You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>FEX</strong><br />
H0(H120) Fire Damper<br />
V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />
The <strong>Halton</strong> <strong>FEX</strong> fire dampers are type-approved class<br />
H0(H120) fire dampers for use in offshore, nuclear<br />
and navy ventilation systems. <strong>FEX</strong> dampers are used<br />
to protect the integrity of bulkheads where they are<br />
penetrated by ventilation ducts. The <strong>Halton</strong> <strong>FEX</strong> dampers<br />
can be installed in rectangular or circular ducts. Dampers<br />
have a fusible link and they prevent the spread of fire<br />
and gases (low-leakage model) within the ventilation<br />
ductwork. When the blades are in a open position, the<br />
device does not cause significant pressure loss, noise or<br />
flow disturbance. <strong>FEX</strong> dampers are set from outside and<br />
are suitable to be installed in bulkheads. An open-closed<br />
label is visible on the outside of the damper.<br />
• Type approved by most recognized classification<br />
societies, class H0(H120) fire damper when suitably<br />
insulated<br />
• Fixed frame and blades of stainless steel AISI 316L.<br />
Painted frame surface as an option on request<br />
• Weldings cleaned by acid treatment<br />
• Lifting lugs as standard<br />
• Blades contain thermal expansion seals<br />
• Nominal release temperatures of fuses are 50 ºC, 74 ºC<br />
and 100 ºC degrees. Other temperatures available<br />
• Automatic electrical, pneumatic or spring operation<br />
system available<br />
• Maximum duct pressure 5000 Pa and maximum air<br />
velocity 15 m/s<br />
PART MATERIAL FINISHING NOTE<br />
Frame Stainless steel Painted -<br />
Frame Stainless steel - -<br />
Blades Stainless steel - -<br />
Blades Stainless steel - -<br />
Maintenance-free bearings Stainless steel - Bronze bearings optional<br />
Shafts Stainless steel - -<br />
<strong>FEX</strong> - H0(H120) Fire Damper
<strong>FEX</strong> DIMENSIONS AND MATERIAL THICKNESS<br />
<strong>FEX</strong> fire dampers are manufactured for both rectangular<br />
and circular ducts. Sizes for rectangular ducts (BxH) are<br />
available from 100x100 mm to 1200x1200 mm in 1 mm<br />
increments of duct.<br />
Sizes for circular ducts (BxH) are available from diameter<br />
100 mm to 1250 mm. Special non-standard dimensions<br />
available on request.<br />
Size of flange is 40 mm as standard. Flanges and<br />
drilling also available according to NORSOK standards<br />
or customer's own specifications.<br />
Standard frame material thickness 3 mm. Blades are<br />
made of two sheets each of them being 1mm thick.<br />
Actuator effect on dimensions<br />
Pneumatical<br />
ACTUATOR<br />
Pneumatic rotating<br />
actuator<br />
R<br />
DIMENSIONS<br />
A<br />
170 H<br />
Electrical BF24 or BF230 90 H<br />
Electrical, EX<br />
Schischek Ext<br />
1524/15230<br />
180 H500 = H<br />
Spring Spring 140 H<br />
V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />
GENERAL <strong>FEX</strong> DRAWING<br />
<strong>FEX</strong> CIRCULAR CONNECTIONS<br />
A<br />
ACTUATOR<br />
40.0<br />
12x14<br />
150 23.0<br />
150<br />
n*150<br />
n*150<br />
H+4<br />
H+84<br />
ØD<br />
MIN.50<br />
23.0<br />
30 R<br />
150 150<br />
n*150<br />
n*150<br />
B+4<br />
B+84<br />
23.0<br />
MIN.50<br />
23.0<br />
361<br />
GENERAL <strong>FEX</strong> DRAWING, TOP<br />
3<br />
255<br />
160<br />
<strong>FEX</strong> - H0(H120) Fire Damper
<strong>FEX</strong> PRODUCT OPTIONS<br />
<strong>Halton</strong> <strong>FEX</strong> is available with following actuators:<br />
• <strong>FEX</strong>-EL: Electrical spring return motor; standard<br />
actuators being BF24 (AC 24 V 50/60 Hz DC 24 V),<br />
BF230 (AC 230 V 50/60 Hz) or BF120 (AC 120 V<br />
50/60 Hz). The motor contains built-in open-closed<br />
limit switches. Separate junction box included in the<br />
EL-model.<br />
• <strong>FEX</strong>-PNR: Pneumatic rotating actuator. Junction box<br />
available as an option.<br />
• <strong>FEX</strong>-SP: Manual spring-actuated damper with fusible<br />
link.<br />
Ask more information for more actuators and<br />
accessories.<br />
OPERATION PRINCIPLE<br />
In the event of a temperature rise in ductwork:<br />
• <strong>FEX</strong>-EL: fusible link releases and cuts off operating<br />
voltage to the spring return motor, allowing the<br />
spring to close the damper blades. The fire damper<br />
opens automatically when the fuse has been<br />
changed and the operating voltage to the motor is reestablished.<br />
• <strong>FEX</strong>-PNR: fusible link releases and cuts off operating<br />
pressure to the spring return actuator, allowing<br />
springs to close the damper blades. The fire<br />
damper opens automatically when the fuse has<br />
been changed and the pneumatic air supply is reestablished.<br />
• <strong>FEX</strong>-SP: fusible link releases allowing the spring to<br />
close the damper blades. When the fuse has been<br />
changed, the fire damper must be reset into open<br />
position manually.<br />
V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />
<strong>FEX</strong>-EL WIRING DIAGRAM<br />
<strong>FEX</strong>-PNR PNEUMATIC DIAGRAM<br />
CLOSED 21 13 21 13 OPEN<br />
BF AC/DC 24V<br />
BF AC 120/230V<br />
1. SPRING RETURN ACTUATOR<br />
2. QUICK EXHAUST VALVE<br />
22<br />
14<br />
22 14<br />
9<br />
1<br />
1<br />
(+) (-)<br />
CLOSE<br />
OPEN<br />
2 3 4 5 6 7 8 9<br />
10<br />
JUNCTION BOX<br />
ABS IP67<br />
3. SILENCER<br />
4. FUSIBLE LINK VALVE<br />
5. OPTION:<br />
SOLENOID VALVE<br />
6. MALE CONNECTOR<br />
7. DOUBLE NIPPLE<br />
3<br />
12<br />
13<br />
6<br />
7<br />
3<br />
6<br />
2<br />
8<br />
4<br />
THERMAL SWITCH<br />
ELMWOOD D070 (72°C)<br />
8. PLASTIC TUBE<br />
9. OPTION:<br />
OPEN/CLOSED SWITCHES<br />
6<br />
3 8<br />
6<br />
10<br />
1<br />
2<br />
S1<br />
S2<br />
S3<br />
S4<br />
S5<br />
S6<br />
FUSIBLE LINK<br />
OPTION: 50/74/100°C<br />
10. OPTION:<br />
MANUAL VALVE<br />
11. PRESSURE REGULATOR<br />
12. MALE ELBOW<br />
13. SPEED CONTROLLER<br />
NOTICE !<br />
ADDITIONAL SOLENOID VALVE<br />
MAX 10 METER FROM FIRE DAMPER<br />
11<br />
6<br />
3 6<br />
6<br />
3<br />
8<br />
5<br />
24V DC<br />
230 VAC<br />
8<br />
M<br />
3°<br />
87°<br />
BF24/BF120/BF230 MOTOR<br />
IP 54<br />
PNEU. INLET (5 - 10 BAR)<br />
FOR A PLASTIC TUBE<br />
Ø6 MM<br />
6<br />
WEIGHTS OF HALTON MARINE <strong>FEX</strong>-EL DAMPERS AND OTHER MODELS (KG)<br />
H/Height<br />
B / Width (mm)<br />
mm 100 200 300 400 500 600 700 800 900 1000 1100 1200 D2 ØD Weight<br />
100 11 13 15 17 19 21 22 24 26 28 31 32 mm kg<br />
200 13 15 17 19 21 24 26 28 30 32 34 36 100 13<br />
300 16 18 20 23 25 28 30 32 35 37 39 42 125 14<br />
400 18 20 23 26 28 31 33 36 38 41 43 46 160 15<br />
500 21 23 26 29 32 35 37 40 43 46 48 51 200 17<br />
600 23 26 29 32 35 38 40 43 46 49 52 55 250 21<br />
700 25 29 32 35 38 41 45 48 51 54 57 61 315 25<br />
800 27 31 34 38 41 44 48 51 54 58 61 65 400 34<br />
900 30 33 37 40 44 48 51 55 59 62 66 70 500 42<br />
1000 31 35 39 43 47 51 54 58 62 66 70 74 630 51<br />
1100 34 38 42 46 50 55 59 63 67 71 75 79 800 68<br />
1200 36 40 45 49 53 57 62 66 70 74 79 83 1000 90<br />
Weights above are with frame thickness of 3 mm.<br />
1250 121<br />
<strong>FEX</strong>-EL weights include actuator BF24 or BF230. Weights of other models compared to <strong>FEX</strong>-EL: <strong>FEX</strong>-PNR +1 kg, <strong>FEX</strong>-SP -2 kg<br />
<strong>FEX</strong> - H0(H120) Fire Damper
<strong>FEX</strong> - H0(H120) Fire Damper<br />
V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.