BACKFLOW PROTECTION DEVICES<br />
10<br />
Installation<br />
The BA 909 backflow protector must be<br />
installed so that it is easily accessible<br />
for maintenance and in order to verify<br />
that it is operating properly.<br />
It must be installed horizontally with a<br />
strainer on the inflow side of the BA<br />
909, in such a way as to protect the<br />
valves against unnecessary<br />
contamination. Moreover, a shut-off<br />
valve must be installed both upstream<br />
and downstream of the device in the<br />
water line. The overflow opening can<br />
be connected to the drain via an airgap<br />
tundish set.<br />
If installed without a drain, the device<br />
must be installed at a height of a<br />
minimum of 2 x DN ≥ 20 mm above the<br />
sink hole. This may only be installed<br />
after the pipe system has been cleaned<br />
in the normal method.<br />
Installation example<br />
Installing two <strong>devices</strong> in<br />
parallel makes it possible to<br />
perform maintenance<br />
properly without disrupting<br />
the water delivery.