, 4-Way Mixing Working with Zone Valve Control<br />
Outdoor<br />
Sensor<br />
BACK OF iVALVE-R MIXING VALVE ACTUATOR<br />
T<br />
T<br />
Thermostats<br />
BOILER<br />
SUPPLY<br />
OUTDOOR<br />
POWER<br />
GREEN<br />
SENSOR<br />
ERROR<br />
RED<br />
SENSOR 24 VAC<br />
COMMON POWER INPUT<br />
C R<br />
24 Volt<br />
Transformer<br />
Power<br />
Input<br />
H<br />
N<br />
Factory<br />
Installed<br />
Transformer<br />
POWER IN<br />
FUSE<br />
(5 AMP MAX)<br />
END N/O COM N/C<br />
SWITCH<br />
TT<br />
<strong>ZONE</strong> 1<br />
ZVC 403<br />
THREE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
<strong>ZONE</strong> 1<br />
1234<br />
TT<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 2<br />
1234<br />
TT<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 3<br />
1234<br />
Motor<br />
M<br />
End Switch<br />
Motor<br />
M<br />
End<br />
Switch<br />
Supply<br />
Sensor<br />
iSeries-R<br />
Boiler<br />
Sensor<br />
FOR ADDITIONAL WIRING DIAGRAMS, PLEASE SEE www.taco-hvac.com/wiringwizard<br />
63
Wiring for Boilers with Honeywell Control Center Model R8285 or Equivalent<br />
TACO LTR0243T-1<br />
FEMALE<br />
CONNECTOR<br />
FACTORY<br />
WIRING<br />
WH<br />
RED<br />
YEL<br />
GRN<br />
YEL<br />
MALE<br />
CONNECTOR<br />
GROUND<br />
CONNECTION<br />
Alternate<br />
Wiring<br />
TACO LTR0243T-1<br />
WH RED YEL GRN<br />
YEL<br />
24 VAC<br />
CLASS 2<br />
TRANSFORMER<br />
HOT<br />
LIMIT<br />
<strong>CONTROLS</strong><br />
120<br />
VAC<br />
24 VAC<br />
GAS<br />
VALVE<br />
COMMON<br />
64
Wiring Boilers with a United Technologies Integrated Control Module and a <strong>Taco</strong> LTR0243U-1<br />
INTEGRATED BOILER<br />
CONTROL<br />
MALE<br />
CONNECTOR<br />
FACTORY WIRING<br />
FEMALE<br />
CONNECTOR<br />
BOILER MODULE<br />
WIRING HARNESS<br />
Wiring Boilers with a United Technologies Ucontrol or other Integrated Control Modules<br />
which accept a 4-pin harness and a <strong>Taco</strong> LTR0243L-1<br />
4-PIN CONNECTOR (#1)<br />
4-PIN CONNECTOR (#2)<br />
WIRING HARNESS<br />
INTEGRATED<br />
CONTROL<br />
MODULE<br />
Wiring Instructions<br />
1. Plug the 4-pin connector on the wiring harness (#1 as<br />
shown) into the integrated control module.<br />
2. Plug the 4-pin connector on the wiring harness (#2 as<br />
shown) into the LTR.<br />
65
Wiring <strong>Taco</strong> LN and LTA-2 Series Low Water Cutoffs<br />
Using Burner Circuit Power Source<br />
*<br />
*Factory Installed<br />
NOTE: For 24 VAC models, LNA024xx and LTA0243S-2, 24 VAC to<br />
be supplied by an EXTERNAL Class 2 power source to terminals<br />
H and N. For 120 VAC models, LNA120xx and LTA1203S-2, 120 VAC<br />
is supplied by an external circuit to terminals H and N.<br />
Wiring <strong>Taco</strong> LN and LTA-2 Series Low Water Cutoffs<br />
Using Power Source Other Than Burner Circuit<br />
NOTE: For 24 VAC models, LNA024xx and LTA0243S-2, 24 VAC to<br />
be supplied by an EXTERNAL Class 2 power source to terminals<br />
H and N. For 120 VAC models, LNA120xx and LTA1203S-2, 120 VAC<br />
is supplied by an external circuit to terminals H and N.<br />
66
Wiring <strong>Taco</strong> LT Series (1st generation, -1) Low Water Cutoffs<br />
Using Burner Circuit Power Source<br />
*<br />
*Factory Installed<br />
NOTE: For 24 VAC models, LTx024xx-1, 24 VAC to be supplied<br />
by an EXTERNAL Class 2 power source to terminals H and N.<br />
For 120 VAC models, LTx120xx-1, 120 VAC is supplied by an<br />
external circuit to terminals H and N.<br />
Wiring <strong>Taco</strong> LT Series (1st generation, -1) Low Water Cutoffs<br />
Using Power Source Other Than Burner Circuit<br />
NOTE: For 24 VAC models, LTx024xx-1, 24 VAC to be supplied<br />
by an EXTERNAL Class 2 power source to terminals H and N.<br />
For 120 VAC models, LTx120xx-1, 120 VAC is supplied by an<br />
external circuit to terminals H and N.<br />
67
Wiring <strong>Taco</strong> LF Series Low Water Cutoffs Using Burner Circuit Power Source<br />
NOTE: Remote probe available on remote probe models only.<br />
NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.<br />
For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.<br />
Wiring <strong>Taco</strong> LF Series Low Water Cutoffs Using Power Source Other Than Burner Circuit<br />
NOTE: For 24 VAC models, LFx024xx, 24 VAC to be supplied by an EXTERNAL Class 2 power source to terminals H and N.<br />
For 120 VAC models, LFx120xx, 120 VAC is supplied by an external circuit to terminals H and N.<br />
68
<strong>Taco</strong> Low Water Cutoff Replacement Guide<br />
<strong>Taco</strong> McDonnell & Miller Hydrolevel Honeywell<br />
LFA1203S-1<br />
LTA1203N-1<br />
LTA1203S-1<br />
LFM1203S-1<br />
LTM1203N-1<br />
LTM1203S-1<br />
LFA0243S-1<br />
LTA0243N-1<br />
LTA0243S-1<br />
LFM0243S-1<br />
LTM0243N-1<br />
LTM0243S-1<br />
LFA1203R-1<br />
LTA1203R-1<br />
LFM1203R-1<br />
LTM1203R-1<br />
LFA1202R-1<br />
LTA1202R-1<br />
LFM1202R-1<br />
LTM1202R-1<br />
LFA0242R-1<br />
LTA0242R-1<br />
LTA0243S-2<br />
LNA0243S-1<br />
LTA1203S-2<br />
LNA1203S-1<br />
LTR0243T-1<br />
P3R-1<br />
EWF120<br />
EWF024<br />
PS-801-120<br />
PSE-801-120<br />
PS-800-120<br />
PS-850-120<br />
900<br />
900C<br />
PS-801-M-120<br />
PS-851-M-120<br />
PS-851-SP-M-120<br />
PS-850-M-120<br />
900M<br />
901M<br />
902M<br />
PS-802-24<br />
PSE-802-24<br />
PS-800-24<br />
PS-850-24<br />
PS-802-M-24<br />
PS-852-M-24<br />
PS-852-SP-M-24<br />
PS-850-M-24<br />
750-T-120<br />
750-120<br />
750-MT-120<br />
750-M-120<br />
PS-851-RX2-120<br />
PS-851-M-RX2-120<br />
PS-802-RX2-24<br />
PS-852-24<br />
PS-852-SP-24<br />
750-MT-SP-24<br />
750P-MT-24<br />
750P-MT-U-24<br />
RB-120<br />
RB-122E<br />
PS-851-120<br />
PS-851-SP-120<br />
750P-MT-120<br />
750P-MT-SP-120<br />
750P-MT-U-120<br />
901<br />
RB-120II<br />
RB-122<br />
RB-24E<br />
RB-24<br />
RS-1-BR-1<br />
RS-1-LP<br />
RS-1-LP-S<br />
WFE-120<br />
WF2-U-120V<br />
WF-2-120<br />
WF-4-120<br />
WFE-24<br />
WF2-U-24V<br />
WF-2-24<br />
WF-4-24<br />
Bold / Italics Indicates Discontinued Part Number<br />
450<br />
CG450<br />
CGT450<br />
OEM170TD<br />
550<br />
550SV<br />
750<br />
OEM170MC<br />
OEM170M<br />
400<br />
CG400<br />
OEM24TD<br />
500<br />
500SV<br />
700<br />
OEM24MC<br />
650R<br />
550R<br />
650R<br />
550R<br />
400R<br />
24<br />
24SV<br />
600<br />
600SV<br />
OEM24C<br />
170<br />
170SV<br />
1150<br />
650<br />
650SV<br />
OEM170C<br />
OEM170<br />
1100<br />
EL1214-R<br />
VRTX-120<br />
V-120-1&2<br />
VRTX-24<br />
V-24-1&2<br />
RW700A1031<br />
RW700A1056<br />
RW700A1080<br />
RW700B1054<br />
RW700B1039<br />
RW700B1021<br />
RW700A1098<br />
RW700A1007<br />
RW700A1006<br />
VW400A1004<br />
VW800A1004<br />
69
<strong>Taco</strong> LF Series 120 Volt LWCO Competitive Wiring Cross Reference<br />
120 VAC Models with 120 VAC Burner Circuits<br />
NC<br />
TACO LFx120x<br />
NO COM H N GND P<br />
McDONNELL & MILLER<br />
PS-801/851-120<br />
w/Red & Amber LEDs<br />
Series 750<br />
1 2 3 4 5<br />
BURNER<br />
CIRCUIT<br />
FACTORY<br />
INSTALLED<br />
JUMPER<br />
120 VAC<br />
CIRCUIT<br />
HOT<br />
NEUTRAL<br />
HOT<br />
NEUTRAL<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HYDROLEVEL<br />
450, 550, 650 & 750<br />
McDONNELL & MILLER<br />
PS-801/851-120<br />
w/Red & Green LEDs<br />
2 1 P1 P2 A<br />
N H C W B<br />
HOT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
NEUTRAL<br />
120 VAC Models with 24 VAC Burner Circuits<br />
NC<br />
TACO LFx120x<br />
NO COM H N GND P<br />
McDONNELL & MILLER<br />
PS-801/851-120<br />
w/Red & Amber LEDs<br />
Series 750<br />
1 2 3 4 5<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
HOT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
24 VAC<br />
TRANSFORMER<br />
NEUTRAL<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
HYDROLEVEL<br />
450, 550, 650 & 750<br />
McDONNELL & MILLER<br />
PS-801/851-120<br />
w/Red & Green LEDs<br />
2 1 P1 P2 A<br />
N H C W B<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
70
<strong>Taco</strong> LF Series 24 Volt LWCO Competitive Wiring Cross Reference<br />
24 VAC Models with 24 VAC Burner Circuits<br />
TACO LFx024x<br />
NC<br />
NO COM H N GND P<br />
BURNER<br />
CIRCUIT<br />
FACTORY<br />
INSTALLED<br />
JUMPER<br />
24 VAC<br />
CIRCUIT<br />
HOT<br />
NEUTRAL<br />
HYDROLEVEL<br />
400, 500, 600 & 700<br />
McDONNELL & MILLER<br />
PS-802/852-24<br />
2 1 P1 P2 A<br />
N H C W B<br />
HOT<br />
HOT<br />
24 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
24 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
NEUTRAL<br />
24 VAC Models with 120 VAC Burner Circuits<br />
TACO LFx024x<br />
NC<br />
NO COM H N GND P<br />
BURNER<br />
CIRCUIT<br />
24 VAC<br />
TRANSFORMER<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
NEUTRAL<br />
HYDROLEVEL<br />
400, 500, 600 & 700<br />
2 1 P1 P2 A<br />
McDONNELL & MILLER<br />
PS-802/852-24<br />
N H C W B<br />
HOT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
BURNER<br />
CIRCUIT<br />
71
<strong>Taco</strong> LTA-2 Series 120 Volt LWCO Competitive Wiring Cross Reference<br />
120 VAC Models with 120 VAC Burner Circuits<br />
TACO LTA1203S-2<br />
N H COM NC NO<br />
McDONNELL & MILLER<br />
RB-120<br />
1 2 3 4 5<br />
HOT<br />
HOT<br />
NEUTRAL<br />
120 VAC<br />
CIRCUIT<br />
FACTORY<br />
INSTALLED<br />
JUMPER<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
McDONNELL & MILLER<br />
RB-122E<br />
N H B C<br />
HYDROLEVEL 1150<br />
CUT-OFF<br />
H N<br />
HYDROLEVEL 170<br />
GN H P1 P2 A<br />
HOT<br />
HOT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
NEUTRAL<br />
NEUTRAL<br />
120 VAC Models with 24 VAC Burner Circuits<br />
TACO LTA1203S-2<br />
McDONNELL & MILLER<br />
RB-120<br />
N H COM NC NO<br />
1 2 3 4 5<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
McDONNELL & MILLER<br />
RB-122E<br />
HYDROLEVEL 1150<br />
HYDROLEVEL 170SV<br />
N H B C H N<br />
CUT-OFF<br />
GN H P1 P2 A<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
NEUTRAL<br />
24 VAC<br />
TRANSFORMER<br />
72
<strong>Taco</strong> LTR and LTA-2 Series 24 Volt LWCO Competitive Wiring Cross Reference<br />
24 VAC Models with 24 VAC Burner Circuits<br />
TACO LTA0243S-2<br />
N H COM NC NO<br />
McDONNELL & MILLER<br />
RB-24E<br />
Red<br />
Wire<br />
White<br />
Wire<br />
Yellow<br />
Wire<br />
Yellow<br />
Wire<br />
HOT<br />
HOT<br />
NEUTRAL<br />
24 VAC<br />
CIRCUIT<br />
FACTORY<br />
INSTALLED<br />
JUMPER<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
24 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
Red<br />
Wire<br />
TACO LTR0243T-1<br />
White<br />
Wire<br />
Yellow<br />
Wire<br />
Yellow<br />
Wire<br />
HYDROLEVEL 1100<br />
Red<br />
Wire<br />
White<br />
Wire<br />
Yellow<br />
Wire<br />
Yellow<br />
Wire<br />
HYDROLEVEL 24<br />
2 1 P1 P2 A<br />
HOT<br />
24 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
24 VAC<br />
CIRCUIT<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
24 VAC<br />
CIRCUIT<br />
JUMPER<br />
BURNER<br />
CIRCUIT<br />
NEUTRAL<br />
NEUTRAL<br />
NEUTRAL<br />
24 VAC Models with 120 VAC Burner Circuits<br />
TACO LTA0243S-2<br />
HYDROLEVEL 24<br />
N H COM NC NO<br />
2 1 P1 P2 A<br />
HOT<br />
HOT<br />
120 VAC<br />
CIRCUIT<br />
NEUTRAL<br />
BURNER<br />
CIRCUIT<br />
120 VAC<br />
CIRCUIT<br />
NEUTRAL<br />
BURNER<br />
CIRCUIT<br />
24 VAC<br />
TRANSFORMER<br />
24 VAC<br />
TRANSFORMER<br />
73
Wiring <strong>Taco</strong> LF Series Low Water Cutoffs<br />
to <strong>Taco</strong> Electric Water Feeder with the Same Voltages<br />
EWF Standard Wiring<br />
<strong>Taco</strong> LFx120x / LFx024x<br />
NC NO COM H N<br />
GND<br />
P<br />
HOT<br />
BURNER<br />
CIRCUIT<br />
FACTORY<br />
INSTALLED<br />
JUMPER<br />
120 V AC / 24 V AC<br />
CIRCUIT<br />
NEUTRAL<br />
LW<br />
N<br />
H<br />
<strong>Taco</strong> E W F120 / E W F024<br />
Wiring <strong>Taco</strong> LF Series Low Water Cutoffs<br />
to <strong>Taco</strong> Electric Water Feeder with Different Burner Voltages<br />
EWF Alternate Wiring<br />
<strong>Taco</strong> LFx120x<br />
<strong>Taco</strong> LFx024x<br />
NC NO COM H N<br />
GND<br />
P<br />
NC<br />
NO COM H N GND P<br />
BURNER<br />
CIRCUIT<br />
HOT<br />
* *<br />
BURNER<br />
120 VAC<br />
CIRCUIT<br />
CIRCUIT<br />
NEUTRAL<br />
HOT<br />
24 V AC<br />
CIRCUIT<br />
NEUTRAL<br />
HOT<br />
HOT<br />
H<br />
N<br />
LW<br />
24 V AC<br />
CIRCUIT<br />
H<br />
N<br />
LW<br />
120 VAC<br />
CIRCUIT<br />
<strong>Taco</strong> EW F024<br />
NEUTRAL<br />
<strong>Taco</strong> EW F120<br />
NEUTRAL<br />
* NOTE: Remove factory installed<br />
jumper between H and COM terminals<br />
74
Wiring <strong>Taco</strong> 24VAC Electric Water Feeder to <strong>Taco</strong> LF Series 24VAC Low Water Cutoff<br />
or 24VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs<br />
McDonnell & Miller<br />
PS-802/852-24<br />
B<br />
W<br />
C<br />
H<br />
N<br />
Hydrolevel<br />
400, 500, 600, & 700<br />
P2<br />
A<br />
P1<br />
1<br />
2<br />
<strong>Taco</strong> LFx024x<br />
NC NO COM H N GND P<br />
BURNER<br />
CIRCUIT<br />
INSTALLED<br />
JUMPER **<br />
HOT<br />
24 V AC<br />
CIRCUIT<br />
** May be factory installed on<br />
some LW COs<br />
LW<br />
N<br />
<strong>Taco</strong> EWF024<br />
H<br />
NEUTRAL<br />
NOTE: Wiring shown only for control<br />
and burner circuits of the same<br />
voltage. Some terminal designations<br />
are not in their actual order on the<br />
LW COs.<br />
Wiring <strong>Taco</strong> 120VAC Electric Water Feeder to <strong>Taco</strong> LF Series 120VAC Low Water Cutoff<br />
or 120VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs<br />
McDonnell & Miller<br />
PS-801/851-120 w/Red &<br />
Am ber LE Ds, Series 750<br />
5<br />
4<br />
3<br />
1 2<br />
McDonnell & Miller<br />
PS-801/851-120<br />
w/Red & Green LEDs<br />
B<br />
W<br />
C<br />
H<br />
N<br />
Hydrolevel<br />
450, 550, 650, & 750<br />
P2<br />
A<br />
P1<br />
1<br />
2<br />
<strong>Taco</strong> LFx120x<br />
NC NO COM H N GND P<br />
HOT<br />
** May be factory installed on<br />
some LW COs<br />
BURNER<br />
CIRCUIT<br />
INSTALLED<br />
JUMPER **<br />
120 V AC<br />
CIRCUIT<br />
NEUTRAL<br />
NOTE: Wiring shown only for control<br />
and burner circuits of the same<br />
voltage. Some terminal designations<br />
are not in their actual order on the<br />
LW COs.<br />
LW<br />
N<br />
H<br />
<strong>Taco</strong> EWF120<br />
75
Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to<br />
McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder<br />
UNI-MATCH<br />
WATER FEEDER<br />
MODEL WF2-U-24<br />
1 2 3<br />
0R<br />
W N H<br />
SWITCH POSITION #2<br />
M&M<br />
2<br />
3<br />
24VAC<br />
SUPPLY<br />
50/60 Hz<br />
N<br />
H<br />
BURNER<br />
Note on switch position:<br />
Switch setting 1 (M&M), the feed cycle repeats<br />
indefinitely. Position 2 and 3 gives one feed cycle.<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
24 VAC LWCO Using Burner Circuit Power Source<br />
Remove jumper between H and COM if using power source<br />
other than burner circuit or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
If using the LTA-2 series, choose whichever position<br />
best matches the application:<br />
WF-2 switch to position 1<br />
- 60 sec. delay, 90 sec. feed, repeats<br />
WF-2 switch to position 2<br />
- 90 sec. delay, 90 sec. feed<br />
WF-2 switch to position 3<br />
- 100 sec. delay, 90 sec. feed<br />
Wiring TACO LTA-2 or LF Series 120VAC Low Water Cutoff to<br />
McDonnell & Miller Series WF2 Uni-Match Electric Water Feeder<br />
UNI-MATCH<br />
WATER FEEDER<br />
MODEL WF2-U-120<br />
1 2 3<br />
0R<br />
W N H<br />
SWITCH POSITION #2<br />
M&M<br />
2<br />
3<br />
120VAC N<br />
SUPPLY<br />
50/60 Hz H<br />
BURNER<br />
Note on switch position:<br />
Switch setting 1 (M&M), the feed cycle repeats<br />
indefinitely. Position 2 and 3 gives one feed cycle.<br />
76<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
120 VAC LWCO Using Burner Circuit Power Source<br />
Remove jumper between H and COM if using power source<br />
other than burner circuit or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
If using the LTA-2 series, choose whichever position<br />
best matches the application:<br />
WF-2 switch to position 1<br />
- 60 sec. delay, 90 sec. feed, repeats<br />
WF-2 switch to position 2<br />
- 90 sec. delay, 90 sec. feed<br />
WF-2 switch to position 3<br />
- 100 sec. delay, 90 sec. feed
Wiring TACO LF Series 24VAC Low Water Cutoff to<br />
Hydrolevel VXT-24 Water Feeder (Non-Display Model)<br />
SAFGARD VXT-24<br />
WATER FEEDER<br />
Set Safgard as desired.<br />
WHITE<br />
BLACK<br />
24VAC N<br />
SUPPLY<br />
50/60 Hz H<br />
BURNER<br />
Remove jumper between H and COM if using<br />
power source other than burner circuit<br />
or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
24 VAC LWCO Using Burner Circuit Power Source<br />
Wiring TACO LF Series 120VAC Low Water Cutoff to<br />
Hydrolevel VXT-120 Water Feeder (Non-Display Model)<br />
SAFGARD VXT-120<br />
WATER FEEDER<br />
Set Safgard as desired.<br />
WHITE<br />
BLACK<br />
120VAC N<br />
SUPPLY<br />
50/60 Hz H<br />
BURNER<br />
Remove jumper between H and COM if using<br />
power source other than burner circuit<br />
or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
120 VAC LWCO Using Burner Circuit Power Source<br />
77
Wiring TACO LTA-2 or LF Series 24VAC Low Water Cutoff to<br />
Hydrolevel VXT-24 Programmable Water Feeder (Model with Display)<br />
SAFGARD VRTX-24<br />
WATER FEEDER<br />
Set Safgard as desired.<br />
WHITE<br />
BLACK<br />
RED<br />
24VAC N<br />
SUPPLY<br />
50/60 Hz H<br />
BURNER<br />
Remove jumper between H and COM if using<br />
power source other than burner circuit<br />
or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
24 VAC LWCO Using Burner Circuit Power Source<br />
Wiring TACO LTA-2 or LF Series 120VAC Low Water Cutoff to<br />
Hydrolevel VXT-120 Programmable Water Feeder (Model with Display)<br />
SAFGARD VRTX-120<br />
WATER FEEDER<br />
Set Safgard as desired.<br />
WHITE<br />
BLACK<br />
RED<br />
120VAC N<br />
SUPPLY<br />
50/60 Hz H<br />
BURNER<br />
Remove jumper between H and COM if using<br />
power source other than burner circuit<br />
or when using mixed voltages.<br />
Do not connect feeder to a manual reset LWCO.<br />
N H COM NC NO<br />
AC POWER OUTPUT CONTACTS<br />
120 VAC LWCO Using Burner Circuit Power Source<br />
78
<strong>Taco</strong> LTR, LN, LT-1, LTA-2 & LF Series Low Water Cutoff and <strong>Taco</strong> Electric Water Feeder Wiring Cross Reference<br />
Power Connections Output Contacts Remote Probes<br />
Probe<br />
Preference<br />
To EWF’s LW<br />
Terminal/Alarm<br />
To Burner<br />
Circuit<br />
Manufacturer Device or Series<br />
Probe<br />
Hot Neutral Common<br />
<strong>Taco</strong> LF & LT-1 Series H N COM NC NO P GND<br />
<strong>Taco</strong> LTA-2 & LN Series H N COM NC NO — —<br />
<strong>Taco</strong> LTR Series Red Wire White Wire Yellow Wire Yellow Wire — — —<br />
PS-801/851 (Older Models<br />
w/Red & Amber LEDs)<br />
1 2 3 5 4 P or J2 Chassis GND<br />
PS-801/851 (New Models<br />
w/Red & Green LEDs)<br />
H N C B W J2 Chassis GND<br />
PS-802/852 (Older Models<br />
w/Red & Amber LEDs)<br />
H N C B W J7 Chassis GND<br />
PS-802/852 (Older Models<br />
w/Red & Green LEDs)<br />
H N C B W J3 Chassis GND<br />
McDonnell & Miller<br />
McDonnell & Miller<br />
McDonnell & Miller<br />
McDonnell & Miller<br />
McDonnell & Miller Series 750 1 2 3 5 4 P Chassis GND<br />
— — —<br />
B<br />
(Yellow Wire)<br />
C<br />
(Yellow Wire)<br />
N<br />
(White Wire)<br />
H<br />
(Black Wire)<br />
McDonnell & Miller RB-122<br />
McDonnell & Miller RB-120 1 2 3 4 5 — —<br />
McDonnell & Miller RB-24 Red Wire White Wire Yellow Wire Yellow Wire — — —<br />
Hydrolevel 24 1 2 P1 P2 A — —<br />
Hydrolevel 170 H GN P1 P2 A — —<br />
Hydrolevel 1100 Red Wire White Wire Yellow Wire Yellow Wire — — —<br />
— — —<br />
CUT-OFF<br />
(Yellow Wire)<br />
CUT-OFF<br />
(Yellow Wire)<br />
N<br />
(White Wire)<br />
H<br />
(Black Wire)<br />
Hydrolevel 1150<br />
1 2 P1 P2 A H3 Chassis GND<br />
400, 500, 600, 700, 450,<br />
550, 650, 750<br />
RW700 Series<br />
(Except RW700A1098)<br />
Hydrolevel<br />
Green Wire<br />
2 Red Wires,<br />
White Wire<br />
L1 L2 — B A<br />
Hydrolevel<br />
Green Wire<br />
2 Red Wires,<br />
White Wire<br />
Hydrolevel RW700A1098 T1 T2 — B A<br />
79
Aquastat Wiring<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1 L2 T T<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C1<br />
ZC<br />
B2 C2 ZR B1<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8124A & C OR EQUAL<br />
MILLI-VOLTAGE<br />
GAS VALVE<br />
B1 B2 T T<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C<br />
L1<br />
L2<br />
C2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
HONEYWELL L8124B OR EQUAL<br />
TV T Z<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C1<br />
C2<br />
B1<br />
B2<br />
L1<br />
L2<br />
LOW VOLTAGE<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
HONEYWELL L8124E OR EQUAL<br />
80
Aquastat Wiring<br />
TV T Z<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
L1<br />
ZC<br />
L2<br />
ZR<br />
B2<br />
C2<br />
B1<br />
C1<br />
LINE<br />
VOLTAGE<br />
OIL BURNER<br />
RELAY OR<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
HONEYWELL L8124G & L OR EQUAL<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1 L2 T T<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C1<br />
ZC<br />
B2<br />
C2<br />
ZR<br />
B1<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8124M OR EQUAL<br />
L1<br />
(HOT)<br />
L1 L2 T T<br />
3<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C1<br />
C2<br />
B1<br />
B2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8148A OR EQUAL<br />
81
Aquastat Wiring<br />
TV W T<br />
Z<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
C1<br />
C2<br />
B1<br />
B2<br />
L1<br />
L2<br />
LOW VOLTAGE<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
HONEYWELL L8148E OR EQUAL<br />
TV W T<br />
TP<br />
Z<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
MILLI-<br />
VOLTAGE<br />
GAS<br />
VALVE<br />
B1<br />
B2<br />
B3<br />
C1<br />
L1<br />
C2<br />
L2<br />
OR<br />
LOW VOLTAGE<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
HONEYWELL L8148J OR EQUAL<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1<br />
L2<br />
B1<br />
B2<br />
C2<br />
C1<br />
OIL BURNER<br />
AND<br />
IGNITION<br />
END SWITCH<br />
TACO<br />
<strong>ZONE</strong><br />
CONTROL<br />
ZC<br />
ZR<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
T<br />
T<br />
F<br />
F<br />
CAD CELL<br />
HONEYWELL L8182D OR EQUAL<br />
82
Aquastat Wiring<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1 L2 T T<br />
T<br />
THERMOSTAT<br />
(IF INDEPENDENT <strong>ZONE</strong>)<br />
END SWITCH<br />
X X<br />
TACO<br />
SWITCHING<br />
RELAY<br />
ZC ZR N H<br />
C1<br />
ZC<br />
B2 C2 ZR B1<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8124A & C OR EQUAL<br />
T<br />
THERMOSTAT<br />
(IF INDEPENDENT <strong>ZONE</strong>)<br />
TV T Z<br />
END SWITCH<br />
X X<br />
TACO<br />
SWITCHING<br />
RELAY<br />
ZC ZR N H<br />
ZC<br />
ZR<br />
B1<br />
L1<br />
(HOT)<br />
L1<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L2<br />
B2<br />
C2<br />
C1<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE<br />
VOLTAGE<br />
OIL BURNER<br />
RELAY OR<br />
GAS VALVE<br />
HONEYWELL L8124G & L OR EQUAL<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1 L2 T T<br />
T<br />
THERMOSTAT<br />
(IF INDEPENDENT <strong>ZONE</strong>)<br />
END SWITCH<br />
X X<br />
TACO<br />
SWITCHING<br />
RELAY<br />
ZC ZR N H<br />
C1<br />
ZC<br />
B2 C2 ZR B1<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8124M OR EQUAL<br />
83
Aquastat Wiring<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
R<br />
W<br />
B<br />
L1 L2 T T<br />
3<br />
B2<br />
B<br />
T<br />
THERMOSTAT<br />
(IF INDEPENDENT <strong>ZONE</strong>)<br />
END SWITCH<br />
X X<br />
TACO<br />
SWITCHING<br />
RELAY<br />
ZC ZR N H<br />
L6006<br />
LOW<br />
LIMIT<br />
CONTROLER<br />
C1<br />
C2<br />
R<br />
B1<br />
B2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
LINE VOLTAGE<br />
OIL BURNER RELAY<br />
OR GAS VALVE<br />
HONEYWELL L8148A OR EQUAL<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
L1<br />
L2<br />
B1<br />
B2<br />
C2<br />
C1<br />
ZC<br />
OIL BURNER<br />
AND<br />
IGNITION<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
END SWITCH<br />
X X<br />
TACO<br />
SWITCHING<br />
RELAY<br />
ZC ZR N H<br />
ZR<br />
T<br />
T<br />
F<br />
F<br />
T<br />
THERMOSTAT<br />
(IF INDEPENDENT<br />
<strong>ZONE</strong>)<br />
CAD CELL<br />
HONEYWELL L8182D OR EQUAL<br />
84
Wiring for Boilers with Honeywell Aquastat Model L8124E or Equivalent<br />
FACTORY WIRING<br />
(unplug from B1 terminal)<br />
TACO LTR0243T-1<br />
WH RED YEL GRN YEL<br />
TV T Z<br />
HONEYWELL<br />
L8124E<br />
C1<br />
C2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
MALE<br />
CONNECTOR<br />
B1<br />
G<br />
B2<br />
L1<br />
L2<br />
FEMALE<br />
CONNECTOR<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
NOTE: The green wire must be connected to a ground source<br />
electrically common to the boiler ground.<br />
Wiring for Boilers with Honeywell Aquastat Model L8148E or Equivalent<br />
FACTORY WIRING<br />
(unplug from B1 terminal)<br />
TACO LTR0243T-1<br />
WH RED YEL GRN<br />
YEL<br />
TV W T<br />
Z<br />
HONEYWELL<br />
L8148E<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
MALE<br />
CONNECTOR<br />
B1<br />
B2<br />
C1<br />
C2<br />
G<br />
L1<br />
L2<br />
FEMALE<br />
CONNECTOR<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
NOTE: The green wire must be connected to a ground source<br />
electrically common to the boiler ground.<br />
85
Aquastat Wiring to 24VAC Low Water Cutoff<br />
TO<br />
THERMOSTAT<br />
TACO LNA024 or LTA024-2<br />
N H COM NC NO<br />
TV W T<br />
HONEYWELL<br />
L8148E<br />
Z<br />
B<br />
R<br />
C1<br />
C2<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
B1<br />
B2<br />
L1<br />
L2<br />
G<br />
SPILL<br />
SWITCH<br />
LOW VOLTAGE<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)<br />
Aquastat Wiring to 120VAC Low Water Cutoff<br />
TO<br />
THERMOSTAT<br />
TACO LNA120 OR LTA120-2<br />
N H COM NC NO<br />
TV W T<br />
Z<br />
B<br />
HONEYWELL<br />
L8148E<br />
CIRCULATOR<br />
ON BOILER<br />
(IF ATTACHED)<br />
R<br />
C1<br />
C2<br />
B1<br />
B2<br />
L1<br />
L2<br />
G<br />
SPILL<br />
SWITCH<br />
86<br />
LOW VOLTAGE<br />
GAS VALVE<br />
L1<br />
(HOT)<br />
120 VAC<br />
INPUT<br />
L2<br />
(NEUTRAL)
Instruction Sheet<br />
SR501 Switching Relay<br />
Features:<br />
External Indicator Lights<br />
Universal Replaceability<br />
Snap-in PC Board<br />
Simplified Wiring<br />
Fully Enclosed Snap-Out Relays<br />
100% Factory Tested<br />
Contractor Friendly PC Board Layout<br />
Universal Thermostat Compatibility<br />
UL Approved<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Typical<br />
Wiring<br />
SR501<br />
1 <strong>ZONE</strong> SWITCHING RELAY<br />
THERMOSTAT<br />
24<br />
R W VAC<br />
T T COM<br />
POWER<br />
T STAT<br />
Alternative<br />
Wiring<br />
SR501<br />
1 <strong>ZONE</strong> SWITCHING RELAY<br />
THERMOSTAT<br />
24<br />
R W VAC<br />
T T COM<br />
POWER<br />
T STAT<br />
Operation:<br />
Connect a thermostat to the “T T” terminals on<br />
the switching relay. When the thermostat calls for<br />
heat, the relay is energized and power is given to the<br />
circulator.<br />
120 VAC<br />
INPUT<br />
N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />
JUMPER<br />
120 VAC<br />
INPUT<br />
N H 3 4 4 6 6 N/O N/C N/C N/O 5<br />
Power Input:<br />
Connect 120 volt ac power to terminals N and H.<br />
TO: 120 VAC POWER<br />
TO: TT ON BOILER<br />
CIRCULATOR<br />
TO: ZC<br />
TO: ZR<br />
TO: 120 VAC POWER<br />
CIRCULATOR<br />
Jumper Placement:<br />
The jumper is factory installed between terminals H<br />
and 3 to switch power on terminals 4 n/o and 4 n/c.<br />
External Diagnostics:<br />
The External lights show full functionality of the<br />
switching relay. The green light should always be on,<br />
indicating that power is connected. When the thermostat<br />
calls for heat, both the appropriate circulator<br />
and red indicating light is energized.<br />
The <strong>Taco</strong> Connection:<br />
Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />
Priority Zoning Circulators, Thermostats, and the “00”<br />
family of circulators with the advanced features of the<br />
<strong>Taco</strong> Zone Controls to achieve total system integration.<br />
No matter the application, <strong>Taco</strong> now provides<br />
the products to maximize system performance while<br />
simplifying both installation and service.<br />
Note: When using Alternative Wiring diagram, the boiler operating control’s<br />
ZC terminal will see the load of the circulator(s).<br />
Warning: When using Alternative Wiring diagram, wiring instructions<br />
must be followed so power originates from the boiler aquastat. Failure to<br />
follow these wiring instructions may result in a secondary source of power<br />
being connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Terminal Description:<br />
T & T Thermostat Connection<br />
COM Common side of transformer, to power some setback thermostats<br />
N Neutral wire of power input<br />
H Hot wire of power input<br />
3 Common terminal for 4 n/o and 4 n/c<br />
4 n/o Normally open terminal<br />
4 n/c Normally closed terminal<br />
6 n/c Normally closed terminal<br />
6 n/o Normally open terminal<br />
5 Common terminal for 6 n/o and 6 n/c<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR501 1 Zone 120 VAC Input 7.2 amps 4 1/4" 5 1/4" 2 3/4"<br />
All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single<br />
phase motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />
Warning: Wiring connections must be made in accordance with all applicable electrical<br />
codes and these instructions. Use copper wire only. Failure to follow this<br />
instruction can result in personal injury or death and/or property damage. 10-18<br />
gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22<br />
gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />
wire for 24 VAC source with 5 in.lbs. max torque.<br />
TACO SR501 REPLACEMNENT CROSS-REFERENCE<br />
MANUFACTURER MODEL CONNECTIONS<br />
<strong>Taco</strong> SR501 H N 3 4 NO 4 NC 5 6 NO 6 NC R/T W/T C<br />
Argo AR821 1 2 3 4 5 6 T<br />
AR822 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />
Colombus MR10 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />
Erie SR100 L1 L2 3 4 NO 4 NC 5 6 NO 6 NC R/T G/T C<br />
Honeywell RA89A 1 2 3 4 T T<br />
RA832A 1 2 3 4 X X T T<br />
R845A 1 2 3 4 5 6 T T<br />
White-Rogers 889-189 1 2 3 4 T T<br />
829-845 1 2 3 4 5 6 T T<br />
Do it Once. Do it Right. ®<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.<br />
87
Instruction Sheet<br />
SR501-845RP Universal Replacement Relay<br />
Features:<br />
Universal Replaceability<br />
Indicator Lights<br />
Snap-in PC Board to Existing Enclosure<br />
Simplified Wiring<br />
Fully Enclosed Snap-Out Relay<br />
100% Factory Tested<br />
Universal Thermostat Compatibility<br />
UL Approved<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Operation:<br />
Connect a thermostat to the “T T” terminals on<br />
the switching relay. When the thermostat calls for<br />
heat, the relay is energized and power is given to<br />
the circulator.<br />
Power Input:<br />
Connect 120 volt ac power to terminals L1 and L2.<br />
Typical<br />
Wiring<br />
REPLACES HONEYWELL<br />
R845, RA89A & RA832<br />
OR COMPARABLE RELAY<br />
TO: 120 VAC POWER<br />
JUMPER<br />
R W<br />
T T<br />
UNIVERSAL REPLACEMENT RELAY<br />
MODEL: SR501-845RP<br />
120 VAC<br />
INPUT<br />
L2 L1 3 4 5 6<br />
CIRCULATOR<br />
THERMOSTAT<br />
POWER<br />
T STAT<br />
TO: TT ON BOILER<br />
Alternative<br />
Wiring<br />
REPLACES HONEYWELL<br />
R845, RA89A & RA832<br />
OR COMPARABLE RELAY<br />
TO: ZC<br />
TO: ZR<br />
TO: 120 VAC POWER<br />
120 VAC<br />
INPUT<br />
R W<br />
T T<br />
UNIVERSAL REPLACEMENT RELAY<br />
MODEL: SR501-845RP<br />
L2 L1 3 4 5 6<br />
THERMOSTAT<br />
POWER<br />
T STAT<br />
CIRCULATOR<br />
Jumper Placement:<br />
The jumper is factory installed between terminals<br />
L1 and 3 to switch power on terminal 4.<br />
Diagnostics:<br />
The Indicator lights show full functionality of the<br />
switching relay. The green light should always be<br />
on, indicating that power is connected. When the<br />
thermostat calls for heat, both the appropriate circulator<br />
and red indicating light is energized.<br />
The <strong>Taco</strong> Connection:<br />
Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />
Priority Zoning Circulators, Thermostats, and the<br />
“00” family of circulators with the advanced features<br />
of the <strong>Taco</strong> Zone Controls to achieve total system<br />
integration. No matter the application, <strong>Taco</strong> now provides<br />
the products to maximize system performance<br />
while simplifying both installation and service.<br />
Terminal Description:<br />
T & T Thermostat Connection<br />
L2 Neutral wire of power input<br />
L1 Hot wire of power input<br />
3 Common terminal for 4<br />
4 Normally open terminal<br />
6 Normally open terminal<br />
5 Common terminal for 6<br />
Note: When using Alternative Wiring diagram, the boiler operating control’s<br />
ZC terminal will see the load of the circulator(s).<br />
Warning: When using Alternative Wiring diagram, wiring instructions must<br />
be followed so power originates from the boiler aquastat. Failure to follow<br />
these wiring instructions may result in a secondary source of power being<br />
connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR501-845RP 1 Zone 120 VAC Input 7.2 amps 4 1/4" 5 1/4" 2 3/4"<br />
All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a single phase<br />
motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />
TACO SR501-845RP REPLACEMENT CROSS-REFERENCE<br />
MANUFACTURER MODEL CONNECTIONS<br />
<strong>Taco</strong> SR501-845RP L1 L2 3 4 5 6 R/T W/T<br />
Argo AR821 1 2 3 4 5 6 T<br />
AR822 L1 L2 3 4 NO 5 6 NO R/T G/T<br />
Colombus MR10 L1 L2 3 4 NO 5 6 NO R/T G/T<br />
Erie SR100 L1 L2 3 4 NO 5 6 NO R/T G/T<br />
Honeywell RA89A 1 2 3 4 T T<br />
RA832A 1 2 3 4 X X T T<br />
R845A 1 2 3 4 5 6 T T<br />
White-Rogers 889-189 1 2 3 4 T T<br />
829-845 1 2 3 4 5 6 T T<br />
Warning: Wiring connections must be made in accordance with all applicable electrical<br />
codes and these instructions. Use copper wire only. Failure to follow this<br />
instruction can result in personal injury or death and/or property damage. 10-18<br />
gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22<br />
gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />
wire for 24 VAC source with 5 in.lbs. max torque.<br />
88<br />
Do it Once. Do it Right. ®<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.
Instruction Sheet<br />
SR502 & SR503 Switching Relay<br />
Cold Start Boiler<br />
Application<br />
THERMOSTATS<br />
Tankless Coil Boiler<br />
Application<br />
THERMOSTATS<br />
24 VAC<br />
POWER<br />
24 VAC<br />
POWER<br />
SR 503<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
SR 503<br />
FUSE 1 AMP<br />
N P ZC H<br />
JUMPERS<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
X 2<br />
X 1 ZR <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
X<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
THREE <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
FUSE 1 AMP<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
2<br />
N P ZC H X 1 ZR <strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3<br />
JUMPERS<br />
TO: 120 VAC POWER (NEUTRAL)<br />
TO: 120 VAC POWER (NEUTRAL)<br />
TO: 120 VAC POWER (HOT)<br />
TO: "TT" ON AQUASTAT CONTROL<br />
120 VOLT<br />
CIRCULATORS<br />
TO: 120 VAC POWER (HOT)<br />
TO: "ZC" ON AQUASTAT CONTROL<br />
120 VOLT<br />
CIRCULATORS<br />
TO: "TT" ON AQUASTAT CONTROL<br />
TO: "ZR" ON AQUASTAT CONTROL<br />
Note: When using Alternative Wiring diagram, the boiler operating control’s ZC terminal will see the load of the circulator(s).<br />
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Operation: When the thermostat calls for heat, the appropriate circulator<br />
is energized and the isolated end switch (X 1 and X 2 ) will start the<br />
boiler.<br />
Jumper Placement: The jumper should be placed between terminals<br />
ZC and H. Connect the isolated end switch, X 1 and X 2 to the boiler<br />
aquastat control. For zone 1 priority, remove jumper between<br />
terminals P and ZC.<br />
Power Input: Connect 120 volt ac power input to terminals N and H.<br />
Neutral wire to terminal N. Hot wire to terminal H.<br />
Operation: When any thermostat calls for heat, the boiler and appropriate<br />
circulator are energized when the boiler temperature is above the<br />
set low limit.<br />
Jumper Placement: A jumper should be placed between terminals ZC<br />
and X 1 . Connect terminal ZC to ZC terminal on the aquastat control.<br />
Connect terminal ZR to ZR terminal on the aquastat control. Confirm<br />
polarity is consistent between boiler aquastat and switching relay. For<br />
zone 1 priority, remove jumper between terminals<br />
P and ZC.<br />
Power Input: Connect 120 volt ac power input to terminals N and H.<br />
Neutral wire to terminal N. Hot wire to terminal H.<br />
The <strong>Taco</strong> Connection:<br />
Combine the reliability of the <strong>Taco</strong> Zone Valves, Priority Zoning<br />
Circulators, Thermostats, and the “00” family of circulators with the<br />
advanced features of the <strong>Taco</strong> Zone Controls to achieve total system<br />
integration. No matter the application, <strong>Taco</strong> now provides the products<br />
to maximize system performance while simplifying both installation<br />
and service.<br />
External Diagnostics:<br />
Externally visible lights show full functionality of the switching relay.<br />
The green light should always be on, indicating that power is connected.<br />
When the thermostat calls for heat, both the appropriate circulator<br />
and red indicating light is energized.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR502 2 with Priority 120 VAC Input 15 amps 10 1/4" 6 3/4" 2 3/4"<br />
SR503 3 with Priority 120 VAC Input 15 amps 10 1/4" 6 3/4" 2 3/4"<br />
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />
motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />
Do it Once. Do it Right. ®<br />
Features:<br />
External Indicator Lights<br />
Priority<br />
Simplified Wiring<br />
Fully Enclosed Snap-Out Relays<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Contractor Friendly PC Board Layout<br />
Universal Thermostat Compatibility<br />
UL Approved<br />
24 volt Power Input or Output Terminal<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes and these<br />
instructions. Use copper wire only. Failure to follow this instruction can result in personal injury or<br />
death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs.<br />
max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge<br />
wire for 24 VAC source with 5 in.lbs. max torque.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.<br />
89
Instruction Sheet<br />
SR504 & SR506 Switching Relay<br />
Cold Start Boiler<br />
Application<br />
THERMOSTATS<br />
Tankless Coil Boiler<br />
Application<br />
THERMOSTATS<br />
24 VAC<br />
POWER<br />
SR 506<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
ZC ZR<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6 POWER<br />
120 VOLT CIRCULATORS INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
24 VAC<br />
POWER<br />
SR 506<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
POWER<br />
INPUT<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
FUSE 1 AMP<br />
TO: "ZR" ON AQUASTAT<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC INPUT<br />
TO: "ZC" ON AQUASTAT<br />
JUMPER<br />
120 VAC INPUT<br />
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Operation: When any thermostat calls for heat, the appropriate circulator<br />
is energized and the isolated end switch (X and X) will start the<br />
boiler.<br />
Priority Operation: When zone 6 is switched to the priority setting<br />
and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />
When zone 6 is not switched to priority, all zones will operate<br />
independently.<br />
Jumper Placement: The jumper should be placed between terminals<br />
ZC and ZR. Connect the isolated end switch to the aquastat control on<br />
the boiler.<br />
Power Input: Connect 120 volt ac power input to terminals N and H.<br />
Neutral wire to terminal N. Hot wire to terminal H.<br />
Operation: When any thermostat calls for heat, the boiler and appropriate<br />
circulator are energized when the boiler temperature is above the<br />
set low limit.<br />
Priority Operation: When zone 6 is switched to the priority setting<br />
and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />
When zone 6 is not switched to priority, all zones will operate<br />
independently.<br />
Jumper Placement: MOVE the jumper between terminals ZC and ZR<br />
to end switch X and ZC. Connect terminal ZC to ZC terminal on the<br />
aquastat control. Connect the other end switch X to ZR terminal on the<br />
aquastat control. Confirm polarity is consistent between boiler aquastat<br />
and switching relay.<br />
Power Input: Connect 120 volt ac power input to terminals N and H.<br />
Neutral wire to terminal N. Hot wire to terminal H.<br />
The <strong>Taco</strong> Connection:<br />
Combine the reliability of the <strong>Taco</strong> Zone Valves, Priority Zoning<br />
Circulators, Thermostats, and the “00” family of circulators with the<br />
advanced features of the <strong>Taco</strong> Zone Controls to achieve total system<br />
integration. No matter the application, <strong>Taco</strong> now provides the products<br />
to maximize system performance while simplifying both installation<br />
and service.<br />
External Diagnostics:<br />
Externally visible lights show full functionality of the switching relay.<br />
The green light should always be on, indicating that power is connected.<br />
When the thermostat calls for heat, both the appropriate circulator and<br />
red indicating light is energized.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR504 4 with Priority 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />
SR506 6 with Priority 120 VAC Input 20 amps 11 3/4" 7 1/2" 3"<br />
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />
motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />
Do it Once. Do it Right. ®<br />
Visit our web site at: http://www.taco-hvac.com<br />
90<br />
Features:<br />
External Indicator Lights<br />
Switchable Priority<br />
Simplified Wiring<br />
Fully Enclosed Snap-Out Relays<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Contractor Friendly PC Board Layout<br />
Universal Thermostat Compatibility<br />
UL Approved<br />
24 volt Power Input or Output Terminal<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes<br />
and these instructions. Use copper wire only. Failure to follow this instruction can result in personal<br />
injury or death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections<br />
with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs.<br />
max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs. max torque.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.
Instruction Sheet<br />
SR501-EXP Switching Relay<br />
Cold Start Boiler<br />
Application<br />
TO: "TT" on Boiler Aquastat<br />
THERMOSTAT<br />
T<br />
TO: DHW Aquastat if PC700<br />
Boiler Reset is installed.<br />
Tankless Coil Boiler<br />
Application<br />
THERMOSTAT<br />
T<br />
TO: DHW Aquastat if PC700<br />
Boiler Reset is installed.<br />
POWER<br />
<strong>CONTROLS</strong><br />
POWER<br />
<strong>CONTROLS</strong><br />
MODE<br />
MODE<br />
END<br />
RESET<br />
END<br />
RESET<br />
EXPANSION THERMOSTAT<br />
EXPANSION THERMOSTAT<br />
SWITCH<br />
OVERRIDE RESET<br />
SWITCH<br />
OVERRIDE RESET<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
X X 1 2 3 4 T/R T/W COM 1 2<br />
FUSE<br />
K1-A<br />
FUSE<br />
K1-A<br />
MASTER<br />
1 AMP NORMAL<br />
1 AMP MASTER<br />
NORMAL<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
K1<br />
K2<br />
POWER<br />
T STAT<br />
SLAVE<br />
FUSE<br />
5 AMP<br />
K1<br />
K2<br />
POWER<br />
T STAT<br />
SR 501-EXP<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
K1-B K2-A K2-A<br />
120VAC CIRC<br />
OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
SR 501-EXP<br />
N<br />
POWER<br />
INPUT<br />
H ZC ZR H H<br />
120VAC<br />
INPUT<br />
K1-B K2-A K2-A<br />
120VAC CIRC<br />
OUTPUT OUTPUT<br />
PRIORITY<br />
OUTPUT<br />
JUMPER<br />
TO: ZC on Boiler Control<br />
TO: 120 VAC POWER<br />
CIRCULATOR<br />
TO: ZR on Boiler Control<br />
TO: 120 VAC POWER<br />
CIRCULATOR<br />
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Operation: When the thermostat calls for heat, the appropriate circulator is energized<br />
and the isolated end switch (X and X) will start the boiler. Priority Output<br />
has power all the time, except when the thermostat is calling.<br />
Mode Operation: When the mode switch is set to NORMAL, the end switch<br />
relay will be energized if any zone is in operation. When the switch is set to<br />
RESET, the end switch relay will only be energized through the operation of a<br />
plug-in reset control or closure of Priority Input.<br />
Jumper Placement: The jumper should be placed between terminals ZC and H.<br />
Connect the isolated end switch to the aquastat control on the boiler.<br />
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />
wire to terminal N. Hot wire to terminal H.<br />
Expansion Connections: Set the expansion switch to MASTER on the switching<br />
relay that has the designated priority zone or is utilizing the PowerPort options.<br />
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />
using any combination of -EXP controls.<br />
Operation: When the thermostat calls for heat, the appropriate circulator is energized<br />
when the boiler’s aquastat is above the set low limit. The ZR (120VAC) output<br />
will signal the boiler to start. Priority Output has power all the time, except<br />
when the thermostat is calling.<br />
Mode Operation: When the mode switch is set to NORMAL, the end switch<br />
relay will be energized if any zone is in operation. When the switch is set to<br />
RESET, the end switch relay will only be energized through the operation of a<br />
plug-in reset control or closure of Priority Input.<br />
Jumper Placement: REMOVE the jumper between terminals ZC and H. Connect<br />
terminal ZC to ZC terminal on the aquastat control. Connect terminal ZR to ZR<br />
terminal on the aquastat control. Confirm polarity is consistent between boiler<br />
aquastat and switching relay.<br />
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />
wire to terminal N. Hot wire to terminal H.<br />
Expansion Connections: Set the expansion switch to MASTER on the switching<br />
relay that has the designated priority zone or is utilizing the PowerPort options.<br />
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />
using any combination of -EXP controls.<br />
Features: External Indicator Lights<br />
Ideal for Retrofitting<br />
Priority Output<br />
Simplified Wiring<br />
Add-On Power Controls<br />
Sealed Relays<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Expandable to 20 Zones<br />
Contractor Friendly PC Board<br />
Layout<br />
Universal Thermostat<br />
Compatibility<br />
UL Approved<br />
24 volt Power Input or Output<br />
Terminal<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
External Diagnostics: Externally visible lights show full functionality of the<br />
switching relay. The green light should always be on, indicating that power is<br />
connected. When the thermostat calls for heat, both the appropriate circulator<br />
and red indicating light are energized.<br />
Specifications:<br />
PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S <strong>CONTROLS</strong> VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR501-EXP 1 1 120 VAC Input 5.0 amps 4 1/4" 5 1/4" 2 3/4"<br />
All Switching Relays are relay type DPDT, have a thermostat current of .18, and have a<br />
single phase motor rating per zone of 1/3 hp (5.0A) @ 120 VAC.<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only with a minimum temperature rating of 60/75°C. Failure to follow this instruction can<br />
result in personal injury or death and/or property damage. 12-18 gauge wire recommended for 120 VAC connections, 14-22 gauge wire for thermostat connections, and 14-22 gauge wire for 24 VAC source<br />
connections.<br />
Do it Once. Do it Right. ®<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.<br />
91
Instruction Sheet<br />
SR503-EXP, SR504-EXP & SR506-EXP Switching Relay<br />
Cold Start Boiler<br />
Application<br />
THERMOSTATS<br />
Tankless Coil Boiler<br />
Application<br />
THERMOSTATS<br />
EXPANSION<br />
CONNECTIONS<br />
EXPANSION<br />
CONNECTIONS<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
SLAVE<br />
1234<br />
MASTER<br />
PLUG-IN CARDS<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
POWER<br />
CONTROL<br />
INTERFACE<br />
SLAVE<br />
1234<br />
MASTER<br />
PLUG-IN CARDS<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
<strong>ZONE</strong> 6<br />
PRIORITY<br />
ON<br />
OFF<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
RESET<br />
NORMAL<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
SR 506-EXP<br />
POWER<br />
INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
24 VAC<br />
POWER<br />
120V RELAY<br />
X X<br />
END<br />
SWITCH<br />
RESET<br />
NORMAL<br />
SIX <strong>ZONE</strong> SWITCHING RELAY<br />
WITH OPTIONAL PRIORITY<br />
SR 506-EXP<br />
<strong>ZONE</strong>1 <strong>ZONE</strong>2 <strong>ZONE</strong>3 <strong>ZONE</strong>4 <strong>ZONE</strong>5 <strong>ZONE</strong>6 POWER<br />
ZC ZR<br />
120 VOLT CIRCULATORS<br />
INPUT<br />
POWER<br />
<strong>ZONE</strong> 1<br />
<strong>ZONE</strong> 2<br />
<strong>ZONE</strong> 3<br />
<strong>ZONE</strong> 4<br />
<strong>ZONE</strong> 5<br />
<strong>ZONE</strong> 6<br />
FUSE 1 AMP<br />
FUSE 1 AMP<br />
TO: "TT" ON BOILER<br />
JUMPER<br />
120 VAC INPUT<br />
TO: "ZR" ON AQUASTAT<br />
TO: "ZC" ON AQUASTAT<br />
JUMPER<br />
120 VAC INPUT<br />
Warning: When using Alternative Wiring diagram, wiring instructions must be followed so power originates from the boiler aquastat. Failure to<br />
follow these wiring instructions may result in a secondary source of power being connected to the boiler that may activate it under certain circumstances,<br />
causing injury or death.<br />
Operation: When any thermostat calls for heat, the appropriate circulator is<br />
energized and the isolated end switch (X and X) will start the boiler.<br />
Priority Operation: When zone 6 is switched to the priority setting and is actuated,<br />
all other zones will stop operation until zone 6 is satisfied. When zone 6 is<br />
not switched to priority, all zones will operate independently.<br />
Mode Operation: When the mode switch is set to NORMAL, the end switch<br />
relay will be energized if any zone is in operation. When the switch is set to<br />
RESET, the end switch relay will only be energized if priority zone is in operation,<br />
or through the operation of a plug-in reset control.<br />
Jumper Placement: The jumper should be placed between terminals ZC and ZR.<br />
Connect the isolated end switch to the aquastat control on the boiler.<br />
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />
wire to terminal N. Hot wire to terminal H.<br />
Expansion Connections: Set the expansion switch to MASTER on the switching<br />
relay that has the designated priority zone or is utilizing the PowerPort options.<br />
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />
using any combination of -EXP controls.<br />
Operation: When any thermostat calls for heat, the boiler and appropriate circulator<br />
are energized when the boiler temperature is above the set low limit.<br />
Priority Operation: When zone 6 is switched to the priority setting and is actuated,<br />
all other zones will stop operation until zone 6 is satisfied. When zone 6 is<br />
not switched to priority, all zones will operate independently.<br />
Mode Operation: When the mode switch is set to NORMAL, the end switch<br />
relay will be energized if any zone is in operation. When the switch is set to<br />
RESET, the end switch relay will only be energized if priority zone is in operation,<br />
or through the operation of a plug-in reset control.<br />
Jumper Placement: MOVE the jumper between terminals ZC and ZR to end<br />
switch X and ZC. Connect terminal ZC to ZC terminal on the aquastat control.<br />
Connect the other end switch X to ZR terminal on the aquastat control. Confirm<br />
polarity is consistent between boiler aquastat and switching relay.<br />
Power Input: Connect 120 volt ac power input to terminals N and H. Neutral<br />
wire to terminal N. Hot wire to terminal H.<br />
Expansion Connections: Set the expansion switch to MASTER on the switching<br />
relay that has the designated priority zone or is utilizing the PowerPort options.<br />
Set all other daisy chained controls to SLAVE. Connect thermostat wire (18-22<br />
gauge) between terminals 1, 2, 3, 4 on the master control to the corresponding<br />
1, 2, 3, 4 on the SLAVE control(s). Controls may be daisy chained up to 20 zones<br />
using any combination of -EXP controls.<br />
Features: External Indicator<br />
Lights<br />
Plug-In PowerPort Cards<br />
Switchable Priority<br />
Simplified Wiring<br />
Add-On Power Controls<br />
Fully Enclosed Snap-Out<br />
Relays<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Expandable to 20 Zones<br />
Contractor Friendly PC Board<br />
Layout<br />
Universal Thermostat<br />
Compatibility<br />
UL Approved<br />
24 volt Power Input or Output<br />
Terminal<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
External Diagnostics: Externally visible lights show full functionality of the<br />
switching relay. The green light should always be on, indicating that power is<br />
connected. When the thermostat calls for heat, both the appropriate circulator<br />
and red indicating light is energized.<br />
Specifications:<br />
PRODUCT NUMBER POWER TRANSFORMER MAXIMUM DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S PORTS VOLTAGE COMBINED LOAD WIDTH HEIGHT DEPTH<br />
SR503-EXP 3 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />
SR504-EXP 4 with Priority 3 120 VAC Input 20 amps 10 1/4" 6 3/4" 2 3/4"<br />
SR506-EXP 6 with Priority 3 120 VAC Input 20 amps 11 3/4" 7 1/2" 3"<br />
All Switching Relays are relay type DPST, have a thermostat current of .18, and have a single phase<br />
motor rating per zone of 1/3 hp (7.2A) @ 120 VAC.<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes and these instructions. Use copper wire only. Failure to follow this instruction can result in personal injury or<br />
death and/or property damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire<br />
for 24 VAC source with 5 in.lbs. max torque.<br />
92<br />
Do it Once. Do it Right. ®<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2005<br />
TACO, Inc.
Instruction Sheet<br />
ZVC403 & ZVC405 Zone Valve Control<br />
Wiring<br />
Diagram<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
24 VAC<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
Installation of<br />
Optional System<br />
Circulator<br />
END<br />
SWITCH<br />
N/O COM N/C<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
24 VAC<br />
T<br />
T<br />
END<br />
SWITCH<br />
TO CIRCULATOR<br />
OR BOILER<br />
AQUASTAT RELAY<br />
POWER IN<br />
N/O COM N/C<br />
DRY<br />
CONTACTS<br />
FUSE (5 AMP MAX)<br />
T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
ZVC 405<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
JUMPER<br />
3 & 4<br />
FIVE <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
1<br />
2<br />
3<br />
MOTOR END<br />
SWITCH<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
POWER<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
T<br />
T<br />
BOILER<br />
120 VAC<br />
HOT<br />
NEUTRAL<br />
Operation/External Diagnostics: When any thermostat<br />
calls for heat, the appropriate zone valve is energized and<br />
the yellow light goes on. When the zone valve is fully<br />
open, the red light goes on and energizes the end switch<br />
relay. The green light should always be on, indicating that<br />
power is connected.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />
ZVC403 3 Zone 120 VAC Input 40 VA 10 1 ⁄ 4" 6 3 ⁄ 4" 2 3 ⁄ 4"<br />
ZVC405 5 Zone 120 VAC Input 80 VA 11 3 ⁄ 4" 7 1 ⁄ 2" 3"<br />
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of<br />
1 ⁄ 6 hp (5A) @ 120 VAC.<br />
The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong><br />
Zone Valves, Priority Zoning Circulators, Thermostats, and<br />
the “00” family of circulators with the advanced features of<br />
the <strong>Taco</strong> Zone Controls to achieve total system integration.<br />
No matter the application, <strong>Taco</strong> now provides the<br />
products to maximize system performance while simplifying<br />
both installation and service.<br />
Warning: Wiring connections must be made in accordance with all applicable<br />
electrical codes. Use copper wire only. Failure to follow this instruction can result<br />
in personal injury or death and/or property damage. 10-18 gauge wire recommended<br />
for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for<br />
thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24<br />
VAC source with 5 in.lbs. max torque.<br />
Do it Once. Do it Right.<br />
Features:<br />
External Indicator<br />
Lights<br />
Simplified Wiring<br />
Works with 2, 3, or 4-<br />
Wire Zone Valves<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Extra Set of Dry Contacts<br />
Contractor Friendly PC<br />
Board Layout<br />
Universal Thermostat<br />
Compatibility<br />
UL Approved<br />
Sturdy Screw Connections<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.<br />
93
Instruction Sheet<br />
ZVC404 & ZVC406 Zone Valve Control<br />
Wiring<br />
Diagram<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
INDIRECT<br />
WATER HEATER<br />
AQUASTAT<br />
OR THERMOSTAT<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
Installation of<br />
Optional System<br />
and/or DHW Circulator<br />
24 VAC<br />
24 VAC<br />
MAIN<br />
END<br />
SWITCH<br />
POWER IN<br />
EXTRA<br />
END<br />
SWITCH<br />
MODE<br />
NORMAL RESET<br />
FUSE (7 AMP MAX)<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
24 VAC<br />
<strong>ZONE</strong> 6 PRIORITY<br />
OFF<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
ZVC 406<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTROL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5<br />
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER<br />
MAIN<br />
END<br />
SWITCH<br />
EXTRA<br />
END<br />
SWITCH<br />
N/O COM N/C<br />
T<br />
T<br />
TO CIRCULATOR<br />
OR BOILER<br />
AQUASTAT RELAY<br />
DRY<br />
CONTACTS<br />
JUMPER<br />
3 & 4<br />
1<br />
2<br />
3<br />
MOTOR<br />
END<br />
SWITCH<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
SEE NOTE<br />
T<br />
T<br />
BOILER<br />
SYSTEM CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
DHW CIRCULATOR (See Note)<br />
120 VAC<br />
NEUTRAL<br />
HOT<br />
Operation/External Diagnostics: When any thermostat<br />
calls for heat, the appropriate zone valve is energized and the<br />
yellow light goes on. When the zone valve is fully open, the<br />
red light goes on and energizes the end switch relay. The green<br />
light should always be on, indicating that power is connected.<br />
Priority Operation: When zone 6 is switched to the priority<br />
setting and is actuated, all other zones will stop operation until<br />
zone 6 is satisfied. When zone 6 is not switched to priority, all<br />
zones will operate independently. Note: When a circulator is<br />
used on the priority zone instead of a zone valve, jumper 3 and<br />
4 of the priority zone.<br />
Mode Operation: When the mode switch is set to NORMAL,<br />
the end switch relay will be energized if any zone is in operation.<br />
When the switch is set to RESET, the end switch relay<br />
will only be energized if priority zone is in operation.<br />
The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong><br />
Zone Valves, Priority Zoning Circulators, Thermostats, and the<br />
“00” family of circulators with the advanced features of the<br />
<strong>Taco</strong> Zone Controls to achieve total system integration. No<br />
matter the application, <strong>Taco</strong> now provides the products to<br />
maximize system performance while simplifying both installation<br />
and service.<br />
94<br />
Do it Once. Do it Right.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />
ZVC404 4 with Priority 120 VAC Input 40 VA 10 1 ⁄ 4" 6 3 ⁄ 4" 2 3 ⁄ 4"<br />
ZVC406 6 with Priority 120 VAC Input 80 VA 11 3 ⁄ 4" 7 1 ⁄ 2" 3"<br />
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone of<br />
1 ⁄ 6 hp (5A) @ 120 VAC.<br />
Features: External Indicator Lights<br />
Switchable Priority<br />
Simplified Wiring<br />
Works with 2, 3, or 4-Wire Zone Valves<br />
Compact Design<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Extra Set of Dry Contacts<br />
Contractor Friendly PC Board Layout<br />
Universal Thermostat Compatibility<br />
UL Approved<br />
Sturdy Screw Connections<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper<br />
wire only. Failure to follow this instruction can result in personal injury or death and/or property damage.<br />
10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for<br />
thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with 5 in.lbs.<br />
max torque.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.
Instruction Sheet<br />
ZVC404-EXP & ZVC406-EXP Zone Valve Control<br />
Wiring<br />
Diagram<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
WHITE<br />
120 VAC<br />
INPUT<br />
BLACK<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
FACTORY<br />
INSTALLED<br />
TRANSFORMER<br />
Installation of<br />
Optional System<br />
and/or DHW Circulator<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
N/O COM N/C<br />
24 VAC<br />
24 VAC<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
TACO, INC ZVC406-EXP<br />
POWER IN<br />
POWER<br />
<strong>CONTROLS</strong><br />
RESET<br />
END<br />
SWITCH<br />
B<br />
PUMP<br />
TO CIRCULATOR<br />
OR BOILER<br />
AQUASTAT RELAY<br />
SLAVE 1 2 3 4<br />
EXPANSION<br />
MASTER<br />
MODE<br />
NORMAL<br />
N/O COM N/C<br />
<strong>ZONE</strong> 6 RELAY<br />
DRY<br />
CONTACTS<br />
END<br />
SWITCH<br />
A<br />
BOILER<br />
TO CIRCULATOR<br />
OR BOILER<br />
AQUASTAT RELAY<br />
PLUG-IN<br />
<strong>ZONE</strong> 6<br />
CARDS PRIORITY<br />
ON<br />
T T T T T T T T T T T T<br />
<strong>ZONE</strong> 1 <strong>ZONE</strong> 2 <strong>ZONE</strong> 3 <strong>ZONE</strong> 4 <strong>ZONE</strong> 5 <strong>ZONE</strong> 6<br />
OFF<br />
FUSE 7 AMP MAX<br />
<strong>ZONE</strong> 1<br />
1 2 3 4<br />
THERMOSTAT THERMOSTAT THERMOSTAT<br />
JUMPER<br />
3 & 4<br />
24 VAC<br />
ZVC 406-EXP<br />
SIX <strong>ZONE</strong> <strong>ZONE</strong> VALVE CONTOL<br />
WITH OPTIONAL PRIORITY<br />
<strong>ZONE</strong> 2<br />
1 2 3 4<br />
1<br />
2<br />
3<br />
<strong>ZONE</strong> 3<br />
1 2 3 4<br />
<strong>ZONE</strong> 4<br />
1 2 3 4<br />
<strong>ZONE</strong> 5<br />
1 2 3 4<br />
MOTOR<br />
END<br />
SWITCH<br />
<strong>ZONE</strong> 6<br />
1 2 3 4<br />
JUMPER<br />
3 & 4<br />
PRIORITY<br />
<strong>ZONE</strong><br />
INDIRECT<br />
WATER HEATER<br />
AQUASTAT<br />
OR THERMOSTAT<br />
T STAT 1<br />
VALVE 1<br />
T STAT 2<br />
VALVE 2<br />
T STAT 3<br />
VALVE 3<br />
T STAT 4<br />
VALVE 4<br />
T STAT 5<br />
VALVE 5<br />
T STAT 6<br />
VALVE 6<br />
POWER ON<br />
SEE NOTE<br />
SYSTEM<br />
CIRCULATOR<br />
2 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(NO END SWITCH)<br />
TACO<br />
3 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
4 <strong>WIRE</strong> <strong>ZONE</strong> VALVE<br />
(POWER OPEN, SELF CLOSING)<br />
DHW<br />
120 VAC<br />
CIRCULATOR<br />
(See Note)<br />
NEUTRAL HOT<br />
T T<br />
BOILER<br />
Operation/External Diagnostics: When any thermostat calls for<br />
heat, the appropriate zone valve is energized and the yellow light goes<br />
on. When the zone valve is fully open, the red light goes on and energizes<br />
the end switch relays. The green light should always be on, indicating<br />
that power is connected.<br />
Priority Operation: When zone 6 is switched to the priority setting<br />
and is actuated, all other zones will stop operation until zone 6 is satisfied.<br />
When zone 6 is not switched to priority, all zones will operate<br />
independently. Note: When a circulator is used on the priority zone<br />
instead of a zone valve, jumper 3 and 4 of the priority zone.<br />
Mode Operation: When the mode switch is set to NORMAL, both end<br />
switch relays will be energized if any zone is in operation. When the<br />
mode switch is set to RESET, the end switch relay “A” will only be energized<br />
when the priority zone is in operation. The end switch relay “B”<br />
will be energized when any zone is in operation<br />
Power Input: Connect 120 volt ac power input to leads on transformer.<br />
Neutral to white wire. Hot to black wire.<br />
Expansion Connections: Set the expansion switch to MASTER on the<br />
zone valve control that has the designated priority zone or is utilizing<br />
the PowerPort options. Set all other daisy chained controls to SLAVE.<br />
Connect thermostat wire (18-22 gauge) between terminals 1, 2, 3, 4 on<br />
the master control to the corresponding 1, 2, 3, 4 on the SLAVE control(s).<br />
Controls may be daisy chained up to 20 zones using any combination<br />
of Switching Relay -EXP or Zone Valve -EXP controls.<br />
The <strong>Taco</strong> Connection: Combine the reliability of the <strong>Taco</strong> Zone Valves,<br />
Priority Zoning Circulators, Thermostats, and the “00” family of circulators<br />
with the advanced features of the <strong>Taco</strong> Zone Controls to achieve<br />
total system integration. No matter the application, <strong>Taco</strong> now provides<br />
the products to maximize system performance while simplifying both<br />
installation and service.<br />
Specifications:<br />
PRODUCT NUMBER TRANSFORMER MAX OUTPUT DIMENSIONS OF ENCLOSURE<br />
NUMBER OF <strong>ZONE</strong>S VOLTAGE AT 24 VAC WIDTH HEIGHT DEPTH<br />
ZVC404-EXP 4 with Priority 120 VAC Input 80 VA 11 3 ⁄4" 7 1 ⁄2" 3"<br />
ZVC406-EXP 6 with Priority 120 VAC Input 80 VA 11 3 ⁄4" 7 1 ⁄2" 3"<br />
All Zone Valve Controls are relay type DPDT and have a single phase motor rating per zone<br />
of 1 ⁄ 6 hp (5A) @ 120 VAC.<br />
Features:<br />
External Indicator Lights<br />
Plug-In PowerPort Cards<br />
Switchable Priority<br />
Simplified Wiring<br />
Add-On Power Controls<br />
Works with 2, 3, or 4-Wire<br />
Zone Valves<br />
UL Approved<br />
Fuse Protected<br />
100% Factory Tested<br />
Isolated End Switch<br />
Expandable to 20 Zones<br />
Extra Set of Dry Contacts<br />
Contractor Friendly PC<br />
Board Layout<br />
Universal Thermostat<br />
Compatibility<br />
Sturdy Screw Connections<br />
Extended 3 Year Warranty<br />
Made in the USA<br />
Warning: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. Failure to follow this instruction can result in personal injury or death and/or property<br />
damage. 10-18 gauge wire recommended for 120 VAC connections with 9 in.lbs. max torque, 12-22 gauge wire for thermostat connections with 9 in.lbs. max torque, and 12-22 gauge wire for 24 VAC source with<br />
5 in.lbs. max torque.<br />
Do it Once. Do it Right.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.<br />
95
Instruction Sheet<br />
Hydro Air Fan Controls<br />
Operation HAFC101 and 201:<br />
The Hydro Air Fan Control is an interface<br />
between the thermostat and air handler. It<br />
also has an isolated end switch to start the<br />
boiler and/or pump. When the thermostat<br />
calls for heat, the Fan Control energizes the<br />
end switch relay and allows the fan to operate<br />
at low speed when the water is above the<br />
optional aquastat setting. When the thermostat<br />
calls for cooling, the Fan Control energizes<br />
the condenser and operates on high speed.<br />
Additional HAFC201 Operations:<br />
Selectable one, three or four minute delay on<br />
fan operation in heating mode. Selectable<br />
pump exercise activates circulator but does<br />
not enable boiler contacts. Two minutes every<br />
24 hours minimizes the chance of bacteria<br />
build-up in an open loop system. Thirty seconds<br />
every two weeks minimizes seasonal<br />
start-up problems generally associated with<br />
harsh water conditions. Optional aquastat or<br />
thermostat can be connected to Freeze<br />
Protection TT terminals to reduce the chance<br />
of pipes freezing by energizing the pump dry<br />
contacts (boiler contacts not activated.)<br />
Switch Settings (HAFC201):<br />
1 1 minute on fan delay, in heating mode<br />
2 3 minute on fan delay, in heating mode<br />
1&2 4 minute on fan delay, in heating mode<br />
3 Pump dry contact activated for 2 minutes<br />
every 24 hours (boiler contacts not<br />
activated)<br />
4 Pump dry contacts activated for 30 seconds<br />
every two weeks (boiler contacts<br />
not activated)<br />
External Diagnostics:<br />
The external lights show full functionality of<br />
the Hydro Air Fan Control. The green light<br />
should always be on, indicating that power is<br />
connected. Red lights indicate fan operation<br />
for heating and cooling modes.<br />
Warning:<br />
Wiring connections must be made in accordance with<br />
all applicable electrical codes. Use copper wire only.<br />
Failure to follow this instruction can result in personal<br />
injury or death and/or property damage. 10-18 gauge<br />
wire recommended for 120 VAC connections with<br />
9 in.lbs. max torque, 12-22 gauge wire for thermostat<br />
connections with 9 in.lbs. max torque, and 12-22 gauge<br />
wire for 24 VAC source with 5 in.lbs. max torque.<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
THERMOSTAT<br />
C R W Y<br />
1 MIN ON DELAY - FAN<br />
3 MIN ON DELAY - FAN<br />
2 MIN @ 24 HR - PUMP<br />
30 SEC @ 2 WK - PUMP<br />
OFF ON<br />
THERMOSTAT<br />
Hot<br />
Neutral<br />
(or to “T T” on<br />
switching relay)<br />
Circulator<br />
Dry Contacts<br />
To: “T T” on<br />
Boiler or<br />
Switching<br />
Relay<br />
G T<br />
DRY CONTACTS<br />
5 AMP 1/6 HP RATED<br />
PUMP BOILER<br />
Line 24 VAC<br />
T T T<br />
WATER COIL FREEZE PR<br />
AQUASTATS<br />
HAFC201<br />
HYDRO AIR FAN CONTROL<br />
X X XXCRY<br />
To: Optional<br />
Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
AIR HANDLER<br />
G G<br />
Fan<br />
Relay<br />
M<br />
To: Optional Aquastat<br />
or Thermostat to sense<br />
low ambient<br />
temperature<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
Jumper<br />
Outdoor<br />
Condenser<br />
Unit<br />
Optional Power Wire<br />
to Thermostat<br />
that Requires 24VAC<br />
Dry Contacts<br />
To: “T T” on Boiler<br />
or Switching Relay<br />
THERMOSTAT<br />
C R W Y<br />
THERMOSTAT<br />
G T T<br />
AQUASTAT<br />
HAFC101<br />
HYDRO AIR FAN CONTROL<br />
BOILER AIR HANDLER<br />
X X C R Y G G<br />
To: Aquastat on<br />
Return Line of<br />
Hydro Coil<br />
1 Speed Air Handler*<br />
2 Speed Air Handler*<br />
* Both HAFC101 and 201 capable of 1 and 2 speed applications<br />
Terminal Description:<br />
Thermostat:<br />
C Optional: Common side of transformer W White - Heating signal<br />
to power some styles of thermostats Y Yellow - Condenser signal<br />
R Red - Hot side of transformer used to G Green - Fan signal<br />
switch all functions<br />
Water Coil Aquastat:<br />
TT Connect to aquastat at air handler to control operation of the fan when<br />
in the heating mode. Install a jumper if the aquastat is not used<br />
Freeze Protection Aquastat:<br />
TT Connect to aquastat or thermostat to sense low ambient temperature.<br />
Reduces the chance of pipes freezing by energizing the pump dry contacts.<br />
Pump Dry Contacts:<br />
XX May switch pump directly by bringing in external line voltage or connect<br />
to “T T” on a switching relay.<br />
Boiler Dry Contacts:<br />
XX Connect to the boiler or “T T” terminals on a switching relay.<br />
Air Handler:<br />
C Common side of transformer to power the Fan Control<br />
R Red - Hot side of transformer used to switch all functions<br />
Y Yellow - Condenser signal<br />
One Speed Motor:<br />
G low Connect the fan to the relay. Keep the jumper installed between G high and G low.<br />
Two Speed Motor:<br />
G high Remove jumper and connect G high to the high speed fan relay and<br />
connect G low to the low speed fan relay.<br />
Line 24 VAC<br />
Low<br />
High<br />
M<br />
Fan Relays<br />
Power On<br />
Call for Heat<br />
Fan, Cooling<br />
Fan, Heating<br />
Outdoor<br />
Condenser<br />
Unit<br />
Specifications:<br />
** Model number changed from SR501-F<br />
PRODUCT<br />
NUMBER<br />
NUMBER<br />
OF <strong>ZONE</strong>S<br />
POWER INPUT<br />
VOLTAGE<br />
MAXIMUM<br />
COMBINED LOAD<br />
RELAY<br />
TYPE<br />
THERMOSTAT<br />
CURRENT<br />
SINGLE PHAZE MOTOR<br />
RATING (RELAY)<br />
DIMENSIONS OF ENCLOSURE<br />
WIDTH HEIGHT DEPTH<br />
HAFC101** 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC 4 1/4" 5 1/4" 2 3/4"<br />
HAFC201•• 1 Zone 24 VAC Input 5 amps DPDT .18 1/6 HP(5A) @120VAC 4 1/4" 5 1/4" 2 3/4"<br />
The Hydro Air Fan Controls are relay type DPDT, have a thermostat current of .18 and a single phase motor rating per zone of 1/6 HP (5A) @ 120 VAC.<br />
Do it Once. Do it Right.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
96<br />
Printed in USA<br />
Copyright 1999<br />
TACO, Inc.
Instruction Sheet<br />
PC600 Post Purge Timer Plug-In PowerPort Card<br />
102-094<br />
SUPERSEDES: August 1, 1997 EFFECTIVE: May 1, 2000<br />
Plant ID No. 9300-867<br />
Operation:<br />
Once the priority zone is satisfied, the PC600 maintains power to the circulator, but does not fire the boiler. The circulator purges excess heat into the priority zone,<br />
minimizing standby loss during warm weather months and optimizing boiler operation when used with a boiler reset control. Power can be maintained to the circulator<br />
from a minimum of 10 seconds to a maximum of 420 seconds. The power LED light is energized when the priority zone or the post purge card is in operation.<br />
Installation:<br />
The PC600 can be installed in any one of the PowerPort terminals located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Remove the shunt/jumper between pins 9<br />
& 10 on the PowerPort terminal before installing the PC600. Align the connector on the base of the post purge card with the PowerPort terminal on the Expandable<br />
Control and push until the two mate.<br />
XX Terminals (Optional):<br />
The XX terminals on the post purge card can be wired to TT on the boiler to fire only when the priority zone is calling for heat. If using a boiler with an internal<br />
reset control, wire the XX terminals in parallel with the TT connections of the internal reset control.<br />
Do it Once. Do it Right.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.<br />
Instruction Sheet<br />
PC605 Priority Protection Plug-In PowerPort Card<br />
102-095<br />
SUPERSEDES: MAY 1, 1998 EFFECTIVE: MAY 1, 2000<br />
PLANT ID NO. 9300-1012<br />
Operation:<br />
The PC605 Priority Protection Plug-In Card is a solid state control that helps prevent freeze-ups in the event of a priority zone failure. If the priority zone calls for heat<br />
continuously for more than one hour, power is returned to the space heating (non-priority) zones, allowing all zones to function independently. Once the priority zone is<br />
satisfied, the PC605’s auto-reset is activated and the priority zone is again allowed to have priority for up to one hour the next time it calls. The one hour time frame is<br />
not adjustable. The red LED light is energized only when the Priority Protection Card is operating in priority override mode.<br />
Installation:<br />
The PC605 can be installed in any unoccupied PowerPort terminal located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 &<br />
10 on the Expandable Control unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the<br />
Expandable Control and push until the two mate. The PC605 can be used in conjunction with any other <strong>Taco</strong> PC style PowerPort Cards or Add-on Controls.<br />
Do it Once. Do it Right.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.<br />
Instruction Sheet<br />
PC610 Pump Exercise and Timer Plug-In PowerPort Card<br />
102-096<br />
SUPERSEDES: May 31, 1998 EFFECTIVE: May 1, 2000<br />
Plant ID No. 9300-1025<br />
Operation:<br />
The PC610 Pump Exercise and Timer Plug-In Card is a solid state universal timer designed to cycle all the pumps that are attached to the Expandable Control(s)<br />
at selected time intervals. This minimizes seasonal start-up problems generally associated with harsh water conditions. The control can be configured to reduce<br />
the chance of freeze-ups by cycling the pumps more often during cold weather months. Bacteria can be minimized in heating systems that utilize domestic hot<br />
water heaters as their heat source by systematically circulating the water.<br />
Installation:<br />
The PC610 can be installed in any unoccupied PowerPort terminal located on the <strong>Taco</strong> Expandable (-EXP) Control(s). Do not remove the shunt between pins 9 & 10 on<br />
the Expandable Switching Relay unless a PC600 is also installed. Align the connector on the base of the priority protection card with the PowerPort terminal on the<br />
Expandable Switching Relay and push until the two mate. The PC610 can be used in conjunction with any other <strong>Taco</strong> PC style PowerPort Cards or Add-on Controls.<br />
Typical Settings:<br />
Application On Time Off Time<br />
Pump Exercise 30 sec. 2 weeks<br />
Bacteria Minimization 4 min. 12 hours<br />
Freeze Protection 4 min. 1 hour<br />
Do it Once. Do it Right.<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Printed in USA<br />
Copyright 2000<br />
TACO, Inc.<br />
97
Standard Terms and Definitions<br />
Switching Relay: Transformer and relay in one box, which allows a low voltage thermostat to control a line voltage load (circulator),<br />
with an isolated end switch that can energize the boiler.<br />
Zone Valve Control: Transformer and relay in one box, which allows a low voltage thermostat to control a low voltage zone valve, with<br />
an isolated end switch that can energize the boiler and/or circulators.<br />
Dry Contacts: Set of relay contacts that make and beak, where no voltage is present. Usually can switch 24 or 120 VAC.<br />
Isolated End Set Switch: Set of dry contacts that make when a zone calls for heat. Usually connected to a boiler’s aquastat TT.<br />
Mode Switch: Switch set to NORMAL – When any zone calls for heat, the end switch will make and fire the boiler.<br />
Switch set to RESET – When any zone calls for heat, a heat demand signal is given to external add-on reset control and it controls<br />
boiler operation.Also when the priority zone calls for heat and is switched to priority, the end switch will override reset control and<br />
fire boiler to high limit.<br />
TT: Where thermostat or aquastat connects on a heating control.<br />
XX: Denotes Isolated End Switch.<br />
Low Voltage: 24 VAC for most HVAC systems.<br />
Line Voltage: Normally 120 VAC relative to ground.<br />
H or L1: Hot side of line voltage.<br />
N or L2: Neutral side of line voltage.<br />
ZR: 120 VAC (Hot) signal from switching relay to boiler’s operating aquastat to fire the burner to high limit when any zone calls for<br />
heat. Also ideal for controlling primary circulator.<br />
ZC: 120 VAC (Hot) signal from boiler’s operating aquastat to switching relay allowing circulator(s) to run when aquastat is above the<br />
set low limit.<br />
Cold Start: A boiler that fires only when there is a call for heat.<br />
Tankless Coil: A method of heating domestic water utilizing a heat exchanger inside a boiler.The boiler also maintains heat year round<br />
to deliver hot water on demand.<br />
DHW Heater: A method of heating domestic water utilizing a heat exchanger and storage tank.<br />
Transformer: A component for increasing or reducing AC voltage. Rated in VA (volts x amps).<br />
OHMS Law: Example: A 24 volt, 40 VA transformer can produce how much current?<br />
Current = VA / Voltage<br />
40 / 24 = 1.6 Amps<br />
I = E/R where I = Current in Amps<br />
R = E/I<br />
R = Resistance in Ohms<br />
E = I x R<br />
E = Volts<br />
W = E x I<br />
W = Watts or VA<br />
I = W(VA)/E<br />
RELAY CONTACTS:<br />
N/C: Normally closed connection of a relay, when not energized.<br />
N/O: Normally open connection of a relay, when not energized.<br />
Com: The common terminal for normally open and normally closed.<br />
Pole: The number of independent circuits of a switch or relay.<br />
Throw: The number of settings which a switch or relay can have.<br />
3 4 4 6 6 5<br />
COM N/O N/C N/C N/O COM<br />
DPDT = Double Pole Double Throw<br />
98
TACO Zone Controls Cross-Reference<br />
TACO ARGO ERIE HONEYWELL WHITE-ROGERS<br />
SWITCHING RELAYS<br />
1 Zone Switching Relay (DPDT) SR501 AR821 (1), AR822 SR100 RA89A (2), RA845A (1), RA832A (1) 889-189 (2), 829-845 (1)<br />
1 Zone Switching Relay Replacement PC Board (DTSP) SR501-845RP<br />
2 Zone Switching Relay with Priority SR502 AR-861-2 (3) SR201<br />
3 Zone Switching Relay with Priority SR503 AR-861-3 (3) SR301 R8888A1007<br />
4 Zone Switching Relay with Priority SR504 AR-842 SR601 R8888B1005<br />
6 Zone Switching Relay with Priority SR506 AR-866 SR601 (4)<br />
SWITCHING RELAYS<br />
WITH POWERPORT OPTIONS<br />
3 Zone Switching Relay with Priority and 3 Power Ports SR503-EXP ARM-861-DP (5,6),ARM-3P<br />
4 Zone Switching Relay with Priority and 3 Power Ports SR504-EXP ARM-842-DP (5,6),ARM-4P<br />
6 Zone Switching Relay with Priority and 3 Power Ports SR506-EXP ARM-866-DP (5,6),ARM-6P<br />
<strong>ZONE</strong> VALVE <strong>CONTROLS</strong><br />
3 Zone Valve Control ZVC403 (7) AZ-3 R8889A1014<br />
4 Zone Valve Control with Priority ZVC404 (7) AZ-4P R8889B1012<br />
5 Zone Valve Control ZVC405 (7) AZ-5 VL500 (8)<br />
6 Zone Valve Control with Priority ZVC406 (7) AZ-6P VL500 (8)<br />
<strong>ZONE</strong> VALVE <strong>CONTROLS</strong><br />
WITH POWERPORT OPTIONS<br />
4 Zone Valve Control with Priority and 2 Power Ports ZVC404-EXP<br />
6 Zone Valve Control with Priority and 2 Power Ports ZVC406-EXP<br />
PLUG IN POWERPORT CARDS<br />
Post Purge Timer Plug-In Card PC600<br />
Priority Protection Plug-In Card PC605 DPM-1<br />
Universal Timer/Pump Exercize Plug-In Card PC610<br />
99
TACO Zone Controls Cross-Reference (Continued)<br />
100<br />
TACO ARGO ERIE HONEYWELL WHITE-ROGERS<br />
ADD-ON POWER <strong>CONTROLS</strong><br />
Boiler Reset Control PC700 DPM-2 BB1200<br />
2-Stage Boiler Reset Control PC702<br />
Variable Speed Pump Injection Mixing Control PC705 BB3000<br />
FAN <strong>CONTROLS</strong><br />
1 Zone Hydro Air Fan Control (1 or 2 Speed) HAFC101 ARH-1,ARH-2,ARH-3 WA300<br />
1 Zone Hydro Air Fan Control with Time Delays (1 or 2 Speed) HAFC201<br />
REPLACEMENT PARTS<br />
24 Volt Replacement Relay SR024-001RP R-35 EXP10<br />
120 Volt Replacement Relay SR120-001RP R-49<br />
NOTES:<br />
1. Does not have both normally open and normally closed contacts.<br />
2. Has only one set of normally open contacts (SPST).<br />
3. Does not have optional priority.<br />
4. Can be expanded to five and six zones with the addition of EXP10 relays.<br />
5. Argo ARM units are expandable to 10 zones using special controls (ARM-1,ARM-4) with a phone jack.<br />
TACO switching relays can be expanded up to 20 zones using any combination of -EXP models with no special connections.<br />
6. Includes only one data port for adding data port modules.<br />
7. All TACO zone valve controls include an extra set of dry contacts (N/O, Common, N/C).<br />
8. VL500 is only 5 zones, 4 normal and 1 priority.
<strong>CONTROLS</strong> MADE EASY. ®<br />
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360.<br />
TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.<br />
Visit our web site at: http://www.taco-hvac.com<br />
Printed in USA<br />
Copyright 2010<br />
TACO, Inc.