Paper 3 –<strong>Set</strong> A Key<br />
Statement A: Reducing condensing temperature by 5.5°C, results in a 20 – 25% decrease in<br />
compressor power consumption<br />
Statement B: 5.5°C increase in evaporator temperature reduces compressor power<br />
consumption by 20 – 25%<br />
a) statements A & B are TRUE b) statements A & B are FALSE<br />
c) statement A is TRUE & B is FALSE d) statement A is FALSE & B is TRUE<br />
24 Decreasing the rpm of a fan at partial loading by 10% results in:<br />
25<br />
a) decrease of 10% in flow rate <strong>and</strong> decrease of 27% in power requirement<br />
b) decrease of 10% in flow rate <strong>and</strong> decrease of 19% in power requirement<br />
c) decrease of 10% in flow rate <strong>and</strong> increase of 10% in power requirement<br />
d) increase of 10% in flow rate <strong>and</strong> no appreciable change in power requirement<br />
The power drawn by a centrifugal fan is<br />
a) inversely proportional to fan efficiency b) directly proportional to fan efficiency<br />
c) inversely proportional to static pressure d) inversely proportional to flow rate<br />
26 The frictional loss in a piping system is proportional to<br />
a) flow b) flow 2 c) 1/flow d) 1/flow 2<br />
27 For the same flow, through which of the following diameter pipes, the pump will work with<br />
maximum pressure<br />
a) 100 mm b) 150 mm c) 200 mm d) 250 mm<br />
28 It is possible to run pumps in parallel if their _________________ are similar.<br />
a) suction heads b) discharge heads c) closed valve heads d) none of the above<br />
29 Input power to the motor driving a pump is 20 kW. The motor efficiency is 0.9 <strong>and</strong> pump<br />
efficiency is 0.7. The power transmitted to the water is<br />
a) 12.6 kW b) 18.0 kW c) 14.0 kW d) 31.75 kW<br />
30 Small by-pass lines are installed in pumps some times to _____.<br />
a) increase flow b) control pump delivery head<br />
c) prevent pump running at zero flow d) reduce pump power consumption<br />
31 The refrigeration load in TR when 10 m 3 /hr of water is cooled from a 15 o C to 7 o C is about<br />
a) 10 b) 8 c) 26.5 d) none of the above<br />
32 The order of movement of thermal energy in HVAC system is:<br />
a) Indoor air - Chilled water - Refrigerant-Condenser water- Cooling tower<br />
b) Chilled water - Indoor air - Refrigerant-Cooling tower - Condenser water<br />
c) Indoor air - Condenser water - Chilled water - Cooling tower - Refrigerant<br />
d) Indoor air - Chilled water – Refrigerant - Cooling tower - Condenser water<br />
33 In a cooling tower,<br />
Statement A: Surface of heat exchange is the surface area of the water droplets, which is in<br />
_______________________<br />