16.01.2015 Views

hygrotest humidity transmitters

hygrotest humidity transmitters

hygrotest humidity transmitters

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

P - Probe with cable<br />

testo <strong>humidity</strong><br />

sensor + NTC<br />

Plastic probes<br />

(PHT -20/70) or<br />

stainless steel probes<br />

(PHT -20/120)<br />

Channel 1 + 2 (PHT)<br />

Cable, 250..2,000 mm<br />

Broad selection of displays (optional)<br />

Control menu via 3 internal buttons<br />

The <strong>hygrotest</strong> 600<br />

A professional instrument, the <strong>hygrotest</strong> 600 is applied in industrial<br />

processes and air conditioning systems, wherever long-term<br />

stability is required. The various versions allow for wall-mounting<br />

for measurement in rooms and similar areas, for duct-mounting<br />

for measurement in ducts and for location of the probe up to 2<br />

metres from the housing (connected by a<br />

cable). Instead of the relative <strong>humidity</strong>, the dew point temperature<br />

can be output.<br />

Technical data, <strong>hygrotest</strong> 600<br />

Housing:<br />

Material: ABS, colour grey (RAL 7035)<br />

Size:<br />

Screw connections:<br />

130 x 140 x 53 mm<br />

2 x M16 x 1.5 (ABS)<br />

Ambient temperature: -20...+70 °C<br />

Storage temperature: -40...+80 °C<br />

Protection type: IP 65<br />

Sensor:<br />

Humidity:<br />

Temperature:<br />

Measuring range:<br />

Testo <strong>humidity</strong> sensor<br />

NTC<br />

Humidity: 0...100 % RH *<br />

Temperature: Version Operating temperature range<br />

Accuracy:<br />

Humidity:<br />

Temperature:<br />

Analogue outputs:<br />

Humidity and temperature:<br />

Analogue output, <strong>humidity</strong>:<br />

Resolution:<br />

Drift:<br />

Analogue output, temperature:<br />

Resolution:<br />

Drift:<br />

Supply:<br />

Supply:<br />

Supply with display H1:<br />

Max. load:<br />

Max. load with display H1:<br />

Typical temperature<br />

coefficients of the outputs:<br />

Response time:<br />

EMC:<br />

600 WH -<br />

600 WHT -20/70 -20...+80 °C (scale set at +70°)<br />

600 DH -<br />

600 DHT -20/70 -20...+80 °C (scale set at +70°)<br />

600 DHT -20/120 -20...+120 °C<br />

600 PHT -20/70 -20...+80 °C (scale set at +70°)<br />

600 PHT -20/120 -20...+120 °C<br />

±2 % RH (within a range of 0...90 % RH), ±3 % RH (90...100 % RH)<br />

± 0.3 °C (-20...+50 °C), 1.5 % of value (> 50 °C)<br />

4...20 mA (2-wire system)<br />

0.02 mA<br />

0.001 mA/K<br />

0.02 mA<br />

0.003 mA/K<br />

24 V DC (10...30 V DC)<br />

minimum 20 VDC<br />

at 10 V 100 , at 18...30 V 500 <br />

at 20...30 V, 50 <br />

±0.002 mA/°C (referred to 25 °C)<br />

t90 approx. 10...20 sec.<br />

in accordance with directive 89/336 EEC<br />

All data relate to a nominal temperature of +25 °C.<br />

Probes: (diameter 12 mm)<br />

Version Material Overall length, Min./ Max. Sensor protection cap,<br />

incl.protection cap probe length standard<br />

600 WH PC 65 mm - ABS slotted<br />

600 WHT -20/70 PC 65 mm - ABS slotted<br />

600 DH PC 200 mm - sintered stainless steel cap<br />

600 DHT -20/70 PC 200 mm - sintered stainless steel cap<br />

600 DHT -20/120 Stainless steel 200 mm 100/800 mm sintered stainless steel cap<br />

600 PHT -20/70 PC 100 mm - sintered stainless steel cap<br />

600 PHT -20/120 Stainless steel 210 mm 150/800 mm sintered stainless steel cap<br />

* For continuous use in high <strong>humidity</strong> (RH > 90 %), select the Hygrotest<br />

650 PHT or 650 HP.<br />

Monitored warehousing of paper,<br />

textiles, granulates and<br />

pharmaceuticals.<br />

Channel 1 Channel 2<br />

Measured value % RH, °Ctd, °Ftd T<br />

Range 0 ... 100 % -20 ... +70/120 °C<br />

Output 4 ... 20 mA 4 ... 20 mA<br />

Freely scalable<br />

Freely scalable<br />

e.g. 20..100 % e.g. 10..40 °C<br />

7