29.11.2014 Views

Small Systems Water Treatment Plant Operator Program Manual

Small Systems Water Treatment Plant Operator Program Manual

Small Systems Water Treatment Plant Operator Program Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Community Works Management System<br />

Technical Specifications<br />

APPENDIX 2: LIQUID WASTE COLLECTION & DISTRIBUTION SYSTEM<br />

Activity<br />

Code:<br />

Activity Description<br />

Activity<br />

Code:<br />

Activity Description<br />

o120 Sewage Collection Trucked o126 Sewage Pump/Lift Station<br />

o121 Honey Bag Collection o127 Sewage <strong>Treatment</strong><br />

o122 Sewage Lagoons O&M o128 Sewage Sampling<br />

o123 Honey Bag Cell O&M o129 Signage<br />

o124 Sewage Mains o199 Sewage Other<br />

x125 Manholes/Access Vaults<br />

1. Facility: Sewage System<br />

2. Crew Size:<br />

2-System <strong>Operator</strong> &<br />

Helper<br />

3. Equipment:<br />

Vacuum Truck, safety gear<br />

4. Materials:<br />

5. Activities to complete<br />

Semi-Annual<br />

7. Quality Standard:<br />

6. Time to Complete each Activity<br />

S/A 1.50 hrs<br />

(Per manhole)<br />

8. Work Method:<br />

SA 1. Check if dangerous gases are present before entering manhole. Allow gases to<br />

dissipate, or ventilate manhole prior to entering.<br />

Do Not, under any circumstances, perform interior work on any access vault alone,<br />

work on the interior of an access must be performed with a two man crew.<br />

SA 2. If the access vault contains a sump pump, inspect the pump and control floats, and<br />

operate the pump for a short period of time.<br />

SA 3. Check manhole heating systems operation (where applicable).<br />

SA 4. Check and service main valves.<br />

SA 5. Check for obvious obstructions in the sewer main in the vicinity of the access vault by<br />

removing the clean out cover.<br />

SA 6. Check to see that sewer pipe clean out cap is closed and sealed tight.<br />

SA 7. Check that access vault lock is in place and operational.<br />

SA 8. Check that frost cover is intact.<br />

SA 9. Inspect grading around manhole/access vault, and confirm that grading drains all<br />

surface runoff away from the access vault.<br />

SA 10. Check for groundwater or other infiltration into access vault from surcharging,<br />

permafrost or water main cross connections. Infiltration into an access vault, or<br />

debris that accumulates must be removed.