<strong>FEX</strong><br />

H0(H120) Fire Damper<br />

V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />

The <strong>Halton</strong> <strong>FEX</strong> fire dampers are type-approved class<br />

H0(H120) fire dampers for use in offshore, nuclear<br />

and navy ventilation systems. <strong>FEX</strong> dampers are used<br />

to protect the integrity of bulkheads where they are<br />

penetrated by ventilation ducts. The <strong>Halton</strong> <strong>FEX</strong> dampers<br />

can be installed in rectangular or circular ducts. Dampers<br />

have a fusible link and they prevent the spread of fire<br />

and gases (low-leakage model) within the ventilation<br />

ductwork. When the blades are in a open position, the<br />

device does not cause significant pressure loss, noise or<br />

flow disturbance. <strong>FEX</strong> dampers are set from outside and<br />

are suitable to be installed in bulkheads. An open-closed<br />

label is visible on the outside of the damper.<br />

• Type approved by most recognized classification<br />

societies, class H0(H120) fire damper when suitably<br />

insulated<br />

• Fixed frame and blades of stainless steel AISI 316L.<br />

Painted frame surface as an option on request<br />

• Weldings cleaned by acid treatment<br />

• Lifting lugs as standard<br />

• Blades contain thermal expansion seals<br />

• Nominal release temperatures of fuses are 50 ºC, 74 ºC<br />

and 100 ºC degrees. Other temperatures available<br />

• Automatic electrical, pneumatic or spring operation<br />

system available<br />

• Maximum duct pressure 5000 Pa and maximum air<br />

velocity 15 m/s<br />

PART MATERIAL FINISHING NOTE<br />

Frame Stainless steel Painted -<br />

Frame Stainless steel - -<br />

Blades Stainless steel - -<br />

Blades Stainless steel - -<br />

Maintenance-free bearings Stainless steel - Bronze bearings optional<br />

Shafts Stainless steel - -<br />

<strong>FEX</strong> - H0(H120) Fire Damper


<strong>FEX</strong> DIMENSIONS AND MATERIAL THICKNESS<br />

<strong>FEX</strong> fire dampers are manufactured for both rectangular<br />

and circular ducts. Sizes for rectangular ducts (BxH) are<br />

available from 100x100 mm to 1200x1200 mm in 1 mm<br />

increments of duct.<br />

Sizes for circular ducts (BxH) are available from diameter<br />

100 mm to 1250 mm. Special non-standard dimensions<br />

available on request.<br />

Size of flange is 40 mm as standard. Flanges and<br />

drilling also available according to NORSOK standards<br />

or customer's own specifications.<br />

Standard frame material thickness 3 mm. Blades are<br />

made of two sheets each of them being 1mm thick.<br />

Actuator effect on dimensions<br />

Pneumatical<br />

ACTUATOR<br />

Pneumatic rotating<br />

actuator<br />

R<br />

DIMENSIONS<br />

A<br />

170 H<br />

Electrical BF24 or BF230 90 H<br />

Electrical, EX<br />

Schischek Ext<br />

1524/15230<br />

180 H500 = H<br />

Spring Spring 140 H<br />

V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />

GENERAL <strong>FEX</strong> DRAWING<br />

<strong>FEX</strong> CIRCULAR CONNECTIONS<br />

A<br />

ACTUATOR<br />

40.0<br />

12x14<br />

150 23.0<br />

150<br />

n*150<br />

n*150<br />

H+4<br />

H+84<br />

ØD<br />

MIN.50<br />

23.0<br />

30 R<br />

150 150<br />

n*150<br />

n*150<br />

B+4<br />

B+84<br />

23.0<br />

MIN.50<br />

23.0<br />

361<br />

GENERAL <strong>FEX</strong> DRAWING, TOP<br />

3<br />

255<br />

160<br />

<strong>FEX</strong> - H0(H120) Fire Damper


<strong>FEX</strong> PRODUCT OPTIONS<br />

<strong>Halton</strong> <strong>FEX</strong> is available with following actuators:<br />

• <strong>FEX</strong>-EL: Electrical spring return motor; standard<br />

actuators being BF24 (AC 24 V 50/60 Hz DC 24 V),<br />

BF230 (AC 230 V 50/60 Hz) or BF120 (AC 120 V<br />

50/60 Hz). The motor contains built-in open-closed<br />

limit switches. Separate junction box included in the<br />

EL-model.<br />

• <strong>FEX</strong>-PNR: Pneumatic rotating actuator. Junction box<br />

available as an option.<br />

• <strong>FEX</strong>-SP: Manual spring-actuated damper with fusible<br />

link.<br />

Ask more information for more actuators and<br />

accessories.<br />

OPERATION PRINCIPLE<br />

In the event of a temperature rise in ductwork:<br />

• <strong>FEX</strong>-EL: fusible link releases and cuts off operating<br />

voltage to the spring return motor, allowing the<br />

spring to close the damper blades. The fire damper<br />

opens automatically when the fuse has been<br />

changed and the operating voltage to the motor is reestablished.<br />

• <strong>FEX</strong>-PNR: fusible link releases and cuts off operating<br />

pressure to the spring return actuator, allowing<br />

springs to close the damper blades. The fire<br />

damper opens automatically when the fuse has<br />

been changed and the pneumatic air supply is reestablished.<br />

• <strong>FEX</strong>-SP: fusible link releases allowing the spring to<br />

close the damper blades. When the fuse has been<br />

changed, the fire damper must be reset into open<br />

position manually.<br />

V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.<br />

<strong>FEX</strong>-EL WIRING DIAGRAM<br />

<strong>FEX</strong>-PNR PNEUMATIC DIAGRAM<br />

CLOSED 21 13 21 13 OPEN<br />

BF AC/DC 24V<br />

BF AC 120/230V<br />

1. SPRING RETURN ACTUATOR<br />

2. QUICK EXHAUST VALVE<br />

22<br />

14<br />

22 14<br />

9<br />

1<br />

1<br />

(+) (-)<br />

CLOSE<br />

OPEN<br />

2 3 4 5 6 7 8 9<br />

10<br />

JUNCTION BOX<br />

ABS IP67<br />

3. SILENCER<br />

4. FUSIBLE LINK VALVE<br />

5. OPTION:<br />

SOLENOID VALVE<br />

6. MALE CONNECTOR<br />

7. DOUBLE NIPPLE<br />

3<br />

12<br />

13<br />

6<br />

7<br />

3<br />

6<br />

2<br />

8<br />

4<br />

THERMAL SWITCH<br />

ELMWOOD D070 (72°C)<br />

8. PLASTIC TUBE<br />

9. OPTION:<br />

OPEN/CLOSED SWITCHES<br />

6<br />

3 8<br />

6<br />

10<br />

1<br />

2<br />

S1<br />

S2<br />

S3<br />

S4<br />

S5<br />

S6<br />

FUSIBLE LINK<br />

OPTION: 50/74/100°C<br />

10. OPTION:<br />

MANUAL VALVE<br />

11. PRESSURE REGULATOR<br />

12. MALE ELBOW<br />

13. SPEED CONTROLLER<br />

NOTICE !<br />

ADDITIONAL SOLENOID VALVE<br />

MAX 10 METER FROM FIRE DAMPER<br />

11<br />

6<br />

3 6<br />

6<br />

3<br />

8<br />

5<br />

24V DC<br />

230 VAC<br />

8<br />

M<br />

3°<br />

87°<br />

BF24/BF120/BF230 MOTOR<br />

IP 54<br />

PNEU. INLET (5 - 10 BAR)<br />

FOR A PLASTIC TUBE<br />

Ø6 MM<br />

6<br />

WEIGHTS OF HALTON MARINE <strong>FEX</strong>-EL DAMPERS AND OTHER MODELS (KG)<br />

H/Height<br />

B / Width (mm)<br />

mm 100 200 300 400 500 600 700 800 900 1000 1100 1200 D2 ØD Weight<br />

100 11 13 15 17 19 21 22 24 26 28 31 32 mm kg<br />

200 13 15 17 19 21 24 26 28 30 32 34 36 100 13<br />

300 16 18 20 23 25 28 30 32 35 37 39 42 125 14<br />

400 18 20 23 26 28 31 33 36 38 41 43 46 160 15<br />

500 21 23 26 29 32 35 37 40 43 46 48 51 200 17<br />

600 23 26 29 32 35 38 40 43 46 49 52 55 250 21<br />

700 25 29 32 35 38 41 45 48 51 54 57 61 315 25<br />

800 27 31 34 38 41 44 48 51 54 58 61 65 400 34<br />

900 30 33 37 40 44 48 51 55 59 62 66 70 500 42<br />

1000 31 35 39 43 47 51 54 58 62 66 70 74 630 51<br />

1100 34 38 42 46 50 55 59 63 67 71 75 79 800 68<br />

1200 36 40 45 49 53 57 62 66 70 74 79 83 1000 90<br />

Weights above are with frame thickness of 3 mm.<br />

1250 121<br />

<strong>FEX</strong>-EL weights include actuator BF24 or BF230. Weights of other models compared to <strong>FEX</strong>-EL: <strong>FEX</strong>-PNR +1 kg, <strong>FEX</strong>-SP -2 kg<br />

<strong>FEX</strong> - H0(H120) Fire Damper


<strong>FEX</strong> - H0(H120) Fire Damper<br />

V1M08Y2006/<strong>Halton</strong> Marine reserves the right to alter products without notice.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!