Manufacturing<br />

Birch Road<br />

Dumbarton, G82 2RF<br />

Tel: 0044 (0)1389 742214<br />

Fax: 0044 (0)1389 742554<br />

EQUIPMENT DATA SHEET<br />

Diesel Generating Set<br />

50Hz 500kVA<br />

60Hz<br />

500kW<br />

No.<br />

Rev.<br />

Date<br />

Page<br />

G08.0137<br />

A<br />

Aug 98<br />

1 of 3<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

Model<br />

Part Number<br />

Specification<br />

Installation Drawing<br />

Maximum Ambient<br />

Electrical Output<br />

ISO 8528-1<br />

- Continuous <strong>Power</strong> (COP)<br />

- Prime <strong>Power</strong> (PRP)<br />

- Permissable average of PRP<br />

ISO3046/1<br />

- Fuel Stop <strong>Power</strong>/Standby<br />

Single Step load application<br />

Alternator<br />

Class F Temp. Rise (105°C)<br />

- Three phase<br />

- Single phase<br />

Ends Out<br />

Make & Type<br />

AVR<br />

Regulation<br />

Circuit Breaker<br />

Make & Type<br />

Number of poles<br />

Rating<br />

Trip Unit Type<br />

Overload <strong>Pro</strong>tection Range<br />

Short Circuit <strong>Pro</strong>tection Range<br />

Load Terminals<br />

Type<br />

Fuel Consumption<br />

Standby/Fuel Stop<br />

100% Prime <strong>Power</strong><br />

75%<br />

50%<br />

SEE NOTE (ii)<br />

Ref<br />

Ref<br />

Ref<br />

SEE NOTE (i) Ref<br />

°C (°F)<br />

kW (kVA)<br />

kW (kVA)<br />

kW (kVA)<br />

Amps<br />

Amps<br />

Amps<br />

lit/hr(US gal/hr)<br />

" "<br />

" "<br />

" "<br />

Technical Department - Dumbarton Approved by<br />

Hz<br />

kW (kVA)<br />

kW (kVA)<br />

%<br />

%<br />

%<br />

NHC20 / KTA19G4<br />

602050<br />

602051<br />

602061<br />

602074<br />

G32.0016<br />

A05.0068<br />

56 (132)<br />

50<br />

328 (410)<br />

416 (520)<br />

70<br />

467 (584)<br />

64<br />

443 (554)<br />

176 (220)<br />

12<br />

Newage Stamford HCI534E2<br />

MX321<br />

± 0.5<br />

Terasaki XS1250NE<br />

4<br />

1250<br />

Electronic<br />

630 - 1250<br />

2363 - 15000<br />

Busbar M12<br />

121 (31.9)<br />

107 (28.4)<br />

UNCONTROLLED<br />

82 (21.6)<br />

57 (14.9)<br />

53 (127)<br />

60<br />

397 (496)<br />

470 (588)<br />

70<br />

523 (654)<br />

64<br />

520 (650)<br />

182 (228)<br />

133 (35.2)<br />

120 (31.7)<br />

92 (24.3)<br />

65 (17.0)<br />

FOR INFORMATION ONLY


Manufacturing<br />

Birch Road<br />

Dumbarton, G82 2RF<br />

Tel: 0044 (0)1389 742214<br />

Fax: 0044 (0)1389 742554<br />

EQUIPMENT DATA SHEET<br />

Diesel Generating Set<br />

50Hz 500kVA<br />

60Hz<br />

500kW<br />

No.<br />

Rev.<br />

Date<br />

Page<br />

G08.0137<br />

A<br />

Aug 98<br />

2 of 3<br />

11<br />

Running Hours<br />

100% Prime <strong>Power</strong><br />

Hours<br />

11.7<br />

10.4<br />

75%<br />

15.3<br />

13.6<br />

50%<br />

22.0<br />

19.3<br />

12<br />

Exhaust Emissions<br />

Measurement Method<br />

Cummins Exhaust Emissions Data Sheet<br />

Specific Load<br />

100% Prime ±2%<br />

NOx - Oxides of Nitrogen<br />

(g/kW.h)<br />

12.30<br />

12.06<br />

PM - Particulate Matter<br />

0.20<br />

0.13<br />

CO - Carbon Monoxide<br />

4.29<br />

1.23<br />

HC - Unburnt Hydrocarbons<br />

0.23<br />

0.25<br />

13<br />

Exhaust Silencer<br />

Make & Type<br />

Discom or IMS type MAA<br />

Certificate<br />

No<br />

M-8872 or M-8154<br />

Permissable back pressure<br />

mm (ins) Hg<br />

12 (0.5”)<br />

12 (0.5”)<br />

14<br />

Noise<br />

Sound <strong>Power</strong> - EEC<br />

dBA (Lw)<br />

98.7<br />

Certificate<br />

No<br />

GB/02/778/97<br />

Sound Pressure at 1 metre<br />

dBA<br />

77<br />

80<br />

Sound Pressure at 7 metre<br />

dBA<br />

74<br />

77<br />

15<br />

Engine<br />

Make & Type<br />

Cummins KTA19G4<br />

Cylinders & Form<br />

6 Inline<br />

Aspiration<br />

Turbocharged and Aftercooled<br />

Fuel Pump<br />

Cummins PT<br />

Governor Type<br />

Electronic<br />

Make & Model<br />

Cummins EFC<br />

Steady State frequency<br />

%<br />

± 0.25<br />

Battery Voltage<br />

Volts<br />

24<br />

16<br />

Overall Dimensions<br />

SEE NOTE (i)<br />

- Length<br />

Metres (feet)<br />

6.06 (20’0”)<br />

- Width<br />

Metres (feet)<br />

2.44 (8’0”)<br />

- Height<br />

Metres (feet)<br />

2.60 (8’6”)<br />

17<br />

Weight<br />

SEE NOTE (i)<br />

- Without fuel<br />

Kg (lbs)<br />

10856 (23933)<br />

- With fuel<br />

Kg (lbs)<br />

12072 (26614)<br />

UNCONTROLLED<br />

Technical Department - Dumbarton Approved by<br />

FOR INFORMATION ONLY


Manufacturing<br />

Birch Road<br />

Dumbarton, G82 2RF<br />

Tel: 0044 (0)1389 742214<br />

Fax: 0044 (0)1389 742554<br />

EQUIPMENT DATA SHEET<br />

Diesel Generating Set<br />

50Hz 500kVA<br />

60Hz<br />

500kW<br />

No.<br />

Rev.<br />

Date<br />

Page<br />

G08.0137<br />

A<br />

Aug 98<br />

3 of 3<br />

18<br />

Capacities<br />

- Fuel gross<br />

Litres (US gall)<br />

1431 (378)<br />

usable<br />

1253 (331)<br />

- Lub oil total<br />

50 (13)<br />

pan<br />

38-32 (10-8.5)<br />

- Coolant<br />

112 (30)<br />

19<br />

External fuel supply<br />

- maximum above base<br />

Metres (feet)<br />

2.40 (7’10”)<br />

- maximum below base<br />

Metres (feet)<br />

1.50 (4’11”)<br />

Notes<br />

(i)<br />

(ii)<br />

On the DNV model the following applies:<br />

4. Installation Drawing Ref A05.0107<br />

16. Length Metres (feet) 6.18 (20’3”)<br />

17. Weight<br />

- Without fuel Kg (lbs) 12336 (27196)<br />

- With fuel Kg (lbs) 13552 (29877)<br />

On USA and AIP (602074) specification sets, the following UL approved circuit breaker is fitted:<br />

Make and Type<br />

Merlin Gerin UL Masterpact MP20 ACB<br />

Number of Poles 3<br />

Rating Amps 2000<br />

Trip Unit Type<br />

STR58U<br />

Overload <strong>Pro</strong>tection Range Amps 800 - 2000 (rating plug dependent)<br />

Short Circuit <strong>Pro</strong>tection Range Amps 1200 - 20000 (rating plug dependent)<br />

On plant numbers 7921 onwards an IEC type control unit is fitted in place of rating plugs. Therefore, the<br />

protection ranges, dependent on position of selector switch are as follows:<br />

Overload <strong>Pro</strong>tection Range Amps 800 - 2000<br />

Short Circuit <strong>Pro</strong>tection Range Amps 4000 - 40000<br />

UNCONTROLLED<br />

Technical Department - Dumbarton Approved by<br />

FOR INFORMATION ONLY