Application guidelines<br />
Single phase electrical characteristics<br />
Electrical connections and wiring<br />
LRA - Locked Rotor<br />
Current (A)<br />
MCC - Maximum Continuous<br />
Current (A)<br />
Winding resistance (Ω)<br />
( ± 7 % at 68° F)<br />
Motor Code 1 5 1 5 1 5<br />
Winding run start run start<br />
MT/MTZ018 51 40 13 10 1.36 4.82 1.80 4.70<br />
MT/MTZ022 49.3 41 17 15 1.25 2.49 1.78 4.74<br />
MT/MTZ028 81 51 25 20 0.74 1.85 1.16 3.24<br />
MT/MTZ032 84 70 26.5 20 0.64 2.85 0.90 4.30<br />
MT/MTZ036 84 60 30 22 0.64 2.85 0.89 4.35<br />
MT/MTZ040 99 - 34 - 0.53 2.00 - -<br />
MT/MTZ044 97 - 31 - 0.45 1.90 - -<br />
MT/MTZ050 114 92 36 29 0.37 1.79 0.52 2.65<br />
MT/MTZ056 136 - 42.5 - 0.32 1.61 - -<br />
MT/MTZ064 143 - 46 - 0.32 2.10 - -<br />
Nominal capacitor values and relays<br />
* PSC: Permanent Split Capacitor<br />
CSR: Capacitor Start Run<br />
(1) Run capacitors: 440 volts<br />
(2) Start capacitors: 330 Volts<br />
50 Hz<br />
60 Hz<br />
Models<br />
PSC/CSR*<br />
CSR only<br />
Run capacitors (1) Start capacitors (2)<br />
(A) µF (C) µF (B) µF<br />
MT/MTZ018 JA-5 20 10 100<br />
MT/MTZ022 JC-5 20 10 100<br />
MT/MTZ028 JE-5 20 10 100<br />
MT/MTZ032 JF-5 25 10 135<br />
MT/MTZ036 JG-5 25 10 135<br />
MT/MTZ050 HK-5 30 15 135<br />
MT/MTZ018 JA-1 15 10 100<br />
MT/MTZ022 JC-1 30 15 100<br />
MT/MTZ028 JE-1 25 25 135<br />
MT/MTZ032 JF-1 25 20 100<br />
MT/MTZ036 JG-1 25 20 100<br />
MT/MTZ040 JH-1 35 20 100<br />
MT/MTZ044 HJ-1 30 15 135<br />
MT/MTZ050 HK-1 30 15 135<br />
MT/MTZ056 HL-1 35 20 200<br />
MT/MTZ064 HM-1 30 25 235<br />
Start relay<br />
3ARR3J4A4<br />
/RVA6AMKL<br />
3ARR3J4A4<br />
/RVA6AMKL<br />
Trickle circuit<br />
PSC wiring<br />
CSR wiring<br />
The trickle circuit provides the facility of<br />
heating the compressor crankcase by feeding<br />
a small current to the auxiliary winding<br />
and the run capacitor (See the drawings<br />
page 14.)<br />
By using PSC or CSR starting systems, compressor<br />
models MT / MTZ 018 - 022 can be<br />
PSC wiring may be used for refrigerant circuits<br />
with capillary tubes or expansion valves<br />
with bleed ports. Pressure equalization must<br />
CSR wiring provides additional motor torque<br />
at start-up, by the use of a start capacitor in<br />
combination with the run capacitor. This system<br />
can be used for refrigerant circuits with<br />
capillary tubes or expansion valves. The start<br />
capacitor is only connected during the starting<br />
operation, a potential relay is used to disconnect<br />
it after the start sequence.<br />
The single phase compressor motors are internally<br />
protected by a temperature/current<br />
operated without crankcase heaters as the<br />
heater function is provided by the trickle circuit.<br />
For the larger single phase compressor models<br />
MT / MTZ 028 - 064, the use of the PTC<br />
crankcase heater is recommended.<br />
be ensured before start-up because of the<br />
low starting torque characteristics of this<br />
system.<br />
sensing bimetallic protector, which senses<br />
the main and start winding currents, and also<br />
the winding temperature. Once the protector<br />
has tripped, it may take up to two to four<br />
hours to reset and restart the compressor.<br />
Check that power supply corresponds<br />
to compressor characteristics (refer to<br />
compressor nameplate).<br />
USCO.PC.004.A4.22 13