28.12.2014 Views

Air cooled liquid chillers and reverse cycle air/water heat pumps ...

Air cooled liquid chillers and reverse cycle air/water heat pumps ...

Air cooled liquid chillers and reverse cycle air/water heat pumps ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Air</strong> <strong>cooled</strong> <strong>liquid</strong> <strong>chillers</strong> <strong>and</strong> <strong>reverse</strong> <strong>cycle</strong> <strong>air</strong>/<strong>water</strong> <strong>heat</strong> <strong>pumps</strong><br />

Range: from 34 kW to 262 kW<br />

• R410A refrigerant<br />

• Scroll compressors<br />

• Part load efficiency<br />

• Range flexibility<br />

• IDRORELAX Network Unit


Climaveneta presents its new NECS (New Evolution Climaveneta System) range of <strong>chillers</strong> (<strong>heat</strong> <strong>pumps</strong>)<br />

fitted with R410A rotary scroll compressors.<br />

The range comprises one-circuit versions with due compressors <strong>and</strong> two-circuit versions with four<br />

compressors.<br />

Consistently with corporate culture, the NECS series exploits cutting-edge technology to achieve<br />

extremely high levels of quality, focusing on maximum energy efficiency <strong>and</strong> minimum noise emissions.<br />

WHY R410A<br />

Though R410A is a blend, it behaves just like a pure gas <strong>and</strong><br />

features a negligible temperature glide. Thanks to its outst<strong>and</strong>ing<br />

<strong>heat</strong> conductivity, R410A contributes towards achieving elevated<br />

system efficiency.<br />

R410A is also an ecological gas, both because its elevated<br />

efficiency reduces electricity consumption <strong>and</strong>, consequently,<br />

CO 2 , emissions <strong>and</strong> because it does not damage<br />

the ozone layer (ODP = 0).<br />

The scroll compressor has been expressly redesigned<br />

for use with the new gas <strong>and</strong> is now even more compact<br />

<strong>and</strong> silent than before.<br />

NECS, THE CLIMAVENETA R410A RANGE<br />

Scroll compressors,<br />

featuring high efficiency,<br />

low vibrations <strong>and</strong><br />

low noise emissions.<br />

R410A refrigerant,<br />

thanks to its enhanced <strong>heat</strong><br />

conductivity compared with R407C<br />

<strong>and</strong> the generous sizing of the<br />

<strong>heat</strong> exchange surfaces of the<br />

units, this refrigerant has<br />

considerably increased the EER<br />

<strong>and</strong> ESEER energy indices.<br />

Part load efficiency,<br />

part load efficiency has been improved<br />

(ESEER > 4.3) in the new single-circuit,<br />

dual-compressor version, with a 35%<br />

saving in seasonal electricity consumption<br />

compared with the previous R407C<br />

version.<br />

ESEER<br />

Range flexibility,<br />

the Climaveneta range has been designed<br />

to satisfy a wide variety of needs.<br />

For this reason, a good<br />

16 sizes <strong>and</strong> up to 5<br />

versions are<br />

available in<br />

the 34-262<br />

kW range.<br />

New controller, all the units can be connected<br />

to the new W3000 controller featuring a “user<br />

friendly” interface.<br />

Main functions:<br />

QuickMind, local <strong>and</strong><br />

remote FWS supervision,<br />

<strong>and</strong> dual setpoint<br />

management confirm<br />

Climaveneta's<br />

commitment to<br />

continually developing its<br />

electronics technology.<br />

IDRORELAX,<br />

the NECS range of<br />

<strong>chillers</strong> is available<br />

in the –IR configuration. This allows interfacing with<br />

the IDRORELAX system.


INTEGRATED HYDRONIC UNIT (Optional).<br />

Compact PLUG <strong>and</strong> PLAY units.<br />

NECS has been designed to reduce installation work to a minimum.<br />

The integrated hydronic unit incorporates all the hydraulic components, thus optimising installation space,<br />

time <strong>and</strong> costs.<br />

The integrated hydronic unit comprises:<br />

• storage tank<br />

• circulation pump with composite impeller<br />

• pre-mounted Y-shaped <strong>water</strong> filter with stainless steel mesh<br />

• <strong>water</strong> flow switch<br />

• pump inlet pressure gauge<br />

• output flow adjustment valve<br />

• safety valve<br />

• expansion tank<br />

• <strong>air</strong> vent<br />

• <strong>water</strong> drain.<br />

A circulation pump with a two-pole electric motor <strong>and</strong> an elevated useful static head is available<br />

for all sizes.<br />

Pumps with a low useful static head <strong>and</strong> a 2- or 4-pole electric motor are available for units with four<br />

compressors (NECS xxx4) in order to more fully adapt the unit to system requirements in terms of flow<br />

rate/head. On request, the hydronic assembly can be supplied with two circulation <strong>pumps</strong>, one of which<br />

backing up the other, featuring a programmed rotation schedule <strong>and</strong> automatic swap-over should the<br />

working pump fail.<br />

In this case, the hydronic assembly is fitted with a check valve in order to ensure the unit is installed <strong>and</strong><br />

operated correctly.<br />

Hydronic unit rendering


Comparison between NECS <strong>and</strong> traditional<br />

R407C units - Range from 34 to 262 kW<br />

The energy efficiency (EER) of these<br />

Climaveneta units is further enhanced thanks<br />

to the fact that the design of the <strong>heat</strong><br />

exchange surfaces, coils <strong>and</strong> plate exchangers<br />

was focused on minimising running costs.<br />

As well as achieving an EER close to 2.9,<br />

this design focus achieves very high levels<br />

of reliability <strong>and</strong> lengthens the working<br />

life of the compressor.<br />

EER<br />

2,90<br />

2,85<br />

2,80<br />

2,75<br />

2,7<br />

2,65<br />

2,60<br />

2,81<br />

2,63<br />

2,75<br />

2,61<br />

2,80<br />

2,82<br />

2,77<br />

+ 10%<br />

R407C unit<br />

2,89<br />

2,60 2,60<br />

2,55<br />

2,58<br />

2,54<br />

2,50<br />

ELEVATED PERFORMANCE AT ESEER PART LOADS<br />

Increasingly closer attention is being paid towards<br />

the power consumption of <strong>air</strong>-conditioning<br />

equipment, both at national <strong>and</strong> European level.<br />

An installed chiller reduces rated energy for<br />

extremely short periods of time, while most of the<br />

energy is produced with part loads ranging<br />

between 50% <strong>and</strong> 75%.<br />

The ESEER parameter proposed by Eurovent, takes<br />

part load operating conditions into account when<br />

assessing unit efficiency.<br />

It should be pointed out that units are only<br />

required to deliver 100% of their rated cooling<br />

power for 1.4% of their total running time,<br />

according to European calculations, <strong>and</strong> just 0.5%<br />

according to American calculations (IPLV).<br />

In these conditions, the energy produced by a unit<br />

accounts for respectively 3% <strong>and</strong> just 1% of the<br />

total energy produced during its working life.<br />

load - energy %<br />

125<br />

100<br />

75<br />

50<br />

25<br />

0<br />

ESEER<br />

carico<br />

peso<br />

18 20 22 24 26 28 30 32 34 36<br />

IPLV (American)<br />

carico<br />

peso<br />

12 14 16 18 20 22 24 26 28 30 32 34 36<br />

external <strong>air</strong> temperature (°C)<br />

external <strong>air</strong> temperature (°C)<br />

ESEER<br />

IPLV (American)<br />

Load <strong>Air</strong> temp. Time Energy <strong>Air</strong> temp. Time Energy<br />

100 % 35 °C 1,4 % 3 % 35 °C 0,5 % 1 %<br />

75 % 30 °C 19,9 % 33 % 26,7 °C 28,7 % 42 %<br />

50 % 25 °C 37,1 % 41 % 18,3 °C 46,2 % 45 %<br />

25 % 20 °C 41,6 % 23 % 12,8 °C 24,6 % 12 %<br />

Energy = percentage of total power produced in the various load conditions<br />

ESEER values of the new NECS units<br />

ESEER = Energy 100% * EER 100% + Energy 75% * EER 75% + Energy 50% * EER 50% + Energy 25% * EER 25%<br />

SINGLE-CIRCUIT<br />

NECS 302LN<br />

R410A UNIT<br />

EER 100% 2,59<br />

EER 75% 3,59<br />

EER 50% 4,45<br />

EER 25% 4,39<br />

TRADITIONAL TWO-CIRCUIT<br />

R407C UNIT<br />

WITH TWO SCROLL COMPRESSORS<br />

2,44 EER 100%<br />

2,71 EER 75%<br />

3,21 EER 50%<br />

3,27 EER 25%<br />

ESEER 4,10<br />

3,04 ESEER


NECS 0152-1004 Ver. 0152 0182 0202 0252 0302 0352 0412<br />

B 38,1 45,1 50,5 57,0 76,0 86,8 96,9<br />

Cooling capacity (1) LN 36,1 42,8 50,7 57,6 74,2 84,4 96,4<br />

SL 33,8 42,3 47,8 55,5 69,9 85,4 96,8<br />

B 14,4 15,6 19,1 21,5 27,8 31,9 36,3<br />

Total power input (1) LN 15,0 16,5 18,9 21,3 28,6 33,6 37,1<br />

SL 16,3 17,0 20,3 22,6 30,8 33,6 37,4<br />

B 2,65 2,89 2,65 2,65 2,73 2,72 2,67<br />

Total EER LN 2,40 2,60 2,68 2,71 2,59 2,51 2,60<br />

SL 2,07 2,49 2,35 2,46 2,27 2,54 2,59<br />

B 4,03 4,27 4,21 4,14 4,13 4,31 4,16<br />

ESEER LN 4,03 4,18 4,23 4,20 4,10 4,03 4,00<br />

SL 3,77 3,92 4,01 3,93 3,85 3,91 3,89<br />

B 84 84 84 84 85 86 86<br />

Sound power level (3) LN 79 79 80 80 81 83 83<br />

SL 76 77 77 78 78 81 81<br />

B 52 52 52 52 53 54 54<br />

Sound pressur level (4) LN 47 47 48 48 49 51 51<br />

SL 44 45 45 46 46 49 49<br />

NECS-N 0152-1004 Ver. 0152 0182 0202 0252 0302 0352 0412<br />

B 37,7 42,8 47,9 57,5 72,0 82,5 93,9<br />

Cooling capacity (1) LN 35,8 42,0 48,0 54,6 73,2 83,5 93,9<br />

SL - - - - - - -<br />

B 13,6 15,7 19,2 20,4 28,0 32,0 36,0<br />

Total power input (1) LN 14,3 16,2 19,1 21,3 27,2 32,0 36,0<br />

SL - - - - - - -<br />

B 42,6 47,8 53,8 64,8 80,6 92,9 105<br />

Heating capacity (2) LN 41,6 47,9 53,7 63,2 83,6 95,6 108<br />

SL - - - - - - -<br />

B 14,2 15,6 18,1 21,2 26,1 29,8 33,9<br />

Total power input (2) LN 13,8 15,3 18,1 20,7 26,0 30,4 34,2<br />

SL - - - - - - -<br />

B 2,99 3,07 2,97 3,06 3,09 3,12 3,09<br />

Total COP LN 3,01 3,14 2,97 3,06 3,21 3,14 3,17<br />

SL - - - - - - -<br />

B 84 84 84 84 85 86 86<br />

Sound power level (3) LN 79 79 80 80 81 83 83<br />

SL - - - - - - -<br />

B 52 52 52 52 53 54 54<br />

Sound pressure level (4) LN 47 47 48 48 49 51 51<br />

SL - - - - - - -<br />

NECS 0152-1004<br />

Dim. (5) Ver. 0152 0182 0202 0252 0302 0352 0412 0452 0512 0504 0524<br />

B 1695 1695 1695 1695 2195 2195 2745 2745 3245 3110 3110<br />

A LN 1695 1695 2195 2195 2745 2745 2745 2745 3245 3110 3110<br />

SL 1695 2195 2195 2745 2745 3245 3245 3245 3245 3110 3110<br />

B 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220<br />

B LN 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220<br />

SL 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220<br />

B 1420 1420 1420 1420 1420 1420 1420 1420 1620 1700 1700<br />

H LN 1420 1420 1420 1420 1420 1620 1620 1620 1620 1700 1700<br />

SL 1420 1420 1420 1420 1420 1620 1620 1620 1620 1700 2150<br />

B 370 410 410 420 620 650 730 780 930 1230 1450<br />

Operating<br />

LN 370 410 460 490 660 720 790 820 930 1230 1450<br />

weight<br />

SL 390 450 480 540 700 780 860 910 940 1360 1570<br />

NECS-N 0152-1004<br />

Dim. (5) Ver. 0152 0182 0202 0252 0302 0352 0412 0452 0512 0504 0524<br />

B 1695 1695 1695 2195 2195 2195 2745 2745 3245 3110 3110<br />

A LN 1695 1695 2195 2195 2745 2745 2745 2745 3245 3110 3110<br />

SL - - - - - - - - - 3110 3110<br />

B 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220<br />

B LN 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220<br />

SL - - - - - - - - - 2220 2220<br />

B 1420 1420 1420 1420 1420 1420 1420 1420 1620 1700 1700<br />

H LN 1420 1420 1420 1420 1420 1620 1620 1620 1620 1700 1700<br />

SL - - - - - - - - - 1700 2150<br />

B 400 410 420 500 630 690 770 850 950 1380 1570<br />

Operating<br />

LN 400 420 460 500 710 770 830 880 990 1380 1570<br />

weight<br />

SL - - - - - - - - - 1460 1700


0452 0512 0504 0524 0604 0704 0804 0904 1004<br />

112 127 113 136 154 177 200 223 255<br />

109 122 104 129 147 167 187 208 242<br />

106 118 113 130 147 162 193 211 235<br />

39,7 43,8 45,6 53,8 59,7 68,1 74,9 84,2 94,1<br />

41,4 46,0 47,9 53,5 60,0 69,6 77,6 87,8 95,3<br />

43,1 48,4 45,2 51,8 58,8 71,1 75,4 87,2 96,7<br />

2,83 2,90 2,48 2,53 2,58 2,60 2,67 2,65 2,71<br />

2,63 2,65 2,17 2,41 2,45 2,40 2,41 2,37 2,54<br />

2,46 2,44 2,50 2,51 2,50 2,28 2,56 2,42 2,43<br />

4,34 4,23 4,05 3,60 3,77 3,91 4,04 4,14 3,93<br />

4,21 4,04 3,92 3,85 3,92 4,02 3,98 4,07 4,01<br />

3,98 3,89 4,01 4,14 4,14 4,13 4,07 4,08 4,09<br />

86 87 91 92 92 92 92 93 94<br />

83 84 85 86 86 86 86 87 88<br />

81 82 82 82 82 82 83 83 83<br />

54 55 59 60 60 60 60 61 62<br />

51 52 53 54 54 54 54 55 56<br />

49 50 50 50 50 50 51 51 51<br />

0452 0512 0504 0524 0604 0704 0804 0904 1004<br />

107 120 111 129 147 166 189 211 240<br />

103 119 103 123 141 156 177 199 227<br />

- - 108 124 141 159 183 201 225<br />

39,9 44,0 43,7 54,0 60,0 68,9 75,9 85,1 95,6<br />

41,6 44,5 46,2 53,5 60,0 70,3 78,3 87,7 96,2<br />

- - 45,0 52,1 58,3 67,7 75,3 87,4 95,3<br />

121 135 127 145 167 185 209 234 267<br />

120 137 122 138 158 176 198 225 254<br />

- - 125 140 158 178 205 226 253<br />

38,1 42,3 43,6 52,7 58,0 64,7 72,1 79,9 92,1<br />

37,9 42,3 41,5 48,9 53,7 60,7 67,8 75,5 86,1<br />

- - 42,8 47,5 52,1 59,5 68,6 75,8 83,8<br />

3,18 3,19 2,91 2,75 2,88 2,86 2,90 2,93 2,90<br />

3,16 3,23 2,94 2,82 2,94 2,90 2,92 2,98 2,95<br />

- - 2,92 2,95 3,03 2,99 2,99 2,98 3,02<br />

86 87 91 92 92 92 92 93 94<br />

83 84 85 86 86 86 86 87 88<br />

- - 82 82 82 82 83 83 83<br />

87 55 59 60 60 60 60 61 62<br />

84 52 53 54 54 54 54 55 56<br />

- - 50 50 50 50 51 51 51<br />

0604 0704 0804 0904 1004<br />

3110 3110 3110 4110 4110<br />

3110 3110 3110 4110 4110<br />

3110 3110 4110 4110 4110<br />

2220 2220 2220 2220 2220<br />

2220 2220 2220 2220 2220<br />

2220 2220 2220 2220 2220<br />

1700 2150 2150 2150 2150<br />

1700 2150 2150 2150 2150<br />

2150 2150 2150 2150 2150<br />

1620 1780 1890 2070 2220<br />

1620 1780 1890 2070 2220<br />

1770 1860 2120 2180 2320<br />

Data referred to:<br />

Units fitted with a hydronic unit with one 2-pole high-head pump. Data<br />

referring to other configurations can be obtained from our sales department.<br />

1) Evaporator <strong>water</strong> (in/out) 12/7 °C<br />

Condenser <strong>air</strong> (in) 35 °C<br />

2) Condenser <strong>water</strong> (in/out) 40/45 °C<br />

Evaporator <strong>air</strong> (in) 7 °C<br />

3) Acoustic power measured according to ISO 3744 <strong>and</strong> Eurovent 8/1.<br />

4) Acoustic pressure measured in free field conditions on a reflecting plane.<br />

Average value on the condensing coil side, 10 metre from the outer surface <strong>and</strong><br />

10 metre above the base of the unit.<br />

4) Free space required around the unit:<br />

Electrical panel side 600 mm<br />

Opposite side from electrical panel 600 mm<br />

Condensation coil side 1000 mm<br />

The information contained in this document may be modified without notice<br />

<strong>and</strong> refers to units designed for the European Market.<br />

0604 0704 0804 0904 1004<br />

3110 3110 3110 4110 4110<br />

3110 3110 3110 4110 4110<br />

3110 3110 4110 4110 4110<br />

2220 2220 2220 2220 2220<br />

2220 2220 2220 2220 2220<br />

2220 2220 2220 2220 2220<br />

1700 2150 2150 2150 2150<br />

1700 2150 2150 2150 2150<br />

2150 2150 2150 2150 2150<br />

1750 1900 2080 2270 2410<br />

1750 1900 2080 2270 2410<br />

1900 2050 2310 2370 2520<br />

H<br />

H<br />

A<br />

A<br />

B<br />

B<br />

NECS / NECS-N 0152-0512 NECS / NECS-N 0504-1004


LOW-NOISE VERSIONS<br />

Two noise reduction versions are available<br />

for all sizes: low noise <strong>and</strong> super low noise.<br />

Low noise levels are achieved by reducing<br />

fan speed while the circuitry has been optimised<br />

<strong>and</strong> the coils generously sized to ensure<br />

the unit works correctly.<br />

Example of low-noise configuration<br />

NECS 0704 sound power levels:<br />

LN version =- 6<br />

dB(A)<br />

compared with the st<strong>and</strong>ard version<br />

SL version =-10 dB(A)<br />

compared with the st<strong>and</strong>ard version<br />

Climaveneta certifies <strong>and</strong> guarantees<br />

its noise parameters<br />

CONTROLLER WITH LCD INTERFACE<br />

All the units can be connected to the new W3000<br />

controller featuring a “user friendly” interface.<br />

(Std. for 4 compressors).<br />

The interface is also available in the remote version.<br />

Main functions: QuickMind, local <strong>and</strong> remote FWS<br />

supervision, dual setpoint management, etc.,<br />

confirm Climaveneta's commitment to continually<br />

developing its electronics technology.<br />

The <strong>heat</strong> <strong>pumps</strong>, moreover, are fitted with the original<br />

Climaveneta defrosting control system called “Autotuning<br />

Defrost” which considerably reduces defrosting times,<br />

thus improving the energy performance of the unit.<br />

Interfaces with BMS systems: METASYS ® , MODBUS ® ,<br />

LONWORKS ® , SYEMENS ® , TREND ® .<br />

QuickMind is a special control unit which monitors<br />

the main operating parameters, predicts system<br />

behaviour <strong>and</strong> anticipates unit settings in order<br />

to constantly optimise performance; it allows both<br />

return <strong>and</strong> delivery <strong>water</strong> temperatures to be chosen<br />

as adjustment parameters.<br />

Black Box logs data relative<br />

to 200 alarm events which<br />

can be printed with any kind<br />

of personal computer.<br />

IDRORELAX<br />

The NECS range of <strong>chillers</strong> with <strong>heat</strong> pump is available<br />

in the IR configuration; this allows units to be combined<br />

with IDRORELAX, a centralised hydronic system<br />

for managing cooling <strong>and</strong> <strong>heat</strong>ing requirements<br />

<strong>and</strong> producing hot running <strong>water</strong> for residential, hotel <strong>and</strong> office applications.<br />

Further information on the IDRORELAX system can be obtained by consulting<br />

the relative documentation.


A100HL_101_110D_CV_05_06_GB (V.02)<br />

CLIMAVENETA S.p.A.<br />

Via Sarson, 57/c<br />

36061 Bassano del Grappa (VI) - Italia<br />

Tel. +39 0424 509 500<br />

Fax +39 0424 509 509<br />

info@climaveneta.it<br />

www.climaveneta.it

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!