GS 33Q05L01-31E
GS 33Q05L01-31E
GS 33Q05L01-31E
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
General<br />
Specifications<br />
LPC2800<br />
UOI Integration Package for<br />
Power Generation Applications<br />
<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong><br />
• GENERAL<br />
This <strong>GS</strong> (General Specifications) describes the specifications of the UOI Integration Package, which provides an<br />
integrated operation between General Electric Company SPEEDTRONIC Mark VI / Mark V Turbine Control System<br />
and YOKOGAWA CENTUM CS 3000 System (hereafter referred to as CS 3000) - a control system for HRSG (Heat<br />
Recovery Steam Generator) and BOP (Balance of Plant) auxiliaries - using GE Fanuc CIMPLICITY HMI System<br />
as an operator interface used in the common platform for control applications at combined cycle power generation<br />
plants. The common platform concept, called Unified Operator Interface (UOI), provides uniformity of operation<br />
across the HRSG/BOP and Turbine Controls. This is achieved through direct access to Turbine Displays and Data/<br />
Messages through the unique UOI concept.<br />
• STANDARD SPECIFICATIONS<br />
• Feature<br />
The UOI system employs a Server/Client (Viewer) architecture, which is the core technology of the UOI system, and<br />
provides functions such as data access, alarm and message management and Tag/Object conversion by using GE<br />
Fanuc CIMPLICITY HMI System. General Electric Company PEECC Server/Client (Viewer) also employs the same<br />
CIMPLICITY HMI system and UOI Viewers can access both UOI Server and PEECC Server as a common HMI platform.<br />
By installing CS 3000 Control Bus Interface Card and UOI Integration Package in the UOI Server, it can access to<br />
CS 3000 FCS as a primary HMI interface of HRSG/BOP operation. It also supports a dual redundant configuration to<br />
provide a highly reliable system.<br />
Since the UOI Server is configured independently from the PEECC Server, the operation can be integrated on the UOI<br />
Viewers via Plant Data Highway without affecting the Turbine Control system.<br />
Unified Operator Interface (UOI)<br />
UOI<br />
UOI<br />
Configuration PC<br />
Unit Data Highway for Mark VI<br />
Stage Link for Mark V<br />
SPEEDTRONIC<br />
Mark VI or V<br />
(for Gas Turbines)<br />
UOI Viewer(s) (GE Fanuc CIMPLICITY HMI Viewer)<br />
Data/Message from Data/Message from<br />
Turbine Project UOI BOP/HRSG Project UOI UOI<br />
PEECC (*1)<br />
Server(s)<br />
(CIMPLICITY HMI<br />
Server)<br />
CS 3000<br />
UOI Integration<br />
Package<br />
SPEEDTRONIC<br />
Mark VI or V<br />
(for Steam Turbine)<br />
UOI Server(s)<br />
(CIMPLICITY HMI<br />
Server)<br />
Control Bus<br />
(Vnet, Vnet/IP)<br />
CENTUM CS 3000<br />
FCS(s)<br />
(for HRSG/BOP)<br />
Plant Data Highway<br />
(Ethernet)<br />
CENTUM CS 3000/<br />
ProSafe-RS<br />
Builder PC<br />
ProSafe-RS SCS(s)<br />
(for Protection)<br />
Turbine Controls by General Electric Company<br />
HRSG/BOP Controls by YOKOGAWA<br />
*1: PEECC; Packaged Electrical and Electronic Control Compartment<br />
Figure: UOI’s Basic System Configuration<br />
F01E.ai<br />
Yokogawa Electric Corporation<br />
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan<br />
Tel.: 81-422-52-5637 Fax.: 81-422-52-4499<br />
<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong><br />
©Copyright Jul. 1, 2001<br />
8th Edition Sep. 1, 2007
• CS 3000 FCS<br />
Field Control Stations (FCS) are connected to the UOI<br />
Server PCs and the CS 3000 Builder PC. CS 3000<br />
FCS(s) provide control functions for HRSG/BOP operation.<br />
• UOI Viewer PC Functions<br />
UOI Viewer PCs are connected to the UOI Server<br />
PC(s) via Plant Data Highway (Ethernet) and provides<br />
operation and monitoring functions for CS 3000’s FCS<br />
and SPEEDTRONIC Mark VI / Mark V.<br />
CIMPLICITY HMI System is configured of UOI Viewers<br />
(Client) as its platform.<br />
UOI Viewer also provides the following functions and<br />
components and can create the monitoring and operation<br />
functions, such as Graphics, Trend Chart, Alarm<br />
Viewer, Faceplate, Data Entry Dialog Box, by utilizing<br />
the following functions.<br />
- HMI client connection and login function<br />
- CIMPLICITY data server client-side function<br />
- Graphic viewer function<br />
- Interactive ActiveX alarm viewing object<br />
- Interactive ActiveX object for viewing trend data<br />
- ActiveX object for plotting multiple X-Y data<br />
- Visual Basic for applications scripting language<br />
See GE Fanuc CIMPLICITY HMI’s manual for details.<br />
• UOI Server PC Functions<br />
UOI Server PC(s) are connected to the CS 3000<br />
FCS(s) via Control Bus for device communication and<br />
provides the following data access services:<br />
- HMI client connection management<br />
- Data access security functions<br />
- Data routing and change management<br />
- Alarm/event notification and routing<br />
- Alarm state management (Acknowledgment/Reset/<br />
Deletion)<br />
- Trend data buffering<br />
In addition to the above, the following functions are<br />
provided as the UOI system for CS 3000 FCS’ data<br />
integration.<br />
- FCS tag data to CIMPLICITY point data mapping<br />
- FCS process data communications<br />
- FCS message management<br />
- FCS alarm/event to CIMPLICITY alarm/event mapping<br />
CIMPLICTY HMI System is also configured of UOI<br />
Server(s) as its platform.<br />
See GE Fanuc CIMPLICTY HMI’s manual for details.<br />
• Integrated Data and Messages<br />
UOI System provides a Server/Client architecture using<br />
GE Fanuc CIMPLICITY HMI System:<br />
The data and messages from the SPEEDTRONIC<br />
Mark VI / Mark V and CS 3000 FCS can be displayed<br />
on UOI Viewers. Various operations, such as displaying<br />
data on graphic screen, displaying messages on<br />
alarm window, assigning data on trend chart, can be<br />
integrated on the UOI Viewers.<br />
• CS 3000 FCS Builder Functions<br />
The CS 3000 FCS Builder functions provide configuration<br />
and maintenance of FCS using the CS 3000<br />
Standard Builder Function software package installed<br />
in the CS 3000 Builder PC.<br />
For the tuning of control functions, it requires CS 3000<br />
Operation & Monitoring Standard Function software<br />
package in the CS 3000 Builder PC.<br />
The configuration procedure and control functions are<br />
the same as CS 3000 specified under the Software<br />
Requirements in this <strong>GS</strong>.<br />
• Station Configuration on CS 3000<br />
In the station configuration on CS 3000, the UOI Server<br />
PC is assigned as a UHMIS station and the CS 3000<br />
Builder PC is assigned as an HIS station.<br />
2<br />
• Tag/Object Conversion Function<br />
This function is one of the utilities included in this package.<br />
It converts the Tag List generated by CS 3000<br />
Builder to the configuration used for CIMPLICITY Objects<br />
(Tag Common Attributes) and CIMPLICITY Points<br />
(Data Item Attributes). This tool runs on the UOI Server<br />
PC. When the Tag List is changed in the CS 3000<br />
Builder PC, it must be equalized to the UOI Server’s<br />
Project Database using this conversion tool.<br />
• ProSafe-RS Integration<br />
UOI system is capable to monitor data on ProSafe-<br />
RS system. It handles data on Safety Control Station<br />
(SCS) as equivalent as data on FCS throughout CS<br />
3000 integration capability with ProSafe-RS system.<br />
UOI Tag/Object Conversion Function generates CIM-<br />
PLICITY Objects and Points from SCS Tag List.<br />
• SYSTEM SPECIFICATIONS<br />
The application capacity and the number of configuring<br />
systems for CS 3000, including CIMPLICITY HMI, are<br />
as follows.<br />
• Application Capacity<br />
Number of CS 3000 Tags maintained in CIMPLICITY<br />
HMI Database: Max. 10,000 tags/UOI<br />
server<br />
CS 3000 FCS: Same as CS 3000 FCS’ standard<br />
specifications<br />
• Maximum System Size<br />
Number of UOI Viewers: Max. 8/UOI server<br />
Number of CS 3000 Builder PC : Max.1/UOI system<br />
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation<br />
<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong> Sep. 1, 2007-00
• OPERATING ENVIRONMENT<br />
• Hardware Requirements<br />
UOI Server PC<br />
PC type: IBM PC/AT compatible<br />
CPU: Pentium III 600 MHz or faster<br />
Main memory: 512 MB or larger<br />
Hard disk: 4 GB or bigger (with at least 2.3 GB of<br />
free capacity)<br />
Serial port: One or more RS-232C ports<br />
Parallel port: One or more ports<br />
Network interface:<br />
One Ethernet Card for UOI Viewer PC<br />
One VI701 Control Bus Interface Card for<br />
CS 3000 Vnet/IP System or<br />
One VF701 Control Bus Interface Card for<br />
CS 3000 Vnet System<br />
UOI Viewer PC<br />
PC type: IBM PC/AT compatible<br />
CPU: Pentium II 300 MHz or faster<br />
Main memory: 256 MB or larger<br />
Hard disk: 2 GB or bigger (with at least 600 MB of<br />
free capacity)<br />
Serial port: One or more RS-232C ports<br />
Parallel port: One or more ports<br />
Network interface: One Ethernet Card for UOI Server<br />
PC<br />
CS 3000 Builder PC<br />
PC type: IBM PC/AT compatible<br />
CPU:<br />
Pentium 300 MHz or faster for Windows 2000<br />
Pentium 800 MHz or faster for Windows XP<br />
Main memory: 96 MB or larger (To use optional<br />
software packages, engineering functions<br />
or general-purpose software, add more<br />
memory)<br />
256 MB or larger for Windows XP<br />
Hard disk: 4 GB or bigger (with at least 500 MB of<br />
free capacity)<br />
CRT display: 1024 x 768 or more, 256 colors (Video<br />
memory: 2MB or more, CRT: multi-scan<br />
17-inch or larger recommended)<br />
Serial port: One or more RS-232C ports<br />
Parallel port: One or more ports<br />
Network interface:<br />
One Ethernet Card for UOI Server PC<br />
One VI701 Control Bus Interface Card for<br />
CS 3000 Vnet/IP System or<br />
One VF701 Control Bus Interface Card for<br />
CS 3000 Vnet System<br />
• Software Requirements<br />
3<br />
UOI Server PC<br />
OS:<br />
Windows 2000 Server Service Pack 4<br />
Windows Server 2003 Service Pack 1<br />
Other Software: GE Fanuc CIMPLICITY HMI Plant<br />
Edition / Server Development System<br />
(Ver.6.1 / Service Pack 5)<br />
Option Software: GE Fanuc CIMPLICITY HMI Plant<br />
Edition / Runtime System<br />
(Ver.6.1 / Service Pack 5)<br />
UOI Viewer PC<br />
OS:<br />
Windows 2000 (Professional or Server)<br />
Service Pack 4<br />
Windows XP Professional<br />
Service Pack 2<br />
Windows Server 2003 Service Pack 1<br />
Other Software: GE Fanuc CIMPLICITY HMI Plant<br />
Edition / Viewer Development System<br />
(Ver.6.1 / Service Pack 5)<br />
Option Software: GE Fanuc CIMPLICITY HMI Plant<br />
Edition / Viewer Runtime System<br />
(Ver.6.1 / Service Pack 5)<br />
CS 3000 Builder PC and Option Software<br />
OS:<br />
Windows 2000 (Professional or Server)<br />
Service Pack 4<br />
Windows XP Professional<br />
Service Pack 2<br />
Windows Server 2003 Service Pack 1<br />
Other Software:<br />
LHS5100 Standard Builder Function<br />
LHS1100 Standard Operation and Monitoring<br />
Function<br />
Option Software:<br />
LHS1150 Server for Remote Operation and Monitoring<br />
Function<br />
LHS4410 Control Drawing Status Display Package<br />
LHS4420 Logic Chart Status Display Package (*1)<br />
LHS5420 Test Function<br />
LHS5425 Expanded Test Functions (*2)<br />
LHS5490 Self-Documentation Package<br />
LHS5495 Electronic Instruction Manual<br />
LPC6910 SOE Server Configurator Package (*3)<br />
LPC6920 SOE Viewer Package (*3)<br />
*1: Supported by R2.05 or later.<br />
*2: Supported by R2.10 or later.<br />
*3: Supported by R3.03 or later.<br />
The packages, which are not listed, please contact<br />
YOKOGAWA’s sales office.<br />
See each software’s <strong>GS</strong> of CS 3000 for details.<br />
Note: All the General Electric Company’s products<br />
configuring the UOI system belong to General<br />
Electric Company.<br />
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation <strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong> Sep. 1, 2007-00
• MODEL AND SUFFIX CODES<br />
Model<br />
Suffix<br />
Codes<br />
Description<br />
UOI Integration Package for Power<br />
LPC2800 Generation Applications (R2.05)<br />
[Media model: LPCSM80-C11]<br />
-S Basic software license<br />
1 Always 1<br />
1 English-language version<br />
*1: This package contains an instruction manual in<br />
PDF to be read using Acrobat Reader.<br />
• ORDERING INFORMATION<br />
Specify model and suffix codes.<br />
*1: This package runs when CENTUM CS 3000<br />
R3.08.10 or later is used for CS 3000 Builder PC.<br />
*2: To purchase GE Fanuc CIMPLICITY HMI Plant<br />
Edition Server / Viewer Ver. 6.1 software, please<br />
contact GE Fanuc sales office.<br />
*3: Please order the CENTUM CS 3000 system ID license<br />
(Model: LHSDM01-S11) from YOKOGAWA<br />
together with LPC2800.<br />
One CENTUM CS 3000 system ID license is required<br />
for each LPC2800 license for the key code<br />
generation.<br />
4<br />
• TRADEMARKS<br />
- CENTUM is a registered trademark of Yokogawa<br />
Electric Corporation.<br />
- CIMPLICITY and CIMPLICITY HMI Plant Edition are<br />
a registered trademark of GE Fanuc Automation<br />
North America, Inc.<br />
- SPEEDTRONIC is a registered trademark of General<br />
Electric Company, USA.<br />
- ARCNET is a registered trademark of Datapoint Corporation.<br />
- Ethernet is a registered trademark of Xerox Corporation.<br />
- Windows and ActiveX are registered trademarks of<br />
Microsoft Corporation.<br />
- Pentium is a registered trademark of Intel Corporation.<br />
- PC, IBM PC/AT and IBM are registered trademarks of<br />
International Business Machines Corporation.<br />
- FOUNDATION is a trademark of Fieldbus Foundation.<br />
- Acrobat is registered trademarks of Adobe Systems<br />
Incorporated and registered within particular jurisdictions.<br />
- Other product and company names appearing in this<br />
document are trademarks or registered trademarks of<br />
their respective holders.<br />
All specifications are subject to change without written<br />
notice.<br />
All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation<br />
Subject to change without notice.<br />
<strong>GS</strong> <strong>33Q05L01</strong>-<strong>31E</strong> Sep. 1, 2007-00