Fire protection<br />

Overview of fire protection products for<br />

pipe penetrations<br />

Product<br />

Area of application<br />

MÜPROFLAM fire<br />

intumescent pipe collar<br />

Isolation of <strong>com</strong>bustible<br />

piping<br />

MÜPROFLAM fire<br />

intumescent sealant<br />

Intumescent fire protection<br />

sealant for the bulkheading<br />

of <strong>com</strong>bustible<br />

and and non-<strong>com</strong>bustible<br />

pipes and for single flammable<br />

cables<br />

MypoTHERM ® caoutchouc<br />

Bulkheading of insulated<br />

heating system pipes and<br />

hot water pipes<br />

MypoTHERM ® caoutchouc<br />

for chilled water<br />

Bulkheading of insulated<br />

cold water pipes<br />

Fire resistance duration R90 R90 R60–R120 R90–R120<br />

Building material class B2 acc. to DIN 4102 B1 acc. to DIN 4102 B1 acc. to DIN 4102<br />

Combustible pipes <strong>Pipe</strong> outer diameter<br />

32 – 160 mm<br />

Wall thickness<br />

1.8 – 6.2 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 32 mm<br />

Copper piping<br />

Steel, stainless steel<br />

piping<br />

Cast pipe<br />

<strong>Pipe</strong> outer diameter<br />

≤ 160 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 160 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 160 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 48 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 48 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 48 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 42 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 76 mm<br />

<strong>Pipe</strong> outer diameter<br />

≤ 76 mm<br />

Insulation Acc. to LAR 03/2000 9 – 38 mm 13 – 32 mm<br />

Ceiling penetration Thickness ≥ 150 mm Thickness ≥ 80 mm Thickness ≥ 150 mm Thickness ≥ 150 mm<br />

Wall penetration Thickness ≥ 100 mm Thickness ≥ 80 mm Thickness ≥ 150 mm Thickness ≥ 150 mm<br />

Light partition wall Thickness ≥ 100 mm Thickness ≥ 80 mm<br />

Supplementary products Plugs, anchors or threaded<br />

rods with washers and<br />

Mineral wool melting<br />

point<br />

Mortar<br />

MG 2, 2a or 3<br />

Mortar<br />

MG 2, 2a or 3<br />

nuts<br />

Ts > 1,000 °C<br />

Verification, specification Z-19.11-1668 LAR 03/2000, previously P-3487/0239-MPA BS P-3487/0239-MPA BS<br />

MLAR 03/2000<br />

Documentation Nameplate<br />

Declaration of conformity<br />

Declaration of conformity Declaration of conformity<br />

Remarks<br />

Annular gap width<br />

≤ 15 mm<br />

Keep to the distance<br />

specifications in LAR<br />

03/2000<br />

Gap between adjacent<br />

insulations, A ≥ 200 mm<br />

Observe the fire resistance<br />

specifications in the<br />

test certificate<br />

Gap between adjacent<br />

insulations, A ≥ 100 mm<br />

Observe the fire resistance<br />

specifications in the<br />

test certificate<br />

2/2<br />