<strong>CYCLON</strong> SINGLE CELL PERFORMANCE SPECIFICATIONS<br />

Constant current discharge/amps to 1.67 vpc @ 25°C<br />

D U R AT I O N<br />

P r o d u c t s 5 min. 10 min. 15 m i n . 30 min. 60 min. 90 min. 5 hr. 8 hr. 10 hr. 20 hr.<br />

D cell (2.5Ah) 14 . 8 8 . 1 5 . 9 3 . 4 1 . 9 1 . 4 . 48 . 32 . 26 . 13<br />

DT cell (4.5Ah) 25 . 2 15 . 0 11 . 2 6 . 6 3 . 7 2 . 6 . 85 . 55 . 45 . 24<br />

X cell (5.0Ah) 27 . 3 17 . 8 13 . 2 7 . 0 3 . 9 2 . 8 . 96 . 61 . 50 . 26<br />

E cell (8.0Ah) 41 . 7 26 . 4 19 . 0 11 . 0 6 . 2 4 . 4 1 . 6 1 . 0 . 81 . 42<br />

J cell (12.0Ah) 51 . 7 38 . 1 29 . 4 18 . 0 9 . 2 6 . 5 2 . 3 1 . 5 1 . 20 . 66<br />

Constant power discharge/watts per cell to 1.67 vpc @ 25°C<br />

D U R AT I O N<br />

P r o d u c t s 5 min. 10 min. 15 m i n . 30 min. 60 min. 90 min. 5 hr. 8 hr. 10 hr. 20 hr.<br />

D cell (2.5Ah) 26 . 4 16 . 1 11 . 6 6 . 7 3 . 8 2 . 7 . 94 . 61 . 50 . 25<br />

DT cell (4.5Ah) 45 . 0 28 . 1 21 . 0 12 . 5 7 . 1 5 . 1 1 . 7 1 . 1 . 90 . 46<br />

X cell (5.0Ah) 45 . 4 31 . 9 23 . 9 13 . 9 7 . 8 5 . 6 1 . 9 1 . 2 1 . 0 . 51<br />

E cell (8.0Ah) 77 . 8 51 . 0 35 . 5 21 . 1 12 . 4 8 . 9 3 . 1 2 . 0 1 . 6 . 85<br />

J cell (12.0Ah) 90 . 4 68 . 4 53 . 4 31 . 6 18 . 3 13 . 2 4 . 7 3 . 0 2 . 3 1 . 3<br />

C h a r g i n g / Te m p e r a t u r e / L i f e :<br />

CHARGING PER CELL<br />

T E M P E R ATURE RANGE<br />

LIFE EXPECTA N C Y<br />

Storage & C/5 Cycle life Float life at<br />

P r o d u c t s C y c l i c F l o a t d i s c h a r g e C h a r g e 100% DOD 25°C (20°C)<br />

D, DT, X, E & J cell CV 2.45–2.50 CV 2.27–2.35 -65°C to +80°C -40°C to +80°C 300 10 years<br />

C C * C C * (15 years)<br />

Maximum recommended storage time before recharge—24 months @ 25°C or 2.0vpc, whichever is earlier<br />

Atmospheric pressure range—Vacuum to 8 atmospheres<br />

* Users planning to use CC should consult the <strong>EnerSys</strong> Application Support Department<br />

UL Recognized Component. Meets UL 1989<br />

Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container<br />

Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact <strong>EnerSys</strong> Customer Service for details.<br />

Certificate Number EMS 39520, ISO 14001 Certified<br />

Certificate Number FM 32099, ISO 9001 Certified<br />

Publication No. US-CYC-SG-001 February 2003<br />