Explosive Risk<br />
OLC 10<br />
OLC10 TWIN<br />
OLCT 10<br />
<strong>Detector</strong> / <strong>Transmitter</strong> <strong>for</strong> <strong>combustible</strong> <strong>gas</strong><br />
Especially studied <strong>for</strong><br />
applications in boiler rooms and<br />
carparks, the range of sensors<br />
OLC(T)10 is a model of quality-price<br />
ratio <strong>for</strong> the monitoring of <strong>gas</strong>es and<br />
<strong>combustible</strong> vapors in ambient air.<br />
Reduced size, simplicity of<br />
installation and use are the principal<br />
assets of these 4-20 mA detectortransmitters.<br />
Used with the MX15<br />
control unit, they guarantee a<br />
solution in con<strong>for</strong>mity with the<br />
French and European standards.<br />
Spécifications :<br />
- Catalytic Cells<br />
- Signal 4-20 mA on<br />
OLCT10<br />
- IP66<br />
- Reactivity<br />
- ATEX Approvals <strong>for</strong> use<br />
in explosive atmospheres<br />
OLC 10 / OLC 10 TWIN OLCT 10<br />
Detection principle :<br />
Catalytic cells<br />
Standard ranges : 0-100 % LEL Methane, Propane, Butane or Hydrogen<br />
Output signal : Wheastone Bridge 4-20mA , default < 0.5 mA or<br />
> 23.2mA<br />
Non ambiguity reading : From OLDHAM control unit fixed at 23.2 mA if value<br />
> 100% LEL<br />
Acknowledgement switching<br />
on / off the transmitter<br />
Possibility to disable non<br />
ambiguity reading by<br />
programming slot<br />
Settings : On OLDHAM control unit Direct by potentiometers Zero<br />
and Sensitivity:<br />
access to the pots by trap door<br />
on front plate<br />
2 mAoutput signal in<br />
maintenance mode<br />
4 points connector to get <strong>gas</strong><br />
measurement and tension<br />
image (shunt of 100 Ω)<br />
Power supply : By MX15 control unit OLCT10 : from 15 to 30 V DC<br />
1:I out (signal) 2 : 0V 3 : +24V DC<br />
Consumption : Depends on control unit 100 mA max<br />
Connections: 3 wires connector block,<br />
outdistances maximum 300m with<br />
1.5 mm²<br />
1 cable-gland M16 : diameter of<br />
cable 4 to 8 mm<br />
Oldham control unit :<br />
1 km with 3 x 1,5 mm²<br />
(32 Ω max in loop)<br />
OLC 10 TWIN : 1 connector block<br />
3 wires to control unit, 1<br />
connector block 4 wires to 2 nd<br />
detector, outdistances maximum<br />
300m with 1.5mm², 2 cable-glands<br />
M16, diameter of cable 4 to 8 mm.<br />
3 wires Connector block,<br />
1 cable gland M16, diameter<br />
of cable 4 to 8 mm<br />
Dimensions :<br />
width 118 mm, height 157 mm, depth 60 mm<br />
Made of :<br />
ABS<br />
Protection :<br />
IP66<br />
Estimated useful life :<br />
> 36 months<br />
Temperature range : -10 to + 45 °C<br />
Humidity range :<br />
0 % HR to 95 %HR<br />
Pressure range : 1 bar ± 20 %<br />
Temperature effect < 5 % LEL Methane or < 20 % of indicated value<br />
OLCT 10 ( -10 °C + 40 °C) :<br />
Long-term effect <strong>for</strong> Methane<br />
under normal conditions of<br />
Zero drift < 5 % LEL / year<br />
Sensitivity : < 10 % of reading / year<br />
use:<br />
Humidity effect: ± 5 % from relative humidity / (10 to 90 % RH) at 40°C<br />
Response time :<br />
T50
Dimensions :<br />
MX15 control unit<br />
Connection diagram between an OLC 10 or OLCT10 and MX15 control unit :<br />
1 2 3<br />
104<br />
1 2 3<br />
Connect the 3 wires according to<br />
classification<br />
Connection diagram of 2 OLC 10 TWIN from MX15 control unit :<br />
MX15 control unit<br />
1 2 3<br />
IN<br />
1 2 3<br />
1 2 3<br />
1 2 3 4<br />
1 2 3 4<br />
OUT<br />
IN<br />