03.01.2015 Views

Gestra® Float Trap • Liquid Drainer UNA 14P

Gestra® Float Trap • Liquid Drainer UNA 14P

Gestra® Float Trap • Liquid Drainer UNA 14P

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

fl owserve.com<br />

Gestra ® <strong>Float</strong> <strong>Trap</strong> •<br />

<strong>Liquid</strong> <strong>Drainer</strong><br />

Class Rating: <strong>UNA</strong> 14p - PN 16 Available Sizes: ½", ¾" and 1"<br />

(DN 15, 20 and 25)<br />

<strong>UNA</strong> <strong>14P</strong><br />

230<br />

psi<br />

Maximum Δp<br />

(16 bar)<br />

Not intended for use as a steam trap.<br />

<strong>UNA</strong> 14p: 230 Maximum Δp<br />

Application<br />

<strong>UNA</strong> <strong>14P</strong> (Simplex with Perbunan ball):<br />

Same as the 14/16 except the SST ball is replaced with a<br />

Perbunan (Buna-N) ball for improved air closure.<br />

Temperature and pH limitations apply. Please consult with<br />

your local Flowserve Gestra representative.<br />

Features and Benefits<br />

• Bolted cover for in-line inspection and maintenance.<br />

• Easily field-converted from horizontal (H) to vertical (V) to<br />

reduce inventories.<br />

• Useful for other heat transfer fluids.<br />

• Operation is unaffected by back pressure.<br />

• Rolling ball valve mechanism ensures smooth operation<br />

with no sticking and minimum wear. Internal SST shielding<br />

prevents body damage from outlet flows.<br />

• Hand Vent Valve Option<br />

• Two (2) year guarantee.<br />

Materials<br />

• Body and Cover – Cast Iron A126 Cl B (DIN 0.6025)<br />

• All Other Internals – Stainless Steel<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Pressure / Temperature Ratings<br />

With Perbunan valve ball<br />

<strong>UNA</strong> 14p<br />

[psig] 230<br />

Maximum Service Pressure<br />

[barg] 16<br />

[°F] 104<br />

Related Temperature<br />

[°C] 40<br />

Maximum Differential Pressure 230 psi (16 bar)<br />

<br />

With Steel valve ball<br />

<strong>UNA</strong> 14p<br />

[psig] 230<br />

Maximum Service Pressure<br />

[barg] 16<br />

[°F] 248<br />

Related Temperature<br />

[°C] 120<br />

Maximum Differential Pressure 230 psi (16 bar)<br />

Dimensions and Weights<br />

Nominal Sizes<br />

End Connections [inch] 1/2 3/4 1<br />

[mm] 15 20 25<br />

Flanged L<br />

[inch] 5.9 5.9 6.3<br />

[mm] 150 150 160<br />

Butt-Weld L<br />

[inch] 7.9 7.9 7.9<br />

[mm] 200 200 200<br />

Socketweld L [inch] 3.7 3.7 3.7<br />

Screwed [mm] 95 95 95<br />

Approx. Weight Flanged [lbs] 13 14 15<br />

[kg] 6 6.5 7<br />

S.W., B.W. [lbs] 10 10 3<br />

Screwed [kg] 4.5 4.5 1.5


230<br />

psi<br />

Maximum Δp<br />

(16 bar)<br />

Gestra ® <strong>Float</strong> <strong>Trap</strong> •<br />

<strong>Liquid</strong> <strong>Drainer</strong><br />

Class Rating: <strong>UNA</strong> 14p - PN 16 Available Sizes: ½", ¾" and 1"<br />

(DN 15, 20 and 25)<br />

<strong>UNA</strong> <strong>14P</strong><br />

<br />

<br />

<br />

<br />

<br />

Capacity Charts<br />

The charts show the maximum capacities of cold water<br />

based on the orifice of the liquid drainers. The capacities<br />

are a function of differential pressure or the difference<br />

between inlet and outlet pressures for the trap.<br />

<br />

<br />

<br />

<br />

Orifice Number<br />

The orifice number listed on the capacity curve refers to<br />

the maximum differential pressure (in bar) for which the<br />

<strong>UNA</strong> 14p may be used.<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Body Pressure/Temperature Rating<br />

The chart shows the maximum shell (body) pressure<br />

and temperature rating. Operating differential pressure is<br />

limited to 230 psi.<br />

Material/Test Certificates<br />

All inspection requirements must be stated at time of order.<br />

Test certificates can be issued on request in accordance<br />

with EN 10204 – 2.2 and -3.1B. Heat codes from body and<br />

cover are required for certifications.<br />

<br />

Available End Connections<br />

NPT<br />

Flanged: ANSI 150<br />

How to Order<br />

Specify drainer, initial orientation, end connection size<br />

and orifice. Horizontal (H) provided as standard initial<br />

orientation. Please specify if vertical (V) inital orientation<br />

is desired.<br />

<br />

<br />

For Example: <strong>UNA</strong> 14hp A016 1" NPT<br />

Standard Spare Parts<br />

D<br />

G<br />

Item<br />

Number<br />

Description<br />

<strong>UNA</strong> 14<br />

Control Unit with Perbunan Ball<br />

Orifice 16 560418<br />

Cover<br />

Gasket<br />

522752