BACKFLOW PROTECTION DEVICES<br />

10<br />

Installation<br />

The BA 909 backflow protector must be<br />

installed so that it is easily accessible<br />

for maintenance and in order to verify<br />

that it is operating properly.<br />

It must be installed horizontally with a<br />

strainer on the inflow side of the BA<br />

909, in such a way as to protect the<br />

valves against unnecessary<br />

contamination. Moreover, a shut-off<br />

valve must be installed both upstream<br />

and downstream of the device in the<br />

water line. The overflow opening can<br />

be connected to the drain via an airgap<br />

tundish set.<br />

If installed without a drain, the device<br />

must be installed at a height of a<br />

minimum of 2 x DN ≥ 20 mm above the<br />

sink hole. This may only be installed<br />

after the pipe system has been cleaned<br />

in the normal method.<br />

Installation example<br />

Installing two <strong>devices</strong> in<br />

parallel makes it possible to<br />

perform maintenance<br />

properly without disrupting<br />

the water delivery.