General<br />

Specifications<br />

LPC2800<br />

UOI Integration Package for<br />

Power Generation Applications<br />

<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong><br />

• GENERAL<br />

This <strong>GS</strong> (General Specifications) describes the specifications of the UOI Integration Package, which provides an<br />

integrated operation between General Electric Company SPEEDTRONIC Mark VI / Mark V Turbine Control System<br />

and YOKOGAWA CENTUM CS 3000 System (hereafter referred to as CS 3000) - a control system for HRSG (Heat<br />

Recovery Steam Generator) and BOP (Balance of Plant) auxiliaries - using GE Fanuc CIMPLICITY HMI System<br />

as an operator interface used in the common platform for control applications at combined cycle power generation<br />

plants. The common platform concept, called Unified Operator Interface (UOI), provides uniformity of operation<br />

across the HRSG/BOP and Turbine Controls. This is achieved through direct access to Turbine Displays and Data/<br />

Messages through the unique UOI concept.<br />

• STANDARD SPECIFICATIONS<br />

• Feature<br />

The UOI system employs a Server/Client (Viewer) architecture, which is the core technology of the UOI system, and<br />

provides functions such as data access, alarm and message management and Tag/Object conversion by using GE<br />

Fanuc CIMPLICITY HMI System. General Electric Company PEECC Server/Client (Viewer) also employs the same<br />

CIMPLICITY HMI system and UOI Viewers can access both UOI Server and PEECC Server as a common HMI platform.<br />

By installing CS 3000 Control Bus Interface Card and UOI Integration Package in the UOI Server, it can access to<br />

CS 3000 FCS as a primary HMI interface of HRSG/BOP operation. It also supports a dual redundant configuration to<br />

provide a highly reliable system.<br />

Since the UOI Server is configured independently from the PEECC Server, the operation can be integrated on the UOI<br />

Viewers via Plant Data Highway without affecting the Turbine Control system.<br />

Unified Operator Interface (UOI)<br />

UOI<br />

UOI<br />

Configuration PC<br />

Unit Data Highway for Mark VI<br />

Stage Link for Mark V<br />

SPEEDTRONIC<br />

Mark VI or V<br />

(for Gas Turbines)<br />

UOI Viewer(s) (GE Fanuc CIMPLICITY HMI Viewer)<br />

Data/Message from Data/Message from<br />

Turbine Project UOI BOP/HRSG Project UOI UOI<br />

PEECC (*1)<br />

Server(s)<br />

(CIMPLICITY HMI<br />

Server)<br />

CS 3000<br />

UOI Integration<br />

Package<br />

SPEEDTRONIC<br />

Mark VI or V<br />

(for Steam Turbine)<br />

UOI Server(s)<br />

(CIMPLICITY HMI<br />

Server)<br />

Control Bus<br />

(Vnet, Vnet/IP)<br />

CENTUM CS 3000<br />

FCS(s)<br />

(for HRSG/BOP)<br />

Plant Data Highway<br />

(Ethernet)<br />

CENTUM CS 3000/<br />

ProSafe-RS<br />

Builder PC<br />

ProSafe-RS SCS(s)<br />

(for Protection)<br />

Turbine Controls by General Electric Company<br />

HRSG/BOP Controls by YOKOGAWA<br />

*1: PEECC; Packaged Electrical and Electronic Control Compartment<br />

Figure: UOI’s Basic System Configuration<br />

F01E.ai<br />

Yokogawa Electric Corporation<br />

2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan<br />

Tel.: 81-422-52-5637 Fax.: 81-422-52-4499<br />

<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong><br />

©Copyright Jul. 1, 2001<br />

8th Edition Sep. 1, 2007


• CS 3000 FCS<br />

Field Control Stations (FCS) are connected to the UOI<br />

Server PCs and the CS 3000 Builder PC. CS 3000<br />

FCS(s) provide control functions for HRSG/BOP operation.<br />

• UOI Viewer PC Functions<br />

UOI Viewer PCs are connected to the UOI Server<br />

PC(s) via Plant Data Highway (Ethernet) and provides<br />

operation and monitoring functions for CS 3000’s FCS<br />

and SPEEDTRONIC Mark VI / Mark V.<br />

CIMPLICITY HMI System is configured of UOI Viewers<br />

(Client) as its platform.<br />

UOI Viewer also provides the following functions and<br />

components and can create the monitoring and operation<br />

functions, such as Graphics, Trend Chart, Alarm<br />

Viewer, Faceplate, Data Entry Dialog Box, by utilizing<br />

the following functions.<br />

- HMI client connection and login function<br />

- CIMPLICITY data server client-side function<br />

- Graphic viewer function<br />

- Interactive ActiveX alarm viewing object<br />

- Interactive ActiveX object for viewing trend data<br />

- ActiveX object for plotting multiple X-Y data<br />

- Visual Basic for applications scripting language<br />

See GE Fanuc CIMPLICITY HMI’s manual for details.<br />

• UOI Server PC Functions<br />

UOI Server PC(s) are connected to the CS 3000<br />

FCS(s) via Control Bus for device communication and<br />

provides the following data access services:<br />

- HMI client connection management<br />

- Data access security functions<br />

- Data routing and change management<br />

- Alarm/event notification and routing<br />

- Alarm state management (Acknowledgment/Reset/<br />

Deletion)<br />

- Trend data buffering<br />

In addition to the above, the following functions are<br />

provided as the UOI system for CS 3000 FCS’ data<br />

integration.<br />

- FCS tag data to CIMPLICITY point data mapping<br />

- FCS process data communications<br />

- FCS message management<br />

- FCS alarm/event to CIMPLICITY alarm/event mapping<br />

CIMPLICTY HMI System is also configured of UOI<br />

Server(s) as its platform.<br />

See GE Fanuc CIMPLICTY HMI’s manual for details.<br />

• Integrated Data and Messages<br />

UOI System provides a Server/Client architecture using<br />

GE Fanuc CIMPLICITY HMI System:<br />

The data and messages from the SPEEDTRONIC<br />

Mark VI / Mark V and CS 3000 FCS can be displayed<br />

on UOI Viewers. Various operations, such as displaying<br />

data on graphic screen, displaying messages on<br />

alarm window, assigning data on trend chart, can be<br />

integrated on the UOI Viewers.<br />

• CS 3000 FCS Builder Functions<br />

The CS 3000 FCS Builder functions provide configuration<br />

and maintenance of FCS using the CS 3000<br />

Standard Builder Function software package installed<br />

in the CS 3000 Builder PC.<br />

For the tuning of control functions, it requires CS 3000<br />

Operation & Monitoring Standard Function software<br />

package in the CS 3000 Builder PC.<br />

The configuration procedure and control functions are<br />

the same as CS 3000 specified under the Software<br />

Requirements in this <strong>GS</strong>.<br />

• Station Configuration on CS 3000<br />

In the station configuration on CS 3000, the UOI Server<br />

PC is assigned as a UHMIS station and the CS 3000<br />

Builder PC is assigned as an HIS station.<br />

2<br />

• Tag/Object Conversion Function<br />

This function is one of the utilities included in this package.<br />

It converts the Tag List generated by CS 3000<br />

Builder to the configuration used for CIMPLICITY Objects<br />

(Tag Common Attributes) and CIMPLICITY Points<br />

(Data Item Attributes). This tool runs on the UOI Server<br />

PC. When the Tag List is changed in the CS 3000<br />

Builder PC, it must be equalized to the UOI Server’s<br />

Project Database using this conversion tool.<br />

• ProSafe-RS Integration<br />

UOI system is capable to monitor data on ProSafe-<br />

RS system. It handles data on Safety Control Station<br />

(SCS) as equivalent as data on FCS throughout CS<br />

3000 integration capability with ProSafe-RS system.<br />

UOI Tag/Object Conversion Function generates CIM-<br />

PLICITY Objects and Points from SCS Tag List.<br />

• SYSTEM SPECIFICATIONS<br />

The application capacity and the number of configuring<br />

systems for CS 3000, including CIMPLICITY HMI, are<br />

as follows.<br />

• Application Capacity<br />

Number of CS 3000 Tags maintained in CIMPLICITY<br />

HMI Database: Max. 10,000 tags/UOI<br />

server<br />

CS 3000 FCS: Same as CS 3000 FCS’ standard<br />

specifications<br />

• Maximum System Size<br />

Number of UOI Viewers: Max. 8/UOI server<br />

Number of CS 3000 Builder PC : Max.1/UOI system<br />

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation<br />

<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong> Sep. 1, 2007-00


• OPERATING ENVIRONMENT<br />

• Hardware Requirements<br />

UOI Server PC<br />

PC type: IBM PC/AT compatible<br />

CPU: Pentium III 600 MHz or faster<br />

Main memory: 512 MB or larger<br />

Hard disk: 4 GB or bigger (with at least 2.3 GB of<br />

free capacity)<br />

Serial port: One or more RS-232C ports<br />

Parallel port: One or more ports<br />

Network interface:<br />

One Ethernet Card for UOI Viewer PC<br />

One VI701 Control Bus Interface Card for<br />

CS 3000 Vnet/IP System or<br />

One VF701 Control Bus Interface Card for<br />

CS 3000 Vnet System<br />

UOI Viewer PC<br />

PC type: IBM PC/AT compatible<br />

CPU: Pentium II 300 MHz or faster<br />

Main memory: 256 MB or larger<br />

Hard disk: 2 GB or bigger (with at least 600 MB of<br />

free capacity)<br />

Serial port: One or more RS-232C ports<br />

Parallel port: One or more ports<br />

Network interface: One Ethernet Card for UOI Server<br />

PC<br />

CS 3000 Builder PC<br />

PC type: IBM PC/AT compatible<br />

CPU:<br />

Pentium 300 MHz or faster for Windows 2000<br />

Pentium 800 MHz or faster for Windows XP<br />

Main memory: 96 MB or larger (To use optional<br />

software packages, engineering functions<br />

or general-purpose software, add more<br />

memory)<br />

256 MB or larger for Windows XP<br />

Hard disk: 4 GB or bigger (with at least 500 MB of<br />

free capacity)<br />

CRT display: 1024 x 768 or more, 256 colors (Video<br />

memory: 2MB or more, CRT: multi-scan<br />

17-inch or larger recommended)<br />

Serial port: One or more RS-232C ports<br />

Parallel port: One or more ports<br />

Network interface:<br />

One Ethernet Card for UOI Server PC<br />

One VI701 Control Bus Interface Card for<br />

CS 3000 Vnet/IP System or<br />

One VF701 Control Bus Interface Card for<br />

CS 3000 Vnet System<br />

• Software Requirements<br />

3<br />

UOI Server PC<br />

OS:<br />

Windows 2000 Server Service Pack 4<br />

Windows Server 2003 Service Pack 1<br />

Other Software: GE Fanuc CIMPLICITY HMI Plant<br />

Edition / Server Development System<br />

(Ver.6.1 / Service Pack 5)<br />

Option Software: GE Fanuc CIMPLICITY HMI Plant<br />

Edition / Runtime System<br />

(Ver.6.1 / Service Pack 5)<br />

UOI Viewer PC<br />

OS:<br />

Windows 2000 (Professional or Server)<br />

Service Pack 4<br />

Windows XP Professional<br />

Service Pack 2<br />

Windows Server 2003 Service Pack 1<br />

Other Software: GE Fanuc CIMPLICITY HMI Plant<br />

Edition / Viewer Development System<br />

(Ver.6.1 / Service Pack 5)<br />

Option Software: GE Fanuc CIMPLICITY HMI Plant<br />

Edition / Viewer Runtime System<br />

(Ver.6.1 / Service Pack 5)<br />

CS 3000 Builder PC and Option Software<br />

OS:<br />

Windows 2000 (Professional or Server)<br />

Service Pack 4<br />

Windows XP Professional<br />

Service Pack 2<br />

Windows Server 2003 Service Pack 1<br />

Other Software:<br />

LHS5100 Standard Builder Function<br />

LHS1100 Standard Operation and Monitoring<br />

Function<br />

Option Software:<br />

LHS1150 Server for Remote Operation and Monitoring<br />

Function<br />

LHS4410 Control Drawing Status Display Package<br />

LHS4420 Logic Chart Status Display Package (*1)<br />

LHS5420 Test Function<br />

LHS5425 Expanded Test Functions (*2)<br />

LHS5490 Self-Documentation Package<br />

LHS5495 Electronic Instruction Manual<br />

LPC6910 SOE Server Configurator Package (*3)<br />

LPC6920 SOE Viewer Package (*3)<br />

*1: Supported by R2.05 or later.<br />

*2: Supported by R2.10 or later.<br />

*3: Supported by R3.03 or later.<br />

The packages, which are not listed, please contact<br />

YOKOGAWA’s sales office.<br />

See each software’s <strong>GS</strong> of CS 3000 for details.<br />

Note: All the General Electric Company’s products<br />

configuring the UOI system belong to General<br />

Electric Company.<br />

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation <strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong> Sep. 1, 2007-00


• MODEL AND SUFFIX CODES<br />

Model<br />

Suffix<br />

Codes<br />

Description<br />

UOI Integration Package for Power<br />

LPC2800 Generation Applications (R2.05)<br />

[Media model: LPCSM80-C11]<br />

-S Basic software license<br />

1 Always 1<br />

1 English-language version<br />

*1: This package contains an instruction manual in<br />

PDF to be read using Acrobat Reader.<br />

• ORDERING INFORMATION<br />

Specify model and suffix codes.<br />

*1: This package runs when CENTUM CS 3000<br />

R3.08.10 or later is used for CS 3000 Builder PC.<br />

*2: To purchase GE Fanuc CIMPLICITY HMI Plant<br />

Edition Server / Viewer Ver. 6.1 software, please<br />

contact GE Fanuc sales office.<br />

*3: Please order the CENTUM CS 3000 system ID license<br />

(Model: LHSDM01-S11) from YOKOGAWA<br />

together with LPC2800.<br />

One CENTUM CS 3000 system ID license is required<br />

for each LPC2800 license for the key code<br />

generation.<br />

4<br />

• TRADEMARKS<br />

- CENTUM is a registered trademark of Yokogawa<br />

Electric Corporation.<br />

- CIMPLICITY and CIMPLICITY HMI Plant Edition are<br />

a registered trademark of GE Fanuc Automation<br />

North America, Inc.<br />

- SPEEDTRONIC is a registered trademark of General<br />

Electric Company, USA.<br />

- ARCNET is a registered trademark of Datapoint Corporation.<br />

- Ethernet is a registered trademark of Xerox Corporation.<br />

- Windows and ActiveX are registered trademarks of<br />

Microsoft Corporation.<br />

- Pentium is a registered trademark of Intel Corporation.<br />

- PC, IBM PC/AT and IBM are registered trademarks of<br />

International Business Machines Corporation.<br />

- FOUNDATION is a trademark of Fieldbus Foundation.<br />

- Acrobat is registered trademarks of Adobe Systems<br />

Incorporated and registered within particular jurisdictions.<br />

- Other product and company names appearing in this<br />

document are trademarks or registered trademarks of<br />

their respective holders.<br />

All specifications are subject to change without written<br />

notice.<br />

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation<br />

Subject to change without notice.<br />