Application guidelines<br />

Single phase electrical characteristics<br />

Electrical connections and wiring<br />

LRA - Locked Rotor<br />

Current (A)<br />

MCC - Maximum Continuous<br />

Current (A)<br />

Winding resistance (Ω)<br />

( ± 7 % at 68° F)<br />

Motor Code 1 5 1 5 1 5<br />

Winding run start run start<br />

MT/MTZ018 51 40 13 10 1.36 4.82 1.80 4.70<br />

MT/MTZ022 49.3 41 17 15 1.25 2.49 1.78 4.74<br />

MT/MTZ028 81 51 25 20 0.74 1.85 1.16 3.24<br />

MT/MTZ032 84 70 26.5 20 0.64 2.85 0.90 4.30<br />

MT/MTZ036 84 60 30 22 0.64 2.85 0.89 4.35<br />

MT/MTZ040 99 - 34 - 0.53 2.00 - -<br />

MT/MTZ044 97 - 31 - 0.45 1.90 - -<br />

MT/MTZ050 114 92 36 29 0.37 1.79 0.52 2.65<br />

MT/MTZ056 136 - 42.5 - 0.32 1.61 - -<br />

MT/MTZ064 143 - 46 - 0.32 2.10 - -<br />

Nominal capacitor values and relays<br />

* PSC: Permanent Split Capacitor<br />

CSR: Capacitor Start Run<br />

(1) Run capacitors: 440 volts<br />

(2) Start capacitors: 330 Volts<br />

50 Hz<br />

60 Hz<br />

Models<br />

PSC/CSR*<br />

CSR only<br />

Run capacitors (1) Start capacitors (2)<br />

(A) µF (C) µF (B) µF<br />

MT/MTZ018 JA-5 20 10 100<br />

MT/MTZ022 JC-5 20 10 100<br />

MT/MTZ028 JE-5 20 10 100<br />

MT/MTZ032 JF-5 25 10 135<br />

MT/MTZ036 JG-5 25 10 135<br />

MT/MTZ050 HK-5 30 15 135<br />

MT/MTZ018 JA-1 15 10 100<br />

MT/MTZ022 JC-1 30 15 100<br />

MT/MTZ028 JE-1 25 25 135<br />

MT/MTZ032 JF-1 25 20 100<br />

MT/MTZ036 JG-1 25 20 100<br />

MT/MTZ040 JH-1 35 20 100<br />

MT/MTZ044 HJ-1 30 15 135<br />

MT/MTZ050 HK-1 30 15 135<br />

MT/MTZ056 HL-1 35 20 200<br />

MT/MTZ064 HM-1 30 25 235<br />

Start relay<br />

3ARR3J4A4<br />

/RVA6AMKL<br />

3ARR3J4A4<br />

/RVA6AMKL<br />

Trickle circuit<br />

PSC wiring<br />

CSR wiring<br />

The trickle circuit provides the facility of<br />

heating the compressor crankcase by feeding<br />

a small current to the auxiliary winding<br />

and the run capacitor (See the drawings<br />

page 14.)<br />

By using PSC or CSR starting systems, compressor<br />

models MT / MTZ 018 - 022 can be<br />

PSC wiring may be used for refrigerant circuits<br />

with capillary tubes or expansion valves<br />

with bleed ports. Pressure equalization must<br />

CSR wiring provides additional motor torque<br />

at start-up, by the use of a start capacitor in<br />

combination with the run capacitor. This system<br />

can be used for refrigerant circuits with<br />

capillary tubes or expansion valves. The start<br />

capacitor is only connected during the starting<br />

operation, a potential relay is used to disconnect<br />

it after the start sequence.<br />

The single phase compressor motors are internally<br />

protected by a temperature/current<br />

operated without crankcase heaters as the<br />

heater function is provided by the trickle circuit.<br />

For the larger single phase compressor models<br />

MT / MTZ 028 - 064, the use of the PTC<br />

crankcase heater is recommended.<br />

be ensured before start-up because of the<br />

low starting torque characteristics of this<br />

system.<br />

sensing bimetallic protector, which senses<br />

the main and start winding currents, and also<br />

the winding temperature. Once the protector<br />

has tripped, it may take up to two to four<br />

hours to reset and restart the compressor.<br />

Check that power supply corresponds<br />

to compressor characteristics (refer to<br />

compressor nameplate).<br />

USCO.PC.004.A4.22 13