Explosive Risk<br />

OLC 10<br />

OLC10 TWIN<br />

OLCT 10<br />

<strong>Detector</strong> / <strong>Transmitter</strong> <strong>for</strong> <strong>combustible</strong> <strong>gas</strong><br />

Especially studied <strong>for</strong><br />

applications in boiler rooms and<br />

carparks, the range of sensors<br />

OLC(T)10 is a model of quality-price<br />

ratio <strong>for</strong> the monitoring of <strong>gas</strong>es and<br />

<strong>combustible</strong> vapors in ambient air.<br />

Reduced size, simplicity of<br />

installation and use are the principal<br />

assets of these 4-20 mA detectortransmitters.<br />

Used with the MX15<br />

control unit, they guarantee a<br />

solution in con<strong>for</strong>mity with the<br />

French and European standards.<br />

Spécifications :<br />

- Catalytic Cells<br />

- Signal 4-20 mA on<br />

OLCT10<br />

- IP66<br />

- Reactivity<br />

- ATEX Approvals <strong>for</strong> use<br />

in explosive atmospheres<br />

OLC 10 / OLC 10 TWIN OLCT 10<br />

Detection principle :<br />

Catalytic cells<br />

Standard ranges : 0-100 % LEL Methane, Propane, Butane or Hydrogen<br />

Output signal : Wheastone Bridge 4-20mA , default < 0.5 mA or<br />

> 23.2mA<br />

Non ambiguity reading : From OLDHAM control unit fixed at 23.2 mA if value<br />

> 100% LEL<br />

Acknowledgement switching<br />

on / off the transmitter<br />

Possibility to disable non<br />

ambiguity reading by<br />

programming slot<br />

Settings : On OLDHAM control unit Direct by potentiometers Zero<br />

and Sensitivity:<br />

access to the pots by trap door<br />

on front plate<br />

2 mAoutput signal in<br />

maintenance mode<br />

4 points connector to get <strong>gas</strong><br />

measurement and tension<br />

image (shunt of 100 Ω)<br />

Power supply : By MX15 control unit OLCT10 : from 15 to 30 V DC<br />

1:I out (signal) 2 : 0V 3 : +24V DC<br />

Consumption : Depends on control unit 100 mA max<br />

Connections: 3 wires connector block,<br />

outdistances maximum 300m with<br />

1.5 mm²<br />

1 cable-gland M16 : diameter of<br />

cable 4 to 8 mm<br />

Oldham control unit :<br />

1 km with 3 x 1,5 mm²<br />

(32 Ω max in loop)<br />

OLC 10 TWIN : 1 connector block<br />

3 wires to control unit, 1<br />

connector block 4 wires to 2 nd<br />

detector, outdistances maximum<br />

300m with 1.5mm², 2 cable-glands<br />

M16, diameter of cable 4 to 8 mm.<br />

3 wires Connector block,<br />

1 cable gland M16, diameter<br />

of cable 4 to 8 mm<br />

Dimensions :<br />

width 118 mm, height 157 mm, depth 60 mm<br />

Made of :<br />

ABS<br />

Protection :<br />

IP66<br />

Estimated useful life :<br />

> 36 months<br />

Temperature range : -10 to + 45 °C<br />

Humidity range :<br />

0 % HR to 95 %HR<br />

Pressure range : 1 bar ± 20 %<br />

Temperature effect < 5 % LEL Methane or < 20 % of indicated value<br />

OLCT 10 ( -10 °C + 40 °C) :<br />

Long-term effect <strong>for</strong> Methane<br />

under normal conditions of<br />

Zero drift < 5 % LEL / year<br />

Sensitivity : < 10 % of reading / year<br />

use:<br />

Humidity effect: ± 5 % from relative humidity / (10 to 90 % RH) at 40°C<br />

Response time :<br />

T50


Dimensions :<br />

MX15 control unit<br />

Connection diagram between an OLC 10 or OLCT10 and MX15 control unit :<br />

1 2 3<br />

104<br />

1 2 3<br />

Connect the 3 wires according to<br />

classification<br />

Connection diagram of 2 OLC 10 TWIN from MX15 control unit :<br />

MX15 control unit<br />

1 2 3<br />

IN<br />

1 2 3<br />

1 2 3<br />

1 2 3 4<br />

1 2 3 4<br />

OUT<br />

IN<br />

France :<br />

NORD : 03 21 60 80 20<br />

PARIS-NORMANDIE : 01 30 12 08 50<br />

EST : 03 87 50 83 90<br />

OUEST : 02 99 22 70 22<br />

SUD-EST : 04 78 26 53 62<br />

MEDITERANNEE : 04 42 46 10 46<br />

SUD-OUEST : 05 63 21 16 00<br />

1 2 3 4<br />

OUT<br />

1 2 3 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!