RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

560CMG10<br />

560CIG10<br />

Serial interfaces 3<br />

Ethernet 10/100 BaseT 1<br />

Integrated I/Os<br />

16 binary inputs<br />

8 binary outputs<br />

8 analog inputs (mA)<br />

Extension<br />

I/O modules<br />

Dimensions<br />

W x H x D<br />

Binary inputs/outputs<br />

Analogue inputs/outputs<br />

Direct analog inputs<br />

Optional: fault current detection<br />

204 x 105 x 55 mm 230 x 150 x 84 mm<br />

© ABB Group<br />

March 4, 2012 | Slide 3


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

23CM61<br />

DIN rail RTU211<br />

Serial interfaces 1/4 3<br />

Ethernet 10/100<br />

BaseT<br />

Integrated I/Os<br />

0 1<br />

16 binary inputs<br />

8 binary outputs<br />

560<strong>CMU</strong>01<br />

Up to 4 of the following modules:<br />

16 binary inputs<br />

8 binary outputs<br />

6 analog inputs (mA)<br />

2 analog outputs<br />

6 temperature sensors<br />

Extension<br />

I/O modules<br />

Binary inputs/outputs<br />

Analog inputs/outputs<br />

Binary inputs/outputs<br />

Analog inputs/outputs<br />

Direct analog inputs<br />

Optional: Fault current detection<br />

Dimensions<br />

W x H x D<br />

(290 – 400) x 116 x 81 mm (181 – 741) x 116 x 81 mm<br />

Depending on integrated I/Os<br />

© ABB Group<br />

March 4, 2012 | Slide 4


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

23CM61<br />

512 kByte flash memory<br />

256 kByte RAM<br />

4 x RS232 ports<br />

RP570 communication protocols<br />

IEC 60870-5-101 or DNP3<br />

communication protocols<br />

Built-in “Local Automation Function”<br />

(LAF)<br />

Monitoring of system power<br />

Integrated alarm relay<br />

16 binary inputs<br />

8 binary outputs<br />

6 analog inputs<br />

1 out of n check<br />

© ABB Group<br />

March 4, 2012 | Slide 5


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

RTU211 based on 560<strong>CMU</strong>01<br />

560<strong>CMU</strong>01<br />

<br />

<br />

3 serial interfaces<br />

1 ethernet interface<br />

Up to 4 of the following I/O modules:<br />

<br />

<br />

<br />

<br />

<br />

16 binary inputs<br />

8 binary outputs<br />

6 analog inputs (mA)<br />

2 analog outputs<br />

6 temperature sensors<br />

560PSU10<br />

<br />

Total output of approx. 38 W, split to:<br />

+ 5 V DC and 1 A = 5 Watt<br />

+ 15 V DC and 0.5 A = 7.5 Watt<br />

15 V DC and 0.5 A = 7.5 Watt<br />

+ 18 V DC and 1A = 18 W<br />

© ABB Group<br />

March 4, 2012 | Slide 6


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

Binary input Binary output Analog input Analog output<br />

23BI61<br />

23BO62/63<br />

23AI60<br />

23AO60<br />

<strong>CMU</strong>s 16 inputs 24/ 48/ 60 VDC 3A @ 110 VDC / 3A Analog inputs mA DC Analog output mA DC<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

23BE40<br />

16 inputs 110/ 220/250 VDC<br />

23BA40<br />

50 VA (L/R=40ms) @ 220 VDC / 8A<br />

560CVT02<br />

Analog inputs A/V AC<br />

23BE50<br />

64 inputs 24/ 48/ 60 VDC<br />

560CVT10<br />

Analog inputs<br />

© ABB Group<br />

March 4, 2012 | Slide 7


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Binary input 23BI61<br />

16 binary inputs for single or double<br />

indication, digital measurands,<br />

pulse counter<br />

R0001: 2448 VDC<br />

R0002: 60110 VDC<br />

Grouped with common return per 8<br />

inputs<br />

One LED per input<br />

1 ms time resolution<br />

Length 105 mm<br />

Housing should be ordered<br />

separately<br />

© ABB Group<br />

March 4, 2012 | Slide 8


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Direct process-interface 23BE40<br />

16 binary input channels<br />

Input Voltage<br />

110 VDC: 23BE40 R0011<br />

220 VDC: 23BE40 R0012<br />

Inputs without common<br />

return<br />

Galvanic insulation by optocouplers<br />

Input current 1,5 mA (chopped)<br />

Oxide film break function for 8<br />

inputs<br />

LEDs for signalization of input<br />

channels<br />

Power supply: 24 Vdc<br />

© ABB Group<br />

March 4, 2012 | Slide 9


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

64 binary input module 23BE50<br />

64 binary inputs<br />

Input range: 2460 VDC<br />

Input functions as 23BE23<br />

Groups with common return per 16<br />

inputs<br />

Galvanic insulation by optical<br />

couplers<br />

LEDs for signalization of each input<br />

channel<br />

Power supply: 24 VDC<br />

Usable without additional terminals<br />

© ABB Group<br />

March 4, 2012 | Slide 10


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Binary output 23BO62<br />

8 binary relay outputs for 1, 1,5 or 2<br />

pole commands<br />

Isolated outputs<br />

One LED per output<br />

High switching capacity:<br />

3A @ 110 VDC<br />

Continuous current: 3A<br />

Length 140 mm<br />

Housing should be ordered<br />

separately<br />

© ABB Group<br />

March 4, 2012 | Slide 11


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

1 out of n check 23BO63<br />

1 out of n supervision in<br />

combination with 23BO62<br />

High switching capacity up to 110<br />

VDC, 3 A<br />

Length 70 mm<br />

Housing should be ordered<br />

separately<br />

© ABB Group<br />

March 4, 2012 | Slide 12


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Direct process-interface 23BA40<br />

16 binary relay output channels<br />

Outputs without common return<br />

(23BA40 R0011)<br />

Galvanic insulation by relays<br />

Switching voltage<br />

max. 250 VDC/AC<br />

Switching capacity:<br />

50 VA (L/R=40ms) @ 220 VDC<br />

Continuous current: 8A<br />

© ABB Group<br />

March 4, 2012 | Slide 13


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Analog input 23AI60<br />

6 analog inputs<br />

Resolution: 11 bit +sign<br />

Accuracy class: 0,25<br />

Ranges: ± 5mA, ± 10 mA,<br />

+20 mA, 420 mA, ± VDC, ±<br />

10VDC<br />

Length: 70 mm<br />

Housing should be ordered<br />

separately<br />

© ABB Group<br />

March 4, 2012 | Slide 14


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Direct transducer interface 560CVT02<br />

3 voltage inputs 110 VAC<br />

110 VAC: 560CVT02 R000x<br />

(for measurement with voltage<br />

transformers)<br />

230 VAC: 560CVT02 R001x<br />

(for direct voltage measurement at<br />

the low voltage side)<br />

3 Current Inputs<br />

1A: 560CVT02 R00x1<br />

5A: 560CVT02 R00x5<br />

Accuracy: 0,2%<br />

Calculated values:<br />

Active, reactive, apparent power<br />

Active, reactive energy<br />

Power factor<br />

Frequency<br />

Harmonic distortion (THD)<br />

Integrated in RTU560 engineering<br />

© ABB Group<br />

March 4, 2012 | Slide 15


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s R0011: 1A<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Over Current Detection<br />

Saturation<br />

Phase x Current<br />

OCx_FV<br />

Over Current detected<br />

Time<br />

Direct transducer interface 560CVT10<br />

3 current inputs<br />

<br />

R0015: 5A<br />

3 voltage inputs max. 300V<br />

Accuracy up to 0.2%<br />

Low input burden<br />

<br />

<br />

Voltage 0.15VA at 300 V<br />

Current 0.2 VA of rating<br />

Additional fault current measurement<br />

up to 20 x line<br />

Over current detection<br />

Total harmonic distortion (THD)<br />

PLC applications for voltage dip<br />

detection available<br />

Power supply: 24V DC (± 20%)<br />

MODBUS interface<br />

Integrated in RTU560 engineering<br />

© ABB Group<br />

March 4, 2012 | Slide 16


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Analog output 23AO60<br />

2 analog outputs for set points<br />

Resolution: 11 bit +sign<br />

Accuracy class: 0,25<br />

Ranges: ± 2,5 mA, ± 5mA, ± 10 m,<br />

± 20 mA, 420 mA, ± 1 VDC,<br />

± 10VDC<br />

Length: 105 mm<br />

Housing should be ordered<br />

separately<br />

© ABB Group<br />

March 4, 2012 | Slide 17


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Analog line modems<br />

560FSM10/11<br />

1872 VDC<br />

Serial optical interfaces<br />

560FOC40<br />

18...30VDC<br />

560FOC80<br />

5 VDC<br />

23SC60<br />

R008 glass fiber<br />

R009 plastic fiber<br />

ABB 560FOC80<br />

© ABB Group<br />

March 4, 2012 | Slide 18


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Modem 560FSM10 and 560FSM11<br />

560FSM10<br />

V.23 modem<br />

Functionality comparable to<br />

23WT23<br />

Power supply: 1872 VDC<br />

560FSM11 R0001<br />

9600 baud modem<br />

Functionality comparable to<br />

23WT24<br />

Power supply: 18..72 VDC<br />

© ABB Group<br />

March 4, 2012 | Slide 19


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Serial optical interface 560FOC40 and<br />

560FOC80<br />

Opto coupler unit<br />

Power supply:<br />

560FOC40: 24 VDC (18..30VDC)<br />

560FOC80: 5 VDC<br />

Support of glass fiber (62,5/125µm)<br />

BFOC 2,5 connector<br />

RS485 electrical interface<br />

ABB 560FOC80<br />

Compatible to 23OK22/24<br />

© ABB Group<br />

March 4, 2012 | Slide 20


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Star coupler 23SC60<br />

Used to connect decentralize I/O<br />

racks up to 2 km<br />

Versions for different medias<br />

R008x: multi mode glass fiber<br />

R009x: plastic fiber<br />

2..5 optical interfaces per housing<br />

available<br />

To be used to connect 23BE40,<br />

23BA40 and 23BE50 to DIN rail<br />

RTUs<br />

© ABB Group<br />

March 4, 2012 | Slide 21


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Power supply units<br />

560PSU10<br />

560PSU40<br />

Input 110220<br />

VDC<br />

Output 24<br />

VDC/2,5A<br />

560PSU41 23PU63<br />

Input 2460 VDC Input 24110 VDC<br />

Output 24 VDC/2,5A Output 5V/1A, ±15V/0,<br />

18V/1A, 24V/0,5A<br />

23VG23/24<br />

© ABB Group<br />

March 4, 2012 | Slide 22


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Power supply 23PSU40/41<br />

Input voltage<br />

560PSU40: 110220 VDC<br />

560PSU41: 2460 VDC<br />

Max. output power 60 W, 24 VDC:<br />

2,5 A<br />

1 LED for voltage supervision<br />

24VDC<br />

Overload and short-circuit<br />

protection<br />

Power good signal available (only<br />

560PSU40)<br />

Parallel peration possible (only<br />

560PSU40)<br />

© ABB Group<br />

March 4, 2012 | Slide 23


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

560PSU10<br />

560PSU10: Power supply unit for<br />

RTU560 DIN rail in cooperation with<br />

560<strong>CMU</strong>01<br />

The 560PSU10 supplies a total<br />

output of approx. 38 W. This is split<br />

to:<br />

<br />

<br />

<br />

<br />

+ 5 V DC and 1 A = 5 Watt<br />

+ 15 V DC and 0.5 A = 7.5 Watt<br />

15 V DC and 0.5 A = 7.5 Watt<br />

+ 18 V DC and 1A = 18 W<br />

© ABB Group<br />

March 4, 2012 | Slide 24


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

Power supply 23PU63<br />

25W power supply<br />

Input voltage<br />

24 – 110 VDC (+/- 20%)<br />

Output voltage<br />

5V 1A (internal usage)<br />

+/-15V 0,2 A (RS232, AI/AO)<br />

18 V 1A (relays, AO)


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Main adapter 23VG23<br />

Input Voltage 115 / 230 V AC<br />

without switch over<br />

24 VDC output voltage<br />

Power output 48 W<br />

Output current min. 0.2 A and max.<br />

2 A<br />

Integrated components:<br />

<br />

<br />

<br />

Battery charging device<br />

Switch over device<br />

Exhaustive discharge protection<br />

© ABB Group<br />

March 4, 2012 | Slide 26


<strong>Modules</strong><br />

RTU560/RTU211 DIN rail solution<br />

Technical data<br />

RTU560 for DIN rail<br />

Technical data<br />

RTU211 for DIN rail<br />

<strong>CMU</strong>s<br />

I/Os<br />

Communication<br />

modules<br />

Auxiliary<br />

Main adapter 23VG24<br />

Input Voltage 115 / 230 V AC<br />

Power output approx. 240 W<br />

24 VDC output voltage<br />

Output current max. 10 A<br />