<strong>Ceiling</strong> <strong>diffusers</strong><br />
4<br />
SPK- square <strong>diffusers</strong><br />
4-way square diffuser for ceiling mounting<br />
made of white lacquered steel (RAL 9010).<br />
The diffuser is equipped with a removable<br />
core.<br />
Application<br />
As air supply and return air grille<br />
in ventilation, air conditioning<br />
and heating systems.<br />
Fixation<br />
Fixation by means of a screw in<br />
the plenum box.<br />
Options<br />
D: Volume control damper with<br />
counter-revolving blades.<br />
RES: Plenum box with lateral<br />
connection.<br />
In option: insulated plenum box<br />
is available.<br />
© ATC<br />
www.airtradecentre.com
Dimensions<br />
Type A x A L x L B x B C x C<br />
(mm) (mm) (mm) (mm)<br />
288 294 147 144 222<br />
363 369 222 219 297<br />
438 444 297 294 372<br />
513 519 372 369 447<br />
595 594 447 444 522<br />
663 669 522 519 597<br />
738 744 597 741 672<br />
Aticle number: SPK-4 : A04 031 1 xxx 000<br />
(xxx = type of diffuser)<br />
SPK-4<br />
L x L<br />
B x B<br />
C x C<br />
A x A<br />
Options<br />
SPK-4 + D<br />
L x L<br />
B x B<br />
D: Volume control damper with counter-revolving blades. The<br />
volume control damper is supplied separately and is mounted<br />
on the diffuser by means of clips. Settings are done by means<br />
of a screwdriver after taking out the diffuser core.<br />
Article number: A04 031 2 xxx 000 (xxx = type of diffuser)<br />
RES: Plenum box with lateral connection. Available with or<br />
without insulation.<br />
RES<br />
C x C<br />
A x A<br />
© ATC
Technical data<br />
Complementary information to the selection table (see back page)<br />
• Q = air flow rate in m 3 /h.<br />
• Veff = effective air velocity between the blades of<br />
the diffuser in m/s.<br />
• L0,25 = throw in m at a terminal velocity of<br />
0,25m/s.<br />
• ∆Pt = total pressure loss in Pa.<br />
• NR = sound level.<br />
• Throw correction factor for the distance between<br />
the diffuser and the ceiling (Ch).<br />
For adherent jets, i.e. diffuser aligned with the<br />
ceiling, Ch = 1.<br />
For free jets, with the diffuser separated from the<br />
ceiling, Ch = 1,4.<br />
• The selection table is based on laboratory tests<br />
according to standards ISO 5219, ISO 5135 and ISO<br />
3741.<br />
• The diffuser is aligned with the ceiling.<br />
• The diffuser was placed in the centre of a square<br />
test room.<br />
• The height of the room is 3 +/- 0,5m.<br />
• The temperature difference between the supply<br />
air and the room temperature is -10°C<br />
• The NR values are based on the sound power<br />
level without room attenuation and without<br />
volume control damper.<br />
The corrected throw then is: Lc = L0,25 x Ch.<br />
• Correction factor when using a volume control<br />
damper (D).<br />
The volume control damper modifies the values of<br />
the sound level and pressure loss given in the selection<br />
tables in function of the percentage opening of<br />
the volume control damper. The correction factors<br />
are indicated in the following table:<br />
Opening 100% 50% 25%<br />
∆P X 1,5 X 2,5 X 4,5<br />
∆NR + 0 dB + 4 dB + 10 dB<br />
Some additional information:<br />
• To obtain an adherent jet with cold air, it is<br />
advisable not to exceed the maximum distance<br />
between the diffuser and the ceiling (h. max.) in<br />
function of the temperature difference (∆t) (difference<br />
between room and supply air temperature)<br />
indicated in the following table:<br />
∆t (°C) 0 6 9 12<br />
h max (m) 0,2 0,1 0,07 0,05<br />
© ATC<br />
• Minimum recommended velocity in the occupied<br />
zone, Vz:<br />
Due to the difference in temperature (∆t)<br />
between air in the room and the cold supply air,<br />
the following minimum velocities Vz are recommended<br />
in the occupied zone:<br />
∆t (°C) 0 6 9 12<br />
Vz (m/s) 0,15 0,15 0,2 0,25
Selection table<br />
Legend<br />
Q = air flow rate in m 3 /h<br />
Veff = effective air velocity between the blades<br />
of the diffuser in m/s<br />
L0,25 = throw in m at a terminal velocity of 0,25 m/s.<br />
∆P = total pressure loss in Pa<br />
NR = sound level<br />
∆T=10°C Type 288 363 438 513 595 663 738<br />
Q Ak (m 2 ) 0,0102 0,0229 0,0408 0,0637 0,0917 0,1249 0,1631<br />
(m 3 /h)<br />
100 Vk (m/s) 2,72 1,21<br />
L0,25 (m) 1,00 0,70<br />
∆P (Pa) 3,30 0,60<br />
NR 22 5<br />
150 Vk (m/s) 4,08 1,82 1,02<br />
L0,25 (m) 1,60 1,80 0,75<br />
∆P (Pa) 7,40 1,50 0,45<br />
NR 33 15 3<br />
200 Vk (m/s) 5,45 2,43 1,36<br />
L0,25 (m) 2,10 1,40 1,00<br />
∆P (Pa) 13,10 2,60 0,80<br />
NR 41 23 10<br />
300 Vk (m/s) 8,17 3,64 2,04 1,31<br />
L0,25 (m) 3,10 2,10 1,60 1,20<br />
∆P (Pa) 29,40 5,80 1,80 0,80<br />
NR 51 33 21 11<br />
400 Vk (m/s) 4,85 2,72 1,74 1,21<br />
L0,25 (m) 2,80 2,10 1,70 1,40<br />
∆P (Pa) 10,40 3,30 1,30 0,60<br />
NR 41 28 19 11<br />
500 Vk (m/s) 6,07 3,40 2,18 1,51 1,11<br />
L0,25 (m) 3,50 2,60 2,10 1,70 1,50<br />
∆P (Pa) 16,20 5,10 2,10 1,00 0,50<br />
NR 47 34 24 16 10<br />
700 Vk (m/s) 8,49 4,77 3,05 2,12 1,56 1,19<br />
L0,25 (m) 4,80 3,60 2,90 2,40 2,10 1,80<br />
∆P (Pa) 31,70 10,00 4,10 2,00 1,10 0,60<br />
NR 56 43 33 25 18 13<br />
1000 Vk (m/s) 6,81 4,36 3,03 2,22 1,70<br />
L0,25 (m) 5,20 4,10 3,50 3,00 2,60<br />
∆P (Pa) 20,40 8,40 4,00 2,20 1,30<br />
NR 52 43 35 28 22<br />
1500 Vk (m/s) 6,54 4,54 3,34 2,55<br />
L0,25 (m) 6,20 5,15 4,40 3,85<br />
∆P (Pa) 19,00 9,05 4,85 2,90<br />
NR 53 41 39 33<br />
2000 Vk (m/s) 8,72 6,06 4,45 3,41<br />
L0,25 (m) 8,30 6,90 5,90 5,20<br />
∆P (Pa) 33,50 16,10 8,70 5,10<br />
NR 61 53 46 40<br />
2500 Vk (m/s) 7,57 5,56 4,26<br />
L0,25 8,60 7,40 6,50<br />
∆P (Pa) 25,20 13,60 8,00<br />
NR 59 52 46<br />
3000 Vk (m/s) 6,67 5,11<br />
L0,25 (m) 8,90 7,80<br />
∆P (Pa) 19,60 11,50<br />
NR 57 51<br />
4000 Vk (m/s) 8,90 6,81<br />
L0,25 (m) 11,80 10,40<br />
∆P (Pa) 34,80 20,40<br />
NR 64 58<br />
Models can be subject to construction changes.<br />
© ATC<br />