14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2008<br />

http://theguide.schneider-electric.com<br />

Technical Series<br />

Electrical<br />

<strong>installation</strong> guide<br />

According to IEC International Standards


This technical guide is the result <strong>of</strong><br />

a collective effort.<br />

Technical advisor:<br />

Serge Volut - Jacques Schonek<br />

Illustrations and production:<br />

AXESS - Valence -France<br />

Printing:<br />

Les Deux-Ponts - France<br />

Edition<br />

March 2008<br />

Price: 90 �<br />

ISBN: 978.2.9531643.0.5<br />

N° dépôt légal: 1er semestre 2008<br />

© Schneider Electric<br />

All rights reserved in all countries<br />

This guide has been written for <strong>electrical</strong> Engineers who have to<br />

<strong>design</strong>, realize, inspect or maintain <strong>electrical</strong> <strong>installation</strong>s in compliance<br />

with international Standards <strong>of</strong> the International Electrotechnical<br />

Commission (IEC).<br />

“Which technical solution will guarantee that all relevant safety <strong>rules</strong> are<br />

met?” This question has been a permanent guideline for the elaboration <strong>of</strong><br />

this document.<br />

An international Standard such as the IEC 60364 “Electrical Installation<br />

in Buldings” specifies extensively the <strong>rules</strong> to comply with to ensure<br />

safety and predicted operational characteristics for all types <strong>of</strong> <strong>electrical</strong><br />

<strong>installation</strong>s. As the Standard must be extensive, and has to be applicable<br />

to all types <strong>of</strong> products and the technical solutions in use worldwide, the<br />

text <strong>of</strong> the IEC <strong>rules</strong> is complex, and not presented in a ready-to-use order.<br />

The Standard cannot therefore be considered as a working handbook, but<br />

only as a reference document.<br />

The aim <strong>of</strong> the present guide is to provide a clear, practical and stepby-step<br />

explanation for the complete study <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong>,<br />

according to IEC 60364 and other relevant IEC Standards. Therefore, the<br />

first chapter (B) presents the methodology to be used, and each chapter<br />

deals with one out <strong>of</strong> the eight steps <strong>of</strong> the study. The two last chapter are<br />

devoted to particular supply sources, loads and locations, and appendix<br />

provides additional information. Special attention must be paid to the<br />

EMC appendix, which is based on the broad and practical experience on<br />

electromagnetic compatibility problems.<br />

We all hope that you, the user, will find this handbook genuinely helpful.<br />

Schneider Electric S.A.<br />

The Electrical Installation Guide is a single document covering the<br />

techniques, regulations and standards related to <strong>electrical</strong> <strong>installation</strong>s.<br />

It is intended for <strong>electrical</strong> pr<strong>of</strong>essionals in companies, <strong>design</strong> <strong>of</strong>fices,<br />

inspection organisations, etc.<br />

This Technical Guide is aimed at pr<strong>of</strong>essional users and is only intended<br />

to provide them guidelines for the definition <strong>of</strong> an industrial, tertiary or<br />

domestic <strong>electrical</strong> <strong>installation</strong>. Information and guidelines contained in this<br />

Guide are provided AS IS. Schneider Electric makes no warranty <strong>of</strong> any<br />

kind, whether express or implied, such as but not limited to the warranties<br />

<strong>of</strong> merchantability and fitness for a particular purpose, nor assumes any<br />

legal liability or responsibility for the accuracy, completeness, or usefulness<br />

<strong>of</strong> any information, apparatus, product, or process disclosed in this Guide,<br />

nor represents that its use would not infringe privately owned rights.<br />

The purpose <strong>of</strong> this guide is to facilitate the implementation <strong>of</strong> International<br />

<strong>installation</strong> standards for <strong>design</strong>ers & contractors, but in all cases the<br />

original text <strong>of</strong> International or local standards in force shall prevail.<br />

This new edition has been published to take into account changes in<br />

techniques, standards and regulations, in particular <strong>electrical</strong> <strong>installation</strong><br />

standard IEC 60364.<br />

We thank all the readers <strong>of</strong> the previous edition <strong>of</strong> this guide for their<br />

comments that have helped improve the current edition.<br />

We also thank the many people and organisations, to numerous to name<br />

here, who have contributed in one way or another to the preparation <strong>of</strong> this<br />

guide.


Guiding tools for more efficiency in <strong>electrical</strong><br />

distribution <strong>design</strong><br />

Technical knowledge Pre-<strong>design</strong> help for budget<br />

approach<br />

10-30mn eLearning modules for<br />

individual training<br />

Articles giving base skills about<br />

general subjects: “Cahiers<br />

Techniques”<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Selection criterias & method<br />

to follow in order to pre-define<br />

project specification:<br />

b Architecture guide<br />

b ID-Spec s<strong>of</strong>tware<br />

Solutions and examples with<br />

recommended architectures in<br />

Solution guides:<br />

b airport<br />

b automative<br />

b food<br />

b retail<br />

b <strong>of</strong>fice<br />

b industrial buildings<br />

b healthcare<br />

b ...


Design support Specification help Help in <strong>installation</strong>, use &<br />

maintenance<br />

Practical data & methods<br />

through major <strong>design</strong> guides:<br />

b Electrical Installation Guide<br />

b Protection guide<br />

b Industrial <strong>electrical</strong> network<br />

<strong>design</strong> guide<br />

b ...<br />

Product presentation <strong>of</strong> technical<br />

characteristics in all Schneider<br />

Electric product Catalogues<br />

Design S<strong>of</strong>tware:<br />

b My Ecodial<br />

Ecodial s<strong>of</strong>tware provides a<br />

complete <strong>design</strong> package for<br />

LV <strong>installation</strong>s, in accordance<br />

with IEC standards and<br />

recommendations.<br />

Main features:<br />

v Create diagrams<br />

v Optimise circuit breakers curves<br />

v Determine source power<br />

v Follow step by step calculation<br />

v Print the project <strong>design</strong> file<br />

b SISPRO building<br />

b ...<br />

Drawing source files for<br />

connection, dimension, diagram,<br />

mounting & safety: CAD library<br />

Technical specification on<br />

products & solutions for tender<br />

request<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Product <strong>installation</strong> data<br />

Product how to use data<br />

Product maintenance data


<strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong><br />

<strong>installation</strong> <strong>design</strong><br />

Connection to the MV utility<br />

distribution network<br />

Connection to the LV utility<br />

distribution network<br />

MV & LV architecture selection<br />

guide<br />

LV Distribution<br />

Protection against electric<br />

shocks<br />

Sizing and protection <strong>of</strong><br />

conductors<br />

LV switchgear: functions &<br />

selection<br />

Protection against voltage<br />

surges in LV<br />

Energy Efficiency in <strong>electrical</strong><br />

distribution<br />

Power factor correction and<br />

harmonic filtering<br />

Harmonic management<br />

Characteristics <strong>of</strong> particular<br />

sources and loads<br />

Residential and other special<br />

locations<br />

EMC guidelines<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

H<br />

J<br />

K<br />

L<br />

M<br />

N<br />

P<br />

Q


A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

H<br />

<strong>General</strong> contents<br />

<strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

1 Methodology A2<br />

2 Rules and statutory regulations A4<br />

3 Installed power loads - Characteristics A10<br />

4 Power loading <strong>of</strong> an <strong>installation</strong> A15<br />

Connection to the MV utility distribution network<br />

1 Supply <strong>of</strong> power at medium voltage B2<br />

2 Procedure for the establishment <strong>of</strong> a new substation B14<br />

3 Protection aspect B16<br />

4 The consumer substation with LV metering B22<br />

5 The consumer substation with MV metering B30<br />

6 Constitution <strong>of</strong> MV/LV distribution substations B35<br />

Connection to the LV utility distribution network<br />

1 Low voltage utility distribution networks C2<br />

2 Tariffs and metering C16<br />

MV & LV architecture selection guide<br />

1 Stakes for the user D3<br />

2 Simplified architecture <strong>design</strong> process D4<br />

3 Electrical <strong>installation</strong> characteristics D7<br />

4 Technological characteristics D11<br />

5 Architecture assessment criteria D13<br />

6 Choice <strong>of</strong> architecture fundamentals D15<br />

7 Choice <strong>of</strong> architecture details D19<br />

8 Choice <strong>of</strong> equiment D24<br />

9 Recommendations for architecture optimization D26<br />

10 Glossary D29<br />

11 ID-Spec s<strong>of</strong>tware D30<br />

12 Example: <strong>electrical</strong> <strong>installation</strong> in a printworks D31<br />

LV Distribution<br />

1 Earthing schemes E2<br />

2 The <strong>installation</strong> system E15<br />

3 External influences (IEC 60364-5-51) E25<br />

Protection against electric shocks<br />

1 <strong>General</strong> F2<br />

2 Protection against direct contact F4<br />

3 Protection against indirect contact F6<br />

4 Protection <strong>of</strong> goods due to insulation fault F17<br />

5 Implementation <strong>of</strong> the TT system F19<br />

6 Implementation <strong>of</strong> the TN system F25<br />

7 Implementation <strong>of</strong> the IT system F31<br />

8 Residual current differential devices RCDs F38<br />

Sizing and protection <strong>of</strong> conductors<br />

1 <strong>General</strong> G2<br />

2 Practical method for determining the smallest allowable G7<br />

cross-sectional area <strong>of</strong> circuit conductors<br />

3 Determination <strong>of</strong> voltage drop G20<br />

4 Short-circuit current G24<br />

5 Particular cases <strong>of</strong> short-circuit current G30<br />

6 Protective earthing conductor G37<br />

7 The neutral conductor G42<br />

8 Worked example <strong>of</strong> cable calculation G46<br />

LV switchgear: functions & selection<br />

1 The basic functions <strong>of</strong> LV switchgear H2<br />

2 The switchgear H5<br />

3 Choice <strong>of</strong> switchgear H10<br />

4 Circuit breaker H11<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


J<br />

K<br />

L<br />

M<br />

N<br />

P<br />

Q<br />

<strong>General</strong> contents<br />

Protection against voltage surges in LV<br />

1 <strong>General</strong> J2<br />

2 Overvoltage protection devices J6<br />

3 Standards J11<br />

4 Choosing a protection device J14<br />

Energy Efficiency in <strong>electrical</strong> distribution<br />

1 Introduction K2<br />

2 Energy efficiency and electricity K3<br />

3 One process, several players K5<br />

4 From <strong>electrical</strong> measurement to <strong>electrical</strong> information K10<br />

5 Communication and Information System K16<br />

Power factor correction and harmonic filtering<br />

1 Reactive energy and power factor L2<br />

2 Why to improve the power factor? L5<br />

3 How to improve the power factor? L7<br />

4 Where to install power correction capacitors? L10<br />

5 How to decide the optimum level <strong>of</strong> compensation? L12<br />

6 Compensation at the terminals <strong>of</strong> a transformer L15<br />

7 Power factor correction <strong>of</strong> induction motors L18<br />

8 Example <strong>of</strong> an <strong>installation</strong> before and after power factor correction L20<br />

9 The effects <strong>of</strong> harmonics L21<br />

10 Implementation <strong>of</strong> capacitor banks L24<br />

Harmonic management<br />

1 The problem: M2<br />

Why is it necessary to detect and eliminate harmonics?<br />

2 Standards M3<br />

3 <strong>General</strong> M4<br />

4 Main effects <strong>of</strong> harmonics in <strong>installation</strong>s M6<br />

5 Essential indicators <strong>of</strong> harmonic distortion and M11<br />

measurement principles<br />

6 Measuring the indicators M14<br />

7 Detection devices M16<br />

8 Solutions to attenuate harmonics M17<br />

Characteristics <strong>of</strong> particular sources and loads<br />

1 Protection <strong>of</strong> a LV generator set and the downstream circuits N2<br />

2 Uninterruptible Power Supply Units (UPS) N11<br />

3 Protection <strong>of</strong> LV/LV transformers N24<br />

4 Lighting circuits N27<br />

5 Asynchronous motors N42<br />

Residential and other special locations<br />

1 Residential and similar premises P2<br />

2 Bathrooms and showers P8<br />

3 Recommendations applicable to special <strong>installation</strong>s and locations P12<br />

EMC guidelines<br />

1 Electrical distribution Q2<br />

2 Earthing principles and structures Q3<br />

3 Implementation Q5<br />

4 Coupling mechanism and counter-measures Q14<br />

5 Wiring recommendations Q20<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


2<br />

3<br />

4<br />

<strong>Chapter</strong> A<br />

<strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong><br />

<strong>installation</strong> <strong>design</strong><br />

Contents<br />

Methodology A2<br />

Rules and statutory regulations A4<br />

2.1 Definition <strong>of</strong> voltage ranges A4<br />

2.2 Regulations A5<br />

2.3 Standards A5<br />

2.4 Quality and safety <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong> A6<br />

2.5 Initial testing <strong>of</strong> an <strong>installation</strong> A6<br />

2.6 Periodic check-testing <strong>of</strong> an <strong>installation</strong><br />

2.7 Conformity (with standards and specifications) <strong>of</strong> equipment<br />

A7<br />

used in the <strong>installation</strong> A7<br />

2.8 Environment A8<br />

Installed power loads - Characteristics A 0<br />

3.1 Induction motors<br />

3.2 Resistive-type heating appliances and incandescent lamps<br />

A10<br />

(conventional or halogen) A12<br />

Power loading <strong>of</strong> an <strong>installation</strong> A 5<br />

4.1 Installed power (kW) A15<br />

4.2 Installed apparent power (kVA) A15<br />

4.3 Estimation <strong>of</strong> actual maximum kVA demand A16<br />

4.4 Example <strong>of</strong> application <strong>of</strong> factors ku and ks A17<br />

4.5 Diversity factor A18<br />

4.6 Choice <strong>of</strong> transformer rating A19<br />

4.7 Choice <strong>of</strong> power-supply sources A20<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

A2<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

B – Connection to the MV utility distribution<br />

network<br />

C - Connection to the LV utility distribution<br />

network<br />

D - MV & LV architecture selection guide<br />

E - LV Distribution<br />

F - Protection against electric shocks<br />

G - Sizing and protection <strong>of</strong> conductors<br />

H - LV switchgear: functions & selection<br />

Methodology<br />

For the best results in <strong>electrical</strong> <strong>installation</strong> <strong>design</strong> it is recommended to read all the<br />

chapters <strong>of</strong> this guide in the order in which they are presented.<br />

Listing <strong>of</strong> power demands<br />

The study <strong>of</strong> a proposed <strong>electrical</strong> <strong>installation</strong> requires an adequate understanding <strong>of</strong><br />

all governing <strong>rules</strong> and regulations.<br />

The total power demand can be calculated from the data relative to the location and<br />

power <strong>of</strong> each load, together with the knowledge <strong>of</strong> the operating modes (steady<br />

state demand, starting conditions, non simultaneous operation, etc.)<br />

From these data, the power required from the supply source and (where appropriate)<br />

the number <strong>of</strong> sources necessary for an adequate supply to the <strong>installation</strong> are<br />

readily obtained.<br />

Local information regarding tariff structures is also required to allow the best choice<br />

<strong>of</strong> connection arrangement to the power-supply network, e.g. at medium voltage or<br />

low voltage level.<br />

Service connection<br />

This connection can be made at:<br />

b Medium Voltage level<br />

A consumer-type substation will then have to be studied, built and equipped. This<br />

substation may be an outdoor or indoor <strong>installation</strong> conforming to relevant standards<br />

and regulations (the low-voltage section may be studied separately if necessary).<br />

Metering at medium-voltage or low-voltage is possible in this case.<br />

b Low Voltage level<br />

The <strong>installation</strong> will be connected to the local power network and will (necessarily) be<br />

metered according to LV tariffs.<br />

Electrical Distribution architecture<br />

The whole <strong>installation</strong> distribution network is studied as a complete system.<br />

A selection guide is proposed for determination <strong>of</strong> the most suitable architecture.<br />

MV/LV main distribution and LV power distribution levels are covered.<br />

Neutral earthing arrangements are chosen according to local regulations, constraints<br />

related to the power-supply, and to the type <strong>of</strong> loads.<br />

The distribution equipment (panelboards, switchgears, circuit connections, ...) are<br />

determined from building plans and from the location and grouping <strong>of</strong> loads.<br />

The type <strong>of</strong> premises and allocation can influence their immunity to external<br />

disturbances.<br />

Protection against electric shocks<br />

The earthing system (TT, IT or TN) having been previously determined, then the<br />

appropriate protective devices must be implemented in order to achieve protection<br />

against hazards <strong>of</strong> direct or indirect contact.<br />

Circuits and switchgear<br />

Each circuit is then studied in detail. From the rated currents <strong>of</strong> the loads, the level<br />

<strong>of</strong> short-circuit current, and the type <strong>of</strong> protective device, the cross-sectional area<br />

<strong>of</strong> circuit conductors can be determined, taking into account the nature <strong>of</strong> the<br />

cableways and their influence on the current rating <strong>of</strong> conductors.<br />

Before adopting the conductor size indicated above, the following requirements must<br />

be satisfied:<br />

b The voltage drop complies with the relevant standard<br />

b Motor starting is satisfactory<br />

b Protection against electric shock is assured<br />

The short-circuit current Isc is then determined, and the thermal and electrodynamic<br />

withstand capability <strong>of</strong> the circuit is checked.<br />

These calculations may indicate that it is necessary to use a conductor size larger<br />

than the size originally chosen.<br />

The performance required by the switchgear will determine its type and<br />

characteristics.<br />

The use <strong>of</strong> cascading techniques and the discriminative operation <strong>of</strong> fuses and<br />

tripping <strong>of</strong> circuit breakers are examined.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

J – Protection against voltage surges in LV<br />

K – Energy efficiency in <strong>electrical</strong> distribution<br />

L - Power factor correction and harmonic filtering<br />

M - Harmonic management<br />

N - Characteristics <strong>of</strong> particular sources and<br />

loads<br />

P - Residential and other special locations<br />

Q - EMC guideline<br />

(1) Ecodial is a Merlin Gerin product and is available in French<br />

and English versions.<br />

Methodology<br />

Protection against overvoltages<br />

Direct or indirect lightning strokes can damage <strong>electrical</strong> equipment at a distance<br />

<strong>of</strong> several kilometers. Operating voltage surges, transient and industrial frequency<br />

over-voltage can also produce the same consequences.The effects are examined<br />

and solutions are proposed.<br />

Energy efficiency in electrial distribution<br />

Implementation <strong>of</strong> measuring devices with an adequate communication system<br />

within the <strong>electrical</strong> <strong>installation</strong> can produce high benefits for the user or owner:<br />

reduced power consumption, reduced cost <strong>of</strong> energy, better use <strong>of</strong> <strong>electrical</strong><br />

equipment.<br />

Reactive energy<br />

The power factor correction within <strong>electrical</strong> <strong>installation</strong>s is carried out locally,<br />

globally or as a combination <strong>of</strong> both methods.<br />

Harmonics<br />

Harmonics in the network affect the quality <strong>of</strong> energy and are at the origin <strong>of</strong> many<br />

disturbances as overloads, vibrations, ageing <strong>of</strong> equipment, trouble <strong>of</strong> sensitive<br />

equipment, <strong>of</strong> local area networks, telephone networks. This chapter deals with the<br />

origins and the effects <strong>of</strong> harmonics and explain how to measure them and present<br />

the solutions.<br />

Particular supply sources and loads<br />

Particular items or equipment are studied:<br />

b Specific sources such as alternators or inverters<br />

b Specific loads with special characteristics, such as induction motors, lighting<br />

circuits or LV/LV transformers<br />

b Specific systems, such as direct-current networks<br />

Generic applications<br />

Certain premises and locations are subject to particularly strict regulations: the most<br />

common example being residential dwellings.<br />

EMC Guidelines<br />

Some basic <strong>rules</strong> must be followed in order to ensure Electromagnetic Compatibility.<br />

Non observance <strong>of</strong> these <strong>rules</strong> may have serious consequences in the operation <strong>of</strong><br />

the <strong>electrical</strong> <strong>installation</strong>: disturbance <strong>of</strong> communication systems, nuisance tripping<br />

<strong>of</strong> protection devices, and even destruction <strong>of</strong> sensitive devices.<br />

Ecodial s<strong>of</strong>tware<br />

Ecodial s<strong>of</strong>tware (1) provides a complete <strong>design</strong> package for LV <strong>installation</strong>s, in<br />

accordance with IEC standards and recommendations.<br />

The following features are included:<br />

b Construction <strong>of</strong> one-line diagrams<br />

b Calculation <strong>of</strong> short-circuit currents<br />

b Calculation <strong>of</strong> voltage drops<br />

b Optimization <strong>of</strong> cable sizes<br />

b Required ratings <strong>of</strong> switchgear and fusegear<br />

b Discrimination <strong>of</strong> protective devices<br />

b Recommendations for cascading schemes<br />

b Verification <strong>of</strong> the protection <strong>of</strong> people<br />

b Comprehensive print-out <strong>of</strong> the foregoing calculated <strong>design</strong> data<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

A<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

2 Rules and statutory regulations<br />

Low-voltage <strong>installation</strong>s are governed by a number <strong>of</strong> regulatory and advisory texts,<br />

which may be classified as follows:<br />

b Statutory regulations (decrees, factory acts,etc.)<br />

b Codes <strong>of</strong> practice, regulations issued by pr<strong>of</strong>essional institutions, job specifications<br />

b National and international standards for <strong>installation</strong>s<br />

b National and international standards for products<br />

2.1 Definition <strong>of</strong> voltage ranges<br />

IEC voltage standards and recommendations<br />

Three-phase four-wire or three-wire systems Single-phase three-wire systems<br />

Nominal voltage (V) Nominal voltage (V)<br />

50 Hz 60 Hz 60 Hz<br />

– 120/208 120/240<br />

– 240 –<br />

230/400 (1) 277/480 –<br />

400/690 (1) 480 –<br />

– 347/600 –<br />

1000 600 –<br />

(1) The nominal voltage <strong>of</strong> existing 220/380 V and 240/415 V systems shall evolve<br />

toward the recommended value <strong>of</strong> 230/400 V. The transition period should be as short<br />

as possible and should not exceed the year 2003. During this period, as a first step, the<br />

electricity supply authorities <strong>of</strong> countries having 220/380 V systems should bring the<br />

voltage within the range 230/400 V +6 %, -10 % and those <strong>of</strong> countries having<br />

240/415 V systems should bring the voltage within the range 230/400 V +10 %,<br />

-6 %. At the end <strong>of</strong> this transition period, the tolerance <strong>of</strong> 230/400 V ± 10 % should<br />

have been achieved; after this the reduction <strong>of</strong> this range will be considered. All the<br />

above considerations apply also to the present 380/660 V value with respect to the<br />

recommended value 400/690 V.<br />

Fig. A1 : Standard voltages between 100 V and 1000 V (IEC 60038 Edition 6.2 2002-07)<br />

Series I Series II<br />

Highest voltage Nominal system Highest voltage Nominal system<br />

for equipment (kV) voltage (kV) for equipment (kV) voltage (kV)<br />

3.6 (1) 3.3 (1) 3 (1) 4.40 (1) 4.16 (1)<br />

7.2 (1) 6.6 (1) 6 (1) – –<br />

12 11 10 – –<br />

– – – 13.2 (2) 12.47 (2)<br />

– – – 13.97 (2) 13.2 (2)<br />

– – – 14.52 (1) 13.8 (1)<br />

(17.5) – (15) – –<br />

24 22 20 – –<br />

– – – 26.4 (2) 24.94 (2)<br />

36 (3) 33 (3) – – –<br />

– – – 36.5 34.5<br />

40.5 (3) – 35 (3) – –<br />

These systems are generally three-wire systems unless otherwise indicated.<br />

The values indicated are voltages between phases.<br />

The values indicated in parentheses should be considered as non-preferred values. It is<br />

recommended that these values should not be used for new systems to be constructed<br />

in future.<br />

Note 1: It is recommended that in any one country the ratio between two adjacent<br />

nominal voltages should be not less than two.<br />

Note 2: In a normal system <strong>of</strong> Series I, the highest voltage and the lowest voltage do<br />

not differ by more than approximately ±10 % from the nominal voltage <strong>of</strong> the system.<br />

In a normal system <strong>of</strong> Series II, the highest voltage does not differ by more then +5 %<br />

and the lowest voltage by more than -10 % from the nominal voltage <strong>of</strong> the system.<br />

(1) These values should not be used for public distribution systems.<br />

(2) These systems are generally four-wire systems.<br />

(3) The unification <strong>of</strong> these values is under consideration.<br />

Fig. A2 : Standard voltages above 1 kV and not exceeding 35 kV<br />

(IEC 60038 Edition 6.2 2002-07)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

2 Rules and statutory regulations<br />

2.2 Regulations<br />

In most countries, <strong>electrical</strong> <strong>installation</strong>s shall comply with more than one set <strong>of</strong><br />

regulations, issued by National Authorities or by recognized private bodies. It is<br />

essential to take into account these local constraints before starting the <strong>design</strong>.<br />

2.3 Standards<br />

This Guide is based on relevant IEC standards, in particular IEC 60364. IEC 60364<br />

has been established by medical and engineering experts <strong>of</strong> all countries in the<br />

world comparing their experience at an international level. Currently, the safety<br />

principles <strong>of</strong> IEC 60364 and 60479-1 are the fundamentals <strong>of</strong> most <strong>electrical</strong><br />

standards in the world (see table below and next page).<br />

IEC 60038 Standard voltages<br />

IEC 60076-2 Power transformers - Temperature rise<br />

IEC 60076-3 Power transformers - Insulation levels, dielectric tests and external clearances in air<br />

IEC 60076- Power transformers - Ability to withstand short-circuit<br />

IEC 60076-10 Power transformers - Determination <strong>of</strong> sound levels<br />

IEC 601 6 Semiconductor convertors - <strong>General</strong> requirements and line commutated convertors<br />

IEC 602 Electrical relays<br />

IEC 6026 -1 High-voltage switches - High-voltage switches for rated voltages above 1 kV and less than 52 kV<br />

IEC 60269-1 Low-voltage fuses - <strong>General</strong> requirements<br />

IEC 60269-2 Low-voltage fuses - Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications)<br />

IEC 60282-1 High-voltage fuses - Current-limiting fuses<br />

IEC 60287-1-1 Electric cables - Calculation <strong>of</strong> the current rating - Current rating equations (100% load factor) and calculation <strong>of</strong> losses - <strong>General</strong><br />

IEC 6036 Electrical <strong>installation</strong>s <strong>of</strong> buildings<br />

IEC 6036 -1 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Fundamental principles<br />

IEC 6036 - - 1 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Protection for safety - Protection against electric shock<br />

IEC 6036 - - 2 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Protection for safety - Protection against thermal effects<br />

IEC 6036 - - 3 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Protection for safety - Protection against overcurrent<br />

IEC 6036 - - Electrical <strong>installation</strong>s <strong>of</strong> buildings - Protection for safety - Protection against electromagnetic and voltage disrurbance<br />

IEC 6036 - - 1 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Selection and erection <strong>of</strong> <strong>electrical</strong> equipment - Common <strong>rules</strong><br />

IEC 6036 - - 2 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Selection and erection <strong>of</strong> <strong>electrical</strong> equipment - Wiring systems<br />

IEC 6036 - - 3 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Selection and erection <strong>of</strong> <strong>electrical</strong> equipment - Isolation, switching and control<br />

IEC 6036 - - Electrical <strong>installation</strong>s <strong>of</strong> buildings - Selection and erection <strong>of</strong> <strong>electrical</strong> equipment - Earthing arrangements<br />

IEC 6036 - - Electrical <strong>installation</strong>s <strong>of</strong> buildings - Selection and erection <strong>of</strong> <strong>electrical</strong> equipment - Other equipments<br />

IEC 6036 -6-61 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Verification and testing - Initial verification<br />

IEC 6036 -7-701 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Locations containing a bath tub or shower basin<br />

IEC 6036 -7-702 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Swimming pools and other basins<br />

IEC 6036 -7-703 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Locations containing sauna heaters<br />

IEC 6036 -7-70 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Construction and demolition site <strong>installation</strong>s<br />

IEC 6036 -7-70 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Electrical <strong>installation</strong>s <strong>of</strong> agricultural and horticultural<br />

premises<br />

IEC 6036 -7-706 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Restrictive conducting locations<br />

IEC 6036 -7-707 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Earthing requirements for the <strong>installation</strong> <strong>of</strong> data<br />

processing equipment<br />

IEC 6036 -7-708 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Electrical <strong>installation</strong>s in caravan parks and caravans<br />

IEC 6036 -7-709 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Marinas and pleasure craft<br />

IEC 6036 -7-710 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Medical locations<br />

IEC 6036 -7-711 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Exhibitions, shows and stands<br />

IEC 6036 -7-712 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Solar photovoltaic (PV) power supply systems<br />

IEC 6036 -7-713 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Furniture<br />

IEC 6036 -7-71 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - External lighting <strong>installation</strong>s<br />

IEC 6036 -7-71 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Extra-low-voltage lighting <strong>installation</strong>s<br />

IEC 6036 -7-717 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Mobile or transportable units<br />

IEC 6036 -7-7 0 Electrical <strong>installation</strong>s <strong>of</strong> buildings - Requirements for special <strong>installation</strong>s or locations - Temporary <strong>electrical</strong> <strong>installation</strong>s for structures,<br />

amusement devices and booths at fairgrounds, amusement parks and circuses<br />

IEC 60 27 High-voltage alternating current circuit-breakers<br />

IEC 60 39-1 Low-voltage switchgear and controlgear assemblies - Type-tested and partially type-tested assemblies<br />

IEC 60 39-2 Low-voltage switchgear and controlgear assemblies - Particular requirements for busbar trunking systems (busways)<br />

IEC 60 39-3 Low-voltage switchgear and controlgear assemblies - Particular requirements for low-voltage switchgear and controlgear assemblies intended to<br />

be installed in places where unskilled persons have access for their use - Distribution boards<br />

IEC 60 39- Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies for construction sites (ACS)<br />

IEC 60 6 Basic and safety principles for man-machine interface, marking and identification - Identification <strong>of</strong> conductors by colours or numerals<br />

IEC 60 39- Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies intended to be installed outdoors in public places<br />

- Cable distribution cabinets (CDCs)<br />

IEC 60 79-1 Effects <strong>of</strong> current on human beings and livestock - <strong>General</strong> aspects<br />

IEC 60 79-2 Effects <strong>of</strong> current on human beings and livestock - Special aspects<br />

IEC 60 79-3 Effects <strong>of</strong> current on human beings and livestock - Effects <strong>of</strong> currents passing through the body <strong>of</strong> livestock<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

(Continued on next page)<br />

A<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

A6<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

2 Rules and statutory regulations<br />

IEC 60 29 Degrees <strong>of</strong> protection provided by enclosures (IP code)<br />

IEC 606 Spécification for high-voltage fuse-links for motor circuit applications<br />

IEC 6066 Insulation coordination for equipment within low-voltage systems<br />

IEC 6071 Dimensions <strong>of</strong> low-voltage switchgear and controlgear. Standardized mounting on rails for mechanical support <strong>of</strong> <strong>electrical</strong> devices in switchgear<br />

and controlgear <strong>installation</strong>s.<br />

IEC 6072 Short-circuit temperature limits <strong>of</strong> electric cables with rated voltages <strong>of</strong> 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV)<br />

IEC 607 <strong>General</strong> requirements for residual current operated protective devices<br />

IEC 60787 Application guide for the selection <strong>of</strong> fuse-links <strong>of</strong> high-voltage fuses for transformer circuit application<br />

IEC 60831 Shunt power capacitors <strong>of</strong> the self-healing type for AC systems having a rated voltage up to and including 1000 V - <strong>General</strong> - Performance, testing<br />

and rating - Safety requirements - Guide for <strong>installation</strong> and operation<br />

IEC 609 7-1 Low-voltage switchgear and controlgear - <strong>General</strong> <strong>rules</strong><br />

IEC 609 7-2 Low-voltage switchgear and controlgear - Circuit-breakers<br />

IEC 609 7-3 Low-voltage switchgear and controlgear - Switches, disconnectors, switch-disconnectors and fuse-combination units<br />

IEC 609 7- -1 Low-voltage switchgear and controlgear - Contactors and motor-starters - Electromechanical contactors and motor-starters<br />

IEC 609 7-6-1 Low-voltage switchgear and controlgear - Multiple function equipment - Automatic transfer switching equipment<br />

IEC 61000 Electromagnetic compatibility (EMC)<br />

IEC 611 0 Protection against electric shocks - common aspects for <strong>installation</strong> and equipment<br />

IEC 61 7-1 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring <strong>of</strong> protective<br />

measures - <strong>General</strong> requirements<br />

IEC 61 7-8 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring <strong>of</strong> protective<br />

measures<br />

IEC 61 7-9 Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for insulation fault location in IT systems<br />

IEC 61 8-2-6 Safety <strong>of</strong> power transformers, power supply units and similar - Particular requirements for safety isolating transformers for general use<br />

IEC 62271-1 Common specifications for high-voltage switchgear and controlgear standards<br />

IEC 62271-100 High-voltage switchgear and controlgear - High-voltage alternating-current circuit-breakers<br />

IEC 62271-102 High-voltage switchgear and controlgear - Alternating current disconnectors and earthing switches<br />

IEC 62271-10 High-voltage switchgear and controlgear - Alternating current switch-fuse combinations<br />

IEC 62271-200 High-voltage switchgear and controlgear - Alternating current metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to<br />

and including 52 kV<br />

IEC 62271-202 High-voltage/low voltage prefabricated substations<br />

2. Quality and safety <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong><br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

(Concluded)<br />

In so far as control procedures are respected, quality and safety will be assured<br />

only if:<br />

b The initial checking <strong>of</strong> conformity <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong> with the standard and<br />

regulation has been achieved<br />

b The <strong>electrical</strong> equipment comply with standards<br />

b The periodic checking <strong>of</strong> the <strong>installation</strong> recommended by the equipment<br />

manufacturer is respected.<br />

2. Initial testing <strong>of</strong> an <strong>installation</strong><br />

Before a utility will connect an <strong>installation</strong> to its supply network, strict precommissioning<br />

<strong>electrical</strong> tests and visual inspections by the authority, or by its<br />

appointed agent, must be satisfied.<br />

These tests are made according to local (governmental and/or institutional)<br />

regulations, which may differ slightly from one country to another. The principles <strong>of</strong><br />

all such regulations however, are common, and are based on the observance <strong>of</strong><br />

rigorous safety <strong>rules</strong> in the <strong>design</strong> and realization <strong>of</strong> the <strong>installation</strong>.<br />

IEC 60364-6-61 and related standards included in this guide are based on an<br />

international consensus for such tests, intended to cover all the safety measures and<br />

approved <strong>installation</strong> practices normally required for residential, commercial and (the<br />

majority <strong>of</strong>) industrial buildings. Many industries however have additional regulations<br />

related to a particular product (petroleum, coal, natural gas, etc.). Such additional<br />

requirements are beyond the scope <strong>of</strong> this guide.<br />

The pre-commissioning <strong>electrical</strong> tests and visual-inspection checks for <strong>installation</strong>s<br />

in buildings include, typically, all <strong>of</strong> the following:<br />

b Insulation tests <strong>of</strong> all cable and wiring conductors <strong>of</strong> the fixed <strong>installation</strong>, between<br />

phases and between phases and earth<br />

b Continuity and conductivity tests <strong>of</strong> protective, equipotential and earth-bonding<br />

conductors<br />

b Resistance tests <strong>of</strong> earthing electrodes with respect to remote earth<br />

b Verification <strong>of</strong> the proper operation <strong>of</strong> the interlocks, if any<br />

b Check <strong>of</strong> allowable number <strong>of</strong> socket-outlets per circuit


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

Conformity <strong>of</strong> equipment with the relevant<br />

standards can be attested in several ways<br />

2 Rules and statutory regulations<br />

b Cross-sectional-area check <strong>of</strong> all conductors for adequacy at the short-circuit<br />

levels prevailing, taking account <strong>of</strong> the associated protective devices, materials and<br />

<strong>installation</strong> conditions (in air, conduit, etc.)<br />

b Verification that all exposed- and extraneous metallic parts are properly earthed<br />

(where appropriate)<br />

b Check <strong>of</strong> clearance distances in bathrooms, etc.<br />

These tests and checks are basic (but not exhaustive) to the majority <strong>of</strong> <strong>installation</strong>s,<br />

while numerous other tests and <strong>rules</strong> are included in the regulations to cover<br />

particular cases, for example: TN-, TT- or IT-earthed <strong>installation</strong>s, <strong>installation</strong>s based<br />

on class 2 insulation, SELV circuits, and special locations, etc.<br />

The aim <strong>of</strong> this guide is to draw attention to the particular features <strong>of</strong> different types<br />

<strong>of</strong> <strong>installation</strong>, and to indicate the essential <strong>rules</strong> to be observed in order to achieve<br />

a satisfactory level <strong>of</strong> quality, which will ensure safe and trouble-free performance.<br />

The methods recommended in this guide, modified if necessary to comply with any<br />

possible variation imposed by a utility, are intended to satisfy all precommissioning<br />

test and inspection requirements.<br />

2.6 Periodic check-testing <strong>of</strong> an <strong>installation</strong><br />

In many countries, all industrial and commercial-building <strong>installation</strong>s, together with<br />

<strong>installation</strong>s in buildings used for public gatherings, must be re-tested periodically by<br />

authorized agents.<br />

Figure A3 shows the frequency <strong>of</strong> testing commonly prescribed according to the<br />

kind <strong>of</strong> <strong>installation</strong> concerned.<br />

Type <strong>of</strong> <strong>installation</strong> Testing<br />

frequency<br />

Installations which b Locations at which a risk <strong>of</strong> degradation, Annually<br />

require the protection fire or explosion exists<br />

<strong>of</strong> employees b Temporary <strong>installation</strong>s at worksites<br />

b Locations at which MV <strong>installation</strong>s exist<br />

b Restrictive conducting locations<br />

where mobile equipment is used<br />

Other cases Every 3 years<br />

Installations in buildings According to the type <strong>of</strong> establishment From one to<br />

used for public gatherings, and its capacity for receiving the public three years<br />

where protection against<br />

the risks <strong>of</strong> fire and panic<br />

are required<br />

Residential According to local regulations<br />

Fig A3 : Frequency <strong>of</strong> check-tests commonly recommended for an <strong>electrical</strong> <strong>installation</strong><br />

2.7 Conformity (with standards and specifications)<br />

<strong>of</strong> equipment used in the <strong>installation</strong><br />

Attestation <strong>of</strong> conformity<br />

The conformity <strong>of</strong> equipment with the relevant standards can be attested:<br />

b By an <strong>of</strong>ficial mark <strong>of</strong> conformity granted by the certification body concerned, or<br />

b By a certificate <strong>of</strong> conformity issued by a certification body, or<br />

b By a declaration <strong>of</strong> conformity from the manufacturer<br />

The first two solutions are generally not available for high voltage equipment.<br />

Declaration <strong>of</strong> conformity<br />

Where the equipment is to be used by skilled or instructed persons, the<br />

manufacturer’s declaration <strong>of</strong> conformity (included in the technical documentation),<br />

is generally recognized as a valid attestation. Where the competence <strong>of</strong> the<br />

manufacturer is in doubt, a certificate <strong>of</strong> conformity can reinforce the manufacturer’s<br />

declaration.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

A8<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

2 Rules and statutory regulations<br />

Note: CE marking<br />

In Europe, the European directives require the manufacturer or his authorized<br />

representative to affix the CE marking on his own responsibility. It means that:<br />

b The product meets the legal requirements<br />

b It is presumed to be marketable in Europe<br />

The CE marking is neither a mark <strong>of</strong> origin nor a mark <strong>of</strong> conformity.<br />

Mark <strong>of</strong> conformity<br />

Marks <strong>of</strong> conformity are affixed on appliances and equipment generally used by<br />

ordinary non instructed people (e.g in the field <strong>of</strong> domestic appliances). A mark <strong>of</strong><br />

conformity is delivered by certification body if the equipment meet the requirements<br />

from an applicable standard and after verification <strong>of</strong> the manufacturer’s quality<br />

management system.<br />

Certification <strong>of</strong> Quality<br />

The standards define several methods <strong>of</strong> quality assurance which correspond to<br />

different situations rather than to different levels <strong>of</strong> quality.<br />

Assurance<br />

A laboratory for testing samples cannot certify the conformity <strong>of</strong> an entire production<br />

run: these tests are called type tests. In some tests for conformity to standards,<br />

the samples are destroyed (tests on fuses, for example).<br />

Only the manufacturer can certify that the fabricated products have, in fact,<br />

the characteristics stated.<br />

Quality assurance certification is intended to complete the initial declaration or<br />

certification <strong>of</strong> conformity.<br />

As pro<strong>of</strong> that all the necessary measures have been taken for assuring the quality <strong>of</strong><br />

production, the manufacturer obtains certification <strong>of</strong> the quality control system which<br />

monitors the fabrication <strong>of</strong> the product concerned. These certificates are issued<br />

by organizations specializing in quality control, and are based on the international<br />

standard ISO 9001: 2000.<br />

These standards define three model systems <strong>of</strong> quality assurance control<br />

corresponding to different situations rather than to different levels <strong>of</strong> quality:<br />

b Model 3 defines assurance <strong>of</strong> quality by inspection and checking <strong>of</strong> final products.<br />

b Model 2 includes, in addition to checking <strong>of</strong> the final product, verification <strong>of</strong> the<br />

manufacturing process. For example, this method is applied, to the manufacturer <strong>of</strong><br />

fuses where performance characteristics cannot be checked without destroying the<br />

fuse.<br />

b Model 1 corresponds to model 2, but with the additional requirement that the<br />

quality <strong>of</strong> the <strong>design</strong> process must be rigorously scrutinized; for example, where it is<br />

not intended to fabricate and test a prototype (case <strong>of</strong> a custom-built product made to<br />

specification).<br />

2.8 Environment<br />

Environmental management systems can be certified by an independent body if they<br />

meet requirements given in ISO 14001. This type <strong>of</strong> certification mainly concerns<br />

industrial settings but can also be granted to places where products are <strong>design</strong>ed.<br />

A product environmental <strong>design</strong> sometimes called “eco-<strong>design</strong>” is an approach <strong>of</strong><br />

sustainable development with the objective <strong>of</strong> <strong>design</strong>ing products/services best<br />

meeting the customers’ requirements while reducing their environmental impact<br />

over their whole life cycle. The methodologies used for this purpose lead to choose<br />

equipment’s architecture together with components and materials taking into account<br />

the influence <strong>of</strong> a product on the environment along its life cycle (from extraction <strong>of</strong><br />

raw materials to scrap) i.e. production, transport, distribution, end <strong>of</strong> life etc.<br />

In Europe two Directives have been published, they are called:<br />

b RoHS Directive (Restriction <strong>of</strong> Hazardous Substances) coming into force on<br />

July 2006 (the coming into force was on February 13th , 2003, and the application<br />

date is July 1st , 2006) aims to eliminate from products six hazardous substances:<br />

lead, mercury, cadmium, hexavalent chromium, polybrominated biphenyls (PBB) or<br />

polybrominated diphenyl ethers (PBDE).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

2 Rules and statutory regulations<br />

b WEEE Directive (Waste <strong>of</strong> Electrical and Electronic Equipment) coming into<br />

force in August 2005 (the coming into force was on February 13 th , 2003, and<br />

the application date is August 13 th , 2005) in order to master the end <strong>of</strong> life and<br />

treatments for household and non household equipment.<br />

In other parts <strong>of</strong> the world some new legislation will follow the same objectives.<br />

In addition to manufacturers action in favour <strong>of</strong> products eco-<strong>design</strong>, the contribution<br />

<strong>of</strong> the whole <strong>electrical</strong> <strong>installation</strong> to sustainable development can be significantly<br />

improved through the <strong>design</strong> <strong>of</strong> the <strong>installation</strong>. Actually, it has been shown that an<br />

optimised <strong>design</strong> <strong>of</strong> the <strong>installation</strong>, taking into account operation conditions, MV/LV<br />

substations location and distribution structure (switchboards, busways, cables),<br />

can reduce substantially environmental impacts (raw material depletion, energy<br />

depletion, end <strong>of</strong> life)<br />

See chapter D about location <strong>of</strong> the substation and the main LV switchboard.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A9<br />

© Schneider Electric - all rights reserved


A10<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

An examination <strong>of</strong> the actual apparentpower<br />

demands <strong>of</strong> different loads: a<br />

necessary preliminary step in the <strong>design</strong> <strong>of</strong> a<br />

LV <strong>installation</strong><br />

The nominal power in kW (Pn) <strong>of</strong> a motor<br />

indicates its rated equivalent mechanical power<br />

output.<br />

The apparent power in kVA (Pa) supplied to<br />

the motor is a function <strong>of</strong> the output, the motor<br />

efficiency and the power factor.<br />

Pa = Pn<br />

ηcosϕ 3 Installed power loads -<br />

Characteristics<br />

The examination <strong>of</strong> actual values <strong>of</strong> apparent-power required by each load enables<br />

the establishment <strong>of</strong>:<br />

b A declared power demand which determines the contract for the supply <strong>of</strong> energy<br />

b The rating <strong>of</strong> the MV/LV transformer, where applicable (allowing for expected<br />

increased load)<br />

b Levels <strong>of</strong> load current at each distribution board<br />

3.1 Induction motors<br />

Current demand<br />

The full-load current Ia supplied to the motor is given by the following formulae:<br />

b 3-phase motor: Ia = Pn x 1,000 / (√3 x U x η x cos ϕ)<br />

b 1-phase motor: Ia = Pn x 1,000 / (U x η x cos ϕ)<br />

where<br />

Ia: current demand (in amps)<br />

Pn: nominal power (in kW)<br />

U: voltage between phases for 3-phase motors and voltage between the terminals<br />

for single-phase motors (in volts). A single-phase motor may be connected phase-toneutral<br />

or phase-to-phase.<br />

η: per-unit efficiency, i.e. output kW / input kW<br />

cos ϕ: power factor, i.e. kW input / kVA input<br />

Subtransient current and protection setting<br />

b Subtransient current peak value can be very high ; typical value is about 12<br />

to 15 times the rms rated value Inm. Sometimes this value can reach 25 times Inm.<br />

b Merlin Gerin circuit-breakers, Telemecanique contactors and thermal relays are<br />

<strong>design</strong>ed to withstand motor starts with very high subtransient current (subtransient<br />

peak value can be up to 19 times the rms rated value Inm).<br />

b If unexpected tripping <strong>of</strong> the overcurrent protection occurs during starting, this<br />

means the starting current exceeds the normal limits. As a result, some maximum<br />

switchgear withstands can be reached, life time can be reduced and even some<br />

devices can be destroyed. In order to avoid such a situation, oversizing <strong>of</strong> the<br />

switchgear must be considered.<br />

b Merlin Gerin and Telemecanique switchgears are <strong>design</strong>ed to ensure the<br />

protection <strong>of</strong> motor starters against short-circuits. According to the risk, tables show<br />

the combination <strong>of</strong> circuit-breaker, contactor and thermal relay to obtain type 1 or<br />

type 2 coordination (see chapter N).<br />

Motor starting current<br />

Although high efficiency motors can be found on the market, in practice their starting<br />

currents are roughly the same as some <strong>of</strong> standard motors.<br />

The use <strong>of</strong> start-delta starter, static s<strong>of</strong>t start unit or variable speed drive allows to<br />

reduce the value <strong>of</strong> the starting current (Example : 4 Ia instead <strong>of</strong> 7.5 Ia).<br />

Compensation <strong>of</strong> reactive-power (kvar) supplied to induction motors<br />

It is generally advantageous for technical and financial reasons to reduce the current<br />

supplied to induction motors. This can be achieved by using capacitors without<br />

affecting the power output <strong>of</strong> the motors.<br />

The application <strong>of</strong> this principle to the operation <strong>of</strong> induction motors is generally<br />

referred to as “power-factor improvement” or “power-factor correction”.<br />

As discussed in chapter L, the apparent power (kVA) supplied to an induction motor<br />

can be significantly reduced by the use <strong>of</strong> shunt-connected capacitors. Reduction<br />

<strong>of</strong> input kVA means a corresponding reduction <strong>of</strong> input current (since the voltage<br />

remains constant).<br />

Compensation <strong>of</strong> reactive-power is particularly advised for motors that operate for<br />

long periods at reduced power.<br />

kW input<br />

As noted above cos � = so so that a kVA input reduction in will kVA increase input will<br />

kVA input<br />

increase (i.e. improve) (i.e. improve) the value the <strong>of</strong> cos value ϕ. <strong>of</strong> cos<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

3 Installed power loads -<br />

Characteristics<br />

The current supplied to the motor, after power-factor correction, is given by:<br />

cos �<br />

I=<br />

Ia<br />

cos �'<br />

where cos �ϕ<br />

is the power factor before compensation and cos ϕ’ is the power factor<br />

after compensation, Ia being the original current.<br />

Figure A4 below shows, in function <strong>of</strong> motor rated power, standard motor current<br />

values for several voltage supplies.<br />

kW hp 230 V 380 - 400 V 440 - 500 V 690 V<br />

415 V 480 V<br />

A A A A A A<br />

0.18 - 1.0 - 0.6 - 0.48 0.35<br />

0.25 - 1.5 - 0.85 - 0.68 0.49<br />

0.37 - 1.9 - 1.1 - 0.88 0.64<br />

- 1/2 - 1.3 - 1.1 - -<br />

0.55 - 2.6 - 1.5 - 1.2 0.87<br />

- 3/4 - 1.8 - 1.6 - -<br />

- 1 - 2.3 - 2.1 - -<br />

0.75 - 3.3 - 1.9 - 1.5 1.1<br />

1.1 - 4.7 - 2.7 - 2.2 1.6<br />

- 1-1/2 - 3.3 - 3.0 - -<br />

- 2 - 4.3 - 3.4 - -<br />

1.5 - 6.3 - 3.6 - 2.9 2.1<br />

2.2 - 8.5 - 4.9 - 3.9 2.8<br />

- 3 - 6.1 - 4.8 - -<br />

3.0 - 11.3 - 6.5 - 5.2 3.8<br />

3.7 - - - - - - -<br />

4 - 15 9.7 8.5 7.6 6.8 4.9<br />

5.5 - 20 - 11.5 - 9.2 6.7<br />

- 7-1/2 - 14.0 - 11.0 - -<br />

- 10 - 18.0 - 14.0 - -<br />

7.5 - 27 - 15.5 - 12.4 8.9<br />

11 - 38.0 - 22.0 - 17.6 12.8<br />

- 15 - 27.0 - 21.0 - -<br />

- 20 - 34.0 - 27.0 - -<br />

15 - 51 - 29 - 23 17<br />

18.5 - 61 - 35 - 28 21<br />

- 25 - 44 - 34 -<br />

22 - 72 - 41 - 33 24<br />

- 30 - 51 - 40 - -<br />

- 40 - 66 - 52 - -<br />

30 - 96 - 55 - 44 32<br />

37 - 115 - 66 - 53 39<br />

- 50 - 83 - 65 - -<br />

- 60 - 103 - 77 - -<br />

45 - 140 - 80 - 64 47<br />

55 - 169 - 97 - 78 57<br />

- 75 - 128 - 96 - -<br />

- 100 - 165 - 124 - -<br />

75 - 230 - 132 - 106 77<br />

90 - 278 - 160 - 128 93<br />

- 125 - 208 - 156 - -<br />

110 - 340 - 195 156 113<br />

- 150 - 240 - 180 - -<br />

132 - 400 - 230 - 184 134<br />

- 200 - 320 - 240 - -<br />

150 - - - - - - -<br />

160 - 487 - 280 - 224 162<br />

185 - - - - - - -<br />

- 250 - 403 - 302 - -<br />

200 - 609 - 350 - 280 203<br />

220 - - - - - - -<br />

- 300 - 482 - 361 - -<br />

250 - 748 - 430 - 344 250<br />

280 - - - - - - -<br />

- 350 - 560 - 414 - -<br />

- 400 - 636 - 474 - -<br />

300 - - - - - - -<br />

Fig. A4 : Rated operational power and currents (continued on next page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A11<br />

© Schneider Electric - all rights reserved


A12<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

3 Installed power loads -<br />

Characteristics<br />

kW hp 230 V 380 - 400 V 440 - 500 V 690 V<br />

415 V 480 V<br />

A A A A A A<br />

315 - 940 - 540 - 432 313<br />

- 540 - - - 515 - -<br />

335 - - - - - - -<br />

355 - 1061 - 610 - 488 354<br />

- 500 - 786 - 590 - -<br />

375 - - - - - - -<br />

400 - 1200 - 690 - 552 400<br />

425 - - - - - - -<br />

450 - - - - - - -<br />

475 - - - - - - -<br />

500 - 1478 - 850 - 680 493<br />

530 - - - - - - -<br />

560 - 1652 - 950 - 760 551<br />

600 - - - - - - -<br />

630 - 1844 - 1060 - 848 615<br />

670 - - - - - - -<br />

710 - 2070 - 1190 - 952 690<br />

750 - - - - - - -<br />

800 - 2340 - 1346 - 1076 780<br />

850 - - - - - - -<br />

900 - 2640 - 1518 - 1214 880<br />

950 - - - - - - -<br />

1000 - 2910 - 1673 - 1339 970<br />

Fig. A4 : Rated operational power and currents (concluded)<br />

3.2 Resistive-type heating appliances and<br />

incandescent lamps (conventional or halogen)<br />

The current demand <strong>of</strong> a heating appliance or an incandescent lamp is easily<br />

obtained from the nominal power Pn quoted by the manufacturer (i.e. cos ϕ = 1)<br />

(see Fig. A5).<br />

Fig. A5 : Current demands <strong>of</strong> resistive heating and incandescent lighting (conventional or<br />

halogen) appliances<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Nominal Current demand (A)<br />

power 1-phase 1-phase 3-phase 3-phase<br />

(kW) 127 V 230 V 230 V 400 V<br />

0.1 0.79 0.43 0.25 0.14<br />

0.2 1.58 0.87 0.50 0.29<br />

0.5 3.94 2.17 1.26 0.72<br />

1 7.9 4.35 2.51 1.44<br />

1.5 11.8 6.52 3.77 2.17<br />

2 15.8 8.70 5.02 2.89<br />

2.5 19.7 10.9 6.28 3.61<br />

3 23.6 13 7.53 4.33<br />

3.5 27.6 15.2 8.72 5.05<br />

4 31.5 17.4 10 5.77<br />

4.5 35.4 19.6 11.3 6.5<br />

5 39.4 21.7 12.6 7.22<br />

6 47.2 26.1 15.1 8.66<br />

7 55.1 30.4 17.6 10.1<br />

8 63 34.8 20.1 11.5<br />

9 71 39.1 22.6 13<br />

10 79 43.5 25.1 14.4


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

(1) Ia in amps; U in volts. Pn is in watts. If Pn is in kW, then<br />

multiply the equation by 1,000<br />

(2) “Power-factor correction” is <strong>of</strong>ten referred to as<br />

“compensation” in discharge-lighting-tube terminology.<br />

Cos ϕ is approximately 0.95 (the zero values <strong>of</strong> V and I<br />

are almost in phase) but the power factor is 0.5 due to the<br />

impulsive form <strong>of</strong> the current, the peak <strong>of</strong> which occurs “late”<br />

in each half cycle<br />

3 Installed power loads -<br />

Characteristics<br />

The currents are given by:<br />

b 3-phase case: I a = Pn<br />

3 U<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

(1)<br />

(1)<br />

b 1-phase case: I a = Pn<br />

U<br />

where U is the voltage between the terminals <strong>of</strong> the equipment.<br />

where U is the voltage between the terminals <strong>of</strong> the equipment.<br />

For an incandescent lamp, the use <strong>of</strong> halogen gas allows a more concentrated light<br />

source. The light output is increased and the lifetime <strong>of</strong> the lamp is doubled.<br />

Note: At the instant <strong>of</strong> switching on, the cold filament gives rise to a very brief but<br />

intense peak <strong>of</strong> current.<br />

Fluorescent lamps and related equipment<br />

The power Pn (watts) indicated on the tube <strong>of</strong> a fluorescent lamp does not include<br />

the power dissipated in the ballast.<br />

The current is is given by: by:<br />

P +<br />

I a = ballast Pn<br />

U cos �<br />

If no power-loss value is indicated for the ballast, a figure <strong>of</strong> 25% <strong>of</strong> Pn may be used.<br />

Where U = the voltage applied to the lamp, complete with its related equipment.<br />

If no power-loss value is indicated for the ballast, a figure <strong>of</strong> 25% <strong>of</strong> Pn may be used.<br />

Standard tubular fluorescent lamps<br />

With (unless otherwise indicated):<br />

b cos ϕ = 0.6 with no power factor (PF) correction (2) capacitor<br />

b cos ϕ = 0.86 with PF correction (2) (single or twin tubes)<br />

b cos ϕ = 0.96 for electronic ballast.<br />

If no power-loss value is indicated for the ballast, a figure <strong>of</strong> 25% <strong>of</strong> Pn may be used.<br />

Figure A6 gives these values for different arrangements <strong>of</strong> ballast.<br />

Arrangement Tube power Current (A) at 230 V Tube<br />

<strong>of</strong> lamps, starters (W) (3) Magnetic ballast Electronic length<br />

and ballasts ballast (cm)<br />

Without PF With PF<br />

correction correction<br />

capacitor capacitor<br />

Single tube 18 0.20 0.14 0.10 60<br />

36 0.33 0.23 0.18 120<br />

58 0.50 0.36 0.28 150<br />

Twin tubes 2 x 18 0.28 0.18 60<br />

2 x 36 0.46 0.35 120<br />

2 x 58 0.72 0.52 150<br />

(3) Power in watts marked on tube<br />

Fig. A6 : Current demands and power consumption <strong>of</strong> commonly-dimensioned fluorescent<br />

lighting tubes (at 230 V-50 Hz)<br />

Compact fluorescent lamps<br />

Compact fluorescent lamps have the same characteristics <strong>of</strong> economy and long life<br />

as classical tubes. They are commonly used in public places which are permanently<br />

illuminated (for example: corridors, hallways, bars, etc.) and can be mounted in<br />

situations otherwise illuminated by incandescent lamps (see Fig. A7 next page).<br />

A13<br />

© Schneider Electric - all rights reserved


A14<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

The power in watts indicated on the tube <strong>of</strong><br />

a discharge lamp does not include the power<br />

dissipated in the ballast.<br />

Fig. A8 : Current demands <strong>of</strong> discharge lamps<br />

3 Installed power loads -<br />

Characteristics<br />

Fig. A7 : Current demands and power consumption <strong>of</strong> compact fluorescent lamps (at 230 V - 50 Hz)<br />

Discharge lamps<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Type <strong>of</strong> lamp Lamp power Current at 230 V<br />

(W) (A)<br />

Separated 10 0.080<br />

ballast lamp 18 0.110<br />

26 0.150<br />

Integrated 8 0.075<br />

ballast lamp 11 0.095<br />

16 0.125<br />

21 0.170<br />

Figure A8 gives the current taken by a complete unit, including all associated<br />

ancillary equipment.<br />

These lamps depend on the luminous <strong>electrical</strong> discharge through a gas or vapour<br />

<strong>of</strong> a metallic compound, which is contained in a hermetically-sealed transparent<br />

envelope at a pre-determined pressure. These lamps have a long start-up time,<br />

during which the current Ia is greater than the nominal current In. Power and current<br />

demands are given for different types <strong>of</strong> lamp (typical average values which may<br />

differ slightly from one manufacturer to another).<br />

Type <strong>of</strong> Power Current In(A) Starting Luminous Average Utilization<br />

lamp (W) demand PF not PF Ia/In Period efficiency timelife <strong>of</strong><br />

(W) at corrected corrected (mins) (lumens lamp (h)<br />

230 V 400 V 230 V 400 V 230 V 400 V per watt)<br />

High-pressure sodium vapour lamps<br />

50 60 0.76 0.3 1.4 to 1.6 4 to 6 80 to 120 9000 b Lighting <strong>of</strong><br />

70 80 1 0.45 large halls<br />

100 115 1.2 0.65 b Outdoor spaces<br />

150 168 1.8 0.85 b Public lighting<br />

250 274 3 1.4<br />

400 431 4.4 2.2<br />

1000 1055 10.45 4.9<br />

Low-pressure sodium vapour lamps<br />

26 34.5 0.45 0.17 1.1 to 1.3 7 to 15 100 to 200 8000 b Lighting <strong>of</strong><br />

36 46.5 0.22 to 12000 autoroutes<br />

66 80.5 0.39 b Security lighting,<br />

91 105.5 0.49 station<br />

131 154 0.69 b Platform, storage<br />

areas<br />

Mercury vapour + metal halide (also called metal-iodide)<br />

70 80.5 1 0.40 1.7 3 to 5 70 to 90 6000 b Lighting <strong>of</strong> very<br />

150 172 1.80 0.88 6000 large areas by<br />

250 276 2.10 1.35 6000 projectors (for<br />

400 425 3.40 2.15 6000 example: sports<br />

1000 1046 8.25 5.30 6000 stadiums, etc.)<br />

2000 2092 2052 16.50 8.60 10.50 6 2000<br />

Mercury vapour + fluorescent substance (fluorescent bulb)<br />

50 57 0.6 0.30 1.7 to 2 3 to 6 40 to 60 8000 b Workshops<br />

80 90 0.8 0.45 to 12000 with very high<br />

125 141 1.15 0.70 ceilings (halls,<br />

250 268 2.15 1.35 hangars)<br />

400 421 3.25 2.15 b Outdoor lighting<br />

700 731 5.4 3.85 b Low light output (1)<br />

1000 1046 8.25 5.30<br />

2000 2140 2080 15 11 6.1<br />

(1) Replaced by sodium vapour lamps.<br />

Note: these lamps are sensitive to voltage dips. They extinguish if the voltage falls to less than 50% <strong>of</strong> their nominal voltage, and will<br />

not re-ignite before cooling for approximately 4 minutes.<br />

Note: Sodium vapour low-pressure lamps have a light-output efficiency which is superior to that <strong>of</strong> all other sources. However, use <strong>of</strong><br />

these lamps is restricted by the fact that the yellow-orange colour emitted makes colour recognition practically impossible.


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

The installed power is the sum <strong>of</strong> the nominal<br />

powers <strong>of</strong> all power consuming devices in the<br />

<strong>installation</strong>.<br />

This is not the power to be actually supplied in<br />

practice.<br />

The installed apparent power is commonly<br />

assumed to be the arithmetical sum <strong>of</strong> the kVA<br />

<strong>of</strong> individual loads. The maximum estimated<br />

kVA to be supplied however is not equal to the<br />

total installed kVA.<br />

(1) For greater precision, account must be taken <strong>of</strong> the factor<br />

<strong>of</strong> maximum utilization as explained below in 4.3<br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

In order to <strong>design</strong> an <strong>installation</strong>, the actual maximum load demand likely to be<br />

imposed on the power-supply system must be assessed.<br />

To base the <strong>design</strong> simply on the arithmetic sum <strong>of</strong> all the loads existing in the<br />

<strong>installation</strong> would be extravagantly uneconomical, and bad engineering practice.<br />

The aim <strong>of</strong> this chapter is to show how some factors taking into account the diversity<br />

(non simultaneous operation <strong>of</strong> all appliances <strong>of</strong> a given group) and utilization<br />

(e.g. an electric motor is not generally operated at its full-load capability, etc.) <strong>of</strong><br />

all existing and projected loads can be assessed. The values given are based on<br />

experience and on records taken from actual <strong>installation</strong>s. In addition to providing<br />

basic <strong>installation</strong>-<strong>design</strong> data on individual circuits, the results will provide a<br />

global value for the <strong>installation</strong>, from which the requirements <strong>of</strong> a supply system<br />

(distribution network, MV/LV transformer, or generating set) can be specified.<br />

4.1 Installed power (kW)<br />

Most <strong>electrical</strong> appliances and equipments are marked to indicate their nominal<br />

power rating (Pn).<br />

The installed power is the sum <strong>of</strong> the nominal powers <strong>of</strong> all power-consuming<br />

devices in the <strong>installation</strong>. This is not the power to be actually supplied in practice.<br />

This is the case for electric motors, where the power rating refers to the output power<br />

at its driving shaft. The input power consumption will evidently be greater<br />

Fluorescent and discharge lamps associated with stabilizing ballasts, are other<br />

cases in which the nominal power indicated on the lamp is less than the power<br />

consumed by the lamp and its ballast.<br />

Methods <strong>of</strong> assessing the actual power consumption <strong>of</strong> motors and lighting<br />

appliances are given in Section 3 <strong>of</strong> this <strong>Chapter</strong>.<br />

The power demand (kW) is necessary to choose the rated power <strong>of</strong> a generating set<br />

or battery, and where the requirements <strong>of</strong> a prime mover have to be considered.<br />

For a power supply from a LV public-supply network, or through a MV/LV transformer,<br />

the significant quantity is the apparent power in kVA.<br />

4.2 Installed apparent power (kVA)<br />

The installed apparent power is commonly assumed to be the arithmetical sum <strong>of</strong><br />

the kVA <strong>of</strong> individual loads. The maximum estimated kVA to be supplied however is<br />

not equal to the total installed kVA.<br />

The apparent-power demand <strong>of</strong> a load (which might be a single appliance) is<br />

obtained from its nominal power rating (corrected if necessary, as noted above for<br />

motors, etc.) and the application <strong>of</strong> the following coefficients:<br />

η = the per-unit efficiency = output kW / input kW<br />

cos ϕ = the power factor = kW / kVA<br />

The apparent-power kVA demand <strong>of</strong> the load<br />

Pa = Pn /(η x cos ϕ)<br />

From this value, the full-load current Ia (A) (1) From this value, the full-load current taken by the load will be:<br />

3<br />

Pa x 10<br />

cb Ia =<br />

V<br />

for<br />

From<br />

single phase-to-neutral connected load<br />

for single this phase-to-neutral value, the full-load connected current load<br />

Pa x 103<br />

c b Ia =<br />

3 x U<br />

for<br />

for three-phase<br />

single phase-to-neutral<br />

balanced load<br />

connected<br />

where:<br />

load<br />

V = phase-to-neutral voltage (volts)<br />

U = phase-to-phase voltage (volts)<br />

It may be noted that, strictly speaking, the total kVA <strong>of</strong> apparent power is not the<br />

arithmetical sum <strong>of</strong> the calculated kVA ratings <strong>of</strong> individual loads (unless all loads are<br />

at the same power factor).<br />

It is common practice however, to make a simple arithmetical summation, the result<br />

<strong>of</strong> which will give a kVA value that exceeds the true value by an acceptable “<strong>design</strong><br />

margin”.<br />

When some or all <strong>of</strong> the load characteristics are not known, the values shown<br />

in Figure A9 next page may be used to give a very approximate estimate <strong>of</strong> VA<br />

demands (individual loads are generally too small to be expressed in kVA or kW).<br />

The estimates for lighting loads are based on floor areas <strong>of</strong> 500 m2 .<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A15<br />

© Schneider Electric - all rights reserved


A16<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

Fluorescent lighting (corrected to cos ϕ = 0.86)<br />

Type <strong>of</strong> application Estimated (VA/m 2 ) Average lighting<br />

fluorescent tube level (lux = lm/m 2 )<br />

with industrial reflector (1)<br />

Roads and highways 7 150<br />

storage areas, intermittent work<br />

Heavy-duty works: fabrication and 14 300<br />

assembly <strong>of</strong> very large work pieces<br />

Day-to-day work: <strong>of</strong>fice work 24 500<br />

Fine work: drawing <strong>of</strong>fices 41 800<br />

high-precision assembly workshops<br />

Power circuits<br />

Type <strong>of</strong> application Estimated (VA/m 2 )<br />

Pumping station compressed air 3 to 6<br />

Ventilation <strong>of</strong> premises 23<br />

Electrical convection heaters:<br />

private houses 115 to 146<br />

flats and apartments 90<br />

Offices 25<br />

Dispatching workshop 50<br />

Assembly workshop 70<br />

Machine shop 300<br />

Painting workshop 350<br />

Heat-treatment plant 700<br />

(1) example: 65 W tube (ballast not included), flux 5,100 lumens (Im),<br />

luminous efficiency <strong>of</strong> the tube = 78.5 Im / W.<br />

Fig. A9 : Estimation <strong>of</strong> installed apparent power<br />

4.3 Estimation <strong>of</strong> actual maximum kVA demand<br />

All individual loads are not necessarily operating at full rated nominal power nor<br />

necessarily at the same time. Factors ku and ks allow the determination <strong>of</strong> the<br />

maximum power and apparent-power demands actually required to dimension the<br />

<strong>installation</strong>.<br />

Factor <strong>of</strong> maximum utilization (ku)<br />

In normal operating conditions the power consumption <strong>of</strong> a load is sometimes less<br />

than that indicated as its nominal power rating, a fairly common occurrence that<br />

justifies the application <strong>of</strong> an utilization factor (ku) in the estimation <strong>of</strong> realistic values.<br />

This factor must be applied to each individual load, with particular attention to<br />

electric motors, which are very rarely operated at full load.<br />

In an industrial <strong>installation</strong> this factor may be estimated on an average at 0.75 for<br />

motors.<br />

For incandescent-lighting loads, the factor always equals 1.<br />

For socket-outlet circuits, the factors depend entirely on the type <strong>of</strong> appliances being<br />

supplied from the sockets concerned.<br />

Factor <strong>of</strong> simultaneity (ks)<br />

It is a matter <strong>of</strong> common experience that the simultaneous operation <strong>of</strong> all installed<br />

loads <strong>of</strong> a given <strong>installation</strong> never occurs in practice, i.e. there is always some degree<br />

<strong>of</strong> diversity and this fact is taken into account for estimating purposes by the use <strong>of</strong> a<br />

simultaneity factor (ks).<br />

The factor ks is applied to each group <strong>of</strong> loads (e.g. being supplied from a distribution<br />

or sub-distribution board). The determination <strong>of</strong> these factors is the responsibility<br />

<strong>of</strong> the <strong>design</strong>er, since it requires a detailed knowledge <strong>of</strong> the <strong>installation</strong> and the<br />

conditions in which the individual circuits are to be exploited. For this reason, it is not<br />

possible to give precise values for general application.<br />

Factor <strong>of</strong> simultaneity for an apartment block<br />

Some typical values for this case are given in Figure A10 opposite page, and are<br />

applicable to domestic consumers supplied at 230/400 V (3-phase 4-wires). In the<br />

case <strong>of</strong> consumers using <strong>electrical</strong> heat-storage units for space heating, a factor <strong>of</strong><br />

0.8 is recommended, regardless <strong>of</strong> the number <strong>of</strong> consumers.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

Example (see Fig. A11):<br />

5 storeys apartment building with 25 consumers, each having 6 kVA <strong>of</strong> installed load.<br />

The total installed load for the building is: 36 + 24 + 30 + 36 + 24 = 150 kVA<br />

The apparent-power supply required for the building is: 150 x 0.46 = 69 kVA<br />

From Figure A10, it is possible to determine the magnitude <strong>of</strong> currents in different<br />

sections <strong>of</strong> the common main feeder supplying all floors. For vertical rising mains<br />

fed at ground level, the cross-sectional area <strong>of</strong> the conductors can evidently be<br />

progressively reduced from the lower floors towards the upper floors.<br />

These changes <strong>of</strong> conductor size are conventionally spaced by at least 3-floor<br />

intervals.<br />

In the example, the current entering the rising main at ground level is:<br />

3<br />

150 x 0.46 x 10<br />

= 100 A<br />

400 3<br />

the current entering the third floor is:<br />

3<br />

(36 + 24) x 0.63 x 10<br />

= 55 A<br />

400 3<br />

4th<br />

floor<br />

3 rd<br />

floor<br />

2nd<br />

floor<br />

1 st<br />

floor<br />

ground<br />

floor<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Number <strong>of</strong> downstream Factor <strong>of</strong><br />

consumers simultaneity (ks)<br />

2 to 4 1<br />

5 to 9 0.78<br />

10 to 14 0.63<br />

15 to 19 0.53<br />

20 to 24 0.49<br />

25 to 29 0.46<br />

30 to 34 0.44<br />

35 to 39 0.42<br />

40 to 49 0.41<br />

50 and more 0.40<br />

Fig. A10 : Simultaneity factors in an apartment block<br />

6 consumers<br />

36 kVA<br />

4 consumers<br />

24 kVA<br />

5 consumers<br />

30 kVA<br />

6 consumers<br />

36 kVA<br />

4 consumers<br />

24 kVA<br />

0.78<br />

0.63<br />

0.53<br />

0.49<br />

0.46<br />

Fig. A11 : Application <strong>of</strong> the factor <strong>of</strong> simultaneity (ks) to an apartment block <strong>of</strong> 5 storeys<br />

A17<br />

© Schneider Electric - all rights reserved


A18<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

Factor <strong>of</strong> simultaneity for distribution boards<br />

Figure A12 shows hypothetical values <strong>of</strong> ks for a distribution board supplying a<br />

number <strong>of</strong> circuits for which there is no indication <strong>of</strong> the manner in which the total<br />

load divides between them.<br />

If the circuits are mainly for lighting loads, it is prudent to adopt ks values close to<br />

unity.<br />

Fig. A12 : Factor <strong>of</strong> simultaneity for distribution boards (IEC 60439)<br />

Circuit function Factor <strong>of</strong> simultaneity (ks)<br />

Lighting 1<br />

Heating and air conditioning 1<br />

Socket-outlets 0.1 to 0.2 (1)<br />

Lifts and catering hoist (2) b For the most powerful<br />

motor 1<br />

b For the second most<br />

powerful motor 0.75<br />

b For all motors 0.60<br />

(1) In certain cases, notably in industrial <strong>installation</strong>s, this factor can be higher.<br />

(2) The current to take into consideration is equal to the nominal current <strong>of</strong> the motor,<br />

increased by a third <strong>of</strong> its starting current.<br />

Fig. A13 : Factor <strong>of</strong> simultaneity according to circuit function<br />

4.4 Example <strong>of</strong> application <strong>of</strong> factors ku and ks<br />

An example in the estimation <strong>of</strong> actual maximum kVA demands at all levels <strong>of</strong> an<br />

<strong>installation</strong>, from each load position to the point <strong>of</strong> supply is given Fig. A14 (opposite<br />

page).<br />

In this example, the total installed apparent power is 126.6 kVA, which corresponds<br />

to an actual (estimated) maximum value at the LV terminals <strong>of</strong> the MV/LV transformer<br />

<strong>of</strong> 65 kVA only.<br />

Note: in order to select cable sizes for the distribution circuits <strong>of</strong> an <strong>installation</strong>, the<br />

current I (in amps) through a circuit is determined from the equation:<br />

I = kVA x 10<br />

U<br />

3<br />

3<br />

where kVA is the actual maximum 3-phase apparent-power value shown on the<br />

diagram for the circuit concerned, and U is the phase to- phase voltage (in volts).<br />

4.5 Diversity factor<br />

The term diversity factor, as defined in IEC standards, is identical to the factor <strong>of</strong><br />

simultaneity (ks) used in this guide, as described in 4.3. In some English-speaking<br />

countries however (at the time <strong>of</strong> writing) diversity factor is the inverse <strong>of</strong> ks i.e. it is<br />

always u 1.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Number <strong>of</strong> Factor <strong>of</strong><br />

circuits simultaneity (ks)<br />

Assemblies entirely tested 0.9<br />

2 and 3<br />

4 and 5 0.8<br />

6 to 9 0.7<br />

10 and more 0.6<br />

Assemblies partially tested 1.0<br />

in every case choose<br />

Factor <strong>of</strong> simultaneity according to circuit function<br />

ks factors which may be used for circuits supplying commonly-occurring loads, are<br />

shown in Figure A13.


A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

Workshop A Lathe no. 1 5 0.8<br />

Pedestaldrill<br />

30 fluorescent<br />

lamps<br />

Workshop B Compressor<br />

Oven<br />

no. 2<br />

no. 3<br />

no. 4<br />

no. 1<br />

no. 2<br />

5 socketoutlets<br />

10/16 A<br />

3 socketoutlets<br />

10/16 A<br />

10 fluorescent<br />

lamps<br />

Workshop C Ventilation no. 1<br />

no. 2<br />

no. 1<br />

no. 2<br />

5 socketoutlets<br />

10/16 A<br />

20 fluorescent<br />

lamps<br />

5<br />

5<br />

5<br />

2<br />

2<br />

18<br />

0.8<br />

0.8<br />

0.8<br />

0.8<br />

0.8<br />

1<br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

Distribution<br />

box<br />

3 1 3<br />

1<br />

15<br />

10.6<br />

1<br />

2.5<br />

2.5<br />

15<br />

15<br />

18<br />

2<br />

1<br />

0.8<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

1<br />

4<br />

4<br />

4<br />

4<br />

1.6<br />

1.6<br />

18<br />

12<br />

10.6<br />

1<br />

2.5<br />

2.5<br />

15<br />

15<br />

18<br />

2<br />

Fig A14 : An example in estimating the maximum predicted loading <strong>of</strong> an <strong>installation</strong> (the factor values used are for demonstration purposes only)<br />

0.75<br />

0.2<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1<br />

0.4<br />

1<br />

Distribution<br />

box<br />

1<br />

0.28<br />

1<br />

Level 1 Level 2 Level 3<br />

Utilization Apparent Utilization Apparent Simultaneity Apparent Simultaneity Apparent Simultaneity Apparent<br />

power factor power factor power factor power factor power<br />

(Pa) max. demand demand demand demand<br />

kVA max. kVA kVA kVA kVA<br />

14.4<br />

3.6<br />

3<br />

Power<br />

circuit<br />

Socketoulets<br />

Lighting<br />

circuit<br />

Powver<br />

circuit<br />

Workshop A<br />

distribution<br />

box<br />

Power<br />

circuit<br />

12 Workshop B<br />

Socketoulets<br />

distribution<br />

4.3 box<br />

1<br />

35<br />

5<br />

2<br />

Lighting<br />

circuit<br />

Socketoulets<br />

Lighting<br />

circuit<br />

0.9<br />

0.9<br />

Workshop C<br />

distribution<br />

box<br />

0.9<br />

18.9<br />

15.6<br />

37.8<br />

4.6 Choice <strong>of</strong> transformer rating<br />

Main<br />

general<br />

distribution<br />

board<br />

MGDB<br />

0.9<br />

65<br />

LV / MV<br />

When an <strong>installation</strong> is to be supplied directly from a MV/LV transformer and<br />

the maximum apparent-power loading <strong>of</strong> the <strong>installation</strong> has been determined, a<br />

suitable rating for the transformer can be decided, taking into account the following<br />

considerations (see Fig. A15):<br />

b The possibility <strong>of</strong> improving the power factor <strong>of</strong> the <strong>installation</strong> (see chapter L)<br />

b Anticipated extensions to the <strong>installation</strong><br />

b Installation constraints (e.g. temperature)<br />

b Standard transformer ratings<br />

Apparent power In (A)<br />

kVA 237 V 410 V<br />

100 244 141<br />

160 390 225<br />

250 609 352<br />

315 767 444<br />

400 974 563<br />

500 1218 704<br />

630 1535 887<br />

800 1949 1127<br />

1000 2436 1408<br />

1250 3045 1760<br />

1600 3898 2253<br />

2000 4872 2816<br />

2500 6090 3520<br />

3150 7673 4436<br />

Fig. A15 : Standard apparent powers for MV/LV transformers and related nominal output currents<br />

A19<br />

© Schneider Electric - all rights reserved


A20<br />

© Schneider Electric - all rights reserved<br />

A - <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong><br />

4 Power loading <strong>of</strong> an <strong>installation</strong><br />

The nominal full-load current In on the LV side <strong>of</strong> a 3-phase transformer is given by:<br />

a x 10<br />

In<br />

3<br />

= P<br />

U 3<br />

where<br />

b Pa = kVA rating <strong>of</strong> the transformer<br />

b U = phase-to-phase voltage at no-load in volts (237 V or 410 V)<br />

b In is in amperes.<br />

For a single-phase transformer:<br />

a x 10<br />

In<br />

3<br />

= P<br />

V<br />

where<br />

where<br />

b V = voltage between LV terminals at no-load (in volts)<br />

Simplified equation for 400 V (3-phase load)<br />

b In = kVA x 1.4<br />

The IEC standard for power transformers is IEC 60076.<br />

4.7 Choice <strong>of</strong> power-supply sources<br />

The importance <strong>of</strong> maintaining a continuous supply raises the question <strong>of</strong> the use <strong>of</strong><br />

standby-power plant. The choice and characteristics <strong>of</strong> these alternative sources are<br />

part <strong>of</strong> the architecture selection, as described in chapter D.<br />

For the main source <strong>of</strong> supply the choice is generally between a connection to the<br />

MV or the LV network <strong>of</strong> the power-supply utility.<br />

In practice, connection to a MV source may be necessary where the load exceeds<br />

(or is planned eventually to exceed) a certain level - generally <strong>of</strong> the order <strong>of</strong><br />

250 kVA, or if the quality <strong>of</strong> service required is greater than that normally available<br />

from a LV network.<br />

Moreover, if the <strong>installation</strong> is likely to cause disturbance to neighbouring consumers,<br />

when connected to a LV network, the supply authorities may propose a MV service.<br />

Supplies at MV can have certain advantages: in fact, a MV consumer:<br />

b Is not disturbed by other consumers, which could be the case at LV<br />

b Is free to choose any type <strong>of</strong> LV earthing system<br />

b Has a wider choice <strong>of</strong> economic tariffs<br />

b Can accept very large increases in load<br />

It should be noted, however, that:<br />

b The consumer is the owner <strong>of</strong> the MV/LV substation and, in some countries,<br />

he must build and equip it at his own expense. The power utility can, in certain<br />

circumstances, participate in the investment, at the level <strong>of</strong> the MV line for example<br />

b A part <strong>of</strong> the connection costs can, for instance, <strong>of</strong>ten be recovered if a second<br />

consumer is connected to the MV line within a certain time following the original<br />

consumer’s own connection<br />

b The consumer has access only to the LV part <strong>of</strong> the <strong>installation</strong>, access to the<br />

MV part being reserved to the utility personnel (meter reading, operations, etc.).<br />

However, in certain countries, the MV protective circuit-breaker (or fused load-break<br />

switch) can be operated by the consumer<br />

b The type and location <strong>of</strong> the substation are agreed between the consumer and<br />

the utility<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


2<br />

3<br />

4<br />

5<br />

6<br />

<strong>Chapter</strong> B<br />

Connection to the MV utility<br />

distribution network<br />

Contents<br />

Supply <strong>of</strong> power at medium voltage B2<br />

1.1 Power supply characteristics <strong>of</strong> medium voltage B2<br />

utility distribution network<br />

1.2 Different MV service connections B11<br />

1.3 Some operational aspects <strong>of</strong> MV distribution networks B12<br />

Procedure for the establishment <strong>of</strong> a new substation B 4<br />

2.1 Preliminary informations B14<br />

2.2 Project studies B15<br />

2.3 Implementation B15<br />

2.4 Commissioning B15<br />

Protection aspect B 6<br />

3.1 Protection against electric shocks B16<br />

3.2 Protection <strong>of</strong> transformer and circuits B17<br />

3.3 Interlocks and conditioned operations B19<br />

The consumer substation with LV metering B22<br />

4.1 <strong>General</strong> B22<br />

4.2 Choice <strong>of</strong> MV switchgear B22<br />

4.3 Choice <strong>of</strong> MV switchgear panel for a transformer circuit B25<br />

4.4 Choice <strong>of</strong> MV/LV transformer B25<br />

4.5 Instructions for use <strong>of</strong> MV equipment B29<br />

The consumer substation with MV metering B32<br />

5.1 <strong>General</strong> B32<br />

5.2 Choice <strong>of</strong> panels B34<br />

5.3 Parallel operation <strong>of</strong> transformers B35<br />

Constitution <strong>of</strong> MV/LV distribution substations B37<br />

6.1 Different types <strong>of</strong> substation B37<br />

6.2 Indoor substation B37<br />

6.3 Outdoor substation B39<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

B2<br />

B - Connection to the MV public<br />

distribution network<br />

The main features which characterize a powersupply<br />

system include:<br />

b The nominal voltage and related insulation<br />

levels<br />

b The short-circuit current<br />

b The rated normal current <strong>of</strong> items <strong>of</strong> plant<br />

and equipment<br />

b The earthing system<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

The term "medium voltage" is commonly used for distribution systems with voltages<br />

above 1 kV and generally applied up to and including 52 kV (see IEC 601-01-28<br />

Standard).<br />

In this chapter, distribution networks which operate at voltages <strong>of</strong> 1,000 V or less<br />

are referred to as Low-Voltage systems, while systems <strong>of</strong> power distribution which<br />

require one stage <strong>of</strong> stepdown voltage transformation, in order to feed into low voltage<br />

networks, will be referred to as Medium- Voltage systems.<br />

For economic and technical reasons the nominal voltage <strong>of</strong> medium-voltage<br />

distribution systems, as defined above, seldom exceeds 35 kV.<br />

. Power supply characteristics <strong>of</strong> medium voltage<br />

utility distribution network<br />

Nominal voltage and related insulation levels<br />

The nominal voltage <strong>of</strong> a system or <strong>of</strong> an equipment is defined in IEC 60038 Standard<br />

as “the voltage by which a system or equipment is <strong>design</strong>ated and to which certain<br />

operating characteristics are referred”. Closely related to the nominal voltage is the<br />

“highest voltage for equipment” which concerns the level <strong>of</strong> insulation at normal<br />

working frequency, and to which other characteristics may be referred in relevant<br />

equipment recommendations.<br />

The “highest voltage for equipment” is defined in IEC 60038 Standard as:<br />

“the maximum value <strong>of</strong> voltage for which equipment may be used, that occurs under<br />

normal operating conditions at any time and at any point on the system. It excludes<br />

voltage transients, such as those due to system switching, and temporary voltage<br />

variations”.<br />

Notes:<br />

- The highest voltage for equipment is indicated for nominal system voltages<br />

higher than 1,000 V only. It is understood that, particularly for some categories<br />

<strong>of</strong> equipment, normal operation cannot be ensured up to this "highest voltage for<br />

equipment", having regard to voltage sensitive characteristics such as losses <strong>of</strong><br />

capacitors, magnetizing current <strong>of</strong> transformers, etc. In such cases, IEC standards<br />

specify the limit to which the normal operation <strong>of</strong> this equipment can be ensured.<br />

2- It is understood that the equipment to be used in systems having nominal voltage<br />

not exceeding 1,000 V should be specified with reference to the nominal system<br />

voltage only, both for operation and for insulation.<br />

3- The definition for “highest voltage for equipment” given in IEC 60038 Standard<br />

is identical to the definition given in IEC 62271-1 Standard for “rated voltage”.<br />

IEC 62271-1 Standard concerns switchgear for voltages exceeding 1,000 V.<br />

The following values <strong>of</strong> Figure B , taken from IEC 60038 Standard, list the<br />

most-commonly used standard levels <strong>of</strong> medium-voltage distribution, and relate<br />

the nominal voltages to corresponding standard values <strong>of</strong> “Highest Voltage for<br />

Equipment”.<br />

These systems are generally three-wire systems unless otherwise indicated. The<br />

values shown are voltages between phases.<br />

The values indicated in parentheses should be considered as non-preferred values.<br />

It is recommended that these values should not be used for new systems to be<br />

constructed in future.<br />

It is recommended that in any one country the ratio between two adjacent nominal<br />

voltages should be not less than two.<br />

Series I (for 50 Hz and 60 Hz networks)<br />

Nominal system voltage Highest voltage for equipement<br />

(kV) (kV)<br />

3.3 (1) 3 (1) 3.6 (1)<br />

6.6 (1) 6 (1) 7.2 (1)<br />

11 10 12<br />

- 15 17.5<br />

22 20 24<br />

33 (2) - 36 (2)<br />

- 35 (2) 40.5 (2)<br />

(1) These values should not be used for public distribution systems.<br />

(2) The unification <strong>of</strong> these values is under consideration.<br />

Fig. B1 : Relation between nominal system voltages and highest voltages for the equipment<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

(1) This means basically that List 1 generally applies to<br />

switchgear to be used on underground-cable systems while<br />

List 2 is chosen for switchgear to be used on overhead-line<br />

systems.<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

In order to ensure adequate protection <strong>of</strong> equipment against abnormally-medium<br />

short term power-frequency overvoltages, and transient overvoltages caused by<br />

lightning, switching, and system fault conditions, etc. all MV equipment must be<br />

specified to have appropriate rated insulation levels.<br />

A "rated insulation level" is a set <strong>of</strong> specified dielectric withstand values covering<br />

various operating conditions. For MV equipment, in addition to the "highest voltage<br />

for equipment", it includes lightning impulse withstand and short-duration power<br />

frequency withstand.<br />

Switchgear<br />

Figure B2 shown below, lists normal values <strong>of</strong> “withstand” voltage requirements<br />

from IEC 62271-1 Standard. The choice between List 1 and List 2 values <strong>of</strong> table<br />

B2 depends on the degree <strong>of</strong> exposure to lightning and switching overvoltages (1) ,<br />

the type <strong>of</strong> neutral earthing, and the type <strong>of</strong> overvoltage protection devices, etc. (for<br />

further guidance reference should be made to IEC 60071).<br />

Rated Rated lightning impulse withstand voltage Rated short-duration<br />

voltage (peak value) power-frequency<br />

U (r.m.s. withstand voltage<br />

value) List List 2 (r.m.s. value)<br />

To earth, Across the To earth, Across the To earth, Across the<br />

between isolating between isolating between isolating<br />

poles distance poles distance poles distance<br />

and across and across and across<br />

open open open<br />

switching switching switching<br />

device device device<br />

(kV) (kV) (kV) (kV) (kV) (kV) (kV)<br />

3.6 20 23 40 46 10 12<br />

7.2 40 46 60 70 20 23<br />

12 60 70 75 85 28 32<br />

17.5 75 85 95 110 38 45<br />

24 95 110 125 145 50 60<br />

36 145 165 170 195 70 80<br />

52 - - 250 290 95 110<br />

72.5 - - 325 375 140 160<br />

Note: The withstand voltage values “across the isolating distance” are valid only for<br />

the switching devices where the clearance between open contacts is <strong>design</strong>ed to meet<br />

requirements specified for disconnectors (isolators).<br />

Fig. B2 : Switchgear rated insulation levels<br />

It should be noted that, at the voltage levels in question, no switching overvoltage<br />

ratings are mentioned. This is because overvoltages due to switching transients are<br />

less severe at these voltage levels than those due to lightning.<br />

Transformers<br />

Figure B3 shown below have been extracted from IEC 60076-3.<br />

The significance <strong>of</strong> list 1 and list 2 is the same as that for the switchgear table, i.e.<br />

the choice depends on the degree <strong>of</strong> exposure to lightning, etc.<br />

Highest voltage Rated short duration Rated lightning impulse<br />

for equipment power frequency withstand voltage<br />

(r.m.s.) withstand voltage (peak)<br />

(r.m.s.) List List 2<br />

(kV) (kV) (kV) (kV)<br />

y 1.1 3 - -<br />

3.6 10 20 40<br />

7.2 20 40 60<br />

12 28 60 75<br />

17.5 38 75 95<br />

24 50 95 125<br />

36 70 145 170<br />

52 95 250<br />

72.5 140 325<br />

Fig. B3 : Transformers rated insulation levels<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

B4<br />

B - Connection to the MV public<br />

distribution network<br />

The national standards <strong>of</strong> any particular country<br />

are normally rationalized to include one or two<br />

levels only <strong>of</strong> voltage, current, and fault-levels,<br />

etc.<br />

A circuit-breaker (or fuse switch, over a limited<br />

voltage range) is the only form <strong>of</strong> switchgear<br />

capable <strong>of</strong> safely breaking all kinds <strong>of</strong> fault<br />

currents occurring on a power system.<br />

I p<br />

Current (I)<br />

22I'' k<br />

t min<br />

22I b<br />

IDC 22Ik Time (t)<br />

Fig. B5 : Graphic representation <strong>of</strong> short-circuit quantities as<br />

per IEC 60909<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Other components<br />

It is evident that the insulation performance <strong>of</strong> other MV components associated<br />

with these major items, e.g. porcelain or glass insulators, MV cables, instrument<br />

transformers, etc. must be compatible with that <strong>of</strong> the switchgear and<br />

transformers noted above. Test schedules for these items are given in appropriate<br />

IEC publications.<br />

The national standards <strong>of</strong> any particular country are normally rationalized to include<br />

one or two levels only <strong>of</strong> voltage, current, and fault-levels, etc.<br />

<strong>General</strong> note:<br />

The IEC standards are intended for worldwide application and consequently<br />

embrace an extensive range <strong>of</strong> voltage and current levels.<br />

These reflect the diverse practices adopted in countries <strong>of</strong> different meteorologic,<br />

geographic and economic constraints.<br />

Short-circuit current<br />

Standard values <strong>of</strong> circuit-breaker short-circuit current-breaking capability are<br />

normally given in kilo-amps.<br />

These values refer to a 3-phase short-circuit condition, and are expressed as the<br />

average <strong>of</strong> the r.m.s. values <strong>of</strong> the AC component <strong>of</strong> current in each <strong>of</strong> the three<br />

phases.<br />

For circuit-breakers in the rated voltage ranges being considered in this chapter,<br />

Figure B4 gives standard short-circuit current-breaking ratings.<br />

kV 3.6 7.2 2 7.5 24 36 52<br />

kA 8 8 8 8 8 8 8<br />

(rms) 10 12.5 12.5 12.5 12.5 12.5 12.5<br />

16 16 16 16 16 16 20<br />

25 25 25 25 25 25<br />

40 40 40 40 40 40<br />

50<br />

Fig. B4 : Standard short-circuit current-breaking ratings<br />

Short-circuit current calculation<br />

The <strong>rules</strong> for calculating short-circuit currents in <strong>electrical</strong> <strong>installation</strong>s are presented<br />

in IEC standard 60909.<br />

The calculation <strong>of</strong> short-circuit currents at various points in a power system can<br />

quickly turn into an arduous task when the <strong>installation</strong> is complicated.<br />

The use <strong>of</strong> specialized s<strong>of</strong>tware accelerates calculations.<br />

This general standard, applicable for all radial and meshed power systems, 50 or<br />

60 Hz and up to 550 kV, is extremely accurate and conservative.<br />

It may be used to handle the different types <strong>of</strong> solid short-circuit (symmetrical or<br />

dissymmetrical) that can occur in an <strong>electrical</strong> <strong>installation</strong>:<br />

b Three-phase short-circuit (all three phases), generally the type producing the<br />

highest currents<br />

b Two-phase short-circuit (between two phases), currents lower than three-phase faults<br />

b Two-phase-to-earth short-circuit (between two phases and earth)<br />

b Phase-to-earth short-circuit (between a phase and earth), the most frequent type<br />

(80% <strong>of</strong> all cases).<br />

When a fault occurs, the transient short-circuit current is a function <strong>of</strong> time and<br />

comprises two components (see Fig. B5).<br />

b An AC component, decreasing to its steady-state value, caused by the various<br />

rotating machines and a function <strong>of</strong> the combination <strong>of</strong> their time constants<br />

b A DC component, decreasing to zero, caused by the initiation <strong>of</strong> the current and a<br />

function <strong>of</strong> the circuit impedances<br />

Practically speaking, one must define the short-circuit values that are useful in<br />

selecting system equipment and the protection system:<br />

b I’’ k: rms value <strong>of</strong> the initial symmetrical current<br />

b Ib: rms value <strong>of</strong> the symmetrical current interrupted by the switching device when<br />

the first pole opens at tmin (minimum delay)<br />

b Ik: rms value <strong>of</strong> the steady-state symmetrical current<br />

b Ip: maximum instantaneous value <strong>of</strong> the current at the first peak<br />

b IDC: DC value <strong>of</strong> the current<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

These currents are identified by subscripts 3, 2, 2E, 1, depending on the type <strong>of</strong><br />

short-circuit, respectively three-phase, two-phase clear <strong>of</strong> earth, two-phase-to-earth,<br />

phase-to-earth.<br />

The method, based on the Thevenin superposition theorem and decomposition into<br />

symmetrical components, consists in applying to the short-circuit point an equivalent<br />

source <strong>of</strong> voltage in view <strong>of</strong> determining the current. The calculation takes place in<br />

three steps.<br />

b Define the equivalent source <strong>of</strong> voltage applied to the fault point. It represents the<br />

voltage existing just before the fault and is the rated voltage multiplied by a factor<br />

taking into account source variations, transformer on-load tap changers and the<br />

subtransient behavior <strong>of</strong> the machines.<br />

b Calculate the impedances, as seen from the fault point, <strong>of</strong> each branch arriving at<br />

this point. For positive and negative-sequence systems, the calculation does not take<br />

into account line capacitances and the admittances <strong>of</strong> parallel, non-rotating loads.<br />

b Once the voltage and impedance values are defined, calculate the characteristic<br />

minimum and maximum values <strong>of</strong> the short-circuit currents.<br />

The various current values at the fault point are calculated using:<br />

b The equations provided<br />

b A summing law for the currents flowing in the branches connected to the node:<br />

v I’’ k (see Fig. B6 for I’’ k calculation, where voltage factor c is defined by the<br />

standard; geometric or algebraic summing)<br />

v I p = κ x 2 x I’’ k, where κ is less than 2, depending on the R/X ratio <strong>of</strong> the positive<br />

sequence impedance for the given branch; peak summing<br />

v I b = μ x q x I’’ k, where μ and q are less than 1, depending on the generators and<br />

motors, and the minimum current interruption delay; algebraic summing<br />

v I k = I’’ k, when the fault is far from the generator<br />

v I k = λ x I r, for a generator, where Ir is the rated generator current and λ is a factor<br />

depending on its saturation inductance; algebraic summing.<br />

Type <strong>of</strong> short-circuit I’’ k<br />

<strong>General</strong> situation Distant faults<br />

3-phase<br />

2-phase<br />

2-phase-to-earth<br />

Phase-to-earth + 0 + 1 0<br />

Fig. B6 : Short-circuit currents as per IEC 60909<br />

Characterization<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

c Un<br />

3 Z1 c Un<br />

Z1 + Z2<br />

c Un 3 Z2<br />

Z1 Z2 + Z2 Z0 + Z1 Z0<br />

c Un 3<br />

Z1<br />

+Z +Z 2 0<br />

c Un<br />

3 Z1 c Un<br />

2Z1<br />

c Un 3<br />

1 + Z 2Z0 c Un 3<br />

2 Z1 + Z0<br />

There are 2 types <strong>of</strong> system equipment, based on whether or not they react when a<br />

fault occurs.<br />

Passive equipment<br />

This category comprises all equipment which, due to its function, must have<br />

the capacity to transport both normal current and short-circuit current.<br />

This equipment includes cables, lines, busbars, disconnecting switches, switches,<br />

transformers, series reactances and capacitors, instrument transformers.<br />

For this equipment, the capacity to withstand a short-circuit without damage<br />

is defined in terms <strong>of</strong>:<br />

b Electrodynamic withstand (“peak withstand current”; value <strong>of</strong> the peak current<br />

expressed in kA), characterizing mechanical resistance to electrodynamic stress<br />

b Thermal withstand (“short time withstand current”; rms value expressed in kA<br />

for duration between 0,5 and 3 seconds, with a preferred value <strong>of</strong> 1 second),<br />

characterizing maximum permissible heat dissipation.<br />

B5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

B6<br />

B - Connection to the MV public<br />

distribution network<br />

Current (I)<br />

I AC<br />

I DC<br />

I AC : Peak <strong>of</strong> the periodic component<br />

I DC : Aperiodic component<br />

Time (t)<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Active equipment<br />

This category comprises the equipment <strong>design</strong>ed to clear short-circuit currents, i.e.<br />

circuit-breakers and fuses. This property is expressed by the breaking capacity and,<br />

if required, the making capacity when a fault occurs.<br />

b Breaking capacity (see Fig. B7)<br />

This basic characteristic <strong>of</strong> a fault interrupting device is the maximum current (rms<br />

value expressed in kA) it is capable <strong>of</strong> breaking under the specific conditions defined<br />

by the standards; in the IEC 62271-100 standard, it refers to the rms value <strong>of</strong> the<br />

AC component <strong>of</strong> the short-circuit current. In some other standards, the rms value<br />

<strong>of</strong> the sum <strong>of</strong> the 2 components (AC and DC) is specified, in which case, it is the<br />

“asymmetrical current”.<br />

The breaking capacity depends on other factors such as:<br />

v Voltage<br />

v R/X ratio <strong>of</strong> the interrupted circuit<br />

v Power system natural frequency<br />

v Number <strong>of</strong> breaking operations at maximum current, for example the cycle:<br />

O - C/O - C/O (O = opening, C = closing)<br />

The breaking capacity is a relatively complicated characteristic to define and it<br />

therefore comes as no surprise that the same device can be assigned different<br />

breaking capacities depending on the standard by which it is defined.<br />

b Short-circuit making capacity<br />

In general, this characteristic is implicitly defined by the breaking capacity because a<br />

device should be able to close for a current that it can break.<br />

Sometimes, the making capacity needs to be higher, for example for circuit-breakers<br />

protecting generators.<br />

The making capacity is defined in terms <strong>of</strong> peak value (expressed in kA) because the<br />

first asymmetric peak is the most demanding from an electrodynamic point <strong>of</strong> view.<br />

For example, according to standard IEC 62271-100, a circuit-breaker used in a 50 Hz<br />

power system must be able to handle a peak making current equal to 2.5 times the<br />

rms breaking current (2.6 times for 60 Hz systems).<br />

Making capacity is also required for switches, and sometimes for disconnectors, even<br />

if these devices are not able to clear the fault.<br />

b Prospective short-circuit breaking current<br />

Some devices have the capacity to limit the fault current to be interrupted.<br />

Their breaking capacity is defined as the maximum prospective breaking current that<br />

would develop during a solid short-circuit across the upstream terminals <strong>of</strong> the device.<br />

Specific device characteristics<br />

The functions provided by various interrupting devices and their main constraints are<br />

presented in Figure B8.<br />

Device Isolation <strong>of</strong> Current switching Main constrains<br />

two active conditions<br />

networks Normal Fault<br />

Disconnector Yes No No Longitudinal input/output isolation<br />

Switch No Yes No Making and breaking <strong>of</strong> normal<br />

load current<br />

Short-circuit making capacity<br />

Contactor No Yes No Rated making and breaking<br />

capacities<br />

Maximum making and breaking<br />

capacities<br />

Duty and endurance<br />

characteristics<br />

Circuit-breaker No Yes Yes Short-circuit breaking capacity<br />

Short-circuit making capacity<br />

Fuse No No Yes Minimum short-circuit breaking<br />

capacity<br />

Maximum short-circuit breaking<br />

capacity<br />

Fig. B7 : Rated breaking current <strong>of</strong> a circuit-breaker subjected<br />

to a short-circuit as per IEC 60056 Fig. B8 : Functions provided by interrupting devices<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

The most common normal current rating for<br />

general-purpose MV distribution switchgear is<br />

400 A.<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Rated normal current<br />

The rated normal current is defined as “the r.m.s. value <strong>of</strong> the current which can be<br />

carried continuously at rated frequency with a temperature rise not exceeding that<br />

specified by the relevant product standard”.<br />

The rated normal current requirements for switchgear are decided at the substation<br />

<strong>design</strong> stage.<br />

The most common normal current rating for general-purpose MV distribution<br />

switchgear is 400 A.<br />

In industrial areas and medium-load-density urban districts, circuits rated at 630 A<br />

are sometimes required, while at bulk-supply substations which feed into MV<br />

networks,<br />

800 A; 1,250 A; 1,600 A; 2,500 A and 4,000 A circuit-breakers are listed as standard<br />

ratings for incoming-transformer circuits, bus-section and bus-coupler CBs, etc.<br />

For MV/LV transformer with a normal primary current up to roughly 60 A,<br />

a MV switch-fuse combination can be used . For higher primary currents,<br />

switch-fuse combination usually does not have the required performances.<br />

There are no IEC-recommended rated current values for switch-fuse combinations.<br />

The actual rated current <strong>of</strong> a given combination, meaning a switchgear base<br />

and defined fuses, is provided by the manufacturer <strong>of</strong> the combination as a table<br />

"fuse reference / rated current". These values <strong>of</strong> the rated current are defined by<br />

considering parameters <strong>of</strong> the combination as:<br />

b Normal thermal current <strong>of</strong> the fuses<br />

b Necessary derating <strong>of</strong> the fuses, due to their usage within the enclosure.<br />

When combinations are used for protecting transformers, then further parameters<br />

are to be considered, as presented in Appendix A <strong>of</strong> the IEC 62271-105 and in the<br />

IEC 60787. They are mainly:<br />

b The normal MV current <strong>of</strong> the transformer<br />

b The possible need for overloading the transformer<br />

b The inrush magnetizing current<br />

b The MV short-circuit power<br />

b The tapping switch adjustment range.<br />

Manufacturers usually provide an application table "service voltage / transformer<br />

power / fuse reference" based on standard distribution network and transformer<br />

parameters, and such table should be used with care, if dealing with unusual<br />

<strong>installation</strong>s.<br />

In such a scheme, the load-break switch should be suitably fitted with a tripping<br />

device e.g. with a relay to be able to trip at low fault-current levels which must cover<br />

(by an appropriate margin) the rated minimum breaking current <strong>of</strong> the MV fuses. In<br />

this way, medium values <strong>of</strong> fault current which are beyond the breaking capability <strong>of</strong><br />

the load-break switch will be cleared by the fuses, while low fault-current values, that<br />

cannot be correctly cleared by the fuses, will be cleared by the tripped load-break<br />

switch.<br />

Influence <strong>of</strong> the ambient temperature and altitude on the rated current<br />

Normal-current ratings are assigned to all current-carrying <strong>electrical</strong> appliances,<br />

and upper limits are decided by the acceptable temperature rise caused by the<br />

I 2 R (watts) dissipated in the conductors, (where I = r.m.s. current in amperes and<br />

R = the resistance <strong>of</strong> the conductor in ohms), together with the heat produced<br />

by magnetic-hysteresis and eddy-current losses in motors, transformers, steel<br />

enclosures, etc. and dielectric losses in cables and capacitors, where appropriate.<br />

The temperature rise above the ambient temperature will depend mainly on the<br />

rate at which the heat is removed. For example, large currents can be passed<br />

through electric motor windings without causing them to overheat, simply because<br />

a cooling fan fixed to the shaft <strong>of</strong> the motor removes the heat at the same rate as it<br />

is produced, and so the temperature reaches a stable value below that which could<br />

damage the insulation and result in a burnt-out motor.<br />

The normal-current values recommended by IEC are based on ambientair<br />

temperatures common to temperate climates at altitudes not exceeding<br />

1,000 metres, so that items which depend on natural cooling by radiation and<br />

air-convection will overheat if operated at rated normal current in a tropical climate<br />

and/ or at altitudes exceeding 1,000 metres. In such cases, the equipment has to be<br />

derated, i.e. be assigned a lower value <strong>of</strong> normal current rating.<br />

The case <strong>of</strong> transformer is addressed in IEC 60076-2.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

B8<br />

B - Connection to the MV public<br />

distribution network<br />

Earth faults on medium-voltage systems<br />

can produce dangerous voltage levels on<br />

LV <strong>installation</strong>s. LV consumers (and substation<br />

operating personnel) can be safeguarded<br />

against this danger by:<br />

b Restricting the magnitude <strong>of</strong> MV earth-fault<br />

currents<br />

b Reducing the substation earthing resistance<br />

to the lowest possible value<br />

b Creating equipotential conditions at the<br />

substation and at the consumer’s <strong>installation</strong><br />

Fault<br />

HV LV<br />

I f<br />

I f<br />

R s<br />

Fig. B9 : Transferred potential<br />

V= I f R s<br />

Consumer<br />

(1) The others being unearthed. A particular case <strong>of</strong> earth-fault<br />

current limitation is by means <strong>of</strong> a Petersen coil.<br />

1<br />

2<br />

3<br />

N<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Earthing systems<br />

Earthing and equipment-bonding earth connections require careful consideration,<br />

particularly regarding safety <strong>of</strong> the LV consumer during the occurrence <strong>of</strong> a shortcircuit<br />

to earth on the MV system.<br />

Earth electrodes<br />

In general, it is preferable, where physically possible, to separate the electrode<br />

provided for earthing exposed conductive parts <strong>of</strong> MV equipment from the electrode<br />

intended for earthing the LV neutral conductor. This is commonly practised in rural<br />

systems where the LV neutral-conductor earth electrode is installed at one or two<br />

spans <strong>of</strong> LV distribution line away from the substation.<br />

In most cases, the limited space available in urban substations precludes this<br />

practice, i.e. there is no possibility <strong>of</strong> separating a MV electrode sufficiently from<br />

a LV electrode to avoid the transference <strong>of</strong> (possibly dangerous) voltages to the<br />

LV system.<br />

Earth-fault current<br />

Earth-fault current levels at medium voltage are generally (unless deliberately<br />

restricted) comparable to those <strong>of</strong> a 3-phase short-circuit.<br />

Such currents passing through an earth electrode will raise its voltage to a medium<br />

value with respect to “remote earth” (the earth surrounding the electrode will be<br />

raised to a medium potential; “remote earth” is at zero potential).<br />

For example, 10,000 A <strong>of</strong> earth-fault current passing through an electrode with an<br />

(unusually low) resistance <strong>of</strong> 0.5 ohms will raise its voltage to 5,000 V.<br />

Providing that all exposed metal in the substation is “bonded” (connected together)<br />

and then connected to the earth electrode, and the electrode is in the form <strong>of</strong> (or is<br />

connected to) a grid <strong>of</strong> conductors under the floor <strong>of</strong> the substation, then there is no<br />

danger to personnel, since this arrangement forms an equipotential “cage” in which<br />

all conductive material, including personnel, is raised to the same potential.<br />

Transferred potential<br />

A danger exists however from the problem known as Transferred Potential. It will be<br />

seen in Figure B9 that the neutral point <strong>of</strong> the LV winding <strong>of</strong> the MV/LV transformer<br />

is also connected to the common substation earth electrode, so that the neutral<br />

conductor, the LV phase windings and all phase conductors are also raised to the<br />

electrode potential.<br />

Low-voltage distribution cables leaving the substation will transfer this potential to<br />

consumers <strong>installation</strong>s. It may be noted that there will be no LV insulation failure<br />

between phases or from phase to neutral since they are all at the same potential. It is<br />

probable, however, that the insulation between phase and earth <strong>of</strong> a cable or some<br />

part <strong>of</strong> an <strong>installation</strong> would fail.<br />

Solutions<br />

A first step in minimizing the obvious dangers <strong>of</strong> transferred potentials is to reduce<br />

the magnitude <strong>of</strong> MV earth-fault currents. This is commonly achieved by earthing the<br />

MV system through resistors or reactors at the star points <strong>of</strong> selected transformers (1) ,<br />

located at bulk-supply substations.<br />

A relatively medium transferred potential cannot be entirely avoided by this means,<br />

however, and so the following strategy has been adopted in some countries.<br />

The equipotential earthing <strong>installation</strong> at a consumer’s premises represents a remote<br />

earth, i.e. at zero potential. However, if this earthing <strong>installation</strong> were to be connected<br />

by a low-impedance conductor to the earth electrode at the substation, then the<br />

equipotential conditions existing in the substation would also exist at the consumer’s<br />

<strong>installation</strong>.<br />

Low-impedance interconnection<br />

This low-impedance interconnection is achieved simply by connecting the neutral<br />

conductor to the consumer’s equipotential <strong>installation</strong>, and the result is recognized as<br />

the TN earthing system (IEC 60364) as shown in diagram A <strong>of</strong> Figure B 0 next page.<br />

The TN system is generally associated with a Protective Multiple Earthing (PME)<br />

scheme, in which the neutral conductor is earthed at intervals along its length (every<br />

3rd or 4th pole on a LV overhead-line distributor) and at each consumer’s service<br />

position. It can be seen that the network <strong>of</strong> neutral conductors radiating from a<br />

substation, each <strong>of</strong> which is earthed at regular intervals, constitutes, together with<br />

the substation earthing, a very effective low-resistance earth electrode.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Diagram Rs value<br />

A - TN-a<br />

MV LV<br />

C - TT-a<br />

MV LV<br />

E - TT-b<br />

MV LV<br />

R S<br />

R S<br />

R S<br />

R N<br />

1<br />

2<br />

3<br />

N<br />

1<br />

2<br />

3<br />

N<br />

1<br />

2<br />

3<br />

N<br />

B - IT-a<br />

MV LV<br />

R S<br />

D - IT-b<br />

MV LV<br />

F - IT-c<br />

MV LV<br />

In cases E and F the LV protective conductors (bonding exposed conductive parts) in the substation<br />

are earthed via the substation earth electrode, and it is therefore the substation LV equipment (only)<br />

that could be subjected to overvoltage.<br />

R S<br />

R S<br />

R N<br />

Fig. B10 : Maximum earthing resistance Rs at a MV/LV substation to ensure safety during a short-circuit to earth fault on the medium-voltage equipment for different<br />

earthing systems<br />

The combination <strong>of</strong> restricted earth-fault currents, equipotential <strong>installation</strong>s and<br />

low resistance substation earthing, results in greatly reduced levels <strong>of</strong> overvoltage<br />

and limited stressing <strong>of</strong> phase-to-earth insulation during the type <strong>of</strong> MV earth-fault<br />

situation described above.<br />

Limitation <strong>of</strong> the MV earth-fault current and earth resistance <strong>of</strong> the substation<br />

Another widely-used earthing system is shown in diagram C <strong>of</strong> Figure B10. It will be<br />

seen that in the TT system, the consumer’s earthing <strong>installation</strong> (being isolated from<br />

that <strong>of</strong> the substation) constitutes a remote earth.<br />

This means that, although the transferred potential will not stress the phase-to-phase<br />

insulation <strong>of</strong> the consumer’s equipment, the phase-to-earth insulation <strong>of</strong> all three<br />

phases will be subjected to overvoltage.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1<br />

2<br />

3<br />

N<br />

1<br />

2<br />

3<br />

N<br />

1<br />

2<br />

3<br />

N<br />

Cases A and B<br />

No particular resistance value for Rs is imposed<br />

in these cases<br />

Cases C and D<br />

Uw - Uo<br />

Rs y<br />

Im<br />

Where<br />

Uw = the rated normal-frequency withstand<br />

voltage for low-voltage equipment at<br />

consumer <strong>installation</strong>s<br />

Uo = phase to neutral voltage at consumer's<br />

<strong>installation</strong>s<br />

Im = maximum value <strong>of</strong> MV earth-fault current<br />

Cases E and F<br />

Uws - U<br />

Rs y<br />

Im<br />

Where<br />

Uws = the normal-frequency withstand voltage<br />

for low-voltage equipments in the<br />

substation (since the exposed conductive<br />

parts <strong>of</strong> these equipments are earthed<br />

via Rs)<br />

U = phase to neutral voltage at the substation<br />

for the TT(s) system, but the phase-tophase<br />

voltage for the IT(s) system<br />

Im = maximum value <strong>of</strong> MV earth-fault current<br />

Notes:<br />

b For TN-a and IT-a, the MV and LV exposed conductive parts at the substation and those at the consumer’s <strong>installation</strong>s, together with the<br />

LV neutral point <strong>of</strong> the transformer, are all earthed via the substation electrode system.<br />

b For TT-a and IT-b, the MV and LV exposed conductive parts at the substation, together with the LV neutral point <strong>of</strong> the transformer are earthed via<br />

the substation electrode system.<br />

b For TT-b and IT-c, the LV neutral point <strong>of</strong> the transformer is separately earthed outside <strong>of</strong> the area <strong>of</strong> influence <strong>of</strong> the substation earth electrode.<br />

Uw and Uws are commonly given the (IEC 60364-4-44) value Uo + 1200 V, where Uo is the nominal phase-to-neutral voltage <strong>of</strong> the LV system<br />

concerned.<br />

B9<br />

© Schneider Electric - all rights reserved


B 0<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

The strategy in this case, is to reduce the resistance <strong>of</strong> the substation earth<br />

electrode, such that the standard value <strong>of</strong> 5-second withstand-voltage-to-earth for<br />

LV equipment and appliances will not be exceeded.<br />

Practical values adopted by one national <strong>electrical</strong> power-supply authority, on its<br />

20 kV distribution systems, are as follows:<br />

b Maximum earth-fault current in the neutral connection on overhead line distribution<br />

systems, or mixed (O/H line and U/G cable) systems, is 300 A<br />

b Maximum earth-fault current in the neutral connection on underground systems is<br />

1,000 A<br />

The formula required to determine the maximum value <strong>of</strong> earthing resistance Rs at<br />

the<br />

the<br />

substation,<br />

substation,<br />

to<br />

to<br />

ensure<br />

ensure<br />

that<br />

that<br />

the<br />

the<br />

LV<br />

LV<br />

withstand<br />

withstand<br />

voltage<br />

voltage will<br />

will<br />

not<br />

not<br />

be<br />

be<br />

exceeded,<br />

exceeded,<br />

is:<br />

is:<br />

Uw �Uo<br />

Rs = in ohms (see cases C and D in Figure B10). C10).<br />

Im<br />

Where<br />

Where<br />

Uw = the lowest standard value (in volts) <strong>of</strong> short-term (5 s) withstand voltage for the<br />

consumer’s <strong>installation</strong> and appliances = Uo + 1200 V (IEC 60364-4-44)<br />

Uo = phase to neutral voltage (in volts) at the consumer’s LV service position<br />

Im = maximum earth-fault current on the MV system (in amps). This maximum earth<br />

fault current Im is the vectorial sum <strong>of</strong> maximum earth-fault current in the neutral<br />

connection and total unbalanced capacitive current <strong>of</strong> the network.<br />

A third form <strong>of</strong> system earthing referred to as the “IT” system in IEC 60364 is<br />

commonly used where continuity <strong>of</strong> supply is essential, e.g. in hospitals, continuousprocess<br />

manufacturing, etc. The principle depends on taking a supply from an<br />

unearthed source, usually a transformer, the secondary winding <strong>of</strong> which is<br />

unearthed, or earthed through a medium impedance (u1,000 ohms). In these cases,<br />

an insulation failure to earth in the low-voltage circuits supplied from the secondary<br />

windings will result in zero or negligible fault-current flow, which can be allowed to<br />

persist until it is convenient to shut-down the affected circuit to carry out repair work.<br />

Diagrams B, D and F (Figure B10)<br />

They show IT systems in which resistors (<strong>of</strong> approximately 1,000 ohms) are included<br />

in the neutral earthing lead.<br />

If however, these resistors were removed, so that the system is unearthed, the<br />

following notes apply.<br />

Diagram B (Figure B10)<br />

All phase wires and the neutral conductor are “floating” with respect to earth, to which<br />

they are “connected” via the (normally very medium) insulation resistances and (very<br />

small) capacitances between the live conductors and earthed metal (conduits, etc.).<br />

Assuming perfect insulation, all LV phase and neutral conductors will be raised by<br />

electrostatic induction to a potential approaching that <strong>of</strong> the equipotential conductors.<br />

In practice, it is more likely, because <strong>of</strong> the numerous earth-leakage paths <strong>of</strong> all live<br />

conductors in a number <strong>of</strong> <strong>installation</strong>s acting in parallel, that the system will behave<br />

similarly to the case where a neutral earthing resistor is present, i.e. all conductors<br />

will be raised to the potential <strong>of</strong> the substation earth.<br />

In these cases, the overvoltage stresses on the LV insulation are small or nonexistent.<br />

Diagrams D and F (Figure B10)<br />

In these cases, the medium potential <strong>of</strong> the substation (S/S) earthing system acts on<br />

the isolated LV phase and neutral conductors:<br />

b Through the capacitance between the LV windings <strong>of</strong> the transformer and the<br />

transformer tank<br />

b Through capacitance between the equipotential conductors in the S/S and the<br />

cores <strong>of</strong> LV distribution cables leaving the S/S<br />

b Through current leakage paths in the insulation, in each case.<br />

At positions outside the area <strong>of</strong> influence <strong>of</strong> the S/S earthing, system capacitances<br />

exist between the conductors and earth at zero potential (capacitances between<br />

cores are irrelevant - all cores being raised to the same potential).<br />

The result is essentially a capacitive voltage divider, where each “capacitor” is<br />

shunted by (leakage path) resistances.<br />

In general, LV cable and <strong>installation</strong> wiring capacitances to earth are much<br />

larger, and the insulation resistances to earth are much smaller than those <strong>of</strong> the<br />

corresponding parameters at the S/S, so that most <strong>of</strong> the voltage stresses appear at<br />

the substation between the transformer tank and the LV winding.<br />

The rise in potential at consumers’ <strong>installation</strong>s is not likely therefore to be a problem<br />

where the MV earth-fault current level is restricted as previously mentioned.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Overhead line<br />

Fig. B11 : Single-line service<br />

Underground cable<br />

ring main<br />

Fig. B12 : Ring-main service<br />

(1) Copper is cathodic to most other metals and therefore<br />

resists corrosion.<br />

(2) A ring main is a continuous distributor in the form <strong>of</strong> a<br />

closed loop, which originates and terminates on one set <strong>of</strong><br />

busbars. Each end <strong>of</strong> the loop is controlled by its own circuitbreaker.<br />

In order to improve operational flexibility the busbars<br />

are <strong>of</strong>ten divided into two sections by a normally closed bussection<br />

circuit-breaker, and each end <strong>of</strong> the ring is connected<br />

to a different section.<br />

An interconnector is a continuous untapped feeder connecting<br />

the busbars <strong>of</strong> two substations. Each end <strong>of</strong> the interconnector<br />

is usually controlled by a circuit beaker.<br />

An interconnector-distributor is an interconnector which<br />

supplies one or more distribution substations along its length.<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

All IT-earthed transformers, whether the neutral point is isolated or earthed through<br />

a medium impedance, are routinely provided with an overvoltage limiting device<br />

which will automatically connect the neutral point directly to earth if an overvoltage<br />

condition approaches the insulation-withstand level <strong>of</strong> the LV system.<br />

In addition to the possibilities mentioned above, several other ways in which these<br />

overvoltages can occur are described in Clause 3.1.<br />

This kind <strong>of</strong> earth-fault is very rare, and when does occur is quickly detected and<br />

cleared by the automatic tripping <strong>of</strong> a circuit-breaker in a properly <strong>design</strong>ed and<br />

constructed <strong>installation</strong>.<br />

Safety in situations <strong>of</strong> elevated potentials depends entirely on the provision <strong>of</strong><br />

properly arranged equipotential areas, the basis <strong>of</strong> which is generally in the form <strong>of</strong> a<br />

widemeshed grid <strong>of</strong> interconnected bare copper conductors connected to verticallydriven<br />

copper-clad (1) steel rods.<br />

The equipotential criterion to be respected is that which is mentioned in <strong>Chapter</strong> F<br />

dealing with protection against electric shock by indirect contact, namely: that the<br />

potential between any two exposed metal parts which can be touched simultaneously<br />

by any parts the body must never, under any circumstances, exceed 50 V in dry<br />

conditions, or 25 V in wet conditions.<br />

Special care should be taken at the boundaries <strong>of</strong> equipotential areas to avoid steep<br />

potential gradients on the surface <strong>of</strong> the ground which give rise to dangerous “step<br />

potentials”.<br />

This question is closely related to the safe earthing <strong>of</strong> boundary fences and is further<br />

discussed in Sub-clause 3.1.<br />

.2 Different MV service connections<br />

According to the type <strong>of</strong> medium-voltage network, the following supply arrangements<br />

are commonly adopted.<br />

Single-line service<br />

The substation is supplied by a single circuit tee-<strong>of</strong>f from a MV distributor (cable or<br />

line).<br />

In general, the MV service is connected into a panel containing a load-break/<br />

isolating switch-fuse combination and earthing switches, as shown in Figure B .<br />

In some countries a pole-mounted transformer with no MV switchgear or fuses<br />

(at the pole) constitutes the “substation”. This type <strong>of</strong> MV service is very common in<br />

rural areas.<br />

Protection and switching devices are remote from the transformer, and generally<br />

control a main overhead line, from which a number <strong>of</strong> these elementary service lines<br />

are tapped.<br />

Ring-main service<br />

Ring-main units (RMU) are normally connected to form a MV ring main (2) or<br />

interconnector-distributor (2) , such that the RMU busbars carry the full ring-main or<br />

interconnector current (see Fig. B 2).<br />

The RMU consists <strong>of</strong> three units, integrated to form a single assembly, viz:<br />

b 2 incoming units, each containing a load break/isolating switch and a circuit<br />

earthing switch<br />

b 1 outgoing and general protection unit, containing a load-break switch and<br />

MV fuses, or a combined load-break/fuse switch, or a circuit-breaker and isolating<br />

switch, together with a circuit-earthing switch in each case.<br />

All load-break switches and earthing switches are fully rated for short-circuit currentmaking<br />

duty.<br />

This arrangement provides the user with a two-source supply, thereby reducing<br />

considerably any interruption <strong>of</strong> service due to system faults or operations by the<br />

supply authority, etc.<br />

The main application for RMUs is in utility supply MV underground-cable networks in<br />

urban areas.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B<br />

© Schneider Electric - all rights reserved


B 2<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Paralleled underground<br />

cable distributors<br />

Fig. B13 : Parallel feeders service<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

Parallel feeders service<br />

Where a MV supply connection to two lines or cables originating from the same<br />

busbar <strong>of</strong> a substation is possible, a similar MV switchboard to that <strong>of</strong> a RMU is<br />

commonly used (see Fig. B 3).<br />

The main operational difference between this arrangement and that <strong>of</strong> a RMU is that<br />

the two incoming panels are mutually interlocked, such that one incoming switch only<br />

can be closed at a time, i.e. its closure prevents the closure <strong>of</strong> the other.<br />

On the loss <strong>of</strong> power supply, the closed incoming switch must be opened and the<br />

(formerly open) switch can then be closed.<br />

The sequence may be carried out manually or automatically.<br />

This type <strong>of</strong> switchboard is used particularly in networks <strong>of</strong> medium-load density and<br />

in rapidly-expanding urban areas supplied by MV underground cable systems.<br />

.3 Some operational aspects <strong>of</strong> MV distribution<br />

networks<br />

Overhead lines<br />

Medium winds, ice formation, etc., can cause the conductors <strong>of</strong> overhead lines to<br />

touch each other, thereby causing a momentary (i.e. not permanent) short-circuit<br />

fault.<br />

Insulation failure due to broken ceramic or glass insulators, caused by air-borne<br />

debris; careless use <strong>of</strong> shot-guns, etc., or again, heavily polluted insulator surfaces,<br />

can result in a short-circuit to earth.<br />

Many <strong>of</strong> these faults are self-clearing. For example, in dry conditions, broken<br />

insulators can very <strong>of</strong>ten remain in service undetected, but are likely to flashover to<br />

earth (e.g. to a metal supporting structure) during a rainstorm. Moreover, polluted<br />

surfaces generally cause a flashover to earth only in damp conditions.<br />

The passage <strong>of</strong> fault current almost invariably takes the form <strong>of</strong> an electric arc, the<br />

intense heat <strong>of</strong> which dries the current path, and to some extent, re-establishes its<br />

insulating properties. In the meantime, protective devices have usually operated to<br />

clear the fault, i.e. fuses have blown or a circuit-breaker has tripped.<br />

Experience has shown that in the large majority <strong>of</strong> cases, restoration <strong>of</strong> supply by<br />

replacing fuses or by re-closing a circuit-breaker will be successful.<br />

For this reason it has been possible to considerably improve the continuity <strong>of</strong> service<br />

on MV overhead-line distribution networks by the application <strong>of</strong> automatic circuitbreaker<br />

reclosing schemes at the origin <strong>of</strong> the circuits concerned.<br />

These automatic schemes permit a number <strong>of</strong> reclosing operations if a first attempt<br />

fails, with adjustable time delays between successive attempts (to allow de-ionization<br />

<strong>of</strong> the air at the fault) before a final lock-out <strong>of</strong> the circuit-breaker occurs, after all<br />

(generally three) attempts fail.<br />

Other improvements in service continuity are achieved by the use <strong>of</strong> remotelycontrolled<br />

section switches and by automatic isolating switches which operate in<br />

conjunction with an auto-reclosing circuit-breaker.<br />

This last scheme is exemplified by the final sequence shown in Figure B 4 next<br />

page.<br />

The principle is as follows: if, after two reclosing attempts, the circuit-breaker trips,<br />

the fault is assumed to be permanent, then there are two possibilities:<br />

b The fault is on the section downstream the Automatic Line Switch, and while the<br />

feeder is dead the ALS opens to isolate this section <strong>of</strong> the network, before the third<br />

(and final) reclosing takes place,<br />

b The fault is on the section upstream the ALS and the circuit-breaker will make a<br />

third reclosing attempt and thus trip and lock out.<br />

While these measures have greatly improved the reliability <strong>of</strong> supplies from<br />

MV overhead line systems, the consumers must, where considered necessary, make<br />

their own arrangements to counter the effects <strong>of</strong> momentary interruptions to supply<br />

(between reclosures), for example:<br />

b Uninterruptible standby emergency power<br />

b Lighting that requires no cooling down before re-striking (“hot restrike”).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Centralized remote control, based on SCADA<br />

(Supervisory Control And Data Acquisition)<br />

systems and recent developments in IT<br />

(Information Technology) techniques, is<br />

becoming more and more common in countries<br />

in which the complexity <strong>of</strong> highly interconnected<br />

systems justifies the expenditure.<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

1- Cycle 1SR<br />

If O1 O2<br />

In Io 15 to 30 s<br />

fault<br />

0.3 s 0.4 s<br />

2 - Cycle 2SR<br />

a - Fault on main feeder<br />

If O1 O2<br />

In Io 15 to 30s<br />

fault<br />

b - Fault on section supplied through Automatic Line Switch<br />

If O1 O2<br />

SR1 O3<br />

In Io 15 to 30 s<br />

15 to 30 s<br />

Fault<br />

0.3 s 0.4 s<br />

0.3 s 0.4 s<br />

Fig. B14 : Automatic reclosing cycles <strong>of</strong> a circuit-breaker controlling a radial MV feeder<br />

Underground cable networks<br />

Faults on underground cable networks are sometimes the result <strong>of</strong> careless<br />

workmanship by cable jointers or by cable laying contractors, etc., but are more<br />

commonly due to damage from tools such as pick-axes, pneumatic drills and trench<br />

excavating machines, and so on, used by other utilities.<br />

Insulation failures sometimes occur in cable terminating boxes due to overvoltage,<br />

particularly at points in a MV system where an overhead line is connected to an<br />

underground cable. The overvoltage in such a case is generally <strong>of</strong> atmospheric<br />

origin, and electromagnetic-wave reflection effects at the joint box (where the natural<br />

impedance <strong>of</strong> the circuit changes abruptly) can result in overstressing <strong>of</strong> the cablebox<br />

insulation to the point <strong>of</strong> failure. Overvoltage protection devices, such as lightning<br />

arresters, are frequently installed at these locations.<br />

Faults occurring in cable networks are less frequent than those on overhead (O/H)<br />

line systems, but are almost invariably permanent faults, which require more time for<br />

localization and repair than those on O/H lines.<br />

Where a cable fault occurs on a ring, supply can be quickly restored to all consumers<br />

when the faulty section <strong>of</strong> cable has been determined.<br />

If, however, the fault occurs on a radial feeder, the delay in locating the fault and<br />

carrying out repair work can amount to several hours, and will affect all consumers<br />

downstream <strong>of</strong> the fault position. In any case, if supply continuity is essential on all,<br />

or part <strong>of</strong>, an <strong>installation</strong>, a standby source must be provided.<br />

Remote control <strong>of</strong> MV networks<br />

Remote control on MV feeders is useful to reduce outage durations in case <strong>of</strong> cable<br />

fault by providing an efficient and fast mean for loop configuration. This is achieved<br />

by motor operated switches implemented in some <strong>of</strong> the substations along the loop<br />

associated with relevant remote telecontrol units. Remote controled substation will<br />

always be reenergized through telecontroled operation when the other ones could<br />

have to wait for further manual operation.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

SR O3<br />

Permanent fault<br />

SR1 O3<br />

0.4 s<br />

0.4 s<br />

15 to 30 s<br />

SR2 O4<br />

Permanent fault<br />

0.45 s<br />

SR2<br />

Opening <strong>of</strong> ALS<br />

B 3<br />

© Schneider Electric - all rights reserved


B14<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

The consumer must provide certain data to the<br />

utility at the earliest stage <strong>of</strong> the project.<br />

2 Procedure for the establishment<br />

<strong>of</strong> a new substation<br />

Large consumers <strong>of</strong> electricity are invariably supplied at MV.<br />

On LV systems operating at 120/208 V (3-phase 4-wires), a load <strong>of</strong> 50 kVA might be<br />

considered to be “large”, while on a 240/415 V 3-phase system a “large” consumer<br />

could have a load in excess <strong>of</strong> 100 kVA. Both systems <strong>of</strong> LV distribution are common<br />

in many parts <strong>of</strong> the world.<br />

As a matter <strong>of</strong> interest, the IEC recommends a “world” standard <strong>of</strong> 230/400 V for<br />

3-phase 4-wire systems. This is a compromise level and will allow existing systems<br />

which operate at 220/380 V and at 240/415 V, or close to these values, to comply<br />

with the proposed standard simply by adjusting the <strong>of</strong>f-circuit tapping switches <strong>of</strong><br />

standard distribution transformers.<br />

The distance over which the energy has to be transmitted is a further factor in<br />

considering an MV or LV service. Services to small but isolated rural consumers are<br />

obvious examples.<br />

The decision <strong>of</strong> a MV or LV supply will depend on local circumstances and<br />

considerations such as those mentioned above, and will generally be imposed by the<br />

utility for the district concerned.<br />

When a decision to supply power at MV has been made, there are two widelyfollowed<br />

methods <strong>of</strong> proceeding:<br />

1 - The power-supplier constructs a standard substation close to the consumer’s<br />

premises, but the MV/LV transformer(s) is (are) located in transformer chamber(s)<br />

inside the premises, close to the load centre<br />

2 - The consumer constructs and equips his own substation on his own premises, to<br />

which the power supplier makes the MV connection<br />

In method no. 1 the power supplier owns the substation, the cable(s) to the<br />

transformer(s), the transformer(s) and the transformer chamber(s), to which he has<br />

unrestricted access.<br />

The transformer chamber(s) is (are) constructed by the consumer (to plans and<br />

regulations provided by the supplier) and include plinths, oil drains, fire walls and<br />

ceilings, ventilation, lighting, and earthing systems, all to be approved by the supply<br />

authority.<br />

The tariff structure will cover an agreed part <strong>of</strong> the expenditure required to provide<br />

the service.<br />

Whichever procedure is followed, the same principles apply in the conception and<br />

realization <strong>of</strong> the project. The following notes refer to procedure no. 2.<br />

2.1 Preliminary information<br />

Before any negotiations or discussions can be initiated with the supply authorities,<br />

the following basic elements must be established:<br />

Maximum anticipated power (kVA) demand<br />

Determination <strong>of</strong> this parameter is described in <strong>Chapter</strong> A, and must take into<br />

account the possibility <strong>of</strong> future additional load requirements. Factors to evaluate at<br />

this stage are:<br />

b The utilization factor (ku)<br />

b The simultaneity factor (ks)<br />

Layout plans and elevations showing location <strong>of</strong> proposed substation<br />

Plans should indicate clearly the means <strong>of</strong> access to the proposed substation, with<br />

dimensions <strong>of</strong> possible restrictions, e.g. entrances corridors and ceiling height,<br />

together with possible load (weight) bearing limits, and so on, keeping in mind that:<br />

b The power-supply personnel must have free and unrestricted access to the<br />

MV equipment in the substation at all times<br />

b Only qualified and authorized consumer’s personnel are allowed access to the<br />

substation<br />

b Some supply authorities or regulations require that the part <strong>of</strong> the <strong>installation</strong> operated<br />

by the authority is located in a separated room from the part operated by the customer.<br />

Degree <strong>of</strong> supply continuity required<br />

The consumer must estimate the consequences <strong>of</strong> a supply failure in terms <strong>of</strong> its<br />

duration:<br />

b Loss <strong>of</strong> production<br />

b Safety <strong>of</strong> personnel and equipment<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

The utility must give specific information to the<br />

prospective consumer.<br />

The utility must give <strong>of</strong>ficial approval <strong>of</strong> the<br />

equipment to be installed in the substation,<br />

and <strong>of</strong> proposed methods <strong>of</strong> <strong>installation</strong>.<br />

After testing and checking <strong>of</strong> the <strong>installation</strong> by<br />

an independent test authority, a certificate is<br />

granted which permits the substation to be put<br />

into service.<br />

2 Procedure for the establishment<br />

<strong>of</strong> a new substation<br />

2.2 Project studies<br />

From the information provided by the consumer, the power-supplier must indicate:<br />

The type <strong>of</strong> power supply proposed, and define:<br />

b The kind <strong>of</strong> power-supply system: overheadline or underground-cable network<br />

b Service connection details: single-line service, ring-main <strong>installation</strong>, or parallel<br />

feeders, etc.<br />

b Power (kVA) limit and fault current level<br />

The nominal voltage and rated voltage (Highest voltage for equipment)<br />

Existing or future, depending on the development <strong>of</strong> the system.<br />

Metering details which define:<br />

b The cost <strong>of</strong> connection to the power network<br />

b Tariff details (consumption and standing charges)<br />

2.3 Implementation<br />

Before any <strong>installation</strong> work is started, the <strong>of</strong>ficial agreement <strong>of</strong> the power-supplier<br />

must be obtained. The request for approval must include the following information,<br />

largely based on the preliminary exchanges noted above:<br />

b Location <strong>of</strong> the proposed substation<br />

b Single-line diagram <strong>of</strong> power circuits and connections, together with earthingcircuit<br />

proposals<br />

b Full details <strong>of</strong> <strong>electrical</strong> equipment to be installed, including performance<br />

characteristics<br />

b Layout <strong>of</strong> equipment and provision for metering components<br />

b Arrangements for power-factor improvement if required<br />

b Arrangements provided for emergency standby power plant (MV or LV) if eventually<br />

required<br />

2.4 Commissioning<br />

When required by the authority, commissioning tests must be successfully completed<br />

before authority is given to energize the <strong>installation</strong> from the power supply system.<br />

Even if no test is required by the authority it is better to do the following verification tests:<br />

b Measurement <strong>of</strong> earth-electrode resistances<br />

b Continuity <strong>of</strong> all equipotential earth-and safety bonding conductors<br />

b Inspection and functional testing <strong>of</strong> all MV components<br />

b Insulation checks <strong>of</strong> MV equipment<br />

b Dielectric strength test <strong>of</strong> transformer oil (and switchgear oil if appropriate), if<br />

applicable<br />

b Inspection and testing <strong>of</strong> the LV <strong>installation</strong> in the substation<br />

b Checks on all interlocks (mechanical key and <strong>electrical</strong>) and on all automatic<br />

sequences<br />

b Checks on correct protective-relay operation and settings<br />

It is also imperative to check that all equipment is provided, such that any properly<br />

executed operation can be carried out in complete safety. On receipt <strong>of</strong> the certificate<br />

<strong>of</strong> conformity (if required):<br />

b Personnel <strong>of</strong> the power-supply authority will energize the MV equipment and check<br />

for correct operation <strong>of</strong> the metering<br />

b The <strong>installation</strong> contractor is responsible for testing and connection <strong>of</strong> the<br />

LV <strong>installation</strong><br />

When finally the substation is operational:<br />

b The substation and all equipment belongs to the consumer<br />

b The power-supply authority has operational control over all MV switchgear in the<br />

substation, e.g. the two incoming load-break switches and the transformer MV switch<br />

(or CB) in the case <strong>of</strong> a RingMainUnit, together with all associated MV earthing switches<br />

b The power-supply personnel has unrestricted access to the MV equipment<br />

b The consumer has independent control <strong>of</strong> the MV switch (or CB) <strong>of</strong> the transformer(s)<br />

only, the consumer is responsible for the maintenance <strong>of</strong> all substation equipment,<br />

and must request the power-supply authority to isolate and earth the switchgear to<br />

allow maintenance work to proceed. The power supplier must issue a signed permitto-work<br />

to the consumers maintenance personnel, together with keys <strong>of</strong> locked-<strong>of</strong>f<br />

isolators, etc. at which the isolation has been carried out.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B15<br />

© Schneider Electric - all rights reserved


B16<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Protection against electric shocks and<br />

overvoltages is closely related to the<br />

achievement <strong>of</strong> efficient (low resistance)<br />

earthing and effective application <strong>of</strong> the<br />

principles <strong>of</strong> equipotential environments.<br />

3 Protection aspect<br />

The subject <strong>of</strong> protection in the <strong>electrical</strong> power industry is vast: it covers all aspects<br />

<strong>of</strong> safety for personnel, and protection against damage or destruction <strong>of</strong> property,<br />

plant, and equipment.<br />

These different aspects <strong>of</strong> protection can be broadly classified according to the<br />

following objectives:<br />

b Protection <strong>of</strong> personnel and animals against the dangers <strong>of</strong> overvoltages and<br />

electric shock, fire, explosions, and toxic gases, etc.<br />

b Protection <strong>of</strong> the plant, equipment and components <strong>of</strong> a power system against<br />

the stresses <strong>of</strong> short-circuit faults, atmospheric surges (lightning) and power-system<br />

instability (loss <strong>of</strong> synchronism) etc.<br />

b Protection <strong>of</strong> personnel and plant from the dangers <strong>of</strong> incorrect power-system<br />

operation, by the use <strong>of</strong> <strong>electrical</strong> and mechanical interlocking. All classes <strong>of</strong><br />

switchgear (including, for example, tap-position selector switches on transformers,<br />

and so on...) have well-defined operating limits. This means that the order in which<br />

the different kinds <strong>of</strong> switching device can be safely closed or opened is vitally<br />

important. Interlocking keys and analogous <strong>electrical</strong> control circuits are frequently<br />

used to ensure strict compliance with correct operating sequences.<br />

It is beyond the scope <strong>of</strong> a guide to describe in full technical detail the numerous<br />

schemes <strong>of</strong> protection available to power-systems engineers, but it is hoped that the<br />

following sections will prove to be useful through a discussion <strong>of</strong> general principles.<br />

While some <strong>of</strong> the protective devices mentioned are <strong>of</strong> universal application,<br />

descriptions generally will be confined to those in common use on MV and<br />

LV systems only, as defined in Sub-clause 1.1 <strong>of</strong> this <strong>Chapter</strong>.<br />

3.1 Protection against electric shocks<br />

Protective measures against electric shock are based on two common dangers:<br />

b Contact with an active conductor, i.e. which is live with respect to earth in normal<br />

circumstances. This is referred to as a “direct contact” hazard.<br />

b Contact with a conductive part <strong>of</strong> an apparatus which is normally dead, but which<br />

has become live due to insulation failure in the apparatus. This is referred to as an<br />

“indirect contact” hazard.<br />

It may be noted that a third type <strong>of</strong> shock hazard can exist in the proximity <strong>of</strong> MV or<br />

LV (or mixed) earth electrodes which are passing earth-fault currents. This hazard<br />

is due to potential gradients on the surface <strong>of</strong> the ground and is referred to as a<br />

“step-voltage” hazard; shock current enters one foot and leaves by the other foot, and<br />

is particular dangerous for four-legged animals. A variation <strong>of</strong> this danger, known as<br />

a “touch voltage” hazard can occur, for instance, when an earthed metallic part is<br />

situated in an area in which potential gradients exist.<br />

Touching the part would cause current to pass through the hand and both feet.<br />

Animals with a relatively long front-to-hind legs span are particularly sensitive to<br />

step-voltage hazards and cattle have been killed by the potential gradients caused by<br />

a low voltage (230/400 V) neutral earth electrode <strong>of</strong> insufficiently low resistance.<br />

Potential-gradient problems <strong>of</strong> the kind mentioned above are not normally<br />

encountered in <strong>electrical</strong> <strong>installation</strong>s <strong>of</strong> buildings, providing that equipotential<br />

conductors properly bond all exposed metal parts <strong>of</strong> equipment and all extraneous<br />

metal (i.e. not part <strong>of</strong> an <strong>electrical</strong> apparatus or the <strong>installation</strong> - for example<br />

structural steelwork, etc.) to the protective-earthing conductor.<br />

Direct-contact protection or basic protection<br />

The main form <strong>of</strong> protection against direct contact hazards is to contain all live parts<br />

in housings <strong>of</strong> insulating material or in metallic earthed housings, by placing out <strong>of</strong><br />

reach (behind insulated barriers or at the top <strong>of</strong> poles) or by means <strong>of</strong> obstacles.<br />

Where insulated live parts are housed in a metal envelope, for example transformers,<br />

electric motors and many domestic appliances, the metal envelope is connected to<br />

the <strong>installation</strong> protective earthing system.<br />

For MV switchgear, the IEC standard 62271-200 (Prefabricated Metal Enclosed<br />

switchgear and controlgear for voltages up to 52 kV) specifies a minimum Protection<br />

Index (IP coding) <strong>of</strong> IP2X which ensures the direct-contact protection. Furthermore,<br />

the metallic enclosure has to demonstrate an <strong>electrical</strong> continuity, then establishing<br />

a good segregation between inside and ouside <strong>of</strong> the enclosure. Proper grounding <strong>of</strong><br />

the enclosure further participates to the <strong>electrical</strong> protection <strong>of</strong> the operators under<br />

normal operating conditions.<br />

For LV appliances this is achieved through the third pin <strong>of</strong> a 3-pin plug and socket.<br />

Total or even partial failure <strong>of</strong> insulation to the metal, can raise the voltage <strong>of</strong> the<br />

envelope to a dangerous level (depending on the ratio <strong>of</strong> the resistance <strong>of</strong> the leakage<br />

path through the insulation, to the resistance from the metal envelope to earth).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

3 Protection aspect<br />

Indirect-contact protection or fault protection<br />

A person touching the metal envelope <strong>of</strong> an apparatus with a faulty insulation, as<br />

described above, is said to be making an indirect contact.<br />

An indirect contact is characterized by the fact that a current path to earth exists<br />

(through the protective earthing (PE) conductor) in parallel with the shock current<br />

through the person concerned.<br />

Case <strong>of</strong> fault on L.V. system<br />

Extensive tests have shown that, providing the potential <strong>of</strong> the metal envelope is not<br />

greater than 50 V with respect to earth, or to any conductive material within reaching<br />

distance, no danger exists.<br />

Indirect-contact hazard in the case <strong>of</strong> a MV fault<br />

If the insulation failure in an apparatus is between a MV conductor and the metal<br />

envelope, it is not generally possible to limit the rise <strong>of</strong> voltage <strong>of</strong> the envelope to<br />

50 V or less, simply by reducing the earthing resistance to a low value. The solution<br />

in this case is to create an equipotential situation, as described in Sub-clause 1.1<br />

“Earthing systems”.<br />

3.2 Protection <strong>of</strong> transformer and circuits<br />

<strong>General</strong><br />

The <strong>electrical</strong> equipment and circuits in a substation must be protected in order<br />

to avoid or to control damage due to abnormal currents and/or voltages. All<br />

equipment normally used in power system <strong>installation</strong>s have standardized short-time<br />

withstand ratings for overcurrent and overvoltage. The role <strong>of</strong> protective scheme is<br />

to ensure that this withstand limits can never be exceeded. In general, this means<br />

that fault conditions must be cleared as fast as possible without missing to ensure<br />

coordination between protective devices upstream and downstream the equipement<br />

to be protected. This means, when there is a fault in a network, generally several<br />

protective devices see the fault at the same time but only one must act.<br />

These devices may be:<br />

b Fuses which clear the faulty circuit directly or together with a mechanical tripping<br />

attachment, which opens an associated three-phase load-break switch<br />

b Relays which act indirectly on the circuit-breaker coil<br />

Transformer protection<br />

Stresses due to the supply network<br />

Some voltage surges can occur on the network such as :<br />

b Atmospheric voltage surges<br />

Atmospheric voltage surges are caused by a stroke <strong>of</strong> lightning falling on or near an<br />

overhead line.<br />

b Operating voltage surges<br />

A sudden change in the established operating conditions in an <strong>electrical</strong> network<br />

causes transient phenomena to occur. This is generally a high frequency or damped<br />

oscillation voltage surge wave.<br />

For both voltage surges, the overvoltage protection device generally used is a<br />

varistor (Zinc Oxide).<br />

In most cases, voltage surges protection has no action on switchgear.<br />

Stresses due to the load<br />

Overloading is frequently due to the coincidental demand <strong>of</strong> a number <strong>of</strong> small<br />

loads, or to an increase in the apparent power (kVA) demand <strong>of</strong> the <strong>installation</strong>,<br />

due to expansion in a factory, with consequent building extensions, and so on. Load<br />

increases raise the temperature <strong>of</strong> the wirings and <strong>of</strong> the insulation material. As<br />

a result, temperature increases involve a reduction <strong>of</strong> the equipment working life.<br />

Overload protection devices can be located on primary or secondary side <strong>of</strong> the<br />

transformer.<br />

The protection against overloading <strong>of</strong> a transformer is now provided by a digital relay<br />

which acts to trip the circuit-breaker on the secondary side <strong>of</strong> the transformer. Such<br />

relay, generally called thermal overload relay, artificially simulates the temperature,<br />

taking into account the time constant <strong>of</strong> the transformer. Some <strong>of</strong> them are able to<br />

take into account the effect <strong>of</strong> harmonic currents due to non linear loads (rectifiers,<br />

computer equipment, variable speed drives…).This type <strong>of</strong> relay is also able to<br />

predict the time before overload tripping and the waiting time after tripping. So, this<br />

information is very helpful to control load shedding operation.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B17<br />

© Schneider Electric - all rights reserved


B18<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Fig. B15 : Transformer with conservator tank<br />

Fig. B16 : Totally filled transformer<br />

1<br />

2<br />

3<br />

Overcurrent relay<br />

E/F relay<br />

HV LV<br />

Fig. B17 : Protection against earth fault on the MV winding<br />

1<br />

2<br />

3<br />

N<br />

3 Protection aspect<br />

In addition, larger oil-immersed transformers frequently have thermostats with two<br />

settings, one for alarm purposes and the other for tripping.<br />

Dry-type transformers use heat sensors embedded in the hottest part <strong>of</strong> the windings<br />

insulation for alarm and tripping.<br />

Internal faults<br />

The protection <strong>of</strong> transformers by transformer-mounted devices, against the effects<br />

<strong>of</strong> internal faults, is provided on transformers which are fitted with airbreathing<br />

conservator tanks by the classical Buchholz mechanical relay (see Fig. B15). These<br />

relays can detect a slow accumulation <strong>of</strong> gases which results from the arcing <strong>of</strong><br />

incipient faults in the winding insulation or from the ingress <strong>of</strong> air due to an oil leak.<br />

This first level <strong>of</strong> detection generally gives an alarm, but if the condition deteriorates<br />

further, a second level <strong>of</strong> detection will trip the upstream circuit-breaker.<br />

An oil-surge detection feature <strong>of</strong> the Buchholz relay will trip the upstream circuitbreaker<br />

“instantaneously” if a surge <strong>of</strong> oil occurs in the pipe connecting the main tank<br />

with the conservator tank.<br />

Such a surge can only occur due to the displacement <strong>of</strong> oil caused by a rapidly<br />

formed bubble <strong>of</strong> gas, generated by an arc <strong>of</strong> short-circuit current in the oil.<br />

By specially <strong>design</strong>ing the cooling-oil radiator elements to perform a concerting action,<br />

“totally filled” types <strong>of</strong> transformer as large as 10 MVA are now currently available.<br />

Expansion <strong>of</strong> the oil is accommodated without an excessive rise in pressure by the<br />

“bellows” effect <strong>of</strong> the radiator elements. A full description <strong>of</strong> these transformers is<br />

given in Sub-clause 4.4 (see Fig. B16).<br />

Evidently the Buchholz devices mentioned above cannot be applied to this <strong>design</strong>; a<br />

modern counterpart has been developed however, which measures:<br />

b The accumulation <strong>of</strong> gas<br />

b Overpressure<br />

b Overtemperature<br />

The first two conditions trip the upstream circuit-breaker, and the third condition trips<br />

the downstream circuit-breaker <strong>of</strong> the transformer.<br />

Internal phase-to-phase short-circuit<br />

Internal phase-to-phase short-circuit must be detected and cleared by:<br />

b 3 fuses on the primary side <strong>of</strong> the tranformer or<br />

b An overcurrent relay that trips a circuit-breaker upstream <strong>of</strong> the transformer<br />

Internal phase-to-earth short-circuit<br />

This is the most common type <strong>of</strong> internal fault. It must be detected by an earth fault<br />

relay. Earth fault current can be calculated with the sum <strong>of</strong> the 3 primary phase<br />

currents (if 3 current transformers are used) or by a specific core current transformer.<br />

If a great sensitivity is needed, specific core current transformer will be prefered. In<br />

such a case, a two current transformers set is sufficient (see Fig. B17).<br />

Protection <strong>of</strong> circuits<br />

The protection <strong>of</strong> the circuits downstream <strong>of</strong> the transformer must comply with the<br />

IEC 60364 requirements.<br />

Discrimination between the protective devices upstream and<br />

downstream <strong>of</strong> the transformer<br />

The consumer-type substation with LV metering requires discriminative operation<br />

between the MV fuses or MV circuit-breaker and the LV circuit-breaker or fuses.<br />

The rating <strong>of</strong> the MV fuses will be chosen according to the characteristics <strong>of</strong> the<br />

transformer.<br />

The tripping characteristics <strong>of</strong> the LV circuit-breaker must be such that, for an<br />

overload or short-circuit condition downstream <strong>of</strong> its location, the breaker will trip<br />

sufficiently quickly to ensure that the MV fuses or the MV circuit-breaker will not be<br />

adversely affected by the passage <strong>of</strong> overcurrent through them.<br />

The tripping performance curves for MV fuses or MV circuit-breaker and LV circuitbreakers<br />

are given by graphs <strong>of</strong> time-to-operate against current passing through<br />

them. Both curves have the general inverse-time/current form (with an abrupt<br />

discontinuity in the CB curve at the current value above which “instantaneous”<br />

tripping occurs).<br />

These curves are shown typically in Figure B18.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Time<br />

D<br />

C<br />

A<br />

B<br />

Minimum pre-arcing<br />

time <strong>of</strong> MV fuse<br />

B/A u 1.35 at any<br />

moment in time<br />

D/C u 2 at any<br />

current value<br />

Circuit breaker<br />

tripping<br />

characteristic<br />

Current<br />

Fig. B18 : Discrimination between MV fuse operation and LV<br />

circuit-breaker tripping, for transformer protection<br />

U 1 MV LV U 2<br />

Fig. B19 : MV fuse and LV circuit-breaker configuration<br />

3 Protection aspect<br />

b In order to achieve discrimination:<br />

All parts <strong>of</strong> the fuse or MV circuit-breaker curve must be above and to the right <strong>of</strong> the<br />

CB curve.<br />

b In order to leave the fuses unaffected (i.e. undamaged):<br />

All parts <strong>of</strong> the minimum pre-arcing fuse curve must be located to the right <strong>of</strong> the CB<br />

curve by a factor <strong>of</strong> 1.35 or more (e.g. where, at time T, the CB curve passes through<br />

a point corresponding to 100 A, the fuse curve at the same time T must pass through<br />

a point corresponding to 135 A, or more, and so on...) and, all parts <strong>of</strong> the fuse curve<br />

must be above the CB curve by a factor <strong>of</strong> 2 or more (e.g. where, at a current level I<br />

the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve<br />

at the same current level I must pass through a point corresponding to 3 seconds, or<br />

more, etc.).<br />

The factors 1.35 and 2 are based on standard maximum manufacturing tolerances<br />

for MV fuses and LV circuit-breakers.<br />

In order to compare the two curves, the MV currents must be converted to the<br />

equivalent LV currents, or vice-versa.<br />

Where a LV fuse-switch is used, similar separation <strong>of</strong> the characteristic curves <strong>of</strong> the<br />

MV and LV fuses must be respected.<br />

b In order to leave the MV circuit-breaker protection untripped:<br />

All parts <strong>of</strong> the minimum pre-arcing fuse curve must be located to the right <strong>of</strong> the<br />

CB curve by a factor <strong>of</strong> 1.35 or more (e.g. where, at time T, the LV CB curve passes<br />

through a point corresponding to 100 A, the MV CB curve at the same time T must<br />

pass through a point corresponding to 135 A, or more, and so on...) and, all parts <strong>of</strong><br />

the MV CB curve must be above the LV CB curve (time <strong>of</strong> LV CB curve must be less<br />

or equal than MV CB curves minus 0.3 s)<br />

The factors 1.35 and 0.3 s are based on standard maximum manufacturing<br />

tolerances for MV current transformers, MV protection relay and LV circuit-breakers.<br />

In order to compare the two curves, the MV currents must be converted to the<br />

equivalent LV currents, or vice-versa.<br />

Choice <strong>of</strong> protective device on the primary side <strong>of</strong> the<br />

transformer<br />

As explained before, for low reference current, the protection may be by fuses or by<br />

circuit-breaker.<br />

When the reference current is high, the protection will be achieved by circuit-breaker.<br />

Protection by circuit-breaker provides a more sensitive transformer protection<br />

compared with fuses. The implementation <strong>of</strong> additional protections (earth fault<br />

protection, thermal overload protection) is easier with circuit-breakers.<br />

3.3 Interlocks and conditioned operations<br />

Mechanical and <strong>electrical</strong> interlocks are included on mechanisms and in the control<br />

circuits <strong>of</strong> apparatus installed in substations, as a measure <strong>of</strong> protection against an<br />

incorrect sequence <strong>of</strong> manœuvres by operating personnel.<br />

Mechanical protection between functions located on separate equipment<br />

(e.g. switchboard and transformer) is provided by key-transfer interlocking.<br />

An interlocking scheme is intended to prevent any abnormal operational manœuvre.<br />

Some <strong>of</strong> such operations would expose operating personnel to danger, some others<br />

would only lead to an <strong>electrical</strong> incident.<br />

Basic interlocking<br />

Basic interlocking functions can be introduced in one given functionnal unit; some<br />

<strong>of</strong> these functions are made mandatory by the IEC 62271-200, for metal-enclosed<br />

MV switchgear, but some others are the result <strong>of</strong> a choice from the user.<br />

Considering access to a MV panel, it requires a certain number <strong>of</strong> operations<br />

which shall be carried out in a pre-determined order. It is necessary to carry out<br />

operations in the reverse order to restore the system to its former condition. Either<br />

proper procedures, or dedicated interlocks, can ensure that the required operations<br />

are performed in the right sequence. Then such accessible compartment will be<br />

classified as “accessible and interlocked” or “accessible by procedure”. Even for<br />

users with proper rigorous procedures, use <strong>of</strong> interlocks can provide a further help<br />

for safety <strong>of</strong> the operators.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B19<br />

© Schneider Electric - all rights reserved


B20<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

(1) If the earthing switch is on an incoming circuit, the<br />

associated isolating switches are those at both ends <strong>of</strong> the<br />

circuit, and these should be suitably interlocked. In such<br />

situation, the interlocking function becomes a multi-units key<br />

interlock.<br />

3 Protection aspect<br />

Key interlocking<br />

Beyond the interlocks available within a given functionnal unit (see also 4.2), the<br />

most widely-used form <strong>of</strong> locking/interlocking depends on the principle <strong>of</strong> key transfer.<br />

The principle is based on the possibility <strong>of</strong> freeing or trapping one or several keys,<br />

according to whether or not the required conditions are satisfied.<br />

These conditions can be combined in unique and obligatory sequences, thereby<br />

guaranteeing the safety <strong>of</strong> personnel and <strong>installation</strong> by the avoidance <strong>of</strong> an incorrect<br />

operational procedure.<br />

Non-observance <strong>of</strong> the correct sequence <strong>of</strong> operations in either case may have<br />

extremely serious consequences for the operating personnel, as well as for the<br />

equipment concerned.<br />

Note: It is important to provide for a scheme <strong>of</strong> interlocking in the basic <strong>design</strong> stage<br />

<strong>of</strong> planning a MV/LV substation. In this way, the apparatuses concerned will be<br />

equipped during manufacture in a coherent manner, with assured compatibility <strong>of</strong><br />

keys and locking devices.<br />

Service continuity<br />

For a given MV switchboard, the definition <strong>of</strong> the accessible compartments as well<br />

as their access conditions provide the basis <strong>of</strong> the “Loss <strong>of</strong> Service Continuity”<br />

classification defined in the standard IEC 62271-200. Use <strong>of</strong> interlocks or only proper<br />

procedure does not have any influence on the service continuity. Only the request for<br />

accessing a given part <strong>of</strong> the switchboard, under normal operation conditions, results<br />

in limiting conditions which can be more or less severe regarding the continuity <strong>of</strong> the<br />

<strong>electrical</strong> distribution process.<br />

Interlocks in substations<br />

In a MV/LV distribution substation which includes:<br />

b A single incoming MV panel or two incoming panels (from parallel feeders) or two<br />

incoming/outgoing ring-main panels<br />

b A transformer switchgear-and-protection panel, which can include a load-break/<br />

disconnecting switch with MV fuses and an earthing switch, or a circuit-breaker and<br />

line disconnecting switch together with an earthing switch<br />

b A transformer compartment<br />

Interlocks allow manœuvres and access to different panels in the following conditions:<br />

Basic interlocks, embedded in single functionnal units<br />

b Operation <strong>of</strong> the load-break/isolating switch<br />

v If the panel door is closed and the associated earthing switch is open<br />

b Operation <strong>of</strong> the line-disconnecting switch <strong>of</strong> the transformer switchgear - and<br />

- protection panel<br />

v If the door <strong>of</strong> the panel is closed, and<br />

v If the circuit-breaker is open, and the earthing switch(es) is (are) open<br />

b Closure <strong>of</strong> an earthing switch<br />

v If the associated isolating switch(es) is (are) open (1)<br />

b Access to an accessible compartment <strong>of</strong> each panel, if interlocks have been<br />

specified<br />

v If the isolating switch for the compartment is open and the earthing switch(es) for<br />

the compartment is (are) closed<br />

b Closure <strong>of</strong> the door <strong>of</strong> each accessible compartment, if interlocks have been<br />

specified<br />

v If the earthing switch(es) for the compartment is (are) closed<br />

Functional interlocks involving several functional units or separate equipment<br />

b Access to the terminals <strong>of</strong> a MV/LV transformer<br />

v If the tee-<strong>of</strong>f functional unit has its switch open and its earthing switch closed.<br />

According to the possibility <strong>of</strong> back-feed from the LV side, a condition on the LV main<br />

breaker can be necessary.<br />

Practical example<br />

In a consumer-type substation with LV metering, the interlocking scheme most<br />

commonly used is MV/LV/TR (high voltage/ low voltage/transformer).<br />

The aim <strong>of</strong> the interlocking is:<br />

b To prevent access to the transformer compartment if the earthing switch has not<br />

been previously closed<br />

b To prevent the closure <strong>of</strong> the earthing switch in a transformer switchgear-andprotection<br />

panel, if the LV circuit-breaker <strong>of</strong> the transformer has not been previously<br />

locked “open” or “withdrawn”<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

S<br />

MV switch and LV CB closed<br />

O<br />

S<br />

MV fuses accessible<br />

S<br />

Fig. B20 : Example <strong>of</strong> MV/LV/TR interlocking<br />

O<br />

O<br />

Transformer MV terminals accessible<br />

Legend<br />

Key absent<br />

Key free<br />

Key trapped<br />

Panel or door<br />

(1) Or may be provided with a common protective cover over<br />

the three terminals.<br />

S<br />

S<br />

S<br />

O<br />

3 Protection aspect<br />

Access to the MV or LV terminals <strong>of</strong> a transformer, (protected upstream by a<br />

MV switchgear-and-protection panel, containing a MV load-break / isolating<br />

switch, MV fuses, and a MV earthing switch) must comply with the strict procedure<br />

described below, and is illustrated by the diagrams <strong>of</strong> Figure B20.<br />

Note: The transformer in this example is provided with plug-in type MV terminal<br />

connectors which can only be removed by unlocking a retaining device common to<br />

all three phase connectors (1) .<br />

The MV load-break / disconnecting switch is mechanically linked with the<br />

MV earthing switch such that only one <strong>of</strong> the switches can be closed, i.e. closure<br />

<strong>of</strong> one switch automatically locks the closure <strong>of</strong> the other.<br />

Procedure for the isolation and earthing <strong>of</strong> the power transformer, and removal<br />

<strong>of</strong> the MV plug-type shrouded terminal connections (or protective cover)<br />

Initial conditions<br />

b MV load-break/disconnection switch and LV circuit-breaker are closed<br />

b MV earthing switch locked in the open position by key “O”<br />

b Key “O” is trapped in the LV circuit-breaker as long as that circuit-breaker is closed<br />

Step 1<br />

b Open LV CB and lock it open with key “O”<br />

b Key “O” is then released<br />

Step 2<br />

b Open the MV switch<br />

b Check that the “voltage presence” indicators extinguish when the MV switch is<br />

opened<br />

Step 3<br />

b Unlock the MV earthing switch with key “O” and close the earthing switch<br />

b Key “O” is now trapped<br />

Step 4<br />

The access panel to the MV fuses can now be removed (i.e. is released by closure <strong>of</strong><br />

the MV earthing switch). Key “S” is located in this panel, and is trapped when the MV<br />

switch is closed<br />

b Turn key “S” to lock the MV switch in the open position<br />

b Key “S” is now released<br />

Step 5<br />

Key “S” allows removal <strong>of</strong> the common locking device <strong>of</strong> the plug-type MV terminal<br />

connectors on the transformer or <strong>of</strong> the common protective cover over the terminals,<br />

as the case may be.<br />

In either case, exposure <strong>of</strong> one or more terminals will trap key “S” in the interlock.<br />

The result <strong>of</strong> the foregoing procedure is that:<br />

b The MV switch is locked in the open position by key “S”.<br />

Key “S” is trapped at the transformer terminals interlock as long as the terminals are<br />

exposed.<br />

b The MV earthing switch is in the closed position but not locked, i.e. may be opened<br />

or closed. When carrying out maintenance work, a padlock is generally used to lock<br />

the earthing switch in the closed position, the key <strong>of</strong> the padlock being held by the<br />

engineer supervizing the work.<br />

b The LV CB is locked open by key “O”, which is trapped by the closed MV earthing<br />

switch. The transformer is therefore safely isolated and earthed.<br />

It may be noted that the upstream terminal <strong>of</strong> the load-break disconnecting switch<br />

may remain live in the procedure described as the terminals in question are located<br />

in a separate non accessible compartment in the particular switchgear under<br />

discussion. Any other technical solution with exposed terminals in the accessed<br />

compartment would need further de-energisation and interlocks.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B21<br />

© Schneider Electric - all rights reserved


B22<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

(1) Polychlorinated biphenyl<br />

4 The consumer substation<br />

with LV metering<br />

4.1 <strong>General</strong><br />

A consumer substation with LV metering is an <strong>electrical</strong> <strong>installation</strong> connected to a<br />

utility supply system at a nominal voltage <strong>of</strong> 1 kV - 35 kV, and includes a single<br />

MV/LV transformer generally not exceeding 1,250 kVA.<br />

Functions<br />

The substation<br />

All component parts <strong>of</strong> the substation are located in one room, either in an existing<br />

building, or in the form <strong>of</strong> a prefabricated housing exterior to the building.<br />

Connection to the MV network<br />

Connection at MV can be:<br />

b Either by a single service cable or overhead line, or<br />

b Via two mechanically interlocked load-break switches with two service cables from<br />

duplicate supply feeders, or<br />

b Via two load-break switches <strong>of</strong> a ring-main unit<br />

The transformer<br />

Since the use <strong>of</strong> PCB (1) -filled transformers is prohibited in most countries,<br />

the preferred available technologies are:<br />

b Oil-immersed transformers for substations located outside premises<br />

b Dry-type, vacuum-cast-resin transformers for locations inside premises, e.g.<br />

multistoreyed buildings, buildings receiving the public, and so on...<br />

Metering<br />

Metering at low voltage allows the use <strong>of</strong> small metering transformers at modest cost.<br />

Most tariff structures take account <strong>of</strong> MV/LV transformer losses.<br />

LV <strong>installation</strong> circuits<br />

A low-voltage circuit-breaker, suitable for isolation duty and locking <strong>of</strong>f facilities, to:<br />

b Supply a distribution board<br />

b Protect the transformer against overloading and the downstream circuits against<br />

short-circuit faults.<br />

One-line diagrams<br />

The diagrams on the following page (see Fig. B21) represent the different methods<br />

<strong>of</strong> MV service connection, which may be one <strong>of</strong> four types:<br />

b Single-line service<br />

b Single-line service (equipped for extension to form a ring main)<br />

b Duplicate supply service<br />

b Ring main service<br />

4.2 Choice <strong>of</strong> MV switchgear<br />

Standards and specifications<br />

The switchgear and equipment described below are rated for 1 kV - 24 kV systems<br />

and comply with the following international standards:<br />

IEC 62271-1, 62271-200, 60265-1, 62271-102, 62271-100, 62271-105<br />

Local regulations can also require compliance with national standards as:<br />

b France: UTE<br />

b United Kingdom: BS<br />

b Germany: VDE<br />

b United States <strong>of</strong> America: ANSI<br />

Type <strong>of</strong> equipment<br />

In addition <strong>of</strong> Ring Main Units discussed in section 1.2, all kinds <strong>of</strong> switchgear<br />

arrangements are possible when using modular switchgear, and provisions for later<br />

extensions are easily realized.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Power supply<br />

system<br />

Service<br />

connection<br />

Supplier/consumer<br />

interface<br />

Single-line service<br />

Single-line service<br />

(equipped for extension<br />

to form a ring main)<br />

Duplicatesupply<br />

service<br />

Fig. B21 : Consumer substation with LV metering<br />

4 The consumer substation<br />

with LV metering<br />

MV protection and<br />

MV/LV transformation<br />

Protection<br />

Permitted if only one<br />

transformer and rated power<br />

low enough to accomodate<br />

the limitations <strong>of</strong> fuses and<br />

combinations<br />

Protection<br />

Permitted if only one<br />

transformer and rated power<br />

low enough to accomodate<br />

the limitations <strong>of</strong> fuses and<br />

combinations<br />

Transformer<br />

LV terminals<br />

LV metering<br />

and isolation<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

LV distribution<br />

and protection<br />

Downstream terminals<br />

<strong>of</strong> LV isolator<br />

Protection<br />

Protection<br />

+<br />

Auto-changeover<br />

switch<br />

Ring main<br />

service<br />

Protection<br />

Automatic<br />

LV standby<br />

source<br />

Always permitted<br />

B23<br />

© Schneider Electric - all rights reserved


B24<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Fig. B22 : Metal enclosed MV load break disconnecting switch<br />

(1) Where MV fuses are used they are located in this<br />

compartment.<br />

4 The consumer substation<br />

with LV metering<br />

Operational safety <strong>of</strong> metal enclosed switchgear<br />

Description<br />

The following notes describe a “state-<strong>of</strong>-the art” load-break / disconnecting-switch<br />

panel (see Fig. B22) incorporating the most modern developments for ensuring:<br />

b Operational safety<br />

b Minimum space requirements<br />

b Extendibility and flexibility<br />

b Minimum maintenance requirements<br />

Each panel includes 3 compartments:<br />

b Switchgear: the load-break disconnecting switch is incorporated in an hermetically<br />

sealed (for life) molded epoxy-resin unit<br />

b Connections: by cable at terminals located on the molded switch unit<br />

b Busbars: modular, such that any number <strong>of</strong> panels may be assembled side-by-side<br />

to form a continuous switchboard, and for control and indication a low voltage cabinet<br />

which can accommodate automatic control and relaying equipment. An additional<br />

cabinet may be mounted above the existing one if further space is required.<br />

Cable connections are provided inside a cable-terminating compartment at the<br />

front <strong>of</strong> the unit, to which access is gained by removal <strong>of</strong> the front panel <strong>of</strong> the<br />

compartment.<br />

The units are connected <strong>electrical</strong>ly by means <strong>of</strong> prefabricated sections <strong>of</strong> busbars.<br />

Site erection is effected by following the assembly instructions.<br />

Operation <strong>of</strong> the switchgear is simplified by the grouping <strong>of</strong> all controls and<br />

indications on a control panel at the front <strong>of</strong> each unit.<br />

The technology <strong>of</strong> these switchgear units is essentially based on operational safety,<br />

ease <strong>of</strong> <strong>installation</strong> and low maintenance requirements.<br />

Switchgear internal safety measures<br />

b The load-break/disconnecting switch fully satisfies the requirement <strong>of</strong> “reliable<br />

position indicating device” as defined in IEC 62271-102 (disconnectors and earthing<br />

switches)<br />

b The functionnal unit incorporates the basic interlocks specified by the<br />

IEC 62271-200 (prefabricated metal enclosed switchgear and controlgear):<br />

v Closure <strong>of</strong> the switch is not possible unless the earth switch is open<br />

v Closure <strong>of</strong> the earthing switch is only possible if the load break/isolating switch is<br />

open<br />

b Access to the cable compartment, which is the only user-accessible compartment<br />

during operation, is secured by further interlocks:<br />

v Opening <strong>of</strong> the access panel to the cable terminations compartment (1) is only<br />

possible if the earthing switch is closed<br />

v The load-break/disconnecting switch is locked in the open position when the<br />

above-mentioned access panel is open. Opening <strong>of</strong> the earthing switch is then<br />

possible, for instance to allow a dielectric test on the cables.<br />

With such features, the switchboard can be operated with live busbars and cables,<br />

except for the unit where the access to cables is made. It complies then with the<br />

Loss <strong>of</strong> Service Continuity class LSB2A, as defined in the IEC 62271-200.<br />

Apart from the interlocks noted above, each switchgear panel includes:<br />

b Built-in padlocking facilities on the operation levers<br />

b 5 predrilled sets <strong>of</strong> fixing holes for possible future interlocking locks<br />

Operations<br />

b Operating handles, levers, etc. required for switching operations are grouped<br />

together on a clearly illustrated panel<br />

b All closing-operation levers are identical on all units (except those containing a<br />

circuit-breaker)<br />

b Operation <strong>of</strong> a closing lever requires very little effort<br />

b Opening or closing <strong>of</strong> a load-break/disconnecting switch can be by lever or by<br />

push-button for automatic switches<br />

b Conditions <strong>of</strong> switches (Open, Closed, Spring-charged), are clearly indicated<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

4 The consumer substation<br />

with LV metering<br />

4.3 Choice <strong>of</strong> MV switchgear panel for a transformer<br />

circuit<br />

Three types <strong>of</strong> MV switchgear panel are generally available:<br />

b Load-break switch and separate MV fuses in the panel<br />

b Load-break switch/MV fuses combination<br />

b Circuit-breaker<br />

Seven parameters influence the optimum choice:<br />

b The primary current <strong>of</strong> the transformer<br />

b The insulating medium <strong>of</strong> the transformer<br />

b The position <strong>of</strong> the substation with respect to the load centre<br />

b The kVA rating <strong>of</strong> the transformer<br />

b The distance from switchgear to the transformer<br />

b The use <strong>of</strong> separate protection relays (as opposed to direct-acting trip coils).<br />

Note: The fuses used in the load-break/switch fuses combination have striker-pins<br />

which ensure tripping <strong>of</strong> the 3-pole switch on the operation <strong>of</strong> one (or more) fuse(s).<br />

4.4 Choice <strong>of</strong> MV/LV transformer<br />

Characteristic parameters <strong>of</strong> a transformer<br />

A transformer is characterized in part by its <strong>electrical</strong> parameters, but also by its<br />

technology and its conditions <strong>of</strong> use.<br />

Electrical characteristics<br />

b Rated power (Pn): the conventional apparent-power in kVA on which other <strong>design</strong>parameter<br />

values and the construction <strong>of</strong> the transformer are based. Manufacturing<br />

tests and guarantees are referred to this rating<br />

b Frequency: for power distribution systems <strong>of</strong> the kind discussed in this guide, the<br />

frequency will be 50 Hz or 60 Hz<br />

b Rated primary and secondary voltages: For a primary winding capable <strong>of</strong> operating at<br />

more than one voltage level, a kVA rating corresponding to each level must be given.<br />

The secondary rated voltage is its open circuit value<br />

b Rated insulation levels are given by overvoltage-withstand test values at power<br />

frequency, and by high voltage impulse tests values which simulate lightning<br />

discharges. At the voltage levels discussed in this guide, overvoltages caused by<br />

MV switching operations are generally less severe than those due to lightning, so<br />

that no separate tests for switching-surge withstand capability are made<br />

b Off-circuit tap-selector switch generally allows a choice <strong>of</strong> up to ± 2.5% and ± 5%<br />

level about the rated voltage <strong>of</strong> the highest voltage winding. The transformer must be<br />

de-energized before this switch is operated<br />

b Winding configurations are indicated in diagrammatic form by standard symbols for<br />

star, delta and inter-connected-star windings; (and combinations <strong>of</strong> these for special<br />

duty, e.g. six-or twelve-phase rectifier transformers, etc.) and in an IEC-recommended<br />

alphanumeric code. This code is read from left-to-right, the first letter refers to the<br />

highest voltage winding, the second letter to the next highest, and so on:<br />

v Capital letters refer to the highest voltage winding<br />

D = delta<br />

Y = star<br />

Z = interconnected-star (or zigzag)<br />

N = neutral connection brought out to a terminal<br />

v Lower-case letters are used for tertiary and secondary windings<br />

d = delta<br />

y = star<br />

z = interconnected-star (or zigzag)<br />

n = neutral connection brought out to a terminal<br />

v A number from 0 to 11, corresponding to those, on a clock dial (“0” is used instead<br />

<strong>of</strong> “12”) follows any pair <strong>of</strong> letters to indicate the phase change (if any) which occurs<br />

during the transformation.<br />

A very common winding configuration used for distribution transformers is that<br />

<strong>of</strong> a Dyn 11 transformer, which has a delta MV winding with a star-connected<br />

secondary winding the neutral point <strong>of</strong> which is brought out to a terminal. The phase<br />

change through the transformer is +30 degrees, i.e. phase 1 secondary voltage is<br />

at “11 o’clock” when phase 1 <strong>of</strong> the primary voltage is at “12 o’clock”, as shown in<br />

Figure B31 page B34. All combinations <strong>of</strong> delta, star and zigzag windings produce a<br />

phase change which (if not zero) is either 30 degrees or a multiple <strong>of</strong> 30 degrees.<br />

IEC 60076-4 describes the “clock code” in detail.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B25<br />

© Schneider Electric - all rights reserved


B26<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Fig. B23 : Dry-type transformer<br />

4 The consumer substation<br />

with LV metering<br />

Characteristics related to the technology and utilization <strong>of</strong> the transformer<br />

This list is not exhaustive:<br />

b Choice <strong>of</strong> technology<br />

The insulating medium is:<br />

v Liquid (mineral oil) or<br />

v Solid (epoxy resin and air)<br />

b For indoor or outdoor <strong>installation</strong><br />

b Altitude (


B - Connection to the MV public<br />

distribution network<br />

Fig. B24 : Hermetically-sealed totally-filled tank<br />

Fig. B25 : Air-breathing conservator-type tank at atmosphere<br />

pressure<br />

4 The consumer substation<br />

with LV metering<br />

There are two ways in which this pressure limitation is commonly achieved:<br />

b Hermetically-sealed totally-filled tank (up to 10 MVA at the present time)<br />

Developed by a leading French manufacturer in 1963, this method was adopted by the<br />

national utility in 1972, and is now in world-wide service (see Fig. B24).<br />

Expansion <strong>of</strong> the liquid is compensated by the elastic deformation <strong>of</strong> the oil-cooling<br />

passages attached to the tank.<br />

The “total-fill” technique has many important advantages over other methods:<br />

v Oxydation <strong>of</strong> the dielectric liquid (with atmospheric oxygen) is entirely precluded<br />

v No need for an air-drying device, and so no consequent maintenance (inspection<br />

and changing <strong>of</strong> saturated dessicant)<br />

v No need for dielectric-strength test <strong>of</strong> the liquid for at least 10 years<br />

v Simplified protection against internal faults by means <strong>of</strong> a DGPT device is possible<br />

v Simplicity <strong>of</strong> <strong>installation</strong>: lighter and lower pr<strong>of</strong>ile (than tanks with a conservator)<br />

and access to the MV and LV terminals is unobstructed<br />

v Immediate detection <strong>of</strong> (even small) oil leaks; water cannot enter the tank<br />

b Air-breathing conservator-type tank at atmospheric pressure<br />

Expansion <strong>of</strong> the insulating liquid is taken up by a change in the level <strong>of</strong> liquid in<br />

an expansion (conservator) tank, mounted above the transformer main tank, as<br />

shown in Figure B25. The space above the liquid in the conservator may be filled<br />

with air which is drawn in when the level <strong>of</strong> liquid falls, and is partially expelled<br />

when the level rises. When the air is drawn in from the surrounding atmosphere it is<br />

admitted through an oil seal, before passing through a dessicating device (generally<br />

containing silica-gel crystals) before entering the conservator. In some <strong>design</strong>s <strong>of</strong><br />

larger transformers the space above the oil is occupied by an impermeable air bag<br />

so that the insulation liquid is never in contact with the atmosphere. The air enters<br />

and exits from the deformable bag through an oil seal and dessicator, as previously<br />

described. A conservator expansion tank is obligatory for transformers rated above<br />

10 MVA (which is presently the upper limit for “total-fill” type transformers).<br />

Choice <strong>of</strong> technology<br />

As discussed above, the choice <strong>of</strong> transformer is between liquid-filled or dry type.<br />

For ratings up to 10 MVA, totally-filled units are available as an alternative to<br />

conservator-type transformers.<br />

A choice depends on a number <strong>of</strong> considerations, including:<br />

b Safety <strong>of</strong> persons in proximity to the transformer. Local regulations and <strong>of</strong>ficial<br />

recommendations may have to be respected<br />

b Economic considerations, taking account <strong>of</strong> the relative advantages <strong>of</strong> each technique<br />

The regulations affecting the choice are:<br />

b Dry-type transformer:<br />

v In some countries a dry-type transformer is obligatory in high apartment blocks<br />

v Dry-type transformers impose no constraints in other situations<br />

b Transformers with liquid insulation:<br />

v This type <strong>of</strong> transformer is generally forbidden in high apartment blocks<br />

v For different kinds <strong>of</strong> insulation liquids, <strong>installation</strong> restrictions, or minimum<br />

protection against fire risk, vary according to the class <strong>of</strong> insulation used<br />

v Some countries in which the use <strong>of</strong> liquid dielectrics is highly developed, classify<br />

the several categories <strong>of</strong> liquid according to their fire performance. This latter is<br />

assessed according to two criteria: the flash-point temperature, and the minimum<br />

calorific power. The principal categories are shown in Figure B26 in which a<br />

classification code is used for convenience.<br />

As an example, French standard defines the conditions for the <strong>installation</strong> <strong>of</strong> liquidfilled<br />

transformers. No equivalent IEC standard has yet been established.<br />

The French standard is aimed at ensuring the safety <strong>of</strong> persons and property and<br />

recommends, notably, the minimum measures to be taken against the risk <strong>of</strong> fire.<br />

Code Dielectric fluid Flash-point Minimum calorific power<br />

(°C) (MJ/kg)<br />

O1 Mineral oil < 300 -<br />

K1 High-density hydrocarbons > 300 48<br />

K2 Esters > 300 34 - 37<br />

K3 Silicones > 300 27 - 28<br />

L3 Insulating halogen liquids - 12<br />

Fig. B26 : Categories <strong>of</strong> dielectric fluids<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B27<br />

© Schneider Electric - all rights reserved


B28<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

4 The consumer substation<br />

with LV metering<br />

The main precautions to observe are indicated in Figure B27.<br />

b For liquid dielectrics <strong>of</strong> class L3 there are no special measures to be taken<br />

b For dielectrics <strong>of</strong> classes O1 and K1 the measures indicated are applicable only if<br />

there are more than 25 litres <strong>of</strong> dielectric liquid in the transformer<br />

b For dielectrics <strong>of</strong> classes K2 and K3 the measures indicated are applicable only if<br />

there are more than 50 litres <strong>of</strong> dielectric liquid in the transformer.<br />

Class No. <strong>of</strong> Locations<br />

<strong>of</strong> litres above Chamber or enclosed area reserved to qualified Reserved to trained personnel Other chambers<br />

dielectric which and authorized personnel, and separated from any and isolated from work areas or locations (2)<br />

fluid measures other building by a distance D by fire-pro<strong>of</strong> walls (2 hours rating)<br />

must be D > 8 m 4 m < D < 8 m D < 4 m (1) in the direc- No openings With opening(s)<br />

taken tion <strong>of</strong> occupied areas<br />

O1 25 No special Interposition <strong>of</strong> Fire-pro<strong>of</strong> wall Measures Measures Measures<br />

measures a fire-pro<strong>of</strong> (2 hour rating) (1 + 2) (1 + 2 + 5) (1A + 2 + 4) (3)<br />

K1 screen against adjoining or 3 or 3 or 3<br />

(1 hour rating) building or 4 or (4 + 5)<br />

K2 50 No special measures Interposition <strong>of</strong> a No special Measures 1A Measures 1<br />

K3 fire-pro<strong>of</strong> screen measures or 3 or 3<br />

(1 hour rating) or 4 or 4<br />

L3 No special measures<br />

Measure 1: Arrangements such that if the dielectric escapes from the transformer, it will be completely contained (in a sump, by sills around the<br />

transformer, and by blocking <strong>of</strong> cable trenches, ducts and so on, during construction).<br />

Measure 1A: In addition to measure 1, arrange that, in the event <strong>of</strong> liquid ignition there is no possibility <strong>of</strong> the fire spreading (any combustible<br />

material must be moved to a distance <strong>of</strong> at least 4 metres from the transformer, or at least 2 metres from it if a fire-pro<strong>of</strong> screen [<strong>of</strong> 1 hour rating] is<br />

interposed).<br />

Measure 2: Arrange that burning liquid will extinguish rapidly and naturally (by providing a pebble bed in the containment sump).<br />

Measure 3: An automatic device (gas, pressure & thermal relay, or Buchholz) for cutting <strong>of</strong>f the primary power supply, and giving an alarm, if gas<br />

appears in the transformer tank.<br />

Measure 4: Automatic fire-detection devices in close proximity to the transformer, for cutting <strong>of</strong>f primary power supply, and giving an alarm.<br />

Measure 5: Automatic closure by fire-pro<strong>of</strong> panels (1/2 hour minimum rating) <strong>of</strong> all openings (ventilation louvres, etc.) in the walls and ceiling <strong>of</strong><br />

the substation chamber.<br />

Notes:<br />

(1) A fire-pro<strong>of</strong> door (rated at 2 hours) is not considered to be an opening.<br />

(2) Transformer chamber adjoining a workshop and separated from it by walls, the fire-pro<strong>of</strong> characteristics <strong>of</strong> which are not rated for 2 hours.<br />

Areas situated in the middle <strong>of</strong> workshops the material being placed (or not) in a protective container.<br />

(3) It is indispensable that the equipment be enclosed in a chamber, the walls <strong>of</strong> which are solid, the only orifices being those necessary for<br />

ventilation purposes.<br />

Fig. B27 : Safety measures recommended in <strong>electrical</strong> <strong>installation</strong>s using dielectric liquids <strong>of</strong> classes 01, K1, K2 or K3<br />

The determination <strong>of</strong> optimal power<br />

Oversizing a transformer<br />

It results in:<br />

b Excessive investment and unecessarily high no-load losses, but<br />

b Lower on-load losses<br />

Undersizing a transformer<br />

It causes:<br />

b A reduced efficiency when fully loaded, (the highest efficiency is attained in the<br />

range 50% - 70% full load) so that the optimum loading is not achieved<br />

b On long-term overload, serious consequences for<br />

v The transformer, owing to the premature ageing <strong>of</strong> the windings insulation, and in<br />

extreme cases, resulting in failure <strong>of</strong> insulation and loss <strong>of</strong> the transformer<br />

v The <strong>installation</strong>, if overheating <strong>of</strong> the transformer causes protective relays to trip<br />

the controlling circuit-breaker.<br />

Definition <strong>of</strong> optimal power<br />

In order to select an optimal power (kVA) rating for a transformer, the following<br />

factors must be taken into account:<br />

b List the power <strong>of</strong> installed power-consuming equipment as described in <strong>Chapter</strong> A<br />

b Decide the utilization (or demand) factor for each individual item <strong>of</strong> load<br />

b Determine the load cycle <strong>of</strong> the <strong>installation</strong>, noting the duration <strong>of</strong> loads and overloads<br />

b Arrange for power-factor correction, if justified, in order to:<br />

v Reduce cost penalties in tariffs based, in part, on maximum kVA demand<br />

v Reduce the value <strong>of</strong> declared load (P(kVA) = P (kW)/cos ϕ)<br />

b Select, among the range <strong>of</strong> standard transformer ratings available, taking into<br />

account all possible future extensions to the <strong>installation</strong>.<br />

It is important to ensure that cooling arrangements for the transformer are adequate.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Fig. B28 : SM6 metal enclosed indoor MV eqpuipment<br />

4 The consumer substation<br />

with LV metering<br />

4.5 Instructions for use <strong>of</strong> MV equipment<br />

The purpose <strong>of</strong> this chapter is to provide general guidelines on how to avoid<br />

or greatly reduce MV equipment degradation on sites exposed to humidity and<br />

pollution.<br />

Normal service conditions for indoor MV equipment<br />

All MV equipments comply with specific standards and with the IEC 62271-1<br />

standard “Common specifications for high-voltage switchgear and controlgear”,<br />

which defines the normal conditions for the <strong>installation</strong> and use <strong>of</strong> such equipment.<br />

For instance, regarding humidity, the standard mentions:<br />

The conditions <strong>of</strong> humidity are as follows:<br />

b The average value <strong>of</strong> the relative humidity, measured over a period <strong>of</strong> 24 h does<br />

not exceed 90%;<br />

b The average value <strong>of</strong> the water vapour pressure, over a period <strong>of</strong> 24 h does not<br />

exceed 2.2 kPa;<br />

b The average value <strong>of</strong> the relative humidity, over a period <strong>of</strong> one month does not<br />

exceed 90%;<br />

b The average value <strong>of</strong> water vapour pressure, over a period <strong>of</strong> one month does not<br />

exceed 1.8 kPa;<br />

Under these conditions, condensation may occasionally occur.<br />

NOTE 1: Condensation can be expected where sudden temperature changes occur<br />

in period <strong>of</strong> high humidity.<br />

NOTE 2: To withstand the effects <strong>of</strong> high humidity and condensation, such as a<br />

breakdown <strong>of</strong> insulation or corrosion <strong>of</strong> metallic parts, switchgear <strong>design</strong>ed for such<br />

conditions and tested accordingly shoul be used.<br />

NOTE 3: Condensation may be prevented by special <strong>design</strong> <strong>of</strong> the building or<br />

housing, by suitable ventilation and heating <strong>of</strong> the station or by use <strong>of</strong> dehumifying<br />

equipment.<br />

As indicated in the standard, condensation may occasionally occur even under<br />

normal conditions. The standard goes on to indicate special measures concerning<br />

the substation premises that can be implemented to prevent condensation.<br />

Use under severe conditions<br />

Under certain severe conditions concerning humidity and pollution, largely beyond<br />

the normal conditions <strong>of</strong> use mentioned above, correctly <strong>design</strong>ed <strong>electrical</strong><br />

equipment can be subject to damage by rapid corrosion <strong>of</strong> metal parts and surface<br />

degradation <strong>of</strong> insulating parts.<br />

Remedial measures for condensation problems<br />

b Carefully <strong>design</strong> or adapt substation ventilation.<br />

b Avoid temperature variations.<br />

b Eliminate sources <strong>of</strong> humidity in the substation environment.<br />

b Install an air conditioning system.<br />

b Make sure cabling is in accordance with applicable <strong>rules</strong>.<br />

Remedial measures for pollution problems<br />

b Equip substation ventilation openings with chevron-type baffles to reduce entry<br />

<strong>of</strong> dust and pollution.<br />

b Keep substation ventilation to the minimum required for evacuation <strong>of</strong> transformer<br />

heat to reduce entry <strong>of</strong> pollution and dust.<br />

b Use MV cubicles with a sufficiently high degree <strong>of</strong> protection (IP).<br />

b Use air conditioning systems with filters to restrict entry <strong>of</strong> pollution and dust.<br />

b Regularly clean all traces <strong>of</strong> pollution from metal and insulating parts.<br />

Ventilation<br />

Substation ventilation is generally required to dissipate the heat produced by<br />

transformers and to allow drying after particularly wet or humid periods.<br />

However, a number <strong>of</strong> studies have shown that excessive ventilation can drastically<br />

increase condensation.<br />

Ventilation should therefore be kept to the minimum level required.<br />

Furthermore, ventilation should never generate sudden temperature variations that<br />

can cause the dew point to be reached.<br />

For this reason:<br />

Natural ventilation should be used whenever possible. If forced ventilation is<br />

necessary, the fans should operate continuously to avoid temperature fluctuations.<br />

Guidelines for sizing the air entry and exit openings <strong>of</strong> substations are presented<br />

hereafter.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B29<br />

© Schneider Electric - all rights reserved


B30<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Fig. B29 : Natural ventilation<br />

200 mm<br />

mini<br />

Fig. B30 : Ventilation opening locations<br />

S<br />

S'<br />

H<br />

4 The consumer substation<br />

with LV metering<br />

Calculation methods<br />

A number <strong>of</strong> calculation methods are available to estimate the required size <strong>of</strong><br />

substation ventilation openings, either for the <strong>design</strong> <strong>of</strong> new substations or the<br />

adaptation <strong>of</strong> existing substations for which condensation problems have occurred.<br />

The basic method is based on transformer dissipation.<br />

The required ventilation opening surface areas S and S’ can be estimated using the<br />

following formulas:<br />

S � 1.8 x 10-4 P<br />

H<br />

and S'� 1.10 x S<br />

where:<br />

S = Lower (air entry) ventilation opening area [m²] (grid surface deducted)<br />

S’= Upper (air exit) ventilation opening area [m²] (grid surface deducted)<br />

P = Total dissipated power [W]<br />

P is the sum <strong>of</strong> the power dissipated by:<br />

b The transformer (dissipation at no load and due to load)<br />

b The LV switchgear<br />

b The MV switchgear<br />

H = Height between ventilation opening mid-points [m]<br />

See Fig. B29<br />

Note:<br />

This formula is valid for a yearly average temperature <strong>of</strong> 20 °C and a maximum<br />

altitude <strong>of</strong> 1,000 m.<br />

It must be noted that these formulae are able to determine only one order <strong>of</strong><br />

magnitude <strong>of</strong> the sections S and S', which are qualified as thermal section, i.e. fully<br />

open and just necessary to evacuate the thermal energy generated inside the MV/LV<br />

substation.<br />

The pratical sections are <strong>of</strong> course larger according ot the adopted technological<br />

solution.<br />

Indeed, the real air flow is strongly dependant:<br />

b on the openings shape and solutions adopted to ensure the cubicle protection<br />

index (IP): metal grid, stamped holes, chevron louvers,...<br />

b on internal components size and their position compared to the openings:<br />

transformer and/or retention oil box position and dimensions, flow channel between<br />

the components, ...<br />

b and on some physical and environmental parameters: outside ambient<br />

temperature, altitude, magnitude <strong>of</strong> the resulting temperature rise.<br />

The understanding and the optimization <strong>of</strong> the attached physical phenomena are<br />

subject to precise flow studies, based on the fluid dynamics laws, and realized with<br />

specific analytic s<strong>of</strong>tware.<br />

Example:<br />

Transformer dissipation = 7,970 W<br />

LV switchgear dissipation = 750 W<br />

MV switchgear dissipation = 300 W<br />

The height between ventilation opening mid-points is 1.5 m.<br />

Calculation:<br />

Dissipated Power P = 7,970 + 750 + 300 = 9,020 W<br />

S � 1.8 x 10-4 P<br />

1.5<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

� 1.32 m 2 and S'� 1.1 x 1.32 � 1.46 m 2<br />

Ventilation opening locations<br />

To favour evacuation <strong>of</strong> the heat produced by the transformer via natural convection,<br />

ventilation openings should be located at the top and bottom <strong>of</strong> the wall near the<br />

transformer. The heat dissipated by the MV switchboard is negligible.<br />

To avoid condensation problems, the substation ventilation openings should be<br />

located as far as possible from the switchboard (see Fig. B 30).


B - Connection to the MV public<br />

distribution network<br />

Fig. B31 : Chevron-blade baffles<br />

4 The consumer substation<br />

with LV metering<br />

Type <strong>of</strong> ventilation openings<br />

To reduce the entry <strong>of</strong> dust, pollution, mist, etc., the substation ventilation openings<br />

should be equipped with chevron-blade baffles.<br />

Always make sure the baffles are oriented in the right direction (see Fig. B31).<br />

Temperature variations inside cubicles<br />

To reduce temperature variations, always install anti-condensation heaters inside<br />

MV cubicles if the average relative humidity can remain high over a long period <strong>of</strong><br />

time. The heaters must operate continuously, 24 hours a day all year long.<br />

Never connect them to a temperature control or regulation system as this could lead<br />

to temperature variations and condensation as well as a shorter service life for the<br />

heating elements. Make sure the heaters <strong>of</strong>fer an adequate service life (standard<br />

versions are generally sufficient).<br />

Temperature variations inside the substation<br />

The following measures can be taken to reduce temperature variations inside the<br />

substation:<br />

b Improve the thermal insulation <strong>of</strong> the substation to reduce the effects <strong>of</strong> outdoor<br />

temperature variations on the temperature inside the substation.<br />

b Avoid substation heating if possible. If heating is required, make sure the regulation<br />

system and/or thermostat are sufficiently accurate and <strong>design</strong>ed to avoid excessive<br />

temperature swings (e.g. no greater than 1 °C).<br />

If a sufficiently accurate temperature regulation system is not available, leave the<br />

heating on continuously, 24 hours a day all year long.<br />

b Eliminate cold air drafts from cable trenches under cubicles or from openings in the<br />

substation (under doors, ro<strong>of</strong> joints, etc.).<br />

Substation environment and humidity<br />

Various factors outside the substation can affect the humidity inside.<br />

b Plants<br />

Avoid excessive plant growth around the substation.<br />

b Substation waterpro<strong>of</strong>ing<br />

The substation ro<strong>of</strong> must not leak. Avoid flat ro<strong>of</strong>s for which<br />

waterpro<strong>of</strong>ing is difficult to implement and maintain.<br />

b Humidity from cable trenches<br />

Make sure cable trenches are dry under all conditions.<br />

A partial solution is to add sand to the bottom <strong>of</strong> the cable trench.<br />

Pollution protection and cleaning<br />

Excessive pollution favours leakage current, tracking and flashover on insulators.<br />

To prevent MV equipment degradation by pollution, it is possible to either protect the<br />

equipment against pollution or regularly clean the resulting contamination.<br />

Protection<br />

Indoor MV switchgear can be protected by enclosures providing a sufficiently high<br />

degree <strong>of</strong> protection (IP).<br />

Cleaning<br />

If not fully protected, MV equipment must be cleaned regularly to prevent<br />

degradation by contamination from pollution.<br />

Cleaning is a critical process. The use <strong>of</strong> unsuitable products can irreversibly<br />

damage the equipment.<br />

For cleaning procedures, please contact your Schneider Electric correspondent.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B31<br />

© Schneider Electric - all rights reserved


B32<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

A consumer substation with MV metering<br />

is an <strong>electrical</strong> <strong>installation</strong> connected to a<br />

utility supply system at a nominal voltage <strong>of</strong><br />

1 kV - 35 kV and generally includes a single<br />

MV/LV transformer which exceeds 1,250 kVA,<br />

or several smaller transformers.<br />

The rated current <strong>of</strong> the MV switchgear does<br />

not normally exceed 400 A.<br />

5 The consumer substation<br />

with MV metering<br />

5.1 <strong>General</strong><br />

Functions<br />

The substation<br />

According to the complexity <strong>of</strong> the <strong>installation</strong> and the manner in which the load is<br />

divided, the substation:<br />

b Might include one room containing the MV switchboard and metering panel(s),<br />

together with the transformer(s) and low-voltage main distribution board(s),<br />

b Or might supply one or more transformer rooms, which include local LV distribution<br />

boards, supplied at MV from switchgear in a main substation, similar to that<br />

described above.<br />

These substations may be installed, either:<br />

b Inside a building, or<br />

b Outdoors in prefabricated housings.<br />

Connection to the MV network<br />

Connection at MV can be:<br />

b Either by a single service cable or overhead line, or<br />

b Via two mechanically interlocked load-break switches with two service cables from<br />

duplicate supply feeders, or<br />

b Via two load-break switches <strong>of</strong> a ring-main unit.<br />

Metering<br />

Before the <strong>installation</strong> project begins, the agreement <strong>of</strong> the power-supply utility<br />

regarding metering arrangements must be obtained.<br />

A metering panel will be incorporated in the MV switchboard. Voltage transformers<br />

and current transformers, having the necessary metering accuracy, may be included<br />

in the main incoming circuit-breaker panel or (in the case <strong>of</strong> the voltage transformer)<br />

may be installed separately in the metering panel.<br />

Transformer rooms<br />

If the <strong>installation</strong> includes a number <strong>of</strong> transformer rooms, MV supplies from the main<br />

substation may be by simple radial feeders connected directly to the transformers, or<br />

by duplicate feeders to each room, or again, by a ring-main, according to the degree<br />

<strong>of</strong> supply availability desired.<br />

In the two latter cases, 3-panel ring-main units will be required at each transformer<br />

room.<br />

Local emergency generators<br />

Emergency standby generators are intended to maintain a power supply to essential<br />

loads, in the event <strong>of</strong> failure <strong>of</strong> the power supply system.<br />

Capacitors<br />

Capacitors will be installed, according to requirements:<br />

b In stepped MV banks at the main substation, or<br />

b At LV in transformer rooms.<br />

Transformers<br />

For additional supply-security reasons, transformers may be arranged for automatic<br />

changeover operation, or for parallel operation.<br />

One-line diagrams<br />

The diagrams shown in Figure B32 next page represent:<br />

b The different methods <strong>of</strong> MV service connection, which may be one <strong>of</strong> four types:<br />

v Single-line service<br />

v Single-line service (equipped for extension to form a ring main)<br />

v Duplicate supply service<br />

v Ring main service<br />

b <strong>General</strong> protection at MV, and MV metering functions<br />

b Protection <strong>of</strong> outgoing MV circuits<br />

b Protection <strong>of</strong> LV distribution circuits<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

Power supply<br />

system<br />

Service connection MV protection<br />

and metering<br />

Supplier/consumer<br />

interface<br />

Single-line service<br />

Single-line service<br />

(equipped for<br />

extension to form<br />

a ring main)<br />

Duplicatesupply<br />

service<br />

Ring-main<br />

service<br />

Fig. B32 : Consumer substation with MV metering<br />

5 The consumer substation<br />

with MV metering<br />

MV distribution and protection<br />

<strong>of</strong> outgoing circuits<br />

Downstream terminals <strong>of</strong><br />

MV isolator for the <strong>installation</strong><br />

A single transformer<br />

Protection<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

LV distribution<br />

and protection<br />

LV terminals <strong>of</strong><br />

transformer<br />

Protection<br />

LV<br />

Automatic LV/MV<br />

standby source<br />

Protection<br />

+ automatic<br />

changeover<br />

feature<br />

Automatic LV<br />

standby source<br />

B33<br />

© Schneider Electric - all rights reserved


B34<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

MV distribution<br />

panels for<br />

which standby<br />

supply is<br />

required<br />

Automatic<br />

changeover<br />

panel<br />

Busbar<br />

transition<br />

panel<br />

From standby generator<br />

P y 20,000 kVA<br />

To remainder<br />

<strong>of</strong> the MV<br />

switchboard<br />

Fig. B33 : Section <strong>of</strong> MV switchboard including standby supply<br />

panel<br />

5 The consumer substation<br />

with MV metering<br />

5.2 Choice <strong>of</strong> panels<br />

A substation with MV metering includes, in addition to the panels described in 4.2,<br />

panels specifically <strong>design</strong>ed for metering and, if required, for automatic or manual<br />

changeover from one source to another.<br />

Metering and general protection<br />

These two functions are achieved by the association <strong>of</strong> two panels:<br />

b One panel containing the VT<br />

b The main MV circuit-breaker panel containing the CTs for measurement and<br />

protection<br />

The general protection is usually against overcurrent (overload and short-circuit) and<br />

earth faults. Both schemes use protective relays which are sealed by the powersupply<br />

utility.<br />

Substation including generators<br />

Generator in stand alone operation<br />

If the <strong>installation</strong> needs great power supply availability, a MV standby generator set<br />

can be used. In such a case, the <strong>installation</strong> must include an automatic changeover.<br />

In order to avoid any posssibility <strong>of</strong> parallel operation <strong>of</strong> the generator with the power<br />

supply network, a specific panel with automatic changeover is needed (see Fig. B33).<br />

b Protection<br />

Specific protective devices are intended to protect the generator itself. It must be<br />

noted that, due to the very low short-circuit power <strong>of</strong> the generator comparing with<br />

the power supply network, a great attention must be paid to protection discrimination.<br />

b Control<br />

A voltage regulator controlling an alternator is generally arranged to respond to a<br />

reduction <strong>of</strong> voltage at its terminals by automatically increasing the excitation current<br />

<strong>of</strong> the alternator, until the voltage is restored to normal. When it is intended that<br />

the alternator should operate in parallel with others, the AVR (Automatic Voltage<br />

Regulator) is switched to “parallel operation” in which the AVR control circuit is<br />

slightly modified (compounded) to ensure satisfactory sharing <strong>of</strong> kvars with the other<br />

parallel machines.<br />

When a number <strong>of</strong> alternators are operating in parallel under AVR control, an<br />

increase in the excitation current <strong>of</strong> one <strong>of</strong> them (for example, carried out manually<br />

after switching its AVR to Manual control) will have practically no effect on the voltage<br />

level. In fact, the alternator in question will simply operate at a lower power factor<br />

(more kVA, and therefore more current) than before.<br />

The power factor <strong>of</strong> all the other machines will automatically improve, such that the<br />

load power factor requirements are satisfied, as before.<br />

Generator operating in parallel with the utility supply network<br />

To connect a generator set on the network, the agreement <strong>of</strong> the power supply utility<br />

is usually required. <strong>General</strong>ly the equipement (panels, protection relays) must be<br />

approved by the utility.<br />

The following notes indicate some basic consideration to be taken into account for<br />

protection and control.<br />

b Protection<br />

To study the connection <strong>of</strong> generator set, the power supply utility needs some data<br />

as follows :<br />

v Power injected on the network<br />

v Connection mode<br />

v Short-circuit current <strong>of</strong> the generator set<br />

v Voltage unbalance <strong>of</strong> the generator<br />

v etc.<br />

Depending on the connection mode, dedicated uncoupling protection functions are<br />

required :<br />

v Under-voltage and over-voltage protection<br />

v Under-frequency and over-frequency protection<br />

v Zero sequence overvoltage protection<br />

v Maximum time <strong>of</strong> coupling (for momentary coupling)<br />

v Reverse real power<br />

For safety reasons, the switchgear used for uncoupling must also be provided<br />

with the characteristics <strong>of</strong> a disconnector (i.e total isolation <strong>of</strong> all active conductors<br />

between the generator set and the power supply network).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


B - Connection to the MV public<br />

distribution network<br />

5 The consumer substation<br />

with MV metering<br />

b Control<br />

When generators at a consumer’s substation operate in parallel with all the<br />

generation <strong>of</strong> the utility power supply system, supposing the power system voltage is<br />

reduced for operational reasons (it is common to operate MV systems within a range<br />

<strong>of</strong> ± 5% <strong>of</strong> nominal voltage, or even more, where load-flow patterns require it), an<br />

AVR set to maintain the voltage within ± 3% (for example) will immediately attempt to<br />

raise the voltage by increasing the excitation current <strong>of</strong> the alternator.<br />

Instead <strong>of</strong> raising the voltage, the alternator will simply operate at a lower power<br />

factor than before, thereby increasing its current output, and will continue to do so,<br />

until it is eventually tripped out by its overcurrent protective relays. This is a wellknown<br />

problem and is usually overcome by the provision <strong>of</strong> a “constant power-<br />

factor” control switch on the AVR unit.<br />

By making this selection, the AVR will automatically adjust the excitation current<br />

to match whatever voltage exists on the power system, while at the same time<br />

maintaining the power factor <strong>of</strong> the alternator constant at the pre-set value (selected<br />

on the AVR control unit).<br />

In the event that the alternator becomes decoupled from the power system, the AVR<br />

must be automatically (rapidly) switched back to “constant-voltage” control.<br />

5.3 Parallel operation <strong>of</strong> transformers<br />

The need for operation <strong>of</strong> two or more transformers in parallel <strong>of</strong>ten arises due to:<br />

b Load growth, which exceeds the capactiy <strong>of</strong> an existing transformer<br />

b Lack <strong>of</strong> space (height) for one large transformer<br />

b A measure <strong>of</strong> security (the probability <strong>of</strong> two transformers failing at the same time<br />

is very small)<br />

b The adoption <strong>of</strong> a standard size <strong>of</strong> transformer throughout an <strong>installation</strong><br />

Total power (kVA)<br />

The total power (kVA) available when two or more transformers <strong>of</strong> the same<br />

kVA rating are connected in parallel, is equal to the sum <strong>of</strong> the individual ratings,<br />

providing that the percentage impedances are all equal and the voltage ratios are<br />

identical.<br />

Transformers <strong>of</strong> unequal kVA ratings will share a load practically (but not exactly)<br />

in proportion to their ratings, providing that the voltage ratios are identical and the<br />

percentage impedances (at their own kVA rating) are identical, or very nearly so.<br />

In these cases, a total <strong>of</strong> more than 90% <strong>of</strong> the sum <strong>of</strong> the two ratings is normally<br />

available.<br />

It is recommended that transformers, the kVA ratings <strong>of</strong> which differ by more<br />

than 2:1, should not be operated permanently in parallel.<br />

Conditions necessary for parallel operation<br />

All paralleled units must be supplied from the same network.<br />

The inevitable circulating currents exchanged between the secondary circuits <strong>of</strong><br />

paralleled transformers will be negligibly small providing that:<br />

b Secondary cabling from the transformers to the point <strong>of</strong> paralleling have<br />

approximately equal lengths and characteristics<br />

b The transformer manufacturer is fully informed <strong>of</strong> the duty intended for the<br />

transformers, so that:<br />

v The winding configurations (star, delta, zigzag star) <strong>of</strong> the several transformers<br />

have the same phase change between primary and secondary voltages<br />

v The short-circuit impedances are equal, or differ by less than 10%<br />

v Voltage differences between corresponding phases must not exceed 0.4%<br />

v All possible information on the conditions <strong>of</strong> use, expected load cycles, etc. should<br />

be given to the manufacturer with a view to optimizing load and no-load losses<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B35<br />

© Schneider Electric - all rights reserved


B36<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

5 The consumer substation<br />

with MV metering<br />

Common winding arrangements<br />

As described in 4.4 “Electrical characteristics-winding configurations” the<br />

relationships between primary, secondary, and tertiary windings depend on:<br />

b Type <strong>of</strong> windings (delta, star, zigzag)<br />

b Connection <strong>of</strong> the phase windings<br />

Depending on which ends <strong>of</strong> the windings form the star point (for example), a<br />

star winding will produce voltages which are 180° displaced with respect to those<br />

produced if the opposite ends had been joined to form the star point. Similar 180°<br />

changes occur in the two possible ways <strong>of</strong> connecting phase-to-phase coils to form<br />

delta windings, while four different combinations <strong>of</strong> zigzag connections are possible.<br />

b The phase displacement <strong>of</strong> the secondary phase voltages with respect to the<br />

corresponding primary phase voltages.<br />

As previously noted, this displacement (if not zero) will always be a multiple <strong>of</strong><br />

30° and will depend on the two factors mentioned above, viz type <strong>of</strong> windings and<br />

connection (i.e. polarity) <strong>of</strong> the phase windings.<br />

By far the most common type <strong>of</strong> distribution transformer winding configuration is the<br />

Dyn 11 connection (see Fig. B34).<br />

Voltage vectors<br />

1<br />

Fig. B34 : Phase change through a Dyn 11 transformer<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

1<br />

2<br />

3<br />

V 12<br />

Windings<br />

correspondence<br />

V 12 on the primary winding produces V 1N in the<br />

secondary winding and so on ...<br />

2<br />

1<br />

3<br />

N<br />

N<br />

2<br />

1<br />

2<br />

3


B - Connection to the MV public<br />

distribution network<br />

6 Constitution <strong>of</strong><br />

MV/LV distribution substations<br />

MV/LV substations are constructed according to the magnitude <strong>of</strong> the load and the<br />

kind <strong>of</strong> power system in question.<br />

Substations may be built in public places, such as parks, residential districts, etc. or<br />

on private premises, in which case the power supply authority must have unrestricted<br />

access. This is normally assured by locating the substation, such that one <strong>of</strong> its<br />

walls, which includes an access door, coincides with the boundary <strong>of</strong> the consumers<br />

premises and the public way.<br />

6.1 Different types <strong>of</strong> substation<br />

Substations may be classified according to metering arrangements (MV or LV) and<br />

type <strong>of</strong> supply (overhead line or underground cable).<br />

The substations may be installed:<br />

b Either indoors in room specially built for the purpose, within a building, or<br />

b An outdoor <strong>installation</strong> which could be :<br />

v Installed in a dedicated enclosure prefabricated or not, with indoor equipment<br />

(switchgear and transformer)<br />

v Ground mounted with outdoor equipment (switchgear and transformers)<br />

v Pole mounted with dedicated outdoor equipment (swithgear and transformers)<br />

Prefabricated substations provide a particularly simple, rapid and competitive choice.<br />

6.2 Indoor substation<br />

Conception<br />

Figure B35 shows a typical equipment layout recommended for a LV metering<br />

substation.<br />

Remark: the use <strong>of</strong> a cast-resin dry-type transformer does not need a fireprotection<br />

oil sump. However, periodic cleaning is needed.<br />

MV connections to transformer<br />

(included in a panel or free-standing)<br />

2 incoming<br />

MV panels<br />

MV<br />

switching<br />

and<br />

protection<br />

panel<br />

Connection to the powersupply<br />

network by single-core<br />

or three-core cables,<br />

with or without a cable trench<br />

Fig. B35 : Typical arrangment <strong>of</strong> switchgear panels for LV metering<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

LV connections<br />

from<br />

transformer<br />

LV switchgear<br />

Current<br />

transformers<br />

provided by<br />

power-supply<br />

authority<br />

Transformer Oil sump LV cable<br />

trench<br />

B37<br />

© Schneider Electric - all rights reserved


B38<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

6 Constitution <strong>of</strong><br />

MV/LV distribution substations<br />

Service connections and equipment interconnections<br />

At high voltage<br />

b Connections to the MV system are made by, and are the responsibility <strong>of</strong> the utility<br />

b Connections between the MV switchgear and the transformers may be:<br />

v By short copper bars where the transformer is housed in a panel forming part <strong>of</strong><br />

the MV switchboard<br />

v By single-core screened cables with synthetic insulation, with possible use <strong>of</strong> plugin<br />

type terminals at the transformer<br />

At low voltage<br />

b Connections between the LV terminals <strong>of</strong> the transformer and the LV switchgear<br />

may be:<br />

v Single-core cables<br />

v Solid copper bars (circular or rectangular section) with heat-shrinkable insulation<br />

Metering (see Fig. B36)<br />

b Metering current transformers are generally installed in the protective cover <strong>of</strong> the<br />

power transformer LV terminals, the cover being sealed by the supply utility<br />

b Alternatively, the current transformers are installed in a sealed compartment within<br />

the main LV distribution cabinet<br />

b The meters are mounted on a panel which is completely free from vibrations<br />

b Placed as close to the current transformers as possible, and<br />

b Are accessible only to the utility<br />

100<br />

MV supply LV distribution<br />

Fig. B36 : Plan view <strong>of</strong> typical substation with LV metering<br />

Earthing circuits<br />

Common earth busbar<br />

for the substation<br />

The substation must include:<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Safety accessories<br />

800 mini<br />

Meters<br />

b An earth electrode for all exposed conductive parts <strong>of</strong> <strong>electrical</strong> equipment in the<br />

substation and exposed extraneous metal including:<br />

v Protective metal screens<br />

v Reinforcing rods in the concrete base <strong>of</strong> the substation<br />

Substation lighting<br />

Supply to the lighting circuits can be taken from a point upstream or downstream<br />

<strong>of</strong> the main incoming LV circuit-breaker. In either case, appropriate overcurrent<br />

protection must be provided. A separate automatic circuit (or circuits) is (are)<br />

recommended for emergency lighting purposes.<br />

Operating switches, pushbuttons, etc. are normally located immediately adjacent to<br />

entrances.<br />

Lighting fittings are arranged such that:<br />

b Switchgear operating handles and position indication markings are adequately<br />

illuminated<br />

b All metering dials and instruction plaques and so on, can be easily read


B - Connection to the MV public<br />

distribution network<br />

Walk-in Non walk-in Half buried<br />

a - b -<br />

Underground<br />

Fig. B38 : The four <strong>design</strong>s according to IEC 62271-202<br />

standard and two pictures [a] walk-in type MV/LV substation;<br />

[b] half buried type MV/LV substation<br />

6 Constitution <strong>of</strong><br />

MV/LV distribution substations<br />

Materials for operation and safety<br />

According to local safety <strong>rules</strong>, generally, the substation is provided with:<br />

b Materials for assuring safe exploitation <strong>of</strong> the equipment including:<br />

v Insulating stool and/or an insulating mat (rubber or synthetic)<br />

v A pair <strong>of</strong> insulated gloves stored in an envelope provided for the purpose<br />

v A voltage-detecting device for use on the MV equipment<br />

v Earthing attachments (according to type <strong>of</strong> switchgear)<br />

b Fire-extinguishing devices <strong>of</strong> the powder or CO2 type<br />

b Warning signs, notices and safety alarms:<br />

v On the external face <strong>of</strong> all access doors, a DANGER warning plaque and<br />

prohibition <strong>of</strong> entry notice, together with instructions for first-aid care for victims <strong>of</strong><br />

<strong>electrical</strong> accidents.<br />

6.3 Outdoor substations<br />

Outdoor substation with prefabricated enclosures<br />

A prefabricated MV/LV substation complying with IEC 62271-202 standard includes :<br />

b equipement in accordance with IEC standards<br />

b a type tested enclosure, which means during its <strong>design</strong>, it has undergone a battery<br />

<strong>of</strong> tests (see Fig. B37):<br />

v Degree <strong>of</strong> protection<br />

v Functional tests<br />

v Temperature class<br />

v Non-flammable materials<br />

v Mechanical resistance <strong>of</strong> the enclosure<br />

v Sound level<br />

v Insulation level<br />

v Internal arc withstand<br />

v Earthing circuit test<br />

v Oil retention,…<br />

Use <strong>of</strong> equipment conform<br />

to IEC standards:<br />

b Degree <strong>of</strong> protection<br />

b Electromagnetic<br />

compatibility<br />

b Functional tests<br />

b Temperature class<br />

b Non-flammable<br />

materials<br />

Fig. B37 : Type tested substation according to IEC 62271-202 standard<br />

Main benefits are :<br />

b Safety:<br />

v For public and operators thanks to a high reproducible quality level<br />

b Cost effective:<br />

v Manufactured, equipped and tested in the factory<br />

b Delivery time<br />

v Delivered ready to be connected.<br />

IEC 62271-202 standard includes four main <strong>design</strong>s (see Fig. B38)<br />

b Walk-in type substation :<br />

v Operation protected from bad weather conditions<br />

b Non walk-in substation<br />

v Ground space savings, and outdoors operations<br />

b Half buried substation<br />

v Limited visual impact<br />

b Underground substation<br />

v Blends completely into the environment.<br />

LV<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MV<br />

Earthing circuit test Oil retention<br />

Mechanical resistance<br />

<strong>of</strong> the enclosure:<br />

b Sound level<br />

b Insulation level<br />

b Internal arcing<br />

withstand<br />

B39<br />

© Schneider Electric - all rights reserved


B40<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Fig. B39 : Outdoor substations without enclosures<br />

6 Constitution <strong>of</strong><br />

MV/LV distribution substations<br />

Outdoor substations without enclosures (see Fig. B39)<br />

These kinds <strong>of</strong> outdoor substation are common in some countries, based on<br />

weatherpro<strong>of</strong> equipment exposed to the elements.<br />

These substations comprise a fenced area in which three or more concrete plinths<br />

are installed for:<br />

b A ring-main unit, or one or more switch-fuse or circuit-breaker unit(s)<br />

b One or more transformer(s), and<br />

b One or more LV distribution panel(s).<br />

Pole mounted substations<br />

Field <strong>of</strong> application<br />

These substations are mainly used to supply isolated rural consumers from MV<br />

overhead line distribution systems.<br />

Constitution<br />

In this type <strong>of</strong> substation, most <strong>of</strong>ten, the MV transformer protection is provided by<br />

fuses.<br />

Lightning arresters are provided, however, to protect the transformer and consumers<br />

as shown in Figure B40.<br />

<strong>General</strong> arrangement <strong>of</strong> equipment<br />

As previously noted the location <strong>of</strong> the substation must allow easy access, not only<br />

for personnel but for equipment handling (raising the transformer, for example) and<br />

the manœuvring <strong>of</strong> heavy vehicles.<br />

LV circuit breaker D1<br />

Safety earth mat<br />

Fig. B40 : Pole-mounted transformer substation<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Lightning<br />

arresters<br />

Earthing conductor 25 mm 2 copper<br />

Protective conductor cover


2<br />

<strong>Chapter</strong> C<br />

Connection to the LV utility<br />

distribution network<br />

Contents<br />

Low-voltage utility distribution networks C2<br />

1.1 Low-voltage consumers C2<br />

1.2 Low-voltage distribution networks C10<br />

1.3 The consumer service connection C11<br />

1.4 Quality <strong>of</strong> supply voltage C15<br />

Tariffs and metering C 6<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

C2<br />

C - Connecion to the LV public<br />

distribution network<br />

The most-common LV supplies are within the<br />

range 120 V single phase to 240/415 V<br />

3-phase 4-wires.<br />

Loads up to 250 kVA can be supplied at LV, but<br />

power-supply organizations generally propose<br />

a MV service at load levels for which their<br />

LV networks are marginally adequate.<br />

An international voltage standard for 3-phase<br />

4-wire LV systems is recommended by the<br />

IEC 60038 to be 230/400 V<br />

Low-voltage utility distribution<br />

networks<br />

. Low-voltage consumers<br />

In Europe, the transition period on the voltage tolerance to “230V/400V + 10% / - 10%”<br />

has been extended for another 5 years up to the year 2008.<br />

Low-voltage consumers are, by definition, those consumers whose loads can be<br />

satisfactorily supplied from the low-voltage system in their locality.<br />

The voltage <strong>of</strong> the local LV network may be 120/208 V or 240/415 V, i.e. the lower<br />

or upper extremes <strong>of</strong> the most common 3-phase levels in general use, or at some<br />

intermediate level, as shown in Figure C .<br />

An international voltage standard for 3-phase 4-wire LV systems is recommended<br />

by the IEC 60038 to be 230/400 V.<br />

Loads up to 250 kVA can be supplied at LV, but power-supply organizations<br />

generally propose a MV service at load levels for which their LV networks are<br />

marginally adequate.<br />

Country Frequency & tolerance Domestic (V) Commercial (V) Industrial (V)<br />

(Hz & %)<br />

Afghanistan 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k)<br />

Algeria 50 ± 1.5 220/127 (e) 380/220 (a) 10,000<br />

220 (k) 220/127 (a) 5,500<br />

6,600<br />

380/220 (a)<br />

Angola 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k)<br />

Antigua and Barbuda 60 240 (k) 400/230 (a) 400/230 (a)<br />

120 (k) 120/208 (a) 120/208 (a)<br />

Argentina 50 ± 2 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Armenia 50 ± 5 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Australia 50 ± 0.1 415/240 (a) 415/240 (a) 22,000<br />

240 (k) 440/250 (a) 11,000<br />

440 (m) 6,600<br />

415/240<br />

440/250<br />

Austria 50 ± 0.1 230 (k) 380/230 (a) (b) 5,000<br />

230 (k) 380/220 (a)<br />

Azerbaijan 50 ± 0.1 208/120 (a) 208/120 (a)<br />

240/120 (k) 240/120 (k)<br />

Bahrain 50 ± 0.1 415/240 (a) 415/240 (a) 11,000<br />

240 (k) 240 (k) 415/240 (a)<br />

240 (k)<br />

Bangladesh 50 ± 2 410/220 (a) 410/220 (a) 11,000<br />

220 (k) 410/220 (a)<br />

Barbados 50 ± 6 230/115 (j) 230/115 (j) 230/400 (g)<br />

115 (k) 200/115 (a) 230/155 (j)<br />

220/115 (a)<br />

Belarus 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

220/127 (a)<br />

127 (k)<br />

Belgium 50 ± 5 230 (k) 230 (k) 6,600<br />

230 (a) 230 (a) 10,000<br />

3N, 400 3N, 400 11,000<br />

15,000<br />

Bolivia 50 ± 0.5 230 (k) 400/230 (a) 400/230 (a)<br />

230 (k)<br />

Botswana 50 ± 3 220 (k) 380/220 (a) 380/220 (a)<br />

Brazil 60 220 (k) 220/380 (a) 13,800<br />

127 (k) 127/220 (a) 11,200<br />

220/380 (a)<br />

127/220 (a)<br />

Brunei 50 ± 2 230 230 11,000<br />

68,000<br />

Bulgaria 50 ± 0.1 220 220/240 1,000<br />

690<br />

380<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


C - Connecion to the LV public<br />

distribution network<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Low-voltage utility distribution<br />

networks<br />

Country Frequency & tolerance<br />

(Hz & %)<br />

Domestic (V) Commercial (V) Industrial (V)<br />

Cambodia 50 ± 1 220 (k) 220/300 220/380<br />

Cameroon 50 ± 1 220/260 (k) 220/260 (k) 220/380 (a)<br />

Canada 60 ± 0.02 120/240 (j) 347/600 (a) 7,200/12,500<br />

480 (f) 347/600 (a)<br />

240 (f) 120/208<br />

120/240 (j) 600 (f)<br />

120/208 (a) 480 (f)<br />

240 (f)<br />

Cape Verde 220 220 380/400<br />

Chad 50 ± 1 220 (k) 220 (k) 380/220 (a)<br />

Chile 50 ± 1 220 (k) 380/220 (a) 380/220 (a)<br />

China 50 ± 0.5 220 (k) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Colombia 60 ± 1 120/240 (g) 120/240 (g) 13,200<br />

120 (k) 120 (k) 120/240 (g)<br />

Congo 50 220 (k) 240/120 (j)<br />

120 (k)<br />

380/220 (a)<br />

Croatia 50 400/230 (a) 400/230 (a) 400/230 (a)<br />

230 (k) 230 (k)<br />

Cyprus 50 ± 0.1 240 (k) 415/240 11,000<br />

415/240<br />

Czech Republic 50 ± 1 230 500 400,000<br />

230/400 220,000<br />

110,000<br />

35,000<br />

22,000<br />

10,000<br />

6,000<br />

3,000<br />

Denmark 50 ± 1 400/230 (a) 400/230 (a) 400/230 (a)<br />

Djibouti 50 400/230 (a) 400/230 (a)<br />

Dominica 50 230 (k) 400/230 (a) 400/230 (a)<br />

Egypt 50 ± 0.5 380/220 (a) 380/220 (a) 66,000<br />

220 (k) 220 (k) 33,000<br />

20,000<br />

11,000<br />

6,600<br />

380/220 (a)<br />

Estonia 50 ± 1 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Ethiopia 50 ± 2.5 220 (k) 380/231 (a) 15 000<br />

380/231 (a)<br />

Falkland Islands 50 ± 3 230 (k) 415/230 (a) 415/230 (a)<br />

Fidji Islands 50 ± 2 415/240 (a) 415/240 (a) 11,000<br />

240 (k) 240 (k) 415/240 (a)<br />

Finland 50 ± 0.1 230 (k) 400/230 (a) 690/400 (a)<br />

400/230 (a)<br />

France 50 ± 1 400/230 (a) 400/230 20,000<br />

230 (a) 690/400 10,000<br />

590/100 230/400<br />

Gambia 50 220 (k) 220/380 380<br />

Georgia 50 ± 0.5 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Germany 50 ± 0.3 400/230 (a) 400/230 (a) 20,000<br />

230 (k) 230 (k) 10,000<br />

6,000<br />

690/400<br />

400/230<br />

Ghana 50 ± 5 220/240 220/240 415/240 (a)<br />

Gibraltar 50 ± 1 415/240 (a) 415/240 (a) 415/240 (a)<br />

Greece 50 220 (k) 6,000 22,000<br />

230 380/220 (a) 20,000<br />

15,000<br />

6,600<br />

Granada 50 230 (k) 400/230 (a) 400/230 (a)<br />

Hong Kong 50 ± 2 220 (k) 380/220 (a) 11,000<br />

220 (k) 386/220 (a)<br />

Hungary 50 ± 5 220 220 220/380<br />

Iceland 50 ± 0.1 230 230/400 230/400<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

C<br />

C - Connecion to the LV public<br />

distribution network<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Low-voltage utility distribution<br />

networks<br />

Country Frequency & tolerance Domestic (V) Commercial (V) Industrial (V)<br />

(Hz & %)<br />

India 50 ± 1.5 440/250 (a) 440/250 (a) 11,000<br />

230 (k) 230 (k) 400/230 (a)<br />

440/250 (a)<br />

Indonesia 50 ± 2 220 (k) 380/220 (a) 150,000<br />

20,000<br />

380/220 (a)<br />

Iran 50 ± 5 220 (k) 380/220 (a) 20,000<br />

11,000<br />

400/231 (a)<br />

380/220 (a)<br />

Iraq 50 220 (k) 380/220 (a) 11,000<br />

6,600<br />

3,000<br />

380/220 (a)<br />

Ireland 50 ± 2 230 (k) 400/230 (a) 20,000<br />

10,000<br />

400/230 (a)<br />

Israel 50 ± 0.2 400/230 (a) 400/230 (a) 22,000<br />

230 (k) 230 (k) 12,600<br />

6,300<br />

400/230 (a)<br />

Italy 50 ± 0.4 400/230 (a) 400/230 (a) 20,000<br />

230 (k) 15,000<br />

10,000<br />

400/230 (a)<br />

Jamaica 50 ± 1 220/110 (g) (j) 220/110 (g) (j) 4,000<br />

2,300<br />

220/110 (g)<br />

Japan (east) + 0.1 200/100 (h) 200/100 (h) 140,000<br />

- 0.3 (up to 50 kW) 60,000<br />

20,000<br />

6,000<br />

200/100 (h)<br />

Jordan 50 380/220 (a) 380/220 (a) 400 (a)<br />

400/230 (k)<br />

Kazakhstan 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

220/127 (a)<br />

127 (k)<br />

Kenya 50 240 (k) 415/240 (a) 415/240 (a)<br />

Kirghizia 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

220/127 (a)<br />

127 (k)<br />

Korea (North) 60 +0, -5 220 (k) 220/380 (a) 13,600<br />

6,800<br />

Korea (South) 60 100 (k) 100/200 (j)<br />

Kuwait 50 ± 3 240 (k) 415/240 (a) 415/240 (a)<br />

Laos 50 ± 8 380/220 (a) 380/220 (a) 380/220 (a)<br />

Lesotho 220 (k) 380/220 (a) 380/220 (a)<br />

Latvia 50 ± 0.4 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Lebanon 50 220 (k) 380/220 (a) 380/220 (a)<br />

Libya 50 230 (k) 400/230 (a) 400/230 (a)<br />

127 (k) 220/127 (a) 220/127 (a)<br />

230 (k)<br />

127 (k)<br />

Lithuania 50 ± 0.5 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Luxembourg 50 ± 0.5 380/220 (a) 380/220 (a) 20,000<br />

15,000<br />

5,000<br />

Macedonia 50 380/220 (a) 380/220 (a) 10,000<br />

220 (k) 220 (k) 6,600<br />

380/220 (a)<br />

Madagascar 50 220/110 (k) 380/220 (a) 35,000<br />

5,000<br />

380/220<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


C - Connecion to the LV public<br />

distribution network<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Low-voltage utility distribution<br />

networks<br />

Country Frequency & tolerance<br />

(Hz & %)<br />

Domestic (V) Commercial (V) Industrial (V)<br />

Malaysia 50 ± 1 240 (k)<br />

415 (a)<br />

415/240 (a) 415/240 (a)<br />

Malawi 50 ± 2.5 230 (k) 400 (a)<br />

230 (k)<br />

400 (a)<br />

Mali 50 220 (k) 380/220 (a) 380/220 (a)<br />

127 (k) 220/127 (a)<br />

220 (k)<br />

127 (k)<br />

220/127 (a)<br />

Malta 50 ± 2 240 (k) 415/240 (a) 415/240 (a)<br />

Martinique 50 127 (k) 220/127 (a)<br />

127 (k)<br />

220/127 (a)<br />

Mauritania 50 ± 1 230 (k) 400/230 (a) 400/230 (a)<br />

Mexico 60 ± 0.2 127/220 (a) 127/220 (a) 13,800<br />

220 (k) 220 (k) 13,200<br />

120 (l) 120 (l) 277/480 (a)<br />

127/220 (b)<br />

Moldavia 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k)<br />

220/127 (a)<br />

127 (k)<br />

220 (k)<br />

Morocco 50 ± 5 380/220 (a) 380/220 (a) 225,000<br />

220/110 (a) 150,000<br />

60,000<br />

22,000<br />

20,000<br />

Mozambique 50 380/220 (a) 380/220 (a) 6,000<br />

10,000<br />

Nepal 50 ± 1 220 (k) 440/220 (a) 11,000<br />

220 (k) 440/220 (a)<br />

Netherlands 50 ± 0.4 230/400 (a) 230/400 (a) 25,000<br />

230 (k) 20,000<br />

12,000<br />

10,000<br />

230/400<br />

New Zealand 50 ± 1.5 400/230 (e) (a) 400/230 (e) (a) 11,000<br />

230 (k)<br />

460/230 (e)<br />

230 (k) 400/230 (a)<br />

Niger 50 ± 1 230 (k) 380/220 (a) 15,000<br />

380/220 (a)<br />

Nigeria 50 ± 1 230 (k) 400/230 (a) 15,000<br />

220 (k) 380/220 (a) 11,000<br />

400/230 (a)<br />

380/220 (a)<br />

Norway 50 ± 2 230/400 230/400 230/400<br />

690<br />

Oman 50 240 (k) 415/240 (a)<br />

240 (k)<br />

415/240 (a)<br />

Pakistan 50 230 (k) 400/230 (a)<br />

230 (k)<br />

400/230 (a)<br />

Papua New Guinea 50 ± 2 240 (k) 415/240 (a) 22,000<br />

240 (k) 11,000<br />

415/240 (a)<br />

Paraguay 50 ± 0.5 220 (k) 380/220 (a) 22,000<br />

220 (k) 380/220 (a)<br />

Philippines (Rep <strong>of</strong> the) 60 ± 0.16 110/220 (j) 13,800 13,800<br />

4,160 4,160<br />

2,400 2,400<br />

110/220 (h) 440 (b)<br />

110/220 (h)<br />

Poland 50 ± 0.1 230 (k) 400/230 (a) 1,000<br />

690/400<br />

400/230 (a)<br />

Portugal 50 ± 1 380/220 (a) 15,000 15,000<br />

220 (k) 5,000 5,000<br />

380/220 (a)<br />

220 (k)<br />

380/220 (a)<br />

Qatar 50 ± 0.1 415/240 (k) 415/240 (a) 11,000<br />

415/240 (a)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

C6<br />

C - Connecion to the LV public<br />

distribution network<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Low-voltage utility distribution<br />

networks<br />

Country Frequency & tolerance Domestic (V) Commercial (V) Industrial (V)<br />

(Hz & %)<br />

Romania 50 ± 0.5 220 (k) 220/380 (a) 20,000<br />

220/380 (a) 10,000<br />

6,000<br />

220/380 (a)<br />

Russia 50 ± 0.2 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

Rwanda 50 ± 1 220 (k) 380/220 (a) 15,000<br />

6,600<br />

380/220 (a)<br />

Saint Lucia 50 ± 3 240 (k) 415/240 (a) 11,000<br />

415/240 (a)<br />

Samoa 400/230<br />

San Marino 50 ± 1 230/220 380 15,000<br />

380<br />

Saudi Arabia 60 220/127 (a) 220/127 (a) 11,000<br />

380/220 (a) 7,200<br />

380/220 (a)<br />

The Solomon Islands 50 ± 2 240 415/240 415/240<br />

Senegal 50 ± 5 220 (a) 380/220 (a) 90,000<br />

127 (k) 220/127 (k) 30,000<br />

6,600<br />

Serbia and Montenegro 50 380/220 (a) 380/220 (a) 10,000<br />

220 (k) 220 (k) 6,600<br />

380/220 (a)<br />

Seychelles 50 ± 1 400/230 (a) 400/230 (a) 11,000<br />

400/230 (a)<br />

Sierra Leone 50 ± 5 230 (k) 400/230 (a) 11,000<br />

230 (k) 400<br />

Singapore 50 400/230 (a) 400/230 (a) 22,000<br />

230 (k) 6,600<br />

400/230 (a)<br />

Slovakia 50 ± 0.5 230 230 230/400<br />

Slovenia 50 ± 0.1 220 (k) 380/220 (a) 10,000<br />

6,600<br />

380/220 (a)<br />

Somalia 50 230 (k) 440/220 (j) 440/220 (g)<br />

220 (k) 220/110 (j) 220/110 (g)<br />

110 (k) 230 (k)<br />

South Africa 50 ± 2.5 433/250 (a) 11,000 11,000<br />

400/230 (a) 6,600 6,600<br />

380/220 (a) 3,300 3,300<br />

220 (k) 433/250 (a) 500 (b)<br />

400/230 (a) 380/220 (a)<br />

380/220 (a)<br />

Spain 50 ± 3 380/220 (a) (e) 380/220 (a) 15,000<br />

220 (k) 220/127 (a) (e) 11,000<br />

220/127 (a) 380/220 (a)<br />

127 (k)<br />

Sri Lanka 50 ± 2 230 (k) 400/230 (a) 11,000<br />

230 (k) 400/230 (a)<br />

Sudan 50 240 (k) 415/240 (a) 415/240 (a)<br />

240 (k)<br />

Swaziland 50 ± 2.5 230 (k) 400/230 (a) 11,000<br />

230 (k) 400/230 (a)<br />

Sweden 50 ± 0.5 400/230 (a) 400/230 (a) 6,000<br />

230 (k) 230 (k) 400/230 (a)<br />

Switzerland 50 ± 2 400/230 (a) 400/230 (a) 20,000<br />

10,000<br />

3,000<br />

1,000<br />

690/500<br />

Syria 50 220 (k) 380/220 (a) 380/220 (a)<br />

115 (k) 220 (k)<br />

200/115 (a)<br />

Tadzhikistan 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k)<br />

220/127 (a)<br />

127 (k)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


C - Connecion to the LV public<br />

distribution network<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (continued on next page)<br />

Low-voltage utility distribution<br />

networks<br />

Country Frequency & tolerance<br />

(Hz & %)<br />

Domestic (V) Commercial (V) Industrial (V)<br />

Tanzania 50 400/230 (a) 400/230 (a) 11,000<br />

400/230 (a)<br />

Thailand 50 220 (k) 380/220 (a)<br />

220 (k)<br />

380/220 (a)<br />

Togo 50 220 (k) 380/220 (a) 20,000<br />

5,500<br />

380/220 (a)<br />

Tunisia 50 ± 2 380/220 (a) 380/220 (a) 30,000<br />

220 (k) 220 (k) 15,000<br />

10,000<br />

380/220 (a)<br />

Turkmenistan 50 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k)<br />

220/127 (a)<br />

127 (k)<br />

220 (k)<br />

Turkey 50 ± 1 380/220 (a) 380/220 (a) 15,000<br />

6,300<br />

380/220 (a)<br />

Uganda + 0.1 240 (k) 415/240 (a) 11,000<br />

415/240 (a)<br />

Ukraine + 0.2 / - 1.5 380/220 (a) 380/220 (a) 380/220 (a)<br />

220 (k) 220 (k) 220 (k)<br />

United Arab Emirates 50 ± 1 220 (k) 415/240 (a) 6,600<br />

380/220 (a) 415/210 (a)<br />

220 (k) 380/220 (a)<br />

United Kingdom 50 ± 1 230 (k) 400/230 (a) 22,000<br />

(except Northern 11,000<br />

Ireland) 6,600<br />

3,300<br />

400/230 (a)<br />

United Kingdom 50 ± 0.4 230 (k) 400/230 (a) 400/230 (a)<br />

(Including Northern<br />

Ireland)<br />

220 (k) 380/220 (a) 380/220 (a)<br />

United States <strong>of</strong> 60 ± 0.06 120/240 (j) 265/460 (a) 14,400<br />

America 120/208 (a) 120/240 (j) 7,200<br />

Charlotte 120/208 (a) 2,400<br />

(North Carolina) 575 (f)<br />

460 (f)<br />

240 (f)<br />

265/460 (a)<br />

120/240 (j)<br />

120/208 (a)<br />

United States <strong>of</strong> 60 ± 0.2 120/240 (j) 480 (f) 13,200<br />

America 120/208 (a) 120/240 (h) 4,800<br />

Detroit (Michigan) 120/208 (a) 4,160<br />

480 (f)<br />

120/240 (h)<br />

120/208 (a)<br />

United States <strong>of</strong> 60 ± 0.2 120/240 (j) 4,800 4,800<br />

America<br />

Los Angeles (California)<br />

120/240 (g) 120/240 (g)<br />

United States <strong>of</strong> 60 ± 0.3 120/240 (j) 120/240 (j) 13,200<br />

America 120/208 (a) 120/240 (h) 2,400<br />

Miami (Florida) 120/208 (a) 480/277 (a)<br />

120/240 (h)<br />

United States <strong>of</strong> 60 120/240 (j) 120/240 (j) 12,470<br />

America New York 120/208 (a) 120/208 (a) 4,160<br />

(New York) 240 (f) 277/480 (a)<br />

480 (f)<br />

United States <strong>of</strong> 60 ± 0.03 120/240 (j) 265/460 (a) 13,200<br />

America 120/240 (j) 11,500<br />

Pittsburg 120/208 (a) 2,400<br />

(Pennsylvania) 460 (f) 265/460 (a)<br />

230 (f) 120/208 (a)<br />

460 (f)<br />

230 (f)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

C<br />

C - Connecion to the LV public<br />

distribution network<br />

Country Frequency & tolerance Domestic (V) Commercial (V) Industrial (V)<br />

(Hz & %)<br />

United States <strong>of</strong> 60 120/240 (j) 227/480 (a) 19,900<br />

America 120/240 (j) 12,000<br />

Portland (Oregon) 120/208 (a) 7,200<br />

480 (f) 2,400<br />

240 (f) 277/480 (a)<br />

120/208 (a)<br />

480 (f)<br />

240 (f)<br />

United States <strong>of</strong> 60 ± 0.08 120/240 (j) 277/480 (a) 20,800<br />

America 120/240 (j) 12,000<br />

San Francisco 4,160<br />

(California) 277/480 (a)<br />

120/240 (g)<br />

United States <strong>of</strong> 60 ± 0.08 120/240 (j) 277/480 (c) 12,470<br />

America 120/208 (a) 120/240(h) 7,200<br />

Toledo (Ohio) 120/208 (j) 4,800<br />

4,160<br />

480 (f)<br />

277/480 (a)<br />

120/208 (a)<br />

Uruguay 50 ± 1 220 (b) (k) 220 (b) (k) 15,000<br />

6,000<br />

220 (b)<br />

Vietnam 50 ± 0.1 220 (k) 380/220 (a) 35,000<br />

15,000<br />

10,000<br />

6,000<br />

Yemen 50 250 (k) 440/250 (a) 440/250 (a)<br />

Zambia 50 ± 2.5 220 (k) 380/220 (a) 380 (a)<br />

Zimbabwe 50 225 (k) 390/225 (a) 11,000<br />

390/225 (a)<br />

Circuit diagrams<br />

(a) Three-phase star;<br />

Four-wire:<br />

Earthed neutral<br />

(f) Three-phase delta:<br />

Three-wire<br />

(j) Single-phase;<br />

Three-wire:<br />

Earthed mid point<br />

(b) Three-phase star:<br />

Three-wire<br />

(g) Three-phase delta;<br />

Four-wire:<br />

Earthed mid point <strong>of</strong><br />

one phase<br />

(k) Single-phase;<br />

Two-wire:<br />

Earthed end <strong>of</strong> phase<br />

(l) Single-phase;<br />

Two-wire<br />

Unearthed<br />

Fig. C1 : Voltage <strong>of</strong> local LV network and their associated circuit diagrams (concluded)<br />

Low-voltage utility distribution<br />

networks<br />

(c) Three-phase star;<br />

Three-wire:<br />

Earthed neutral<br />

(h) Three-phase open delta;<br />

Four-wire:<br />

Earthed mid point <strong>of</strong> one<br />

phase<br />

V Vk<br />

(m) Single-wire:<br />

Earthed return (swer)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

(d) Three-phase star;<br />

Four-wire:<br />

Non-earthed neutral<br />

(e) Two-phase star;<br />

Three-wire<br />

Earthed neutral<br />

(i) Three-phase<br />

open delta:<br />

Earthed junction<br />

<strong>of</strong> phases<br />

(n) DC:<br />

Three-wire:<br />

Unearthed


C - Connecion to the LV public<br />

distribution network<br />

(1) The Figure C2 values shown are indicative only, being<br />

(arbitrarily) based on 60 A maximum service currents for the<br />

first three systems, since smaller voltage drops are allowed at<br />

these lower voltages, for a given percentage statutory limit.<br />

The second group <strong>of</strong> systems is (again, arbitrarily) based on a<br />

maximum permitted service current <strong>of</strong> 120 A.<br />

Low-voltage utility distribution<br />

networks<br />

Residential and commercial consumers<br />

The function <strong>of</strong> a LV “mains” distributor is to provide service connections<br />

(underground cable or overhead line) to a number <strong>of</strong> consumers along its route.<br />

The current-rating requirements <strong>of</strong> distributors are estimated from the number <strong>of</strong><br />

consumers to be connected and an average demand per consumer.<br />

The two principal limiting parameters <strong>of</strong> a distributor are:<br />

b The maximum current which it is capable <strong>of</strong> carrying indefinitely, and<br />

b The maximum length <strong>of</strong> cable which, when carrying its maximum current, will not<br />

exceed the statutory voltage-drop limit<br />

These constraints mean that the magnitude <strong>of</strong> loads which utilities are willing to<br />

connect to their LV distribution mains, is necessarily restricted.<br />

For the range <strong>of</strong> LV systems mentioned in the second paragraph <strong>of</strong> this sub-clause<br />

(1.1) viz: 120 V single phase to 240/415 V 3-phase, typical maximum permitted loads<br />

connected to a LV distributor might (1) be (see Fig. C2):<br />

System Assumed max. permitted current kVA<br />

per consumer service<br />

120 V 1-phase 2-wire 60 A 7.2<br />

120/240 V 1-phase 3-wire 60 A 14.4<br />

120/208 V 3-phase 4-wire 60 A 22<br />

220/380 V 3-phase 4-wire 120 A 80<br />

230/400 V 3-phase 4-wire 120 A 83<br />

240/415 V 3-phase 4-wire 120 A 86<br />

Fig. C2 : Typical maximum permitted loads connected to a LV distributor<br />

Practices vary considerably from one power supply organization to another, and no<br />

“standardized” values can be given.<br />

Factors to be considered include:<br />

b The size <strong>of</strong> an existing distribution network to which the new load is to be connected<br />

b The total load already connected to the distribution network<br />

b The location along the distribution network <strong>of</strong> the proposed new load, i.e. close to<br />

the substation, or near the remote end <strong>of</strong> the distribution network, etc<br />

In short, each case must be examined individually.<br />

The load levels listed above are adequate for all normal residential consumers, and<br />

will be sufficient for the <strong>installation</strong>s <strong>of</strong> many administrative, commercial and similar<br />

buildings.<br />

Medium-size and small industrial consumers (with dedicated<br />

LV lines direct from a utility supply MV/LV substation)<br />

Medium and small industrial consumers can also be satisfactorily supplied at lowvoltage.<br />

For loads which exceed the maximum permitted limit for a service from a distributor,<br />

a dedicated cable can usually be provided from the LV distribution fuse- (or switch-)<br />

board, in the power utility substation.<br />

<strong>General</strong>y, the upper load limit which can be supplied by this means is restricted only<br />

by the available spare transformer capacity in the substation.<br />

In practice, however:<br />

b Large loads (e.g. > 300 kVA) require correspondingly large cables, so that,<br />

unless the load centre is close to the substation, this method can be economically<br />

unfavourable<br />

b Many utilities prefer to supply loads exceeding 200 kVA (this figure varies with<br />

different suppliers) at medium voltage<br />

For these reasons, dedicated supply lines at LV are generally applied (at 220/380 V<br />

to 240/415 V) to a load range <strong>of</strong> 80 kVA to 250 kVA.<br />

Consumers normally supplied at low voltage include:<br />

b Residential dwellings<br />

b Shops and commercial buildings<br />

b Small factories, workshops and filling stations<br />

b Restaurants<br />

b Farms, etc<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


C 0<br />

© Schneider Electric - all rights reserved<br />

C - Connecion to the LV public<br />

distribution network<br />

In cities and large towns, standardized<br />

LV distribution cables form a network through<br />

link boxes. Some links are removed, so that<br />

each (fused) distributor leaving a substation<br />

forms a branched open-ended radial system,<br />

as shown in Figure C3<br />

Low-voltage utility distribution<br />

networks<br />

.2 LV distribution networks<br />

In European countries the standard 3-phase 4-wire distribution voltage level is<br />

230/400 V. Many countries are currently converting their LV systems to the latest IEC<br />

standard <strong>of</strong> 230/400 V nominal (IEC 60038). Medium<br />

to large-sized towns and cities have underground cable distribution systems.<br />

MV/LV distribution substations, mutually spaced at approximately 500-600 metres,<br />

are typically equipped with:<br />

b A 3-or 4-way MV switchboard, <strong>of</strong>ten made up <strong>of</strong> incoming and outgoing loadbreak<br />

switches forming part <strong>of</strong> a ring main, and one or two MV circuit-breakers or<br />

combined fuse/ load-break switches for the transformer circuits<br />

b One or two 1,000 kVA MV/LV transformers<br />

b One or two (coupled) 6-or 8-way LV 3-phase 4-wire distribution fuse boards, or<br />

moulded-case circuit-breaker boards, control and protect outgoing 4-core distribution<br />

cables, generally referred to as “distributors”<br />

The output from a transformer is connected to the LV busbars via a load-break<br />

switch, or simply through isolating links.<br />

In densely-loaded areas, a standard size <strong>of</strong> distributor is laid to form a network,<br />

with (generally) one cable along each pavement and 4-way link boxes located in<br />

manholes at street corners, where two cables cross.<br />

Recent trends are towards weather-pro<strong>of</strong> cabinets above ground level, either against<br />

a wall, or where possible, flush-mounted in the wall.<br />

Links are inserted in such a way that distributors form radial circuits from the<br />

substation with open-ended branches (see Fig. C3). Where a link box unites a<br />

distributor from one substation with that from a neighbouring substation, the phase<br />

links are omitted or replaced by fuses, but the neutral link remains in place.<br />

Service<br />

cable<br />

Fig. C3 : Showing one <strong>of</strong> several ways in which a LV distribution network may be arranged for<br />

radial branched-distributor operation, by removing (phase) links<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

HV/LV<br />

substation<br />

4-way<br />

link box<br />

Phase links<br />

removed


C - Connecion to the LV public<br />

distribution network<br />

In less-densely loaded urban areas a moreeconomic<br />

system <strong>of</strong> tapered radial distribution<br />

is commonly used, in which conductors <strong>of</strong><br />

reduced size are installed as the distance from<br />

a substation increases<br />

Improved methods using insulated twisted<br />

conductors to form a pole mounted aerial cable<br />

are now standard practice in many countries<br />

In Europe, each utility-supply distribution<br />

substation is able to supply at LV an area<br />

corresponding to a radius <strong>of</strong> approximately<br />

300 metres from the substation.<br />

North and Central American systems <strong>of</strong><br />

distribution consist <strong>of</strong> a MV network from which<br />

numerous (small) MV/LV transformers each<br />

supply one or several consumers, by direct<br />

service cable (or line) from the transformer<br />

location<br />

Service components and metering equipment<br />

were formerly installed inside a consumer’s<br />

building. The modern tendency is to locate<br />

these items outside in a weatherpro<strong>of</strong> cabinet<br />

Low-voltage utility distribution<br />

networks<br />

This arrangement provides a very flexible system in which a complete substation can<br />

be taken out <strong>of</strong> service, while the area normally supplied from it is fed from link boxes<br />

<strong>of</strong> the surrounding substations.<br />

Moreover, short lengths <strong>of</strong> distributor (between two link boxes) can be isolated for<br />

fault-location and repair.<br />

Where the load density requires it, the substations are more closely spaced, and<br />

transformers up to 1,500 kVA are sometimes necessary.<br />

Other forms <strong>of</strong> urban LV network, based on free-standing LV distribution pillars,<br />

placed above ground at strategic points in the network, are widely used in areas <strong>of</strong><br />

lower load density. This scheme exploits the principle <strong>of</strong> tapered radial distributors in<br />

which the distribution cable conductor size is reduced as the number <strong>of</strong> consumers<br />

downstream diminish with distance from the substation.<br />

In this scheme a number <strong>of</strong> large-sectioned LV radial feeders from the distribution<br />

board in the substation supply the busbars <strong>of</strong> a distribution pillar, from which smaller<br />

distributors supply consumers immediately surrounding the pillar.<br />

Distribution in market towns, villages and rural areas generally has, for many years,<br />

been based on bare copper conductors supported on wooden, concrete or steel<br />

poles, and supplied from pole-mounted or ground-mounted transformers.<br />

In recent years, LV insulated conductors, twisted to form a two-core or 4-core self<br />

supporting cable for overhead use, have been developed, and are considered to be<br />

safer and visually more acceptable than bare copper lines.<br />

This is particularly so when the conductors are fixed to walls (e.g. under-eaves<br />

wiring) where they are hardly noticeable.<br />

As a matter <strong>of</strong> interest, similar principles have been applied at higher voltages, and<br />

self supporting “bundled” insulated conductors for MV overhead <strong>installation</strong>s are now<br />

available for operation at 24 kV.<br />

Where more than one substation supplies a village, arrangements are made at poles<br />

on which the LV lines from different substations meet, to interconnect corresponding<br />

phases.<br />

North and Central American practice differs fundamentally from that in Europe, in<br />

that LV networks are practically nonexistent, and 3-phase supplies to premises in<br />

residential areas are rare.<br />

The distribution is effectively carried out at medium voltage in a way, which again<br />

differs from standard European practices. The MV system is, in fact, a 3-phase<br />

4-wire system from which single-phase distribution networks (phase and neutral<br />

conductors) supply numerous single-phase transformers, the secondary windings<br />

<strong>of</strong> which are centre-tapped to produce 120/240 V single-phase 3-wire supplies.<br />

The central conductors provide the LV neutrals, which, together with the MV neutral<br />

conductors, are solidly earthed at intervals along their lengths.<br />

Each MV/LV transformer normally supplies one or several premises directly from the<br />

transformer position by radial service cable(s) or by overhead line(s).<br />

Many other systems exist in these countries, but the one described appears to be<br />

the most common.<br />

Figure C (next page) shows the main features <strong>of</strong> the two systems.<br />

. The consumer-service connection<br />

In the past, an underground cable service or the wall-mounted insulated conductors<br />

from an overhead line service, invariably terminated inside the consumer’s premises,<br />

where the cable-end sealing box, the utility fuses (inaccessible to the consumer) and<br />

meters were installed.<br />

A more recent trend is (as far as possible) to locate these service components in a<br />

weatherpro<strong>of</strong> housing outside the building.<br />

The utility/consumer interface is <strong>of</strong>ten at the outgoing terminals <strong>of</strong> the meter(s) or,<br />

in some cases, at the outgoing terminals <strong>of</strong> the <strong>installation</strong> main circuit-breaker<br />

(depending on local practices) to which connection is made by utility staff, following a<br />

satisfactory test and inspection <strong>of</strong> the <strong>installation</strong>.<br />

A typical arrangement is shown in Figure C (next page).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


C 2<br />

© Schneider Electric - all rights reserved<br />

C - Connecion to the LV public<br />

distribution network<br />

1 2 3<br />

1<br />

2<br />

13.8 kV / 2.4-4.16 kV<br />

Fig. C4 : Widely-used American and European-type systems<br />

N<br />

Each MV/LV transformer shown<br />

represents many similar units<br />

2.4 kV / 120-240 V<br />

1 ph - 3 wire<br />

distribution<br />

transformer<br />

N<br />

N<br />

Low-voltage utility distribution<br />

networks<br />

2<br />

3<br />

N<br />

1<br />

N<br />

2<br />

N<br />

HV (1)<br />

MV (2)<br />

Fig. C5 : Typical service arrangement for TT-earthed systems<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

For primary voltages > 72.5 kV<br />

(see note) primary<br />

winding may be:<br />

- Delta<br />

- Earthed star<br />

- Earthed zigzag<br />

Depending on the country concerned<br />

Tertiary delta normally<br />

(not always) used if the<br />

primary winding is not delta<br />

1 ph MV / 230 V<br />

service transformer<br />

to isolated consumer(s)<br />

(rural supplies)<br />

Resistor replaced<br />

by a Petersen<br />

coil on O/H line<br />

systems in some<br />

countries<br />

Ph N<br />

1 2 3 N<br />

N<br />

N 1 2 3<br />

Main 3 ph and neutral<br />

MV distributor<br />

LV distribution network<br />

(1) 132 kV for example<br />

(2) 11 kV for example<br />

Note: At primary voltages greater than 72.5 kV in bulk-supply substations, it is common practice in some European countries<br />

to use an earthed-star primary winding and a delta secondary winding. The neutral point on the secondary side is then<br />

provided by a zigzag earthing reactor, the star point <strong>of</strong> which is connected to earth through a resistor.<br />

Frequently, the earthing reactor has a secondary winding to provide LV 3-phase supplies for the substation. It is then referred<br />

to as an “earthing transformer”.<br />

CB<br />

M<br />

F<br />

A<br />

}<br />

3 ph<br />

MV / 230/400 V<br />

4-wire distribution<br />

transformer


C - Connecion to the LV public<br />

distribution network<br />

LV consumers are normally supplied according<br />

to the TN or TT system, as described in<br />

chapters F and G. The <strong>installation</strong> main circuitbreaker<br />

for a TT supply must include a residual<br />

current earth-leakage protective device. For a<br />

TN service, overcurrent protection by circuitbreaker<br />

or switch-fuse is required<br />

Low-voltage utility distribution<br />

networks<br />

A MCCB -moulded case circuit-breaker- which incorporates a sensitive residualcurrent<br />

earth-fault protective feature is mandatory at the origin <strong>of</strong> any LV <strong>installation</strong><br />

forming part <strong>of</strong> a TT earthing system. The reason for this feature and related<br />

leakage-current tripping levels are discussed in Clause 3 <strong>of</strong> <strong>Chapter</strong> G.<br />

A further reason for this MCCB is that the consumer cannot exceed his (contractual)<br />

declared maximum load, since the overload trip setting, which is sealed by the<br />

supply authority, will cut <strong>of</strong>f supply above the declared value. Closing and tripping <strong>of</strong><br />

the MCCB is freely available to the consumer, so that if the MCCB is inadvertently<br />

tripped on overload, or due to an appliance fault, supplies can be quickly restored<br />

following correction <strong>of</strong> the anomaly.<br />

In view <strong>of</strong> the inconvenience to both the meter reader and consumer, the location <strong>of</strong><br />

meters is nowadays generally outside the premises, either:<br />

b In a free-standing pillar-type housing as shown in Figures C6 and C<br />

b In a space inside a building, but with cable termination and supply authority’s fuses<br />

located in a flush-mounted weatherpro<strong>of</strong> cabinet accessible from the public way, as<br />

shown in Figure C next page<br />

b For private residential consumers, the equipment shown in the cabinet in<br />

Figure C5 is installed in a weatherpro<strong>of</strong> cabinet mounted vertically on a metal<br />

frame in the front garden, or flush-mounted in the boundary wall, and accessible to<br />

authorized personnel from the pavement. Figure C (next page) shows the general<br />

arrangement, in which removable fuse links provide the means <strong>of</strong> isolation<br />

Fig. C6 : Typical rural-type <strong>installation</strong><br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F<br />

A<br />

M<br />

CB<br />

In this kind <strong>of</strong> <strong>installation</strong> it is <strong>of</strong>ten necessary to place the main <strong>installation</strong> circuitbreaker<br />

some distance from the point <strong>of</strong> utilization, e.g. saw-mills, pumping stations,<br />

etc.<br />

The main <strong>installation</strong> CB is located in the consumer’s premises in cases where it is<br />

set to trip if the declared kVA load demand is exceeded.<br />

CB<br />

Fig. C7 : Semi-urban <strong>installation</strong>s (shopping precincts, etc.)<br />

M<br />

F<br />

A<br />

C<br />

© Schneider Electric - all rights reserved


C<br />

© Schneider Electric - all rights reserved<br />

C - Connecion to the LV public<br />

distribution network<br />

Low-voltage utility distribution<br />

networks<br />

The service cable terminates in a flushmounted wall cabinet which contains the<br />

isolating fuse links, accessible from the public way. This method is preferred for<br />

esthetic reasons, when the consumer can provide a suitable metering and mainswitch<br />

location.<br />

Fig. C8 : Town centre <strong>installation</strong>s<br />

Service cable<br />

Isolation by<br />

fuse links<br />

Meter cabinet<br />

Fig. C9 : Typical LV service arrangement for residential consumers<br />

In the field <strong>of</strong> electronic metering, techniques have developed which make their<br />

use attractive by utilities either for electricity metering and for billing purposes, the<br />

liberalisation <strong>of</strong> the electricity market having increased the needs for more data<br />

collection to be returned from the meters. For example electronic metering can also<br />

help utilities to understand their customers’ consumption pr<strong>of</strong>iles. In the same way,<br />

they will be useful for more and more power line communication and radio-frequency<br />

applications as well.<br />

In this area, prepayment systems are also more and more employed when<br />

economically justified. They are based on the fact that for instance consumers having<br />

made their payment at vending stations, generate tokens to pass the information<br />

concerning this payment on to the meters. For these systems the key issues are<br />

security and inter-operability which seem to have been addressed successfully<br />

now. The attractiveness <strong>of</strong> these systems is due to the fact they not only replace the<br />

meters but also the billing systems, the reading <strong>of</strong> meters and the administration <strong>of</strong><br />

the revenue collection.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Meter<br />

F<br />

A<br />

Interface<br />

Utility<br />

Main<br />

circuit<br />

breaker<br />

CB<br />

M<br />

Consumer<br />

Installation


C - Connecion to the LV public<br />

distribution network<br />

An adequate level <strong>of</strong> voltage at the consumers<br />

supply-service terminals is essential for<br />

satisfactory operation <strong>of</strong> equipment and<br />

appliances. Practical values <strong>of</strong> current, and<br />

resulting voltage drops in a typical LV system,<br />

show the importance <strong>of</strong> maintaining a high<br />

Power Factor as a means <strong>of</strong> reducing voltage<br />

drop.<br />

(1) Transformers <strong>design</strong>ed for the 230/400 V IEC standard<br />

will have a no-load output <strong>of</strong> 420 V, i.e. 105% <strong>of</strong> the nominal<br />

voltage<br />

Low-voltage utility distribution<br />

networks<br />

. Quality <strong>of</strong> supply voltage<br />

The quality <strong>of</strong> the LV network supply voltage in its widest sense implies:<br />

b Compliance with statutory limits <strong>of</strong> magnitude and frequency<br />

b Freedom from continual fluctuation within those limits<br />

b Uninterrupted power supply, except for scheduled maintenance shutdowns, or as a<br />

result <strong>of</strong> system faults or other emergencies<br />

b Preservation <strong>of</strong> a near-sinusoidal wave form<br />

In this Sub-clause the maintenance <strong>of</strong> voltage magnitude only will be discussed.<br />

In most countries, power-supply authorities have a statutory obligation to maintain<br />

the level <strong>of</strong> voltage at the service position <strong>of</strong> consumers within the limits <strong>of</strong> ± 5% (or<br />

in some cases ± 6% or more-see table C1) <strong>of</strong> the declared nominal value.<br />

Again, IEC and most national standards recommend that LV appliances be <strong>design</strong>ed<br />

and tested to perform satisfactorily within the limits <strong>of</strong> ± 10% <strong>of</strong> nominal voltage. This<br />

leaves a margin, under the worst conditions (<strong>of</strong> minus 5% at the service position, for<br />

example) <strong>of</strong> 5% allowable voltage drop in the <strong>installation</strong> wiring.<br />

The voltage drops in a typical distribution system occur as follows: the voltage at<br />

the MV terminals <strong>of</strong> a MV/LV transformer is normally maintained within a ± 2% band<br />

by the action <strong>of</strong> automatic onload tapchangers <strong>of</strong> the transformers at bulk-supply<br />

substations, which feed the MV network from a higher-voltage subtransmission<br />

system.<br />

If the MV/LV transformer is in a location close to a bulk-supply substation, the ± 2%<br />

voltage band may be centered on a voltage level which is higher than the nominal<br />

MV value. For example, the voltage could be 20.5 kV ± 2% on a 20 kV system. In this<br />

case, the MV/LV distribution transformer should have its MV <strong>of</strong>f-circuit tapping switch<br />

selected to the + 2.5% tap position.<br />

Conversely, at locations remote from bulk supply substations a value <strong>of</strong> 19.5 kV ±<br />

2% is possible, in which case the <strong>of</strong>f-circuit tapping switch should be selected to the<br />

- 5% position.<br />

The different levels <strong>of</strong> voltage in a system are normal, and depend on the system<br />

powerflow pattern. Moreover, these voltage differences are the reason for the term<br />

“nominal” when referring to the system voltage.<br />

Practical application<br />

With the MV/LV transformer correctly selected at its <strong>of</strong>f-circuit tapping switch, an<br />

unloaded transformer output voltage will be held within a band <strong>of</strong> ± 2% <strong>of</strong> its no-load<br />

voltage output.<br />

To ensure that the transformer can maintain the necessary voltage level when fully<br />

loaded, the output voltage at no-load must be as high as possible without exceeding<br />

the upper + 5% limit (adopted for this example). In present-day practice, the winding<br />

ratios generally give an output voltage <strong>of</strong> about 104% at no-load (1) , when nominal<br />

voltage is applied at MV, or is corrected by the tapping switch, as described above.<br />

This would result in a voltage band <strong>of</strong> 102% to 106% in the present case.<br />

A typical LV distribution transformer has a short-circuit reactance voltage <strong>of</strong> 5%. If it<br />

is assumed that its resistance voltage is one tenth <strong>of</strong> this value, then the voltage drop<br />

within the transformer when supplying full load at 0.8 power factor lagging, will be:<br />

V% drop = R% cos ϕ + X% sin ϕ<br />

= 0.5 x 0.8 + 5 x 0.6<br />

= 0.4 + 3 = 3.4%<br />

The voltage band at the output terminals <strong>of</strong> the fully-loaded transformer will therefore<br />

be (102 - 3.4) = 98.6% to (106 - 3.4) = 102.6%.<br />

The maximum allowable voltage drop along a distributor is therefore 98.6 - 95 = 3.6%.<br />

This means, in practical terms, that a medium-sized 230/400 V 3-phase 4-wire<br />

distribution cable <strong>of</strong> 240 mm 2 copper conductors would be able to supply a total load<br />

<strong>of</strong> 292 kVA at 0.8 PF lagging, distributed evenly over 306 metres <strong>of</strong> the distributor.<br />

Alternatively, the same load at the premises <strong>of</strong> a single consumer could be supplied<br />

at a distance <strong>of</strong> 153 metres from the transformer, for the same volt-drop, and so on...<br />

As a matter <strong>of</strong> interest, the maximum rating <strong>of</strong> the cable, based on calculations<br />

derived from IEC 60287 (1982) is 290 kVA, and so the 3.6% voltage margin is not<br />

unduly restrictive, i.e. the cable can be fully loaded for distances normally required in<br />

LV distribution systems.<br />

Furthermore, 0.8 PF lagging is appropriate to industrial loads. In mixed semiindustrial<br />

areas 0.85 is a more common value, while 0.9 is generally used for<br />

calculations concerning residential areas, so that the volt-drop noted above may be<br />

considered as a “worst case” example.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

C<br />

© Schneider Electric - all rights reserved


C16<br />

© Schneider Electric - all rights reserved<br />

C - Connecion to the LV public<br />

distribution network<br />

(1) Ripple control is a system <strong>of</strong> signalling in which a voice<br />

frequency current (commonly at 175 Hz) is injected into the<br />

LV mains at appropriate substations. The signal is injected<br />

as coded impulses, and relays which are tuned to the signal<br />

frequency and which recognize the particular code will operate<br />

to initiate a required function. In this way, up to 960 discrete<br />

control signals are available.<br />

2 Tariffs and metering<br />

No attempt will be made in this guide to discuss particular tariffs, since there appears<br />

to be as many different tariff structures around the world as there are utilities.<br />

Some tariffs are very complicated in detail but certain elements are basic to all <strong>of</strong><br />

them and are aimed at encouraging consumers to manage their power consumption<br />

in a way which reduces the cost <strong>of</strong> generation, transmission and distribution.<br />

The two predominant ways in which the cost <strong>of</strong> supplying power to consumers can<br />

be reduced, are:<br />

b Reduction <strong>of</strong> power losses in the generation, transmission and distribution <strong>of</strong><br />

<strong>electrical</strong> energy. In principle the lowest losses in a power system are attained when<br />

all parts <strong>of</strong> the system operate at unity power factor<br />

b Reduction <strong>of</strong> the peak power demand, while increasing the demand at low-load<br />

periods, thereby exploiting the generating plant more fully, and minimizing plant<br />

redundancy<br />

Reduction <strong>of</strong> losses<br />

Although the ideal condition noted in the first possibility mentioned above cannot<br />

be realized in practice, many tariff structures are based partly on kVA demand, as<br />

well as on kWh consumed. Since, for a given kW loading, the minimum value <strong>of</strong> kVA<br />

occurs at unity power factor, the consumer can minimize billing costs by taking steps<br />

to improve the power factor <strong>of</strong> the load (as discussed in <strong>Chapter</strong> L). The kVA demand<br />

generally used for tariff purposes is the maximum average kVA demand occurring<br />

during each billing period, and is based on average kVA demands, over fixed periods<br />

(generally 10, 30 or 60 minute periods) and selecting the highest <strong>of</strong> these values.<br />

The principle is described below in “principle <strong>of</strong> kVA maximum-demand metering”.<br />

Reduction <strong>of</strong> peak power demand<br />

The second aim, i.e. that <strong>of</strong> reducing peak power demands, while increasing demand<br />

at low-load periods, has resulted in tariffs which <strong>of</strong>fer substantial reduction in the cost<br />

<strong>of</strong> energy at:<br />

b Certain hours during the 24-hour day<br />

b Certain periods <strong>of</strong> the year<br />

The simplest example is that <strong>of</strong> a residential consumer with a storage-type water<br />

heater (or storage-type space heater, etc.). The meter has two digital registers, one<br />

<strong>of</strong> which operates during the day and the other (switched over by a timing device)<br />

operates during the night. A contactor, operated by the same timing device, closes<br />

the circuit <strong>of</strong> the water heater, the consumption <strong>of</strong> which is then indicated on the<br />

register to which the cheaper rate applies. The heater can be switched on and <strong>of</strong>f at<br />

any time during the day if required, but will then be metered at the normal rate. Large<br />

industrial consumers may have 3 or 4 rates which apply at different periods during<br />

a 24-hour interval, and a similar number for different periods <strong>of</strong> the year. In such<br />

schemes the ratio <strong>of</strong> cost per kWh during a period <strong>of</strong> peak demand for the year, and<br />

that for the lowest-load period <strong>of</strong> the year, may be as much as 10: 1.<br />

Meters<br />

It will be appreciated that high-quality instruments and devices are necessary to<br />

implement this kind <strong>of</strong> metering, when using classical electro-mechanical equipment.<br />

Recent developments in electronic metering and micro-processors, together with<br />

remote ripple-control (1) from an utility control centre (to change peak-period timing<br />

throughout the year, etc.) are now operational, and facilitate considerably the<br />

application <strong>of</strong> the principles discussed.<br />

In most countries, some tariffs, as noted above, are partly based on kVA demand,<br />

in addition to the kWh consumption, during the billing periods (<strong>of</strong>ten 3-monthly<br />

intervals). The maximum demand registered by the meter to be described, is, in fact,<br />

a maximum (i.e. the highest) average kVA demand registered for succeeding periods<br />

during the billing interval.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


C - Connecion to the LV public<br />

distribution network<br />

2 Tariffs and metering<br />

Figure C10 shows a typical kVA demand curve over a period <strong>of</strong> two hours divided<br />

into succeeding periods <strong>of</strong> 10 minutes. The meter measures the average value <strong>of</strong><br />

kVA during each <strong>of</strong> these 10 minute periods.<br />

kVA<br />

Fig. C10 : Maximum average value <strong>of</strong> kVA over an interval <strong>of</strong> 2 hours<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Maximum average value<br />

during the 2 hour interval<br />

Average values<br />

for 10 minute<br />

periods<br />

0 1 2 hrs<br />

Principle <strong>of</strong> kVA maximum demand metering<br />

A kVAh meter is similar in all essentials to a kWh meter but the current and voltage<br />

phase relationship has been modified so that it effectively measures kVAh (kilovolt-ampere-hours).<br />

Furthermore, instead <strong>of</strong> having a set <strong>of</strong> decade counter dials,<br />

as in the case <strong>of</strong> a conventional kWh meter, this instrument has a rotating pointer.<br />

When the pointer turns it is measuring kVAh and pushing a red indicator before it.<br />

At the end <strong>of</strong> 10 minutes the pointer will have moved part way round the dial (it is<br />

<strong>design</strong>ed so that it can never complete one revolution in 10 minutes) and is then<br />

<strong>electrical</strong>ly reset to the zero position, to start another 10 minute period. The red<br />

indicator remains at the position reached by the measuring pointer, and that position,<br />

corresponds to the number <strong>of</strong> kVAh (kilo-volt-ampere-hours) taken by the load in<br />

10 minutes. Instead <strong>of</strong> the dial being marked in kVAh at that point however it can be<br />

marked in units <strong>of</strong> average kVA. The following figures will clarify the matter.<br />

Supposing the point at which the red indicator reached corresponds to 5 kVAh.<br />

It is known that a varying amount <strong>of</strong> kVA <strong>of</strong> apparent power has been flowing for<br />

10 minutes, i.e. 1/6 hour.<br />

If now, the 5 kVAh is divided by the number <strong>of</strong> hours, then the average kVA for the<br />

period is obtained.<br />

In this case the average kVA for the period will be:<br />

5 x 1 = 5 x 6 = 30 kVA<br />

1<br />

6<br />

Every point around the dial will be similarly marked i.e. the figure for average kVA will<br />

be 6 times greater than the kVAh value at any given point. Similar reasoning can be<br />

applied to any other reset-time interval.<br />

At the end <strong>of</strong> the billing period, the red indicator will be at the maximum <strong>of</strong> all the<br />

average values occurring in the billing period.<br />

The red indicator will be reset to zero at the beginning <strong>of</strong> each billing period. Electromechanical<br />

meters <strong>of</strong> the kind described are rapidly being replaced by electronic<br />

instruments. The basic measuring principles on which these electronic meters<br />

depend however, are the same as those described above.<br />

t<br />

C17<br />

© Schneider Electric - all rights reserved


2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

<strong>Chapter</strong> D<br />

MV & LV architecture selection<br />

guide<br />

Contents<br />

Stakes for the user D3<br />

Simplified architecture <strong>design</strong> process D4<br />

2.1 The architecture <strong>design</strong> D4<br />

2.2 The whole process D5<br />

Electrical <strong>installation</strong> characteristics D7<br />

3.1 Activity D7<br />

3.2 Site topology D7<br />

3.3 Layout latitude D7<br />

3.4 Service reliability D8<br />

3.5 Maintainability D8<br />

3.6 Installation flexibility D8<br />

3.7 Power demand D8<br />

3.8 Load distribution D9<br />

3.9 Power interruption sensitivity D9<br />

3.10 Disturbance sensitivity D9<br />

3.11 Disturbance capability <strong>of</strong> circuits D10<br />

3.12 Other considerations or constraints D10<br />

Technological characteristics D<br />

4.1 Environment, atmosphere D11<br />

4.2 Service Index D11<br />

4.3 Other considerations D12<br />

Architecture assessment criteria D 3<br />

5.1 On-site work time D13<br />

5.2 Environmental impact D13<br />

5.3 Preventive maintenance level D13<br />

5.4 Availability <strong>of</strong> <strong>electrical</strong> power supply D14<br />

Choice <strong>of</strong> architecture fundamentals D 5<br />

6.1 Connection to the upstream network D15<br />

6.2 MV circuit configuration D16<br />

6.3 Number and distribution <strong>of</strong> MV/LV transformation substations D17<br />

6.4 Number <strong>of</strong> MV/LV transformers D18<br />

6.5 MV back-up generator D18<br />

Choice <strong>of</strong> architecture details D 9<br />

7.1 Layout D19<br />

7.2 Centralized or distributed layout D20<br />

7.3 Presence <strong>of</strong> an Uninterruptible Power Supply (UPS) D22<br />

7.4 Configuration <strong>of</strong> LV circuits D22<br />

Choice <strong>of</strong> equiment D24<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

D2<br />

D - MV & LV architecture selection guide<br />

9<br />

0<br />

2<br />

Recommendations for architecture optimization D26<br />

9.1 On-site work time D26<br />

9.2 Environmental impact D26<br />

9.3 Preventive maintenance volume D28<br />

9.4 Electrical power availability D28<br />

Glossary D29<br />

ID-Spec s<strong>of</strong>tware D30<br />

Example: <strong>electrical</strong> <strong>installation</strong> in a printworks D3<br />

12.1 Brief description D31<br />

12.2 Installation characteristics D31<br />

12.3 Technological characteristics D31<br />

12.4 Architecture assessment criteria D32<br />

12.5 Choice <strong>of</strong> technogical solutions D34<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

Potential for<br />

optimization<br />

Fig. D1 : Optimization potential<br />

ID-Spec<br />

Preliminary<br />

<strong>design</strong><br />

Stakes for the user<br />

Choice <strong>of</strong> distribution architecture<br />

The choice <strong>of</strong> distribution architecture has a decisive impact on <strong>installation</strong><br />

performance throughout its lifecycle:<br />

b right from the construction phase, choices can greatly influence the <strong>installation</strong><br />

time, possibilities <strong>of</strong> work rate, required competencies <strong>of</strong> <strong>installation</strong> teams, etc.<br />

b there will also be an impact on performance during the operation phase in terms<br />

<strong>of</strong> quality and continuity <strong>of</strong> power supply to sensitive loads, power losses in power<br />

supply circuits,<br />

b and lastly, there will be an impact on the proportion <strong>of</strong> the <strong>installation</strong> that can be<br />

recycled in the end-<strong>of</strong>-life phase.<br />

The Electrical Distribution architecture <strong>of</strong> an <strong>installation</strong> involves the spatial<br />

configuration, the choice <strong>of</strong> power sources, the definition <strong>of</strong> different distribution<br />

levels, the single-line diagram and the choice <strong>of</strong> equipment.<br />

The choice <strong>of</strong> the best architecture is <strong>of</strong>ten expressed in terms <strong>of</strong> seeking a<br />

compromise between the various performance criteria that interest the customer who<br />

will use the <strong>installation</strong> at different phases in its lifecycle. The earlier we search for<br />

solutions, the more optimization possibilities exist (see Fig. D1).<br />

Ecodial<br />

Detailled<br />

<strong>design</strong><br />

Installation<br />

A successful search for an optimal solution is also strongly linked to the ability for<br />

exchange between the various players involved in <strong>design</strong>ing the various sections <strong>of</strong><br />

a project:<br />

b the architect who defines the organization <strong>of</strong> the building according to user<br />

requirements,<br />

b the <strong>design</strong>ers <strong>of</strong> different technical sections (lighting, heating, air conditioning,<br />

fluids, etc.),<br />

b the user’s representatives e.g. defining the process.<br />

The following paragraphs present the selection criteria as well as the architecture<br />

<strong>design</strong> process to meet the project performance criteria in the context <strong>of</strong> industrial<br />

and tertiary buildings (excluding large sites).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Exploitation<br />

D3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

D<br />

D - MV & LV architecture selection guide<br />

2 Simplified architecture <strong>design</strong><br />

process<br />

2.1 The architecture <strong>design</strong><br />

The architecture <strong>design</strong> considered in this document is positioned at the Draft<br />

Design stage. It generally covers the levels <strong>of</strong> MV/LV main distribution, LV power<br />

distribution, and exceptionally the terminal distribution level. (see Fig. D2).<br />

MV/LV main<br />

distribution<br />

LV power<br />

distribution<br />

LV terminal<br />

distribution<br />

The <strong>design</strong> <strong>of</strong> an <strong>electrical</strong> distribution architecture can be described by a 3-stage<br />

process, with iterative possibilities. This process is based on taking account <strong>of</strong> the<br />

<strong>installation</strong> characteristics and criteria to be satisfied.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M M M M<br />

Fig. D2 : Example <strong>of</strong> single-line diagram


D - MV & LV architecture selection guide<br />

Data<br />

Step<br />

Deliverable<br />

See § 4<br />

Technological<br />

characteristics<br />

See § 5<br />

Assessment<br />

criteria<br />

Fig. D3 : Flow diagram for choosing the <strong>electrical</strong> distribution architecture<br />

2 Simplified architecture <strong>design</strong><br />

process<br />

2.2 The whole process<br />

The whole process is described briefly in the following paragraphs and illustrated on<br />

Figure D3.<br />

The process described in this document is not intended as the only solution. This<br />

document is a guide intended for the use <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong>ers.<br />

See § 3<br />

Installation<br />

characteristics<br />

See § 6<br />

Step 1<br />

Choice <strong>of</strong><br />

fundamentals<br />

Schematic<br />

diagram<br />

See § 7<br />

Step 2<br />

Choice <strong>of</strong><br />

architecturedetails<br />

See § 8<br />

Detailed<br />

diagram<br />

Step 3<br />

Choice <strong>of</strong><br />

equipment<br />

Techno.<br />

Solution<br />

ASSESSMENT<br />

Definitive<br />

solution<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

See § 9<br />

Optimisation<br />

recommendations<br />

Step 1: Choice <strong>of</strong> distribution architecture fundamentals<br />

This involves defining the general features <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong>. It is based<br />

on taking account <strong>of</strong> macroscopic characteristics concerning the <strong>installation</strong> and its<br />

usage.<br />

These characteristics have an impact on the connection to the upstream network,<br />

MV circuits, the number <strong>of</strong> transformer substations, etc.<br />

At the end <strong>of</strong> this step, we have several distribution schematic diagram solutions,<br />

which are used as a starting point for the single-line diagram. The definitive choice is<br />

confirmed at the end <strong>of</strong> the step 2.<br />

D<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

D<br />

D - MV & LV architecture selection guide<br />

2 Simplified architecture <strong>design</strong><br />

process<br />

Step 2: choice <strong>of</strong> architecture details<br />

This involves defining the <strong>electrical</strong> <strong>installation</strong> in more detail. It is based on the<br />

results <strong>of</strong> the previous step, as well as on satisfying criteria relative to implementation<br />

and operation <strong>of</strong> the <strong>installation</strong>.<br />

The process loops back into step1 if the criteria are not satisfied. An iterative process<br />

allows several assessment criteria combinations to be analyzed.<br />

At the end <strong>of</strong> this step, we have a detailed single-line diagram.<br />

Step 3: choice <strong>of</strong> equipment<br />

The choice <strong>of</strong> equipment to be implemented is carried out in this stage, and results<br />

from the choice <strong>of</strong> architecture. The choices are made from the manufacturer<br />

catalogues, in order to satisfy certain criteria.<br />

This stage is looped back into step 2 if the characteristics are not satisfied.<br />

Assessment<br />

This assessment step allows the Engineering Office to have figures as a basis for<br />

discussions with the customer and other players.<br />

According to the result <strong>of</strong> these discussions, it may be possible to loop back into step 1.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

3 Electrical <strong>installation</strong><br />

characteristics<br />

These are the main <strong>installation</strong> characteristics enabling the defining <strong>of</strong> the<br />

fundamentals and details <strong>of</strong> the <strong>electrical</strong> distribution architecture. For each <strong>of</strong> these<br />

characteristics, we supply a definition and the different categories or possible values.<br />

3.1 Activity<br />

Definition:<br />

Main economic activity carried out on the site.<br />

Indicative list <strong>of</strong> sectors considered for industrial buildings:<br />

b Manufacturing<br />

b Food & Beverage<br />

b Logistics<br />

Indicative list <strong>of</strong> sectors considered for tertiary buildings:<br />

b Offices buildings<br />

b Hypermarkets<br />

b Shopping malls<br />

3.2 Site topology<br />

Definition:<br />

Architectural characteristic <strong>of</strong> the building(s), taking account <strong>of</strong> the number <strong>of</strong><br />

buildings, number <strong>of</strong> floors, and <strong>of</strong> the surface area <strong>of</strong> each floor.<br />

Different categories:<br />

b Single storey building,<br />

b Multi-storey building,<br />

b Multi-building site,<br />

b High-rise building.<br />

3.3 Layout latitude<br />

Definition:<br />

Characteristic taking account <strong>of</strong> constraints in terms <strong>of</strong> the layout <strong>of</strong> the <strong>electrical</strong><br />

equipment in the building:<br />

b aesthetics,<br />

b accessibility,<br />

b presence <strong>of</strong> dedicated locations,<br />

b use <strong>of</strong> technical corridors (per floor),<br />

b use <strong>of</strong> technical ducts (vertical).<br />

Different categories:<br />

b Low: the position <strong>of</strong> the <strong>electrical</strong> equipment is virtually imposed<br />

b Medium: the position <strong>of</strong> the <strong>electrical</strong> equipment is partially imposed, to the<br />

detriment <strong>of</strong> the criteria to be satisfied<br />

b High: no constraints. The position <strong>of</strong> the <strong>electrical</strong> equipment can be defined to<br />

best satisfy the criteria.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

D<br />

D - MV & LV architecture selection guide<br />

3 Electrical <strong>installation</strong><br />

characteristics<br />

3.4 Service reliability<br />

Definition:<br />

The ability <strong>of</strong> a power system to meet its supply function under stated conditions for<br />

a specified period <strong>of</strong> time.<br />

Different categories:<br />

b Minimum: this level <strong>of</strong> service reliability implies risk <strong>of</strong> interruptions related to<br />

constraints that are geographical (separate network, area distant from power<br />

production centers), technical (overhead line, poorly meshed system), or economic<br />

(insufficient maintenance, under-dimensioned generation).<br />

b Standard<br />

b Enhanced: this level <strong>of</strong> service reliability can be obtained by special measures<br />

taken to reduce the probability <strong>of</strong> interruption (underground network, strong meshing,<br />

etc.)<br />

3.5 Maintainability<br />

Definition:<br />

Features input during <strong>design</strong> to limit the impact <strong>of</strong> maintenance actions on the<br />

operation <strong>of</strong> the whole or part <strong>of</strong> the <strong>installation</strong>.<br />

Different categories:<br />

b Minimum: the <strong>installation</strong> must be stopped to carry out maintenance operations.<br />

b Standard: maintenance operations can be carried out during <strong>installation</strong><br />

operations, but with deteriorated performance. These operations must be preferably<br />

scheduled during periods <strong>of</strong> low activity. Example: several transformers with partial<br />

redundancy and load shedding.<br />

b Enhanced: special measures are taken to allow maintenance operations without<br />

disturbing the <strong>installation</strong> operations. Example: double-ended configuration.<br />

3.6 Installation flexibility<br />

Definition:<br />

Possibility <strong>of</strong> easily moving electricity delivery points within the <strong>installation</strong>, or to<br />

easily increase the power supplied at certain points. Flexibility is a criterion which<br />

also appears due to the uncertainty <strong>of</strong> the building during the pre-project summary<br />

stage.<br />

Different categories:<br />

b No flexibility: the position <strong>of</strong> loads is fixed throughout the lifecycle, due to the high<br />

constraints related to the building construction or the high weight <strong>of</strong> the supplied<br />

process. E.g.: smelting works.<br />

b Flexibility <strong>of</strong> <strong>design</strong>: the number <strong>of</strong> delivery points, the power <strong>of</strong> loads or their<br />

location are not precisely known.<br />

b Implementation flexibility: the loads can be installed after the <strong>installation</strong> is<br />

commissioned.<br />

b Operating flexibility: the position <strong>of</strong> loads will fluctuate, according to process reorganization.<br />

Examples:<br />

v industrial building: extension, splitting and changing usage<br />

v <strong>of</strong>fice building: splitting<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

* indicative value, supplied by standard EN50160:<br />

“Characteristics <strong>of</strong> the voltage supplied by public distribution<br />

networks”.<br />

3 Electrical <strong>installation</strong><br />

characteristics<br />

3. Power demand<br />

Definition:<br />

The sum <strong>of</strong> the apparent load power (in kVA), to which is applied a usage coefficient.<br />

This represents the maximum power which can be consumed at a given time for the<br />

<strong>installation</strong>, with the possibility <strong>of</strong> limited overloads that are <strong>of</strong> short duration.<br />

Significant power ranges correspond to the transformer power limits most commonly<br />

used:<br />

b < 630kVA<br />

b from 630 to 1250kVA<br />

b from 1250 to 2500kVA<br />

b > 2500kVA<br />

3. Load distribution<br />

Definition:<br />

A characteristic related to the uniformity <strong>of</strong> load distribution (in kVA / m²) over an area<br />

or throughout the building.<br />

Different categories:<br />

b Uniform distribution: the loads are generally <strong>of</strong> an average or low unit power and<br />

spread throughout the surface area or over a large area <strong>of</strong> the building (uniform<br />

density).<br />

E.g.: lighting, individual workstations<br />

b intermediate distribution: the loads are generally <strong>of</strong> medium power, placed in<br />

groups over the whole building surface area<br />

E.g.: machines for assembly, conveying, workstations, modular logistics “sites”<br />

b localized loads: the loads are generally high power and localized in several areas<br />

<strong>of</strong> the building (non-uniform density).<br />

E.g.: HVAC<br />

3. Power Interruption Sensitivity<br />

Definition:<br />

The aptitude <strong>of</strong> a circuit to accept a power interruption.<br />

Different categories:<br />

b “Sheddable” circuit: possible to shut down at any time for an indefinite duration<br />

b Long interruption acceptable: interruption time > 3 minutes *<br />

b Short interruption acceptable: interruption time < 3 minutes *<br />

b No interruption acceptable.<br />

We can distinguish various levels <strong>of</strong> severity <strong>of</strong> an <strong>electrical</strong> power interruption,<br />

according to the possible consequences:<br />

b No notable consequence,<br />

b Loss <strong>of</strong> production,<br />

b Deterioration <strong>of</strong> the production facilities or loss <strong>of</strong> sensitive data,<br />

b Causing mortal danger.<br />

This is expressed in terms <strong>of</strong> the criticality <strong>of</strong> supplying <strong>of</strong> loads or circuits.<br />

b Non-critical:<br />

The load or the circuit can be “shed” at any time. E.g.: sanitary water heating circuit.<br />

b Low criticality:<br />

A power interruption causes temporary discomfort for the occupants <strong>of</strong> a building,<br />

without any financial consequences. Prolonging <strong>of</strong> the interruption beyond the critical<br />

time can cause a loss <strong>of</strong> production or lower productivity. E.g.: heating, ventilation<br />

and air conditioning circuits (HVAC).<br />

b Medium criticality<br />

A power interruption causes a short break in process or service. Prolonging <strong>of</strong><br />

the interruption beyond a critical time can cause a deterioration <strong>of</strong> the production<br />

facilities or a cost <strong>of</strong> starting for starting back up.<br />

E.g.: refrigerated units, lifts.<br />

b High criticality<br />

Any power interruption causes mortal danger or unacceptable financial losses.<br />

E.g.: operating theatre, IT department, security department.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D<br />

© Schneider Electric - all rights reserved


D10<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

3 Electrical <strong>installation</strong><br />

characteristics<br />

3.10 Disturbance sensitivity<br />

Definition<br />

The ability <strong>of</strong> a circuit to work correctly in presence <strong>of</strong> an <strong>electrical</strong> power<br />

disturbance.<br />

A disturbance can lead to varying degrees <strong>of</strong> malfunctioning. E.g.: stopping working,<br />

incorrect working, accelerated ageing, increase <strong>of</strong> losses, etc<br />

Types <strong>of</strong> disturbances with an impact on circuit operations:<br />

b brown-outs,<br />

b overvoltages<br />

b voltage distortion,<br />

b voltage fluctuation,<br />

b voltage imbalance.<br />

Different categories:<br />

b low sensitivity: disturbances in supply voltages have very little effect on operations.<br />

E.g.: heating device.<br />

b medium sensitivity: voltage disturbances cause a notable deterioration in<br />

operations.<br />

E.g.: motors, lighting.<br />

b high sensitivity: voltage disturbances can cause operation stoppages or even the<br />

deterioration <strong>of</strong> the supplied equipment.<br />

E.g.: IT equipment.<br />

The sensitivity <strong>of</strong> circuits to disturbances determines the <strong>design</strong> <strong>of</strong> shared or<br />

dedicated power circuits. Indeed it is better to separate “sensitive” loads from<br />

“disturbing” loads. E.g.: separating lighting circuits from motor supply circuits.<br />

This choice also depends on operating features. E.g.: separate power supply <strong>of</strong><br />

lighting circuits to enable measurement <strong>of</strong> power consumption.<br />

3.11 Disturbance capability <strong>of</strong> circuits<br />

Definition<br />

The ability <strong>of</strong> a circuit to disturb the operation <strong>of</strong> surrounding circuits due to<br />

phenomena such as: harmonics, in-rush current, imbalance, High Frequency<br />

currents, electromagnetic radiation, etc.<br />

Different categories<br />

b Non disturbing: no specific precaution to take<br />

b moderate or occasional disturbance: separate power supply may be necessary in<br />

the presence <strong>of</strong> medium or high sensitivity circuits. E.g.: lighting circuit generating<br />

harmonic currents.<br />

b Very disturbing: a dedicated power circuit or ways <strong>of</strong> attenuating disturbances are<br />

essential for the correct functioning <strong>of</strong> the <strong>installation</strong>. E.g.: <strong>electrical</strong> motor with a<br />

strong start-up current, welding equipment with fluctuating current.<br />

3.12 Other considerations or constraints<br />

b Environment<br />

E.g.: lightning classification, sun exposure<br />

b Specific <strong>rules</strong><br />

E.g.: hospitals, high rise buildings, etc.<br />

b Rule <strong>of</strong> the Energy Distributor<br />

Example: limits <strong>of</strong> connection power for LV, access to MV substation, etc<br />

b Attachment loads<br />

Loads attached to 2 independent circuits for reasons <strong>of</strong> redundancy.<br />

b Designer experience<br />

Consistency with previous <strong>design</strong>s or partial usage <strong>of</strong> previous <strong>design</strong>s,<br />

standardization <strong>of</strong> sub-assemblies, existence <strong>of</strong> an installed equipment base.<br />

b Load power supply constraints<br />

Voltage level (230V, 400V, 690V), voltage system (single-phase, three-phase with or<br />

without neutral, etc)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

Fig. D4 : Different index values<br />

4 Technological characteristics<br />

The technological solutions considered concern the various types <strong>of</strong> MV and LV<br />

equipment, as well as Busbar Trunking Systems .<br />

The choice <strong>of</strong> technological solutions is made following the choice <strong>of</strong> single-line<br />

diagram and according to characteristics given below.<br />

4.1 Environment, atmosphere<br />

A notion taking account <strong>of</strong> all <strong>of</strong> the environmental constraints (average ambient<br />

temperature, altitude, humidity, corrosion, dust, impact, etc.) and bringing together<br />

protection indexes IP and IK.<br />

Different categories:<br />

b Standard: no particular environmental constraints<br />

b Enhanced: severe environment, several environmental parameters generate<br />

important constraints for the installed equipment<br />

b Specific: atypical environment, requiring special enhancements<br />

4.2 Service Index<br />

The service index (IS) is a value that allows us to characterize an LV switchboard<br />

according to user requirements in terms <strong>of</strong> operation, maintenance, and scalability.<br />

The different index values are indicated in the following table (Fig D4):<br />

Operation Maintenance Upgrade<br />

Level 1 IS = 1 • •<br />

Operation may lead to complete<br />

stoppage <strong>of</strong> the switchboard<br />

Level 2 IS = 2 • •<br />

Operation may lead to stoppage <strong>of</strong><br />

only the functional unit<br />

Level 3 IS = 3 • •<br />

Operation may lead to stoppage <strong>of</strong><br />

the power <strong>of</strong> the functional unit only<br />

IS = • 1 •<br />

Operation may lead to complete<br />

stoppage <strong>of</strong> the switchboard<br />

IS = • 2 •<br />

Operation may lead to stoppage <strong>of</strong><br />

only the functional unit, with work on<br />

connections<br />

IS = • 3 •<br />

Operation may lead to stoppage <strong>of</strong><br />

only the functional unit, without work<br />

on connections<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IS = • • 1<br />

Operation may lead to complete<br />

stoppage <strong>of</strong> the switchboard<br />

IS = • • 2<br />

Operation may lead to stoppage<br />

<strong>of</strong> only the functional unit, with<br />

functional units provided for back-up<br />

IS = • • 3<br />

Operation may lead to stoppage <strong>of</strong><br />

only the functional unit, with total<br />

freedom in terms <strong>of</strong> upgrade<br />

b Examples <strong>of</strong> an operation event: turning <strong>of</strong>f a circuit-breaker, switching operation to<br />

energize/de-energize a machine<br />

b Example <strong>of</strong> a maintenance operation: tightening connections<br />

b Example <strong>of</strong> an upgrade operation: connecting an additional feeder<br />

There are a limited number <strong>of</strong> relevant service indices (see Fig. D5)<br />

IS Operation Maintenance Upgrade<br />

1 1 1 Switching <strong>of</strong>f the whole switchboard Working time > 1h, with total nonavailability<br />

Extension not planned<br />

2 1 1<br />

2 2 3 Working time between 1/4h and 1h,<br />

with work on connections<br />

2 3 2<br />

Individually switching <strong>of</strong>f the functional<br />

unit and re-commissioning < 1h<br />

Working time between 1/4h and 1h,<br />

without work on connections<br />

Possible adding <strong>of</strong> functional units<br />

without stopping the switchboard<br />

Possible adding <strong>of</strong> functional units with<br />

stopping the switchboard<br />

2 3 3 Possible adding <strong>of</strong> functional units<br />

without stopping the switchboard<br />

3 3 2<br />

Possible adding <strong>of</strong> functional units with<br />

stopping the switchboard<br />

3 3 3<br />

Individually switching <strong>of</strong>f the functional<br />

unit and re-commissioning < 1/4h<br />

Possible adding <strong>of</strong> functional units<br />

without stopping the switchboard<br />

Fig. D5 : Relevant service indices (IS)<br />

D11<br />

© Schneider Electric - all rights reserved


D12<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

Service rating Protection index<br />

IP<br />

4 Technological characteristics<br />

The types <strong>of</strong> <strong>electrical</strong> connections <strong>of</strong> functional units can be denoted by a threeletter<br />

code:<br />

b The first letter denotes the type <strong>of</strong> <strong>electrical</strong> connection <strong>of</strong> the main incoming<br />

circuit,<br />

b The second letter denotes the type <strong>of</strong> <strong>electrical</strong> connection <strong>of</strong> the main outgoing<br />

circuit,<br />

b The third letter denotes the type <strong>of</strong> <strong>electrical</strong> connection <strong>of</strong> the auxiliary circuits.<br />

The following letters are used:<br />

b F for fixed connections,<br />

b D for disconnectable connections,<br />

b W for withdrawable connections.<br />

Service ratings are related to other mechanical parameters, such as the Protection<br />

Index (IP), form <strong>of</strong> internal separations, the type <strong>of</strong> connection <strong>of</strong> functional units or<br />

switchgear (Fig. D6):<br />

Form Functional Unit<br />

Withdrawability<br />

1 1 1 2 X X 1 F F F<br />

2 1 1 2 X B 1 F F F<br />

2 2 3 2 X B 3b W F D<br />

2 3 2 2 X B 3b W F W<br />

2 3 3 2 X B 3b W W W<br />

3 3 2 2 X B 3b W W W<br />

3 3 3 2 X B 3b W W W<br />

Fig. D6 : Correspondence between service index and other mechanical parameters<br />

Technological examples are given in chapter E2.<br />

b Definition <strong>of</strong> the protection index: see IEC 60529: “Degree <strong>of</strong> protection given by<br />

enclosures (IP code)”,<br />

b Definitions <strong>of</strong> the form and withdrawability: see IEC 60439-1: “Low-voltage<br />

switchgear and controlgear assemblies; part 1: type-tested and partially type-tested<br />

assemblies”.<br />

4.3 Other considerations<br />

Other considerations have an impact on the choice <strong>of</strong> technological solutions:<br />

b Designer experience,<br />

b Consistency with past <strong>design</strong>s or the partial use <strong>of</strong> past <strong>design</strong>s,<br />

b Standardization <strong>of</strong> sub-assemblies,<br />

b The existence <strong>of</strong> an installed equipment base,<br />

b Utilities requirements,<br />

b Technical criteria: target power factor, backed-up load power, presence <strong>of</strong> harmonic<br />

generators…<br />

These considerations should be taken into account during the detailed <strong>electrical</strong><br />

definition phase following the draft <strong>design</strong> stage.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

5 Architecture assessment criteria<br />

Certain decisive criteria are assessed at the end <strong>of</strong> the 3 stages in defining<br />

architecture, in order to validate the architecture choice. These criteria are listed<br />

below with the different allocated levels <strong>of</strong> priority.<br />

5.1 On-site work time<br />

Time for implementing the <strong>electrical</strong> equipment on the site.<br />

Different levels <strong>of</strong> priority:<br />

b Secondary: the on-site work time can be extended, if this gives a reduction in<br />

overall <strong>installation</strong> costs,<br />

b Special: the on-site work time must be minimized, without generating any<br />

significant excess cost,<br />

b Critical: the on-site work time must be reduced as far as possible, imperatively,<br />

even if this generates a higher total <strong>installation</strong> cost,<br />

5.2 Environmental impact<br />

Taking into consideration environmental constraints in the <strong>installation</strong> <strong>design</strong>. This<br />

takes account <strong>of</strong>: consumption <strong>of</strong> natural resources, Joule losses (related to CO 2<br />

emission), “recyclability” potential, throughout the <strong>installation</strong>’s lifecycle.<br />

Different levels <strong>of</strong> priority:<br />

b Non significant: environmental constraints are not given any special consideration,<br />

b Minimal: the <strong>installation</strong> is <strong>design</strong>ed with minimum regulatory requirements,<br />

b Proactive: the <strong>installation</strong> is <strong>design</strong>ed with a specific concern for protecting<br />

the environment. Excess cost is allowed in this situation. E.g.: using low-loss<br />

transformers.<br />

The environmental impact <strong>of</strong> an <strong>installation</strong> will be determined according to the<br />

method carrying out an <strong>installation</strong> lifecycle analysis, in which we distinguish<br />

between the following 3 phases:<br />

b manufacture,<br />

b operation,<br />

b end <strong>of</strong> life (dismantling, recycling).<br />

In terms <strong>of</strong> environmental impact, 3 indicators (at least) can be taken into account<br />

and influenced by the <strong>design</strong> <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong>. Although each lifecycle<br />

phase contributes to the three indicators, each <strong>of</strong> these indicators is mainly related to<br />

one phase in particular:<br />

b consumption <strong>of</strong> natural resources mainly has an impact on the manufacturing<br />

phase,<br />

b consumption <strong>of</strong> energy has an impact on the operation phase,<br />

b “recycleability” potential has an impact on the end <strong>of</strong> life.<br />

The following table details the contributing factors to the 3 environmental indicators<br />

(Fig D7).<br />

Indicators Contributors<br />

Natural resources consumption Mass and type <strong>of</strong> materials used<br />

Power consumption Joule losses at full load and no load<br />

«Recyclability» potential Mass and type <strong>of</strong> material used<br />

Fig D7 : Contributing factors to the 3 environmental indicators<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D13<br />

© Schneider Electric - all rights reserved


D14<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

5 Architecture assessment criteria<br />

5.3 Preventive maintenance level<br />

Definition:<br />

Number <strong>of</strong> hours and sophistication <strong>of</strong> maintenance carried out during operations in<br />

conformity with manufacturer recommendations to ensure dependable operation <strong>of</strong><br />

the <strong>installation</strong> and the maintaining <strong>of</strong> performance levels (avoiding failure: tripping,<br />

down time, etc).<br />

Different categories:<br />

b Standard: according to manufacturer recommendations.<br />

b Enhanced: according to manufacturer recommendations, with a severe<br />

environment,<br />

b Specific: specific maintenance plan, meeting high requirements for continuity <strong>of</strong><br />

service, and requiring a high level <strong>of</strong> maintenance staff competency.<br />

5.4 Availability <strong>of</strong> <strong>electrical</strong> power supply<br />

Definition:<br />

This is the probability that an <strong>electrical</strong> <strong>installation</strong> be capable <strong>of</strong> supplying quality<br />

power in conformity with the specifications <strong>of</strong> the equipment it is supplying. This is<br />

expressed by an availability level:<br />

Availability (%) = (1 - MTTR/ MTBF) x 100<br />

MTTR (Mean Time To Repair): the average time to make the <strong>electrical</strong> system once<br />

again operational following a failure (this includes detection <strong>of</strong> the reason for failure,<br />

its repair and re-commissioning),<br />

MTBF (Mean Time Between Failure): measurement <strong>of</strong> the average time for which<br />

the <strong>electrical</strong> system is operational and therefore enables correct operation <strong>of</strong> the<br />

application.<br />

The different availability categories can only be defined for a given type <strong>of</strong><br />

<strong>installation</strong>. E.g.: hospitals, data centers.<br />

Example <strong>of</strong> classification used in data centers:<br />

Tier 1: the power supply and air conditioning are provided by one single channel,<br />

without redundancy, which allows availability <strong>of</strong> 99.671%,<br />

Tier 2: the power supply and air conditioning are provided by one single channel,<br />

with redundancy, which allows availability <strong>of</strong> 99.741%,<br />

Tier 3: the power supply and air conditioning are provided by several channels, with<br />

one single redundant channel, which allows availability <strong>of</strong> 99.982%,<br />

Tier 4: the power supply and air conditioning are provided by several channels, with<br />

redundancy, which allows availability <strong>of</strong> 99.995%.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

The single-line diagram can be broken down into different key parts, which are<br />

determined throughout a process in 2 successive stages. During the first stage we<br />

make the following choices:<br />

b connection to the utilities network,<br />

b configuration <strong>of</strong> MV circuits,<br />

b number <strong>of</strong> power transformers,<br />

b number and distribution <strong>of</strong> transformation substations,<br />

b MV back-up generator<br />

6.1 Connection to the upstream network<br />

The main configurations for possible connection are as follows (see Fig. D8 for MV<br />

service):<br />

b LV service,<br />

b MV single-line service,<br />

b MV ring-main service,<br />

b MV duplicate supply service,<br />

b MV duplicate supply service with double busbar.<br />

Metering, protection, disconnection devices, located in the delivery substations are<br />

not represented on the following diagrams. They are <strong>of</strong>ten specific to each utilities<br />

company and do not have an influence on the choice <strong>of</strong> <strong>installation</strong> architecture.<br />

For each connection, one single transformer is shown for simplification purposes, but<br />

in the practice, several transformers can be connected.<br />

(MLVS: Main Low Voltage Switchboard)<br />

a) Single-line: b) Ring-main:<br />

MV<br />

LV<br />

MLVS<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MLVS<br />

c) Duplicate supply: d) Double busbar with duplicate supply:<br />

MV<br />

LV<br />

MLVS<br />

Fig. D8 : MV connection to the utilities network<br />

MV<br />

LV<br />

MV<br />

LV<br />

MLVS1<br />

MV<br />

LV<br />

MLVS2<br />

D15<br />

© Schneider Electric - all rights reserved


D16<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

Characteristic to<br />

consider<br />

Configuration<br />

LV MV<br />

For the different possible configurations, the most probable and usual set <strong>of</strong><br />

characteristics is given in the following table:<br />

Simple-line Ring-main Duplicate supply Duplicate supply<br />

with double<br />

busbars<br />

Activity Any Any Any Hi-tech, sensitive<br />

<strong>of</strong>fice, health-care<br />

Site topology Single building Single building Single building Single building Several buildings<br />

Service reliability Minimal Minimal Standard Enhanced Enhanced<br />

Power demand < 630kVA ≤ 1250kVA ≤ 2500kVA > 2500kVA > 2500kVA<br />

Other connection<br />

constraints<br />

Any Isolated site Low density urban<br />

area<br />

a) Single feeder: b) Open ring, 1 MV substation:<br />

MV MV MV MV MV<br />

LV<br />

MLVS 1<br />

LV<br />

MLVS n<br />

Fig. D9 : MV circuit configuration<br />

LV<br />

MLVS 1<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

High density<br />

urban area<br />

6.2 MV circuit configuration<br />

Any<br />

Urban area with<br />

utility constraint<br />

The main possible connection configurations are as follows (Fig. D9):<br />

b single feeder, one or several transformers<br />

b open ring, one MV incomer<br />

b open ring, 2 MV incomers<br />

The basic configuration is a radial single-feeder architecture, with one single<br />

transformer.<br />

In the case <strong>of</strong> using several transformers, no ring is realised unless all <strong>of</strong> the<br />

transformers are located in a same substation.<br />

Closed-ring configuration is not taken into account.<br />

LV<br />

MLVS 2<br />

LV<br />

MLVS n<br />

c) Open ring, 2 MV substations:<br />

MV<br />

LV<br />

MLVS 1<br />

MV<br />

LV<br />

MLVS 2<br />

MV<br />

LV<br />

MLVS n


D - MV & LV architecture selection guide<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

For the different possible configurations, the most probable and usual set <strong>of</strong><br />

characteristics is given in the table on Fig D10.<br />

Characteristic to<br />

consider<br />

Site topology Any<br />

< 25000m²<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MV circuit configuration<br />

Single feeder Open ring<br />

1 MV substation<br />

Building with one<br />

level or several<br />

buildings<br />

≤ 25000m²<br />

Open ring<br />

2 MV substations<br />

Several buildings<br />

≥ 25000m²<br />

Maintainability Minimal or standard Enhanced Enhanced<br />

Power demand Any > 1250kVA > 2500kVA<br />

Disturbance sensitivity Long interruption<br />

acceptable<br />

Fig. D10 : Typical values <strong>of</strong> the <strong>installation</strong> characteristics<br />

Short interruption<br />

acceptable<br />

Short interruption<br />

acceptable<br />

Another exceptional configuration: power supply by 2 MV substations and connection<br />

<strong>of</strong> the transformers to each <strong>of</strong> these 2 substations (MV “double ended” connection).<br />

6.3 Number and distribution <strong>of</strong> MV/LV<br />

transformation substations<br />

Main characteristics to consider to determine the transformation substations:<br />

b Surface area <strong>of</strong> building or site<br />

b Power demand, (to be compared with standardized transformer power),<br />

b Load distribution<br />

The preferred basic configuration comprises one single substation. Certain factors<br />

contribute to increasing the number <strong>of</strong> substations (> 1):<br />

b A large surface area (> 25000m²),<br />

b The site configuration: several buildings,<br />

b Total power > 2500kVA,<br />

b Sensitivity to interruption: need for redundancy in the case <strong>of</strong> a fire.<br />

Characteristic to<br />

consider<br />

Configuration<br />

1 substation with<br />

N transformers<br />

N substations<br />

N transformers<br />

(identical substations)<br />

Building configuration < 25000m² ≥ 25000m²<br />

1 building with several<br />

floors<br />

N substations<br />

M transformers<br />

(different powers)<br />

≥ 25000m²<br />

several buildings<br />

Power demand < 2500kVA ≥ 2500kVA ≥ 2500kVA<br />

Load distribution Localized loads Uniform distribution Medium density<br />

Fig. D11 : Typical characteristics <strong>of</strong> the different configurations<br />

D17<br />

© Schneider Electric - all rights reserved


D18<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

6.4 Number <strong>of</strong> MV/LV transformers<br />

Main characteristics to consider to determine the number <strong>of</strong> transformers:<br />

b Surface <strong>of</strong> building or site<br />

b Total power <strong>of</strong> the installed loads<br />

b Sensitivity <strong>of</strong> circuits to power interruptions<br />

b Sensitivity <strong>of</strong> circuits to disturbances<br />

b Installation scalability<br />

The basic preferred configuration comprises a single transformer supplying the total<br />

power <strong>of</strong> the installed loads. Certain factors contribute to increasing the number <strong>of</strong><br />

transformers (> 1), preferably <strong>of</strong> equal power:<br />

b A high total installed power (> 1250kVA): practical limit <strong>of</strong> unit power<br />

(standardization, ease <strong>of</strong> replacement, space requirement, etc),<br />

b A large surface area (> 5000m²): the setting up <strong>of</strong> several transformers as close as<br />

possible to the distributed loads allows the length <strong>of</strong> LV trunking to be reduced<br />

b A need for partial redundancy (down-graded operation possible in the case <strong>of</strong> a<br />

transformer failure) or total redundancy (normal operation ensured in the case a<br />

transformer failure)<br />

b Separating <strong>of</strong> sensitive and disturbing loads (e.g.: IT, motors)<br />

6.5 MV back-up generator<br />

Main characteristics to consider for the implementation <strong>of</strong> an MV back-up generator:<br />

b Site activity<br />

b Total power <strong>of</strong> the installed loads<br />

b Sensitivity <strong>of</strong> circuits to power interruptions<br />

b Availability <strong>of</strong> the public distribution network<br />

The preferred basic configuration does not include an MV generator. Certain factors<br />

contribute to installing an MV generator:<br />

b Site activity: process with co-generation, optimizing the energy bill,<br />

b Low availability <strong>of</strong> the public distribution network.<br />

Installation <strong>of</strong> a back-up generator can also be carried out at LV level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

Office<br />

Finishing<br />

7 Choice <strong>of</strong> architecture details<br />

This is the second stage in <strong>design</strong>ing <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong>. During this stage<br />

we carry out the following choices are carried out:<br />

b Layout,<br />

b Centralized or decentralized distribution,<br />

b Presence <strong>of</strong> back-up generators,<br />

b Presence <strong>of</strong> uninterruptible power supplies,<br />

b Configuration <strong>of</strong> LV circuits,<br />

b Architecture combinations.<br />

7.1 Layout<br />

Position <strong>of</strong> the main MV and LV equipment on the site or in the building.<br />

This layout choice is applied to the results <strong>of</strong> stage 1.<br />

Selection guide:<br />

b Place power sources as close as possible to the barycenter <strong>of</strong> power consumers,<br />

b Reduce atmospheric constraints: building dedicated premises if the layout in the<br />

workshop is too restrictive (temperature, vibrations, dust, etc.),<br />

b Placing heavy equipment (transformers, generators, etc) close to walls or main<br />

exists for ease <strong>of</strong> maintenance,<br />

A layout example is given in the following diagram (Fig. D12):<br />

Global current<br />

consumer<br />

Barycenter<br />

Painting<br />

Fig. D12 : The position <strong>of</strong> the global current consumer barycenter guides the positioning <strong>of</strong> power sources<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Panel<br />

shop<br />

D19<br />

© Schneider Electric - all rights reserved


D20<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

7 Choice <strong>of</strong> architecture details<br />

7.2 Centralized or distributed layout<br />

In centralized layout, current consumers are connected to the power sources<br />

by a star-connection. Cables are suitable for centralized layout, with point to point<br />

links between the MLVS and current consumers or sub-distribution boards (radial<br />

distribution, star- distribution) (Fig. D13):<br />

Fig. D13: Example <strong>of</strong> centralized layout with point to point links<br />

In decentralized layout, current consumers are connected to sources via a busway.<br />

Busbar trunking systems are well suited to decentralized layout, to supply many<br />

loads that are spread out, making it easy to change, move or add connections<br />

(Fig D14):<br />

Fig. D14 : Example <strong>of</strong> decentralized layout, with busbar trunking links<br />

Factors in favour <strong>of</strong> centralized layout (see summary table in Fig. D15):<br />

b Installation flexibility: no,<br />

b Load distribution: localized loads (high unit power loads).<br />

Factors in favor <strong>of</strong> decentralized layout:<br />

b Installation flexibility: "Implementation" flexibility (moving <strong>of</strong> workstations, etc…),<br />

b Load distribution: uniform distribution <strong>of</strong> low unit power loads<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

7 Choice <strong>of</strong> architecture details<br />

Load distribution<br />

Flexibility Localized loads Intermediate<br />

distribution<br />

No flexibility<br />

Design flexibility<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Uniform distributed<br />

Centralized Decentralized<br />

Implementation<br />

flexibility Centralized Decentralized<br />

Operation flexibility<br />

Fig. D15 : Recommendations for centralized or decentralized layout<br />

Power supply by cables gives greater independence <strong>of</strong> circuits (lighting, power<br />

sockets, HVAC, motors, auxiliaries, security, etc), reducing the consequences <strong>of</strong> a<br />

fault from the point <strong>of</strong> view <strong>of</strong> power availability.<br />

The use <strong>of</strong> busbar trunking systems allows load power circuits to be combined and<br />

saves on conductors by taking advantage <strong>of</strong> a clustering coefficient. The choice<br />

between cable and busbar trunking, according to the clustering coefficient, allows us<br />

to find an economic optimum between investment costs, implementation costs and<br />

operating costs.<br />

These two distribution modes are <strong>of</strong>ten combined.<br />

Presence <strong>of</strong> back-up generators (Fig. D16)<br />

Here we only consider LV back-up generators.<br />

The <strong>electrical</strong> power supply supplied by a back-up generator is produced by an<br />

alternator, driven by a thermal engine.<br />

No power can be produced until the generator has reached its rated speed. This type<br />

<strong>of</strong> device is therefore not suitable for an uninterrupted power supply.<br />

According to the generator’s capacity to supply power to all or only part <strong>of</strong> the<br />

<strong>installation</strong>, there is either total or partial redundancy.<br />

A back-up generator functions generally disconnected from the network. A source<br />

switching system is therefore necessary.<br />

The generator can function permanently or intermittently. Its back-up time depends<br />

on the quantity <strong>of</strong> available fuel.<br />

Fig. D16 : Connection <strong>of</strong> a back-up generator<br />

LV switchboard<br />

The main characteristics to consider for implementing LV back-up generator:<br />

b Sensitivity <strong>of</strong> loads to power interruption,<br />

b Availability <strong>of</strong> the public distribution network,<br />

b Other constraints (e.g.: generators compulsory in hospitals or high-vise buildings)<br />

The presence <strong>of</strong> generators can be decided to reduce the energy bill or due to the<br />

opportunity for co-generation. These two aspects are not taken into account in this<br />

guide.<br />

The presence <strong>of</strong> a back-up generator is essential if the loads cannot be shed for<br />

an indefinite duration (long interruption only acceptable) or if the utility network<br />

availability is low.<br />

Determining the number <strong>of</strong> back-up generator units is in line with the same criteria<br />

as determining the number <strong>of</strong> transformers, as well as taking account <strong>of</strong> economic<br />

and availability considerations (redundancy, start-up reliability, maintenance facility).<br />

G<br />

D21<br />

© Schneider Electric - all rights reserved


D22<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

MLVS<br />

Fig. D18 : Radial single feeder configuration<br />

MLVS<br />

Fig. D19 : Two-pole configuration<br />

MLVS<br />

NO<br />

Fig. D20 : Two-pole configuration with two ½ MLVS and NO link<br />

7 Choice <strong>of</strong> architecture details<br />

7.3 Presence <strong>of</strong> an Uninterruptible Power Supply (UPS)<br />

The <strong>electrical</strong> power from a UPS is supplied from a storage unit: batteries or inertia<br />

wheel. This system allows us to avoid any power failure. The back-up time <strong>of</strong> the<br />

system is limited: from several minutes to several hours.<br />

The simultaneous presence <strong>of</strong> a back-up generator and a UPS unit is used for<br />

permanently supply loads for which no failure is acceptable (Fig. D17). The back-up<br />

time <strong>of</strong> the battery or the inertia wheel must be compatible with the maximum time<br />

for the generator to start up and be brought on-line.<br />

A UPS unit is also used for supply power to loads that are sensitive to disturbances<br />

(generating a “clean” voltage that is independent <strong>of</strong> the network).<br />

Main characteristics to be considered for implementing a UPS:<br />

b Sensitivity <strong>of</strong> loads to power interruptions,<br />

b Sensitivity <strong>of</strong> loads to disturbances.<br />

The presence <strong>of</strong> a UPS unit is essential if and only if no failure is acceptable.<br />

LV Switchboard<br />

Non-critical<br />

circuit<br />

Fig. D17 : Example <strong>of</strong> connection for a UPS<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Normal<br />

ASI<br />

Critical<br />

circuit<br />

7.4 Configuration <strong>of</strong> LV circuits<br />

G<br />

By-pass<br />

Main possible configurations (see figures D18 to D25):<br />

b Radial single feeder configuration: This is the reference configuration and<br />

the most simple. A load is connected to only one single source. This configuration<br />

provides a minimum level <strong>of</strong> availability, since there is no redundancy in case <strong>of</strong><br />

power source failure.<br />

b Two-pole configuration: The power supply is provided by 2 transformers,<br />

connected to the same MV line. When the transformers are close, they are generally<br />

connected in parallel to the same MLVS.<br />

b Variant: two-pole with two ½ MLVS: In order to increase the availability in case<br />

<strong>of</strong> failure <strong>of</strong> the busbars or authorize maintenance on one <strong>of</strong> the transformers,<br />

it is possible to split the MLVS into 2 parts, with a normally open link (NO). This<br />

configuration generally requires an Automatic Transfer Switch, (ATS).<br />

b Shedable switchboard (simple disconnectable attachment): A series <strong>of</strong><br />

shedable circuits can be connected to a dedicated switchboard. The connection to<br />

the MLVS is interrupted when needed (overload, generator operation, etc)<br />

b Interconnected switchboards: If transformers are physically distant from one<br />

another, they may be connected by a busbar trunking. A critical load can be supplied<br />

by one or other <strong>of</strong> the transformers. The availability <strong>of</strong> power is therefore improved,<br />

since the load can always be supplied in the case <strong>of</strong> failure <strong>of</strong> one <strong>of</strong> the sources.<br />

The redundancy can be:<br />

v Total: each transformer being capable <strong>of</strong> supplying all <strong>of</strong> the <strong>installation</strong>,<br />

v Partial: each transformer only being able to supply part <strong>of</strong> the <strong>installation</strong>. In this<br />

case, part <strong>of</strong> the loads must be disconnected (load-shedding) in the case <strong>of</strong> one <strong>of</strong><br />

the transformers failing.


D - MV & LV architecture selection guide<br />

LV swichboard<br />

Fig. D21 : Shedable switchboard<br />

MLVS<br />

Busbar<br />

Fig. D22 : Interconnected switchboards<br />

Busbar<br />

MLVS<br />

MLVS<br />

Fig. D23 : Ring configuration<br />

Busbar<br />

Busbar<br />

MLVS<br />

MLVS<br />

MLVS<br />

MLVS<br />

Busbar<br />

7 Choice <strong>of</strong> architecture details<br />

b Ring configuration: This configuration can be considered as an extension <strong>of</strong> the<br />

configuration with interconnection between switchboards. Typically, 4 transformers<br />

connected to the same MV line, supply a ring using busbar trunking. A given load<br />

is then supplied power by several clustered transformers. This configuration is well<br />

suited to extended <strong>installation</strong>s, with a high load density (in kVA/m²). If all <strong>of</strong> the loads<br />

can be supplied by 3 transformers, there is total redundancy in the case <strong>of</strong> failure<br />

<strong>of</strong> one <strong>of</strong> the transformers. In fact, each busbar can be fed power by one or other<br />

<strong>of</strong> its ends. Otherwise, downgraded operation must be considered (with partial load<br />

shedding). This configuration requires special <strong>design</strong> <strong>of</strong> the protection plan in order<br />

to ensure discrimination in all <strong>of</strong> the fault circumstances.<br />

b Double-ended power supply: This configuration is implemented in cases where<br />

maximum availability is required. The principle involves having 2 independent power<br />

sources, e.g.:<br />

v 2 transformers supplied by different MV lines,<br />

v 1 transformer and 1 generator,<br />

v 1 transformer and 1 UPS.<br />

An automatic transfer switch (ATS) is used to avoid the sources being parallel<br />

connected. This configuration allows preventive and curative maintenance to be<br />

carried out on all <strong>of</strong> the <strong>electrical</strong> distribution system upstream without interrupting<br />

the power supply.<br />

b Configuration combinations: An <strong>installation</strong> can be made up <strong>of</strong> several subasssemblies<br />

with different configurations, according to requirements for the<br />

availability <strong>of</strong> the different types <strong>of</strong> load. E.g.: generator unit and UPS, choice by<br />

sectors (some sectors supplied by cables and others by busbar trunking).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

or G or UPS<br />

Fig. D24 : Double-ended configuration with automatic transfer switch<br />

1<br />

MLVS<br />

2 3<br />

Busbar<br />

MLVS<br />

Fig. D25 : Example <strong>of</strong> a configuration combination<br />

1: Single feeder, 2: Switchboard interconnection, 3: Double-ended<br />

G<br />

D23<br />

© Schneider Electric - all rights reserved


D24<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

Characteristic to be<br />

considered<br />

Configuration<br />

7 Choice <strong>of</strong> architecture details<br />

For the different possible configurations, the most probable and usual set <strong>of</strong><br />

characteristics is given in the following table:<br />

Radial Two-pole Sheddable load Interconnected<br />

switchboards<br />

Site topology Any Any Any 1 level<br />

5 to 25000m²<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Ring Double-ended<br />

1 level<br />

5 to 25000m²<br />

Location latitude Any Any Any Medium <strong>of</strong> high Medium or high Any<br />

Maintainability Minimal Standard Minimal Standard Standard Enhanced<br />

Power demand < 2500kVA Any Any ≥ 1250kVA > 2500kVA Any<br />

Load distribution Localized loads Localized loads Localized load Intermediate or<br />

uniforme distribution<br />

Interruptions sensitivity Long<br />

interruption<br />

acceptable<br />

Long<br />

interruption<br />

acceptable<br />

Sheddable Long<br />

interruption<br />

acceptable<br />

Any<br />

Uniform distribution Localized loads<br />

Long<br />

interruption<br />

acceptable<br />

Short or no<br />

interruption<br />

Disturbances sensitivity Low sensitivity High sensitivity Low sensitivity High sensitivity High sensitivity High sensitivity<br />

Other constraints / / / / / Double-ended<br />

loads


D - MV & LV architecture selection guide<br />

8 Choice <strong>of</strong> equipment<br />

The choice <strong>of</strong> equipment is step 3 in the <strong>design</strong> <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong>. The aim<br />

<strong>of</strong> this step is to select equipment from the manufacturers’ catalogues. The choice <strong>of</strong><br />

technological solutions results from the choice <strong>of</strong> architecture.<br />

List <strong>of</strong> equipment to consider:<br />

b MV/LV substation,<br />

b MV switchboards,<br />

b Transformers,<br />

b LV switchboards,<br />

b Busbar trunking,<br />

b UPS units,<br />

b Power factor correction and filtering equipment.<br />

Criteria to consider:<br />

b Atmosphere, environment,<br />

b Service index,<br />

b Offer availability per country,<br />

b Utilities requirements,<br />

b Previous architecture choices.<br />

The choice <strong>of</strong> equipment is basically linked to the <strong>of</strong>fer availability in the country. This<br />

criterion takes into account the availability <strong>of</strong> certain ranges <strong>of</strong> equipment or local<br />

technical support.<br />

The detailed selection <strong>of</strong> equipment is out <strong>of</strong> the scope <strong>of</strong> this document.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D25<br />

© Schneider Electric - all rights reserved


D26<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

9 Recommendations for<br />

architecture optimization<br />

These recommendations are intended to guide the <strong>design</strong>er towards architecture<br />

upgrades which allow him to improve assessment criteria.<br />

9.1 On-site work<br />

To be compatible with the “special” or “critical” work-site time, it is recommended to<br />

limit uncertainties by applying the following recommendations:<br />

b Use <strong>of</strong> proven solutions and equipment that has been validated and tested by<br />

manufacturers (“functional” switchboard or “manufacturer” switchboard according to<br />

the application criticality),<br />

b Prefer the implementation <strong>of</strong> equipment for which there is a reliable distribution<br />

network and for which it is possible to have local support (supplier well established),<br />

b Prefer the use <strong>of</strong> factory-built equipment (MV/LV substation, busbar trunking),<br />

allowing the volume <strong>of</strong> operations on site to be limited,<br />

b Limit the variety <strong>of</strong> equipment implemented (e.g. the power <strong>of</strong> transformers),<br />

b Avoid mixing equipment from different manufacturers.<br />

9.2 Environmental impact<br />

The optimization <strong>of</strong> the environmental assessment <strong>of</strong> an <strong>installation</strong> will involve<br />

reducing:<br />

b Power losses at full load and no load during <strong>installation</strong> operation,<br />

b Overall, the mass <strong>of</strong> materials used to produce the <strong>installation</strong>.<br />

Taken separately and when looking at only one piece <strong>of</strong> equipment, these 2<br />

objectives may seem contradictory. However, when applied to whole <strong>installation</strong>, it<br />

is possible to <strong>design</strong> the architecture to contribute to both objectives. The optimal<br />

<strong>installation</strong> will therefore not be the sum <strong>of</strong> the optimal equipment taken separately,<br />

but the result <strong>of</strong> an optimization <strong>of</strong> the overall <strong>installation</strong>.<br />

Figure D26 gives an example <strong>of</strong> the contribution per equipment category to the<br />

weight and energy dissipation for a 3500 kVA <strong>installation</strong> spread over 10000m².<br />

LV switchboard<br />

and switchgear<br />

5 %<br />

LV cables<br />

and trunking<br />

75 %<br />

Transformers<br />

20 %<br />

10 %<br />

LV cables<br />

and trunking<br />

46 %<br />

Transformers<br />

44 %<br />

Total loss for equipment considered: 414 MWh Total mass <strong>of</strong> equipment considered: 18,900 kg<br />

Fig. D26 : Example <strong>of</strong> the spread <strong>of</strong> losses and the weight <strong>of</strong> material for each equipment category<br />

LV switchboard<br />

and switchgear<br />

<strong>General</strong>ly speaking, LV cables and trunking as well as the MV/LV transformers are<br />

the main contributors to operating losses and the weight <strong>of</strong> equipment used.<br />

Environmental optimization <strong>of</strong> the <strong>installation</strong> by the architecture will therefore<br />

involve:<br />

b reducing the length <strong>of</strong> LV circuits in the <strong>installation</strong>,<br />

b clustering LV circuits wherever possible to take advantage <strong>of</strong> the factor <strong>of</strong><br />

simultaneity ks (see chapter A: <strong>General</strong> <strong>rules</strong> <strong>of</strong> <strong>electrical</strong> <strong>installation</strong> <strong>design</strong>, <strong>Chapter</strong><br />

– Power loading <strong>of</strong> an <strong>installation</strong>, 4.3 “Estimation <strong>of</strong> actual maximum kVA demand”)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

Objectives Resources<br />

Reducing the length <strong>of</strong> LV<br />

circuits<br />

Solution Barycenter position<br />

N°1<br />

N°2<br />

Fig. D28 : Example <strong>of</strong> barycenter positioning<br />

MLVS area<br />

MLVS area<br />

Workshop 1<br />

Workshop 1<br />

Barycenter<br />

Barycenter<br />

line 1<br />

Workshop 1<br />

9 Recommendations for<br />

architecture optimization<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Placing MV/LV substations as close as possible to the barycenter<br />

<strong>of</strong> all <strong>of</strong> the LV loads to be supplied<br />

Clustering LV circuits When the simultaneity factor <strong>of</strong> a group <strong>of</strong> loads to be supplied<br />

is less than 0.7, the clustering <strong>of</strong> circuits allows us to limit the<br />

volume <strong>of</strong> conductors supplying power to these loads.<br />

In real terms this involves:<br />

b setting up sub-distribution switchboards as close as possible to<br />

the barycenter <strong>of</strong> the groups <strong>of</strong> loads if they are localized,<br />

b setting up busbar trunking systems as close as possible to the<br />

barycenter <strong>of</strong> the groups <strong>of</strong> loads if they are distributed.<br />

The search for an optimal solution may lead to consider several<br />

clustering scenarios.<br />

In all cases, reducing the distance between the barycenter <strong>of</strong><br />

a group <strong>of</strong> loads and the equipment that supplies them power<br />

allows to reduce environmental impact.<br />

Fig. D27 : Environmental optimization : Objectives and Ressources.<br />

As an example figure D28 shows the impact <strong>of</strong> clustering circuits on reducing<br />

the distance between the barycenter <strong>of</strong> the loads <strong>of</strong> an <strong>installation</strong> and that <strong>of</strong> the<br />

sources considered (MLVS whose position is imposed). This example concerns a<br />

mineral water bottling plant for which:<br />

b the position <strong>of</strong> <strong>electrical</strong> equipment (MLVS) is imposed in the premises outside <strong>of</strong><br />

the process area for reasons <strong>of</strong> accessibility and atmosphere constraints,<br />

b the installed power is around 4 MVA.<br />

In solution No.1, the circuits are distributed for each workshop.<br />

In solution No. 2, the circuits are distributed by process functions (production lines).<br />

Barycenter<br />

line 2<br />

Workshop 2<br />

Workshop 2<br />

Barycenter<br />

Workshop 2<br />

Barycenter<br />

line 3<br />

Workshop 3<br />

Workshop 3<br />

Barycenter<br />

Workshop 3<br />

Barycenter<br />

line 3<br />

Storage<br />

Storage<br />

D27<br />

© Schneider Electric - all rights reserved


D28<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

9 Recommendations for<br />

architecture optimization<br />

Without changing the layout <strong>of</strong> <strong>electrical</strong> equipment, the second solution allows us<br />

to achieve gains <strong>of</strong> around 15% on the weight <strong>of</strong> LV cables to be installed (gain on<br />

lengths) and a better uniformity <strong>of</strong> transformer power.<br />

To supplement the optimizations carried out in terms <strong>of</strong> architecture, the following<br />

points also contribute to the optimization:<br />

b the setting up <strong>of</strong> LV power factor correction to limit losses in the transformers and<br />

LV circuits if this compensation is distributed,<br />

b the use <strong>of</strong> low loss transformers,<br />

b the use <strong>of</strong> aluminum LV busbar trunking when possible, since natural resources <strong>of</strong><br />

this metal are greater.<br />

9.3 Preventive maintenance volume<br />

Recommendations for reducing the volume <strong>of</strong> preventive maintenance:<br />

b Use the same recommendations as for reducing the work site time,<br />

b Focus maintenance work on critical circuits,<br />

b Standardize the choice <strong>of</strong> equipment,<br />

b Use equipment <strong>design</strong>ed for severe atmospheres (requires less maintenance).<br />

9.4 Electrical power availability<br />

Recommendations for improving the <strong>electrical</strong> power availability:<br />

b Reduce the number <strong>of</strong> feeders per switchboard, in order to limit the effects <strong>of</strong> a<br />

possible failure <strong>of</strong> a switchboard,<br />

b Distributing circuits according to availability requirements,<br />

b Using equipment that is in line with requirements (see Service Index, 4.2),<br />

b Follow the selection guides proposed for steps 1 & 2 (see Fig. D3 page D5).<br />

Recommendations to increase the level <strong>of</strong> availability:<br />

b Change from a radial single feeder configuration to a two-pole configuration,<br />

b Change from a two-pole configuration to a double-ended configuration,<br />

b Change from a double-ended configuration to a uninterruptible configuration with a<br />

UPS unit and a Static Transfer Switch<br />

b Increase the level <strong>of</strong> maintenance (reducing the MTTR, increasing the MTBF)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

10 Glossary<br />

Architecture: choice <strong>of</strong> a single-line diagram and technological solutions, from<br />

connection to the utility network through to load power supply circuits.<br />

Main MV/LV distribution: Level upstream <strong>of</strong> the architecture, from connection<br />

to the network utility through to LV distribution equipment on the site (MLVS – or<br />

equivalent).<br />

MLVS – Main Low Voltage Switchboard: Main switchboard downstream <strong>of</strong> the<br />

MV/LV transformer, starting point <strong>of</strong> power distribution circuits in the <strong>installation</strong><br />

LV power distribution: intermediate level in the architecture, downstream <strong>of</strong> the<br />

main level through to the sub-distribution switchboards (spatial and functional<br />

distribution <strong>of</strong> <strong>electrical</strong> power in the circuits).<br />

LV terminal distribution: Downstream level <strong>of</strong> the architecture, downstream <strong>of</strong> the<br />

sub-distribution switchboards through to the loads. This level <strong>of</strong> distribution is not<br />

dealt with in this guide.<br />

Single-line diagram: general <strong>electrical</strong> schematic diagram to represent the main<br />

<strong>electrical</strong> equipment and their interconnection.<br />

MV substation, transformation substation: Enclosures grouping together MV<br />

equipment and/or MV/LV transformers. These enclosures can be shared or separate,<br />

according to the site layout, or the equipment technology. In certain countries, the<br />

MV substation is assimilated with the delivery substation.<br />

Technological solution: Resulting from the choice <strong>of</strong> technology for an <strong>installation</strong><br />

sub-assembly, from among the different products and equipment proposed by the<br />

manufacturer.<br />

Characteristics: Technical or environmental data relative to the <strong>installation</strong>, enabling<br />

the best-suited architecture to be selected.<br />

Criteria: Parameters for assessing the <strong>installation</strong>, enabling selection <strong>of</strong> the<br />

architecture that is the best-suited to the needs <strong>of</strong> the customer.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

D29<br />

© Schneider Electric - all rights reserved


D30<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

11 ID-Spec s<strong>of</strong>tware<br />

ID-Spec is a new s<strong>of</strong>tware which aims at helping the <strong>design</strong>er to be more productive<br />

in draft <strong>design</strong> phase and argue easily his <strong>design</strong> decisions.<br />

It supports the <strong>design</strong>er in selecting the relevant single line diagram patterns for main<br />

distribution and sub distribution and in adapting these patterns to his project. It also<br />

supports the <strong>design</strong>er in equipment technology and rating selection. Its generates<br />

automatically the corresponding <strong>design</strong> specification documentation including single<br />

line diagram and its argument, list and specification <strong>of</strong> the corresponding equipment.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


D - MV & LV architecture selection guide<br />

12 Example: <strong>electrical</strong> <strong>installation</strong><br />

in a printworks<br />

12.1 Brief description<br />

Printing <strong>of</strong> personalized mailshots intended for mail order sales.<br />

12.2 Installation characteristics<br />

Characteristic Category<br />

Activity Mechanical<br />

Site topology single storey building,<br />

10000m² (8000m² dedicated to the process, 2000m² for<br />

ancillary areas)<br />

Layout latitude High<br />

Service reliability Standard<br />

Maintainability Standard<br />

Installation flexibility b No flexibility planned:<br />

v HVAC<br />

v Process utilities<br />

v Office power supply<br />

b Possible flexibility:<br />

v finishing, putting in envelopes<br />

v special machines, installed at a later date<br />

v rotary machines (uncertainty at the draft <strong>design</strong> stage)<br />

Power demand 3500kVA<br />

Load distribution Intermediate distribution<br />

Power interruptions sensitivity b Sheddable circuits:<br />

v <strong>of</strong>fices (apart from PC power sockets)<br />

v air conditioning, <strong>of</strong>fice heating<br />

v social premises<br />

v maintenance premises<br />

b long interruptions acceptable:<br />

v printing machines<br />

v workshop HVAC (hygrometric control)<br />

v Finishing, envelope filling<br />

v Process utilities (compressor, recycling <strong>of</strong> cooled water)<br />

b No interruptions acceptable:<br />

v servers, <strong>of</strong>fice PCs<br />

Disturbance sensitivity b Average sensitivity:<br />

v motors, lighting<br />

b High sensitivity:<br />

v IT<br />

Disturbance capability Non disturbing<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

No special precaution to be taken due to the connection to<br />

the EdF network (low level <strong>of</strong> disturbance)<br />

Other constraints b Building with lightning classification: lightning surge<br />

arresters installed<br />

b Power supply by overhead single feeder line<br />

12.3 Technological characteristics<br />

Criteria Category<br />

Atmosphere, environment b IP: standard (no dust, no water protection)<br />

b IK: standard (use <strong>of</strong> technical pits, dedicated premises)<br />

b °C: standard (temperature regulation)<br />

Service index 211<br />

Offer availability by country No problem (project carried out in France)<br />

Other criteria Nothing particular<br />

D31<br />

© Schneider Electric - all rights reserved


D32<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

12 Example: <strong>electrical</strong> <strong>installation</strong><br />

in a printworks<br />

12.4 Architecture assessment criteria<br />

Criteria Category<br />

On-site work time Secondary<br />

Environmental impact Minimal: compliance with European standard regulations<br />

Preventive maintenance costs Standard<br />

Power supply availability Level I<br />

Step 1: Architecture fundamentals<br />

Choice Main criteria Solution<br />

Connection to upstream<br />

network<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Isolated site single branch circuit<br />

MV Circuits Layout + criticality single feeder<br />

Number <strong>of</strong> transformers Power > 2500kVA 2 x 2000kVA<br />

Number and distribution <strong>of</strong><br />

substations<br />

Surface area and power<br />

distribution<br />

MV Generator Site activity No<br />

MV<br />

LV<br />

MV<br />

LV<br />

2 possible solutions: 1<br />

substation or 2 substations<br />

b if 1 substations: NO link<br />

between MLVS<br />

b if 2 substations:<br />

interconnected switchboards<br />

MLVS 1 MLVS 2 MLVS 1 MLVS 2<br />

Fig. D29 : Two possible single-line diagrams<br />

MV<br />

LV<br />

Trunking<br />

MV<br />

LV


D - MV & LV architecture selection guide<br />

12 Example: <strong>electrical</strong> <strong>installation</strong><br />

in a printworks<br />

Step 2: Architecture details<br />

“1 substation” solution<br />

Choice Main criteria Solution<br />

Layout Atmospheric constraint Dedicated premises<br />

Centralized or decentralized<br />

layout<br />

Presence <strong>of</strong> back-up<br />

generator<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Uniform loads, distributed<br />

power, scalability possibilities<br />

Non-uniform loads, direct link<br />

from MLVS<br />

Criticality ≤ low<br />

Network availability: standard<br />

b Decentralized with busbar<br />

trunking:<br />

v finishing sector, envelope<br />

filling<br />

b Centralized with cables:<br />

v special machines,<br />

rotary machines, HVAC,<br />

process utilities, <strong>of</strong>fices<br />

(2 switchboards), <strong>of</strong>fice air<br />

conditioning, social premises,<br />

maintenance<br />

No back-up generator<br />

Presence <strong>of</strong> UPS Criticality UPS unit for servers and <strong>of</strong>fice<br />

PCs<br />

LV circuit configuration 2 transformers, possible<br />

partial redundancy<br />

MV<br />

MLVS 1 MLVS 2<br />

ASI<br />

Sheddable Offices<br />

Fig. D30 : Detailed single-line diagram (1 substation)<br />

LV<br />

HVAC<br />

MV<br />

LV<br />

b Two-pole, variant 2 ½ MLVS<br />

+ NO link (reduction <strong>of</strong> the Isc<br />

by MLVS, no redundancy<br />

b process (≤ weak)<br />

b sheddable circuit for noncritical<br />

loads<br />

Trunking<br />

Machines<br />

D33<br />

© Schneider Electric - all rights reserved


D34<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

12 Example: <strong>electrical</strong> <strong>installation</strong><br />

in a printworks<br />

12.5 Choice <strong>of</strong> technological solutions:<br />

Choice Main criteria Solution<br />

MV/LV substation Atmosphere, environment indoor (dedicated premises)<br />

MV switchboard Offer availability by country SM6 (<strong>installation</strong> produced in<br />

France)<br />

Transformers Atmosphere, environment cast resin transfo (avoids<br />

constraints related to oil)<br />

LV switchboard Atmosphere, IS MLVS: Prisma + P<br />

Sub-distribution: Prisma +<br />

Busbar trunking Installed power to be<br />

supplied<br />

UPS units Installed power to be<br />

supplied, back-up time<br />

Power factor correction Installed power, presence <strong>of</strong><br />

harmonics<br />

“2 substation” solution<br />

Ditto apart from:<br />

LV circuit: 2 remote MLVS connected via busbar trunking<br />

MV<br />

LV<br />

Fig. D31 : Detailed single-line diagram (2 substations)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Canalis KS<br />

Galaxy PW<br />

MLVS 1 MLVS 2<br />

Sheddable<br />

ASI<br />

Offices<br />

LV, standard, automatic<br />

(Average Q, ease <strong>of</strong><br />

<strong>installation</strong>)<br />

Trunking Trunking<br />

HVAC<br />

MV<br />

LV<br />

Machines


2<br />

3<br />

<strong>Chapter</strong> E<br />

LV Distribution<br />

Contents<br />

Earthing schemes E2<br />

1.1 Earthing connections E2<br />

1.2 Definition <strong>of</strong> standardised earthing schemes E3<br />

1.3 Characteristics <strong>of</strong> TT, TN and IT systems E6<br />

1.4 Selection criteria for the TT, TN and IT systems E8<br />

1.5 Choice <strong>of</strong> earthing method - implementation E10<br />

1.6 Installation and measurements <strong>of</strong> earth electrodes E11<br />

The <strong>installation</strong> system E 5<br />

2.1 Distribution boards E15<br />

2.2 Cables and busways E18<br />

External influences (IEC 60364-5-5 ) E25<br />

3.1 Definition and reference standards E25<br />

3.2 Classification E25<br />

3.3 List <strong>of</strong> external influences E25<br />

3.4 Protection provided for enclosed equipment: codes IP and IK E28<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

E2<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

In a building, the connection <strong>of</strong> all metal parts<br />

<strong>of</strong> the building and all exposed conductive parts<br />

<strong>of</strong> <strong>electrical</strong> equipment to an earth electrode<br />

prevents the appearance <strong>of</strong> dangerously high<br />

voltages between any two simultaneously<br />

accessible metal parts<br />

4<br />

Extraneous<br />

conductive<br />

parts<br />

4<br />

Heating<br />

Water<br />

Branched<br />

protective<br />

conductors<br />

to individual<br />

consumers<br />

Gas<br />

5<br />

1<br />

5<br />

5<br />

Fig. E1 : An example <strong>of</strong> a block <strong>of</strong> flats in which the main<br />

earthing terminal (6) provides the main equipotential connection;<br />

the removable link (7) allows an earth-electrode-resistance<br />

check<br />

2<br />

7<br />

3<br />

3<br />

3<br />

6<br />

Main<br />

protective<br />

conductor<br />

Earthing schemes<br />

. Earthing connections<br />

Definitions<br />

National and international standards (IEC 60364) clearly define the various elements<br />

<strong>of</strong> earthing connections. The following terms are commonly used in industry and in<br />

the literature. Bracketed numbers refer to Figure E :<br />

b Earth electrode (1): A conductor or group <strong>of</strong> conductors in intimate contact with,<br />

and providing an <strong>electrical</strong> connection with Earth (cf details in section 1.6 <strong>of</strong> <strong>Chapter</strong> E.)<br />

b Earth: The conductive mass <strong>of</strong> the Earth, whose electric potential at any point is<br />

conventionally taken as zero<br />

b Electrically independent earth electrodes: Earth electrodes located at such a<br />

distance from one another that the maximum current likely to flow through one <strong>of</strong><br />

them does not significantly affect the potential <strong>of</strong> the other(s)<br />

b Earth electrode resistance: The contact resistance <strong>of</strong> an earth electrode with the<br />

Earth<br />

b Earthing conductor (2): A protective conductor connecting the main earthing<br />

terminal (6) <strong>of</strong> an <strong>installation</strong> to an earth electrode (1) or to other means <strong>of</strong> earthing<br />

(e.g. TN systems);<br />

b Exposed-conductive-part: A conductive part <strong>of</strong> equipment which can be touched<br />

and which is not a live part, but which may become live under fault conditions<br />

b Protective conductor (3): A conductor used for some measures <strong>of</strong> protection against<br />

electric shock and intended for connecting together any <strong>of</strong> the following parts:<br />

v Exposed-conductive-parts<br />

v Extraneous-conductive-parts<br />

v The main earthing terminal<br />

v Earth electrode(s)<br />

v The earthed point <strong>of</strong> the source or an artificial neutral<br />

b Extraneous-conductive-part: A conductive part liable to introduce a potential,<br />

generally earth potential, and not forming part <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong> (4).<br />

For example:<br />

v Non-insulated floors or walls, metal framework <strong>of</strong> buildings<br />

v Metal conduits and pipework (not part <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong>) for water, gas,<br />

heating, compressed-air, etc. and metal materials associated with them<br />

b Bonding conductor (5): A protective conductor providing equipotential bonding<br />

b Main earthing terminal (6): The terminal or bar provided for the connection <strong>of</strong><br />

protective conductors, including equipotential bonding conductors, and conductors<br />

for functional earthing, if any, to the means <strong>of</strong> earthing.<br />

Connections<br />

The main equipotential bonding system<br />

The bonding is carried out by protective conductors and the aim is to ensure that,<br />

in the event <strong>of</strong> an incoming extraneous conductor (such as a gas pipe, etc.) being<br />

raised to some potential due to a fault external to the building, no difference <strong>of</strong><br />

potential can occur between extraneous-conductive-parts within the <strong>installation</strong>.<br />

The bonding must be effected as close as possible to the point(s) <strong>of</strong> entry into the<br />

building, and be connected to the main earthing terminal (6).<br />

However, connections to earth <strong>of</strong> metallic sheaths <strong>of</strong> communications cables require<br />

the authorisation <strong>of</strong> the owners <strong>of</strong> the cables.<br />

Supplementary equipotential connections<br />

These connections are intended to connect all exposed-conductive-parts and all<br />

extraneous-conductive-parts simultaneously accessible, when correct conditions<br />

for protection have not been met, i.e. the original bonding conductors present an<br />

unacceptably high resistance.<br />

Connection <strong>of</strong> exposed-conductive-parts to the earth electrode(s)<br />

The connection is made by protective conductors with the object <strong>of</strong> providing a lowresistance<br />

path for fault currents flowing to earth.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

The different earthing schemes (<strong>of</strong>ten referred<br />

to as the type <strong>of</strong> power system or system<br />

earthing arrangements) described characterise<br />

the method <strong>of</strong> earthing the <strong>installation</strong><br />

downstream <strong>of</strong> the secondary winding <strong>of</strong> a<br />

MV/LV transformer and the means used for<br />

earthing the exposed conductive-parts <strong>of</strong> the<br />

LV <strong>installation</strong> supplied from it<br />

Earthing schemes<br />

Components (see Fig. E2)<br />

Effective connection <strong>of</strong> all accessible metal fixtures and all exposed-conductive-parts<br />

<strong>of</strong> <strong>electrical</strong> appliances and equipment, is essential for effective protection against<br />

electric shocks.<br />

Component parts to consider:<br />

as exposed-conductive-parts as extraneous-conductive-parts<br />

Cableways Elements used in building construction<br />

b Conduits b Metal or reinforced concrete (RC):<br />

b Impregnated-paper-insulated lead-covered v Steel-framed structure<br />

cable, armoured or unarmoured v Reinforcement rods<br />

b Mineral insulated metal-sheathed cable v Prefabricated RC panels<br />

(pyrotenax, etc.) b Surface finishes:<br />

Switchgear<br />

b cradle <strong>of</strong> withdrawable switchgear<br />

Appliances<br />

b Exposed metal parts <strong>of</strong> class 1 insulated<br />

appliances<br />

v Floors and walls in reinforced concrete<br />

without further surface treatment<br />

v<br />

Tiled surface<br />

b<br />

Metallic covering:<br />

v<br />

Metallic wall covering<br />

Non-<strong>electrical</strong> elements Building services elements other than <strong>electrical</strong><br />

b metallic fittings associated with cableways b Metal pipes, conduits, trunking, etc. for gas,<br />

(cable trays, cable ladders, etc.) water and heating systems, etc.<br />

b Metal objects: b Related metal components (furnaces, tanks,<br />

v Close to aerial conductors or to busbars reservoirs, radiators)<br />

v In contact with <strong>electrical</strong> equipment. b Metallic fittings in wash rooms, bathrooms,<br />

toilets, etc.<br />

b Metallised papers<br />

Component parts not to be considered:<br />

as exposed-conductive-parts as extraneous-conductive-parts<br />

Diverse service channels, ducts, etc. b Wooden-block floors<br />

b Conduits made <strong>of</strong> insulating material b Rubber-covered or linoleum-covered floors<br />

b Mouldings in wood or other insulating b Dry plaster-block partition<br />

material b Brick walls<br />

b Conductors and cables without metallic sheaths b Carpets and wall-to-wall carpeting<br />

Switchgear<br />

b Enclosures made <strong>of</strong> insulating material<br />

Appliances<br />

b All appliances having class II insulation<br />

regardless <strong>of</strong> the type <strong>of</strong> exterior envelope<br />

Fig. E2 : List <strong>of</strong> exposed-conductive-parts and extraneous-conductive-parts<br />

.2 Definition <strong>of</strong> standardised earthing schemes<br />

The choice <strong>of</strong> these methods governs the measures necessary for protection against<br />

indirect-contact hazards.<br />

The earthing system qualifies three originally independent choices made by the<br />

<strong>design</strong>er <strong>of</strong> an <strong>electrical</strong> distribution system or <strong>installation</strong>:<br />

b The type <strong>of</strong> connection <strong>of</strong> the <strong>electrical</strong> system (that is generally <strong>of</strong> the neutral<br />

conductor) and <strong>of</strong> the exposed parts to earth electrode(s)<br />

b A separate protective conductor or protective conductor and neutral conductor<br />

being a single conductor<br />

b The use <strong>of</strong> earth fault protection <strong>of</strong> overcurrent protective switchgear which clear<br />

only relatively high fault currents or the use <strong>of</strong> additional relays able to detect and<br />

clear small insulation fault currents to earth<br />

In practice, these choices have been grouped and standardised as explained below.<br />

Each <strong>of</strong> these choices provides standardised earthing systems with three<br />

advantages and drawbacks:<br />

b Connection <strong>of</strong> the exposed conductive parts <strong>of</strong> the equipment and <strong>of</strong> the neutral<br />

conductor to the PE conductor results in equipotentiality and lower overvoltages but<br />

increases earth fault currents<br />

b A separate protective conductor is costly even if it has a small cross-sectional area<br />

but it is much more unlikely to be polluted by voltage drops and harmonics, etc. than a<br />

neutral conductor is. Leakage currents are also avoided in extraneous conductive parts<br />

b Installation <strong>of</strong> residual current protective relays or insulation monitoring devices are<br />

much more sensitive and permits in many circumstances to clear faults before heavy<br />

damage occurs (motors, fires, electrocution). The protection <strong>of</strong>fered is in addition<br />

independent with respect to changes in an existing <strong>installation</strong><br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

E4<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Rn<br />

Neutral<br />

Earth<br />

Fig. E3 : TT System<br />

Rn<br />

Neutral<br />

Earth<br />

Fig. E4 : TN-C system<br />

Rn<br />

Fig. E5 : TN-S system<br />

Fig. E6 : TN-C-S system<br />

Exposed conductive parts<br />

Earth<br />

Exposed conductive parts<br />

Neutral<br />

PEN<br />

L1<br />

L2<br />

L3<br />

N<br />

PE<br />

L1<br />

L2<br />

L3<br />

PEN<br />

L1<br />

L2<br />

L3<br />

N<br />

PE<br />

TT system (earthed neutral) (see Fig. E3)<br />

One point at the supply source is connected directly to earth. All exposed- and<br />

extraneous-conductive-parts are connected to a separate earth electrode at the<br />

<strong>installation</strong>. This electrode may or may not be <strong>electrical</strong>ly independent <strong>of</strong> the source<br />

electrode. The two zones <strong>of</strong> influence may overlap without affecting the operation <strong>of</strong><br />

protective devices.<br />

TN systems (exposed conductive parts connected to the<br />

neutral)<br />

The source is earthed as for the TT system (above). In the <strong>installation</strong>, all exposed-<br />

and extraneous-conductive-parts are connected to the neutral conductor. The several<br />

versions <strong>of</strong> TN systems are shown below.<br />

TN-C system (see Fig. E4)<br />

The neutral conductor is also used as a protective conductor and is referred to as<br />

a PEN (Protective Earth and Neutral) conductor. This system is not permitted for<br />

conductors <strong>of</strong> less than 10 mm 2 or for portable equipment.<br />

The TN-C system requires an effective equipotential environment within the<br />

<strong>installation</strong> with dispersed earth electrodes spaced as regularly as possible since<br />

the PEN conductor is both the neutral conductor and at the same time carries phase<br />

unbalance currents as well as 3 rd order harmonic currents (and their multiples).<br />

The PEN conductor must therefore be connected to a number <strong>of</strong> earth electrodes in<br />

the <strong>installation</strong>.<br />

Caution: In the TN-C system, the “protective conductor” function has priority over<br />

the “neutral function”. In particular, a PEN conductor must always be connected to<br />

the earthing terminal <strong>of</strong> a load and a jumper is used to connect this terminal to the<br />

neutral terminal.<br />

TN-S system (see Fig. E5)<br />

The TN-S system (5 wires) is obligatory for circuits with cross-sectional areas less<br />

than 10 mm 2 for portable equipment.<br />

The protective conductor and the neutral conductor are separate. On underground<br />

cable systems where lead-sheathed cables exist, the protective conductor is<br />

generally the lead sheath. The use <strong>of</strong> separate PE and N conductors (5 wires)<br />

is obligatory for circuits with cross-sectional areas less than 10 mm 2 for portable<br />

equipment.<br />

TN-C-S system (see Fig. E6 below and Fig. E7 next page)<br />

The TN-C and TN-S systems can be used in the same <strong>installation</strong>. In the TN-C-S<br />

system, the TN-C (4 wires) system must never be used downstream <strong>of</strong> the TN-S<br />

(5 wires) system, since any accidental interruption in the neutral on the upstream<br />

part would lead to an interruption in the protective conductor in the downstream part<br />

and therefore a danger.<br />

PE<br />

Earthing schemes<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

5 x 50 mm 2<br />

Bad Bad<br />

L1<br />

L2<br />

L3<br />

N<br />

PE<br />

16 mm2 6 mm2 16 mm2 16 mm2<br />

PEN<br />

TN-C scheme not permitted<br />

downstream <strong>of</strong> TN-S scheme


E - Distribution in low-voltage <strong>installation</strong>s<br />

Neutral<br />

Isolated or<br />

impedance-earthed<br />

Fig. E8 : IT system (isolated neutral)<br />

MV/LV<br />

C1<br />

Fig. E9 : IT system (isolated neutral)<br />

Exposed conductive parts<br />

Earth<br />

C2<br />

MV/LV<br />

Zct<br />

C3<br />

R1<br />

R2<br />

L1<br />

L2<br />

L3<br />

N<br />

PE<br />

R3<br />

Earthing schemes<br />

Fig. E7 : Connection <strong>of</strong> the PEN conductor in the TN-C system<br />

IT system (isolated or impedance-earthed neutral)<br />

IT system (isolated neutral)<br />

No intentional connection is made between the neutral point <strong>of</strong> the supply source<br />

and earth (see Fig. E8).<br />

Exposed- and extraneous-conductive-parts <strong>of</strong> the <strong>installation</strong> are connected to an<br />

earth electrode.<br />

In practice all circuits have a leakage impedance to earth, since no insulation<br />

is perfect. In parallel with this (distributed) resistive leakage path, there is the<br />

distributed capacitive current path, the two paths together constituting the normal<br />

leakage impedance to earth (see Fig. E9).<br />

Example (see Fig. E 0)<br />

In a LV 3-phase 3-wire system, 1 km <strong>of</strong> cable will have a leakage impedance due to<br />

C1, C2, C3 and R1, R2 and R3 equivalent to a neutral earth impedance Zct <strong>of</strong> 3,000<br />

to 4,000 Ω, without counting the filtering capacitances <strong>of</strong> electronic devices.<br />

IT system (impedance-earthed neutral)<br />

An impedance Zs (in the order <strong>of</strong> 1,000 to 2,000 Ω) is connected permanently<br />

between the neutral point <strong>of</strong> the transformer LV winding and earth (see Fig. E ).<br />

All exposed- and extraneous-conductive-parts are connected to an earth electrode.<br />

The reasons for this form <strong>of</strong> power-source earthing are to fix the potential <strong>of</strong> a small<br />

network with respect to earth (Zs is small compared to the leakage impedance) and to<br />

reduce the level <strong>of</strong> overvoltages, such as transmitted surges from the MV windings,<br />

static charges, etc. with respect to earth. It has, however, the effect <strong>of</strong> slightly<br />

increasing the first-fault current level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

4 x 95 mm 2<br />

Correct Incorrect Correct Incorrect<br />

PEN connected to the neutral<br />

terminal is prohibited<br />

Fig. E10 : Impedance equivalent to leakage impedances in an<br />

IT system Fig. E11 : IT system (impedance-earthed neutral)<br />

L1<br />

L2<br />

L3<br />

PEN<br />

16 mm2 10 mm2 6 mm2 6 mm2 PEN<br />

PEN<br />

N<br />

MV/LV<br />

Zs<br />

S < 10 mm 2<br />

TNC prohibited<br />

E5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

E6<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

The TT system:<br />

b Technique for the protection <strong>of</strong> persons: the<br />

exposed conductive parts are earthed and<br />

residual current devices (RCDs) are used<br />

b Operating technique: interruption for the first<br />

insulation fault<br />

The TN system:<br />

b Technique for the protection <strong>of</strong> persons:<br />

v Interconnection and earthing <strong>of</strong> exposed<br />

conductive parts and the neutral are mandatory<br />

v Interruption for the first fault using overcurrent<br />

protection (circuit-breakers or fuses)<br />

b Operating technique: interruption for the first<br />

insulation fault<br />

Earthing schemes<br />

.3 Characteristics <strong>of</strong> TT, TN and IT systems<br />

TT system (see Fig. E 2)<br />

Fig. E12 : TT system<br />

Note: If the exposed conductive parts are earthed at a number <strong>of</strong> points, an RCD<br />

must be installed for each set <strong>of</strong> circuits connected to a given earth electrode.<br />

Main characteristics<br />

b Simplest solution to <strong>design</strong> and install. Used in <strong>installation</strong>s supplied directly by the<br />

public LV distribution network.<br />

b Does not require continuous monitoring during operation (a periodic check on the<br />

RCDs may be necessary).<br />

b Protection is ensured by special devices, the residual current devices (RCD), which<br />

also prevent the risk <strong>of</strong> fire when they are set to y 500 mA.<br />

b Each insulation fault results in an interruption in the supply <strong>of</strong> power, however the<br />

outage is limited to the faulty circuit by installing the RCDs in series (selective RCDs)<br />

or in parallel (circuit selection).<br />

b Loads or parts <strong>of</strong> the <strong>installation</strong> which, during normal operation, cause high leakage<br />

currents, require special measures to avoid nuisance tripping, i.e. supply the loads<br />

with a separation transformer or use specific RCDs (see section 5.1 in chapter F).<br />

TN system (see Fig. E 3 and Fig. E 4 )<br />

Fig. E13 : TN-C system<br />

Fig. E14 : TN-S system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

PEN<br />

N<br />

PE


E - Distribution in low-voltage <strong>installation</strong>s<br />

IT system:<br />

b Protection technique:<br />

v Interconnection and earthing <strong>of</strong> exposed<br />

conductive parts<br />

v Indication <strong>of</strong> the first fault by an insulation<br />

monitoring device (IMD)<br />

v Interruption for the second fault using<br />

overcurrent protection (circuit-breakers or fuses)<br />

b Operating technique:<br />

v Monitoring <strong>of</strong> the first insulation fault<br />

v Mandatory location and clearing <strong>of</strong> the fault<br />

v Interruption for two simultaneous insulation<br />

faults<br />

Earthing schemes<br />

Main characteristics<br />

b <strong>General</strong>ly speaking, the TN system:<br />

v requires the <strong>installation</strong> <strong>of</strong> earth electrodes at regular intervals throughout the<br />

<strong>installation</strong><br />

v Requires that the initial check on effective tripping for the first insulation fault<br />

be carried out by calculations during the <strong>design</strong> stage, followed by mandatory<br />

measurements to confirm tripping during commissioning<br />

v Requires that any modification or extension be <strong>design</strong>ed and carried out by a<br />

qualified electrician<br />

v May result, in the case <strong>of</strong> insulation faults, in greater damage to the windings <strong>of</strong><br />

rotating machines<br />

v May, on premises with a risk <strong>of</strong> fire, represent a greater danger due to the higher<br />

fault currents<br />

b In addition, the TN-C system:<br />

v At first glance, would appear to be less expensive (elimination <strong>of</strong> a device pole and<br />

<strong>of</strong> a conductor)<br />

v Requires the use <strong>of</strong> fixed and rigid conductors<br />

v Is forbidden in certain cases:<br />

- Premises with a risk <strong>of</strong> fire<br />

- For computer equipment (presence <strong>of</strong> harmonic currents in the neutral)<br />

b In addition, the TN-S system:<br />

v May be used even with flexible conductors and small conduits<br />

v Due to the separation <strong>of</strong> the neutral and the protection conductor, provides a clean<br />

PE (computer systems and premises with special risks)<br />

IT system (see Fig. E 5)<br />

Cardew<br />

Fig. E15 : IT system<br />

IMD<br />

Main characteristics<br />

b Solution <strong>of</strong>fering the best continuity <strong>of</strong> service during operation<br />

b Indication <strong>of</strong> the first insulation fault, followed by mandatory location and clearing,<br />

ensures systematic prevention <strong>of</strong> supply outages<br />

b <strong>General</strong>ly used in <strong>installation</strong>s supplied by a private MV/LV or LV/LV transformer<br />

b Requires maintenance personnel for monitoring and operation<br />

b Requires a high level <strong>of</strong> insulation in the network (implies breaking up the network<br />

if it is very large and the use <strong>of</strong> circuit-separation transformers to supply loads with<br />

high leakage currents)<br />

b The check on effective tripping for two simultaneous faults must be carried out by<br />

calculations during the <strong>design</strong> stage, followed by mandatory measurements during<br />

commissioning on each group <strong>of</strong> interconnected exposed conductive parts<br />

b Protection <strong>of</strong> the neutral conductor must be ensured as indicated in section 7.2 <strong>of</strong><br />

<strong>Chapter</strong> G<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

E8<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Selection does not depend on safety criteria.<br />

The three systems are equivalent in terms<br />

<strong>of</strong> protection <strong>of</strong> persons if all <strong>installation</strong> and<br />

operating <strong>rules</strong> are correctly followed.<br />

The selection criteria for the best system(s)<br />

depend on the regulatory requirements,<br />

the required continuity <strong>of</strong> service, operating<br />

conditions and the types <strong>of</strong> network and loads.<br />

Fig. E16 : Comparison <strong>of</strong> system earthing arrangements<br />

Earthing schemes<br />

.4 Selection criteria for the TT, TN and IT systems<br />

In terms <strong>of</strong> the protection <strong>of</strong> persons, the three system earthing arrangements<br />

(SEA) are equivalent if all <strong>installation</strong> and operating <strong>rules</strong> are correctly followed.<br />

Consequently, selection does not depend on safety criteria.<br />

It is by combining all requirements in terms <strong>of</strong> regulations, continuity <strong>of</strong> service,<br />

operating conditions and the types <strong>of</strong> network and loads that it is possible to<br />

determine the best system(s) (see Fig. E 6).<br />

Selection is determined by the following factors:<br />

b Above all, the applicable regulations which in some cases impose certain types <strong>of</strong><br />

SEA<br />

b Secondly, the decision <strong>of</strong> the owner if supply is via a private MV/LV transformer<br />

(MV subscription) or the owner has a private energy source (or a separate-winding<br />

transformer)<br />

If the owner effectively has a choice, the decision on the SEA is taken following<br />

discussions with the network <strong>design</strong>er (<strong>design</strong> <strong>of</strong>fice, contractor)<br />

The discussions must cover:<br />

b First <strong>of</strong> all, the operating requirements (the required level <strong>of</strong> continuity <strong>of</strong> service)<br />

and the operating conditions (maintenance ensured by <strong>electrical</strong> personnel or not,<br />

in-house personnel or outsourced, etc.)<br />

b Secondly, the particular characteristics <strong>of</strong> the network and the loads<br />

(see Fig. E 7 next page)<br />

TT TN-S TN-C IT IT2 Comments<br />

Electrical characteristics<br />

Fault current - - - - - + - - Only the IT system <strong>of</strong>fers virtually negligible first-fault currents<br />

Fault voltage - - - + - In the IT system, the touch voltage is very low for the first fault,<br />

but is considerable for the second<br />

Touch voltage<br />

Protection<br />

+/- - - - + - In the TT system, the touch voltage is very low if system is<br />

equipotential, otherwise it is high<br />

Protection <strong>of</strong> persons against indirect contact + + + + + All SEAs (system earthing arrangement) are equivalent,<br />

if the <strong>rules</strong> are followed<br />

Protection <strong>of</strong> persons with emergency + - - + - Systems where protection is ensured by RCDs are not sensitive<br />

generating sets to a change in the internal impedance <strong>of</strong> the source<br />

Protection against fire (with an RCD) + + Not + + All SEAs in which RCDs can be used are equivalent.<br />

allowed The TN-C system is forbidden on premises where there is a risk <strong>of</strong> fire<br />

Overvoltages<br />

Continuous overvoltage + + + - + A phase-to-earth overvoltage is continuous in the IT system<br />

if there is a first insulation fault<br />

Transient overvoltage + - - + - Systems with high fault currents may cause transient overvoltages<br />

Overvoltage if transformer breakdown - + + + + In the TT system, there is a voltage imbalance between<br />

(primary/secondary)<br />

Electromagnetic compatibility<br />

the different earth electrodes. The other systems are interconnected<br />

to a single earth electrode<br />

Immunity to nearby lightning strikes - + + + + In the TT system, there may be voltage imbalances between<br />

the earth electrodes. In the TT system, there is a significant current<br />

loop between the two separate earth electrodes<br />

Immunity to lightning strikes on MV lines - - - - - All SEAs are equivalent when a MV line takes a direct lightning strike<br />

Continuous emission <strong>of</strong> an + + - + + Connection <strong>of</strong> the PEN to the metal structures <strong>of</strong> the building is<br />

electromagnetic field conducive to the continuous generation <strong>of</strong> electromagnetic fields<br />

Transient non-equipotentiality <strong>of</strong> the PE<br />

Continuity <strong>of</strong> service<br />

+ - - + - The PE is no longer equipotential if there is a high fault current<br />

Interruption for first fault - - - + + Only the IT system avoids tripping for the first insulation fault<br />

Voltage dip during insulation fault + - - + - The TN-S, TNC and IT (2nd Installation<br />

fault) systems generate high fault<br />

currents which may cause phase voltage dips<br />

Special devices - + + - - The TT system requires the use <strong>of</strong> RCDs. The IT system requires<br />

the use <strong>of</strong> IMDs<br />

Number <strong>of</strong> earth electrodes - + + -/+ -/+ The TT system requires two distinct earth electrodes. The IT system<br />

<strong>of</strong>fers a choice between one or two earth electrodes<br />

Number <strong>of</strong> cables<br />

Maintenance<br />

- - + - - Only the TN-C system <strong>of</strong>fers, in certain cases, a reduction in<br />

the number <strong>of</strong> cables<br />

Cost <strong>of</strong> repairs - - - - - - - - The cost <strong>of</strong> repairs depends on the damage caused by<br />

the amplitude <strong>of</strong> the fault currents<br />

Installation damage + - - ++ - Systems causing high fault currents require a check on<br />

the <strong>installation</strong> after clearing the fault<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

Type <strong>of</strong> network Advised Possible Not advised<br />

Very large network with high-quality earth electrodes TT, TN, IT (1)<br />

for exposed conductive parts (10 Ω max.) or mixed<br />

Very large network with low-quality earth electrodes TN TN-S IT (1)<br />

for exposed conductive parts (> 30 Ω) TN-C<br />

Disturbed area (storms) TN TT IT (2)<br />

(e.g. television or radio transmitter)<br />

Network with high leakage currents (> 500 mA) TN (4) IT (4)<br />

Network with outdoor overhead lines TT<br />

TT (3) (4)<br />

(5) TN (5) (6) IT (6)<br />

Emergency standby generator set IT TT TN (7)<br />

Type <strong>of</strong> loads<br />

Loads sensitive to high fault currents (motors, etc.) IT TT TN (8)<br />

Loads with a low insulation level (electric furnaces, TN (9) TT (9) IT<br />

welding machines, heating elements, immersion heaters,<br />

equipment in large kitchens)<br />

Numerous phase-neutral single-phase loads TT (10) IT (10)<br />

(mobile, semi-fixed, portable) TN-S TN-C (10)<br />

Loads with sizeable risks (hoists, conveyers, etc.) TN (11) TT (11) IT (11)<br />

Numerous auxiliaries (machine tools) TN-S TN-C TT (12)<br />

(1) When the SEA is not imposed by regulations, it is selected according to the level <strong>of</strong> operating characteristics (continuity <strong>of</strong> service that is<br />

mandatory for safety reasons or desired to enhance productivity, etc.)<br />

Whatever the SEA, the probability <strong>of</strong> an insulation failure increases with the length <strong>of</strong> the network. It may be a good idea to break up the<br />

network, which facilitates fault location and makes it possible to implement the system advised above for each type <strong>of</strong> application.<br />

(2) The risk <strong>of</strong> flashover on the surge limiter turns the isolated neutral into an earthed neutral. These risks are high for regions with frequent<br />

thunder storms or <strong>installation</strong>s supplied by overhead lines. If the IT system is selected to ensure a higher level <strong>of</strong> continuity <strong>of</strong> service, the<br />

system <strong>design</strong>er must precisely calculate the tripping conditions for a second fault.<br />

(3) Risk <strong>of</strong> RCD nuisance tripping.<br />

(4) Whatever the SEA, the ideal solution is to isolate the disturbing section if it can be easily identified.<br />

(5) Risks <strong>of</strong> phase-to-earth faults affecting equipotentiality.<br />

(6) Insulation is uncertain due to humidity and conducting dust.<br />

(7) The TN system is not advised due to the risk <strong>of</strong> damage to the generator in the case <strong>of</strong> an internal fault. What is more, when generator sets<br />

supply safety equipment, the system must not trip for the first fault.<br />

(8) The phase-to-earth current may be several times higher than In, with the risk <strong>of</strong> damaging or accelerating the ageing <strong>of</strong> motor windings, or <strong>of</strong><br />

destroying magnetic circuits.<br />

(9) To combine continuity <strong>of</strong> service and safety, it is necessary and highly advised, whatever the SEA, to separate these loads from the rest <strong>of</strong><br />

the <strong>installation</strong> (transformers with local neutral connection).<br />

(10) When load equipment quality is not a <strong>design</strong> priority, there is a risk that the insulation resistance will fall rapidly. The TT system with RCDs<br />

is the best means to avoid problems.<br />

(11) The mobility <strong>of</strong> this type <strong>of</strong> load causes frequent faults (sliding contact for bonding <strong>of</strong> exposed conductive parts) that must be countered.<br />

Whatever the SEA, it is advised to supply these circuits using transformers with a local neutral connection.<br />

(12) Requires the use <strong>of</strong> transformers with a local TN system to avoid operating risks and nuisance tripping at the first fault (TT) or a double fault (IT).<br />

(12 bis) With a double break in the control circuit.<br />

(13) Excessive limitation <strong>of</strong> the phase-to-neutral current due to the high value <strong>of</strong> the zero-phase impedance (at least 4 to 5 times the direct<br />

impedance). This system must be replaced by a star-delta arrangement.<br />

(14) The high fault currents make the TN system dangerous. The TN-C system is forbidden.<br />

(15) Whatever the system, the RCD must be set to Δn y 500 mA.<br />

(16) An <strong>installation</strong> supplied with LV energy must use the TT system. Maintaining this SEA means the least amount <strong>of</strong> modifications on the<br />

existing network (no cables to be run, no protection devices to be modified).<br />

(17) Possible without highly competent maintenance personnel.<br />

(18) This type <strong>of</strong> <strong>installation</strong> requires particular attention in maintaining safety. The absence <strong>of</strong> preventive measures in the TN system means<br />

highly qualified personnel are required to ensure safety over time.<br />

(19) The risks <strong>of</strong> breaks in conductors (supply, protection) may cause the loss <strong>of</strong> equipotentiality for exposed conductive parts. A TT system or a<br />

TN-S system with 30 mA RCDs is advised and is <strong>of</strong>ten mandatory. The IT system may be used in very specific cases.<br />

(20) This solution avoids nuisance tripping for unexpected earth leakage.<br />

Fig. E17 : Influence <strong>of</strong> networks and loads on the selection <strong>of</strong> system earthing arrangements<br />

Earthing schemes<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IT (12 bis)<br />

Miscellaneous<br />

Supply via star-star connected power transformer (13) TT IT IT (13)<br />

without neutral with neutral<br />

Premises with risk <strong>of</strong> fire IT (15) TN-S (15) TN-C (14)<br />

Increase in power level <strong>of</strong> LV utility subscription, TT (16)<br />

requiring a private substation<br />

Installation with frequent modifications TT (17) TN (18)<br />

IT (18)<br />

Installation where the continuity <strong>of</strong> earth circuits is uncertain TT (19) TN-S TN-C<br />

(work sites, old <strong>installation</strong>s) IT (19)<br />

Electronic equipment (computers, PLCs) TN-S TT TN-C<br />

Machine control-monitoring network, PLC sensors and actuators IT (20) LV<br />

MV/LV<br />

TN-S, TT<br />

TT (15)<br />

E9<br />

© Schneider Electric - all rights reserved


E 0<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Earthing schemes<br />

.5 Choice <strong>of</strong> earthing method - implementation<br />

After consulting applicable regulations, Figures E16 and E17 can be used as an aid<br />

in deciding on divisions and possible galvanic isolation <strong>of</strong> appropriate sections <strong>of</strong> a<br />

proposed <strong>installation</strong>.<br />

Division <strong>of</strong> source<br />

This technique concerns the use <strong>of</strong> several transformers instead <strong>of</strong> employing one<br />

high-rated unit. In this way, a load that is a source <strong>of</strong> network disturbances (large<br />

motors, furnaces, etc.) can be supplied by its own transformer.<br />

The quality and continuity <strong>of</strong> supply to the whole <strong>installation</strong> are thereby improved.<br />

The cost <strong>of</strong> switchgear is reduced (short-circuit current level is lower).<br />

The cost-effectiveness <strong>of</strong> separate transformers must be determined on a case by<br />

case basis.<br />

Network islands<br />

The creation <strong>of</strong> galvanically-separated “islands” by means <strong>of</strong> LV/LV transformers<br />

makes it possible to optimise the choice <strong>of</strong> earthing methods to meet specific<br />

requirements (see Fig. E 8 and Fig. E 9 ).<br />

Fig. E18 : TN-S island within an IT system<br />

TN-S system<br />

Fig. E19 : IT islands within a TN-S system<br />

Conclusion<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MV/LV<br />

IT system<br />

MV/LV TN-S<br />

LV/LV<br />

Hospital<br />

LV/LV<br />

IMD<br />

TN-S system<br />

LV/LV<br />

IMD IMD<br />

IT IT<br />

Operating room<br />

The optimisation <strong>of</strong> the performance <strong>of</strong> the whole <strong>installation</strong> governs the choice <strong>of</strong><br />

earthing system.<br />

Including:<br />

b Initial investments, and<br />

b Future operational expenditures, hard to assess, that can arise from insufficient<br />

reliability, quality <strong>of</strong> equipment, safety, continuity <strong>of</strong> service, etc.<br />

An ideal structure would comprise normal power supply sources, local reserve<br />

power supply sources (see section 1.4 <strong>of</strong> <strong>Chapter</strong> E) and the appropriate earthing<br />

arrangements.


E - Distribution in low-voltage <strong>installation</strong>s<br />

A very effective method <strong>of</strong> obtaining a lowresistance<br />

earth connection is to bury a<br />

conductor in the form <strong>of</strong> a closed loop in the<br />

soil at the bottom <strong>of</strong> the excavation for building<br />

foundations.<br />

The resistance R <strong>of</strong> such an electrode (in<br />

homogeneous soil) is given (approximately) in<br />

ohms by: R =<br />

L<br />

2 � where<br />

L L = = length <strong>of</strong> the buried conductor in metres in metres<br />

ρ = soil resistivity in ohm-metres<br />

For n rods: R =<br />

n L<br />

1 �<br />

where<br />

Fig. E20 : Conductor buried below the level <strong>of</strong> the foundations,<br />

i.e. not in the concrete<br />

Earthing schemes<br />

.6 Installation and measurements <strong>of</strong> earth<br />

electrodes<br />

The quality <strong>of</strong> an earth electrode (resistance as low as possible) depends essentially<br />

on two factors:<br />

b Installation method<br />

b Type <strong>of</strong> soil<br />

Installation methods<br />

Three common types <strong>of</strong> <strong>installation</strong> will be discussed:<br />

Buried ring (see Fig. E20)<br />

This solution is strongly recommended, particularly in the case <strong>of</strong> a new building.<br />

The electrode should be buried around the perimeter <strong>of</strong> the excavation made for<br />

the foundations. It is important that the bare conductor be in intimate contact with<br />

the soil (and not placed in the gravel or aggregate hard-core, <strong>of</strong>ten forming a base<br />

for concrete). At least four (widely-spaced) vertically arranged conductors from the<br />

electrode should be provided for the <strong>installation</strong> connections and, where possible,<br />

any reinforcing rods in concrete work should be connected to the electrode.<br />

The conductor forming the earth electrode, particularly when it is laid in an<br />

excavation for foundations, must be in the earth, at least 50 cm below the hard-core<br />

or aggregate base for the concrete foundation. Neither the electrode nor the vertical<br />

rising conductors to the ground floor, should ever be in contact with the foundation<br />

concrete.<br />

For existing buildings, the electrode conductor should be buried around the outside<br />

wall <strong>of</strong> the premises to a depth <strong>of</strong> at least 1 metre. As a general rule, all vertical<br />

connections from an electrode to above-ground level should be insulated for the<br />

nominal LV voltage (600-1,000 V).<br />

The conductors may be:<br />

b Copper: Bare cable (u 25 mm 2 ) or multiple-strip (u 25 mm 2 and u 2 mm thick)<br />

b Aluminium with lead jacket: Cable (u 35 mm 2 )<br />

b Galvanised-steel cable: Bare cable (u 95 mm 2 ) or multiple-strip (u 100 mm 2<br />

and u 3 mm thick)<br />

The approximate resistance R <strong>of</strong> the electrode in ohms:<br />

R =<br />

L<br />

2 � where<br />

L = length where <strong>of</strong> the buried conductor in metres<br />

L = length <strong>of</strong> conductor in metres<br />

ρ = resistivity <strong>of</strong> the soil in ohm-metres (see “Influence <strong>of</strong> the type <strong>of</strong> soil” next page)<br />

Earthing rods (see Fig. E2 )<br />

Vertically driven earthing rods are <strong>of</strong>ten used for existing buildings, and for improving<br />

(i.e. reducing the resistance <strong>of</strong>) existing earth electrodes.<br />

The rods may be:<br />

b Copper or (more commonly) copper-clad steel. The latter are generally 1 or<br />

2 metres long and provided with screwed ends and sockets in order to reach<br />

considerable depths, if necessary (for instance, the water-table level in areas <strong>of</strong> high<br />

soil resistivity)<br />

b Galvanised (see note (1) next page) steel pipe u 25 mm diameter or<br />

rod u 15 mm diameter, u 2 metres long in each case.<br />

Fig. E21 : Earthing rods<br />

L u 3 m<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Rods connected in parallel<br />

E<br />

© Schneider Electric - all rights reserved


E 2<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

For a vertical plate electrode: R =<br />

L<br />

0.8 �<br />

Measurements on earth electrodes in similar<br />

soils are useful to determine the resistivity<br />

value to be applied for the <strong>design</strong> <strong>of</strong> an earthelectrode<br />

system<br />

Fig. E22 : Vertical plate<br />

2 mm thickness (Cu)<br />

(1) Where galvanised conducting materials are used for earth<br />

electrodes, sacrificial cathodic protection anodes may be<br />

necessary to avoid rapid corrosion <strong>of</strong> the electrodes where<br />

the soil is aggressive. Specially prepared magnesium anodes<br />

(in a porous sack filled with a suitable “soil”) are available for<br />

direct connection to the electrodes. In such circumstances, a<br />

specialist should be consulted<br />

It is <strong>of</strong>ten necessary to use more than one rod, in which case the spacing between<br />

them should exceed the depth to which they are driven, by a factor <strong>of</strong> 2 to 3.<br />

The total resistance (in homogeneous soil) is then equal to the resistance <strong>of</strong> one rod,<br />

divided by the number <strong>of</strong> rods in question. The approximate resistance R obtained is:<br />

R =<br />

n L<br />

1 �<br />

if the distance separating the rods > 4L<br />

where<br />

Earthing schemes<br />

where<br />

L = the length <strong>of</strong> the rod in metres<br />

ρ = resistivity <strong>of</strong> the soil in ohm-metres (see “Influence <strong>of</strong> the type <strong>of</strong> soil” below)<br />

n = the number <strong>of</strong> rods<br />

Vertical plates (see Fig. E22)<br />

Rectangular plates, each side <strong>of</strong> which must be u 0.5 metres, are commonly used as<br />

earth electrodes, being buried in a vertical plane such that the centre <strong>of</strong> the plate is<br />

at least 1 metre below the surface <strong>of</strong> the soil.<br />

The plates may be:<br />

b Copper <strong>of</strong> 2 mm thickness<br />

b Galvanised (1) steel <strong>of</strong> 3 mm thickness<br />

The resistance R in ohms is given (approximately), by:<br />

R =<br />

L<br />

0.8 �<br />

L = the perimeter <strong>of</strong> the plate in metres<br />

ρ = resistivity <strong>of</strong> the soil in ohm-metres (see “Influence <strong>of</strong> the type <strong>of</strong> soil” below)<br />

Influence <strong>of</strong> the type <strong>of</strong> soil<br />

Type <strong>of</strong> soil Mean value <strong>of</strong> resistivity<br />

in Ωm<br />

Swampy soil, bogs 1 - 30<br />

Silt alluvium 20 - 100<br />

Humus, leaf mould 10 - 150<br />

Peat, turf 5 - 100<br />

S<strong>of</strong>t clay 50<br />

Marl and compacted clay 100 - 200<br />

Jurassic marl 30 - 40<br />

Clayey sand 50 - 500<br />

Siliceous sand 200 - 300<br />

Stoney ground 1,500 - 3,000<br />

Grass-covered-stoney sub-soil 300 - 500<br />

Chalky soil 100 - 300<br />

Limestone 1,000 - 5,000<br />

Fissured limestone 500 - 1,000<br />

Schist, shale 50 - 300<br />

Mica schist 800<br />

Granite and sandstone 1,500 - 10,000<br />

Modified granite and sandstone 100 - 600<br />

Fig. E23 : Resistivity (Ωm) for different types <strong>of</strong> soil<br />

Type <strong>of</strong> soil Average value <strong>of</strong> resistivity<br />

in Ωm<br />

Fertile soil, compacted damp fill 50<br />

Arid soil, gravel, uncompacted non-uniform fill 500<br />

Stoney soil, bare, dry sand, fissured rocks 3,000<br />

Fig. E24 : Average resistivity (Ωm) values for approximate earth-elect<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

Earthing schemes<br />

Measurement and constancy <strong>of</strong> the resistance between an<br />

earth electrode and the earth<br />

The resistance <strong>of</strong> the electrode/earth interface rarely remains constant<br />

Among the principal factors affecting this resistance are the following:<br />

b Humidity <strong>of</strong> the soil<br />

The seasonal changes in the moisture content <strong>of</strong> the soil can be significant at depths<br />

<strong>of</strong> up to 2 meters.<br />

At a depth <strong>of</strong> 1 metre the resistivity and therefore the resistance can vary by a ratio<br />

<strong>of</strong> 1 to 3 between a wet winter and a dry summer in temperate regions<br />

b Frost<br />

Frozen earth can increase the resistivity <strong>of</strong> the soil by several orders <strong>of</strong> magnitude.<br />

This is one reason for recommending the <strong>installation</strong> <strong>of</strong> deep electrodes, in particular<br />

in cold climates<br />

b Ageing<br />

The materials used for electrodes will generally deteriorate to some extent for<br />

various reasons, for example:<br />

v Chemical reactions (in acidic or alkaline soils)<br />

v Galvanic: due to stray DC currents in the earth, for example from electric railways,<br />

etc. or due to dissimilar metals forming primary cells. Different soils acting on<br />

sections <strong>of</strong> the same conductor can also form cathodic and anodic areas with<br />

consequent loss <strong>of</strong> surface metal from the latter areas. Unfortunately, the most<br />

favourable conditions for low earth-electrode resistance (i.e. low soil resistivity) are<br />

also those in which galvanic currents can most easily flow.<br />

b Oxidation<br />

Brazed and welded joints and connections are the points most sensitive to oxidation.<br />

Thorough cleaning <strong>of</strong> a newly made joint or connection and wrapping with a suitable<br />

greased-tape binding is a commonly used preventive measure.<br />

Measurement <strong>of</strong> the earth-electrode resistance<br />

There must always be one or more removable links to isolate an earth electrode so<br />

that it can be tested.<br />

There must always be removable links which allow the earth electrode to be isolated<br />

from the <strong>installation</strong>, so that periodic tests <strong>of</strong> the earthing resistance can be carried<br />

out. To make such tests, two auxiliary electrodes are required, each consisting <strong>of</strong> a<br />

vertically driven rod.<br />

b Ammeter method (see Fig. E25)<br />

Fig. E25 : Measurement <strong>of</strong> the resistance to earth <strong>of</strong> the earth electrode <strong>of</strong> an <strong>installation</strong> by<br />

means <strong>of</strong> an ammeter<br />

U<br />

A = RT + Rt<br />

= Tt1<br />

1<br />

i1<br />

U<br />

B = Rt + R t t<br />

t = 1 2<br />

1 2<br />

i2<br />

U<br />

C = Rt + R t T<br />

T = 2<br />

2<br />

i3<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

T<br />

A<br />

t2<br />

When the source voltage U is constant (adjusted to be the same value for each test)<br />

then:<br />

U � 1 1 1�<br />

RT<br />

= � + �<br />

2 � i i i<br />

�<br />

1 3 2 �<br />

U<br />

t1<br />

E 3<br />

© Schneider Electric - all rights reserved


E 4<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Earthing schemes<br />

In order to avoid errors due to stray earth currents (galvanic -DC- or leakage currents<br />

from power and communication networks and so on) the test current should be<br />

AC, but at a different frequency to that <strong>of</strong> the power system or any <strong>of</strong> its harmonics.<br />

Instruments using hand-driven generators to make these measurements usually<br />

produce an AC voltage at a frequency <strong>of</strong> between 85 Hz and 135 Hz.<br />

The distances between the electrodes are not critical and may be in different<br />

directions from the electrode being tested, according to site conditions. A number <strong>of</strong><br />

tests at different spacings and directions are generally made to cross-check the test<br />

results.<br />

b Use <strong>of</strong> a direct-reading earthing-resistance ohmmeter<br />

These instruments use a hand-driven or electronic-type AC generator, together<br />

with two auxiliary electrodes, the spacing <strong>of</strong> which must be such that the zone <strong>of</strong><br />

influence <strong>of</strong> the electrode being tested should not overlap that <strong>of</strong> the test electrode (C).<br />

The test electrode (C) furthest from the electrode (X) under test, passes a current<br />

through the earth and the electrode under test, while the second test electrode (P)<br />

picks up a voltage. This voltage, measured between (X) and (P), is due to the test<br />

current and is a measure <strong>of</strong> the contact resistance (<strong>of</strong> the electrode under test) with<br />

earth. It is clear that the distance (X) to (P) must be carefully chosen to give accurate<br />

results. If the distance (X) to (C) is increased, however, the zones <strong>of</strong> resistance <strong>of</strong><br />

electrodes (X) and (C) become more remote, one from the other, and the curve <strong>of</strong><br />

potential (voltage) becomes more nearly horizontal about the point (O).<br />

In practical tests, therefore, the distance (X) to (C) is increased until readings taken<br />

with electrode (P) at three different points, i.e. at (P) and at approximately 5 metres<br />

on either side <strong>of</strong> (P), give similar values. The distance (X) to (P) is generally about<br />

0.68 <strong>of</strong> the distance (X) to (C).<br />

voltage-drop due<br />

to the resistance<br />

<strong>of</strong> electrode (X)<br />

voltage-drop due<br />

to the resistance<br />

<strong>of</strong> electrode (C)<br />

Fig. E26 : Measurement <strong>of</strong> the resistance to the mass <strong>of</strong> earth <strong>of</strong> electrode (X) using an earthelectrode-testing<br />

ohmmeter.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G<br />

V<br />

I<br />

X P<br />

C<br />

a) the principle <strong>of</strong> measurement is based on assumed homogeneous soil conditions. Where the<br />

zones <strong>of</strong> influence <strong>of</strong> electrodes C and X overlap, the location <strong>of</strong> test electrode P is difficult to<br />

determine for satisfactory results.<br />

X P<br />

b) showing the effect on the potential gradient when (X) and (C) are widely spaced. The location<br />

<strong>of</strong> test electrode P is not critical and can be easily determined.<br />

VG<br />

O<br />

O<br />

C<br />

VG


E - Distribution in low-voltage <strong>installation</strong>s<br />

Distribution switchboards, including the main<br />

LV switchboard (MLVS), are critical to the<br />

dependability <strong>of</strong> an <strong>electrical</strong> <strong>installation</strong>.<br />

They must comply with well-defined standards<br />

governing the <strong>design</strong> and construction <strong>of</strong><br />

LV switchgear assemblies<br />

The load requirements dictate the type <strong>of</strong><br />

distribution switchboard to be installed<br />

2 The <strong>installation</strong> system<br />

2.1 Distribution switchboards<br />

A distribution switchboard is the point at which an incoming-power supply divides<br />

into separate circuits, each <strong>of</strong> which is controlled and protected by the fuses or<br />

switchgear <strong>of</strong> the switchboard. A distribution switchboard is divided into a number<br />

<strong>of</strong> functional units, each comprising all the <strong>electrical</strong> and mechanical elements<br />

that contribute to the fulfilment <strong>of</strong> a given function. It represents a key link in the<br />

dependability chain.<br />

Consequently, the type <strong>of</strong> distribution switchboard must be perfectly adapted to its<br />

application. Its <strong>design</strong> and construction must comply with applicable standards and<br />

working practises.<br />

The distribution switchboard enclosure provides dual protection:<br />

b Protection <strong>of</strong> switchgear, indicating instruments, relays, fusegear, etc. against<br />

mechanical impacts, vibrations and other external influences likely to interfere with<br />

operational integrity (EMI, dust, moisture, vermin, etc.)<br />

b The protection <strong>of</strong> human life against the possibility <strong>of</strong> direct and indirect electric<br />

shock (see degree <strong>of</strong> protection IP and the IK index in section 3.3 <strong>of</strong> <strong>Chapter</strong> E).<br />

Types <strong>of</strong> distribution switchboards<br />

Distribution switchboards may differ according to the kind <strong>of</strong> application and the<br />

<strong>design</strong> principle adopted (notably in the arrangement <strong>of</strong> the busbars).<br />

Distribution switchboards according to specific applications<br />

The principal types <strong>of</strong> distribution switchboards are:<br />

b The main LV switchboard - MLVS - (see Fig. E27a)<br />

b Motor control centres - MCC - (see Fig. E27b)<br />

b Sub-distribution switchboards (see Fig. E28)<br />

b Final distribution switchboards (see Fig. E29)<br />

Distribution switchboards for specific applications (e.g. heating, lifts, industrial<br />

processes) can be located:<br />

b Adjacent to the main LV switchboard, or<br />

b Near the application concerned<br />

Sub-distribution and final distribution switchboards are generally distributed<br />

throughout the site.<br />

a b<br />

Fig. E27 : [a] A main LV switchboard - MLVS - (Prisma Plus P) with incoming circuits in the form<br />

<strong>of</strong> busways - [b] A LV motor control centre - MCC - (Okken)<br />

a b c<br />

Fig. E28 : A sub-distribution switchboard (Prisma Plus G) Fig. E29 : Final distribution switchboards [a] Prisma Plus G Pack; [b] Kaedra; [c] mini-Pragma<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E15<br />

© Schneider Electric - all rights reserved


E16<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

A distinction is made between:<br />

b Traditional distribution switchboards in which<br />

switchgear and fusegear, etc. are fixed to a<br />

chassis at the rear <strong>of</strong> an enclosure<br />

b Functional distribution switchboards for<br />

specific applications, based on modular and<br />

standardised <strong>design</strong>.<br />

Fig. E30 : Assembly <strong>of</strong> a final distribution switchboard with<br />

fixed functional units (Prisma Plus G)<br />

Fig. E31 : Distribution switchboard with disconnectable<br />

functional units<br />

Fig. E32 : Distribution switchboard with withdrawable functional<br />

units in drawers<br />

2 The <strong>installation</strong> system<br />

Two technologies <strong>of</strong> distribution switchboards<br />

Traditional distribution switchboards<br />

Switchgear and fusegear, etc. are normally located on a chassis at the rear <strong>of</strong> the<br />

enclosure. Indications and control devices (meters, lamps, pushbuttons, etc.) are<br />

mounted on the front face <strong>of</strong> the switchboard.<br />

The placement <strong>of</strong> the components within the enclosure requires very careful study,<br />

taking into account the dimensions <strong>of</strong> each item, the connections to be made to it,<br />

and the clearances necessary to ensure safe and trouble-free operation. .<br />

Functional distribution switchboards<br />

<strong>General</strong>ly dedicated to specific applications, these distribution switchboards are<br />

made up <strong>of</strong> functional modules that include switchgear devices together with<br />

standardised accessories for mounting and connections, ensuring a high level <strong>of</strong><br />

reliability and a great capacity for last-minute and future changes.<br />

b Many advantages<br />

The use <strong>of</strong> functional distribution switchboards has spread to all levels <strong>of</strong> LV<br />

<strong>electrical</strong> distribution, from the main LV switchboard (MLVS) to final distribution<br />

switchboards, due to their many advantages:<br />

v System modularity that makes it possible to integrate numerous functions in a<br />

single distribution switchboard, including protection, control, technical management<br />

and monitoring <strong>of</strong> <strong>electrical</strong> <strong>installation</strong>s. Modular <strong>design</strong> also enhances distribution<br />

switchboard maintenance, operation and upgrades<br />

v Distribution switchboard <strong>design</strong> is fast because it simply involves adding functional<br />

modules<br />

v Prefabricated components can be mounted faster<br />

v Finally, these distribution switchboards are subjected to type tests that ensure a<br />

high degree <strong>of</strong> dependability.<br />

The new Prisma Plus G and P ranges <strong>of</strong> functional distribution switchboards from<br />

Schneider Electric cover needs up to 3200 A and <strong>of</strong>fer:<br />

v Flexibility and ease in building distribution switchboards<br />

v Certification <strong>of</strong> a distribution switchboard complying with standard IEC 60439 and<br />

the assurance <strong>of</strong> servicing under safe conditions<br />

v Time savings at all stages, from <strong>design</strong> to <strong>installation</strong>, operation and modifications<br />

or upgrades<br />

v Easy adaptation, for example to meet the specific work habits and standards in<br />

different countries<br />

Figures E27a, E28 and E29 show examples <strong>of</strong> functional distribution switchboards<br />

ranging for all power ratings and figure E27b shows a high-power industrial functional<br />

distribution switchboard.<br />

b Main types <strong>of</strong> functional units<br />

Three basic technologies are used in functional distribution switchboards.<br />

v Fixed functional units (see Fig. E30)<br />

These units cannot be isolated from the supply so that any intervention for<br />

maintenance, modifications and so on, requires the shutdown <strong>of</strong> the entire<br />

distribution switchboard. Plug-in or withdrawable devices can however be used to<br />

minimise shutdown times and improve the availability <strong>of</strong> the rest <strong>of</strong> the <strong>installation</strong>.<br />

v Disconnectable functional units (see Fig. E31)<br />

Each functional unit is mounted on a removable mounting plate and provided with a<br />

means <strong>of</strong> isolation on the upstream side (busbars) and disconnecting facilities on the<br />

downstream (outgoing circuit) side. The complete unit can therefore be removed for<br />

servicing, without requiring a general shutdown.<br />

v Drawer-type withdrawable functional units (see Fig. E32)<br />

The switchgear and associated accessories for a complete function are mounted on<br />

a drawer-type horizontally withdrawable chassis. The function is generally complex<br />

and <strong>of</strong>ten concerns motor control.<br />

Isolation is possible on both the upstream and downstream sides by the complete<br />

withdrawal <strong>of</strong> the drawer, allowing fast replacement <strong>of</strong> a faulty unit without deenergising<br />

the rest <strong>of</strong> the distribution switchboard.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

Compliance with applicable standards is<br />

essential in order to ensure an adequate<br />

degree <strong>of</strong> dependability<br />

Three elements <strong>of</strong> standard IEC 60439-1<br />

contribute significantly to dependability:<br />

b Clear definition <strong>of</strong> functional units<br />

b Forms <strong>of</strong> separation between adjacent<br />

functional units in accordance with user<br />

requirements<br />

b Clearly defined routine tests and type tests<br />

Standards<br />

Different standards<br />

Certain types <strong>of</strong> distribution switchboards (in particular, functional distribution<br />

switchboards) must comply with specific standards according to the application or<br />

environment involved.<br />

The reference international standard is IEC 60439-1 type-tested and partially typetested<br />

assemblies<br />

Standard IEC 60439-1<br />

b Categories <strong>of</strong> assemblies<br />

Standard IEC 60439-1 distinguishes between two categories <strong>of</strong> assemblies:<br />

v Type-tested LV switchgear and controlgear assemblies (TTA), which do not diverge<br />

significantly from an established type or system for which conformity is ensured by<br />

the type tests provided in the standard<br />

v Partially type-tested LV switchgear and controlgear assemblies (PTTA), which may<br />

contain non-type-tested arrangements provided that the latter are derived from typetested<br />

arrangements<br />

When implemented in compliance with pr<strong>of</strong>essional work standards and<br />

manufacturer instructions by qualified personnel, they <strong>of</strong>fer the same level <strong>of</strong> safety<br />

and quality.<br />

b Functional units<br />

The same standard defines functional units:<br />

v Part <strong>of</strong> an assembly comprising all the <strong>electrical</strong> and mechanical elements that<br />

contribute to the fulfilment <strong>of</strong> the same function<br />

v The distribution switchboard includes an incoming functional unit and one or more<br />

functional units for outgoing circuits, depending on the operating requirements <strong>of</strong> the<br />

<strong>installation</strong><br />

What is more, distribution switchboard technologies use functional units that may be<br />

fixed, disconnectable or withdrawable (see section 3.1 <strong>of</strong> <strong>Chapter</strong> E).<br />

b Forms (see Fig. E33)<br />

Separation <strong>of</strong> functional units within the assembly is provided by forms that are<br />

specified for different types <strong>of</strong> operation.<br />

The various forms are numbered from 1 to 4 with variations labelled “a” or “b”. Each<br />

step up (from 1 to 4) is cumulative, i.e. a form with a higher number includes the<br />

characteristics <strong>of</strong> forms with lower numbers. The standard distinguishes:<br />

v Form 1: No separation<br />

v Form 2: Separation <strong>of</strong> busbars from the functional units<br />

v Form 3: Separation <strong>of</strong> busbars from the functional units and separation <strong>of</strong> all<br />

functional units, one from another, except at their output terminals<br />

v Form 4: As for Form 3, but including separation <strong>of</strong> the outgoing terminals <strong>of</strong> all<br />

functional units, one from another<br />

The decision on which form to implement results from an agreement between the<br />

manufacturer and the user.<br />

The Prima Plus functional range <strong>of</strong>fers solutions for forms 1, 2b, 3b, 4a, 4b.<br />

Form 1 Form 2a Form 2b Form 3a<br />

Form 3b Form 4a Form 4b<br />

Fig. E33 : Representation <strong>of</strong> different forms <strong>of</strong> LV functional distribution switchboards<br />

2 The <strong>installation</strong> system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Busbar<br />

Separation<br />

E17<br />

© Schneider Electric - all rights reserved


E18<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Total accessibility <strong>of</strong> <strong>electrical</strong> information and<br />

intelligent distribution switchboards are now a<br />

reality<br />

Two types <strong>of</strong> distribution are possible:<br />

b By insulated wires and cables<br />

b By busbar trunking (busways)<br />

2 The <strong>installation</strong> system<br />

b Type tests and routine tests<br />

They ensure compliance <strong>of</strong> each distribution switchboard with the standard. The<br />

availability <strong>of</strong> test documents certified by independent organisations is a guarantee<br />

for users.<br />

Remote monitoring and control <strong>of</strong> the <strong>electrical</strong> <strong>installation</strong><br />

Remote monitoring and control are no longer limited to large <strong>installation</strong>s.<br />

These functions are increasingly used and provide considerable cost savings.<br />

The main potential advantages are:<br />

b Reductions in energy bills<br />

b Reductions in structural costs to maintain the <strong>installation</strong> in running order<br />

b Better use <strong>of</strong> the investment, notably concerning optimisation <strong>of</strong> the <strong>installation</strong> life<br />

cycle<br />

b Greater satisfaction for energy users (in a building or in process industries) due to<br />

improved power availability and/or quality<br />

The above possibilities are all the more an option given the current deregulation <strong>of</strong><br />

the <strong>electrical</strong>-energy sector.<br />

Modbus is increasingly used as the open standard for communication within the<br />

distribution switchboard and between the distribution switchboard and customer<br />

power monitoring and control applications. Modbus exists in two forms, twisted pair<br />

(RS 485) and Ethernet-TCP/IP (IEEE 802.3).<br />

The www.modbus.org site presents all bus specifications and constantly updates the<br />

list <strong>of</strong> products and companies using the open industrial standard.<br />

The use <strong>of</strong> web technologies has largely contributed to wider use by drastically<br />

reducing the cost <strong>of</strong> accessing these functions through the use <strong>of</strong> an interface that is<br />

now universal (web pages) and a degree <strong>of</strong> openness and upgradeability that simply<br />

did not exist just a few years ago.<br />

2.2 Cables and busway trunking<br />

Distribution by insulated conductors and cables<br />

Definitions<br />

b Conductor<br />

A conductor comprises a single metallic core with or without an insulating envelope.<br />

b Cable<br />

A cable is made up <strong>of</strong> a number <strong>of</strong> conductors, <strong>electrical</strong>ly separated, but joined<br />

mechanically, generally enclosed in a protective flexible sheath.<br />

b Cableway<br />

The term cableway refers to conductors and/or cables together with the means <strong>of</strong><br />

support and protection, etc. for example : cable trays, ladders, ducts, trenches, and<br />

so on… are all “cableways”.<br />

Conductor marking<br />

Conductor identification must always respect the following three <strong>rules</strong>:<br />

b Rule 1<br />

The double colour green and yellow is strictly reserved for the PE and PEN<br />

protection conductors.<br />

b Rule 2<br />

v When a circuit comprises a neutral conductor, it must be light blue or marked “1” for<br />

cables with more than five conductors<br />

v When a circuit does not have a neutral conductor, the light blue conductor may be<br />

used as a phase conductor if it is part <strong>of</strong> a cable with more than one conductor<br />

b Rule 3<br />

Phase conductors may be any colour except:<br />

v Green and yellow<br />

v Green<br />

v Yellow<br />

v Light blue (see rule 2)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

Conductors in a cable are identified either by their colour or by numbers (see Fig. E34).<br />

Number <strong>of</strong> Circuit Fixed cableways<br />

conductors Insulated conductors Rigid and flexible multi-<br />

in circuit conductor cables<br />

Ph Ph Pn N PE Ph Ph Ph N PE<br />

1 Protection or earth G/Y<br />

2 Single-phase between phases b b BL LB<br />

Single-phase between phase and neutral b LB BL LB<br />

Single-phase between phase and neutral b G/Y BL G/Y<br />

+ protection conductor<br />

3 Three-phase without neutral b b b BL B LB<br />

2 phases + neutral b b LB BL B LB<br />

2 phases + protection conductor b b G/Y BL LB G/Y<br />

Single-phase between phase and neutral b LB G/Y BL LB G/Y<br />

+ protection conductor<br />

4 Three-phase with neutral b b b LB BL B BL LB<br />

Three-phase with neutral + protection conductor b b b G/Y BL B LB G/Y<br />

2 phases + neutral + protection conductor b b LB G/Y BL B LB G/Y<br />

Three-phase with PEN conductor b b b G/Y BL B LB G/Y<br />

5 Three-phase + neutral + protection conductor b b b LB G/Y BL B BL LB G/Y<br />

> 5 Protection conductor: G/Y - Other conductors: BL: with numbering<br />

The number “1” is reserved for the neutral conductor if it exists<br />

G/Y: Green and yellow BL: Black b : As indicated in rule 3 LB: Light blue B: Brown<br />

Fig. E34 : Conductor identification according to the type <strong>of</strong> circuit<br />

N<br />

Black conductor<br />

Light blue conductor<br />

Fig. E35 : Conductor identification on a circuit-breaker with a<br />

phase and a neutral<br />

2 The <strong>installation</strong> system<br />

Note: If the circuit includes a protection conductor and if the available cable does not<br />

have a green and yellow conductor, the protection conductor may be:<br />

b A separate green and yellow conductor<br />

b The blue conductor if the circuit does not have a neutral conductor<br />

b A black conductor if the circuit has a neutral conductor<br />

In the last two cases, the conductor used must be marked by green and yellow<br />

bands or markings at the ends and on all visible lengths <strong>of</strong> the conductor.<br />

Equipment power cords are marked similar to multi-conductor cables (see Fig. E35).<br />

Distribution and <strong>installation</strong> methods (see Fig. E36)<br />

Distribution takes place via cableways that carry single insulated conductors or<br />

cables and include a fixing system and mechanical protection.<br />

Floor subdistribution<br />

swichboard<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Main LV switchboard<br />

(MLVS)<br />

Fig. E36 : Radial distribution using cables in a hotel<br />

Heating, etc.<br />

Final<br />

distribution<br />

swichboard<br />

Building utilities sub-distribution swichboard<br />

E19<br />

© Schneider Electric - all rights reserved


E20<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Busways, also referred to as busbar trunking<br />

systems, stand out for their ease <strong>of</strong> <strong>installation</strong>,<br />

flexibility and number <strong>of</strong> possible connection<br />

points<br />

2 The <strong>installation</strong> system<br />

Busbar trunking (busways)<br />

Busbar trunking is intended to distribute power (from 20 A to 5000 A) and lighting<br />

(in this application, the busbar trunking may play a dual role <strong>of</strong> supplying <strong>electrical</strong><br />

power and physically holding the lights).<br />

Busbar trunking system components<br />

A busbar trunking system comprises a set <strong>of</strong> conductors protected by an enclosure<br />

(see Fig. E37). Used for the transmission and distribution <strong>of</strong> <strong>electrical</strong> power, busbar<br />

trunking systems have all the necessary features for fitting: connectors, straights,<br />

angles, fixings, etc. The tap-<strong>of</strong>f points placed at regular intervals make power<br />

available at every point in the <strong>installation</strong>.<br />

Straight trunking Tap-<strong>of</strong>f points to<br />

distribute current<br />

Power Unit Range <strong>of</strong> clip-on tap-<strong>of</strong>f units to<br />

connect a load (e.g.: a machine) to<br />

the busbar trunking<br />

Fig. E37 : Busbar trunking system <strong>design</strong> for distribution <strong>of</strong> currents from 25 to 4000 A.<br />

The various types <strong>of</strong> busbar trunking:<br />

Busbar trunking systems are present at every level in <strong>electrical</strong> distribution: from<br />

the link between the transformer and the low voltage switch switchboard (MLVS)<br />

to the distribution <strong>of</strong> power sockets and lighting to <strong>of</strong>fices, or power distribution to<br />

workshops.<br />

Fig. E38 : Radial distribution using busways<br />

We talk about a distributed network architecture.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Fixing system for ceilings, walls or<br />

raised floor, etc.<br />

Angle<br />

End piece


E - Distribution in low-voltage <strong>installation</strong>s<br />

2 The <strong>installation</strong> system<br />

There are essentially three categories <strong>of</strong> busways.<br />

b Transformer to MLVS busbar trunking<br />

Installation <strong>of</strong> the busway may be considered as permanent and will most likely never<br />

be modified. There are no tap-<strong>of</strong>f points.<br />

Frequently used for short runs, it is almost always used for ratings above 1,600 /<br />

2,000 A, i.e. when the use <strong>of</strong> parallel cables makes <strong>installation</strong> impossible. Busways<br />

are also used between the MLVS and downstream distribution switchboards.<br />

The characteristics <strong>of</strong> main-distribution busways authorize operational currents from<br />

1,000 to 5,000 A and short-circuit withstands up to 150 kA.<br />

b Sub-distribution busbar trunking with low or high tap-<strong>of</strong>f densities<br />

Downstream <strong>of</strong> main-distribution busbar trunking , two types <strong>of</strong> applications must be<br />

supplied:<br />

v Mid-sized premises (industrial workshops with injection presses and metalwork<br />

machines or large supermarkets with heavy loads). The short-circuit and current<br />

levels can be fairly high (respectively 20 to 70 kA and 100 to 1,000 A)<br />

v Small sites (workshops with machine-tools, textile factories with small machines,<br />

supermarkets with small loads). The short-circuit and current levels are lower<br />

(respectively 10 to 40 kA and 40 to 400 A)<br />

Sub-distribution using busbar trunking meets user needs in terms <strong>of</strong>:<br />

v Modifications and upgrades given the high number <strong>of</strong> tap-<strong>of</strong>f points<br />

v Dependability and continuity <strong>of</strong> service because tap-<strong>of</strong>f units can be connected<br />

under energized conditions in complete safety<br />

The sub-distribution concept is also valid for vertical distribution in the form <strong>of</strong> 100 to<br />

5,000 A risers in tall buildings.<br />

b Lighting distribution busbar trunking<br />

Lighting circuits can be distributed using two types <strong>of</strong> busbar trunking according to<br />

whether the lighting fixtures are suspended from the busbar trunking or not.<br />

v busbar trunking <strong>design</strong>ed for the suspension <strong>of</strong> lighting fixtures<br />

These busways supply and support light fixtures (industrial reflectors, discharge<br />

lamps, etc.). They are used in industrial buildings, supermarkets, department stores<br />

and warehouses. The busbar trunkings are very rigid and are <strong>design</strong>ed for one or<br />

two 25 A or 40 A circuits. They have tap-<strong>of</strong>f outlets every 0.5 to 1 m.<br />

v busbar trunking not <strong>design</strong>ed for the suspension <strong>of</strong> lighting fixtures<br />

Similar to prefabricated cable systems, these busways are used to supply all types<br />

<strong>of</strong> lighting fixtures secured to the building structure. They are used in commercial<br />

buildings (<strong>of</strong>fices, shops, restaurants, hotels, etc.), especially in false ceilings. The<br />

busbar trunking is flexible and <strong>design</strong>ed for one 20 A circuit. It has tap-<strong>of</strong>f outlets<br />

every 1.2 m to 3 m.<br />

Busbar trunking systems are suited to the requirements <strong>of</strong> a large number <strong>of</strong><br />

buildings.<br />

b Industrial buildings: garages, workshops, farm buildings, logistic centers, etc.<br />

b Commercial areas: stores, shopping malls, supermarkets, hotels, etc.<br />

b Tertiary buildings: <strong>of</strong>fices, schools, hospitals, sports rooms, cruise liners, etc.<br />

Standards<br />

Busbar trunking systems must meet all <strong>rules</strong> stated in IEC 439-2.<br />

This defines the manufacturing arrangements to be complied with in the <strong>design</strong><br />

<strong>of</strong> busbar trunking systems (e.g.: temperature rise characteristics, short-circuit<br />

withstand, mechanical strength, etc.) as well as test methods to check them.<br />

Standard IEC 439-2 defines 13 compulsory type-tests on configurations or system<br />

components..<br />

By assembling the system components on the site according to the assembly<br />

instructions, the contractor benefits from conformity with the standard.<br />

The advantages <strong>of</strong> busbar trunking systems<br />

Flexibility<br />

b Easy to change configuration (on-site modification to change production line<br />

configuration or extend production areas).<br />

b Reusing components (components are kept intact): when an <strong>installation</strong> is subject<br />

to major modifications, the busbar trunking is easy to dismantle and reuse.<br />

b Power availability throughout the <strong>installation</strong> (possibility <strong>of</strong> having a tap-<strong>of</strong>f point<br />

every meter).<br />

b Wide choice <strong>of</strong> tap-<strong>of</strong>f units.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E21<br />

© Schneider Electric - all rights reserved


E22<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Simplicity<br />

b Design can be carried out independently from the distribution and layout <strong>of</strong> current<br />

consumers.<br />

b Performances are independent <strong>of</strong> implementation: the use <strong>of</strong> cables requires a lot<br />

<strong>of</strong> derating coefficients.<br />

b Clear distribution layout<br />

b Reduction <strong>of</strong> fitting time: the trunking system allows fitting times to be reduced by<br />

up to 50% compared with a traditional cable <strong>installation</strong>.<br />

b Manufacturer’s guarantee.<br />

b Controlled execution times: the trunking system concept guarantees that there are<br />

no unexpected surprises when fitting. The fitting time is clearly known in advance<br />

and a quick solution can be provided to any problems on site with this adaptable and<br />

scalable equipment.<br />

b Easy to implement: modular components that are easy to handle, simple and quick<br />

to connect.<br />

Dependability<br />

b Reliability guaranteed by being factory-built<br />

b Fool-pro<strong>of</strong> units<br />

b Sequential assembly <strong>of</strong> straight components and tap-<strong>of</strong>f units making it impossible<br />

to make any mistakes<br />

Continuity <strong>of</strong> service<br />

b The large number <strong>of</strong> tap-<strong>of</strong>f points makes it easy to supply power to any new<br />

current consumer. Connecting and disconnecting is quick and can be carried out in<br />

complete safety even when energized. These two operations (adding or modifying)<br />

take place without having to stop operations.<br />

b Quick and easy fault location since current consumers are near to the line<br />

b Maintenance is non existent or greatly reduced<br />

Major contribution to sustainable development<br />

b Busbar trunking systems allow circuits to be combined. Compared with a<br />

traditional cable distribution system, consumption <strong>of</strong> copper raw materials and<br />

insulators is divided by 3 due to the busbar trunking distributed network concept<br />

(see Fig. E39).<br />

Example:<br />

30 m <strong>of</strong> Canalis KS 250A equipped with 10 25 A, four-pole feeders<br />

Distribution type Conductors<br />

Insulators Consumption<br />

Branched<br />

ΣI x k s<br />

ks: clustering coefficient= 0.6<br />

Centralized<br />

ΣI x k s<br />

ks: clustering coefficient= 0.6<br />

I 1 I 2 I 3 I 4 I 5 I 6 I 7<br />

R R R R R R R<br />

I 1 I 2 I 3 I 4 I 5 I 6 I 7<br />

R R R R R R R<br />

Fig. E39 : Example: 30 m <strong>of</strong> Canalis KS 250A equipped with 10 25 A, four-pole feeders<br />

2 The <strong>installation</strong> system<br />

Alu: 128 mm²<br />

Copper equivalent: 86 mm²<br />

Copper: 250 mm²<br />

b Reusable device and all <strong>of</strong> its components are fully recyclable.<br />

b Does not contain PVC and does not generate toxic gases or waste.<br />

b Reduction <strong>of</strong> risks due to exposure to electromagnetic fields.<br />

New functional features for Canalis<br />

Busbar trunking systems are getting even better. Among the new features we can<br />

mention:<br />

b Increased performance with a IP55 protection index and new ratings <strong>of</strong> 160 A<br />

through to 1000 A (Ks).<br />

b New lighting <strong>of</strong>fers with pre-cabled lights and new light ducts.<br />

b New fixing accessories. Quick fixing system, cable ducts, shared support with<br />

“VDI” (voice, data, images) circuits.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

4 kg<br />

12 kg<br />

1 000 Joules<br />

1 600 Joules


E - Distribution in low-voltage <strong>installation</strong>s<br />

2 The <strong>installation</strong> system<br />

Busbar trunking systems are perfectly integrated with the environment:<br />

b white color to enhance the working environment, naturally integrated in a range <strong>of</strong><br />

<strong>electrical</strong> distribution products.<br />

b conformity with European regulations on reducing hazardous materials (RoHS).<br />

Examples <strong>of</strong> Canalis busbar trunking systems<br />

Fig. E40 : Flexible busbar trunking not capable <strong>of</strong> supporting light fittings : Canalis KDP (20 A)<br />

Fig. E41 : Rigid busbar trunking able to support light fittings : Canalis KBA or KBB (25 and 40 A)<br />

Fig. E42 : Lighting duct : Canalis KBX (25 A)<br />

Fig. E43 : A busway for medium power distribution : Canalis KN (40 up to 160 A)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E23<br />

© Schneider Electric - all rights reserved


E24<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

2 The <strong>installation</strong> system<br />

Fig. E44 : A busway for medium power distribution : Canalis KS (100 up to 1000 A)<br />

Fig. E45 : A busway for high power distribution : Canalis KT (800 up to 1000 A)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

External influences shall be taken into account<br />

when choosing:<br />

b The appropriate measures to ensure the<br />

safety <strong>of</strong> persons (in particular in special<br />

locations or <strong>electrical</strong> <strong>installation</strong>s)<br />

b The characteristics <strong>of</strong> <strong>electrical</strong> equipment,<br />

such as degree <strong>of</strong> protection (IP), mechanical<br />

withstand (IK), etc.<br />

If several external influences appear at the<br />

same time, they can have independent or<br />

mutual effects and the degree <strong>of</strong> protection must<br />

be chosen accordingly<br />

3 External influences<br />

(IEC 60364-5-51)<br />

3.1 Definition and reference standards<br />

Every <strong>electrical</strong> <strong>installation</strong> occupies an environment that presents a variable degree<br />

<strong>of</strong> risk:<br />

b For people<br />

b For the equipment constituting the <strong>installation</strong><br />

Consequently, environmental conditions influence the definition and choice <strong>of</strong><br />

appropriate <strong>installation</strong> equipment and the choice <strong>of</strong> protective measures for the<br />

safety <strong>of</strong> persons.<br />

The environmental conditions are referred to collectively as “external influences”.<br />

Many national standards concerned with external influences include a classification<br />

scheme which is based on, or which closely resembles, that <strong>of</strong> international standard<br />

IEC 60364-5-51.<br />

3.2 Classification<br />

Each condition <strong>of</strong> external influence is <strong>design</strong>ated by a code comprising a group <strong>of</strong><br />

two capital letters and a number as follows:<br />

First letter (A, B or C)<br />

The first letter relates to the general category <strong>of</strong> external influence :<br />

b A = environment<br />

b B = utilisation<br />

b C = construction <strong>of</strong> buildings<br />

Second letter<br />

The second letter relates to the nature <strong>of</strong> the external influence.<br />

Number<br />

The number relates to the class within each external influence.<br />

Additional letter (optional)<br />

Used only if the effective protection <strong>of</strong> persons is greater than that indicated by the<br />

first IP digit.<br />

When only the protection <strong>of</strong> persons is to be specified, the two digits <strong>of</strong> the IP code<br />

are replaced by the X’s.<br />

Example: IP XXB.<br />

Example<br />

For example the code AC2 signifies:<br />

A = environment<br />

AC = environment-altitude<br />

AC2 = environment-altitude > 2,000 m<br />

3.3 List <strong>of</strong> external influences<br />

Figure E46 below is from IEC 60364-5-51, which should be referred to if further<br />

details are required.<br />

Code External influences Characteristics required for equipment<br />

A - Environment<br />

AA Ambient temperature (°C)<br />

Low High Specially <strong>design</strong>ed equipment or appropriate arrangements<br />

AA1 - 60 °C + 5 °C<br />

AA2 - 40 °C + 5 °C<br />

AA3 - 25 °C + 5 °C<br />

AA4 - 5° C + 40 °C Normal (special precautions in certain cases)<br />

AA5 + 5 °C + 40 °C Normal<br />

AA6 + 5 °C + 60 °C Specially <strong>design</strong>ed equipment or appropriate arrangements<br />

AA7 - 25 °C + 55 °C<br />

AA8 - 50 °C + 40 °C<br />

Fig. E46 : List <strong>of</strong> external influences (taken from Appendix A <strong>of</strong> IEC 60364-5-51) (continued on next page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E25<br />

© Schneider Electric - all rights reserved


E26<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

3 External influences<br />

(IEC 60364-5-51)<br />

Code External influences Characteristics required for equipment<br />

A - Environment<br />

AB Atmospheric humidity<br />

Air temperature °C Relative humidity % Absolute humidity g/m 3<br />

Low High Low High Low High<br />

AB1 - 60 °C + 5 °C 3 100 0.003 7 Appropriate arrangements shall be made<br />

AB2 - 40 °C + 5 °C 10 100 0.1 7<br />

AB3 - 25 °C + 5 °C 10 100 0.5 7<br />

AB4 - 5° C + 40 °C 5 95 1 29 Normal<br />

AB5 + 5 °C + 40 °C 5 85 1 25 Normal<br />

AB6 + 5 °C + 60 °C 10 100 1 35 Appropriate arrangements shall be made<br />

AB7 - 25 °C + 55 °C 10 100 0.5 29<br />

AB8 - 50 °C + 40 °C 15 100 0.04 36<br />

AC Altitude<br />

AC1 y 2000 m Normal<br />

AC2 > 2000 m May necessitate precaution (derating factors)<br />

AD Presence <strong>of</strong> water<br />

AD1 Negligible Outdoor or non-weather protected locations IPX0<br />

AD2 Free-falling drops IPX1 or IPX2<br />

AD3 Sprays IPX3<br />

AD4 Splashes IPX4<br />

AD5 Jets Locations where hose water is used regularly IPX5<br />

AD6 Waves Seashore locations (piers, beaches, quays…) IPX6<br />

AD7 Immersion Water 150 mm above the highest point and IPX7<br />

equipment not more than 1m below the surface<br />

AD8 Submersion Equipment is permanently and totally covered IPX8<br />

AE Presence <strong>of</strong> foreign solid bodies<br />

Smallest dimension Example<br />

AE1 Negligible IP0X<br />

AE2 Small objects 2.5 mm Tools IP3X<br />

AE3 Very small objects 1 mm Wire IP4X<br />

AE4 Light dust IP5X if dust penetration is not harmful to functioning<br />

AE5 Moderate dust IP6X if dust should not penetrate<br />

AE6 Heavy dust IP6X<br />

AF Presence <strong>of</strong> corrosive or polluting substances<br />

AF1 Negligible Normal<br />

AF2 Atmospheric According to the nature <strong>of</strong> the substance<br />

AF3 Intermittent, accidental Protection against corrosion<br />

AF4 Continuous Equipment specially <strong>design</strong>ed<br />

AG Mechanical stress impact<br />

AG1 Low severity Normal<br />

AG2 Medium severity Standard where applicable or reinforced material<br />

AG3 High severity Reinforced protection<br />

AH Vibrations<br />

AH1 Low severity Household or similar Normal<br />

AH2 Medium severity Usual industrial conditions Specially <strong>design</strong>ed equipment or special arrangements<br />

AH3 High severity Severe industrial conditions<br />

AJ Other mechanical stresses<br />

AK Presence <strong>of</strong> flora and/or mould growth<br />

AH1 No hazard Normal<br />

AH2 Hazard<br />

AL Presence <strong>of</strong> fauna<br />

AH1 No hazard Normal<br />

AH2 Hazard<br />

AM Electromagnetic, electrostatic or ionising influences / Low frequency electromagnetic phenomena / Harmonics<br />

AM1 Harmonics, interharmonics Refer to applicable IEC standards<br />

AM2 Signalling voltage<br />

AM3 Voltage amplitude variations<br />

AM4 Voltage unbalance<br />

AM5 Power frequency variations<br />

AM6 Induced low-frequency voltages<br />

AM7 Direct current in a.c. networks<br />

AM8 Radiated magnetic fields<br />

AM9 Electric field<br />

AM21 Induced oscillatory voltages or currents<br />

Fig. E46 : List <strong>of</strong> external influences (taken from Appendix A <strong>of</strong> IEC 60364-5-51) (continued on next page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


E - Distribution in low-voltage <strong>installation</strong>s<br />

Fig. E46 : List <strong>of</strong> external influences (taken from Appendix A <strong>of</strong> IEC 60364-5-51) (concluded)<br />

3 External influences<br />

(IEC 60364-5-51)<br />

Code External influences Characteristics required for equipment<br />

A - Environment<br />

AM22 Conducted unidirectional transients <strong>of</strong> the nanosecond time scale Refer to applicable IEC standards<br />

AM23 Conducted unidirectional transients <strong>of</strong> the microsecond to the millisecond<br />

time scale<br />

AM24 Conducted oscillatory transients<br />

AM25 Radiated high frequency phenomena<br />

AM31 Electrostatic discharges<br />

AM41 Ionisation<br />

AN Solar radiation<br />

AN1 Low Normal<br />

AN2 Medium<br />

AN3 High<br />

AP Seismic effect<br />

AP1 Negligible Normal<br />

AP2 Low severity<br />

AP3 Medium severity<br />

AP4 High severity<br />

AQ Lightning<br />

AQ1 Negligible Normal<br />

AQ2 Indirect exposure<br />

AQ3 Direct exposure<br />

AR Movement <strong>of</strong> air<br />

AQ1 Low Normal<br />

AQ2 Medium<br />

AQ3 High<br />

AS Wind<br />

AQ1 Low Normal<br />

AQ2 Medium<br />

AQ3 High<br />

B - Utilization<br />

BA Capability <strong>of</strong> persons<br />

BA1 Ordinary Normal<br />

BA2 Children<br />

BA3 Handicapped<br />

BA4 Instructed<br />

BA5 Skilled<br />

BB Electrical resistance <strong>of</strong> human body<br />

BC Contact <strong>of</strong> persons with earth potential<br />

BC1 None Class <strong>of</strong> equipment according to IEC61140<br />

BC2 Low<br />

BC3 Frequent<br />

BC4 Continuous<br />

BD Condition <strong>of</strong> evacuation in case <strong>of</strong> emergency<br />

BD1 Low density / easy exit Normal<br />

BD2 Low density / difficult exit<br />

BD3 High density / easy exit<br />

BD4 High density / difficult exit<br />

BE Nature <strong>of</strong> processed or stored materials<br />

BE1 No significant risks Normal<br />

BE2 Fire risks<br />

BE3 Explosion risks<br />

BE4 Contamination risks<br />

C - Construction <strong>of</strong> building<br />

CA Construction materials<br />

CA1 Non combustible Normal<br />

CA2 Combustible<br />

CB Building <strong>design</strong><br />

CB1 Negligible risks Normal<br />

CB2 Propagation <strong>of</strong> fire<br />

CB3 Movement<br />

CB4 lexible or unstable<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E27<br />

© Schneider Electric - all rights reserved


E28<br />

© Schneider Electric - all rights reserved<br />

E - Distribution in low-voltage <strong>installation</strong>s<br />

Code letters<br />

(International Protection)<br />

First characteristic numeral<br />

(numerals 0 to 6, or letter X)<br />

Second characteristic numeral<br />

(numerals 0 to 6, or letter X)<br />

Additional letter (optional)<br />

(letters A, B, C, D)<br />

Supplementary letter (optional)<br />

(letters H, M, S, W)<br />

Fig. E47 : IP Code arrangement<br />

IP 2 3 C H<br />

Where a characteristic numeral is not required to be specified,<br />

it shall be replaced by the letter "X" ("XX" if both numerals<br />

are omitted). Additional letters and/or supplementary letters<br />

may be omitted without replacement.<br />

3 External influences<br />

(IEC 60364-5-51)<br />

3.4 Protection provided for enclosed equipment:<br />

codes IP and IK<br />

IP code definition (see Fig. E47)<br />

The degree <strong>of</strong> protection provided by an enclosure is indicated in the IP code,<br />

recommended in IEC 60529.<br />

Protection is afforded against the following external influences:<br />

b Penetration by solid bodies<br />

b Protection <strong>of</strong> persons against access to live parts<br />

b Protection against the ingress <strong>of</strong> dust<br />

b Protection against the ingress <strong>of</strong> liquids<br />

Note: the IP code applies to <strong>electrical</strong> equipment for voltages up to and including<br />

72.5 kV.<br />

Elements <strong>of</strong> the IP Code and their meanings<br />

A brief description <strong>of</strong> the IP Code elements is given in the following chart<br />

(see Fig. E48).<br />

Element Numerals<br />

or letters<br />

Code letters<br />

First<br />

characteristic<br />

numeral<br />

Second<br />

characteristic<br />

numeral<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IP<br />

Additional<br />

letter<br />

(optional) A<br />

B<br />

C<br />

D<br />

Supplementary<br />

letter<br />

(optional)<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

H<br />

M<br />

S<br />

W<br />

Fig. E48 : Elements <strong>of</strong> the IP Code<br />

Meaning for the protection<br />

<strong>of</strong> equipment<br />

Against ingress <strong>of</strong> solid foreign<br />

objects<br />

(non-protected)<br />

u 50 mm diameter<br />

u 12.5 mm diameter<br />

u 2.5 mm diameter<br />

u 1.0 mm diameter<br />

Dust-protected<br />

Dust-tight<br />

Against ingress <strong>of</strong> water with<br />

harmful effects<br />

(non-protected)<br />

Vertically dripping<br />

Dripping (15° tilted)<br />

Spraying<br />

Splashing<br />

Jetting<br />

Powerful jetting<br />

Temporary immersion<br />

Continuous immersion<br />

Supplementary information specific to:<br />

High-voltage apparatus<br />

Motion during water test<br />

Stationary during water test<br />

Weather conditions<br />

Meaning for the<br />

protection <strong>of</strong> persons<br />

Against access to<br />

hazardous parts with<br />

(non-protected)<br />

Back <strong>of</strong> hand<br />

Finger<br />

Tool<br />

Wire<br />

Wire<br />

Wire<br />

Against access to<br />

hazardous parts with<br />

back <strong>of</strong> hand<br />

Finger<br />

Tool<br />

Wire


E - Distribution in low-voltage <strong>installation</strong>s<br />

3 External influences<br />

(IEC 60364-5-51)<br />

IK Code definition<br />

Standard IEC 62262 defines an IK code that characterises the aptitude <strong>of</strong> equipment<br />

to resist mechanical impacts on all sides (see Fig. E49).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IK code Impact energy AG code<br />

(in Joules)<br />

00 0<br />

01 y 0.14<br />

02 y 0.20 AG1<br />

03 y 0.35<br />

04 y 0.50<br />

05 y 0.70<br />

06 y 1<br />

07 y 2 AG2<br />

08 y 5 AG3<br />

09 y 10<br />

10 y 20 AG4<br />

Fig. E49 : Elements <strong>of</strong> the IK Code<br />

IP and IK code specifications for distribution switchboards<br />

The degrees <strong>of</strong> protection IP and IK <strong>of</strong> an enclosure must be specified as a function<br />

<strong>of</strong> the different external influences defined by standard IEC 60364-5-51, in particular:<br />

b Presence <strong>of</strong> solid bodies (code AE)<br />

b Presence <strong>of</strong> water (code AD)<br />

b Mechanical stresses (no code)<br />

b Capability <strong>of</strong> persons (code BA)<br />

b …<br />

Prisma Plus switchboards are <strong>design</strong>ed for indoor <strong>installation</strong>.<br />

Unless the <strong>rules</strong>, standards and regulations <strong>of</strong> a specific country stipulate otherwise,<br />

Schneider Electric recommends the following IP and IK values (see Fig. E50 and<br />

Fig. E51 )<br />

IP recommendations<br />

IP codes according to conditions<br />

Normal without risk <strong>of</strong> vertically falling water Technical rooms 30<br />

Normal with risk <strong>of</strong> vertically falling water Hallways 31<br />

Very severe with risk <strong>of</strong> splashing water Workshops 54/55<br />

from all directions<br />

Fig. E50 : IP recommendations<br />

IK recommendations<br />

IK codes according to conditions<br />

No risk <strong>of</strong> major impact Technical rooms 07<br />

Significant risk <strong>of</strong> major impact that could Hallways 08 (enclosure<br />

damage devices with door)<br />

Maximum risk <strong>of</strong> impact that could damage Workshops 10<br />

the enclosure<br />

Fig. E51 : IK recommendations<br />

E29<br />

© Schneider Electric - all rights reserved


2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

<strong>Chapter</strong> F<br />

Protection against electric shocks<br />

Contents<br />

<strong>General</strong> F2<br />

1.1 Electric shock F2<br />

1.2 Protection against electric shock F3<br />

1.3 Direct and indirect contact F3<br />

Protection against direct contact F4<br />

2.1 Measures <strong>of</strong> protection against direct contact F4<br />

2.2 Additional measure <strong>of</strong> protection against direct contact F6<br />

Protection against indirect contact F6<br />

3.1 Measures <strong>of</strong> protection: two levels F6<br />

3.2 Automatic disconnection for TT system F7<br />

3.3 Automatic disconnection for TN systems F8<br />

3.4 Automatic disconnection on a second fault in an IT system F10<br />

3.5 Measures <strong>of</strong> protection against direct or indirect contact<br />

without automatic disconnection <strong>of</strong> supply F13<br />

Protection <strong>of</strong> goods in case <strong>of</strong> insulation fault F 7<br />

4.1 Measures <strong>of</strong> protection against fire risk with RCDs F17<br />

4.2 Ground Fault Protection (GFP) F17<br />

Implementation <strong>of</strong> the TT system F 9<br />

5.1 Protective measures F19<br />

5.2 Coordination <strong>of</strong> residual current protective devices F20<br />

Implementation <strong>of</strong> the TN system F23<br />

6.1 Preliminary conditions F23<br />

6.2 Protection against indirect contact F23<br />

6.3 High-sensitivity RCDs F27<br />

6.4 Protection in high fire-risk locations F28<br />

6.5 When the fault current-loop impedance is particularly high F28<br />

Implementation <strong>of</strong> the IT system F29<br />

7.1 Preliminary conditions F29<br />

7.2 Protection against indirect contact F30<br />

7.3 High-sensitivity RCDs F34<br />

7.4 Protection in high fire-risk locations F35<br />

7.5 When the fault current-loop impedance is particularly high F35<br />

Residual current differential devices (RCDs) F36<br />

8.1 Types <strong>of</strong> RCDs F36<br />

8.2 Description F36<br />

8.3 Sensitivity <strong>of</strong> RDCs to disturbances F39<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

F2<br />

F - Protection against electric shock<br />

When a current exceeding 30 mA passes<br />

through a part <strong>of</strong> a human body, the person<br />

concerned is in serious danger if the current is<br />

not interrupted in a very short time.<br />

The protection <strong>of</strong> persons against electric<br />

shock in LV <strong>installation</strong>s must be provided in<br />

conformity with appropriate national standards<br />

statutory regulations, codes <strong>of</strong> practice, <strong>of</strong>ficial<br />

guides and circulars etc.<br />

Relevant IEC standards include: IEC 60364,<br />

IEC 60479 series, IEC 61008, IEC 61009 and<br />

IEC 60947-2.<br />

10,000<br />

5,000<br />

2,000<br />

1,000<br />

500<br />

200<br />

100<br />

50<br />

20<br />

10<br />

Duration <strong>of</strong> current<br />

flow I (ms)<br />

AC-1<br />

A B<br />

<strong>General</strong><br />

. Electric shock<br />

Fig. F1 : Zones time/current <strong>of</strong> effects <strong>of</strong> AC current on human body when passing from left hand to feet<br />

An electric shock is the pathophysiological effect <strong>of</strong> an electric current through the<br />

human body.<br />

Its passage affects essentially the muscular, circulatory and respiratory functions and<br />

sometimes results in serious burns. The degree <strong>of</strong> danger for the victim is a function<br />

<strong>of</strong> the magnitude <strong>of</strong> the current, the parts <strong>of</strong> the body through which the current<br />

passes, and the duration <strong>of</strong> current flow.<br />

IEC publication 60479-1 updated in 2005 defines four zones <strong>of</strong> current-magnitude/<br />

time-duration, in each <strong>of</strong> which the pathophysiological effects are described (see Fig<br />

F ). Any person coming into contact with live metal risks an electric shock.<br />

Curve C1 shows that when a current greater than 30 mA passes through a human<br />

being from one hand to feet, the person concerned is likely to be killed, unless the<br />

current is interrupted in a relatively short time.<br />

The point 500 ms/100 mA close to the curve C1 corresponds to a probability <strong>of</strong> heart<br />

fibrillation <strong>of</strong> the order <strong>of</strong> 0.14%.<br />

The protection <strong>of</strong> persons against electric shock in LV <strong>installation</strong>s must be provided<br />

in conformity with appropriate national standards and statutory regulations, codes <strong>of</strong><br />

practice, <strong>of</strong>ficial guides and circulars, etc. Relevant IEC standards include: IEC 60364<br />

series, IEC 60479 series, IEC 60755, IEC 61008 series, IEC 61009 series and IEC<br />

60947-2.<br />

C 1 C 2 C 3<br />

AC-2 AC-3 AC-4<br />

0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 2,000 10,000<br />

1,000 5,000<br />

AC-1 zone: Imperceptible<br />

AC-2 zone: Perceptible<br />

AC-3 zone : Reversible effects: muscular contraction<br />

AC-4 zone: Possibility <strong>of</strong> irreversible effects<br />

AC-4-1 zone: Up to 5%probability <strong>of</strong> heart fibrillation<br />

AC-4-2 zone: Up to 50% probability <strong>of</strong> heart fibrillation<br />

AC-4-3 zone: More than 50% probability <strong>of</strong> heart fibrillation<br />

AC-4.1 AC-4.2<br />

AC-4.3<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A curve: Threshold <strong>of</strong> perception <strong>of</strong> current<br />

B curve: Threshold <strong>of</strong> muscular reactions<br />

Body current<br />

I s (mA)<br />

C 1 curve: Threshold <strong>of</strong> 0% probability <strong>of</strong> ventricular<br />

fibrillation<br />

C 2 curve: Threshold <strong>of</strong> 5% probability <strong>of</strong> ventricular<br />

fibrillation<br />

C 3 curve: Threshold <strong>of</strong> 50% probability <strong>of</strong> ventricular<br />

fibrillation


F - Protection against electric shock<br />

Two measures <strong>of</strong> protection against direct<br />

contact hazards are <strong>of</strong>ten required, since, in<br />

practice, the first measure may not be infallible<br />

Standards and regulations distinguish two kinds<br />

<strong>of</strong> dangerous contact,<br />

b Direct contact<br />

b Indirect contact<br />

and corresponding protective measures<br />

Is<br />

Is: Touch current<br />

1 2 3 N<br />

Busbars<br />

<strong>General</strong><br />

.2 Protection against electric shock<br />

The fundamental rule <strong>of</strong> protection against electric shock is provided by the<br />

document IEC 61140 which covers both <strong>electrical</strong> <strong>installation</strong>s and <strong>electrical</strong><br />

equipment.<br />

Hazardous-live-parts shall not be accessible and accessible conductive parts shall<br />

not be hazardous.<br />

This requirement needs to apply under:<br />

b Normal conditions, and<br />

b Under a single fault condition<br />

Various measures are adopted to protect against this hazard, and include:<br />

b Automatic disconnection <strong>of</strong> the power supply to the connected <strong>electrical</strong> equipment<br />

b Special arrangements such as:<br />

v The use <strong>of</strong> class II insulation materials, or an equivalent level <strong>of</strong> insulation<br />

v Non-conducting location, out <strong>of</strong> arm’s reach or interposition <strong>of</strong> barriers<br />

v Equipotential bonding<br />

v Electrical separation by means <strong>of</strong> isolating transformers<br />

.3 Direct and indirect contact<br />

Direct contact<br />

A direct contact refers to a person coming into contact with a conductor which is live<br />

in normal circumstances (see Fig. F2).<br />

IEC 61140 standard has renamed “protection against direct contact” with the term<br />

“basic protection”. The former name is at least kept for information.<br />

Indirect contact<br />

Fig. F2 : Direct contact Fig F3 : Indirect contact<br />

An indirect contact refers to a person coming into contact with an exposedconductive-part<br />

which is not normally alive, but has become alive accidentally (due<br />

to insulation failure or some other cause).<br />

The fault current raise the exposed-conductive-part to a voltage liable to be<br />

hazardous which could be at the origin <strong>of</strong> a touch current through a person coming<br />

into contact with this exposed-conductive-part (see Fig. F3).<br />

IEC 61140 standard has renamed “protection against indirect contact” with the term<br />

“fault protection”. The former name is at least kept for information.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Is<br />

1 2 3 PE<br />

Id<br />

Insulation<br />

failure<br />

Id: Insulation fault current<br />

F3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

F<br />

F - Protection against electric shock<br />

IEC and national standards frequently<br />

distinguish two protection:<br />

b Complete (insulation, enclosures)<br />

b Partial or particular<br />

Fig. F5 : Example <strong>of</strong> isolation by envelope<br />

2 Protection against direct contact<br />

Two complementary measures are commonly used as protection against the<br />

dangers <strong>of</strong> direct contact:<br />

b The physical prevention <strong>of</strong> contact with live parts by barriers, insulation,<br />

inaccessibility, etc.<br />

b Additional protection in the event that a direct contact occurs, despite or due to<br />

failure <strong>of</strong> the above measures. This protection is based on residual-current operating<br />

device with a high sensitivity (IΔn y 30 mA) and a low operating time. These devices<br />

are highly effective in the majority <strong>of</strong> case <strong>of</strong> direct contact.<br />

2.1 Measures <strong>of</strong> protection against direct contact<br />

Protection by the insulation <strong>of</strong> live parts<br />

This protection consists <strong>of</strong> an insulation which complies with the relevant standards<br />

(see Fig. F ). Paints, lacquers and varnishes do not provide an adequate protection.<br />

Fig. F4 : Inherent protection against direct contact by insulation <strong>of</strong> a 3-phase cable with outer<br />

sheath<br />

Protection by means <strong>of</strong> barriers or enclosures<br />

This measure is in widespread use, since many components and materials are<br />

installed in cabinets, assemblies, control panels and distribution boards (see Fig. F5).<br />

To be considered as providing effective protection against direct contact hazards,<br />

these equipment must possess a degree <strong>of</strong> protection equal to at least IP 2X or<br />

IP XXB (see chapter E sub-clause 3.4).<br />

Moreover, an opening in an enclosure (door, front panel, drawer, etc.) must only be<br />

removable, open or withdrawn:<br />

b By means <strong>of</strong> a key or tool provided for this purpose, or<br />

b After complete isolation <strong>of</strong> the live parts in the enclosure, or<br />

b With the automatic interposition <strong>of</strong> another screen removable only with a key or<br />

a tool. The metal enclosure and all metal removable screen must be bonded to the<br />

protective earthing conductor <strong>of</strong> the <strong>installation</strong>.<br />

Partial measures <strong>of</strong> protection<br />

b Protection by means <strong>of</strong> obstacles, or by placing out <strong>of</strong> arm’s reach<br />

This protection is reserved only to locations to which skilled or instructed<br />

persons only have access. The erection <strong>of</strong> this protective measure is detailed in<br />

IEC 60364-4-41.<br />

Particular measures <strong>of</strong> protection<br />

b Protection by use <strong>of</strong> extra-low voltage SELV (Safety Extra-Low Voltage) or by<br />

limitation <strong>of</strong> the energy <strong>of</strong> discharge.<br />

These measures are used only in low-power circuits, and in particular circumstances,<br />

as described in section 3.5.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

An additional measure <strong>of</strong> protection against<br />

the hazards <strong>of</strong> direct contact is provided by the<br />

use <strong>of</strong> residual current operating device, which<br />

operate at 30 mA or less, and are referred to as<br />

RCDs <strong>of</strong> high sensitivity<br />

Fig. F6 : High sensitivity RCD<br />

2 Protection against direct contact<br />

2.2 Additional measure <strong>of</strong> protection against direct<br />

contact<br />

All the preceding protective measures are preventive, but experience has shown<br />

that for various reasons they cannot be regarded as being infallible. Among these<br />

reasons may be cited:<br />

b Lack <strong>of</strong> proper maintenance<br />

b Imprudence, carelessness<br />

b Normal (or abnormal) wear and tear <strong>of</strong> insulation; for instance flexure and abrasion<br />

<strong>of</strong> connecting leads<br />

b Accidental contact<br />

b Immersion in water, etc. A situation in which insulation is no longer effective<br />

In order to protect users in such circumstances, highly sensitive fast tripping<br />

devices, based on the detection <strong>of</strong> residual currents to earth (which may or may<br />

not be through a human being or animal) are used to disconnect the power<br />

supply automatically, and with sufficient rapidity to prevent injury to, or death by<br />

electrocution, <strong>of</strong> a normally healthy human being (see Fig. F6).<br />

These devices operate on the principle <strong>of</strong> differential current measurement, in which<br />

any difference between the current entering a circuit and that leaving it (on a system<br />

supplied from an earthed source) be flowing to earth, either through faulty insulation<br />

or through contact <strong>of</strong> an earthed part, such as a person, with a live conductor.<br />

Standardised residual-current devices, referred to as RCDs, sufficiently sensitive for<br />

protection against direct contact are rated at 30 mA <strong>of</strong> differential current.<br />

According to IEC 60364-4-41, additional protection by means <strong>of</strong> high sensitivity<br />

RCDs (I∆n y 30 mA) must be provided for circuits supplying socket-outlets with a<br />

rated current y 20 A in all locations, and for circuits supplying mobile equipment with<br />

a rated current y 32 A for use outdoors.<br />

This additional protection is required in certain countries for circuits supplying socketoutlets<br />

rated up to 32 A, and even higher if the location is wet and/or temporary<br />

(such as work sites for instance).<br />

It is also recommended to limit the number <strong>of</strong> socket-outlets protected by a RCD<br />

(e.g. 10 socket-outlets for one RCD).<br />

<strong>Chapter</strong> P section 3 itemises various common locations in which RCDs <strong>of</strong><br />

high sensitivity are obligatory (in some countries), but in any case, are highly<br />

recommended as an effective protection against both direct and indirect contact<br />

hazards.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

F<br />

F - Protection against electric shock<br />

Protection against indirect contact hazards<br />

can be achieved by automatic disconnection <strong>of</strong><br />

the supply if the exposed-conductive-parts <strong>of</strong><br />

equipment are properly earthed<br />

(1) Touch voltage Uc is the voltage existing (as the result <strong>of</strong><br />

insulation failure) between an exposed-conductive-part and<br />

any conductive element within reach which is at a different<br />

(generally earth) potential.<br />

3 Protection against indirect<br />

contact<br />

Exposed-conductive-parts used in the manufacturing process <strong>of</strong> an <strong>electrical</strong><br />

equipment is separated from the live parts <strong>of</strong> the equipment by the “basic insulation”.<br />

Failure <strong>of</strong> the basic insulation will result in the exposed-conductive-parts being alive.<br />

Touching a normally dead part <strong>of</strong> an <strong>electrical</strong> equipment which has become live due<br />

to the failure <strong>of</strong> its insulation, is referred to as an indirect contact.<br />

3.1 Measures <strong>of</strong> protection: two levels<br />

Two levels <strong>of</strong> protective measures exist:<br />

b 1 st level: The earthing <strong>of</strong> all exposed-conductive-parts <strong>of</strong> <strong>electrical</strong> equipment in the<br />

<strong>installation</strong> and the constitution <strong>of</strong> an equipotential bonding network (see chapter G<br />

section 6).<br />

b 2 sd level: Automatic disconnection <strong>of</strong> the supply <strong>of</strong> the section <strong>of</strong> the <strong>installation</strong><br />

concerned, in such a way that the touch-voltage/time safety requirements are<br />

respected for any level <strong>of</strong> touch voltage Uc (1) (see Fig. F7).<br />

Earth<br />

connection<br />

Fig. F7 : Illustration <strong>of</strong> the dangerous touch voltage Uc<br />

The greater the value <strong>of</strong> Uc, the greater the rapidity <strong>of</strong> supply disconnection required<br />

to provide protection (see Fig. F8). The highest value <strong>of</strong> Uc that can be tolerated<br />

indefinitely without danger to human beings is 50 V a.c.<br />

Reminder <strong>of</strong> the theoretical disconnecting-time limits<br />

Uo (V) 50 < Uo y 120 120 < Uo y 230 230 < Uo y 400 Uo > 400<br />

System TN or IT 0.8 0.4 0.2 0.1<br />

TT 0.3 0.2 0.07 0.04<br />

Fig. F8 : Maximum safe duration <strong>of</strong> the assumed values <strong>of</strong> AC touch voltage (in seconds)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Uc


F - Protection against electric shock<br />

Automatic disconnection for TT system is<br />

achieved by RCD having a sensitivity <strong>of</strong><br />

I�n i<br />

R<br />

50<br />

where R A is the resistance <strong>of</strong> the<br />

A<br />

<strong>installation</strong> earth electrode<br />

R n = 10 Ω<br />

Substation<br />

earth<br />

electrode<br />

R A = 20 Ω<br />

Installation<br />

earth<br />

electrode<br />

U f<br />

1<br />

2<br />

3<br />

N<br />

PE<br />

Fig. F9 : Automatic disconnection <strong>of</strong> supply for TT system<br />

3 Protection against indirect<br />

contact<br />

3.2 Automatic disconnection for TT system<br />

Principle<br />

In this system all exposed-conductive-parts and extraneous-conductive-parts <strong>of</strong><br />

the <strong>installation</strong> must be connected to a common earth electrode. The neutral point<br />

<strong>of</strong> the supply system is normally earthed at a pint outside the influence area <strong>of</strong> the<br />

<strong>installation</strong> earth electrode, but need not be so. The impedance <strong>of</strong> the earth-fault loop<br />

therefore consists mainly in the two earth electrodes (i.e. the source and <strong>installation</strong><br />

electrodes) in series, so that the magnitude <strong>of</strong> the earth fault current is generally<br />

too small to operate overcurrent relay or fuses, and the use <strong>of</strong> a residual current<br />

operated device is essential.<br />

This principle <strong>of</strong> protection is also valid if one common earth electrode only is used,<br />

notably in the case <strong>of</strong> a consumer-type substation within the <strong>installation</strong> area, where<br />

space limitation may impose the adoption <strong>of</strong> a TN system earthing, but where all<br />

other conditions required by the TN system cannot be fulfilled.<br />

Protection by automatic disconnection <strong>of</strong> the supply used in TT system is by RCD <strong>of</strong><br />

sensitivity: I�n i<br />

R<br />

50<br />

where R<br />

A<br />

where<br />

<strong>installation</strong> earth electrode<br />

R A is the resistance <strong>of</strong> the earth electrode for the <strong>installation</strong><br />

I Δn is the rated residual operating current <strong>of</strong> the RCD<br />

For temporary supplies (to work sites, …) and agricultural and horticultural premises,<br />

the value <strong>of</strong> 50 V is replaced by 25 V.<br />

Example (see Fig. F9)<br />

b The resistance <strong>of</strong> the earth electrode <strong>of</strong> substation neutral Rn is 10 Ω.<br />

b The resistance <strong>of</strong> the earth electrode <strong>of</strong> the <strong>installation</strong> RA is 20 Ω.<br />

b The earth-fault loop current Id = 7.7 A.<br />

b The fault voltage Uf = Id x RA = 154 V and therefore dangerous, but<br />

IΔn = 50/20 = 2.5 A so that a standard 300 mA RCD will operate in about 30 ms<br />

without intentional time delay and will clear the fault where a fault voltage exceeding<br />

appears on an exposed-conductive-part.<br />

Fig. F10 : Maximum disconnecting time for AC final circuits not exceeding 32 A<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Uo<br />

(1) Uo is the nominal phase to earth voltage<br />

(1) (V) T (s)<br />

50 < Uo y 120 0.3<br />

120 < Uo y 230 0.2<br />

230 < Uo y 400 0.07<br />

Uo > 400 0.04<br />

Specified maximum disconnection time<br />

The tripping times <strong>of</strong> RCDs are generally lower than those required in the majority<br />

<strong>of</strong> national standards; this feature facilitates their use and allows the adoption <strong>of</strong> an<br />

effective discriminative protection.<br />

The IEC 60364-4-41 specifies the maximum operating time <strong>of</strong> protective devices<br />

used in TT system for the protection against indirect contact:<br />

b For all final circuits with a rated current not exceeding 32 A, the maximum<br />

disconnecting time will not exceed the values indicated in Figure F10<br />

b For all other circuits, the maximum disconnecting time is fixed to 1s. This limit<br />

enables discrimination between RCDs when installed on distribution circuits.<br />

RCD is a general term for all devices operating on the residual-current principle.<br />

RCCB (Residual Current Circuit-Breaker) as defined in IEC 61008 series is a specific<br />

class <strong>of</strong> RCD.<br />

Type G (general) and type S (Selective) <strong>of</strong> IEC 61008 have a tripping time/current<br />

characteristics as shown in Figure F11 next page. These characteristics allow a certain<br />

degree <strong>of</strong> selective tripping between the several combination <strong>of</strong> ratings and types, as<br />

shown later in sub-clause 4.3. Industrial type RCD according to IEC 60947-2 provide<br />

more possibilities <strong>of</strong> discrimination due to their flexibility <strong>of</strong> time-delaying.<br />

F7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

F8<br />

F - Protection against electric shock<br />

The automatic disconnection for TN system is<br />

achieved by overcurrent protective devices or<br />

RCD’s<br />

N<br />

A<br />

F<br />

35 mm 2<br />

Fig. F12 : Automatic disconnection in TN system<br />

E<br />

B<br />

D C<br />

1<br />

2<br />

3<br />

PEN<br />

NS160<br />

50 m<br />

35 mm 2<br />

U f<br />

3 Protection against indirect<br />

contact<br />

3.3 Automatic disconnection for TN systems<br />

Principle<br />

x I Δn 1 2 5 > 5<br />

Domestic Instantaneous 0.3 0.15 0.04 0.04<br />

Fig. F11 : Maximum operating time <strong>of</strong> RCD’s (in seconds)<br />

In this system all exposed and extraneous-conductive-parts <strong>of</strong> the <strong>installation</strong> are<br />

connected directly to the earthed point <strong>of</strong> the power supply by protective conductors.<br />

As noted in <strong>Chapter</strong> E Sub-clause 1.2, the way in which this direct connection is<br />

carried out depends on whether the TN-C, TN-S, or TN-C-S method <strong>of</strong> implementing<br />

the TN principle is used. In figure F12 the method TN-C is shown, in which the<br />

neutral conductor acts as both the Protective-Earth and Neutral (PEN) conductor. In<br />

all TN systems, any insulation fault to earth results in a phase to neutral short-circuit.<br />

High fault current levels allow to use overcurrent protection but can give rise to touch<br />

voltages exceeding 50% <strong>of</strong> the phase to neutral voltage at the fault position during<br />

the short disconnection time.<br />

In practice for utility distribution network, earth electrodes are normally installed at<br />

regular intervals along the protective conductor (PE or PEN) <strong>of</strong> the network, while<br />

the consumer is <strong>of</strong>ten required to install an earth electrode at the service entrance.<br />

On large <strong>installation</strong>s additional earth electrodes dispersed around the premises are<br />

<strong>of</strong>ten provided, in order to reduce the touch voltage as much as possible. In high-rise<br />

apartment blocks, all extraneous conductive parts are connected to the protective<br />

conductor at each level. In order to ensure adequate protection, the earth-fault<br />

current<br />

Id or 0.8 I<br />

Uo<br />

=<br />

Zc<br />

Uo<br />

u must be higher or equal to Ia, where:<br />

Zs<br />

b Uo = nominal phase to neutral voltage<br />

b Id = the fault current<br />

b Ia = current equal to the value required to operate the protective device in the time<br />

specified<br />

b Zs = earth-fault current loop impedance, equal to the sum <strong>of</strong> the impedances <strong>of</strong> the<br />

source, the live phase conductors to the fault position, the protective conductors from<br />

the fault position back to the source<br />

b Zc = the faulty-circuit loop impedance (see “conventional method” Sub-clause 6.2)<br />

Note: The path through earth electrodes back to the source will have (generally)<br />

much higher impedance values than those listed above, and need not be considered.<br />

Example (see Fig. F12)<br />

230<br />

The fault voltage Uf = = 115 V and and is is hazardous;<br />

2<br />

The fault loop impedance Zs=Zab + Zbc + Zde + Zen + Zna.<br />

If Zbc and Zde are predominant, then:<br />

L<br />

“conventional Zs = 2� = 64method” . 3 m� , , so and so that in this example will give an estimated fault current <strong>of</strong><br />

S<br />

230<br />

Id=<br />

= (<br />

64.3 x10-3 3,576 A (≈ 22 In based on a NS 160 circuit-breaker).<br />

The “instantaneous” magnetic trip unit adjustment <strong>of</strong> the circuit-breaker is many time<br />

less than this short-circuit value, so that positive operation in the shortest possible<br />

time is assured.<br />

Note: Some authorities base such calculations on the assumption that a voltage<br />

drop <strong>of</strong> 20% occurs in the part <strong>of</strong> the impedance loop BANE.<br />

This method, which is recommended, is explained in chapter F sub-clause 6.2<br />

“conventional<br />

“conventional<br />

method”<br />

method”<br />

and<br />

and<br />

in<br />

in<br />

this<br />

this<br />

example<br />

example<br />

will<br />

will<br />

give<br />

give<br />

an<br />

an<br />

estimated<br />

estimated<br />

fault<br />

fault<br />

current<br />

current<br />

<strong>of</strong><br />

<strong>of</strong><br />

3<br />

230 x 0.8 x 10<br />

= 2,816 A ( (≈ 18 In).<br />

64.3<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Type S 0.5 0.2 0.15 0.15<br />

Industrial Instantaneous 0.3 0.15 0.04 0.04<br />

Time-delay (0.06) 0.5 0.2 0.15 0.15<br />

Time-delay (other) According to manufacturer


F - Protection against electric shock<br />

If the protection is to be provided by a circuitbreaker,<br />

it is sufficient to verify that the fault<br />

current will always exceed the current-setting<br />

level <strong>of</strong> the instantaneous or short-time delay<br />

tripping unit (Im)<br />

t<br />

1: Short-time delayed trip<br />

2: Instantaneous trip<br />

Im Uo/Zs<br />

1<br />

2<br />

I<br />

3 Protection against indirect<br />

contact<br />

Specified maximum disconnection time<br />

The IEC 60364-4-41 specifies the maximum operating time <strong>of</strong> protective devices<br />

used in TN system for the protection against indirect contact:<br />

b For all final circuits with a rated current not exceeding 32 A, the maximum<br />

disconnecting time will not exceed the values indicated in Figure F13<br />

b For all other circuits, the maximum disconnecting time is fixed to 5s. This limit<br />

enables discrimination between protective devices installed on distribution circuits<br />

Note: The use <strong>of</strong> RCDs may be necessary on TN-earthed systems. Use <strong>of</strong> RCDs on<br />

TN-C-S systems means that the protective conductor and the neutral conductor must<br />

(evidently) be separated upstream <strong>of</strong> the RCD. This separation is commonly made at<br />

the service entrance.<br />

Fig. F13 : Maximum disconnecting time for AC final circuits not exceeding 32 A<br />

tc = 0.4 s<br />

Fig. F14 : Disconnection by circuit-breaker for a TN system Fig. F15 : Disconnection by fuses for a TN system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Uo<br />

(1) Uo is the nominal phase to earth voltage<br />

(1) (V) T (s)<br />

50 < Uo y 120 0.8<br />

120 < Uo y 230 0.4<br />

230 < Uo y 400 0.2<br />

Uo > 400 0.1<br />

Protection by means <strong>of</strong> circuit-breaker (see Fig. F14)<br />

The instantaneous trip unit <strong>of</strong> a circuit-breaker will eliminate a short-circuit to earth in<br />

less than 0.1 second.<br />

In consequence, automatic disconnection within the maximum allowable time will<br />

always be assured, since all types <strong>of</strong> trip unit, magnetic or electronic, instantaneous<br />

or slightly retarded, are suitable: Ia = Im. The maximum tolerance authorised<br />

by the relevant standard, however, must always be taken into consideration. It is<br />

sufficient therefore that the fault current Uo Uo<br />

or 0.8 determined by by calculation (or estimated<br />

Zs Zc<br />

(or estimated on site) on site) be greater be greater than than the instantaneous the instantaneous trip-setting trip-setting current, current, or than or than the very short-<br />

the very short-time tripping threshold level, to be sure <strong>of</strong> tripping within the permitted<br />

time limit.<br />

Ia can be determined from the fuse<br />

Protection by means <strong>of</strong> fuses (see Fig. F15)<br />

performance curve. In any case, protection The value <strong>of</strong> current which assures the correct operation <strong>of</strong> a fuse can be<br />

cannot be achieved if the loop impedance Zs ascertained from a current/time performance graph for the fuse concerned.<br />

or Zc exceeds a certain value<br />

therefore that The the fault current Uo Uo<br />

or 0.8 determined as determined by calculation above, must (or largely estimated exceed that<br />

Zs Zc<br />

on site) be greater necessary than the to ensure instantaneous positive operation trip-setting operation <strong>of</strong> current, the fuse. or The than condition the very short- to observe<br />

therefore is that Ia < Uo Uo<br />

or 0.8 as as indicated in Figure in Figure F15. F15.<br />

Zs Zc<br />

t<br />

Ia Uo/Zs<br />

I<br />

F9<br />

© Schneider Electric - all rights reserved


F10<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

In IT system the first fault to earth should not<br />

cause any disconnection<br />

Fig. F16 : Phases to earth insulation monitoring device<br />

obligatory in IT system<br />

(1) Resistive leakage current to earth through the insulation is<br />

assumed to be negligibly small in the example.<br />

3 Protection against indirect<br />

contact<br />

Example: The nominal phase to neutral voltage <strong>of</strong> the network is 230 V and<br />

the maximum disconnection time given by the graph in Figure F15 is 0.4 s.<br />

The corresponding value <strong>of</strong> Ia can be read from the graph. Using the voltage (230 V)<br />

and the current Ia,<br />

Ia,<br />

the<br />

the<br />

complete<br />

complete<br />

loop<br />

loop<br />

impedance<br />

impedance<br />

or<br />

or<br />

the<br />

the<br />

circuit<br />

circuit<br />

loop<br />

loop<br />

impedance<br />

impedance<br />

can<br />

can<br />

230<br />

be calculated from Zs = or Zc = 0.8<br />

Ia Ia<br />

230 . This impedance value must never be<br />

exceeded and should preferably be substantially less to ensure satisfactory fuse<br />

operation.<br />

Protection by means <strong>of</strong> Residual Current Devices for<br />

TN-S circuits<br />

Residual Current Devices must be used where:<br />

b The loop impedance cannot be determined precisely (lengths difficult to estimate,<br />

presence <strong>of</strong> metallic material close to the wiring)<br />

b The fault current is so low that the disconnecting time cannot be met by using<br />

overcurrent protective devices<br />

The rated tripping current <strong>of</strong> RCDs being in the order <strong>of</strong> a few amps, it is well below<br />

the fault current level. RCDs are consequently well adapted to this situation.<br />

In practice, they are <strong>of</strong>ten installed in the LV sub distribution and in many countries,<br />

the automatic disconnection <strong>of</strong> final circuits shall be achieved by Residual Current<br />

Devices.<br />

3.4 Automatic disconnection on a second fault in an<br />

IT system<br />

In this type <strong>of</strong> system:<br />

b The <strong>installation</strong> is isolated from earth, or the neutral point <strong>of</strong> its power-supply<br />

source is connected to earth through a high impedance<br />

b All exposed and extraneous-conductive-parts are earthed via an <strong>installation</strong> earth<br />

electrode.<br />

First fault situation<br />

On the occurrence <strong>of</strong> a true fault to earth, referred to as a “first fault”, the fault current<br />

is very low, such that the rule Id x RA y 50 V (see F3.2) is fulfilled and no dangerous<br />

fault voltages can occur.<br />

In practice the current Id is low, a condition that is neither dangerous to personnel,<br />

nor harmful to the <strong>installation</strong>.<br />

However, in this system:<br />

b A permanent monitoring <strong>of</strong> the insulation to earth must be provided, coupled with<br />

an alarm signal (audio and/or flashing lights, etc.) operating in the event <strong>of</strong> a first<br />

earth fault (see Fig. F1 )<br />

b The rapid location and repair <strong>of</strong> a first fault is imperative if the full benefits <strong>of</strong> the<br />

IT system are to be realised. Continuity <strong>of</strong> service is the great advantage afforded by<br />

the system.<br />

For a network formed from 1 km <strong>of</strong> new conductors, the leakage (capacitive)<br />

impedance to earth Zf is <strong>of</strong> the order <strong>of</strong> 3,500 Ω per phase. In normal operation, the<br />

capacitive current (1) to earth is therefore:<br />

Uo 230<br />

= = 66 mA per phase.<br />

Zf 3,500<br />

During a phase to earth fault, as indicated in Figure F17 opposite page, the current<br />

passing through the electrode resistance RnA is the vector sum <strong>of</strong> the capacitive<br />

currents in the two healthy phases. The voltages <strong>of</strong> the healthy phases have<br />

(because <strong>of</strong> the fault) increased to 3 the normal phase voltage, so that the capacitive<br />

currents increase by the same amount. These currents are displaced, one from the<br />

other by 60°, so that when added vectorially, this amounts to 3 x 66 mA = 198 mA, in<br />

the present example.<br />

The fault voltage Uf is therefore equal to 198 x 5 x 10-3 = 0.99 V, which is obviously<br />

harmless.<br />

The current through the short-circuit to earth is given by the vector sum <strong>of</strong> the<br />

neutral-resistor current Id1 (=153 mA) and the capacitive current Id2 (198 mA).<br />

Since the exposed-conductive-parts <strong>of</strong> the <strong>installation</strong> are connected directly to<br />

earth, the neutral impedance Zct plays practically no part in the production <strong>of</strong> touch<br />

voltages to earth.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

The simultaneous existence <strong>of</strong> two earth faults<br />

(if not both on the same phase) is dangerous,<br />

and rapid clearance by fuses or automatic<br />

circuit-breaker tripping depends on the type <strong>of</strong><br />

earth-bonding scheme, and whether separate<br />

earthing electrodes are used or not, in the<br />

<strong>installation</strong> concerned<br />

(1) Based on the “conventional method” noted in the first<br />

example <strong>of</strong> Sub-clause 3.3.<br />

3 Protection against indirect<br />

contact<br />

Z ct = 1,500 Ω<br />

R nA = 5 Ω<br />

Id1<br />

Fig. F17 : Fault current path for a first fault in IT system<br />

Second fault situation<br />

On the appearance <strong>of</strong> a second fault, on a different phase, or on a neutral conductor,<br />

a rapid disconnection becomes imperative. Fault clearance is carried out differently in<br />

each <strong>of</strong> the following cases:<br />

1 st case<br />

It concerns an <strong>installation</strong> in which all exposed conductive parts are bonded to a<br />

common PE conductor, as shown in Figure F18.<br />

In this case no earth electrodes are included in the fault current path, so that a high<br />

level <strong>of</strong> fault current is assured, and conventional overcurrent protective devices are<br />

used, i.e. circuit-breakers and fuses.<br />

The first fault could occur at the end <strong>of</strong> a circuit in a remote part <strong>of</strong> the <strong>installation</strong>,<br />

while the second fault could feasibly be located at the opposite end <strong>of</strong> the <strong>installation</strong>.<br />

For this reason, it is conventional to double the loop impedance <strong>of</strong> a circuit, when<br />

calculating the anticipated fault setting level for its overcurrent protective device(s).<br />

Where the system includes a neutral conductor in addition to the 3 phase<br />

conductors, the lowest short-circuit fault currents will occur if one <strong>of</strong> the (two) faults is<br />

from the neutral conductor to earth (all four conductors are insulated from earth in an<br />

IT scheme). In four-wire IT <strong>installation</strong>s, therefore, the phase-to-neutral voltage must<br />

be used to calculate short-circuit protective levels i.e. 0.8 Uo<br />

u I a (1) where<br />

2 Zc<br />

Uo = phase to neutral voltage<br />

Zc = impedance <strong>of</strong> the circuit fault-current loop (see F3.3)<br />

Ia = current level for trip setting<br />

If no neutral conductor is distributed, then the voltage to use for the fault-current<br />

calculation is the phase-to-phase value, i.e.<br />

calculation is the phase-to-phase value, i.e. 0.8<br />

b Maximum tripping times<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Ω<br />

Id2<br />

3 Uo<br />

2 Zc<br />

(1)<br />

(1) u I a<br />

Id1 + Id2<br />

Disconnecting times for IT system depends on how the different <strong>installation</strong> and<br />

substation earth electrodes are interconnected.<br />

1<br />

2<br />

3<br />

N<br />

PE<br />

For final circuits supplying <strong>electrical</strong> equipment with a rated current not exceeding<br />

32 A and having their exposed-conductive-parts bonded with the substation earth<br />

electrode, the maximum tripping time is given in table F8. For the other circuits<br />

within the same group <strong>of</strong> interconnected exposed-conductive-parts, the maximum<br />

disconnecting time is 5 s. This is due to the fact that any double fault situation within<br />

this group will result in a short-circuit current as in TN system.<br />

For final circuits supplying <strong>electrical</strong> equipment with a rated current not exceeding<br />

32 A and having their exposed-conductive-parts connected to an independent earth<br />

electrode <strong>electrical</strong>ly separated from the substation earth electrode, the maximum<br />

tripping time is given in Figure F13. For the other circuits within the same group <strong>of</strong><br />

non interconnected exposed-conductive-parts, the maximum disconnecting time is<br />

1s. This is due to the fact that any double fault situation resulting from one insulation<br />

fault within this group and another insulation fault from another group will generate a<br />

fault current limited by the different earth electrode resistances as in TT system.<br />

Zf<br />

B<br />

U f<br />

F11<br />

© Schneider Electric - all rights reserved


F12<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

3 Protection against indirect<br />

contact<br />

Fig. F18 : Circuit-breaker tripping on double fault situation when exposed-conductive-parts are<br />

connected to a common protective conductor<br />

b Protection by circuit-breaker<br />

In the case shown in Figure F18, the adjustments <strong>of</strong> instantaneous and short-time<br />

delay overcurrent trip unit must be decided. The times recommended here above can<br />

be readily complied with. The short-circuit protection provided by the NS 160 circuitbreaker<br />

is suitable to clear a phase to phase short-circuit occurring at the load ends<br />

<strong>of</strong> the circuits concerned.<br />

Reminder: In an IT system, the two circuits involved in a phase to phase short-circuit<br />

are assumed to be <strong>of</strong> equal length, with the same cross sectional area conductors,<br />

the PE conductors being the same cross sectional area as the phase conductors. In<br />

such a case, the impedance <strong>of</strong> the circuit loop when using the “conventional method”<br />

(sub clause 6.2) will be twice that calculated for one <strong>of</strong> the circuits in the TN case,<br />

shown in <strong>Chapter</strong> F sub clause 3.3.<br />

L<br />

So that The the resistance resistance <strong>of</strong> <strong>of</strong> circuit 1 loop FGHJ = 22R RJH JH = 2�<br />

in m�<br />

where: where:<br />

a<br />

ρ = resistance <strong>of</strong> copper rod 1 meter long <strong>of</strong> cross sectional area 1 mm2 , in mΩ<br />

L = length <strong>of</strong> the circuit in meters<br />

a = cross sectional area <strong>of</strong> the conductor in mm2 FGHJ = 2 x 22.5 x 50/35 = 64.3 mΩ<br />

and the loop resistance B, C, D, E, F, G, H, J will be 2 x 64.3 = 129 mΩ.<br />

The fault current will therefore be 0.8 x 3 x 230 x 10 3 /129 = 2,470 A.<br />

b Protection by fuses<br />

The current I a for which fuse operation must be assured in a time specified according<br />

to here above can be found from fuse operating curves, as described in figure F15.<br />

The current indicated should be significantly lower than the fault currents calculated<br />

for the circuit concerned.<br />

b Protection by Residual current circuit-breakers (RCCBs)<br />

For low values <strong>of</strong> short-circuit current, RCCBs are necessary. Protection against<br />

indirect contact hazards can be achieved then by using one RCCB for each circuit.<br />

2 nd case<br />

b It concerns exposed conductive parts which are earthed either individually (each part<br />

having its own earth electrode) or in separate groups (one electrode for each group).<br />

If all exposed conductive parts are not bonded to a common electrode system, then<br />

it is possible for the second earth fault to occur in a different group or in a separately<br />

earthed individual apparatus. Additional protection to that described above for<br />

case 1, is required, and consists <strong>of</strong> a RCD placed at the circuit-breaker controlling<br />

each group and each individually-earthed apparatus.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K<br />

A<br />

Id<br />

R A<br />

NS160<br />

160 A<br />

50 m<br />

35 mm2 F<br />

G<br />

J<br />

H<br />

E<br />

D<br />

B<br />

C<br />

1<br />

2<br />

3<br />

N<br />

PE<br />

50 m<br />

35 mm 2


F - Protection against electric shock<br />

Case 1<br />

Rn<br />

RCD<br />

Ω<br />

N<br />

PIM<br />

RA<br />

Fig. F19 : Correspondence between the earth leakage capacitance and the first fault current<br />

Group<br />

earth<br />

Case 2<br />

Fig. F20 : Application <strong>of</strong> RCDs when exposed-conductive-parts are earthed individually or by group on IT system<br />

Extra-low voltage is used where the risks<br />

are great: swimming pools, wandering-lead<br />

hand lamps, and other portable appliances for<br />

outdoor use, etc.<br />

3 Protection against indirect<br />

contact<br />

The reason for this requirement is that the separate-group electrodes are “bonded”<br />

through the earth so that the phase to phase short-circuit current will generally be<br />

limited when passing through the earth bond by the electrode contact resistances<br />

with the earth, thereby making protection by overcurrent devices unreliable. The<br />

more sensitive RCDs are therefore necessary, but the operating current <strong>of</strong> the RCDs<br />

must evidently exceed that which occurs for a first fault (see Fig. F19).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Leakage capacitance First fault current<br />

(µF) (A)<br />

1 0.07<br />

5 0.36<br />

30 2.17<br />

Note: 1 µF is the 1 km typical leakage capacitance for<br />

4-conductor cable.<br />

For a second fault occurring within a group having a common earth-electrode<br />

system, the overcurrent protection operates, as described above for case 1.<br />

Note 1: See also <strong>Chapter</strong> G Sub-clause 7.2, protection <strong>of</strong> the neutral conductor.<br />

Note 2: In 3-phase 4-wire <strong>installation</strong>s, protection against overcurrent in the neutral<br />

conductor is sometimes more conveniently achieved by using a ring-type current<br />

transformer over the single-core neutral conductor (see Fig. F20).<br />

RCD<br />

Ω<br />

N<br />

PIM<br />

Group<br />

earth 1<br />

RCD RCD<br />

Rn RA1 RA2<br />

Group<br />

earth 2<br />

3.5 Measures <strong>of</strong> protection against direct or indirect<br />

contact without automatic disconnection <strong>of</strong> supply<br />

The use <strong>of</strong> SELV (Safety Extra-Low Voltage)<br />

Safety by extra low voltage SELV is used in situations where the operation <strong>of</strong> <strong>electrical</strong><br />

equipment presents a serious hazard (swimming pools, amusement parks, etc.).<br />

This measure depends on supplying power at extra-low voltage from the secondary<br />

windings <strong>of</strong> isolating transformers especially <strong>design</strong>ed according to national or to<br />

international (IEC 60742) standard. The impulse withstand level <strong>of</strong> insulation between<br />

the primary and secondary windings is very high, and/or an earthed metal screen<br />

is sometimes incorporated between the windings. The secondary voltage never<br />

exceeds 50 V rms.<br />

Three conditions <strong>of</strong> exploitation must be respected in order to provide satisfactory<br />

protection against indirect contact:<br />

b No live conductor at SELV must be connected to earth<br />

b Exposed-conductive-parts <strong>of</strong> SELV supplied equipment must not be connected to<br />

earth, to other exposed conductive parts, or to extraneous-conductive-parts<br />

b All live parts <strong>of</strong> SELV circuits and <strong>of</strong> other circuits <strong>of</strong> higher voltage must be<br />

separated by a distance at least equal to that between the primary and secondary<br />

windings <strong>of</strong> a safety isolating transformer.<br />

F13<br />

© Schneider Electric - all rights reserved


F14<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

The <strong>electrical</strong> separation <strong>of</strong> circuits is suitable<br />

for relatively short cable lengths and high levels<br />

<strong>of</strong> insulation resistance. It is preferably used for<br />

an individual appliance<br />

230 V/230 V<br />

Fig. F22 : Safety supply from a class II separation transformer<br />

3 Protection against indirect<br />

contact<br />

These measures require that:<br />

b SELV circuits must use conduits exclusively provided for them, unless cables which<br />

are insulated for the highest voltage <strong>of</strong> the other circuits are used for the SELV circuits<br />

b Socket outlets for the SELV system must not have an earth-pin contact. The<br />

SELV circuit plugs and sockets must be special, so that inadvertent connection to a<br />

different voltage level is not possible.<br />

Note: In normal conditions, when the SELV voltage is less than 25 V, there is no<br />

need to provide protection against direct contact hazards. Particular requirements<br />

are indicated in <strong>Chapter</strong> P, Clause 3: “special locations”.<br />

The use <strong>of</strong> PELV (Protection by Extra Low Voltage) (see Fig. F21)<br />

This system is for general use where low voltage is required, or preferred for safety<br />

reasons, other than in the high-risk locations noted above. The conception is similar<br />

to that <strong>of</strong> the SELV system, but the secondary circuit is earthed at one point.<br />

IEC 60364-4-41 defines precisely the significance <strong>of</strong> the reference PELV. Protection<br />

against direct contact hazards is generally necessary, except when the equipment<br />

is in the zone <strong>of</strong> equipotential bonding, and the nominal voltage does not exceed<br />

25 V rms, and the equipment is used in normally dry locations only, and large-area<br />

contact with the human body is not expected. In all other cases, 6 V rms is the<br />

maximum permitted voltage, where no direct contact protection is provided.<br />

230 V / 24 V<br />

Fig. F21 : Low-voltage supplies from a safety isolating transformer<br />

FELV system (Functional Extra-Low Voltage)<br />

Where, for functional reasons, a voltage <strong>of</strong> 50 V or less is used, but not all <strong>of</strong> the<br />

requirements relating to SELV or PELV are fulfilled, appropriate measures described<br />

in IEC 60364-4-41 must be taken to ensure protection against both direct and<br />

indirect contact hazards, according to the location and use <strong>of</strong> these circuits.<br />

Note: Such conditions may, for example, be encountered when the circuit contains<br />

equipment (such as transformers, relays, remote-control switches, contactors)<br />

insufficiently insulated with respect to circuits at higher voltages.<br />

The <strong>electrical</strong> separation <strong>of</strong> circuits (see Fig. F22)<br />

The principle <strong>of</strong> the <strong>electrical</strong> separation <strong>of</strong> circuits (generally single-phase circuits)<br />

for safety purposes is based on the following rationale.<br />

The two conductors from the unearthed single-phase secondary winding <strong>of</strong> a<br />

separation transformer are insulated from earth.<br />

If a direct contact is made with one conductor, a very small current only will flow into<br />

the person making contact, through the earth and back to the other conductor, via<br />

the inherent capacitance <strong>of</strong> that conductor with respect to earth. Since the conductor<br />

capacitance to earth is very small, the current is generally below the level <strong>of</strong> perception.<br />

As the length <strong>of</strong> circuit cable increases, the direct contact current will progressively<br />

increase to a point where a dangerous electric shock will be experienced.<br />

Even if a short length <strong>of</strong> cable precludes any danger from capacitive current, a low<br />

value <strong>of</strong> insulation resistance with respect to earth can result in danger, since the<br />

current path is then via the person making contact, through the earth and back to the<br />

other conductor through the low conductor-to-earth insulation resistance.<br />

For these reasons, relatively short lengths <strong>of</strong> well insulated cables are essential in<br />

separation systems.<br />

Transformers are specially <strong>design</strong>ed for this duty, with a high degree <strong>of</strong> insulation<br />

between primary and secondary windings, or with equivalent protection, such as an<br />

earthed metal screen between the windings. Construction <strong>of</strong> the transformer is to<br />

class II insulation standards.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

Symbol:<br />

In principle, safety by placing simultaneouslyaccessible<br />

conductive parts out-<strong>of</strong>-reach, or by<br />

interposing obstacles, requires also a nonconducting<br />

floor, and so is not an easily applied<br />

principle<br />

(1) It is recommended in IEC 364-4-41 that the product <strong>of</strong> the<br />

nominal voltage <strong>of</strong> the circuit in volts and length in metres <strong>of</strong><br />

the wiring system should not exceed 100,000, and that the<br />

length <strong>of</strong> the wiring system should not exceed 500 m.<br />

3 Protection against indirect<br />

contact<br />

As indicated before, successful exploitation <strong>of</strong> the principle requires that:<br />

b No conductor or exposed conductive part <strong>of</strong> the secondary circuit must be<br />

connected to earth,<br />

b The length <strong>of</strong> secondary cabling must be limited to avoid large capacitance values (1) ,<br />

b A high insulation-resistance value must be maintained for the cabling and appliances.<br />

These conditions generally limit the application <strong>of</strong> this safety measure to an<br />

individual appliance.<br />

In the case where several appliances are supplied from a separation transformer, it is<br />

necessary to observe the following requirements:<br />

b The exposed conductive parts <strong>of</strong> all appliances must be connected together by an<br />

insulated protective conductor, but not connected to earth,<br />

b The socket outlets must be provided with an earth-pin connection. The earth-pin<br />

connection is used in this case only to ensure the interconnection (bonding) <strong>of</strong> all<br />

exposed conductive parts.<br />

In the case <strong>of</strong> a second fault, overcurrent protection must provide automatic<br />

disconnection in the same conditions as those required for an IT system <strong>of</strong> power<br />

system earthing.<br />

Class II equipment<br />

These appliances are also referred to as having “double insulation” since in class<br />

II appliances a supplementary insulation is added to the basic insulation (see<br />

Fig. F23).<br />

No conductive parts <strong>of</strong> a class II appliance must be connected to a protective conductor:<br />

b Most portable or semi-fixed equipment, certain lamps, and some types <strong>of</strong><br />

transformer are <strong>design</strong>ed to have double insulation. It is important to take particular<br />

care in the exploitation <strong>of</strong> class II equipment and to verify regularly and <strong>of</strong>ten that the<br />

class II standard is maintained (no broken outer envelope, etc.). Electronic devices,<br />

radio and television sets have safety levels equivalent to class II, but are not formally<br />

class II appliances<br />

b Supplementary insulation in an <strong>electrical</strong> <strong>installation</strong>: IEC 60364-4-41(Sub-clause<br />

413-2) and some national standards such as NF C 15-100 (France) describe in<br />

more detail the necessary measures to achieve the supplementary insulation during<br />

<strong>installation</strong> work.<br />

Fig. F23 : Principle <strong>of</strong> class II insulation level<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Active part<br />

Basic insulation<br />

Supplementary insulation<br />

A simple example is that <strong>of</strong> drawing a cable into a PVC conduit. Methods are also<br />

described for distribution switchboards.<br />

b For distribution switchboards and similar equipment, IEC 60439-1 describes a set<br />

<strong>of</strong> requirements, for what is referred to as “total insulation”, equivalent to class II<br />

b Some cables are recognised as being equivalent to class II by many national standards<br />

Out-<strong>of</strong>-arm’s reach or interposition <strong>of</strong> obstacles<br />

By these means, the probability <strong>of</strong> touching a live exposed-conductive-part, while at<br />

the same time touching an extraneous-conductive-part at earth potential, is extremely<br />

low (see Fig. F24 next page). In practice, this measure can only be applied in a dry<br />

location, and is implemented according to the following conditions:<br />

b The floor and the wall <strong>of</strong> the chamber must be non-conducting, i.e. the resistance<br />

to earth at any point must be:<br />

v > 50 kΩ (<strong>installation</strong> voltage y 500 V)<br />

v > 100 kΩ (500 V < <strong>installation</strong> voltage y 1000 V)<br />

Resistance is measured by means <strong>of</strong> “MEGGER” type instruments (hand-operated<br />

generator or battery-operated electronic model) between an electrode placed on the<br />

floor or against the wall, and earth (i.e. the nearest protective earth conductor). The<br />

electrode contact area pressure must be evidently be the same for all tests.<br />

Different instruments suppliers provide electrodes specific to their own product, so<br />

that care should be taken to ensure that the electrodes used are those supplied with<br />

the instrument.<br />

F15<br />

© Schneider Electric - all rights reserved


F1<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

2.5 m<br />

Electrical<br />

apparatus<br />

Fig. F24 : Protection by out-<strong>of</strong> arm’s reach arrangements and the interposition <strong>of</strong> non-conducting obstacles<br />

Earth-free equipotential chambers are<br />

associated with particular <strong>installation</strong>s<br />

(laboratories, etc.) and give rise to a number <strong>of</strong><br />

practical <strong>installation</strong> difficulties<br />

> 2 m<br />

(1) Extraneous conductive parts entering (or leaving) the<br />

equipotential space (such as water pipes, etc.) must be<br />

encased in suitable insulating material and excluded from the<br />

equipotential network, since such parts are likely to be bonded<br />

to protective (earthed) conductors elsewhere in the <strong>installation</strong>.<br />

3 Protection against indirect<br />

contact<br />

b The placing <strong>of</strong> equipment and obstacles must be such that simultaneous contact<br />

with two exposed-conductive-parts or with an exposed conductive-part and an<br />

extraneous-conductive-part by an individual person is not possible.<br />

b No exposed protective conductor must be introduced into the chamber concerned.<br />

b Entrances to the chamber must be arranged so that persons entering are not at<br />

risk, e.g. a person standing on a conducting floor outside the chamber must not be<br />

able to reach through the doorway to touch an exposed-conductive-part, such as a<br />

lighting switch mounted in an industrial-type cast-iron conduit box, for example.<br />

Insulated floor<br />

Electrical<br />

apparatus<br />

Insulated<br />

obstacles<br />

Earth-free equipotential chambers<br />

In this scheme, all exposed-conductive-parts, including the floor (1) are bonded by<br />

suitably large conductors, such that no significant difference <strong>of</strong> potential can exist<br />

between any two points. A failure <strong>of</strong> insulation between a live conductor and the<br />

metal envelope <strong>of</strong> an appliance will result in the whole “cage” being raised to phaseto-earth<br />

voltage, but no fault current will flow. In such conditions, a person entering<br />

the chamber would be at risk (since he/she would be stepping on to a live floor).<br />

Suitable precautions must be taken to protect personnel from this danger (e.g. nonconducting<br />

floor at entrances, etc.). Special protective devices are also necessary to<br />

detect insulation failure, in the absence <strong>of</strong> significant fault current.<br />

M<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

< 2 m<br />

Insulating material<br />

Electrical<br />

apparatus<br />

Conductive<br />

floor<br />

Insulated<br />

walls<br />

Fig. F25 : Equipotential bonding <strong>of</strong> all exposed-conductive-parts simultaneously accessible


F - Protection against electric shock<br />

RCDs are very effective devices to provide<br />

protection against fire risk due to insulation<br />

fault because they can detect leakage current<br />

(ex : 300 mA) wich are too low for the other<br />

protections, but sufficient to cause a fire<br />

Beginning <strong>of</strong> fire<br />

Fig. F26 : Origin <strong>of</strong> fires in buildings<br />

Id


F18<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

4 Protection <strong>of</strong> goods<br />

in case <strong>of</strong> insulation fault<br />

Positioning GFP devices in the <strong>installation</strong><br />

Type / <strong>installation</strong> level Main-distribution Sub-distribution Comments<br />

Source Ground Return<br />

(SGR)<br />

v Used<br />

Residual Sensing (RS)<br />

(SGR)<br />

v b Often used<br />

Zero Sequence<br />

(SGR)<br />

v Possible<br />

v b Rarely used<br />

b Recommended or required<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

A<br />

RCD<br />

Fig. F29 : Distribution circuits<br />

RCD<br />

B<br />

RCD<br />

RA1 RA2<br />

Distant location<br />

5 Implementation <strong>of</strong> the TT system<br />

5.1 Protective measures<br />

Protection against indirect contact<br />

<strong>General</strong> case<br />

Protection against indirect contact is assured by RCDs, the sensitivity IΔn <strong>of</strong> which<br />

50 V<br />

complies with the condition I �n i (1) (1)<br />

RA<br />

The choice <strong>of</strong> sensitivity <strong>of</strong> the residual current device is a function <strong>of</strong> the resistance<br />

RA <strong>of</strong> the earth electrode for the <strong>installation</strong>, and is given in Figure F28.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IΔn Maximum resistance <strong>of</strong> the earth electrode<br />

(50 V) (25 V)<br />

3 A 16 Ω 8 Ω<br />

1 A 50 Ω 25 Ω<br />

500 mA 100 Ω 50 Ω<br />

300 mA 166 Ω 83 Ω<br />

30 mA 1666 Ω 833 Ω<br />

Fig. F28 : The upper limit <strong>of</strong> resistance for an <strong>installation</strong> earthing electrode which must not be<br />

exceeded, for given sensitivity levels <strong>of</strong> RCDs at U L voltage limits <strong>of</strong> 50 V and 25 V<br />

Case <strong>of</strong> distribution circuits (see Fig. F29)<br />

IEC 60364-4-41 and a number <strong>of</strong> national standards recognize a maximum tripping<br />

time <strong>of</strong> 1 second in <strong>installation</strong> distribution circuits (as opposed to final circuits). This<br />

allows a degree <strong>of</strong> selective discrimination to be achieved:<br />

b At level A: RCD time-delayed, e.g. “S” type<br />

b At level B: RCD instantaneous<br />

Case where the exposed conductive parts <strong>of</strong> an appliance, or group <strong>of</strong><br />

appliances, are connected to a separate earth electrode (see Fig. F30)<br />

Protection against indirect contact by a RCD at the circuit-breaker level protecting<br />

each group or separately-earthed individual appliance.<br />

In each case, the sensitivity must be compatible with the resistance <strong>of</strong> the earth<br />

electrode concerned.<br />

High-sensitivity RCDs (see Fig. F31)<br />

Fig. F30 : Separate earth electrode Fig. F31 : Circuit supplying socket-outlets<br />

(1) 25 V for work-site <strong>installation</strong>s, agricultural establishments, etc.<br />

According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for<br />

protection <strong>of</strong> socket outlets with rated current y 20 A in all locations. The use <strong>of</strong> such<br />

RCDs is also recommended in the following cases:<br />

b Socket-outlet circuits in wet locations at all current ratings<br />

b Socket-outlet circuits in temporary <strong>installation</strong>s<br />

b Circuits supplying laundry rooms and swimming pools<br />

b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs<br />

See 2.2 and chapter P, section 3<br />

F19<br />

© Schneider Electric - all rights reserved


F20<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Fig. F32 : Fire-risk location<br />

Fire-risk<br />

location<br />

5 Implementation <strong>of</strong> the TT system<br />

In high fire risk locations (see Fig. F32)<br />

RCD protection at the circuit-breaker controlling all supplies to the area at risk is<br />

necessary in some locations, and mandatory in many countries.<br />

The sensitivity <strong>of</strong> the RCD must be y 500 mA, but a 300 mA sensitivity is<br />

recommended.<br />

Protection when exposed conductive parts are not connected<br />

to earth (see Fig. F33)<br />

(In the case <strong>of</strong> an existing <strong>installation</strong> where the location is dry and provision <strong>of</strong><br />

an earthing connection is not possible, or in the event that a protective earth wire<br />

becomes broken).<br />

RCDs <strong>of</strong> high sensitivity (y 30 mA) will afford both protection against indirect-contact<br />

hazards, and the additional protection against the dangers <strong>of</strong> direct-contact.<br />

Fig. F33 : Unearthed exposed conductive parts (A)<br />

5.2 Coordination <strong>of</strong> residual current protective<br />

devices<br />

Discriminative-tripping coordination is achieved either by time-delay or by subdivision<br />

<strong>of</strong> circuits, which are then protected individually or by groups, or by a combination <strong>of</strong><br />

both methods.<br />

Such discrimination avoids the tripping <strong>of</strong> any RCD, other than that immediately<br />

upstream <strong>of</strong> a fault position:<br />

b With equipment currently available, discrimination is possible at three or four<br />

different levels <strong>of</strong> distribution :<br />

v At the main general distribution board<br />

v At local general distribution boards<br />

v At sub-distribution boards<br />

v At socket outlets for individual appliance protection<br />

b In general, at distribution boards (and sub-distribution boards, if existing) and on<br />

individual-appliance protection, devices for automatic disconnection in the event <strong>of</strong><br />

an indirect-contact hazard occurring are installed together with additional protection<br />

against direct-contact hazards.<br />

Discrimination between RCDs<br />

The general specification for achieving total discrimination between two RCDs is as<br />

follow:<br />

b The ratio between the rated residual operating currents must be > 2<br />

b Time delaying the upstream RCD<br />

Discrimination is achieved by exploiting the several levels <strong>of</strong> standardized sensitivity:<br />

30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown<br />

opposite page in Figure F34.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

10,000<br />

1,000<br />

500<br />

300<br />

250<br />

200<br />

150<br />

130<br />

100<br />

60<br />

40<br />

10<br />

t (ms)<br />

15<br />

30<br />

Fig. F34 : Total discrimination at 2 levels<br />

Fig. F35 : Total discrimination at 2 levels<br />

A<br />

A<br />

60<br />

100<br />

RCD 300 mA<br />

type S<br />

Relay with separate<br />

toroidal CT 3 A<br />

delay time 500 ms<br />

RCD<br />

30 mA<br />

Fig. F36 : Total discrimination at 3 or 4 levels<br />

B<br />

RCCB 1 A<br />

delay time 250 ms<br />

C<br />

150<br />

B<br />

RCCB 300 A<br />

delay time 50 ms<br />

or type S<br />

D<br />

RCCB<br />

30 mA<br />

300<br />

500<br />

600<br />

1,000<br />

5 Implementation <strong>of</strong> the TT system<br />

Discrimination at 2 levels (see Fig. F35)<br />

Protection<br />

b Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic<br />

device) for protection against indirect contacts<br />

b Level B: RCD instantaneous, with high sensitivity on circuits supplying socketoutlets<br />

or appliances at high risk (washing machines, etc.) See also <strong>Chapter</strong> P<br />

Clause 3<br />

Schneider Electric solutions<br />

b Level A: Compact or Multi 9 circuit-breaker with adaptable RCD module<br />

(Vigi NS160 or Vigi NC100), setting I or S type<br />

b Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable<br />

RCD module (e.g. Vigi C60 or Vigi NC100) or Vigicompact<br />

Note: The setting <strong>of</strong> upstream RCCB must comply with selectivity <strong>rules</strong> and take into<br />

account all the downstream earth leakage currents.<br />

Discrimination at 3 or 4 levels (see Fig. F36)<br />

Protection<br />

b Level A: RCD time-delayed (setting III)<br />

b Level B: RCD time-delayed (setting II)<br />

b Level C: RCD time-delayed (setting I) or type S<br />

b Level D: RCD instantaneous<br />

Schneider Electric solutions<br />

b Level A: Circuit-breaker associated with RCD and separate toroidal transformer<br />

(Vigirex RH54A)<br />

b Level B: Vigicompact or Vigirex<br />

b Level C: Vigirex, Vigicompact or Vigi NC100 or Vigi C60<br />

b Level D:<br />

v Vigicompact or<br />

v Vigirex or<br />

v Multi 9 with integrated or adaptable RCD module : Vigi C60 or DPN Vigi<br />

Note: The setting <strong>of</strong> upstream RCCB must comply with selectivity <strong>rules</strong> and take into<br />

account all the downstream earth leakage currents<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Current<br />

(mA)<br />

1 1.5 10 100 500 1,000 (A)<br />

II<br />

I<br />

selective RCDs<br />

domestic S<br />

and industrial<br />

(settings I and II)<br />

RCD 30 mA<br />

general domestic<br />

and industrial setting 0<br />

F21<br />

© Schneider Electric - all rights reserved


F22<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

MV/LV<br />

NC100<br />

diff.<br />

300 mA<br />

selective<br />

S<br />

5 Implementation <strong>of</strong> the TT system<br />

Discriminative protection at three levels (see Fig. F37)<br />

Withdrawable Masterpact<br />

or Visucompact<br />

NC100L MA<br />

intantaneous<br />

300 mA<br />

Vigicompact<br />

NS100<br />

Setting 1<br />

300 mA<br />

Leakage current<br />

<strong>of</strong> the filter: 20 mA Terminal<br />

board<br />

Fig. F37 : Typical 3-level <strong>installation</strong>, showing the protection <strong>of</strong> distribution circuits in a TT-earthed system. One motor is provided with specific protection<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Discont.<br />

Leakage current equal to 3,5 mA per<br />

socket outlet (Information technology<br />

equipement): max 4 sockets outlets.<br />

NS100 MA


F - Protection against electric shock<br />

Three methods <strong>of</strong> calculation are commonly<br />

used:<br />

b The method <strong>of</strong> impedances, based on the<br />

trigonometric addition <strong>of</strong> the system resistances<br />

and inductive reactances<br />

b The method <strong>of</strong> composition<br />

b The conventional method, based on an<br />

assumed voltage drop and the use <strong>of</strong> prepared<br />

tables<br />

6 Implementation <strong>of</strong> the TN system<br />

6.1 Preliminary conditions<br />

At the <strong>design</strong> stage, the maximum permitted lengths <strong>of</strong> cable downstream <strong>of</strong> a<br />

protective circuit-breaker (or set <strong>of</strong> fuses) must be calculated, while during the<br />

<strong>installation</strong> work certain <strong>rules</strong> must be fully respected.<br />

Certain conditions must be observed, as listed below and illustrated in Figure F38.<br />

1. PE conductor must be regularly connected to earth as much as possible.<br />

2. The PE conductor must not pass through ferro-magnetic conduit, ducts, etc. or<br />

be mounted on steel work, since inductive and/or proximity effects can increase the<br />

effective impedance <strong>of</strong> the conductor.<br />

3. In the case <strong>of</strong> a PEN conductor (a neutral conductor which is also used as a<br />

protective conductor), connection must be made directly to the earth terminal <strong>of</strong> an<br />

appliance (see 3 in Figure F38) before being looped to the neutral terminal <strong>of</strong> the<br />

same appliance.<br />

4. Where the conductor y 6 mm 2 for copper or 10 mm 2 for aluminium, or where a<br />

cable is movable, the neutral and protective conductors should be separated (i.e. a<br />

TN-S system should be adopted within the <strong>installation</strong>).<br />

5. Earth faults may be cleared by overcurrent-protection devices, i.e. by fuses and<br />

circuit-breakers.<br />

The foregoing list indicates the conditions to be respected in the implementation <strong>of</strong> a<br />

TN scheme for the protection against indirect contacts.<br />

RpnA<br />

PEN<br />

Notes:<br />

b The TN scheme requires that the LV neutral <strong>of</strong> the MV/LV transformer, the exposed<br />

conductive parts <strong>of</strong> the substation and <strong>of</strong> the <strong>installation</strong>, and the extraneous conductive<br />

parts in the substation and <strong>installation</strong>, all be earthed to a common earthing system.<br />

b For a substation in which the metering is at low-voltage, a means <strong>of</strong> isolation is required at<br />

the origin <strong>of</strong> the LV <strong>installation</strong>, and the isolation must be clearly visible.<br />

b A PEN conductor must never be interrupted under any circumstances. Control and<br />

protective switchgear for the several TN arrangements will be:<br />

v 3-pole when the circuit includes a PEN conductor,<br />

v Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate<br />

PE conductor.<br />

Fig. F38 : Implementation <strong>of</strong> the TN system <strong>of</strong> earthing<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1<br />

5<br />

2 2<br />

3<br />

5<br />

PE N<br />

4<br />

TN-C system TN-C-S system<br />

6.2 Protection against indirect contact<br />

Methods <strong>of</strong> determining levels <strong>of</strong> short-circuit current<br />

In TN-earthed systems, a short-circuit to earth will, in principle, always provide<br />

sufficient current to operate an overcurrent device.<br />

The source and supply mains impedances are much lower than those <strong>of</strong> the<br />

<strong>installation</strong> circuits, so that any restriction in the magnitude <strong>of</strong> earth-fault currents<br />

will be mainly caused by the <strong>installation</strong> conductors (long flexible leads to appliances<br />

greatly increase the “fault-loop” impedance, with a corresponding reduction <strong>of</strong> shortcircuit<br />

current).<br />

The most recent IEC recommendations for indirect-contact protection on TN earthing<br />

systems only relates maximum allowable tripping times to the nominal system<br />

voltage (see Figure F12 in Sub-clause 3.3).<br />

5<br />

F23<br />

© Schneider Electric - all rights reserved


F24<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

For calculations, modern practice is to use<br />

s<strong>of</strong>tware agreed by National Authorities, and<br />

based on the method <strong>of</strong> impedances, such as<br />

Ecodial 3. National Authorities generally also<br />

publish Guides, which include typical values,<br />

conductor lengths, etc.<br />

(1) This results in a calculated current value which is less than<br />

that it would actually flow. If the overcurrent settings are based<br />

on this calculated value, then operation <strong>of</strong> the relay, or fuse, is<br />

assured.<br />

6 Implementation <strong>of</strong> the TN system<br />

The reasoning behind these recommendations is that, for TN systems, the current<br />

which must flow in order to raise the potential <strong>of</strong> an exposed conductive part to 50 V<br />

or more is so high that one <strong>of</strong> two possibilities will occur:<br />

b Either the fault path will blow itself clear, practically instantaneously, or<br />

b The conductor will weld itself into a solid fault and provide adequate current to<br />

operate overcurrent devices<br />

To ensure correct operation <strong>of</strong> overcurrent devices in the latter case, a reasonably<br />

accurate assessment <strong>of</strong> short-circuit earth-fault current levels must be determined at<br />

the <strong>design</strong> stage <strong>of</strong> a project.<br />

A rigorous analysis requires the use <strong>of</strong> phase-sequence-component techniques<br />

applied to every circuit in turn. The principle is straightforward, but the amount <strong>of</strong><br />

computation is not considered justifiable, especially since the zero-phase-sequence<br />

impedances are extremely difficult to determine with any reasonable degree <strong>of</strong><br />

accuracy in an average LV <strong>installation</strong>.<br />

Other simpler methods <strong>of</strong> adequate accuracy are preferred. Three practical methods<br />

are:<br />

b The “method <strong>of</strong> impedances”, based on the summation <strong>of</strong> all the impedances<br />

(positive-phase-sequence only) around the fault loop, for each circuit<br />

b The “method <strong>of</strong> composition”, which is an estimation <strong>of</strong> short-circuit current at<br />

the remote end <strong>of</strong> a loop, when the short-circuit current level at the near end <strong>of</strong> the<br />

loop is known<br />

b The “conventional method” <strong>of</strong> calculating the minimum levels <strong>of</strong> earth-fault<br />

currents, together with the use <strong>of</strong> tables <strong>of</strong> values for obtaining rapid results<br />

These methods are only reliable for the case in which the cables that make up the<br />

earth-fault-current loop are in close proximity (to each other) and not separated by<br />

ferro-magnetic materials.<br />

Method <strong>of</strong> impedances<br />

This method summates the positive-sequence impedances <strong>of</strong> each item (cable, PE<br />

conductor, transformer, etc.) included in the earth-fault loop circuit from which the<br />

short-circuit earth-fault current is calculated, using the formula:<br />

U<br />

I =<br />

2 2<br />

( R) + ( X)<br />

� �<br />

where<br />

(ΣR) 2 = (the sum <strong>of</strong> all resistances in the loop) 2 at the <strong>design</strong> stage <strong>of</strong> a project.<br />

and (ΣX) 2 = (the sum <strong>of</strong> all inductive reactances in the loop) 2<br />

and U = nominal system phase-to-neutral voltage.<br />

The application <strong>of</strong> the method is not always easy, because it supposes a knowledge<br />

<strong>of</strong> all parameter values and characteristics <strong>of</strong> the elements in the loop. In many<br />

cases, a national guide can supply typical values for estimation purposes.<br />

Method <strong>of</strong> composition<br />

This method permits the determination <strong>of</strong> the short-circuit current at the end <strong>of</strong><br />

a loop from the known value <strong>of</strong> short-circuit at the sending end, by means <strong>of</strong> the<br />

approximate formula:<br />

U<br />

I = Isc<br />

U+ Zs. Isc<br />

where<br />

Isc where = upstream short-circuit current<br />

I = end-<strong>of</strong>-loop short-circuit current<br />

U = nominal system phase voltage<br />

Zs = impedance <strong>of</strong> loop<br />

Note: in this method the individual impedances are added arithmetically (1) as<br />

opposed to the previous “method <strong>of</strong> impedances” procedure.<br />

Conventional method<br />

This method is generally considered to be sufficiently accurate to fix the upper limit<br />

<strong>of</strong> cable lengths.<br />

Principle<br />

The principle bases the short-circuit current calculation on the assumption that the<br />

voltage at the origin <strong>of</strong> the circuit concerned (i.e. at the point at which the circuit<br />

protective device is located) remains at 80% or more <strong>of</strong> the nominal phase to neutral<br />

voltage. The 80% value is used, together with the circuit loop impedance, to compute<br />

the short-circuit current.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

The maximum length <strong>of</strong> any circuit <strong>of</strong> a<br />

TN-earthed <strong>installation</strong> is: 0.8 Uo Sph<br />

max =<br />

� 1+ m Ia<br />

( )<br />

The following tables give the length <strong>of</strong> circuit<br />

which must not be exceeded, in order that<br />

persons be protected against indirect contact<br />

hazards by protective devices<br />

Id<br />

A B<br />

SPE Sph<br />

C<br />

Imagn<br />

Fig. F39 : Calculation <strong>of</strong> L max. for a TN-earthed system, using<br />

the conventional method<br />

L<br />

PE<br />

(1) For the definition <strong>of</strong> type B, C, D circuit-breakers, refer to<br />

chapter H, clause 4.2<br />

6 Implementation <strong>of</strong> the TN system<br />

This coefficient takes account <strong>of</strong> all voltage drops upstream <strong>of</strong> the point considered.<br />

In LV cables, when all conductors <strong>of</strong> a 3-phase 4-wire circuit are in close proximity<br />

(which is the normal case), the inductive reactance internal to and between<br />

conductors is negligibly small compared to the cable resistance.<br />

This approximation is considered to be valid for cable sizes up to 120 mm 2 .<br />

Above that size, the resistance value R is increased as follows:<br />

Core size (mm 2 ) Value <strong>of</strong> resistance<br />

S = 150 mm 2 R+15%<br />

S = 185 mm 2 R+20%<br />

S = 240 mm 2 R+25%<br />

The maximum length <strong>of</strong> a circuit in a TN-earthed <strong>installation</strong> is given by the formula:<br />

0.8 Uo Sph<br />

Lmax<br />

=<br />

� 1+ m Ia<br />

( )<br />

where:<br />

Lmax = maximum length in metres<br />

Uo = phase volts = 230 V for a 230/400 V system<br />

ρ = resistivity at normal working temperature in ohm-mm2 /metre<br />

(= 22.5 10-3 for copper; = 36 10-3 for aluminium)<br />

Ia = trip current setting for the instantaneous operation <strong>of</strong> a circuit-breaker, or<br />

Ia = the current which assures operation <strong>of</strong> the protective fuse concerned, in the<br />

specified time.<br />

m Sph<br />

=<br />

SPE<br />

Sph = cross-sectional area <strong>of</strong> the phase conductors <strong>of</strong> the circuit concerned in mm 2<br />

SPE = cross-sectional area <strong>of</strong> the protective conductor concerned in mm 2 .<br />

(see Fig. F39)<br />

Tables<br />

The following tables, applicable to TN systems, have been established according to<br />

the “conventional method” described above.<br />

The tables give maximum circuit lengths, beyond which the ohmic resistance <strong>of</strong> the<br />

conductors will limit the magnitude <strong>of</strong> the short-circuit current to a level below that<br />

required to trip the circuit-breaker (or to blow the fuse) protecting the circuit, with<br />

sufficient rapidity to ensure safety against indirect contact.<br />

Correction factor m<br />

Figure F40 indicates the correction factor to apply to the values given in Figures F41<br />

to F44 next pages, according to the ratio Sph/SPE, the type <strong>of</strong> circuit, and the<br />

conductor materials.<br />

The tables take into account:<br />

b The type <strong>of</strong> protection: circuit-breakers or fuses<br />

b Operating-current settings<br />

b Cross-sectional area <strong>of</strong> phase conductors and protective conductors<br />

b Type <strong>of</strong> system earthing (see Fig. F45 page F27)<br />

b Type <strong>of</strong> circuit-breaker (i.e. B, C or D) (1)<br />

The tables may be used for 230/400 V systems.<br />

Equivalent tables for protection by Compact and Multi 9 circuit-breakers (Merlin<br />

Gerin) are included in the relevant catalogues.<br />

Circuit Conductor m = Sph/SPE (or PEN)<br />

material m = 1 m = 2 m = 3 m = 4<br />

3P + N or P + N Copper 1 0.67 0.50 0.40<br />

Aluminium 0.62 0.42 0.31 0.25<br />

Fig. F40 : Correction factor to apply to the lengths given in tables F40 to F43 for<br />

TN systems<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F25<br />

© Schneider Electric - all rights reserved


F26<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Circuits protected by general purpose circuit-breakers (Fig. F41)<br />

Nominal Instantaneous or short-time-delayed tripping current Im (amperes)<br />

cross-<br />

sectional<br />

area<br />

<strong>of</strong><br />

conductors<br />

mm 2 50 63 80 100 125 160 200 250 320 400 500 560 630 700 800 875 1000 1120 1250 1600 2000 2500 3200 4000 5000 6300 8000 10000 12500<br />

1.5 100 79 63 50 40 31 25 20 16 13 10 9 8 7 6 6 5 4 4<br />

2.5 167 133 104 83 67 52 42 33 26 21 17 15 13 12 10 10 8 7 7 5 4<br />

4 267 212 167 133 107 83 67 53 42 33 27 24 21 19 17 15 13 12 11 8 7 5 4<br />

6 400 317 250 200 160 125 100 80 63 50 40 36 32 29 25 23 20 18 16 13 10 8 6 5 4<br />

10 417 333 267 208 167 133 104 83 67 60 53 48 42 38 33 30 27 21 17 13 10 8 7 5 4<br />

16 427 333 267 213 167 133 107 95 85 76 67 61 53 48 43 33 27 21 17 13 11 8 7 5 4<br />

25 417 333 260 208 167 149 132 119 104 95 83 74 67 52 42 33 26 21 17 13 10 8 7<br />

35 467 365 292 233 208 185 167 146 133 117 104 93 73 58 47 36 29 23 19 15 12 9<br />

50 495 396 317 283 251 226 198 181 158 141 127 99 79 63 49 40 32 25 20 16 13<br />

70 417 370 333 292 267 233 208 187 146 117 93 73 58 47 37 29 23 19<br />

95 452 396 362 317 283 263 198 158 127 99 79 63 50 40 32 25<br />

120 457 400 357 320 250 200 160 125 100 80 63 50 40 32<br />

150 435 388 348 272 217 174 136 109 87 69 54 43 35<br />

185 459 411 321 257 206 161 128 103 82 64 51 41<br />

240 400 320 256 200 160 128 102 80 64 51<br />

Fig. F41 : Maximum circuit lengths (in metres) for different sizes <strong>of</strong> copper conductor and instantaneous-tripping-current settings for general-purpose circuit-breakers<br />

in 230/240 V TN system with m = 1<br />

Circuits protected by Compact (1) or Multi 9 (1) circuit-breakers for industrial or<br />

domestic use (Fig. F42 to Fig. F44)<br />

Sph Rated current (A)<br />

mm 2 1 2 3 4 6 10 16 20 25 32 40 50 63 80 100 125<br />

1.5 1200 600 400 300 200 120 75 60 48 37 30 24 19 15 12 10<br />

2.5 1000 666 500 333 200 125 100 80 62 50 40 32 25 20 16<br />

4 1066 800 533 320 200 160 128 100 80 64 51 40 32 26<br />

6 1200 800 480 300 240 192 150 120 96 76 60 48 38<br />

10 800 500 400 320 250 200 160 127 100 80 64<br />

16 800 640 512 400 320 256 203 160 128 102<br />

25 800 625 500 400 317 250 200 160<br />

35 875 700 560 444 350 280 224<br />

50 760 603 475 380 304<br />

Fig. F42 : Maximum circuit lengths (in meters) for different sizes <strong>of</strong> copper conductor and rated currents for type B (2) circuit-breakers in a 230/240 V single-phase or<br />

three-phase TN system with m = 1<br />

(1) Merlin Gerin products.<br />

(2) For the definition <strong>of</strong> type B and C circuit-breakers refer to<br />

chapter H clause 4.2.<br />

6 Implementation <strong>of</strong> the TN system<br />

Sph Rated current (A)<br />

mm 2 1 2 3 4 6 10 16 20 25 32 40 50 63 80 100 125<br />

1.5 600 300 200 150 100 60 37 30 24 18 15 12 9 7 6 5<br />

2.5 500 333 250 167 100 62 50 40 31 25 20 16 12 10 8<br />

4 533 400 267 160 100 80 64 50 40 32 25 20 16 13<br />

6 600 400 240 150 120 96 75 60 48 38 30 24 19<br />

10 667 400 250 200 160 125 100 80 63 50 40 32<br />

16 640 400 320 256 200 160 128 101 80 64 51<br />

25 625 500 400 312 250 200 159 125 100 80<br />

35 875 700 560 437 350 280 222 175 140 112<br />

50 760 594 475 380 301 237 190 152<br />

Fig. F43 : Maximum circuit lengths (in metres) for different sizes <strong>of</strong> copper conductor and rated currents for type C (2) circuit-breakers in a 230/240 V single-phase or<br />

three-phase TN system with m = 1<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

6 Implementation <strong>of</strong> the TN system<br />

Sph Rated current (A)<br />

mm 2 1 2 3 4 6 10 16 20 25 32 40 50 63 80 100 125<br />

1.5 429 214 143 107 71 43 27 21 17 13 11 9 7 5 4 3<br />

2.5 714 357 238 179 119 71 45 36 29 22 18 14 11 9 7 6<br />

4 571 381 286 190 114 71 80 46 36 29 23 18 14 11 9<br />

6 857 571 429 286 171 107 120 69 54 43 34 27 21 17 14<br />

10 952 714 476 286 179 200 114 89 71 57 45 36 29 23<br />

16 762 457 286 320 183 143 114 91 73 57 46 37<br />

25 714 446 500 286 223 179 143 113 89 71 57<br />

35 625 700 400 313 250 200 159 125 80 100<br />

50 848 543 424 339 271 215 170 136 109<br />

Fig. F44 : Maximum circuit lengths (in metres) for different sizes <strong>of</strong> copper conductor and rated currents for type D (1) circuit-breakers in a 230/240 V single-phase or<br />

three-phase TN system with m = 1<br />

Fig. F45 : Separate earth electrode<br />

RA1 RA2<br />

Fig. F46 : Circuit supplying socket-outlets<br />

Distant location<br />

(1) For the definition <strong>of</strong> type D circuit-breaker refer to chapter H<br />

Sub-clause 4.2.<br />

Example<br />

A 3-phase 4-wire (230/400 V) <strong>installation</strong> is TN-C earthed. A circuit is protected by a<br />

type B circuit-breaker rated at 63 A, and consists <strong>of</strong> an aluminium cored cable with<br />

50 mm 2 phase conductors and a neutral conductor (PEN) <strong>of</strong> 25 mm 2 .<br />

What is the maximum length <strong>of</strong> circuit, below which protection <strong>of</strong> persons against<br />

indirect-contact hazards is assured by the instantaneous magnetic tripping relay <strong>of</strong><br />

the circuit-breaker?<br />

Figure F42 gives, for 50 mm2 and a 63 A type B circuit-breaker, 603 metres, to which<br />

must be applied a factor <strong>of</strong> 0.42 (Figure F40 for m Sph<br />

= = 2).<br />

SPE<br />

The maximum length <strong>of</strong> circuit is therefore:<br />

603 x 0.42 = 253 metres.<br />

Particular case where one or more exposed conductive part(s)<br />

is (are) earthed to a separate earth electrode<br />

Protection must be provided against indirect contact by a RCD at the origin <strong>of</strong> any<br />

circuit supplying an appliance or group <strong>of</strong> appliances, the exposed conductive parts<br />

<strong>of</strong> which are connected to an independent earth electrode.<br />

The sensitivity <strong>of</strong> the RCD must be adapted to the earth electrode resistance (RA2 in<br />

Figure F45). See specifications applicable to TT system.<br />

6.3 High-sensitivity RCDs (see Fig. F31)<br />

According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for<br />

protection <strong>of</strong> socket outlets with rated current y 20 A in all locations. The use <strong>of</strong> such<br />

RCDs is also recommended in the following cases:<br />

b Socket-outlet circuits in wet locations at all current ratings<br />

b Socket-outlet circuits in temporary <strong>installation</strong>s<br />

b Circuits supplying laundry rooms and swimming pools<br />

b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs<br />

See 2.2 and chapter P, al section 3.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F27<br />

© Schneider Electric - all rights reserved


F28<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Fig. F47 : Fire-risk location<br />

2 y Irm y 4In<br />

Great length <strong>of</strong> cable<br />

Fire-risk<br />

location<br />

PE or PEN<br />

Fig. F48 : Circuit-breaker with low-set instantaneous magnetic<br />

tripping<br />

Phases<br />

Neutral<br />

PE<br />

6.4 Protection in high fire-risk location<br />

According to IEC 60364-422-3.10, circuits in high fire-risk locations must be<br />

protected by RCDs <strong>of</strong> sensitivity y 500 mA. This excludes the TN-C arrangement and<br />

TN-S must be adopted.<br />

A preferred sensitivity <strong>of</strong> 300 mA is mandatory in some countries (see Fig. F47).<br />

6.5 When the fault current-loop impedance is<br />

particularly high<br />

When the earth-fault current is limited due to an inevitably high fault-loop impedance,<br />

so that the overcurrent protection cannot be relied upon to trip the circuit within the<br />

prescribed time, the following possibilities should be considered:<br />

Suggestion 1 (see Fig. F48)<br />

b Install a circuit-breaker which has a lower instantaneous magnetic tripping level, for<br />

example:<br />

2In y Irm y 4In<br />

This affords protection for persons on circuits which are abnormally long. It must<br />

be checked, however, that high transient currents such as the starting currents <strong>of</strong><br />

motors will not cause nuisance trip-outs.<br />

b Schneider Electric solutions<br />

v Type G Compact (2Im y Irm y 4Im)<br />

v Type B Multi 9 circuit-breaker<br />

Suggestion 2 (see Fig. F49)<br />

b Install a RCD on the circuit. The device does not need to be highly-sensitive<br />

(HS) (several amps to a few tens <strong>of</strong> amps). Where socket-outlets are involved, the<br />

particular circuits must, in any case, be protected by HS (y 30 mA) RCDs; generally<br />

one RCD for a number <strong>of</strong> socket outlets on a common circuit.<br />

b Schneider Electric solutions<br />

v RCD Multi 9 NG125 : IΔn = 1 or 3 A<br />

v Vigicompact REH or REM: IΔn = 3 to 30 A<br />

v Type B Multi 9 circuit-breaker<br />

Fig. F49 : RCD protection on TN systems with high earth-faultloop<br />

impedance Fig. F50 : Improved equipotential bonding<br />

6 Implementation <strong>of</strong> the TN system<br />

Suggestion 3<br />

Increase the size <strong>of</strong> the PE or PEN conductors and/or the phase conductors, to<br />

reduce the loop impedance.<br />

Suggestion 4<br />

Add supplementary equipotential conductors. This will have a similar effect to that<br />

<strong>of</strong> suggestion 3, i.e. a reduction in the earth-fault-loop resistance, while at the same<br />

time improving the existing touch-voltage protection measures. The effectiveness<br />

<strong>of</strong> this improvement may be checked by a resistance test between each exposed<br />

conductive part and the local main protective conductor.<br />

For TN-C <strong>installation</strong>s, bonding as shown in Figure F50 is not allowed, and<br />

suggestion 3 should be adopted.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

(1) On systems where the neutral is distributed, as shown in<br />

Figure F56.<br />

7 Implementation <strong>of</strong> the IT system<br />

The basic feature <strong>of</strong> the IT earthing system is that, in the event <strong>of</strong> a short-circuit to<br />

earth fault, the system can continue to operate without interruption. Such a fault is<br />

referred to as a “first fault”.<br />

In this system, all exposed conductive parts <strong>of</strong> an <strong>installation</strong> are connected via<br />

PE conductors to an earth electrode at the <strong>installation</strong>, while the neutral point <strong>of</strong> the<br />

supply transformer is:<br />

b Either isolated from earth<br />

b Or connected to earth through a high resistance (commonly 1,000 ohms or more)<br />

This means that the current through an earth fault will be measured in milli-amps,<br />

which will not cause serious damage at the fault position, or give rise to dangerous<br />

touch voltages, or present a fire hazard. The system may therefore be allowed to<br />

operate normally until it is convenient to isolate the faulty section for repair work. This<br />

enhances continuity <strong>of</strong> service.<br />

In practice, the system earthing requires certain specific measures for its satisfactory<br />

exploitation:<br />

b Permanent monitoring <strong>of</strong> the insulation with respect to earth, which must signal<br />

(audibly or visually) the occurrence <strong>of</strong> the first fault<br />

b A device for limiting the voltage which the neutral point <strong>of</strong> the supply transformer<br />

can reach with respect to earth<br />

b A “first-fault” location routine by an efficient maintenance staff. Fault location is<br />

greatly facilitated by automatic devices which are currently available<br />

b Automatic high-speed tripping <strong>of</strong> appropriate circuit-breakers must take place in<br />

the event <strong>of</strong> a “second fault” occurring before the first fault is repaired. The second<br />

fault (by definition) is an earth fault affecting a different live conductor than that <strong>of</strong> the<br />

first fault (can be a phase or neutral conductor) (1) .<br />

The second fault results in a short-circuit through the earth and/or through<br />

PE bonding conductors.<br />

7.1 Preliminary conditions (see Fig. F51 and Fig. F52)<br />

Minimum functions required Components and devices Examples<br />

Protection against overvoltages (1) Voltage limiter Cardew C<br />

at power frequency<br />

Neutral earthing resistor (2) Resistor Impedance Zx<br />

(for impedance earthing variation)<br />

Overall earth-fault monitor (3) Permanent insulation Vigilohm TR22A<br />

with alarm for first fault condition monitor PIM with alarm feature or XM 200<br />

Automatic fault clearance (4) Four-pole circuit-breakers Compact circuit-breaker<br />

on second fault and (if the neutral is distributed) or RCD-MS<br />

protection <strong>of</strong> the neutral all 4 poles trip<br />

conductor against overcurrent<br />

Location <strong>of</strong> first fault (5) With device for fault-location Vigilohm system<br />

on live system, or by successive<br />

opening <strong>of</strong> circuits<br />

Fig. F51 : Essential functions in IT schemes and examples with Merlin Gerin products<br />

HV/LV<br />

2 1 3<br />

Fig. F52 : Positions <strong>of</strong> essential functions in 3-phase 3-wire IT-earthed system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

4<br />

4<br />

5<br />

4<br />

L1<br />

L2<br />

L3 N<br />

F29<br />

© Schneider Electric - all rights reserved


F30<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Modern monitoring systems greatly facilitate<br />

first-fault location and repair<br />

Fault-location systems comply with<br />

IEC 61157-9 standard<br />

MERLIN GERIN<br />

XM100<br />

XM100<br />

(1) On a 230/400 V 3-phase system.<br />

GR10X<br />

Fig. F53 : Non-automatic (manual) fault location<br />

7 Implementation <strong>of</strong> the IT system<br />

7.2 Protection against indirect contact<br />

First-fault condition<br />

The earth-fault current which flows under a first-fault condition is measured in milliamps.<br />

The fault voltage with respect to earth is the product <strong>of</strong> this current and the<br />

resistance <strong>of</strong> the <strong>installation</strong> earth electrode and PE conductor (from the faulted<br />

component to the electrode). This value <strong>of</strong> voltage is clearly harmless and could<br />

amount to several volts only in the worst case (1,000 Ω earthing resistor will pass<br />

230 mA (1) and a poor <strong>installation</strong> earth-electrode <strong>of</strong> 50 ohms, would give 11.5 V, for<br />

example).<br />

An alarm is given by the permanent insulation monitoring device.<br />

Principle <strong>of</strong> earth-fault monitoring<br />

A generator <strong>of</strong> very low frequency a.c. current, or <strong>of</strong> d.c. current, (to reduce the<br />

effects <strong>of</strong> cable capacitance to negligible levels) applies a voltage between the<br />

neutral point <strong>of</strong> the supply transformer and earth. This voltage causes a small current<br />

to flow according to the insulation resistance to earth <strong>of</strong> the whole <strong>installation</strong>, plus<br />

that <strong>of</strong> any connected appliance.<br />

Low-frequency instruments can be used on a.c. systems which generate transient<br />

d.c. components under fault conditions. Certain versions can distinguish between<br />

resistive and capacitive components <strong>of</strong> the leakage current.<br />

Modern equipment allow the measurement <strong>of</strong> leakage-current evolution, so that<br />

prevention <strong>of</strong> a first fault can be achieved.<br />

Examples <strong>of</strong> equipment<br />

b Manual fault-location (see Fig. F53)<br />

The generator may be fixed (example: XM100) or portable (example: GR10X<br />

permitting the checking <strong>of</strong> dead circuits) and the receiver, together with the magnetic<br />

clamp-type pick-up sensor, are portable.<br />

RM10N<br />

P12 P50<br />

P100 ON/OFF<br />

b Fixed automatic fault location (see Fig. F54 next page)<br />

The monitoring relay XM100, together with the fixed detectors XD1 or XD12 (each<br />

connected to a toroidal CT embracing the conductors <strong>of</strong> the circuit concerned)<br />

provide a system <strong>of</strong> automatic fault location on a live <strong>installation</strong>.<br />

Moreover, the level <strong>of</strong> insulation is indicated for each monitored circuit, and two<br />

levels are checked: the first level warns <strong>of</strong> unusually low insulation resistance so that<br />

preventive measures may be taken, while the second level indicates a fault condition<br />

and gives an alarm.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

MERLIN GERIN<br />

XM100<br />

XM100<br />

Fig. F54 : Fixed automatic fault location<br />

MERLIN GERIN<br />

XM100<br />

XD1<br />

XM100<br />

Fig. F55 : Automatic fault location and insulation-resistance data logging<br />

7 Implementation <strong>of</strong> the IT system<br />

XD1 XD1 XD12<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Toroidal CTs<br />

1 to 12 circuits<br />

b Automatic monitoring, logging, and fault location (see Fig. F55)<br />

The Vigilohm System also allows access to a printer and/or a PC which provides<br />

a global review <strong>of</strong> the insulation level <strong>of</strong> an entire <strong>installation</strong>, and records the<br />

chronological evolution <strong>of</strong> the insulation level <strong>of</strong> each circuit.<br />

The central monitor XM100, together with the localization detectors XD08 and XD16,<br />

associated with toroidal CTs from several circuits, as shown below in Figure F55,<br />

provide the means for this automatic exploitation.<br />

MERLIN GERIN<br />

XL08<br />

897<br />

MERLIN GERIN<br />

XD08 XD16<br />

XL16<br />

678<br />

F31<br />

© Schneider Electric - all rights reserved


F32<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Three methods <strong>of</strong> calculation are commonly<br />

used:<br />

b The method <strong>of</strong> impedances, based on the<br />

trigonometric addition <strong>of</strong> the system resistances<br />

and inductive reactances<br />

b The method <strong>of</strong> composition<br />

b The conventional method, based on an<br />

assumed voltage drop and the use <strong>of</strong> prepared<br />

tables<br />

7 Implementation <strong>of</strong> the IT system<br />

Implementation <strong>of</strong> permanent insulation-monitoring (PIM) devices<br />

b Connection<br />

The PIM device is normally connected between the neutral (or articificial neutral)<br />

point <strong>of</strong> the power-supply transformer and its earth electrode.<br />

b Supply<br />

Power supply to the PIM device should be taken from a highly reliable source. In<br />

practice, this is generally directly from the <strong>installation</strong> being monitored, through<br />

overcurrent protective devices <strong>of</strong> suitable short-circuit current rating.<br />

b Level settings<br />

Certain national standards recommend a first setting at 20% below the insulation<br />

level <strong>of</strong> the new <strong>installation</strong>. This value allows the detection <strong>of</strong> a reduction <strong>of</strong> the<br />

insulation quality, necessitating preventive maintenance measures in a situation <strong>of</strong><br />

incipient failure.<br />

The detection level for earth-fault alarm will be set at a much lower level.<br />

By way <strong>of</strong> an example, the two levels might be:<br />

v New <strong>installation</strong> insulation level: 100 kΩ<br />

v Leakage current without danger: 500 mA (fire risk at > 500 mA)<br />

v Indication levels set by the consumer:<br />

- Threshold for preventive maintenance: 0.8 x 100 = 80 kΩ<br />

- Threshold for short-circuit alarm: 500 Ω<br />

Notes:<br />

v Following a long period <strong>of</strong> shutdown, during which the whole, or part <strong>of</strong> the <strong>installation</strong><br />

remains de-energized, humidity can reduce the general level <strong>of</strong> insulation resistance.<br />

This situation, which is mainly due to leakage current over the damp surface <strong>of</strong><br />

healthy insulation, does not constitute a fault condition, and will improve rapidly as the<br />

normal temperature rise <strong>of</strong> current-carrying conductors reduces the surface humidity.<br />

v The PIM device (XM) can measure separately the resistive and the capacitive<br />

current components <strong>of</strong> the leakage current to earth, thereby deriving the true<br />

insulation resistance from the total permanent leakage current.<br />

The case <strong>of</strong> a second fault<br />

A second earth fault on an IT system (unless occurring on the same conductor<br />

as the first fault) constitutes a phase-phase or phase-to-neutral fault, and whether<br />

occurring on the same circuit as the first fault, or on a different circuit, overcurrent<br />

protective devices (fuses or circuit-breakers) would normally operate an automatic<br />

fault clearance.<br />

The settings <strong>of</strong> overcurrent tripping relays and the ratings <strong>of</strong> fuses are the basic<br />

parameters that decide the maximum practical length <strong>of</strong> circuit that can be<br />

satisfactorily protected, as discussed in Sub-clause 6.2.<br />

Note: In normal circumstances, the fault current path is through common<br />

PE conductors, bonding all exposed conductive parts <strong>of</strong> an <strong>installation</strong>, and so the<br />

fault loop impedance is sufficiently low to ensure an adequate level <strong>of</strong> fault current.<br />

Where circuit lengths are unavoidably long, and especially if the appliances <strong>of</strong> a<br />

circuit are earthed separately (so that the fault current passes through two earth<br />

electrodes), reliable tripping on overcurrent may not be possible.<br />

In this case, an RCD is recommended on each circuit <strong>of</strong> the <strong>installation</strong>.<br />

Where an IT system is resistance earthed, however, care must be taken to ensure<br />

that the RCD is not too sensitive, or a first fault may cause an unwanted trip-out.<br />

Tripping <strong>of</strong> residual current devices which satisfy IEC standards may occur at values<br />

<strong>of</strong> 0.5 ΙΔn to ΙΔn, where ΙΔn is the nominal residual-current setting level.<br />

Methods <strong>of</strong> determining levels <strong>of</strong> short-circuit current<br />

A reasonably accurate assessment <strong>of</strong> short-circuit current levels must be carried out<br />

at the <strong>design</strong> stage <strong>of</strong> a project.<br />

A rigorous analysis is not necessary, since current magnitudes only are important for<br />

the protective devices concerned (i.e. phase angles need not be determined) so that<br />

simplified conservatively approximate methods are normally used. Three practical<br />

methods are:<br />

b The method <strong>of</strong> impedances, based on the vectorial summation <strong>of</strong> all the (positivephase-sequence)<br />

impedances around a fault-current loop<br />

b The method <strong>of</strong> composition, which is an approximate estimation <strong>of</strong> short-circuit<br />

current at the remote end <strong>of</strong> a loop, when the level <strong>of</strong> short-circuit current at the near<br />

end <strong>of</strong> the loop is known. Complex impedances are combined arithmetically in this<br />

method<br />

b The conventional method, in which the minimum value <strong>of</strong> voltage at the origin <strong>of</strong><br />

a faulty circuit is assumed to be 80% <strong>of</strong> the nominal circuit voltage, and tables are<br />

used based on this assumption, to give direct readings <strong>of</strong> circuit lengths.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

The s<strong>of</strong>tware Ecodial is based on the “method<br />

<strong>of</strong> impedance”<br />

The maximum length <strong>of</strong> an IT earthed circuit is:<br />

b For a 3-phase 3-wire scheme<br />

0.8 Uo 3 Sph<br />

Lmax<br />

=<br />

2 �I a 1+<br />

m<br />

( )<br />

b For a 3-phase 4-wire scheme<br />

0.8 Uo S1<br />

Lmax<br />

=<br />

2 �I a 1+<br />

m<br />

( )<br />

N<br />

PE<br />

Id<br />

C<br />

D<br />

Non distributed neutral<br />

(1) Reminder: There is no length limit for earth-fault protection<br />

on a TT scheme, since protection is provided by RCDs <strong>of</strong> high<br />

sensitivity.<br />

7 Implementation <strong>of</strong> the IT system<br />

These methods are reliable only for the cases in which wiring and cables which<br />

make up the fault-current loop are in close proximity (to each other) and are not<br />

separated by ferro-magnetic materials.<br />

Methods <strong>of</strong> impedances<br />

This method as described in Sub-clause 6.2, is identical for both the IT and<br />

TN systems <strong>of</strong> earthing.<br />

Methods <strong>of</strong> composition<br />

This method as described in Sub-clause 6.2, is identical for both the IT and<br />

TN systems <strong>of</strong> earthing.<br />

Conventional method (see Fig. F56)<br />

The principle is the same for an IT system as that described in Sub-clause 6.2 for a<br />

TN system : the calculation <strong>of</strong> maximum circuit lengths which should not be exceeded<br />

downstream <strong>of</strong> a circuit-breaker or fuses, to ensure protection by overcurrent devices.<br />

It is clearly impossible to check circuit lengths for every feasible combination <strong>of</strong> two<br />

concurrent faults.<br />

All cases are covered, however, if the overcurrent trip setting is based on the<br />

assumption that a first fault occurs at the remote end <strong>of</strong> the circuit concerned,<br />

while the second fault occurs at the remote end <strong>of</strong> an identical circuit, as already<br />

mentioned in Sub-clause 3.4. This may result, in general, in one trip-out only<br />

occurring (on the circuit with the lower trip-setting level), thereby leaving the system<br />

in a first-fault situation, but with one faulty circuit switched out <strong>of</strong> service.<br />

b For the case <strong>of</strong> a 3-phase 3-wire <strong>installation</strong> the second fault can only cause a<br />

phase/phase short-circuit, so that the voltage to use in the formula for maximum<br />

circuit length is 3 Uo.<br />

The maximum circuit length is given by:<br />

0.8 Uo 3 Sph<br />

Lmax<br />

=<br />

metres<br />

2 �I a 1+<br />

m<br />

( )<br />

b For the case <strong>of</strong> a 3-phase 4-wire <strong>installation</strong> the lowest value <strong>of</strong> fault current will<br />

occur if one <strong>of</strong> the faults is on a neutral conductor. In this case, Uo is the value to use<br />

for computing the maximum cable length, and<br />

0.8 Uo S1<br />

Lmax<br />

=<br />

2 �I a 1+<br />

m<br />

( )<br />

metres<br />

i.e. 50% only <strong>of</strong> the length permitted for a TN scheme (1)<br />

Fig. F56 : Calculation <strong>of</strong> Lmax. for an IT-earthed system, showing fault-current path for a double-fault condition<br />

Id<br />

A<br />

B<br />

N<br />

PE<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Id<br />

Id<br />

Distributed neutral<br />

F33<br />

© Schneider Electric - all rights reserved


F34<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

The following tables (1) give the length <strong>of</strong> circuit<br />

which must not be exceeded, in order that<br />

persons be protected against indirect contact<br />

hazards by protective devices<br />

Fig. F62 : Circuit supplying socket-outlets<br />

(1) The tables are those shown in Sub-clause 6.2 (Figures<br />

F41 to F44). However, the table <strong>of</strong> correction factors (Figure<br />

F57) which takes into account the ratio Sph/SPE, and <strong>of</strong> the<br />

type <strong>of</strong> circuit (3-ph 3-wire; 3-ph 4-wire; 1-ph 2-wire) as well<br />

as conductor material, is specific to the IT system, and differs<br />

from that for TN.<br />

7 Implementation <strong>of</strong> the IT system<br />

In the preceding formulae:<br />

Lmax = longest circuit in metres<br />

Uo = phase-to-neutral voltage (230 V on a 230/400 V system)<br />

ρ = resistivity at normal operating temperature (22.5 x 10-3 ohms-mm2 /m for copper,<br />

36 x 10-3 ohms-mm2 /m for aluminium)<br />

Ia = overcurrent trip-setting level in amps, or Ia = current in amps required to clear<br />

the fuse in the specified time<br />

m Sph<br />

=<br />

SPE<br />

SPE = cross-sectional area <strong>of</strong> PE conductor in mm 2<br />

S1 = S neutral if the circuit includes a neutral conductor<br />

S1 = Sph if the circuit does not include a neutral conductor<br />

Tables<br />

The following tables have been established according to the “conventional method”<br />

described above.<br />

The tables give maximum circuit lengths, beyond which the ohmic resistance <strong>of</strong><br />

the conductors will limit the magnitude <strong>of</strong> the short-circuit current to a level below<br />

that required to trip the circuit-breaker (or to blow the fuse) protecting the circuit,<br />

with sufficient rapidity to ensure safety against indirect contact. The tables take into<br />

account:<br />

b The type <strong>of</strong> protection: circuit-breakers or fuses, operating-current settings<br />

b Cross-sectional area <strong>of</strong> phase conductors and protective conductors<br />

b Type <strong>of</strong> earthing scheme<br />

b Correction factor: Figure F57 indicates the correction factor to apply to the lengths<br />

given in tables F40 to F43, when considering an IT system<br />

Circuit Conductor m = Sph/SPE (or PEN)<br />

material m = 1 m = 2 m = 3 m = 4<br />

3 phases Copper 0.86 0.57 0.43 0.34<br />

Aluminium 0.54 0.36 0.27 0.21<br />

3ph + N or 1ph + N Copper 0.50 0.33 0.25 0.20<br />

Aluminium 0.31 0.21 0.16 0.12<br />

Fig. F57 : Correction factor to apply to the lengths given in tables F41 to F44 for TN systems<br />

Example<br />

A 3-phase 3-wire 230/400 V <strong>installation</strong> is IT-earthed.<br />

One <strong>of</strong> its circuits is protected by a circuit-breaker rated at 63 A, and consists <strong>of</strong> an<br />

aluminium-cored cable with 50 mm 2 phase conductors. The 25 mm 2 PE conductor<br />

is also aluminum. What is the maximum length <strong>of</strong> circuit, below which protection <strong>of</strong><br />

persons against indirect-contact hazards is assured by the instantaneous magnetic<br />

tripping relay <strong>of</strong> the circuit-breaker?<br />

Figure F42 indicates 603 metres, to which must be applied a correction factor <strong>of</strong> 0.36<br />

(m = 2 for aluminium cable).<br />

The maximum length is therefore 217 metres.<br />

7.3 High-sensitivity RCDs<br />

According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for<br />

protection <strong>of</strong> socket outlets with rated current y 20 A in all locations. The use <strong>of</strong> such<br />

RCDs is also recommended in the following cases:<br />

b Socket-outlet circuits in wet locations at all current ratings<br />

b Socket-outlet circuits in temporary <strong>installation</strong>s<br />

b Circuits supplying laundry rooms and swimming pools<br />

b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs<br />

See 2.2 and chapter P, al section 3<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

Fig. F59 : Fire-risk location<br />

2 y I rm y 4I n<br />

Great length <strong>of</strong> cable<br />

PE<br />

Fig. F60 : A circuit-breaker with low-set instantaneous<br />

magnetic trip<br />

Fire-risk<br />

location<br />

Phases<br />

Neutral<br />

PE<br />

7 Implementation <strong>of</strong> the IT system<br />

7.4 Protection in high fire-risk locations<br />

Protection by a RCD <strong>of</strong> sensitivity y 500 mA at the origin <strong>of</strong> the circuit supplying the<br />

fire-risk locations is mandatory in some countries (see Fig. F59).<br />

A preferred sensitivity <strong>of</strong> 300 mA may be adopted.<br />

7.5 When the fault current-loop impedance is<br />

particularly high<br />

When the earth-fault current is restricted due to an inevitably high fault-loop<br />

impedance, so that the overcurrent protection cannot be relied upon to trip the circuit<br />

within the prescribed time, the following possibilities should be considered:<br />

Suggestion 1 (see Fig. F60)<br />

b Install a circuit-breaker which has an instantaneous magnetic tripping element with<br />

an operation level which is lower than the usual setting, for example:<br />

2In y Irm y 4In<br />

This affords protection for persons on circuits which are abnormally long. It must<br />

be checked, however, that high transient currents such as the starting currents <strong>of</strong><br />

motors will not cause nuisance trip-outs.<br />

b Schneider Electric solutions<br />

v Type G Compact (2Im y Irm y 4Im)<br />

v Type B Multi 9 circuit-breaker<br />

Suggestion 2 (see Fig. F61)<br />

Install a RCD on the circuit. The device does not need to be highly-sensitive (HS)<br />

(several amps to a few tens <strong>of</strong> amps). Where socket-outlets are involved, the<br />

particular circuits must, in any case, be protected by HS (y 30 mA) RCDs; generally<br />

one RCD for a number <strong>of</strong> socket outlets on a common circuit.<br />

b Schneider Electric solutions<br />

v RCD Multi 9 NG125 : ΙΔn = 1 or 3 A<br />

v Vigicompact REH or REM: ΙΔn = 3 to 30 A<br />

Fig. F61 : RCD protection Fig. F62 : Improved equipotential bonding<br />

Suggestion 3<br />

Increase the size <strong>of</strong> the PE conductors and/or the phase conductors, to reduce the<br />

loop impedance.<br />

Suggestion 4 (see Fig. F62)<br />

Add supplementary equipotential conductors. This will have a similar effect to that<br />

<strong>of</strong> suggestion 3, i.e. a reduction in the earth-fault-loop resistance, while at the same<br />

time improving the existing touch-voltage protection measures. The effectiveness<br />

<strong>of</strong> this improvement may be checked by a resistance test between each exposed<br />

conductive part and the local main protective conductor.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F35<br />

© Schneider Electric - all rights reserved


F36<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

Industrial circuit-breakers with an integrated<br />

RCD are covered in IEC 60947-2 and its<br />

appendix B<br />

Household or domestic circuit-breakers with<br />

an integrated RCD are covered in IEC 60898,<br />

IEC 61008 and IEC 61009<br />

8 Residual current devices (RCDs)<br />

8.1 Types <strong>of</strong> RCDs<br />

Residual current devices (RCD) are commonly incorporated in or associated with the<br />

following components:<br />

b Industrial-type moulded-case circuit-breakers (MCCB) conforming to IEC 60947-2<br />

and its appendix B and M<br />

b Industrial type miniature circuit-breakers (MCB) conforming to IEC 60947-2 and its<br />

appendix B and M<br />

b Household and similar miniature circuit-breakers (MCB) complying with IEC 60898,<br />

IEC 61008, IEC 61009<br />

b Residual load switch conforming to particular national standards<br />

b Relays with separate toroidal (ring-type) current transformers, conforming to<br />

IEC 60947-2 Appendix M<br />

RCDs are mandatorily used at the origin <strong>of</strong> TT-earthed <strong>installation</strong>s, where their<br />

ability to discriminate with other RCDs allows selective tripping, thereby ensuring the<br />

level <strong>of</strong> service continuity required.<br />

Industrial type circuit-breakers with integrated or adaptable<br />

RCD module (see Fig. F63)<br />

Industrial type circuit-breaker<br />

Vigi Compact<br />

Fig. F63 : Industrial-type CB with RCD module<br />

Fig. F64 : Domestic residual current circuit-breakers<br />

(RCCBs) for earth leakage protection<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Multi 9 DIN-rail industrial<br />

Circuit-breaker with adaptable Vigi RCD module<br />

Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g.<br />

Compact or Multi 9), are available, to which may be associated an auxiliary RCD<br />

module (e.g. Vigi).<br />

The ensemble provides a comprehensive range <strong>of</strong> protective functions (isolation,<br />

protection against short-circuit, overload, and earth-fault.<br />

Household and similar miniature circuit-breakers with RCD<br />

(see Fig. F64)<br />

The incoming-supply circuitbreaker<br />

can also have timedelayed<br />

characteristics and<br />

integrate a RCD (type S).<br />

“Monobloc” Déclic Vigi residual current circuit-breakers<br />

intended for protection <strong>of</strong> terminal socket-outlet circuits<br />

in domestic and tertiary sector applications.


F - Protection against electric shock<br />

Residual current load break switches are<br />

covered by particular national standards.<br />

RCDs with separate toroidal current<br />

transformers are standardized in IEC 60947-2<br />

appendix M<br />

I1 I2<br />

Fig. F66 : The principle <strong>of</strong> RCD operation<br />

I3<br />

8 Residual current devices (RCDs)<br />

Residual current circuit-breakers and RCDs with separate<br />

toroidal current transformer (see Fig. F65)<br />

RCDs with separate toroidal CTs can be used in association with circuit-breakers or<br />

contactors.<br />

Fig. F65 : RCDs with separate toroidal current transformers<br />

8.2 Description<br />

Principle<br />

The essential features are shown schematically in Figure F66 below.<br />

A magnetic core encompasses all the current-carrying conductors <strong>of</strong> an electric<br />

circuit and the magnetic flux generated in the core will depend at every instant on<br />

the arithmetical sum <strong>of</strong> the currents; the currents passing in one direction being<br />

considered as positive (Ι1), while those passing in the opposite direction will be<br />

negative (Ι2).<br />

In a normally healthy circuit Ι1 + Ι2 = 0 and there will be no flux in the magnetic core,<br />

and zero e.m.f. in its coil.<br />

An earth-fault current Ιd will pass through the core to the fault, but will return to the<br />

source via the earth, or via protective conductors in a TN-earthed system.<br />

The current balance in the conductors passing through the magnetic core therefore<br />

no longer exists, and the difference gives rise to a magnetic flux in the core.<br />

The difference current is known as the “residual” current and the principle is referred<br />

to as the “residual current” principle.<br />

The resultant alternating flux in the core induces an e.m.f. in its coil, so that a current<br />

I3 flows in the tripping-device operating coil. If the residual current exceeds the value<br />

required to operate the tripping device either directly or via an electronic relay, then<br />

the associated circuit-breaker will trip.<br />

8.3 Sensitivity <strong>of</strong> RDCs to disturbances<br />

In certain cases, aspects <strong>of</strong> the environment can disturb the correct operation <strong>of</strong><br />

RCDs:<br />

b “nuisance” tripping: Break in power supply without the situation being really<br />

hazardous. This type <strong>of</strong> tripping is <strong>of</strong>ten repetitive, causing major inconvenience and<br />

detrimental to the quality <strong>of</strong> the user's <strong>electrical</strong> power supply.<br />

b non-tripping, in the event <strong>of</strong> a hazard. Less perceptible than nuisance tripping,<br />

these malfunctions must still be examined carefully since they undermine user safety.<br />

This is why international standards define 3 categories <strong>of</strong> RCDs according to their<br />

immunity to this type <strong>of</strong> disturbance (see below).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F37<br />

© Schneider Electric - all rights reserved


F38<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

100%<br />

90%<br />

10%<br />

60%<br />

Umax<br />

0.5U<br />

U<br />

1.2 s 50 s<br />

Fig. F68 : Standardized 1.2/50 µs voltage transient wave<br />

1<br />

0.9<br />

0.5<br />

0.1<br />

I<br />

I<br />

ca.0.5 s<br />

10 s (f = 100 kHz)<br />

Fig. F67 : Standardized 0.5 µs/100 kHz current transient wave<br />

Fig. F69 : Standardized current-impulse wave 8/20 µs<br />

t<br />

t<br />

t<br />

8 Residual current devices (RCDs)<br />

Main disturbance types<br />

Permanent earth leakage currents<br />

Every LV <strong>installation</strong> has a permanent leakage current to earth, which is either due<br />

to:<br />

b Unbalance <strong>of</strong> the intrinsic capacitance between live conductors and earth for threephase<br />

circuits or<br />

b Capacitance between live conductors and earth for single-phase circuits<br />

The larger the <strong>installation</strong> the greater its capacitance with consequently increased<br />

leakage current.<br />

The capacitive current to earth is sometimes increased significantly by filtering<br />

capacitors associated with electronic equipment (automation, IT and computerbased<br />

systems, etc.).<br />

In the absence <strong>of</strong> more precise data, permanent leakage current in a given<br />

<strong>installation</strong> can be estimated from the following values, measured at 230 V 50 Hz:<br />

Single-phase or three-phase line: 1.5 mA /100m<br />

b Heating floor: 1mA / kW<br />

b Fax terminal, printer: 1 mA<br />

b Microcomputer, workstation: 2 mA<br />

b Copy machine: 1.5 mA<br />

Since RCDs complying with IEC and many national standards may operate under,<br />

the limitation <strong>of</strong> permanent leakage current to 0.25 IΔn, by sub-division <strong>of</strong> circuits<br />

will, in practice, eliminate any unwanted tripping.<br />

For very particular cases, such as the extension, or partial renovation <strong>of</strong> extended<br />

IT-earthed <strong>installation</strong>s, the manufacturers must be consulted.<br />

High frequency components (harmonics, transients, etc.), are found in computer<br />

equipment power supplies, converters, motors with speed regulators, fluorescent<br />

lighting systems and in the vicinity <strong>of</strong> high power switching devices and reactive<br />

energy compensation banks.<br />

Part <strong>of</strong> these high frequency currents may flow to earth through parasite<br />

capacitances (line, units, etc.). Although not hazardous for the user, these currents<br />

can still cause the tripping <strong>of</strong> differential devices.<br />

Energization<br />

The initial energization <strong>of</strong> the capacitances mentioned above gives rise to high<br />

frequency transient currents <strong>of</strong> very short duration, similar to that shown in<br />

Figure F67.<br />

The sudden occurrence <strong>of</strong> a first-fault on an IT-earthed system also causes transient<br />

earth-leakage currents at high frequency, due to the sudden rise <strong>of</strong> the two healthy<br />

phases to phase/phase voltage above earth.<br />

Common mode overvoltages<br />

Electrical networks are subjected to overvoltages due to lightning strikes or to abrupt<br />

changes <strong>of</strong> system operating conditions (faults, fuse operation, switching, etc.).<br />

These sudden changes <strong>of</strong>ten cause large transient voltages and currents in inductive<br />

and capacitive circuits. Records have established that, on LV systems, overvoltages<br />

remain generally below 6 kV, and that they can be adequately represented by the<br />

conventional 1.2/50 μs impulse wave (see Fig. F68).<br />

These overvoltages give rise to transient currents represented by a current impulse<br />

wave <strong>of</strong> the conventional 8/20 μs form, having a peak value <strong>of</strong> several tens <strong>of</strong><br />

amperes (see Fig. F69).<br />

The transient currents flow to earth via the capacitances <strong>of</strong> the <strong>installation</strong>.<br />

Non-sinusoidal fault currents<br />

An RCD must be selected taking into account the type <strong>of</strong> supplied load. This applies<br />

in particular to semiconductor-based devices for which fault currents are not always<br />

sinusoidal.<br />

Type AC, A, B<br />

Standard IEC 60755 (<strong>General</strong> requirements for residual current operated protective<br />

devices) defines three types <strong>of</strong> RCD depending on the characteristics <strong>of</strong> the fault<br />

current:<br />

b Type AC<br />

RCD for which tripping is ensured for residual sinusoidal alternating currents.<br />

b Type A<br />

RCD for which tripping is ensured:<br />

v for residual sinusoidal alternating currents,<br />

v for residual pulsating direct currents,<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


F - Protection against electric shock<br />

8 Residual current devices (RCDs)<br />

b Type B<br />

RCD for which tripping is ensured:<br />

v as for type A,<br />

v for pure direct residual currents which may result from three-phase rectifying<br />

circuits.<br />

Cold: in the cases <strong>of</strong> temperatures under - 5 °C, very high sensitivity<br />

electromechanical relays in the RCD may be “welded” by the condensation – freezing<br />

action.<br />

Type “Si” devices can operate under temperatures down to - 25 °C.<br />

Atmospheres with high concentrations <strong>of</strong> chemicals or dust: the special alloys<br />

used to make the RCDs can be notably damaged by corrosion. Dust can also block<br />

the movement <strong>of</strong> mechanical parts.<br />

See the measures to be taken according to the levels <strong>of</strong> severity defined by<br />

standards in Fig. F70.<br />

Regulations define the choice <strong>of</strong> earth leakage protection and its implementation.<br />

The main reference texts are as follows:<br />

b Standard IEC 60364-3:<br />

v This gives a classification (AFx) for external influences in the presence <strong>of</strong> corrosive<br />

or polluting substances.<br />

v It defines the choice <strong>of</strong> materials to be used according to extreme influences.<br />

Disturbed<br />

network<br />

Influence <strong>of</strong><br />

the <strong>electrical</strong><br />

network<br />

Clean network<br />

Superimmunized<br />

residual current<br />

protections<br />

Type A if: k<br />

Standard<br />

immunized<br />

residual current<br />

protections<br />

Type AC<br />

Fig. F70 : External influence classification according to IEC 60364-3 standard<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

SiE k<br />

residual current<br />

protections<br />

SiE k<br />

residual current<br />

protections<br />

+<br />

Appropriate<br />

additional<br />

protection<br />

(sealed cabinet<br />

or unit)<br />

AF1 AF2 AF3 AF4<br />

b External<br />

influences:<br />

negligible,<br />

b Equipment<br />

characteristics:<br />

normal.<br />

b External<br />

influences:<br />

presence<br />

<strong>of</strong> corrosive<br />

or polluting<br />

atmospheric<br />

agents,<br />

b Equipment<br />

characteristics:<br />

e.g. conformity<br />

with salt mist<br />

or atmospheric<br />

pollution tests.<br />

b External<br />

influences:<br />

intermittent<br />

or accidental<br />

action <strong>of</strong><br />

certain<br />

common<br />

chemicals,<br />

b Equipment<br />

characteristics:<br />

corrosion<br />

protection.<br />

Examples <strong>of</strong> exposed sites External influences<br />

SiE k<br />

residual current<br />

protections<br />

+<br />

Appropriate<br />

additional<br />

protection<br />

(sealed cabinet<br />

or unit +<br />

overpressure)<br />

b External<br />

influences:<br />

permanent<br />

action <strong>of</strong><br />

corrosive<br />

or polluting<br />

chemicals<br />

b Equipment<br />

characteristics:<br />

specifically<br />

studied<br />

according to<br />

the type <strong>of</strong><br />

products.<br />

Iron and steel works. Presence <strong>of</strong> sulfur, sulfur vapor, hydrogen<br />

sulfide.<br />

Marinas, trading ports, boats, sea edges, naval<br />

shipyards.<br />

Salt atmospheres, humid outside, low<br />

temperatures.<br />

Swimming pools, hospitals, food & beverage. Chlorinated compounds.<br />

Petrochemicals. Hydrogen, combustion gases, nitrogen<br />

oxides.<br />

Breeding facilities, tips. Hydrogen sulfide.<br />

F39<br />

© Schneider Electric - all rights reserved


F40<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

8 Residual current devices (RCDs)<br />

Immunity level for Merlin Gerin residual current devices<br />

The Merlin Gerin range comprises various types <strong>of</strong> RCDs allowing earth leakage<br />

protection to be adapted to each application. The table below indicates the choices to<br />

be made according to the type <strong>of</strong> probable disturbances at the point <strong>of</strong> <strong>installation</strong>.<br />

Device type Nuisance<br />

trippings<br />

High<br />

frequency<br />

leakage<br />

current<br />

AC b<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Non-trippings<br />

Fault current Low<br />

Rectified<br />

alternating<br />

Pure direct<br />

temperatures<br />

(down to<br />

- 25 °C)<br />

A b b b<br />

SI b b b b b<br />

Corrosion<br />

Dust<br />

SiE b b b b b b<br />

B b b b b b b<br />

Fig. F71 : Immunity level <strong>of</strong> Merlin Gerin RCDs<br />

Immunity to nuisance tripping<br />

Type Si/SiE RCDs have been <strong>design</strong>ed to avoid nuisance tripping or non-tripping in<br />

case <strong>of</strong> polluted network , lightning effect, high frequency currents, RF waves, etc.<br />

Figure F72 below indicates the levels <strong>of</strong> tests undergone by this type <strong>of</strong> RCDs.<br />

Disturbance type Rated test wave Immunity<br />

Continuous disturbances<br />

Multi9 :<br />

ID-RCCB, DPN Vigi, Vigi C60, Vigi<br />

C120, Vigi NG125<br />

SI / SiE type<br />

Harmonics 1 kHz Earth leakage current = 8 x I∆n<br />

Transient disturbances<br />

Lightning induced overvoltage 1.2 / 50 μs pulse<br />

(IEC/EN 61000-4-5)<br />

Lightning induced current 8 / 20 μs pulse<br />

(IEC/EN 61008)<br />

Switching transient, indirect<br />

lightning currents<br />

Downstream surge arrester<br />

operation, capacitance loading<br />

Electromagnetic compatibility<br />

Inductive load switchings<br />

fluorescent lights, motors, etc.)<br />

Fluorescent lights, thyristor<br />

controlled circuits, etc.<br />

RF waves (TV&<br />

radio, broadcact,<br />

telecommunications,etc.)<br />

0.5 μs / 100 kHz<br />

“ ring wave ”<br />

(IEC/EN 61008)<br />

4.5 kV between conductors 5.5 kV /<br />

earth<br />

5 kA peak<br />

400 A peak<br />

10 ms pulse 500 A<br />

Repeated bursts<br />

(IEC 61000-4-4)<br />

RF conducted<br />

waves<br />

(IEC 61000-4-6)<br />

RF radiated waves<br />

80 MHz to 1 GHz<br />

(IEC 61000-4-3)<br />

4 kV / 400 kHz<br />

66 mA (15 kHz to 150 kHz)<br />

30 V (150 kHz to 230 MHz)<br />

30 V / m<br />

Fig. F72 : Immunity to nuisance tripping tests undergone by Merlin Gerin RCDs


F - Protection against electric shock<br />

8 Residual current devices (RCDs)<br />

Recommendations concerning the <strong>installation</strong> <strong>of</strong> RCDs with<br />

separate toroidal current transformers<br />

The detector <strong>of</strong> residual current is a closed magnetic circuit (usually circular) <strong>of</strong><br />

very high magnetic permeability, on which is wound a coil <strong>of</strong> wire, the ensemble<br />

constituting a toroidal (or ring-type) current transformer.<br />

Because <strong>of</strong> its high permeability, any small deviation from perfect symmetry <strong>of</strong><br />

the conductors encompassed by the core, and the proximity <strong>of</strong> ferrous material<br />

(steel enclosure, chassis members, etc.) can affect the balance <strong>of</strong> magnetic forces<br />

sufficiently, at times <strong>of</strong> large load currents (motor-starting current, transformer<br />

energizing current surge, etc.) to cause unwanted tripping <strong>of</strong> the RCD.<br />

Unless particular measures are taken, the ratio <strong>of</strong> operating current Ι∆n to maximum<br />

phase current Ιph (max.) is generally less than 1/1,000.<br />

This limit can be increased substantially (i.e. the response can be desensitized) by<br />

adopting the measures shown in Figure F73 , and summarized in Figure F74.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L = twice the diameter <strong>of</strong><br />

the magnetic ring core<br />

Fig. F73 : Three measures to reduce the ratio Ι∆n/Ιph (max.)<br />

Measures Diameter Sensitivity<br />

(mm) diminution factor<br />

Careful centralizing <strong>of</strong> cables through the ring core 3<br />

Oversizing <strong>of</strong> the ring core ø 50 → ø 100 2<br />

ø 80 → ø 200 2<br />

ø 120 → ø 300 6<br />

Use <strong>of</strong> a steel or s<strong>of</strong>t-iron shielding sleeve ø 50 4<br />

b Of wall thickness 0.5 mm ø 80 3<br />

b Of length 2 x inside diameter <strong>of</strong> ring core ø 120 3<br />

b Completely surrounding the conductors and ø 200 2<br />

overlapping the circular core equally at both ends<br />

These measures can be combined. By carefully centralizing the cables in a ring core<br />

<strong>of</strong> 200 mm diameter, where a 50 mm core would be large enough, and using a sleeve,<br />

the ratio 1/1,000 could become 1/30,000.<br />

Fig. F74 : Means <strong>of</strong> reducing the ratio IΔn/Iph (max.)<br />

L<br />

F41<br />

© Schneider Electric - all rights reserved


F42<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

a b<br />

In<br />

In1<br />

Fig. F75 : Residual current circuit-breakers (RCCBs)<br />

In<br />

In1 In2 In3 In4<br />

Choice <strong>of</strong> characteristics <strong>of</strong> a residual-current circuit-breaker<br />

(RCCB - IEC 61008)<br />

Rated current<br />

The rated current <strong>of</strong> a RCCB is chosen according to the maximum sustained load<br />

current it will carry.<br />

b If the RCCB is connected in series with, and downstream <strong>of</strong> a circuit-breaker, the<br />

rated current <strong>of</strong> both items will be the same, i.e. Ιn u Ιn1 (1) (see Fig. F75a)<br />

b If the RCCB is located upstream <strong>of</strong> a group <strong>of</strong> circuits, protected by circuitbreakers,<br />

as shown in Figure F75b, then the RCCB rated current will be given by:<br />

Ιn u ku x ks (Ιn1 + Ιn2 + Ιn3 + Ιn4)<br />

Circuit-breaker and RCCB association – maxi Ιsc (r.m.s) value in kA<br />

Electrodynamic withstand requirements<br />

Protection against short-circuits must be provided by an upstream SCPD (Short-<br />

Circuit Protective Device) but it is considered that where the RCCB is located in the<br />

same distribution box (complying with the appropriate standards) as the downstream<br />

circuit-breakers (or fuses), the short-circuit protection afforded by these (outgoingcircuit)<br />

SCPDs is an adequate alternative. Coordination between the RCCB and the<br />

SCPDs is necessary, and manufacturers generally provide tables associating RCCBs<br />

and circuit-breakers or fuses (see Fig. F76).<br />

Upstream circuit-breaker DT40 DT40N C60N C60H C60L C120N C120H NG125N NG125H<br />

Downstream 2P I 20A 6.5 6.5 6.5 6.5 6.5 3 4.5 4.5 4.5<br />

RCCB 230V IN-A 40A 6 10 20 30 30 10 10 15 15<br />

IN-A 63A 6 10 20 30 30 10 10 15 15<br />

I 100A 15 15 15 15<br />

4P I 20A 4.5 4.5 4.5 4.5 4.5 2 3 3 3<br />

400V IN-A 40A 6 10 10 15 15 7 7 15 15<br />

IN-A 63A 6 10 10 15 15 7 7 15 15<br />

NG 125NA 10 16 25 50<br />

Fuses and RCCB association – maxi Ιsc (r.m.s) value in kA<br />

gG upstream fuse 20A 63A 100A 125A<br />

Downstream 2P I 20A 8<br />

RCCB 230V IN-A 40A 30 20<br />

IN-A 63A 30 20<br />

I 100A 6<br />

4P I 20A 8<br />

400V IN-A 40A 30 20<br />

IN-A 63A 30 20<br />

NG 125NA 50<br />

Fig. F76 : Typical manufacturers coordination table for RCCBs, circuit-breakers, and fuses (Merlin Gerin products)<br />

8 Residual current devices (RCDs)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

<strong>Chapter</strong> G<br />

Sizing and protection <strong>of</strong> conductors<br />

Contents<br />

<strong>General</strong> G2<br />

1.1 Methodology and definition G2<br />

1.2 Overcurrent protection principles G4<br />

1.3 Practical values for a protective scheme G4<br />

1.4 Location <strong>of</strong> protective devices G6<br />

1.5 Conductors in parallel G6<br />

Practical method for determining the smallest allowable G7<br />

cross-sectional area <strong>of</strong> circuit conductors<br />

2.1 <strong>General</strong> G7<br />

2.2 <strong>General</strong> method for cables G7<br />

2.3 Recommended simplified approach for cables G16<br />

2.4 Busbar trunking systems G18<br />

Determination <strong>of</strong> voltage drop G20<br />

3.1 Maximum voltage drop limit G20<br />

3.2 Calculation <strong>of</strong> voltage drop in steady load conditions G21<br />

Short-circuit current G24<br />

4.1 Short-circuit current at the secondary terminals <strong>of</strong> G24<br />

a MV/LV distribution transformer<br />

4.2 3-phase short-circuit current (Isc) at any point within G25<br />

a LV <strong>installation</strong><br />

4.3 Isc at the receiving end <strong>of</strong> a feeder in terms <strong>of</strong> the Isc G28<br />

at its sending end<br />

4.4 Short-circuit current supplied by an alternator or an inverter G29<br />

Particular cases <strong>of</strong> short-circuit current G30<br />

5.1 Calculation <strong>of</strong> minimum levels <strong>of</strong> short-circuit current G30<br />

5.2 Verification <strong>of</strong> the withstand capabilities <strong>of</strong> cables under G35<br />

short-circuit conditions<br />

Protective earthing conductor G37<br />

6.1 Connection and choice G37<br />

6.2 Conductor sizing G38<br />

6.3 Protective conductor between MV/LV transformer and G40<br />

the main general distribution board (MGDB)<br />

6.4 Equipotential conductor G41<br />

The neutral conductor G42<br />

7.1 Sizing the neutral conductor G42<br />

7.2 Protection <strong>of</strong> the neutral conductor G42<br />

7.3 Breaking <strong>of</strong> the neutral conductor G44<br />

7.4 Isolation <strong>of</strong> the neutral conductor G44<br />

Worked example <strong>of</strong> cable calculation G46<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

G2<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Component parts <strong>of</strong> an electric circuit and its<br />

protection are determined such that all normal<br />

and abnormal operating conditions are satisfied<br />

(1) The term “cabling” in this chapter, covers all insulated<br />

conductors, including multi-core and single-core cables and<br />

insulated wires drawn into conduits, etc.<br />

<strong>General</strong><br />

. Methodology and definition<br />

Methodology (see Fig. G )<br />

Following a preliminary analysis <strong>of</strong> the power requirements <strong>of</strong> the <strong>installation</strong>, as<br />

described in <strong>Chapter</strong> B Clause 4, a study <strong>of</strong> cabling (1) and its <strong>electrical</strong> protection is<br />

undertaken, starting at the origin <strong>of</strong> the <strong>installation</strong>, through the intermediate stages<br />

to the final circuits.<br />

The cabling and its protection at each level must satisfy several conditions at the<br />

same time, in order to ensure a safe and reliable <strong>installation</strong>, e.g. it must:<br />

b Carry the permanent full load current, and normal short-time overcurrents<br />

b Not cause voltage drops likely to result in an inferior performance <strong>of</strong> certain loads,<br />

for example: an excessively long acceleration period when starting a motor, etc.<br />

Moreover, the protective devices (circuit-breakers or fuses) must:<br />

b Protect the cabling and busbars for all levels <strong>of</strong> overcurrent, up to and including<br />

short-circuit currents<br />

b Ensure protection <strong>of</strong> persons against indirect contact hazards, particularly in<br />

TN- and IT- earthed systems, where the length <strong>of</strong> circuits may limit the magnitude<br />

<strong>of</strong> short-circuit currents, thereby delaying automatic disconnection (it may be<br />

remembered that TT- earthed <strong>installation</strong>s are necessarily protected at the origin by<br />

a RCD, generally rated at 300 mA).<br />

The cross-sectional areas <strong>of</strong> conductors are determined by the general method<br />

described in Sub-clause 2 <strong>of</strong> this <strong>Chapter</strong>. Apart from this method some national<br />

standards may prescribe a minimum cross-sectional area to be observed for reasons<br />

<strong>of</strong> mechanical endurance. Particular loads (as noted in <strong>Chapter</strong> N) require that the<br />

cable supplying them be oversized, and that the protection <strong>of</strong> the circuit be likewise<br />

modified.<br />

Fig. G1 : Flow-chart for the selection <strong>of</strong> cable size and protective device rating for a given circuit<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Power demand:<br />

- kVA to be supplied<br />

- Maximum load current I B<br />

Conductor sizing:<br />

- Selection <strong>of</strong> conductor type and insulation<br />

- Selection <strong>of</strong> method <strong>of</strong> <strong>installation</strong><br />

- Taking account <strong>of</strong> correction factors for<br />

different environment conditions<br />

- Determination <strong>of</strong> cross-sectional areas using<br />

tables giving the current carrying capability<br />

Verification <strong>of</strong> the maximum voltage drop:<br />

- Steady state conditions<br />

- Motor starting conditions<br />

Calculation <strong>of</strong> short-circuit currents:<br />

- Upstream short-circuit power<br />

- Maximum values<br />

- Minimum values at conductor end<br />

Selection <strong>of</strong> protective devices:<br />

- Rated current<br />

- Breaking capability<br />

- Implementation <strong>of</strong> cascading<br />

- Check <strong>of</strong> discrimination


G - Sizing and protection <strong>of</strong> conductors<br />

<strong>General</strong><br />

Definitions<br />

Maximum load current: IB<br />

b At the final circuits level, this current corresponds to the rated kVA <strong>of</strong> the load.<br />

In the case <strong>of</strong> motor-starting, or other loads which take a high in-rush current,<br />

particularly where frequent starting is concerned (e.g. lift motors, resistance-type<br />

spot welding, and so on) the cumulative thermal effects <strong>of</strong> the overcurrents must be<br />

taken into account. Both cables and thermal type relays are affected.<br />

b At all upstream circuit levels this current corresponds to the kVA to be supplied,<br />

which takes account <strong>of</strong> the factors <strong>of</strong> simultaneity (diversity) and utilization, ks and ku<br />

respectively, as shown in Figure G2.<br />

80 A 60 A 100 A<br />

Fig. G2 : Calculation <strong>of</strong> maximum load current IB<br />

Maximum permissible current: Iz<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Main distribution<br />

board<br />

Combined factors <strong>of</strong> simultaneity<br />

(or diversity) and utilization:<br />

ks x ku = 0.69<br />

IB = (80+60+100+50) x 0.69 = 200 A<br />

M<br />

Sub-distribution<br />

board<br />

50 A<br />

Normal load<br />

motor current<br />

50 A<br />

This is the maximum value <strong>of</strong> current that the cabling for the circuit can carry<br />

indefinitely, without reducing its normal life expectancy.<br />

The current depends, for a given cross sectional area <strong>of</strong> conductors, on several<br />

parameters:<br />

b Constitution <strong>of</strong> the cable and cable-way (Cu or Alu conductors; PVC or EPR etc.<br />

insulation; number <strong>of</strong> active conductors)<br />

b Ambient temperature<br />

b Method <strong>of</strong> <strong>installation</strong><br />

b Influence <strong>of</strong> neighbouring circuits<br />

Overcurrents<br />

An overcurrent occurs each time the value <strong>of</strong> current exceeds the maximum load<br />

current IB for the load concerned.<br />

This current must be cut <strong>of</strong>f with a rapidity that depends upon its magnitude, if<br />

permanent damage to the cabling (and appliance if the overcurrent is due to a<br />

defective load component) is to be avoided.<br />

Overcurrents <strong>of</strong> relatively short duration can however, occur in normal operation; two<br />

types <strong>of</strong> overcurrent are distinguished:<br />

b Overloads<br />

These overcurrents can occur in healthy electric circuits, for example, due to a<br />

number <strong>of</strong> small short-duration loads which occasionally occur co-incidentally: motor<br />

starting loads, and so on. If either <strong>of</strong> these conditions persists however beyond a<br />

given period (depending on protective-relay settings or fuse ratings) the circuit will be<br />

automatically cut <strong>of</strong>f.<br />

b Short-circuit currents<br />

These currents result from the failure <strong>of</strong> insulation between live conductors or/and<br />

between live conductors and earth (on systems having low-impedance-earthed<br />

neutrals) in any combination, viz:<br />

v 3 phases short-circuited (and to neutral and/or earth, or not)<br />

v 2 phases short-circuited (and to neutral and/or earth, or not)<br />

v 1 phase short-circuited to neutral (and/or to earth)<br />

G3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

G4<br />

G - Sizing and protection <strong>of</strong> conductors<br />

t<br />

Fig. G3 : Circuit protection by circuit-breaker<br />

t<br />

Maximum<br />

load<br />

current<br />

Temporary<br />

overload<br />

Temporary<br />

overload<br />

I 2 t cable<br />

characteristic<br />

IB Ir Iz<br />

ISCB<br />

IB Ir cIz Iz<br />

Fig. G4 : Circuit protection by fuses<br />

Circuit-breaker<br />

tripping curve<br />

ICU<br />

I 2 t cable<br />

characteristic<br />

Fuse curve<br />

(1) Both <strong>design</strong>ations are commonly used in different<br />

standards.<br />

I<br />

I<br />

<strong>General</strong><br />

.2 Overcurrent protection principles<br />

A protective device is provided at the origin <strong>of</strong> the circuit concerned (see Fig. G3 and<br />

Fig. G4).<br />

b Acting to cut-<strong>of</strong>f the current in a time shorter than that given by the I 2 t<br />

characteristic <strong>of</strong> the circuit cabling<br />

b But allowing the maximum load current IB to flow indefinitely<br />

The characteristics <strong>of</strong> insulated conductors when carrying short-circuit currents<br />

can, for periods up to 5 seconds following short-circuit initiation, be determined<br />

approximately by the formula:<br />

I 2 t = k 2 S 2 which shows that the allowable heat generated is proportional to the<br />

squared cross-sectional-area <strong>of</strong> the condutor.<br />

where<br />

t: Duration <strong>of</strong> short-circuit current (seconds)<br />

S: Cross sectional area <strong>of</strong> insulated conductor (mm 2 )<br />

I: Short-circuit current (A r.m.s.)<br />

k: Insulated conductor constant (values <strong>of</strong> k 2 are given in Figure G52 )<br />

For a given insulated conductor, the maximum permissible current varies according<br />

to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is<br />

less than Iz2 (see Fig. G5). θ means “temperature”.<br />

Note:<br />

v ISC: 3-phase short-circuit current<br />

v ISCB: rated 3-ph. short-circuit breaking current <strong>of</strong> the circuit-breaker<br />

v Ir (or Irth) (1) : regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker<br />

can be regulated to have a protective range, i.e. a conventional overcurrent tripping<br />

level (see Fig. G6 opposite page) similar to that <strong>of</strong> a 30 A circuit-breaker.<br />

.3 Practical values for a protective scheme<br />

The following methods are based on <strong>rules</strong> laid down in the IEC standards, and are<br />

representative <strong>of</strong> the practices in many countries.<br />

<strong>General</strong> <strong>rules</strong><br />

A protective device (circuit-breaker or fuse) functions correctly if:<br />

b Its nominal current or its setting current In is greater than the maximum load<br />

current IB but less than the maximum permissible current Iz for the circuit, i.e.<br />

IB y In y Iz corresponding to zone “a” in Figure G6<br />

b Its tripping current I2 “conventional” setting is less than 1.45 Iz which corresponds<br />

to zone “b” in Figure G6<br />

The “conventional” setting tripping time may be 1 hour or 2 hours according to local<br />

standards and the actual value selected for I2. For fuses, I2 is the current (denoted<br />

If) which will operate the fuse in the conventional time.<br />

5 s<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

t<br />

1 2<br />

Iz1 < Iz2<br />

θa1 > θa2<br />

I 2 t = k 2 S 2<br />

Fig. G5 : I 2 t characteristic <strong>of</strong> an insulated conductor at two different ambient temperatures<br />

I


G - Sizing and protection <strong>of</strong> conductors<br />

0<br />

<strong>General</strong><br />

Loads Circuit cabling<br />

Maximum load current IB<br />

IB<br />

Nominal current In or<br />

its regulated current Ir<br />

I n<br />

zone a<br />

Fig. G6 : Current levels for determining circuir breaker or fuse characteristics<br />

Criteria for circuit-breakers:<br />

IB y In y Iz and ISCB u ISC.<br />

Criteria for fuses:<br />

IB y In y Iz/k3 and ISCF u ISC.<br />

Iz<br />

Maximum load current Iz<br />

zone b<br />

Protective device<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I2<br />

Conventional overcurrent<br />

trip current I2<br />

1.45 Iz<br />

1.45 Iz Isc<br />

ISCB<br />

zone c<br />

3-ph short-circuit<br />

fault-current breaking rating<br />

IB y In y Iz zone a<br />

I2 y 1.45 Iz zone b<br />

ISCB u ISC zone c<br />

b Its 3-phase short-circuit fault-current breaking rating is greater than the 3-phase<br />

short-circuit current existing at its point <strong>of</strong> <strong>installation</strong>. This corresponds to zone “c” in<br />

Figure G6.<br />

Applications<br />

b Protection by circuit-breaker<br />

By virtue <strong>of</strong> its high level <strong>of</strong> precision the current I2 is always less than 1.45 In (or<br />

1.45 Ir) so that the condition I2 y 1.45 Iz (as noted in the “general <strong>rules</strong>” above) will<br />

always be respected.<br />

v Particular case<br />

If the circuit-breaker itself does not protect against overloads, it is necessary to<br />

ensure that, at a time <strong>of</strong> lowest value <strong>of</strong> short-circuit current, the overcurrent device<br />

protecting the circuit will operate correctly. This particular case is examined in Subclause<br />

5.1.<br />

b Protection by fuses<br />

The condition I2 y 1.45 Iz must be taken into account, where I2 is the fusing (melting<br />

level) current, equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular<br />

fuse concerned.<br />

A further factor k3 has been introduced ( k = k2<br />

3 ) such that I2 y 1.45 Iz<br />

1.45<br />

will be valid if In y Iz/k3.<br />

For fuses type gG:<br />

In < 16 A → k3 = 1.31<br />

In u 16 A → k3 = 1.10<br />

Moreover, the short-circuit current breaking capacity <strong>of</strong> the fuse ISCF must exceed<br />

the level <strong>of</strong> 3-phase short-circuit current at the point <strong>of</strong> <strong>installation</strong> <strong>of</strong> the fuse(s).<br />

b Association <strong>of</strong> different protective devices<br />

The use <strong>of</strong> protective devices which have fault-current ratings lower than the fault<br />

level existing at their point <strong>of</strong> <strong>installation</strong> are permitted by IEC and many national<br />

standards in the following conditions:<br />

v There exists upstream, another protective device which has the necessary shortcircuit<br />

rating, and<br />

v The amount <strong>of</strong> energy allowed to pass through the upstream device is less than<br />

that which can be withstood without damage by the downstream device and all<br />

associated cabling and appliances.<br />

G5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

G6<br />

G - Sizing and protection <strong>of</strong> conductors<br />

A protective device is, in general, required at the<br />

origin <strong>of</strong> each circuit<br />

a<br />

b<br />

c<br />

B<br />

Fig. G7 : Location <strong>of</strong> protective devices<br />

P<br />

P2 P3 P4<br />

50 mm 2 10 mm 2 25 mm 2<br />

< 3 m<br />

P2<br />

A<br />

B<br />

P 1<br />

P3<br />

Case (1) Case (2)<br />

P 1: C60 rated 15 A<br />

2.5 mm 2<br />

sc<br />

Short-circuit<br />

protective<br />

device<br />

B<br />

s<br />

Overload<br />

protective<br />

device<br />

Case (3)<br />

S 2:<br />

1.5 mm2<br />

<strong>General</strong><br />

In pratice this arrangement is generally exploited in:<br />

v The association <strong>of</strong> circuit-breakers/fuses<br />

v The technique known as “cascading” or “series rating” in which the strong<br />

current-limiting performance <strong>of</strong> certain circuit-breakers effectively reduces the<br />

severity <strong>of</strong> downstream short-circuits<br />

Possible combinations which have been tested in laboratories are indicated in certain<br />

manufacturers catalogues.<br />

.4 Location <strong>of</strong> protective devices<br />

<strong>General</strong> rule (see Fig. G7a)<br />

A protective device is necessary at the origin <strong>of</strong> each circuit where a reduction <strong>of</strong><br />

permissible maximum current level occurs.<br />

Possible alternative locations in certain circumstances<br />

(see Fig. G7b)<br />

The protective device may be placed part way along the circuit:<br />

b If AB is not in proximity to combustible material, and<br />

b If no socket-outlets or branch connections are taken from AB<br />

Three cases may be useful in practice:<br />

b Consider case (1) in the diagram<br />

v AB y 3 metres, and<br />

v AB has been installed to reduce to a practical minimum the risk <strong>of</strong> a short-circuit<br />

(wires in heavy steel conduit for example)<br />

b Consider case (2)<br />

v The upstream device P1 protects the length AB against short-circuits in<br />

accordance with Sub-clause 5.1<br />

b Consider case (3)<br />

v The overload device (S) is located adjacent to the load. This arrangement is<br />

convenient for motor circuits. The device (S) constitutes the control (start/stop) and<br />

overload protection <strong>of</strong> the motor while (SC) is: either a circuit-breaker (<strong>design</strong>ed for<br />

motor protection) or fuses type aM<br />

v The short-circuit protection (SC) located at the origin <strong>of</strong> the circuit conforms with<br />

the principles <strong>of</strong> Sub-clause 5.1<br />

Circuits with no protection (see Fig. G7c)<br />

Either<br />

b The protective device P1 is calibrated to protect the cable S2 against overloads<br />

and short-circuits<br />

Or<br />

b Where the breaking <strong>of</strong> a circuit constitutes a risk, e.g.<br />

v Excitation circuits <strong>of</strong> rotating machines<br />

v circuits <strong>of</strong> large lifting electromagnets<br />

v the secondary circuits <strong>of</strong> current transformers<br />

No circuit interruption can be tolerated, and the protection <strong>of</strong> the cabling is <strong>of</strong><br />

secondary importance.<br />

.5 Conductors in parallel<br />

Conductors <strong>of</strong> the same cross-sectional-area, the same length, and <strong>of</strong> the same<br />

material, can be connected in parallel.<br />

The maximum permissible current is the sum <strong>of</strong> the individual-core maximum<br />

currents, taking into account the mutual heating effects, method <strong>of</strong> <strong>installation</strong>, etc.<br />

Protection against overload and short-circuits is identical to that for a single-cable<br />

circuit.<br />

The following precautions should be taken to avoid the risk <strong>of</strong> short-circuits on the<br />

paralleled cables:<br />

b Additional protection against mechanical damage and against humidity, by the<br />

introduction <strong>of</strong> supplementary protection<br />

b The cable route should be chosen so as to avoid close proximity to combustible<br />

materials<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

2.1 <strong>General</strong><br />

The reference international standard for the study <strong>of</strong> cabling is IEC 60364-5-52:<br />

“Electrical <strong>installation</strong> <strong>of</strong> buildings - Part 5-52: Selection and erection <strong>of</strong> <strong>electrical</strong><br />

equipment - Wiring system”.<br />

A summary <strong>of</strong> this standard is presented here, with examples <strong>of</strong> the most commonly<br />

used methods <strong>of</strong> <strong>installation</strong>. The current-carrying capacities <strong>of</strong> conductors in all<br />

different situations are given in annex A <strong>of</strong> the standard. A simplified method for use<br />

<strong>of</strong> the tables <strong>of</strong> annex A is proposed in informative annex B <strong>of</strong> the standard.<br />

2.2 <strong>General</strong> method for cables<br />

Possible methods <strong>of</strong> <strong>installation</strong> for different types <strong>of</strong><br />

conductors or cables<br />

The different admissible methods <strong>of</strong> <strong>installation</strong> are listed in Figure G8, in<br />

conjonction with the different types <strong>of</strong> conductors and cables.<br />

Conductors and cables Method <strong>of</strong> <strong>installation</strong><br />

Without Clipped Conduit Cable trunking Cable Cable ladder On Support<br />

fixings direct (including ducting Cable tray insulators wire<br />

skirting trunking, Cable brackets<br />

flush floor trunking)<br />

Bare conductors – – – – – – + –<br />

Insulated conductors – – + + + – + –<br />

Sheathed Multi-core + + + + + + 0 +<br />

cables<br />

(including<br />

armoured Single-core 0 + + + + + 0 +<br />

and<br />

mineral<br />

insulated)<br />

+ Permitted.<br />

– Not permitted.<br />

0 Not applicable, or not normally used in practice.<br />

Fig. G8 : Selection <strong>of</strong> wiring systems (table 52-1 <strong>of</strong> IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

G8<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G9 : Erection <strong>of</strong> wiring systems (table 52-2 <strong>of</strong> IEC 60364-5-52)<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Possible methods <strong>of</strong> <strong>installation</strong> for different situations:<br />

Different methods <strong>of</strong> <strong>installation</strong> can be implemented in different situations. The<br />

possible combinations are presented in Figure G9.<br />

The number given in this table refer to the different wiring systems considered.<br />

(see also Fig. G10)<br />

Situations Method <strong>of</strong> <strong>installation</strong><br />

Without With Conduit Cable trunking Cable Cable ladder On Support<br />

fixings fixings (including ducting cable tray, insulators wire<br />

skirting trunking,<br />

flush floor trunking)<br />

cable brackets<br />

Building voids 40, 46, 0 15, 16, – 43 30, 31, 32, – –<br />

15, 16 41, 42 33, 34<br />

Cable channel 56 56 54, 55 0 44, 45 30, 31, 32,<br />

33, 34<br />

– –<br />

Buried in ground 72, 73 0 70, 71 – 70, 71 0 –<br />

Embedded in structure 57, 58 3 1, 2,<br />

59, 60<br />

50, 51, 52, 53 44, 45 0 – –<br />

Surface mounted – 20, 21 4, 5 6, 7, 8, 9, 12, 13, 14 6, 7, 30, 31, 32, 36 –<br />

22, 23 8, 9 33, 34<br />

Overhead – – 0 10, 11 – 30, 31, 32<br />

33, 34<br />

36 35<br />

Immersed<br />

– Not permitted.<br />

80 80 0 – 0 0 – –<br />

0 Not applicable, or not normally used in practice.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G10 : Examples <strong>of</strong> methods <strong>of</strong> <strong>installation</strong> (part <strong>of</strong> table 52-3 <strong>of</strong> IEC 60364-5-52) (continued on next page)<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Examples <strong>of</strong> wiring systems and reference methods <strong>of</strong><br />

<strong>installation</strong>s<br />

An illustration <strong>of</strong> some <strong>of</strong> the many different wiring systems and methods <strong>of</strong><br />

<strong>installation</strong> is provided in Figure G10.<br />

Several reference methods are defined (with code letters A to G), grouping<br />

<strong>installation</strong> methods having the same characteristics relative to the current-carrying<br />

capacities <strong>of</strong> the wiring systems.<br />

Item No. Methods <strong>of</strong> <strong>installation</strong> Description Reference method <strong>of</strong><br />

<strong>installation</strong> to be used to<br />

obtain current-carrying<br />

capacity<br />

1 Insulated conductors or single-core<br />

cables in conduit in a thermally<br />

insulated wall<br />

A1<br />

Room<br />

2 Multi-core cables in conduit in a A2<br />

thermally insulated wall<br />

4 Insulated conductors or single-core B1<br />

cables in conduit on a wooden, or<br />

masonry wall or spaced less than<br />

0,3 x conduit diameter from it<br />

5 Multi-core cable in conduit on a B2<br />

wooden, or mansonry wall or spaced<br />

less than 0,3 x conduit diameter<br />

from it<br />

20 Single-core or multi-core cables: C<br />

- fixed on, or sapced less than 0.3 x cable<br />

diameter from a wooden wall<br />

30 On unperforated tray C<br />

0.3 De<br />

0.3 De<br />

Room<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G9<br />

© Schneider Electric - all rights reserved


G10<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Item No. Methods <strong>of</strong> <strong>installation</strong> Description Reference method <strong>of</strong><br />

<strong>installation</strong> to be used to<br />

obtain current-carrying<br />

capacity<br />

31 0.3 De<br />

On perforated tray E or F<br />

0.3 De<br />

36 Bare or insulated conductors on G<br />

insulators<br />

70 Multi-core cables in conduit or in cable D<br />

ducting in the ground<br />

71 Single-core cable in conduit or in cable D<br />

ducting in the ground<br />

Fig. G10 : Examples <strong>of</strong> methods <strong>of</strong> <strong>installation</strong> (part <strong>of</strong> table 52-3 <strong>of</strong> IEC 60364-5-52)<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Maximum operating temperature:<br />

The current-carrying capacities given in the subsequent tables have been<br />

determined so that the maximum insulation temperature is not exceeded for<br />

sustained periods <strong>of</strong> time.<br />

For different type <strong>of</strong> insulation material, the maximum admissible temperature is<br />

given in Figure G11.<br />

Type <strong>of</strong> insulation Temperature limit °C<br />

Polyvinyl-chloride (PVC) 70 at the conductor<br />

Cross-linked polyethylene (XLPE) and ethylene 90 at the conductor<br />

propylene rubber (EPR)<br />

Mineral (PVC covered or bare exposed to touch) 70 at the sheath<br />

Mineral (bare not exposed to touch and not in 105 at the seath<br />

contact with combustible material)<br />

Fig. G11 : Maximum operating temperatures for types <strong>of</strong> insulation (table 52-4 <strong>of</strong> IEC 60364-5-52)<br />

Correction factors:<br />

In order to take environnement or special conditions <strong>of</strong> <strong>installation</strong> into account,<br />

correction factors have been introduced.<br />

The cross sectional area <strong>of</strong> cables is determined using the rated load current I B<br />

divided by different correction factors, k1, k2, ...:<br />

I<br />

I' B<br />

B =<br />

k1⋅k 2 ...<br />

I’ B is the corrected load current, to be compared to the current-carrying capacity <strong>of</strong><br />

the considered cable.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

b Ambient temperature<br />

The current-carrying capacities <strong>of</strong> cables in the air are based on an average air<br />

temperature equal to 30 °C. For other temperatures, the correction factor is given in<br />

Figure G12 for PVC, EPR and XLPE insulation material.<br />

The related correction factor is here noted k 1.<br />

Ambient temperature °C Insulation<br />

PVC XLPE and EPR<br />

10 1.22 1.15<br />

15 1.17 1.12<br />

20 1.12 1.08<br />

25 1.06 1.04<br />

35 0.94 0.96<br />

40 0.87 0.91<br />

45 0.79 0.87<br />

50 0.71 0.82<br />

55 0.61 0.76<br />

60 0.50 0.71<br />

65 - 0.65<br />

70 - 0.58<br />

75 - 0.50<br />

80 - 0.41<br />

Fig. G12 : Correction factors for ambient air temperatures other than 30 °C to be applied to the<br />

current-carrying capacities for cables in the air (from table A.52-14 <strong>of</strong> IEC 60364-5-52)<br />

The current-carrying capacities <strong>of</strong> cables in the ground are based on an average<br />

ground temperature equal to 20 °C. For other temperatures, the correction factor is<br />

given in Figure G13 for PVC, EPR and XLPE insulation material.<br />

The related correction factor is here noted k 2.<br />

Ground temperature °C Insulation<br />

PVC XLPE and EPR<br />

10 1.10 1.07<br />

15 1.05 1.04<br />

25 0.95 0.96<br />

30 0.89 0.93<br />

35 0.84 0.89<br />

40 0.77 0.85<br />

45 0.71 0.80<br />

50 0.63 0.76<br />

55 0.55 0.71<br />

60 0.45 0.65<br />

65 - 0.60<br />

70 - 0.53<br />

75 - 0.46<br />

80 - 0.38<br />

Fig. G13 : Correction factors for ambient ground temperatures other than 20 °C to be applied to<br />

the current-carrying capacities for cables in ducts in the ground (from table A.52-15 <strong>of</strong><br />

IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G11<br />

© Schneider Electric - all rights reserved


G12<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

b Soil thermal resistivity<br />

The current-carrying capacities <strong>of</strong> cables in the ground are based on a ground<br />

resistivity equal to 2.5 K.m/W. For other values, the correction factor is given in<br />

Figure G14.<br />

The related correction factor is here noted k3.<br />

Thermal resistivity, K.m/W 1 1.5 2 2.5 3<br />

Correction factor 1.18 1.1 1.05 1 0.96<br />

Fig. G14 : Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5<br />

K.m/W to be applied to the current-carrying capacities for reference method D (table A52.16 <strong>of</strong><br />

IEC 60364-5-52)<br />

Based on experience, a relationship exist between the soil nature and resistivity.<br />

Then, empiric values <strong>of</strong> correction factors k3 are proposed in Figure G15, depending<br />

on the nature <strong>of</strong> soil.<br />

Fig. G15 : Correction factor k3 depending on the nature <strong>of</strong> soil<br />

b Grouping <strong>of</strong> conductors or cables<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Nature <strong>of</strong> soil k3<br />

Very wet soil (saturated) 1.21<br />

Wet soil 1.13<br />

Damp soil 1.05<br />

Dry soil 1.00<br />

Very dry soil (sunbaked) 0.86<br />

The current-carrying capacities given in the subsequent tables relate to single<br />

circuits consisting <strong>of</strong> the following numbers <strong>of</strong> loaded conductors:<br />

v Two insulated conductors or two single-core cables, or one twin-core cable<br />

(applicable to single-phase circuits);<br />

v Three insulated conductors or three single-core cables, or one three-core cable<br />

(applicable to three-phase circuits).<br />

Where more insulated conductors or cables are installed in the same group, a group<br />

reduction factor (here noted k4) shall be applied.<br />

Examples are given in Figures G16 to G18 for different configurations (<strong>installation</strong><br />

methods, in free air or in the ground).<br />

Figure G16 gives the values <strong>of</strong> correction factor k4 for different configurations <strong>of</strong><br />

unburied cables or conductors, grouping <strong>of</strong> more than one circuit or multi-core<br />

cables.<br />

Arrangement Number <strong>of</strong> circuits or multi-core cables Reference methods<br />

(cables touching) 1 2 3 4 5 6 7 8 9 12 16 20<br />

Bunched in air, on a 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38 Methods A to F<br />

surface, embedded or<br />

enclosed<br />

Single layer on wall, floor 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 No further reduction Method C<br />

or unperforated tray factor for more than<br />

Single layer fixed directly 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 nine circuits or<br />

under a wooden ceiling multi-core cables<br />

Single layer on a 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 Methods E and F<br />

perforated horizontal or<br />

vertical tray<br />

Single layer on ladder 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78<br />

support or cleats etc.<br />

Fig. G16 : Reduction factors for groups <strong>of</strong> more than one circuit or <strong>of</strong> more than one multi-core cable (table A.52-17 <strong>of</strong> IEC 60364-5-52)


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Figure G1 gives the values <strong>of</strong> correction factor k 4 for different configurations <strong>of</strong><br />

unburied cables or conductors, for groups <strong>of</strong> more than one circuit <strong>of</strong> single-core<br />

cables in free air.<br />

Method <strong>of</strong> <strong>installation</strong> Number Number <strong>of</strong> three-phase Use as a<br />

<strong>of</strong> tray circuits multiplier to<br />

rating for<br />

1 2 3<br />

Perforated 31 Touching 1 0.98 0.91 0.87 Three cables in<br />

trays horizontal<br />

2 0.96 0.87 0.81 formation<br />

20 mm<br />

3 0.95 0.85 0.78<br />

Vertical 31 Touching 1 0.96 0.86 Three cables in<br />

perforated vertical<br />

trays<br />

225 mm<br />

2 0.95 0.84 formation<br />

Ladder 32 1 1.00 0.97 0.96 Three cables in<br />

supports, Touching<br />

horizontal<br />

cleats, etc... 33 2 0.98 0.93 0.89 formation<br />

34 3 0.97 0.90 0.86<br />

20 mm<br />

Perforated<br />

trays<br />

31<br />

2De<br />

De 1 1.00 0.98 0.96 Three cables in<br />

trefoil formation<br />

2 0.97 0.93 0.89<br />

20 mm<br />

3 0.96 0.92 0.86<br />

Vertical<br />

perforated<br />

31 De<br />

Spaced 1 1.00 0.91 0.89<br />

trays<br />

225 mm<br />

2 1.00 0.90 0.86<br />

2De<br />

Ladder<br />

supports,<br />

32 2De<br />

De<br />

1 1.00 1.00 1.00<br />

cleats, etc... 33 2 0.97 0.95 0.93<br />

34 20 mm 3 0.96 0.94 0.90<br />

Fig. G17 : Reduction factors for groups <strong>of</strong> more than one circuit <strong>of</strong> single-core cables to be applied to reference rating for one circuit <strong>of</strong> single-core cables in free air<br />

- Method <strong>of</strong> <strong>installation</strong> F. (table A.52.21 <strong>of</strong> IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G13<br />

© Schneider Electric - all rights reserved


G14<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Figure G18 gives the values <strong>of</strong> correction factor k4 for different configurations <strong>of</strong><br />

cables or conductors laid directly in the ground.<br />

Number Cable to cable clearance (a) a<br />

<strong>of</strong> circuits Nil (cables One cable 0.125 m 0.25 m 0.5 m<br />

touching) diameter<br />

2 0.75 0.80 0.85 0.90 0.90<br />

3 0.65 0.70 0.75 0.80 0.85<br />

4 0.60 0.60 0.70 0.75 0.80<br />

5 0.55 0.55 0.65 0.70 0.80<br />

6 0.50 0.55 0.60 0.70 0.80<br />

a Multi-core cables<br />

a Single-core cables<br />

Fig. G18 : Reduction factors for more than one circuit, single-core or multi-core cables laid<br />

directly in the ground. Installation method D. (table 52-18 <strong>of</strong> IEC 60364-5-52)<br />

b Harmonic current<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

a a<br />

a a<br />

The current-carrying capacity <strong>of</strong> three-phase, 4-core or 5-core cables is based on<br />

the assumption that only 3 conductors are fully loaded.<br />

However, when harmonic currents are circulating, the neutral current can be<br />

significant, and even higher than the phase currents. This is due to the fact that the<br />

3 rd harmonic currents <strong>of</strong> the three phases do not cancel each other, and sum up in<br />

the neutral conductor.<br />

This <strong>of</strong> course affects the current-carrying capacity <strong>of</strong> the cable, and a correction<br />

factor noted here k5 shall be applied.<br />

In addition, if the 3 rd harmonic percentage h 3 is greater than 33%, the neutral current<br />

is greater than the phase current and the cable size selection is based on the neutral<br />

current. The heating effect <strong>of</strong> harmonic currents in the phase conductors has also to<br />

be taken into account.<br />

The values <strong>of</strong> k5 depending on the 3 rd harmonic content are given in Figure G19.<br />

Third harmonic content Correction factor<br />

<strong>of</strong> phase current % Size selection is based Size selection is based<br />

on phase current on neutral current<br />

0 - 15 1.0<br />

15 - 33 0.86<br />

33 - 45 0.86<br />

> 45 1.0<br />

Fig. G19 : Correction factors for harmonic currents in four-core and five-core cables (table D.52.1<br />

<strong>of</strong> IEC 60364-5-52)<br />

Admissible current as a function <strong>of</strong> nominal cross-sectional<br />

area <strong>of</strong> conductors<br />

IEC standard 60364-5-52 proposes extensive information in the form <strong>of</strong> tables<br />

giving the admissible currents as a function <strong>of</strong> cross-sectional area <strong>of</strong> cables. Many<br />

parameters are taken into account, such as the method <strong>of</strong> <strong>installation</strong>, type <strong>of</strong><br />

insulation material, type <strong>of</strong> conductor material, number <strong>of</strong> loaded conductors.


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

As an example, Figure G20 gives the current-carrying capacities for different<br />

methods <strong>of</strong> <strong>installation</strong> <strong>of</strong> PVC insulation, three loaded copper or aluminium<br />

conductors, free air or in ground.<br />

Nominal Installation methods<br />

cross-sectional A1 A2 B1 B2 C D<br />

area <strong>of</strong> conductors<br />

(mm 2 )<br />

1 2 3 4 5 6<br />

Copper<br />

1.5 13.5 13 15.5 15 17.5 18<br />

2.5 18 17.5 21 20 24 24<br />

4 24 23 28 27 32 31<br />

6 31 29 36 34 41 39<br />

10 42 39 50 46 57 52<br />

16 56 52 68 62 76 67<br />

25 73 68 89 80 96 86<br />

35 89 83 110 99 119 103<br />

50 108 99 134 118 144 122<br />

70 136 125 171 149 184 151<br />

95 164 150 207 179 223 179<br />

120 188 172 239 206 259 203<br />

150 216 196 - - 299 230<br />

185 245 223 - - 341 258<br />

240 286 261 - - 403 297<br />

300 328 298 - - 464 336<br />

Aluminium<br />

2.5 14 13.5 16.5 15.5 18.5 18.5<br />

4 18.5 17.5 22 21 25 24<br />

6 24 23 28 27 32 30<br />

10 32 31 39 36 44 40<br />

16 43 41 53 48 59 52<br />

25 57 53 70 62 73 66<br />

35 70 65 86 77 90 80<br />

50 84 78 104 92 110 94<br />

70 107 98 133 116 140 117<br />

95 129 118 161 139 170 138<br />

120 149 135 186 160 197 157<br />

150 170 155 - - 227 178<br />

185 194 176 - - 259 200<br />

240 227 207 - - 305 230<br />

300 261 237 - - 351 260<br />

Fig. G20 : Current-carrying capacities in amperes for different methods <strong>of</strong> <strong>installation</strong>, PVC insulation, three loaded conductors, copper or aluminium, conductor<br />

temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground (table A.52.4 <strong>of</strong> IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G15<br />

© Schneider Electric - all rights reserved


G16<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

2.3 Recommended simplified approach for cables<br />

In order to facilitate the selection <strong>of</strong> cables, 2 simplified tables are proposed, for<br />

unburied and buried cables.<br />

These tables summarize the most commonly used configurations and give easier<br />

access to the information.<br />

b Unburied cables:<br />

Fig. G21a : Current-carrying capacity in amperes (table B.52-1 <strong>of</strong> IEC 60364-5-52)<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Reference Number <strong>of</strong> loaded conductors and type <strong>of</strong> insulation<br />

methods<br />

A1 2 PVC 3 PVC 3 XLPE 2 XLPE<br />

A2 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

B1 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

B2 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

C 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

E 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

F 3 PVC 2 PVC 3 XLPE 2 XLPE<br />

1 2 3 4 5 6 8 9 10 11 12 13<br />

Size (mm 2 )<br />

Copper<br />

1.5 13 13 .5 14.5 15.5 17 18.5 19.5 22 23 24 26 -<br />

2.5 17.5 18 19.5 21 23 25 27 30 31 33 36 -<br />

4 23 24 26 28 31 34 36 40 42 45 49 -<br />

6 29 31 34 36 40 43 46 51 54 58 63 -<br />

10 39 42 46 50 54 60 63 70 75 80 86 -<br />

16 52 56 61 68 73 80 85 94 100 107 115 -<br />

25 68 73 80 89 95 101 110 119 127 135 149 161<br />

35 - - - 110 117 126 137 147 158 169 185 200<br />

50 - - - 134 141 153 167 179 192 207 225 242<br />

70 - - - 171 179 196 213 229 246 268 289 310<br />

95 - - - 207 216 238 258 278 298 328 352 377<br />

120 - - - 239 249 276 299 322 346 382 410 437<br />

150 - - - - 285 318 344 371 395 441 473 504<br />

185 - - - - 324 362 392 424 450 506 542 575<br />

240 - - - - 380 424 461 500 538 599 641 679<br />

Aluminium<br />

2.5 13.5 14 15 16.5 18.5 19.5 21 23 24 26 28 -<br />

4 17.5 18.5 20 22 25 26 28 31 32 35 38 -<br />

6 23 24 26 28 32 33 36 39 42 45 49 -<br />

10 31 32 36 39 44 46 49 54 58 62 67 -<br />

16 41 43 48 53 58 61 66 73 77 84 91 -<br />

25 53 57 63 70 73 78 83 90 97 101 108 121<br />

35 - - - 86 90 96 103 112 120 126 135 150<br />

50 - - - 104 110 117 125 136 146 154 164 184<br />

70 - - - 133 140 150 160 174 187 198 211 237<br />

95 - - - 161 170 183 195 211 227 241 257 289<br />

120 - - - 186 197 212 226 245 263 280 300 337<br />

150 - - - - 226 245 261 283 304 324 346 389<br />

185 - - - - 256 280 298 323 347 371 397 447<br />

240 - - - - 300 330 352 382 409 439 470 530<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Correction factors are given in Figure G21b for groups <strong>of</strong> several circuits or multicore<br />

cables:<br />

Arrangement Number <strong>of</strong> circuits or multi-core cables<br />

1 2 3 4 6 9 12 16 20<br />

Embedded or enclosed 1.00 0.80 0.70 0.70 0.55 0.50 0.45 0.40 0.40<br />

Single layer on walls, floors 1.00 0.85 0.80 0.75 0.70 0.70 - - -<br />

or on unperforatedtrays<br />

Single layer fixed directly 0.95 0.80 0.70 0.70 0.65 0.60 - - -<br />

under a ceiling<br />

Single layer on perforated 1.00 0.90 0.80 0.75 0.75 0.70 - - -<br />

horizontal trays or on vertical trays<br />

Single layer on cable 1.00 0.85 0.80 0.80 0.80 0.80 - - -<br />

ladder supports or cleats, etc...<br />

Fig. G21b : Reduction factors for groups <strong>of</strong> several circuits or <strong>of</strong> several multi-core cables<br />

(table B.52-3 <strong>of</strong> IEC 60364-5-52)<br />

b Buried cables:<br />

Installation Size Number <strong>of</strong> loaded conductors and type <strong>of</strong> insulation<br />

method mm 2 Two PVC Three PVC Two XLPE Three XLPE<br />

D Copper<br />

1.5 22 18 26 22<br />

2.5 29 24 34 29<br />

4 38 31 44 37<br />

6 47 39 56 46<br />

10 63 52 73 61<br />

16 81 67 95 79<br />

25 104 86 121 101<br />

35 125 103 146 122<br />

50 148 122 173 144<br />

70 183 151 213 178<br />

95 216 179 252 211<br />

120 246 203 287 240<br />

150 278 230 324 271<br />

185 312 258 363 304<br />

240 361 297 419 351<br />

300 408 336 474 396<br />

D Aluminium<br />

2.5 22 18.5 26 22<br />

4 29 24 34 29<br />

6 36 30 42 36<br />

10 48 40 56 47<br />

16 62 52 73 61<br />

25 80 66 93 78<br />

35 96 80 112 94<br />

50 113 94 132 112<br />

70 140 117 163 138<br />

95 166 138 193 164<br />

120 189 157 220 186<br />

150 213 178 249 210<br />

185 240 200 279 236<br />

240 277 230 322 272<br />

300 313 260 364 308<br />

Fig. G22 : Current-carrying capacity in amperes (table B.52-1 <strong>of</strong> IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G1<br />

© Schneider Electric - all rights reserved


G18<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

2.4 Busbar trunking systems<br />

The selection <strong>of</strong> busbar trunking systems is very straightforward, using the data<br />

provided by the manufacturer. Methods <strong>of</strong> <strong>installation</strong>, insulation materials, correction<br />

factors for grouping are not relevant parameters for this technology.<br />

The cross section area <strong>of</strong> any given model has been determined by the manufacturer<br />

based on:<br />

b The rated current,<br />

b An ambient air temperature equal to 35 °C,<br />

b 3 loaded conductors.<br />

Rated current<br />

The rated current can be calculated taking account <strong>of</strong>:<br />

b The layout,<br />

b The current absorbed by the different loads connected along the trunking system.<br />

Ambient temperature<br />

A correction factor has to be applied for temperature higher than 35 °C. The<br />

correction factor applicable to medium and high power range (up to 4,000 A) is given<br />

in Figure G23a.<br />

°C 35 40 45 50 55<br />

Correction factor 1 0.97 0.93 0.90 0.86<br />

Fig. G23a : Correction factor for air temperature higher than 35 °C<br />

Neutral current<br />

Where 3 rd harmonic currents are circulating, the neutral conductor may be carrying a<br />

significant current and the corresponding additional power losses must be taken into<br />

account.<br />

Figure G23b represents the maximum admissible phase and neutral currents (per<br />

unit) in a high power busbar trunking system as functions <strong>of</strong> 3 rd harmonic level.<br />

Maximum admissible current (p.u)<br />

1.4<br />

1.2<br />

1<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

0<br />

0 10 20 30 40<br />

Fig. G23b : Maximum admissible currents (p.u.) in a busbar trunking system as functions <strong>of</strong> the<br />

3 rd harmonic level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

50 60 70<br />

3 rd harmonic current level (%)<br />

Neutral conductor<br />

Phase conductor<br />

80 90


G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

The layout <strong>of</strong> the trunking system depends on the position <strong>of</strong> the current consumers,<br />

the location <strong>of</strong> the power source and the possibilities for fixing the system.<br />

v One single distribution line serves a 4 to 6 meter area<br />

v Protection devices for current consumers are placed in tap-<strong>of</strong>f units, connected<br />

directly to usage points.<br />

v One single feeder supplies all current consumers <strong>of</strong> different powers.<br />

Once the trunking system layout is established, it is possible to calculate the<br />

absorbed current I n on the distribution line.<br />

I n is equal to the sum <strong>of</strong> absorbed currents by the current I n consumers: I n = Σ I B.<br />

The current consumers do not all work at the same time and are not permanently on<br />

full load, so we have to use a clustering coefficient k S : I n = Σ (I B . k S).<br />

Application Number <strong>of</strong> current consumers Ks Coefficient<br />

Lighting, Heating 1<br />

Distribution (engineering<br />

workshop)<br />

2...3<br />

4...5<br />

6...9<br />

10...40<br />

40 and over<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0.9<br />

0.8<br />

0.7<br />

0.6<br />

0.5<br />

Note : for industrial <strong>installation</strong>s, remember to take account <strong>of</strong> upgrading <strong>of</strong> the machine<br />

equipment base. As for a switchboard, a 20 % margin is recommended:<br />

I n ≤ I B x k s x 1.2.<br />

Fig G24 : Clustering coefficient according to the number <strong>of</strong> current consumers<br />

G19<br />

© Schneider Electric - all rights reserved


G20<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

3 Determination <strong>of</strong> voltage drop<br />

The impedance <strong>of</strong> circuit conductors is low but not negligible: when carrying<br />

load current there is a voltage drop between the origin <strong>of</strong> the circuit and the load<br />

terminals. The correct operation <strong>of</strong> a load (a motor, lighting circuit, etc.) depends<br />

on the voltage at its terminals being maintained at a value close to its rated value.<br />

It is necessary therefore to determine the circuit conductors such that at full-load<br />

current, the load terminal voltage is maintained within the limits required for correct<br />

performance.<br />

This section deals with methods <strong>of</strong> determining voltage drops, in order to check that:<br />

b They comply with the particular standards and regulations in force<br />

b They can be tolerated by the load<br />

b They satisfy the essential operational requirements<br />

3.1 Maximum voltage drop<br />

Maximum allowable voltage-drop vary from one country to another. Typical values for<br />

LV <strong>installation</strong>s are given below in Figure G25.<br />

Type <strong>of</strong> <strong>installation</strong>s Lighting Other uses<br />

circuits (heating and power)<br />

A low-voltage service connection from 3% 5%<br />

a LV public power distribution network<br />

Consumers MV/LV substation supplied 6% 8%<br />

from a public distribution MV system<br />

Fig. G25 : Maximum voltage-drop between the service-connection point and the point <strong>of</strong> utilization<br />

These voltage-drop limits refer to normal steady-state operating conditions and do<br />

not apply at times <strong>of</strong> motor starting, simultaneous switching (by chance) <strong>of</strong> several<br />

loads, etc. as mentioned in <strong>Chapter</strong> A Sub-clause 4.3 (factor <strong>of</strong> simultaneity, etc.).<br />

When voltage drops exceed the values shown in Figure G25, larger cables (wires)<br />

must be used to correct the condition.<br />

The value <strong>of</strong> 8%, while permitted, can lead to problems for motor loads; for example:<br />

b In general, satisfactory motor performance requires a voltage within ± 5% <strong>of</strong> its<br />

rated nominal value in steady-state operation,<br />

b Starting current <strong>of</strong> a motor can be 5 to 7 times its full-load value (or even higher).<br />

If an 8% voltage drop occurs at full-load current, then a drop <strong>of</strong> 40% or more will<br />

occur during start-up. In such conditions the motor will either:<br />

v Stall (i.e. remain stationary due to insufficient torque to overcome the load torque)<br />

with consequent over-heating and eventual trip-out<br />

v Or accelerate very slowly, so that the heavy current loading (with possibly<br />

undesirable low-voltage effects on other equipment) will continue beyond the normal<br />

start-up period<br />

b Finally an 8% voltage drop represents a continuous power loss, which, for continuous<br />

loads will be a significant waste <strong>of</strong> (metered) energy. For these reasons it is<br />

recommended that the maximum value <strong>of</strong> 8% in steady operating conditions should not<br />

be reached on circuits which are sensitive to under-voltage problems (see Fig. G26).<br />

Load<br />

Fig. G26 : Maximum voltage drop<br />

LV consumer<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

5% (1)<br />

MV consumer<br />

8% (1)<br />

(1) Between the LV supply point and the load


G - Sizing and protection <strong>of</strong> conductors<br />

3 Determination <strong>of</strong> voltage drop<br />

3.2 Calculation <strong>of</strong> voltage drop in steady load<br />

conditions<br />

Use <strong>of</strong> formulae<br />

Figure G27 below gives formulae commonly used to calculate voltage drop in a<br />

given circuit per kilometre <strong>of</strong> length.<br />

If:<br />

b IB: The full load current in amps<br />

b L: Length <strong>of</strong> the cable in kilometres<br />

b R: Resistance <strong>of</strong> the cable conductor in Ω/km<br />

2<br />

22.5 Ω mm / km<br />

R =<br />

for copper<br />

2<br />

S c.s.a. in mm<br />

( )<br />

2<br />

36 Ω mm / km<br />

R =<br />

for aluminium<br />

2<br />

S c.s.a. in mm<br />

( )<br />

Note: R is negligible above a c.s.a. <strong>of</strong> 500 mm 2<br />

b X: inductive reactance <strong>of</strong> a conductor in Ω/km<br />

Note: X is negligible for conductors <strong>of</strong> c.s.a. less than 50 mm 2 . In the absence <strong>of</strong> any<br />

other information, take X as being equal to 0.08 Ω/km.<br />

b ϕ: phase angle between voltage and current in the circuit considered, generally:<br />

v Incandescent lighting: cos ϕ = 1<br />

v Motor power:<br />

- At start-up: cos ϕ = 0.35<br />

- In normal service: cos ϕ = 0.8<br />

b Un: phase-to-phase voltage<br />

b Vn: phase-to-neutral voltage<br />

For prefabricated pre-wired ducts and bustrunking, resistance and inductive<br />

reactance values are given by the manufacturer.<br />

Circuit Voltage drop (ΔU)<br />

in volts in %<br />

Single phase: phase/phase ∆U = 2I B R cos ϕ + X sin ϕ L<br />

Fig. G27 : Voltage-drop formulae<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

( )<br />

100 ∆U<br />

Un<br />

Single phase: phase/neutral ∆U = 2I B( R cos ϕ + X sin ϕ) L<br />

100 ∆ U<br />

Vn<br />

Balanced 3-phase: 3 phases ∆U = 3 I B( R cos ϕ + X sin ϕ) L 100 ∆ U<br />

Un<br />

(with or without neutral)<br />

Simplified table<br />

Calculations may be avoided by using Figure G28 next page, which gives, with<br />

an adequate approximation, the phase-to-phase voltage drop per km <strong>of</strong> cable per<br />

ampere, in terms <strong>of</strong>:<br />

b Kinds <strong>of</strong> circuit use: motor circuits with cos ϕ close to 0.8, or lighting with a cos ϕ<br />

close to 1.<br />

b Type <strong>of</strong> cable; single-phase or 3-phase<br />

Voltage drop in a cable is then given by:<br />

K x IB x L<br />

K is given by the table,<br />

IB is the full-load current in amps,<br />

L is the length <strong>of</strong> cable in km.<br />

The column motor power “cos ϕ = 0.35” <strong>of</strong> Figure G28 may be used to compute the<br />

voltage drop occurring during the start-up period <strong>of</strong> a motor (see example no. 1 after<br />

the Figure G28).<br />

G21<br />

© Schneider Electric - all rights reserved


G22<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

c.s.a. in mm 2 Single-phase circuit Balanced three-phase circuit<br />

Motor power Lighting Motor power Lighting<br />

Normal service Start-up Normal service Start-up<br />

Cu Al cos ϕ = 0.8 cos ϕ = 0.35 cos ϕ = 1 cos ϕ = 0.8 cos ϕ = 0.35 cos ϕ = 1<br />

1.5 24 10.6 30 20 9.4 25<br />

2.5 14.4 6.4 18 12 5.7 15<br />

4 9.1 4.1 11.2 8 3.6 9.5<br />

6 10 6.1 2.9 7.5 5.3 2.5 6.2<br />

10 16 3.7 1.7 4.5 3.2 1.5 3.6<br />

16 25 2.36 1.15 2.8 2.05 1 2.4<br />

25 35 1.5 0.75 1.8 1.3 0.65 1.5<br />

35 50 1.15 0.6 1.29 1 0.52 1.1<br />

50 70 0.86 0.47 0.95 0.75 0.41 0.77<br />

70 120 0.64 0.37 0.64 0.56 0.32 0.55<br />

95 150 0.48 0.30 0.47 0.42 0.26 0.4<br />

120 185 0.39 0.26 0.37 0.34 0.23 0.31<br />

150 240 0.33 0.24 0.30 0.29 0.21 0.27<br />

185 300 0.29 0.22 0.24 0.25 0.19 0.2<br />

240 400 0.24 0.2 0.19 0.21 0.17 0.16<br />

300 500 0.21 0.19 0.15 0.18 0.16 0.13<br />

Fig. G28 : Phase-to-phase voltage drop ΔU for a circuit, in volts per ampere per km<br />

1,000 A<br />

400 V<br />

Fig. G29 : Example 1<br />

50 m / 35 mm 2 Cu<br />

IB = 100 A<br />

(500 A during start-up)<br />

3 Determination <strong>of</strong> voltage drop<br />

Examples<br />

Example 1 (see Fig. G29)<br />

A three-phase 35 mm 2 copper cable 50 metres long supplies a 400 V motor taking:<br />

b 100 A at a cos ϕ = 0.8 on normal permanent load<br />

b 500 A (5 In) at a cos ϕ = 0.35 during start-up<br />

The voltage drop at the origin <strong>of</strong> the motor cable in normal circumstances (i.e. with<br />

the distribution board <strong>of</strong> Figure G29 distributing a total <strong>of</strong> 1,000 A) is 10 V phase-tophase.<br />

What is the voltage drop at the motor terminals:<br />

b In normal service?<br />

b During start-up?<br />

Solution:<br />

b Voltage drop in normal service conditions:<br />

∆<br />

∆U%<br />

100 U<br />

=<br />

Un<br />

Table G28 shows 1 V/A/km so that:<br />

ΔU for the cable = 1 x 100 x 0.05 = 5 V<br />

ΔU total = 10 + 5 = 15 V = i.e.<br />

15<br />

x 100 3.75%<br />

400 =<br />

This value is less than that authorized (8%) and is satisfactory.<br />

b Voltage drop during motor start-up:<br />

ΔUcable = 0.52 x 500 x 0.05 = 13 V<br />

Owing to the additional current taken by the motor when starting, the voltage drop at<br />

the distribution board will exceed 10 Volts.<br />

Supposing that the infeed to the distribution board during motor starting is<br />

900 + 500 = 1,400 A then the voltage drop at the distribution board will increase<br />

approximately pro rata, i.e.<br />

10 x 1,400<br />

= 14 V<br />

1,000<br />

ΔU distribution board = 14 V<br />

ΔU for the motor cable = 13 V<br />

ΔU total = 13 + 14 = 27 V i.e.<br />

27<br />

x 100 6.75%<br />

400 =<br />

a value which is satisfactory during motor starting.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

3 Determination <strong>of</strong> voltage drop<br />

Example 2 (see Fig. G30)<br />

A 3-phase 4-wire copper line <strong>of</strong> 70 mm 2 c.s.a. and a length <strong>of</strong> 50 m passes a current<br />

<strong>of</strong> 150 A. The line supplies, among other loads, 3 single-phase lighting circuits, each<br />

<strong>of</strong> 2.5 mm 2 c.s.a. copper 20 m long, and each passing 20 A.<br />

It is assumed that the currents in the 70 mm 2 line are balanced and that the three<br />

lighting circuits are all connected to it at the same point.<br />

What is the voltage drop at the end <strong>of</strong> the lighting circuits?<br />

Solution:<br />

b Voltage drop in the 4-wire line:<br />

∆<br />

∆U%<br />

100 U<br />

=<br />

Un<br />

Figure G28 shows 0.55 V/A/km<br />

ΔU line = 0.55 x 150 x 0.05 = 4.125 V phase-to-phase<br />

4 . 125<br />

which gives: = 2.38 V phase to neutral.<br />

3<br />

b Voltage drop in any one <strong>of</strong> the lighting single-phase circuits:<br />

ΔU for a single-phase circuit = 18 x 20 x 0.02 = 7.2 V<br />

The total voltage drop is therefore<br />

7.2 + 2.38 = 9.6 V<br />

9.6 V<br />

x 100 = 4.2%<br />

230 V<br />

This value is satisfactory, being less than the maximum permitted voltage drop <strong>of</strong> 6%.<br />

Fig. G30 : Example 2<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

50 m / 70 mm2 Cu<br />

IB = 150 A<br />

20 m / 2.5 mm2 Cu<br />

IB = 20 A<br />

G23<br />

© Schneider Electric - all rights reserved


G24<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Knowing the levels <strong>of</strong> 3-phase symmetrical<br />

short-circuit currents (Isc) at different points<br />

in an <strong>installation</strong> is an essential feature <strong>of</strong> its<br />

<strong>design</strong><br />

Isc1<br />

Isc2<br />

Fig. G32 : Case <strong>of</strong> several transformers in parallel<br />

Isc3<br />

Isc1 + Isc2 + Isc3<br />

4 Short-circuit current<br />

A knowledge <strong>of</strong> 3-phase symmetrical short-circuit current values (Isc) at strategic<br />

points <strong>of</strong> an <strong>installation</strong> is necessary in order to determine switchgear (fault current<br />

rating), cables (thermal withstand rating), protective devices (discriminative trip<br />

settings) and so on...<br />

In the following notes a 3-phase short-circuit <strong>of</strong> zero impedance (the so-called bolted<br />

short-circuit) fed through a typical MV/LV distribution transformer will be examined.<br />

Except in very unusual circumstances, this type <strong>of</strong> fault is the most severe, and is<br />

certainly the simplest to calculate.<br />

Short-circuit currents occurring in a network supplied from a generator and also in<br />

DC systems are dealt with in <strong>Chapter</strong> N.<br />

The simplified calculations and practical <strong>rules</strong> which follow give conservative results<br />

<strong>of</strong> sufficient accuracy, in the large majority <strong>of</strong> cases, for <strong>installation</strong> <strong>design</strong> purposes.<br />

4.1 Short-circuit current at the secondary terminals<br />

<strong>of</strong> a MV/LV distribution transformer<br />

The case <strong>of</strong> one transformer<br />

b In a simplified approach, the impedance <strong>of</strong> the MV system is assumed to be<br />

In<br />

negligibly small, so that: Isc<br />

In<br />

Usc<br />

P<br />

3<br />

x 100 x 10<br />

= where = and:<br />

U20<br />

3<br />

P = kVA rating <strong>of</strong> the transformer<br />

U20 = phase-to-phase secondary volts on open circuit<br />

In = nominal current in amps<br />

Isc = short-circuit fault current in amps<br />

Usc = short-circuit impedance voltage <strong>of</strong> the transformer in %.<br />

Typical values <strong>of</strong> Usc for distribution transformers are given in Figure G31.<br />

Fig. G31 : Typical values <strong>of</strong> Usc for different kVA ratings <strong>of</strong> transformers with MV windings y 20 kV<br />

b Example<br />

Transformer rating Usc in %<br />

(kVA) Oil-immersed Cast-resin<br />

dry type<br />

50 to 750 4 6<br />

800 to 3,200 6 6<br />

400 kVA transformer, 420 V at no load<br />

Usc = 4%<br />

400<br />

x 10<br />

55 0 x 100<br />

In = = 550 A I sc = = 13. 7 kA<br />

420 x 3<br />

4<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

The case <strong>of</strong> several transformers in parallel feeding a busbar<br />

The value <strong>of</strong> fault current on an outgoing circuit immediately downstream <strong>of</strong><br />

the busbars (see Fig. G32) can be estimated as the sum <strong>of</strong> the Isc from each<br />

transformer calculated separately.<br />

It is assumed that all transformers are supplied from the same MV network, in which<br />

case the values obtained from Figure G31 when added together will give a slightly<br />

higher fault-level value than would actually occur.<br />

Other factors which have not been taken into account are the impedance <strong>of</strong> the<br />

busbars and <strong>of</strong> the circuit-breakers.<br />

The conservative fault-current value obtained however, is sufficiently accurate for<br />

basic <strong>installation</strong> <strong>design</strong> purposes. The choice <strong>of</strong> circuit-breakers and incorporated<br />

protective devices against short-circuit fault currents is described in <strong>Chapter</strong> H Subclause<br />

4.4.


G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G33 : Impedance diagram<br />

Z<br />

(1) Short-circuit MVA: 3 E L Isc where:<br />

b E L = phase-to-phase nominal system voltage expressed in<br />

kV (r.m.s.)<br />

b Isc = 3-phase short-circuit current expressed in kA (r.m.s.)<br />

(2) up to 36 kV<br />

R<br />

X<br />

4 Short-circuit current<br />

4.2 3-phase short-circuit current (Isc) at any point<br />

within a LV <strong>installation</strong><br />

In a 3-phase <strong>installation</strong> Isc at any point is given by:<br />

U<br />

Isc = 20 where<br />

3 ZT<br />

U 20 = phase-to-phase voltage <strong>of</strong> the open circuited secondary windings <strong>of</strong> the power<br />

supply transformer(s).<br />

Z T = total impedance per phase <strong>of</strong> the <strong>installation</strong> upstream <strong>of</strong> the fault location (in Ω)<br />

Method <strong>of</strong> calculating Z T<br />

Each component <strong>of</strong> an <strong>installation</strong> (MV network, transformer, cable, circuit-breaker,<br />

busbar, and so on...) is characterized by its impedance Z, comprising an element<br />

<strong>of</strong> resistance (R) and an inductive reactance (X). It may be noted that capacitive<br />

reactances are not important in short-circuit current calculations.<br />

The parameters R, X and Z are expressed in ohms, and are related by the sides <strong>of</strong> a<br />

right angled triangle, as shown in the impedance diagram <strong>of</strong> Figure G33.<br />

The method consists in dividing the network into convenient sections, and to<br />

calculate the R and X values for each.<br />

Where sections are connected in series in the network, all the resistive elements in<br />

the section are added arithmetically; likewise for the reactances, to give R T and X T.<br />

The impedance (Z T) for the combined sections concerned is then calculated from<br />

2<br />

Z = R + X 2<br />

T T T<br />

Any two sections <strong>of</strong> the network which are connected in parallel, can, if<br />

predominantly both resistive (or both inductive) be combined to give a single<br />

equivalent resistance (or reactance) as follows:<br />

Let R1 and R2 be the two resistances connected in parallel, then the equivalent<br />

resistance R3 will be given by:<br />

R1<br />

x R2<br />

X1<br />

x X2<br />

R3<br />

= or for reactances X3<br />

=<br />

R 1 + R2<br />

X 1 + X2<br />

It should be noted that the calculation <strong>of</strong> X3 concerns only separated circuit without<br />

mutual inductance. If the circuits in parallel are close togother the value <strong>of</strong> X3 will be<br />

notably higher.<br />

Determination <strong>of</strong> the impedance <strong>of</strong> each component<br />

b Network upstream <strong>of</strong> the MV/LV transformer (see Fig. G34)<br />

The 3-phase short-circuit fault level P SC, in kA or in MVA (1) is given by the power<br />

supply authority concerned, from which an equivalent impedance can be deduced.<br />

Psc Uo (V) Ra (mΩ) Xa (mΩ)<br />

250 MVA 420 0.07 0.7<br />

500 MVA 420 0.035 0.351<br />

Fig. G34 : The impedance <strong>of</strong> the MV network referred to the LV side <strong>of</strong> the MV/LV transformer<br />

A formula which makes this deduction and at the same time converts the impedance<br />

to an equivalent value at LV is given, as follows:<br />

Zs U<br />

=<br />

Psc<br />

02<br />

where<br />

Zs = impedance <strong>of</strong> the MV voltage network, expessed in milli-ohms<br />

Uo = phase-to-phase no-load LV voltage, expressed in volts<br />

Psc = MV 3-phase short-circuit fault level, expressed in kVA<br />

The upstream (MV) resistance Ra is generally found to be negligible compared with<br />

the corresponding Xa, the latter then being taken as the ohmic value for Za. If more<br />

accurate calculations are necessary, Xa may be taken to be equal to 0.995 Za and<br />

Ra equal to 0.1 Xa.<br />

Figure G36 gives values for Ra and Xa corresponding to the most common MV (2)<br />

short-circuit levels in utility power-supply networks, namely, 250 MVA and 500 MVA.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G25<br />

© Schneider Electric - all rights reserved


G26<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

(1) For 50 Hz systems, but 0.18 mΩ/m length at 60 Hz<br />

4 Short-circuit current<br />

b Transformers (see Fig. G35)<br />

The impedance Ztr <strong>of</strong> a transformer, viewed from the LV terminals, is given by the<br />

formula:<br />

Ztr U Usc<br />

= x<br />

Pn 202<br />

100<br />

where:<br />

U 20 = open-circuit secondary phase-to-phase voltage expressed in volts<br />

Pn = rating <strong>of</strong> the transformer (in kVA)<br />

Usc = the short-circuit impedance voltage <strong>of</strong> the transformer expressed in %<br />

The transformer windings resistance Rtr can be derived from the total losses as<br />

follows:<br />

2<br />

Pcu x 10<br />

Pcu = 3I<br />

n x Rtr so that Rtr =<br />

2<br />

3I<br />

n<br />

3<br />

in milli-ohms<br />

where<br />

Pcu = total losses in watts<br />

In = nominal full-load current in amps<br />

Rtr = resistance <strong>of</strong> one phase <strong>of</strong> the transformer in milli-ohms (the LV and<br />

corresponding MV winding for one LV phase are included in this resistance value).<br />

2 2<br />

Xtr = Ztr −Rtr<br />

Rated Oil-immersed Cast-resin<br />

For an approximate calculation Rtr may be ignored since X ≈ Z in standard<br />

distribution type transformers.<br />

Power Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ) Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ)<br />

(kVA)<br />

100 4 37.9 59.5 70.6 6 37.0 99.1 105.8<br />

160 4 16.2 41.0 44.1 6 18.6 63.5 66.2<br />

200 4 11.9 33.2 35.3 6 14.1 51.0 52.9<br />

250 4 9.2 26.7 28.2 6 10.7 41.0 42.3<br />

315 4 6.2 21.5 22.4 6 8.0 32.6 33.6<br />

400 4 5.1 16.9 17.6 6 6.1 25.8 26.5<br />

500 4 3.8 13.6 14.1 6 4.6 20.7 21.2<br />

630 4 2.9 10.8 11.2 6 3.5 16.4 16.8<br />

800 6 2.9 12.9 13.2 6 2.6 13.0 13.2<br />

1,000 6 2.3 10.3 10.6 6 1.9 10.4 10.6<br />

1,250 6 1.8 8.3 8.5 6 1.5 8.3 8.5<br />

1,600 6 1.4 6.5 6.6 6 1.1 6.5 6.6<br />

2,000 6 1.1 5.2 5.3 6 0.9 5.2 5.3<br />

Fig. G35 : Resistance, reactance and impedance values for typical distribution 400 V transformers with MV windings y 20 kV<br />

b Circuit-breakers<br />

In LV circuits, the impedance <strong>of</strong> circuit-breakers upstream <strong>of</strong> the fault location must<br />

be taken into account. The reactance value conventionally assumed is 0.15 mΩ per<br />

CB, while the resistance is neglected.<br />

b Busbars<br />

The resistance <strong>of</strong> busbars is generally negligible, so that the impedance is practically<br />

all reactive, and amounts to approximately 0.15 mΩ/metre (1) length for LV busbars<br />

(doubling the spacing between the bars increases the reactance by about 10% only).<br />

b Circuit conductors<br />

L<br />

The resistance <strong>of</strong> a conductor is given by the formula: Rc = ρ<br />

S<br />

where<br />

ρ = the resistivity constant <strong>of</strong> the conductor material at the normal operating<br />

temperature being:<br />

v 22.5 mΩ.mm 2 /m for copper<br />

v 36 mΩ.mm 2 /m for aluminium<br />

L = length <strong>of</strong> the conductor in m<br />

S = c.s.a. <strong>of</strong> conductor in mm 2<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

Cable reactance values can be obtained from the manufacturers. For c.s.a. <strong>of</strong> less<br />

than 50 mm 2 reactance may be ignored. In the absence <strong>of</strong> other information, a value<br />

<strong>of</strong> 0.08 mΩ/metre may be used (for 50 Hz systems) or 0.096 mΩ/metre (for 60 Hz<br />

systems). For prefabricated bus-trunking and similar pre-wired ducting systems, the<br />

manufacturer should be consulted.<br />

b Motors<br />

At the instant <strong>of</strong> short-circuit, a running motor will act (for a brief period) as a<br />

generator, and feed current into the fault.<br />

In general, this fault-current contribution may be ignored. However, for more precise<br />

calculation, particularly in the case <strong>of</strong> large motors and/or numerous smaller motors,<br />

the total contribution can be estimated from the formula:<br />

Iscm = 3.5 In from each motor i.e. 3.5mIn for m similar motors operating concurrently.<br />

The motors concerned will be the 3-phase motors only; single-phase-motor<br />

contribution being insignificant.<br />

b Fault-arc resistance<br />

Short-circuit faults generally form an arc which has the properties <strong>of</strong> a resistance.<br />

The resistance is not stable and its average value is low, but at low voltage this<br />

resistance is sufficient to reduce the fault-current to some extent. Experience has<br />

shown that a reduction <strong>of</strong> the order <strong>of</strong> 20% may be expected. This phenomenon will<br />

effectively ease the current-breaking duty <strong>of</strong> a CB, but affords no relief for its faultcurrent<br />

making duty.<br />

b Recapitulation table (see Fig. G36)<br />

Parts <strong>of</strong> power-supply system R (mΩ) X (mΩ)<br />

M<br />

Supply network<br />

Figure G34<br />

Transformer<br />

Figure G35<br />

Rtr is <strong>of</strong>ten negligible compared to Xtr<br />

for transformers > 100 kVA<br />

with Ztr<br />

Circuit-breaker Negligible XD = 0.15 mΩ/pole<br />

U Usc<br />

= x<br />

Pn 202<br />

100<br />

Busbars Negligible for S > 200 mm2 in the formula: XB = 0.15 mΩ/m<br />

(1)<br />

Circuit conductors (2) (1) L<br />

R = ρ<br />

S<br />

L<br />

R = ρ<br />

S<br />

Cables: Xc = 0.08 mΩ/m<br />

Motors See Sub-clause 4.2 Motors<br />

(<strong>of</strong>ten negligible at LV)<br />

Three-phase short<br />

circuit current in kA Isc =<br />

3<br />

U20<br />

2 2<br />

RT + XT<br />

U 20: Phase-to-phase no-load secondary voltage <strong>of</strong> MV/LV transformer (in volts).<br />

Psc: 3-phase short-circuit power at MV terminals <strong>of</strong> the MV/LV transformers (in kVA).<br />

Pcu: 3-phase total losses <strong>of</strong> the MV/LV transformer (in watts).<br />

Pn: Rating <strong>of</strong> the MV/LV transformer (in kVA).<br />

Usc: Short-circuit impedance voltage <strong>of</strong> the MV/LV transfomer (in %).<br />

R T : Total resistance. X T: Total reactance<br />

(1) ρ = resistivity at normal temperature <strong>of</strong> conductors in service<br />

b ρ = 22.5 mΩ x mm 2 /m for copper<br />

b ρ = 36 mΩ x mm 2 /m for aluminium<br />

(2) If there are several conductors in parallel per phase, then divide the resistance <strong>of</strong> one conductor by the number <strong>of</strong><br />

conductors. The reactance remains practically unchanged.<br />

Fig. G36 : Recapitulation table <strong>of</strong> impedances for different parts <strong>of</strong> a power-supply system<br />

4 Short-circuit current<br />

Pcu<br />

=<br />

3 n<br />

2<br />

x 10<br />

Rtr<br />

I<br />

3<br />

Ra<br />

= 0.1<br />

Xa<br />

U<br />

Xa = 0 995 Za Za = 20<br />

Psc<br />

2 2<br />

Ztr −Rtr<br />

2<br />

. ;<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G27<br />

© Schneider Electric - all rights reserved


G28<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

LV <strong>installation</strong> R (mΩ) X (mΩ) RT (mΩ) XT (mΩ)<br />

MV network<br />

Psc = 500 MVA<br />

0.035 0.351<br />

Transformer<br />

20 kV/420 V<br />

Pn = 1000 kVA<br />

Usc = 5%<br />

Pcu = 13.3 x 10<br />

2.24 8.10<br />

3 watts<br />

Single-core cables<br />

5 m copper<br />

4 x 240 mm<br />

Xc = 0.08 x 5 = 0.40 2.41 8.85 Isc1 = 26 kA<br />

2 /phase<br />

Main<br />

circuit-breaker<br />

RD = 0 XD = 0.15<br />

Busbars<br />

10 m<br />

RB = 0 XB = 1.5 2.41 10.5 Isc2 = 22 kA<br />

Three-core cable<br />

100 m<br />

95 mm<br />

Xc = 100 x 0.08 = 8 26.1 18.5 Isc3 = 7.4 kA<br />

2 copper<br />

Three-core cable<br />

20 m<br />

10 mm<br />

Xc = 20 x 0.08 = 1.6 71.1 20.1 Isc4 = 3.2 kA<br />

2 22.5 5<br />

Rc = x = 0.12<br />

4 240<br />

100<br />

Rc = 22.5 x = 2 3.68<br />

95<br />

copper<br />

final circuits<br />

Rc = 22.5 x =<br />

20<br />

45<br />

10<br />

Fig. G37 : Example <strong>of</strong> short-circuit current calculations for a LV <strong>installation</strong> supplied at 400 V (nominal) from a 1,000 kVA MV/LV transformer<br />

400 V<br />

47,5 mm 2 , Cu<br />

20 m<br />

IB = 55 A IB = 160 A<br />

Isc = 28 kA<br />

Isc = ?<br />

Fig. G38 : Determination <strong>of</strong> downstream short-circuit current<br />

level Isc using Figure G39<br />

4 Short-circuit current<br />

b Example <strong>of</strong> short-circuit calculations (see Fig. G37)<br />

4.3 Isc at the receiving end <strong>of</strong> a feeder as a function<br />

<strong>of</strong> the Isc at its sending end<br />

The network shown in Figure G38 typifies a case for the application <strong>of</strong> Figure G39<br />

next page, derived by the «method <strong>of</strong> composition» (mentioned in <strong>Chapter</strong> F Subclause<br />

6.2). These tables give a rapid and sufficiently accurate value <strong>of</strong> short-circuit<br />

current at a point in a network, knowing:<br />

b The value <strong>of</strong> short-circuit current upstream <strong>of</strong> the point considered<br />

b The length and composition <strong>of</strong> the circuit between the point at which the shortcircuit<br />

current level is known, and the point at which the level is to be determined<br />

It is then sufficient to select a circuit-breaker with an appropriate short-circuit fault<br />

rating immediately above that indicated in the tables.<br />

If more precise values are required, it is possible to make a detailled calculation<br />

(see Sub-Clause 4.2) or to use a s<strong>of</strong>tware package, such as Ecodial. In such a case,<br />

moreover, the possibility <strong>of</strong> using the cascading technique should be considered,<br />

in which the use <strong>of</strong> a current limiting circuit-breaker at the upstream position would<br />

allow all circuit-breakers downstream <strong>of</strong> the limiter to have a short-circuit current<br />

rating much lower than would otherwise be necessary (See chapter H Sub-Clause 4.5).<br />

Method<br />

Select the c.s.a. <strong>of</strong> the conductor in the column for copper conductors (in this<br />

example the c.s.a. is 47.5 mm 2 ).<br />

Search along the row corresponding to 47.5 mm 2 for the length <strong>of</strong> conductor equal<br />

to that <strong>of</strong> the circuit concerned (or the nearest possible on the low side). Descend<br />

vertically the column in which the length is located, and stop at a row in the middle<br />

section (<strong>of</strong> the 3 sections <strong>of</strong> the Figure) corresponding to the known fault-current<br />

level (or the nearest to it on the high side).<br />

In this case 30 kA is the nearest to 28 kA on the high side. The value <strong>of</strong> short-circuit<br />

current at the downstream end <strong>of</strong> the 20 metre circuit is given at the intersection <strong>of</strong><br />

the vertical column in which the length is located, and the horizontal row corresponding<br />

to the upstream Isc (or nearest to it on the high side).<br />

This value in the example is seen to be 14.7 kA.<br />

The procedure for aluminium conductors is similar, but the vertical column must be<br />

ascended into the middle section <strong>of</strong> the table.<br />

In consequence, a DIN-rail-mounted circuit-breaker rated at 63 A and Isc <strong>of</strong> 25 kA<br />

(such as a NG 125N unit) can be used for the 55 A circuit in Figure G38.<br />

A Compact rated at 160 A with an Isc capacity <strong>of</strong> 25 kA (such as a NS160 unit) can<br />

be used to protect the 160 A circuit.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Isc =<br />

420<br />

2 2<br />

3 RT + XT


G - Sizing and protection <strong>of</strong> conductors<br />

4 Short-circuit current<br />

Copper 230 V / 400 V<br />

c.s.a. <strong>of</strong> phase Length <strong>of</strong> circuit (in metres)<br />

conductors (mm 2 )<br />

1.5 1.3 1.8 2.6 3.6 5.2 7.3 10.3 14.6 21<br />

2.5 1.1 1.5 2.1 3.0 4.3 6.1 8.6 12.1 17.2 24 34<br />

4 1.2 1.7 2.4 3.4 4.9 6.9 9.7 13.7 19.4 27 39 55<br />

6 1.8 2.6 3.6 5.2 7.3 10.3 14.6 21 29 41 58 82<br />

10 2.2 3.0 4.3 6.1 8.6 12.2 17.2 24 34 49 69 97 137<br />

16 1.7 2.4 3.4 4.9 6.9 9.7 13.8 19.4 27 39 55 78 110 155 220<br />

25 1.3 1.9 2.7 3.8 5.4 7.6 10.8 15.2 21 30 43 61 86 121 172 243 343<br />

35 1.9 2.7 3.8 5.3 7.5 10.6 15.1 21 30 43 60 85 120 170 240 340 480<br />

47.5 1.8 2.6 3.6 5.1 7.2 10.2 14.4 20 29 41 58 82 115 163 231 326 461<br />

70 2.7 3.8 5.3 7.5 10.7 15.1 21 30 43 60 85 120 170 240 340<br />

95 2.6 3.6 5.1 7.2 10.2 14.5 20 29 41 58 82 115 163 231 326 461<br />

120 1.6 2.3 3.2 4.6 6.5 9.1 12.9 18.3 26 37 52 73 103 146 206 291 412<br />

150 1.2 1.8 2.5 3.5 5.0 7.0 9.9 14.0 19.8 28 40 56 79 112 159 224 317 448<br />

185 1.5 2.1 2.9 4.2 5.9 8.3 11.7 16.6 23 33 47 66 94 133 187 265 374 529<br />

240 1.8 2.6 3.7 5.2 7.3 10.3 14.6 21 29 41 58 83 117 165 233 330 466 659<br />

300 2.2 3.1 4.4 6.2 8.8 12.4 17.6 25 35 50 70 99 140 198 280 396 561<br />

2x120 2.3 3.2 4.6 6.5 9.1 12.9 18.3 26 37 52 73 103 146 206 292 412 583<br />

2x150 2.5 3.5 5.0 7.0 9.9 14.0 20 28 40 56 79 112 159 224 317 448 634<br />

2x185 2.9 4.2 5.9 8.3 11.7 16.6 23 33 47 66 94 133 187 265 375 530 749<br />

553x120 3.4 4.9 6.9 9.7 13.7 19.4 27 39 55 77 110 155 219 309 438 619<br />

3x150 3.7 5.3 7.5 10.5 14.9 21 30 42 60 84 119 168 238 336 476 672<br />

3x185 4.4 6.2 8.8 12.5 17.6 25 35 50 70 100 141 199 281 398 562<br />

Isc upstream Isc downstream<br />

(in kA) (in kA)<br />

100 93 90 87 82 77 70 62 54 45 37 29 22 17.0 12.6 9.3 6.7 4.9 3.5 2.5 1.8 1.3 0.9<br />

90 84 82 79 75 71 65 58 51 43 35 28 22 16.7 12.5 9.2 6.7 4.8 3.5 2.5 1.8 1.3 0.9<br />

80 75 74 71 68 64 59 54 47 40 34 27 21 16.3 12.2 9.1 6.6 4.8 3.5 2.5 1.8 1.3 0.9<br />

70 66 65 63 61 58 54 49 44 38 32 26 20 15.8 12.0 8.9 6.6 4.8 3.4 2.5 1.8 1.3 0.9<br />

60 57 56 55 53 51 48 44 39 35 29 24 20 15.2 11.6 8.7 6.5 4.7 3.4 2.5 1.8 1.3 0.9<br />

50 48 47 46 45 43 41 38 35 31 27 22 18.3 14.5 11.2 8.5 6.3 4.6 3.4 2.4 1.7 1.2 0.9<br />

40 39 38 38 37 36 34 32 30 27 24 20 16.8 13.5 10.6 8.1 6.1 4.5 3.3 2.4 1.7 1.2 0.9<br />

35 34 34 33 33 32 30 29 27 24 22 18.8 15.8 12.9 10.2 7.9 6.0 4.5 3.3 2.4 1.7 1.2 0.9<br />

30 29 29 29 28 27 27 25 24 22 20 17.3 14.7 12.2 9.8 7.6 5.8 4.4 3.2 2.4 1.7 1.2 0.9<br />

25 25 24 24 24 23 23 22 21 19.1 17.4 15.5 13.4 11.2 9.2 7.3 5.6 4.2 3.2 2.3 1.7 1.2 0.9<br />

20 20 20 19.4 19.2 18.8 18.4 17.8 17.0 16.1 14.9 13.4 11.8 10.1 8.4 6.8 5.3 4.1 3.1 2.3 1.7 1.2 0.9<br />

15 14.8 14.8 14.7 14.5 14.3 14.1 13.7 13.3 12.7 11.9 11.0 9.9 8.7 7.4 6.1 4.9 3.8 2.9 2.2 1.6 1.2 0.9<br />

10 9.9 9.9 9.8 9.8 9.7 9.6 9.4 9.2 8.9 8.5 8.0 7.4 6.7 5.9 5.1 4.2 3.4 2.7 2.0 1.5 1.1 0.8<br />

7 7.0 6.9 6.9 6.9 6.9 6.8 6.7 6.6 6.4 6.2 6.0 5.6 5.2 4.7 4.2 3.6 3.0 2.4 1.9 1.4 1.1 0.8<br />

5 5.0 5.0 5.0 4.9 4.9 4.9 4.9 4.8 4.7 4.6 4.5 4.3 4.0 3.7 3.4 3.0 2.5 2.1 1.7 1.3 1.0 0.8<br />

4 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.7 3.6 3.5 3.3 3.1 2.9 2.6 2.2 1.9 1.6 1.2 1.0 0.7<br />

3 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.3 2.1 1.9 1.6 1.4 1.1 0.9 0.7<br />

2 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.7 1.6 1.4 1.3 1.1 1.0 0.8 0.6<br />

1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.8 0.8 0.7 0.6 0.6 0.5<br />

Aluminium 230 V / 400 V<br />

c.s.a. <strong>of</strong> phase Length <strong>of</strong> circuit (in metres)<br />

conductors (mm 2 )<br />

2.5 1.4 1.9 2.7 3.8 5.4 7.6 10.8 15.3 22<br />

4 1.1 1.5 2.2 3.1 4.3 6.1 8.6 12.2 17.3 24 35<br />

6 1.6 2.3 3.2 4.6 6.5 9.2 13.0 18.3 26 37 52<br />

10 1.9 2.7 3.8 5.4 7.7 10.8 15.3 22 31 43 61 86<br />

16 2.2 3.1 4.3 6.1 8.7 12.2 17.3 24 35 49 69 98 138<br />

25 1.7 2.4 3.4 4.8 6.8 9.6 13.5 19.1 27 38 54 76 108 153 216<br />

35 1.7 2.4 3.4 4.7 6.7 9.5 13.4 18.9 27 38 54 76 107 151 214 302<br />

47.5 1.6 2.3 3.2 4.6 6.4 9.1 12.9 18.2 26 36 51 73 103 145 205 290 410<br />

70 2.4 3.4 4.7 6.7 9.5 13.4 19.0 27 38 54 76 107 151 214 303 428<br />

95 2.3 3.2 4.6 6.4 9.1 12.9 18.2 26 36 51 73 103 145 205 290 411<br />

120 2.9 4.1 5.8 8.1 11.5 16.3 23 32 46 65 92 130 184 259 367<br />

150 3.1 4.4 6.3 8.8 12.5 17.7 25 35 50 71 100 141 199 282 399<br />

185 2.6 3.7 5.2 7.4 10.4 14.8 21 30 42 59 83 118 167 236 333 471<br />

240 1.2 1.6 2.3 3.3 4.6 6.5 9.2 13.0 18.4 26 37 52 73 104 147 208 294 415<br />

300 1.4 2.0 2.8 3.9 5.5 7.8 11.1 15.6 22 31 44 62 88 125 177 250 353 499<br />

2x120 1.4 2.0 2.9 4.1 5.8 8.1 11.5 16.3 23 33 46 65 92 130 184 260 367 519<br />

2x150 1.6 2.2 3.1 4.4 6.3 8.8 12.5 17.7 25 35 50 71 100 141 200 282 399<br />

2x185 1.9 2.6 3.7 5.2 7.4 10.5 14.8 21 30 42 59 83 118 167 236 334 472<br />

2x240 2.3 3.3 4.6 6.5 9.2 13.0 18.4 26 37 52 74 104 147 208 294 415 587<br />

3x120 2.2 3.1 4.3 6.1 8.6 12.2 17.3 24 34 49 69 97 138 195 275 389 551<br />

3x150 2.3 3.3 4.7 6.6 9.4 13.3 18.8 27 37 53 75 106 150 212 299 423 598<br />

3x185 2.8 3.9 5.5 7.8 11.1 15.7 22 31 44 63 89 125 177 250 354 500 707<br />

3x240 3.5 4.9 6.9 9.8 13.8 19.5 28 39 55 78 110 156 220 312 441 623<br />

Note: for a 3-phase system having 230 V between phases, divide the above lengths by 3<br />

Fig. G39 : Isc at a point downstream, as a function <strong>of</strong> a known upstream fault-current value and the length and c.s.a. <strong>of</strong> the intervening conductors,<br />

in a 230/400 V 3-phase system<br />

4.4 Short-circuit current supplied by a generator or<br />

an inverter: Please refer to <strong>Chapter</strong> N<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G29<br />

© Schneider Electric - all rights reserved


G30<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

If a protective device in a circuit is intended<br />

only to protect against short-circuit faults, it is<br />

essential that it will operate with certainty at the<br />

lowest possible level <strong>of</strong> short-circuit current that<br />

can occur on the circuit<br />

Circuit breaker with<br />

instantaneous magnetic<br />

short-circuit protective relay only<br />

Load breaking contactor<br />

with thermal overload relay<br />

Fig. G41 : Circuit protected by circuit-breaker without thermal<br />

overload relay<br />

S1<br />

Load with<br />

incorporated<br />

overload<br />

protection<br />

Circuit breaker D<br />

S2 < S1<br />

Fig. G42a : Circuit-breaker D provides protection against shortcircuit<br />

faults as far as and including the load<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

5.1 Calculation <strong>of</strong> minimum levels <strong>of</strong> short-circuit<br />

current<br />

In general, on LV circuits, a single protective device protects against all levels <strong>of</strong><br />

current, from the overload threshold through the maximum rated short-circuit currentbreaking<br />

capability <strong>of</strong> the device.<br />

In certain cases, however, overload protective devices and separate short-circuit<br />

protective devices are used.<br />

Examples <strong>of</strong> such arrangements<br />

Figures G40 to G42 show some common arrangements where overload and<br />

short-circuit protections are achieved by separate devices.<br />

Fig. G40 : Circuit protected by aM fuses<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

aM fuses<br />

(no protection<br />

against overload)<br />

Load breaking contactor<br />

with thermal overload relay<br />

As shown in Figures G40 and G41, the most common circuits using separate<br />

devices control and protect motors.<br />

Figure G42a constitutes a derogation in the basic protection <strong>rules</strong>, and is generally<br />

used on circuits <strong>of</strong> prefabricated bustrunking, lighting rails, etc.<br />

Variable speed drive<br />

Figure G42b shows the functions provided by the variable speed drive, and if<br />

necessary some additional functions provided by devices such as circuit-breaker,<br />

thermal relay, RCD.<br />

Protection to be provided Protection generally provided Additional protection<br />

by the variable speed drive<br />

Cable overload Yes = (1) Not necessary if (1)<br />

Motor overload Yes = (2) Not necessary if (2)<br />

Downstream short-circuit Yes<br />

Variable speed drive overload Yes<br />

Overvoltage Yes<br />

Undervoltage Yes<br />

Loss <strong>of</strong> phase Yes<br />

Upstream short-circuit Circuit-breaker<br />

(short-circuit tripping)<br />

Internal fault Circuit-breaker<br />

(short-circuit and<br />

overload tripping)<br />

Downstream earth fault (self protection) RCD u 300 mA<br />

(indirect contact)<br />

Direct contact fault RCD y 30 mA<br />

Figure G42b : Protection to be provided for variable speeed drive applications


G - Sizing and protection <strong>of</strong> conductors<br />

The protective device must fulfill:<br />

b instantaneous trip setting Im < Isc min for a<br />

circuit-breaker<br />

b fusion current Ia < Isc min for a fuse<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Conditions to be fulfilled<br />

The protective device must therefore satisfy the two following conditions:<br />

b Its fault-current breaking rating must be greater than Isc, the 3-phase short-circuit<br />

current at its point <strong>of</strong> <strong>installation</strong><br />

b Elimination <strong>of</strong> the minimum short-circuit current possible in the circuit, in a time tc<br />

compatible with the thermal constraints <strong>of</strong> the circuit conductors, where:<br />

2 2<br />

K S (valid for tc < 5 seconds)<br />

tc i<br />

I 2<br />

sc min<br />

Comparison <strong>of</strong> the tripping or fusing performance curve <strong>of</strong> protective devices, with<br />

the limit curves <strong>of</strong> thermal constraint for a conductor shows that this condition is<br />

satisfied if:<br />

b Isc (min) > Im (instantaneous or short timedelay circuit-breaker trip setting current<br />

level), (see Fig. G45)<br />

b Isc (min) > Ia for protection by fuses. The value <strong>of</strong> the current Ia corresponds to<br />

the crossing point <strong>of</strong> the fuse curve and the cable thermal withstand curve<br />

(see Fig. G44 and G45)<br />

Fig. G45 : Protection by circuit-breaker<br />

Fig. G46 : Protection by aM-type fuses<br />

Fig. G47 : Protection by gl-type fuses<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

t<br />

t<br />

t<br />

Im<br />

Ia<br />

Ia<br />

t = k2 S 2<br />

I 2<br />

t = k2 S 2<br />

I 2<br />

t = k2 S 2<br />

I 2<br />

I<br />

I<br />

I<br />

G31<br />

© Schneider Electric - all rights reserved


G32<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

In practice this means that the length <strong>of</strong> circuit<br />

downstream <strong>of</strong> the protective device must not<br />

exceed a calculated maximum length:<br />

0.8 U Sph<br />

Lmax<br />

=<br />

2ρI m<br />

(1) For larger c.s.a.’s, the resistance calculated for the<br />

conductors must be increased to account for the non-uniform<br />

current density in the conductor (due to “skin” and “proximity”<br />

effects)<br />

Suitable values are as follows:<br />

150 mm 2 : R + 15%<br />

185 mm 2 : R + 20%<br />

240 mm 2 : R + 25%<br />

300 mm 2 : R + 30%<br />

(2) Or for aluminium according to conductor material<br />

(3) The high value for resistivity is due to the elevated<br />

temperature <strong>of</strong> the conductor when passing short-circuit<br />

current<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Practical method <strong>of</strong> calculating Lmax<br />

The limiting effect <strong>of</strong> the impedance <strong>of</strong> long circuit conductors on the value <strong>of</strong><br />

short-circuit currents must be checked and the length <strong>of</strong> a circuit must be restricted<br />

accordingly.<br />

The method <strong>of</strong> calculating the maximum permitted length has already been<br />

demonstrated in TN- and IT- earthed schemes for single and double earth faults,<br />

respectively (see <strong>Chapter</strong> F Sub-clauses 6.2 and 7.2). Two cases are considered<br />

below:<br />

1 - Calculation <strong>of</strong> L max for a 3-phase 3-wire circuit<br />

The minimum short-circuit current will occur when two phase wires are shortcircuited<br />

at the remote end <strong>of</strong> the circuit (see Fig. G46).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

P<br />

0.8 U<br />

Fig G46 : Definition <strong>of</strong> L for a 3-phase 3-wire circuit<br />

L<br />

Load<br />

Using the “conventional method”, the voltage at the point <strong>of</strong> protection P is assumed<br />

to be 80% <strong>of</strong> the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd,<br />

where:<br />

Zd = impedance <strong>of</strong> the fault loop<br />

Isc = short-circuit current (ph/ph)<br />

U = phase-to-phase nominal voltage<br />

For cables y 120 mm2 , reactance may be neglected, so that<br />

2L<br />

Zd = ρ (1)<br />

Sph<br />

where:<br />

ρ = resistivity <strong>of</strong> copper (2) at the average temperature during a short-circuit,<br />

Sph = c.s.a. <strong>of</strong> a phase conductor in mm 2<br />

L = length in metres<br />

The condition for the cable protection is Im y Isc with Im = magnetic trip current<br />

setting <strong>of</strong> the CB.<br />

This leads to Im y<br />

0.8 U<br />

which gives L y 0.8 U Sph<br />

Zd<br />

Lmax<br />

=<br />

2ρI m<br />

with U = 400 V<br />

ρ = 1.25 x 0.018 = 0.023 Ω.mm 2 /m (3)<br />

Lmax = maximum circuit length in metres<br />

k Sph<br />

L<br />

m<br />

max = I<br />

2 - Calculation <strong>of</strong> Lmax for a 3-phase 4-wire 230/400 V circuit<br />

The minimum Isc will occur when the short-circuit is between a phase conductor and<br />

the neutral.<br />

A calculation similar to that <strong>of</strong> example 1 above is required, but using the following<br />

formulae (for cable y 120 mm2 (1) ).<br />

b Where Sn for the neutral conductor = Sph for the phase conductor<br />

3,333 Sph<br />

Lmax<br />

=<br />

Im<br />

b If Sn for the neutral conductor < Sph, then<br />

L 6,666 Sph 1<br />

max =<br />

where m =<br />

Im<br />

1+ m<br />

Sph<br />

Sn<br />

For larger c.s.a.’s than those listed, reactance values must be combined with those <strong>of</strong><br />

resistance to give an impedance. Reactance may be taken as 0.08 mΩ/m for cables<br />

(at 50 Hz). At 60 Hz the value is 0.096 mΩ/m.


G - Sizing and protection <strong>of</strong> conductors<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Tabulated values for Lmax<br />

Figure G47 below gives maximum circuit lengths (Lmax) in metres, for:<br />

b 3-phase 4-wire 400 V circuits (i.e. with neutral) and<br />

b 1-phase 2-wire 230 V circuits<br />

protected by general-purpose circuit-breakers.<br />

In other cases, apply correction factors (given in Figure G53) to the lengths obtained.<br />

The calculations are based on the above methods, and a short-circuit trip level within<br />

± 20% <strong>of</strong> the adjusted value Im.<br />

For the 50 mm 2 c.s.a., calculation are based on a 47.5 mm 2 real c.s.a.<br />

Operating current c.s.a. (nominal cross-sectional-area) <strong>of</strong> conductors (in mm 2 )<br />

level Im <strong>of</strong> the<br />

instantaneous<br />

magnetic tripping<br />

element (in A) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240<br />

50 100 167 267 400<br />

63 79 133 212 317<br />

80 63 104 167 250 417<br />

100 50 83 133 200 333<br />

125 40 67 107 160 267 427<br />

160 31 52 83 125 208 333<br />

200 25 42 67 100 167 267 417<br />

250 20 33 53 80 133 213 333 467<br />

320 16 26 42 63 104 167 260 365 495<br />

400 13 21 33 50 83 133 208 292 396<br />

500 10 17 27 40 67 107 167 233 317<br />

560 9 15 24 36 60 95 149 208 283 417<br />

630 8 13 21 32 63 85 132 185 251 370<br />

700 7 12 19 29 48 76 119 167 226 333 452<br />

800 6 10 17 25 42 67 104 146 198 292 396<br />

875 6 10 15 23 38 61 95 133 181 267 362 457<br />

1000 5 8 13 20 33 53 83 117 158 233 317 400 435<br />

1120 4 7 12 18 30 48 74 104 141 208 283 357 388 459<br />

1250 4 7 11 16 27 43 67 93 127 187 253 320 348 411<br />

1600 5 8 13 21 33 52 73 99 146 198 250 272 321 400<br />

2000 4 7 10 17 27 42 58 79 117 158 200 217 257 320<br />

2500 5 8 13 21 33 47 63 93 127 160 174 206 256<br />

3200 4 6 10 17 26 36 49 73 99 125 136 161 200<br />

4000 5 8 13 21 29 40 58 79 100 109 128 160<br />

5000 4 7 11 17 23 32 47 63 80 87 103 128<br />

6300 5 8 13 19 25 37 50 63 69 82 102<br />

8000 4 7 10 15 20 29 40 50 54 64 80<br />

10000 5 8 12 16 23 32 40 43 51 64<br />

12500 4 7 9 13 19 25 32 35 41 51<br />

Fig. G47 : Maximum circuit lengths in metres for copper conductors (for aluminium, the lengths must be multiplied by 0.62)<br />

Figures G48 to G50 next page give maximum circuit length (Lmax) in metres for:<br />

b 3-phase 4-wire 400 V circuits (i.e. with neutral) and<br />

b 1-phase 2-wire 230 V circuits<br />

protected in both cases by domestic-type circuit-breakers or with circuit-breakers<br />

having similar tripping/current characteristics.<br />

In other cases, apply correction factors to the lengths indicated. These factors are<br />

given in Figure G51 next page.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G33<br />

© Schneider Electric - all rights reserved


G34<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G48 : Maximum length <strong>of</strong> copper-conductor circuits in metres protected by B-type circuit-breakers<br />

Fig. G49 : Maximum length <strong>of</strong> copper-conductor circuits in metres protected by C-type circuit-breakers<br />

Fig. G50 : Maximum length <strong>of</strong> copper-conductor circuits in metres protected by D-type circuit-breakers<br />

Fig. G51 : Correction factor to apply to lengths obtained from Figures G47 to G50<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Rated current <strong>of</strong> c.s.a. (nominal cross-sectional-area) <strong>of</strong> conductors (in mm 2 )<br />

circuit-breakers (in A) 1.5 2.5 4 6 10 16 25 35 50<br />

6 200 333 533 800<br />

10 120 200 320 480 800<br />

16 75 125 200 300 500 800<br />

20 60 100 160 240 400 640<br />

25 48 80 128 192 320 512 800<br />

32 37 62 100 150 250 400 625 875<br />

40 30 50 80 120 200 320 500 700<br />

50 24 40 64 96 160 256 400 560 760<br />

63 19 32 51 76 127 203 317 444 603<br />

80 15 25 40 60 100 160 250 350 475<br />

100 12 20 32 48 80 128 200 280 380<br />

125 10 16 26 38 64 102 160 224 304<br />

Rated current <strong>of</strong> c.s.a. (nominal cross-sectional-area) <strong>of</strong> conductors (in mm2)<br />

circuit-breakers (in A) 1.5 2.5 4 6 10 16 25 35 50<br />

6 100 167 267 400 667<br />

10 60 100 160 240 400 640<br />

16 37 62 100 150 250 400 625 875<br />

20 30 50 80 120 200 320 500 700<br />

25 24 40 64 96 160 256 400 560 760<br />

32 18.0 31 50 75 125 200 313 438 594<br />

40 15.0 25 40 60 100 160 250 350 475<br />

50 12.0 20 32 48 80 128 200 280 380<br />

63 9.5 16.0 26 38 64 102 159 222 302<br />

80 7.5 12.5 20 30 50 80 125 175 238<br />

100 6.0 10.0 16.0 24 40 64 100 140 190<br />

125 5.0 8.0 13.0 19.0 32 51 80 112 152<br />

Rated current <strong>of</strong> c.s.a. (nominal cross-sectional-area) <strong>of</strong> conductors (in mm2)<br />

circuit-breakers (in A) 1.5 2.5 4 6 10 16 25 35 50<br />

1 429 714<br />

2 214 357 571 857<br />

3 143 238 381 571 952<br />

4 107 179 286 429 714<br />

6 71 119 190 286 476 762<br />

10 43 71 114 171 286 457 714<br />

16 27 45 71 107 179 286 446 625 848<br />

20 21 36 57 86 143 229 357 500 679<br />

25 17.0 29 46 69 114 183 286 400 543<br />

32 13.0 22 36 54 89 143 223 313 424<br />

40 11.0 18.0 29 43 71 114 179 250 339<br />

50 9.0 14.0 23 34 57 91 143 200 271<br />

63 7.0 11.0 18.0 27 45 73 113 159 215<br />

80 5.0 9.0 14.0 21 36 57 89 125 170<br />

100 4.0 7.0 11.0 17.0 29 46 71 100 136<br />

125 3.0 6.0 9.0 14.0 23 37 57 80 109<br />

Circuit detail<br />

3-phase 3-wire 400 V circuit or 1-phase 2-wire 400 V circuit (no neutral) 1.73<br />

1-phase 2-wire (phase and neutral) 230 V circuit 1<br />

3-phase 4-wire 230/400 V circuit or 2-phase 3-wire 230/400 V circuit Sph / S neutral = 1 1<br />

(i.e with neutral) Sph / S neutral = 2 0.67<br />

Note: IEC 60898 accepts an upper short-circuit-current tripping range <strong>of</strong> 10-50 In for<br />

type D circuit-breakers. European standards, and Figure G50 however, are based on<br />

a range <strong>of</strong> 10-20 In, a range which covers the vast majority <strong>of</strong> domestic and similar<br />

<strong>installation</strong>s.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

In general, verification <strong>of</strong> the thermal-withstand<br />

capability <strong>of</strong> a cable is not necessary, except in<br />

cases where cables <strong>of</strong> small c.s.a. are installed<br />

close to, or feeding directly from, the main<br />

general distribution board<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Examples<br />

Example 1<br />

In a 1-phase 2-wire <strong>installation</strong> the protection is provided by a 50 A circuit-breaker<br />

type NS80HMA, the instantaneous short-circuit current trip, is set at 500 A (accuracy<br />

<strong>of</strong> ± 20%), i.e. in the worst case would require 500 x 1,2 = 600 A to trip. The cable<br />

c.s.a. = 10 mm 2 and the conductor material is copper.<br />

In Figure G47, the row Im = 500 A crosses the column c.s.a. = 10 mm 2 at the value<br />

for Lmax <strong>of</strong> 67 m. The circuit-breaker protects the cable against short-circuit faults,<br />

therefore, provided that its length does not exceed 67 metres.<br />

Example 2<br />

In a 3-phase 3-wire 400 V circuit (without neutral), the protection is provided by a<br />

220 A circuit-breaker type NS250N with an instantaneous short-circuit current trip<br />

unit type MA set at 2,000 A (± 20%), i.e. a worst case <strong>of</strong> 2,400 A to be certain <strong>of</strong><br />

tripping. The cable c.s.a. = 120 mm 2 and the conductor material is copper.<br />

In Figure G47 the row Im = 2,000 A crosses the column c.s.a. = 120 mm 2 at the<br />

value for Lmax <strong>of</strong> 200 m. Being a 3-phase 3-wire 400 V circuit (without neutral), a<br />

correction factor from Figure G51 must be applied. This factor is seen to be 1.73.<br />

The circuit-breaker will therefore protect the cable against short-circuit current,<br />

provided that its length does not exceed 200 x 1.73= 346 metres.<br />

5.2 Verification <strong>of</strong> the withstand capabilities <strong>of</strong><br />

cables under short-circuit conditions<br />

Thermal constraints<br />

When the duration <strong>of</strong> short-circuit current is brief (several tenths <strong>of</strong> a second<br />

up to five seconds maximum) all <strong>of</strong> the heat produced is assumed to remain in<br />

the conductor, causing its temperature to rise. The heating process is said to be<br />

adiabatic, an assumption that simplifies the calculation and gives a pessimistic result,<br />

i.e. a higher conductor temperature than that which would actually occur, since in<br />

practice, some heat would leave the conductor and pass into the insulation.<br />

For a period <strong>of</strong> 5 seconds or less, the relationship I 2 t = k 2 S 2 characterizes the<br />

time in seconds during which a conductor <strong>of</strong> c.s.a. S (in mm 2 ) can be allowed to<br />

carry a current I, before its temperature reaches a level which would damage the<br />

surrounding insulation.<br />

The factor k 2 is given in Figure G52 below.<br />

Insulation Conductor copper (Cu) Conductor aluminium (Al)<br />

PVC 13,225 5,776<br />

XLPE 20,449 8,836<br />

Fig. G52 : Value <strong>of</strong> the constant k 2<br />

The method <strong>of</strong> verification consists in checking that the thermal energy I 2 t per<br />

ohm <strong>of</strong> conductor material, allowed to pass by the protecting circuit-breaker (from<br />

manufacturers catalogues) is less than that permitted for the particular conductor (as<br />

given in Figure G53 below).<br />

S (mm 2 ) PVC XLPE<br />

Copper Aluminium Copper Aluminium<br />

1.5 0.0297 0.0130 0.0460 0.0199<br />

2.5 0.0826 0.0361 0.1278 0.0552<br />

4 0.2116 0.0924 0.3272 0.1414<br />

6 0.4761 0.2079 0.7362 0.3181<br />

10 1.3225 0.5776 2.0450 0.8836<br />

16 3.3856 1.4786 5.2350 2.2620<br />

25 8.2656 3.6100 12.7806 5.5225<br />

35 16.2006 7.0756 25.0500 10.8241<br />

50 29.839 13.032 46.133 19.936<br />

Fig. G53 : Maximum allowable thermal stress for cables I 2 t (expressed in ampere 2 x second x 10 6 )<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G35<br />

© Schneider Electric - all rights reserved


G36<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Example<br />

Is a copper-cored XLPE cable <strong>of</strong> 4 mm 2 c.s.a. adequately protected by a<br />

C60N circuit-breaker?<br />

Figure G53 shows that the I 2 t value for the cable is 0.3272 x 10 6 , while the maximum<br />

“let-through” value by the circuit-breaker, as given in the manufacturer’s catalogue, is<br />

considerably less (< 0.1.10 6 A 2 s).<br />

The cable is therefore adequately protected by the circuit-breaker up to its full rated<br />

breaking capability.<br />

Electrodynamic constraints<br />

For all type <strong>of</strong> circuit (conductors or bus-trunking), it is necessary to take<br />

electrodynamic effects into account.<br />

To withstand the electrodynamic constraints, the conductors must be solidly fixed<br />

and the connection must be strongly tightened.<br />

For bus-trunking, rails, etc. it is also necessary to verify that the electrodynamic<br />

withstand performance is satisfactory when carrying short-circuit currents. The peak<br />

value <strong>of</strong> current, limited by the circuit-breaker or fuse, must be less than the busbar<br />

system rating. Tables <strong>of</strong> coordination ensuring adequate protection <strong>of</strong> their products<br />

are generally published by the manufacturers and provide a major advantage <strong>of</strong> such<br />

systems.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

PE<br />

PE<br />

Correct<br />

Incorrect<br />

Fig. G54 : A poor connection in a series arrangement will leave<br />

all downstream appliances unprotected<br />

PEN<br />

Fig. G55 : Direct connection <strong>of</strong> the PEN conductor to the earth<br />

terminal <strong>of</strong> an appliance<br />

6 Protective earthing conductor<br />

(PE)<br />

6.1 Connection and choice<br />

Protective (PE) conductors provide the bonding connection between all exposed<br />

and extraneous conductive parts <strong>of</strong> an <strong>installation</strong>, to create the main equipotential<br />

bonding system. These conductors conduct fault current due to insulation failure<br />

(between a phase conductor and an exposed conductive part) to the earthed neutral<br />

<strong>of</strong> the source. PE conductors are connected to the main earthing terminal <strong>of</strong> the<br />

<strong>installation</strong>.<br />

The main earthing terminal is connected to the earthing electrode (see <strong>Chapter</strong> E)<br />

by the earthing conductor (grounding electrode conductor in the USA).<br />

PE conductors must be:<br />

b Insulated and coloured yellow and green (stripes)<br />

b Protected against mechanical and chemical damage<br />

In IT and TN-earthed schemes it is strongly recommended that PE conductors<br />

should be installed in close proximity (i.e. in the same conduits, on the same cable<br />

tray, etc.) as the live cables <strong>of</strong> the related circuit. This arrangement ensures the<br />

minimum possible inductive reactance in the earth-fault current carrying circuits.<br />

It should be noted that this arrangement is originally provided by bus-trunking.<br />

Connection<br />

PE conductors must:<br />

b Not include any means <strong>of</strong> breaking the continuity <strong>of</strong> the circuit (such as a switch,<br />

removable links, etc.)<br />

b Connect exposed conductive parts individually to the main PE conductor, i.e. in<br />

parallel, not in series, as shown in Figure G54<br />

b Have an individual terminal on common earthing bars in distribution boards.<br />

TT scheme<br />

The PE conductor need not necessarily be installed in close proximity to the live<br />

conductors <strong>of</strong> the corresponding circuit, since high values <strong>of</strong> earth-fault current are<br />

not needed to operate the RCD-type <strong>of</strong> protection used in TT <strong>installation</strong>s.<br />

IT and TN schemes<br />

The PE or PEN conductor, as previously noted, must be installed as close as<br />

possible to the corresponding live conductors <strong>of</strong> the circuit and no ferro-magnetic<br />

material must be interposed between them. A PEN conductor must always be<br />

connected directly to the earth terminal <strong>of</strong> an appliance, with a looped connection<br />

from the earth terminal to the neutral terminal <strong>of</strong> the appliance (see Fig. G55).<br />

b TN-C scheme (the neutral and PE conductor are one and the same, referred to as<br />

a PEN conductor)<br />

The protective function <strong>of</strong> a PEN conductor has priority, so that all <strong>rules</strong> governing<br />

PE conductors apply strictly to PEN conductors<br />

b TN-C to TN-S transition<br />

The PE conductor for the <strong>installation</strong> is connected to the PEN terminal or bar (see<br />

Fig. G56) generally at the origin <strong>of</strong> the <strong>installation</strong>. Downstream <strong>of</strong> the point <strong>of</strong><br />

separation, no PE conductor can be connected to the neutral conductor.<br />

Fig. G56 : The TN-C-S scheme<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

PEN PE<br />

N<br />

G37<br />

© Schneider Electric - all rights reserved


G38<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G57 : Choice <strong>of</strong> protective conductors (PE)<br />

Fig. G58 : Minimum cross section area <strong>of</strong> protective conductors<br />

Types <strong>of</strong> materials<br />

Materials <strong>of</strong> the kinds mentioned below in Figure G57 can be used for PE conductors,<br />

provided that the conditions mentioned in the last column are satisfied.<br />

Type <strong>of</strong> protective earthing conductor (PE) IT scheme TN scheme TT scheme Conditions to be respected<br />

Supplementary In the same cable Strongly Strongly recommended Correct The PE conductor must<br />

conductor as the phases, or in recommended be insulated to the same<br />

the same cable run level as the phases<br />

Independent <strong>of</strong> the Possible (1) Possible (1) (2) Correct b The PE conductor may<br />

phase conductors be bare or insulated (2)<br />

Metallic housing <strong>of</strong> bus-trunking or <strong>of</strong> other Possible (3) PE possible (3) Correct b The <strong>electrical</strong> continuity<br />

prefabricated prewired ducting (5) PEN possible (8) must be assured by protection<br />

External sheath <strong>of</strong> extruded, mineral- insulated Possible (3) PE possible (3) Possible against deterioration by<br />

conductors (e.g. «pyrotenax» type systems) PEN not recommended (2)(3) Certain extraneous conductive elements<br />

mechanical, chemical and<br />

(6) Possible (4) PE possible (4) Possible<br />

electrochemical hazards<br />

such as: PEN forbidden b Their conductance<br />

b Steel building structures<br />

b Machine frames<br />

b Water pipes<br />

must be adequate<br />

(7)<br />

Metallic cable ways, such as, conduits (9) , Possible (4) PE possible (4) Possible<br />

ducts, trunking, trays, ladders, and so on… PEN not recommended (2)(4)<br />

Forbidden for use as PE conductors, are: metal conduits (9) , gas pipes, hot-water pipes, cable-armouring tapes (9) or wires (9)<br />

(1) In TN and IT schemes, fault clearance is generally achieved by overcurrent devices (fuses or circuit-breakers) so that the impedance<br />

<strong>of</strong> the fault-current loop must be sufficiently low to assure positive protective device operation. The surest means <strong>of</strong> achieving a low loop<br />

impedance is to use a supplementary core in the same cable as the circuit conductors (or taking the same route as the circuit conductors).<br />

This solution minimizes the inductive reactance and therefore the impedance <strong>of</strong> the loop.<br />

(2) The PEN conductor is a neutral conductor that is also used as a protective earth conductor. This means that a current may be flowing<br />

through it at any time (in the absence <strong>of</strong> an earth fault). For this reason an insulated conductor is recommended for PEN operation.<br />

(3) The manufacturer provides the necessary values <strong>of</strong> R and X components <strong>of</strong> the impedances (phase/PE, phase/PEN) to include in the<br />

calculation <strong>of</strong> the earth-fault loop impedance.<br />

(4) Possible, but not recomended, since the impedance <strong>of</strong> the earth-fault loop cannot be known at the <strong>design</strong> stage. Measurements on the<br />

completed <strong>installation</strong> are the only practical means <strong>of</strong> assuring adequate protection for persons.<br />

(5) It must allow the connection <strong>of</strong> other PE conductors. Note: these elements must carry an indivual green/yellow striped visual indication,<br />

15 to 100 mm long (or the letters PE at less than 15 cm from each extremity).<br />

(6) These elements must be demountable only if other means have been provided to ensure uninterrupted continuity <strong>of</strong> protection.<br />

(7) With the agreement <strong>of</strong> the appropriate water authorities.<br />

(8) In the prefabricated pre-wired trunking and similar elements, the metallic housing may be used as a PEN conductor, in parallel with the<br />

corresponding bar, or other PE conductor in the housing.<br />

(9) Forbidden in some countries only. Universally allowed to be used for supplementary equipotential conductors.<br />

6.2 Conductor sizing<br />

Figure G58 below is based on IEC 60364-5-54. This table provides two methods <strong>of</strong><br />

determining the appropriate c.s.a. for both PE or PEN conductors.<br />

c.s.a. <strong>of</strong> phase Minimum c.s.a. <strong>of</strong> Minimum c.s.a. <strong>of</strong><br />

conductors Sph (mm2 ) PE conductor (mm2 ) PEN conductor (mm2 )<br />

Cu Al<br />

Simplified Sph y 16 S (2)<br />

ph Sph<br />

(3)<br />

Sph<br />

(3)<br />

method (1) 16 < Sph y 25 16 16<br />

25 < Sph y 35 25<br />

35 < Sph y 50 Sph /2 Sph /2<br />

Sph > 50 S Sph /2<br />

Adiabatic method Any size<br />

6 Protective earthing conductor<br />

(PE)<br />

SPE/PEN<br />

=<br />

(1) Data valid if the prospective conductor is <strong>of</strong> the same material as the line conductor. Otherwise, a correction factor must be applied.<br />

(2) When the PE conductor is separated from the circuit phase conductors, the following minimum values must be respected:<br />

b 2.5 mm 2 if the PE is mechanically protected<br />

b 4 mm 2 if the PE is not mechanically protected<br />

(3) For mechanical reasons, a PEN conductor, shall have a cross-sectional area not less than 10 mm 2 in copper or 16 mm 2 in aluminium.<br />

(4) Refer to table G53 for the application <strong>of</strong> this formula.<br />

I ⋅t<br />

k<br />

2<br />

(3) (4)<br />

(3) (4)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

(1) Grounding electrode conductor<br />

6 Protective earthing conductor<br />

(PE)<br />

The two methods are:<br />

b Adiabatic (which corresponds with that described in IEC 60724)<br />

This method, while being economical and assuring protection <strong>of</strong> the conductor<br />

against overheating, leads to small c.s.a.’s compared to those <strong>of</strong> the corresponding<br />

circuit phase conductors. The result is sometimes incompatible with the necessity<br />

in IT and TN schemes to minimize the impedance <strong>of</strong> the circuit earth-fault loop, to<br />

ensure positive operation by instantaneous overcurrent tripping devices. This method<br />

is used in practice, therefore, for TT <strong>installation</strong>s, and for dimensioning an earthing<br />

conductor (1) .<br />

b Simplified<br />

This method is based on PE conductor sizes being related to those <strong>of</strong> the<br />

corresponding circuit phase conductors, assuming that the same conductor material<br />

is used in each case.<br />

Thus, in Figure G58 for:<br />

Sph y 16 mm 2 SPE = Sph<br />

16 < Sph y 35 mm2 SPE = 16 mm2 Sph > 35 mm2 Sph<br />

Sph > 35 mm2 SPE<br />

=<br />

2<br />

: when, in a TT scheme, the <strong>installation</strong> earth electrode is beyond the zone <strong>of</strong><br />

Note: when, in a TT scheme, the <strong>installation</strong> earth electrode is beyond the zone <strong>of</strong><br />

influence <strong>of</strong> the source earthing electrode, the c.s.a. <strong>of</strong> the PE conductor can be<br />

limited to 25 mm2 (for copper) or 35 mm2 (for aluminium).<br />

The neutral cannot be used as a PEN conductor unless its c.s.a. is equal to or larger<br />

than 10 mm 2 (copper) or 16 mm 2 (aluminium).<br />

Moreover, a PEN conductor is not allowed in a flexible cable. Since a PEN conductor<br />

functions also as a neutral conductor, its c.s.a. cannot, in any case, be less than that<br />

necessary for the neutral, as discussed in Subclause 7.1 <strong>of</strong> this <strong>Chapter</strong>.<br />

This c.s.a. cannot be less than that <strong>of</strong> the phase conductors unless:<br />

b The kVA rating <strong>of</strong> single-phase loads is less than 10% <strong>of</strong> the total kVA load, and<br />

b Imax likely to pass through the neutral in normal circumstances, is less than the<br />

current permitted for the selected cable size.<br />

Furthermore, protection <strong>of</strong> the neutral conductor must be assured by the protective<br />

devices provided for phase-conductor protection (described in Sub-clause 7.2 <strong>of</strong> this<br />

<strong>Chapter</strong>).<br />

Values <strong>of</strong> factor k to be used in the formulae<br />

These values are identical in several national standards, and the temperature rise<br />

ranges, together with factor k values and the upper temperature limits for the different<br />

classes <strong>of</strong> insulation, correspond with those published in IEC 60724 (1984).<br />

The data presented in Figure G59 are those most commonly needed for LV <strong>installation</strong><br />

<strong>design</strong>.<br />

k values Nature <strong>of</strong> insulation<br />

Polyvinylchloride (PVC) Cross-linked-polyethylene<br />

(XLPE)<br />

Ethylene-propylene-rubber<br />

(EPR)<br />

Final temperature (°C) 160 250<br />

Initial temperature (°C) 30 30<br />

Insulated conductors Copper 143 176<br />

not incoporated in<br />

cables or bare<br />

conductors in contact<br />

with cable jackets<br />

Aluminium<br />

Steel<br />

95<br />

52<br />

116<br />

64<br />

Conductors <strong>of</strong> a Copper 115 143<br />

multi-core-cable Aluminium 76 94<br />

Fig. G59 : k factor values for LV PE conductors, commonly used in national standards and<br />

complying with IEC 60724<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G39<br />

© Schneider Electric - all rights reserved


G40<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

These conductors must be sized according to<br />

national practices<br />

6 Protective earthing conductor<br />

(PE)<br />

6.3 Protective conductor between MV/LV transformer<br />

and the main general distribution board (MGDB)<br />

All phase and neutral conductors upstream <strong>of</strong> the main incoming circuit-breaker<br />

controlling and protecting the MGDB are protected by devices at the MV side <strong>of</strong> the<br />

transformer. The conductors in question, together with the PE conductor, must be<br />

dimensioned accordingly. Dimensioning <strong>of</strong> the phase and neutral conductors from<br />

the transformer is exemplified in Sub-clause 7.5 <strong>of</strong> this chapter (for circuit C1 <strong>of</strong> the<br />

system illustrated in Fig. G65).<br />

Recommended conductor sizes for bare and insulated PE conductors from the<br />

transformer neutral point, shown in Figure G60, are indicated below in Figure G61.<br />

The kVA rating to consider is the sum <strong>of</strong> all (if more than one) transformers<br />

connected to the MGDB.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

PE<br />

Main earth bar<br />

for the LV <strong>installation</strong><br />

Fig. G60 : PE conductor to the main earth bar in the MGDB<br />

MGDB<br />

The table indicates the c.s.a. <strong>of</strong> the conductors in mm 2 according to:<br />

b The nominal rating <strong>of</strong> the MV/LV transformer(s) in kVA<br />

b The fault-current clearance time by the MV protective devices, in seconds<br />

b The kinds <strong>of</strong> insulation and conductor materials<br />

If the MV protection is by fuses, then use the 0.2 seconds columns.<br />

In IT schemes, if an overvoltage protection device is installed (between the<br />

transformer neutral point and earth) the conductors for connection <strong>of</strong> the device<br />

should also be dimensioned in the same way as that described above for<br />

PE conductors.<br />

Transformer Conductor Bare PVC-insulated XLPE-insulated<br />

rating in kVA material conductors conductors conductors<br />

(230/400 V Copper t(s) 0.2 0.5 - 0.2 0.5 - 0.2 0.5 -<br />

output) Aluminium t(s) - 0.2 0.5 - 0.2 0.5 - 0.2 0.5<br />

y100 c.s.a. <strong>of</strong> PE 25 25 25 25 25 25 25 25 25<br />

160 conductors 25 25 35 25 25 50 25 25 35<br />

200 SPE (mm 2 ) 25 35 50 25 35 50 25 25 50<br />

250 25 35 70 35 50 70 25 35 50<br />

315 35 50 70 35 50 95 35 50 70<br />

400 50 70 95 50 70 95 35 50 95<br />

500 50 70 120 70 95 120 50 70 95<br />

630 70 95 150 70 95 150 70 95 120<br />

800 70 120 150 95 120 185 70 95 150<br />

1,000 95 120 185 95 120 185 70 120 150<br />

1,250 95 150 185 120 150 240 95 120 185<br />

Fig. G61 : Recommended c.s.a. <strong>of</strong> PE conductor between the MV/LV transformer and the MGDB,<br />

as a function <strong>of</strong> transformer ratings and fault-clearance times.


G - Sizing and protection <strong>of</strong> conductors<br />

6 Protective earthing conductor<br />

(PE)<br />

6.4 Equipotential conductor<br />

The main equipotential conductor<br />

This conductor must, in general, have a c.s.a. at least equal to half <strong>of</strong> that <strong>of</strong> the<br />

largest PE conductor, but in no case need exceed 25 mm 2 (copper) or 35 mm 2<br />

(aluminium) while its minimum c.s.a. is 6 mm 2 (copper) or 10 mm 2 (aluminium).<br />

Supplementary equipotential conductor<br />

This conductor allows an exposed conductive part which is remote from the nearest<br />

main equipotential conductor (PE conductor) to be connected to a local protective<br />

conductor. Its c.s.a. must be at least half <strong>of</strong> that <strong>of</strong> the protective conductor to which<br />

it is connected.<br />

If it connects two exposed conductive parts (M1 and M2 in Figure G62) its c.s.a.<br />

must be at least equal to that <strong>of</strong> the smaller <strong>of</strong> the two PE conductors (for M1 and<br />

M2). Equipotential conductors which are not incorporated in a cable, should be<br />

protected mechanically by conduits, ducting, etc. wherever possible.<br />

Other important uses for supplementary equipotential conductors concern the<br />

reduction <strong>of</strong> the earth-fault loop impedance, particulary for indirect-contact protection<br />

schemes in TN- or IT-earthed <strong>installation</strong>s, and in special locations with increased<br />

<strong>electrical</strong> risk (refer to IEC 60364-4-41).<br />

Between two exposed conductive parts<br />

if SPE1 y SPE2<br />

then SLS = SPE1<br />

M1<br />

SPE1 SPE2<br />

SPE1<br />

M2<br />

Fig. G62 : Supplementary equipotential conductors<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Between an exposed conductive part<br />

and a metallic structure<br />

SLS =<br />

SPE<br />

SLS SLS<br />

2<br />

M1<br />

Metal structures<br />

(conduits, girders…)<br />

G41<br />

© Schneider Electric - all rights reserved


G42<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

(1) Harmonics <strong>of</strong> order 3 and multiple <strong>of</strong> 3<br />

I 1 H1<br />

Fig. G63a : Triplen harmonics are in phase and cumulate in the Neutral<br />

7 The neutral conductor<br />

The c.s.a. and the protection <strong>of</strong> the neutral conductor, apart from its current-carrying<br />

requirement, depend on several factors, namely:<br />

b The type <strong>of</strong> earthing system, TT, TN, etc.<br />

b The harmonic currents<br />

b The method <strong>of</strong> protection against indirect contact hazards according to the<br />

methods described below<br />

The color <strong>of</strong> the neutral conductor is statutorily blue. PEN conductor, when insulated,<br />

shall be marked by one <strong>of</strong> the following methods :<br />

b Green-and-yellow throughout its length with, in addition, light blue markings at the<br />

terminations, or<br />

b Light blue throughout its length with, in addition, green-and-yellow markings at the<br />

terminations<br />

7.1 Sizing the neutral conductor<br />

Influence <strong>of</strong> the type <strong>of</strong> earthing system<br />

TT and TN-S schemes<br />

b Single-phase circuits or those <strong>of</strong> c.s.a. y 16 mm 2 (copper) 25 mm 2 (aluminium): the<br />

c.s.a. <strong>of</strong> the neutral conductor must be equal to that <strong>of</strong> the phases<br />

b Three-phase circuits <strong>of</strong> c.s.a. > 16 mm 2 copper or 25 mm 2 aluminium: the c.s.a. <strong>of</strong><br />

the neutral may be chosen to be:<br />

v Equal to that <strong>of</strong> the phase conductors, or<br />

v Smaller, on condition that:<br />

- The current likely to flow through the neutral in normal conditions is less than the<br />

permitted value Iz. The influence <strong>of</strong> triplen (1) harmonics must be given particular<br />

consideration or<br />

- The neutral conductor is protected against short-circuit, in accordance with the<br />

following Sub-clause G-7.2<br />

- The size <strong>of</strong> the neutral conductor is at least equal to 16 mm 2 in copper or 25 mm 2 in<br />

aluminium<br />

TN-C scheme<br />

The same conditions apply in theory as those mentioned above, but in practice,<br />

the neutral conductor must not be open-circuited under any circumstances since<br />

it constitutes a PE as well as a neutral conductor (see Figure G58 “c.s.a. <strong>of</strong> PEN<br />

conductor” column).<br />

IT scheme<br />

In general, it is not recommended to distribute the neutral conductor, i.e. a 3-phase<br />

3-wire scheme is preferred. When a 3-phase 4-wire <strong>installation</strong> is necessary,<br />

however, the conditions described above for TT and TN-S schemes are applicable.<br />

Influence <strong>of</strong> harmonic currents<br />

Effects <strong>of</strong> triplen harmonics<br />

Harmonics are generated by the non-linear loads <strong>of</strong> the <strong>installation</strong> (computers,<br />

fluorescent lighting, rectifiers, power electronic choppers) and can produce high<br />

currents in the Neutral. In particular triplen harmonics <strong>of</strong> the three Phases have a<br />

tendency to cumulate in the Neutral as:<br />

b Fundamental currents are out-<strong>of</strong>-phase by 2π/3 so that their sum is zero<br />

b On the other hand, triplen harmonics <strong>of</strong> the three Phases are always positioned in<br />

the same manner with respect to their own fundamental, and are in phase with each<br />

other (see Fig. G63a).<br />

+<br />

I 1 H3<br />

I 2 H1 + I 2 H3<br />

I 3 H1<br />

I N =<br />

3<br />

1<br />

I k H1<br />

+<br />

+<br />

I 3 H3<br />

I k H3<br />

0 + 3<br />

IH3 Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

1


G - Sizing and protection <strong>of</strong> conductors<br />

7 The neutral conductor<br />

Figure G63b shows the load factor <strong>of</strong> the neutral conductor as a function <strong>of</strong> the<br />

percentage <strong>of</strong> 3 rd harmonic.<br />

In practice, this maximum load factor cannot exceed 3.<br />

2.0<br />

1.8<br />

1.6<br />

1.4<br />

1.2<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

I Neutral<br />

I Phase<br />

Fig. G63b : Load factor <strong>of</strong> the neutral conductor vs the percentage <strong>of</strong> 3 rd harmonic<br />

Reduction factors for harmonic currents in four-core and five-core cables with<br />

four cores carrying current<br />

The basic calculation <strong>of</strong> a cable concerns only cables with three loaded conductors<br />

i.e there is no current in the neutral conductor. Because <strong>of</strong> the third harmonic current,<br />

there is a current in the neutral. As a result, this neutral current creates an hot<br />

environment for the 3 phase conductors and for this reason, a reduction factor for<br />

phase conductors is necessary (see Fig. G63).<br />

Reduction factors, applied to the current-carrying capacity <strong>of</strong> a cable with three<br />

loaded conductors, give the current-carrying capacity <strong>of</strong> a cable with four loaded<br />

conductors, where the current in the fourth conductor is due to harmonics. The<br />

reduction factors also take the heating effect <strong>of</strong> the harmonic current in the phase<br />

conductors into account.<br />

b Where the neutral current is expected to be higher than the phase current, then the<br />

cable size should be selected on the basis <strong>of</strong> the neutral current<br />

b Where the cable size selection is based on a neutral current which is not<br />

significantly higher than the phase current, it is necessary to reduce the tabulated<br />

current carrying capacity for three loaded conductors<br />

b If the neutral current is more than 135% <strong>of</strong> the phase current and the cable size is<br />

selected on the basis <strong>of</strong> the neutral current then the three phase conductors will not<br />

be fully loaded. The reduction in heat generated by the phase conductors <strong>of</strong>fsets the<br />

heat generated by the neutral conductor to the extent that it is not necessary to apply<br />

any reduction factor to the current carrying capacity for three loaded conductors.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0<br />

0 20 40 60 80 100<br />

i3 (%)<br />

Third harmonic content Reduction factor<br />

<strong>of</strong> phase current Size selection is based on Size selection is based on<br />

(%) phase current neutral current<br />

0 - 15 1.0 -<br />

15 - 33 0.86 -<br />

33 - 45 - 0.86<br />

> 45 - 1.0<br />

Fig. G63 : Reduction factors for harmonic currents in four-core and five-core cables<br />

(according to IEC 60364-5-52)<br />

G43<br />

© Schneider Electric - all rights reserved


G44<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

7 The neutral conductor<br />

Examples<br />

Consider a three-phase circuit with a <strong>design</strong> load <strong>of</strong> 37 A to be installed using fourcore<br />

PVC insulated cable clipped to a wall, <strong>installation</strong> method C. From Figure G24,<br />

a 6 mm 2 cable with copper conductors has a current-carrying capacity <strong>of</strong> 40 A and<br />

hence is suitable if harmonics are not present in the circuit.<br />

b If 20 % third harmonic is present, then a reduction factor <strong>of</strong> 0,86 is applied and the<br />

<strong>design</strong> load becomes: 37/0.86 = 43 A.<br />

For this load a 10 mm 2 cable is necessary.<br />

b If 40 % third harmonic is present, the cable size selection is based on the neutral<br />

current which is: 37 x 0,4 x 3 = 44,4 A and a reduction factor <strong>of</strong> 0,86 is applied,<br />

leading to a <strong>design</strong> load <strong>of</strong>: 44.4/0.86 = 51.6 A.<br />

For this load a 10 mm 2 cable is suitable.<br />

b If 50 % third harmonic is present, the cable size is again selected on the basis <strong>of</strong><br />

the neutral current, which is: 37 x 0,5 x 3 = 55,5 A .In this case the rating factor is<br />

1 and a 16 mm 2 cable is required.<br />

7.2 Protection <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

Protection against overload<br />

If the neutral conductor is correctly sized (including harmonics), no specific<br />

protection <strong>of</strong> the neutral conductor is required because it is protected by the phase<br />

protection.<br />

However, in practice, if the c.s.a. <strong>of</strong> the neutral conductor is lower than the phase<br />

c.s.a, a neutral overload protection must be installed.<br />

Protection against short-circuit<br />

If the c.s.a. <strong>of</strong> the neutral conductor is lower than the c.s.a. <strong>of</strong> the phase conductor,<br />

the neutral conductor must be protected against short-circuit.<br />

If the c.s.a. <strong>of</strong> the neutral conductor is equal or greater than the c.s.a. <strong>of</strong> the phase<br />

conductor, no specific protection <strong>of</strong> the neutral conductor is required because it is<br />

protected by the phase protection.<br />

7.3 Breaking <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

The need to break or not the neutral conductor is related to the protection against<br />

indirect contact.<br />

In TN-C scheme<br />

The neutral conductor must not be open-circuited under any circumstances since it<br />

constitutes a PE as well as a neutral conductor.<br />

In TT, TN-S and IT schemes<br />

In the event <strong>of</strong> a fault, the circuit-breaker will open all poles, including the neutral<br />

pole, i.e. the circuit-breaker is omnipolar.<br />

The action can only be achieved with fuses in an indirect way, in which the operation<br />

<strong>of</strong> one or more fuses triggers a mechanical trip-out <strong>of</strong> all poles <strong>of</strong> an associated<br />

series-connected load-break switch.<br />

7.4 Isolation <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

It is considered to be the good practice that every circuit be provided with the means<br />

for its isolation.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

Single-phase<br />

(Phase-Neutral)<br />

Single-phase<br />

(Phase-Phase)<br />

Three-phase<br />

four wires<br />

Sn u Sph<br />

Three-phase<br />

four wires<br />

Sn < Sph<br />

Fig. G64 : The various situations in which the neutral conductor may appear<br />

TT TN-C TN-S IT<br />

N N N N<br />

or or<br />

N<br />

7 The neutral conductor<br />

(A) (A)<br />

or or<br />

N N N<br />

N<br />

or<br />

N N N<br />

or<br />

(A) Authorized for TT or TN-S systems if a RCD is installed at the origin <strong>of</strong> the circuit or upstream <strong>of</strong> it, and if no artificial<br />

neutral is distributed downstream <strong>of</strong> its location<br />

(B) The neutral overcurrent protection is not necessary:<br />

b If the neutral conductor is protected against short-circuits by a device placed upstream, or,<br />

b If the circuit is protected by a RCD which sensitivity is less than 15% <strong>of</strong> the neutral admissible current.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N<br />

N<br />

N<br />

(B)<br />

(B)<br />

(B)<br />

G45<br />

© Schneider Electric - all rights reserved


G46<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

Q9<br />

C9<br />

L9<br />

B8<br />

x1<br />

Fig. G65 : Example <strong>of</strong> single-line diagram<br />

Q6<br />

C6<br />

T6<br />

Q7<br />

C7<br />

B2<br />

Circuit 9<br />

T1<br />

C1<br />

Q1<br />

Circuit 6<br />

P = 400 kVA<br />

U = 400 V<br />

Circuit 7<br />

ku = 1.0<br />

ib = 250.00 A<br />

P = 147.22 kW<br />

8 Worked example <strong>of</strong> cable<br />

calculation<br />

Worked example <strong>of</strong> cable calculation (see Fig. G65)<br />

The <strong>installation</strong> is supplied through a 1,000 kVA transformer. The process requires<br />

a high degree <strong>of</strong> supply continuity and this is provided by the <strong>installation</strong> <strong>of</strong> a 500 kVA<br />

400 V standby generator and the adoption <strong>of</strong> a 3-phase 3-wire IT system at the main<br />

general distribution board. The remainder <strong>of</strong> the <strong>installation</strong> is isolated by a 400 kVA<br />

400/400 V transformer. The downstream network is a TT-earthed 3-phase 4-wire<br />

system. Following the single-line diagram shown in Figure G65 below, a reproduction<br />

<strong>of</strong> the results <strong>of</strong> a computer study for the circuit C1, the circuit-breaker Q1, the circuit<br />

C6 and the circuit-breaker Q6. These studies were carried out with ECODIAL 3.3<br />

s<strong>of</strong>tware (a Merlin Gerin product).<br />

This is followed by the same calculations carried out by the method described in this<br />

guide.<br />

1000 kVA 400 V 50 Hz<br />

Circuit 1<br />

Q10<br />

C10<br />

L10<br />

Q3<br />

B4<br />

x1<br />

Switchboard 2<br />

Ks = 1.00<br />

ib = 826.8 A<br />

Q12<br />

C12<br />

L12<br />

Circuit 10<br />

ku = 1.0<br />

ib = 160.00 A<br />

P = 94.22 kW<br />

x1<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G5<br />

C5<br />

Q5<br />

Circuit 12<br />

G<br />

ku = 1.0<br />

ib = 250.00 A<br />

P = 147.22 kW<br />

Q11<br />

C11<br />

L11<br />

x1<br />

P = 500 kVA<br />

U = 400 V<br />

Circuit 5<br />

Switchboard 8<br />

Ks = 1.00<br />

ib = 490.0 A<br />

Circuit 11<br />

Switchboard 4<br />

Ks = 1.00<br />

ib = 250.0 A<br />

ku = 1.0<br />

ib = 80.00 A<br />

P = 47.11 kW


G - Sizing and protection <strong>of</strong> conductors<br />

<strong>General</strong> network characteristics<br />

Earthing system IT<br />

Neutral distributed No<br />

Voltage (V) 400<br />

Frequency (Hz) 50<br />

Transformer T1<br />

Number <strong>of</strong> transformers 1<br />

Upstream fault level (MVA) 500<br />

Rating (kVA) 1,000<br />

Short-circuit impedance voltage (%) 6<br />

Resistance <strong>of</strong> MV network (mΩ) 0.0351<br />

Reactance <strong>of</strong> MV network (mΩ) 0.351<br />

Transformer resistance RT (mΩ) 2.293<br />

Transformer reactance XT (mΩ) 10.333<br />

3-phase short-circuit current Ik3 (kA) 23.3<br />

Cable C1<br />

Maximum load current (A) 1,374<br />

Type <strong>of</strong> insulation PVC<br />

Conductor material Copper<br />

Ambient temperature (°C) 30<br />

Single-core or multi-core cable Single<br />

Installation method F<br />

Number <strong>of</strong> circuits in close proximity (table G21b) 1<br />

Other coefficient 1<br />

Selected cross-sectional area (mm 2 ) 6 x 95<br />

Protective conductor 1 x 120<br />

Length (m) 5<br />

Voltage drop ΔU (%) .122<br />

Voltage drop ΔU total (%) .122<br />

3-phase short-circuit current Ik3 (kA) 23<br />

1-phase-to-earth fault current Id (kA) 17<br />

Circuit-breaker Q1<br />

3-ph short-circuit current Ik3 upstream<br />

<strong>of</strong> the circuit-breaker (kA) 23<br />

Maximum load current (A) 1,374<br />

Number <strong>of</strong> poles and protected poles 3P3D<br />

Circuit-breaker NT 16<br />

Type H 1 – 42 kA<br />

Tripping unit type Micrologic 5 A<br />

Rated current (A) 1,600<br />

Fig. G66 : Partial results <strong>of</strong> calculation carried out with Ecodial s<strong>of</strong>tware (Merlin Gerin)<br />

8 Worked example <strong>of</strong> cable<br />

calculation<br />

Calculation using s<strong>of</strong>tware Ecodial 3.3<br />

The same calculation using the simplified method<br />

recommended in this guide<br />

Dimensioning circuit C1<br />

The MV/LV 1,000 kVA transformer has a rated no-load voltage <strong>of</strong> 420 V. Circuit C1<br />

must be suitable for a current <strong>of</strong><br />

3<br />

1,000 x 10<br />

IB = = 1,374 A per phase<br />

3 x 420<br />

Six single-core PVC-insulated copper cables in parallel will be used for each phase.<br />

These cables will be laid on cable trays according to method F. The “k” correction<br />

factors are as follows:<br />

k 1 = 1 (see table G12, temperature = 30 °C)<br />

k 4 = 0.87 (see table G17, touching cables, 1 tray, u 3 circuits)<br />

Other correction factors are not relevant in this example.<br />

The corrected load current is:<br />

IB<br />

1,374<br />

I' B = = = 1,579 A<br />

k1⋅k4 0. 87<br />

Each conductor will therefore carry 263 A. Figure G21a G23 indicates that the the c.s.a. is is<br />

95 mm2 .<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Busbars B2<br />

Maximum load current (A) 1,374<br />

Type Standard on<br />

edge<br />

Ambient temperature (°C) 30<br />

Dimensions (m and mm) 1 m<br />

2x5 mm x 63 mm<br />

Material Copper<br />

3-ph short-circuit current Ik3 (kA) 23<br />

3-ph peak value <strong>of</strong> short-circuit current Ik (kA) 48<br />

Resistance <strong>of</strong> busbar R (mΩ) 2.52<br />

Reactance <strong>of</strong> busbar X (mΩ) 10.8<br />

Circuit-breaker Q6<br />

3-ph short-circuit current upstream<br />

<strong>of</strong> the circuit-breaker Ik3 (kA) 23<br />

Maximum load current (A) 560<br />

Number <strong>of</strong> poles and protected poles 3P3D<br />

Circuit-breaker NS800<br />

Type N – 50 kA<br />

Tripping unit type Micrologic 2.0<br />

Rated current (A) 800<br />

Limit <strong>of</strong> discrimination (kA) Total<br />

Cable C6<br />

Maximum load current (A) 560<br />

Type <strong>of</strong> insulation PVC<br />

Conductor material Copper<br />

Ambient temperature (°C) 30<br />

Single-core or multi-core cable Single<br />

Installation method F<br />

Number <strong>of</strong> circuits in close proximity (table G20) 1<br />

Other coefficient 1<br />

Selected cross-sectional area (mm 2 ) 1 x 300<br />

Protective conductor 1 x 150<br />

Length (m) 15<br />

Voltage drop ΔU (%) .38<br />

Voltage drop ΔU total (%) .54<br />

3-phase short-circuit current Ik3 (kA) 20<br />

1-phase-to-earth fault current Id (kA) 13.7<br />

Specific sizing constraint Overloads<br />

G47<br />

© Schneider Electric - all rights reserved


G48<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

8 Worked example <strong>of</strong> cable<br />

calculation<br />

The resistances and the inductive reactances for the six conductors in parallel are,<br />

for a length <strong>of</strong> 5 metres:<br />

for a length <strong>of</strong> 5 metres:<br />

22.5 x 5<br />

R = = 0.20 mΩ (cable resistance: 22.5 22.5 m mΩ.mm<br />

95 x 6<br />

Ω<br />

2 /m)<br />

X = 0.08 x 5 = 0.40 mΩ (cable reactance: 0.08 mΩ/m)<br />

Dimensioning circuit C6<br />

Circuit C6 supplies a 400 kVA 3-phase 400/400 V isolating transformer<br />

3<br />

400. 10<br />

Primary current = = 550 A<br />

420. 3<br />

A single-core cable laid laid on on a a cable cable tray tray (without (without any any other other cable) cable) in an in ambient an ambient air air<br />

temperature <strong>of</strong> 30 °C is proposed. The circuit-breaker is set at 560 A<br />

The method <strong>of</strong> <strong>installation</strong> is characterized by the reference letter F, and the “k”<br />

correcting factors are all equal to 1.<br />

A c.s.a. <strong>of</strong> 240 mm 2 is appropriate.<br />

The resistance and inductive reactance are respectively:<br />

22.5 x 15<br />

R = = 1.4 mΩ<br />

240<br />

X = 0.08 x 15 = 1.2 mΩ<br />

Calculation <strong>of</strong> short-circuit currents for the selection <strong>of</strong> circuit-breakers<br />

Q 1 and Q 6 (see Fig. G67)<br />

Circuits components R (mΩ) X (mΩ) Z (mΩ) Ikmax (kA)<br />

parts<br />

500 MVA at 0.04 0.36<br />

the MV source network<br />

1 MVA transformer 2.2 9.8 10.0 23<br />

Cable C1 0.20 0.4<br />

Sub-total for Q1 2.44 10.6 10.9 23<br />

Busbar B2 3.6 7.2<br />

Cable C6 1.4 1.2<br />

Sub-total for Q6 4.0 8.4 9.3 20<br />

Fig. G67 : Example <strong>of</strong> short-circuit current evaluation<br />

The protective conductor<br />

Thermal requirements: Figures G58 and G59 show that, when using the adiabatic<br />

method the c.s.a. for for the the protective earth earth (PE) (PE) conductor conductor for circuit for C1 circuit will be: C1 will be:<br />

34,800 x 0.2<br />

143<br />

2<br />

= 108 mm<br />

A single 120 mm 2 conductor dimensioned for other reasons mentioned later is<br />

therefore largely sufficient, provided that it also satisfies the requirements for indirectcontact<br />

protection (i.e. that its impedance is sufficiently low).<br />

For the circuit C6, the c.s.a. <strong>of</strong> its PE conductor should be:<br />

29,300 x 0.2<br />

2<br />

= 92 mm<br />

143<br />

In this case a 95 mm2 conductor may be adequate if the indirect-contact protection<br />

conditions are also satisfied.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


G - Sizing and protection <strong>of</strong> conductors<br />

8 Worked example <strong>of</strong> cable<br />

calculation<br />

Protection against indirect-contact hazards<br />

For circuit C6 <strong>of</strong> Figure G65, Figures F45 and F61, or the formula given page F27<br />

may be used for a 3-phase 3-wire circuit.<br />

The maximum permitted length <strong>of</strong> the circuit is given by :<br />

0.8 x 240 x 230 3 x 1,000<br />

Lmax<br />

2 x 22.5 1+ 240<br />

=<br />

= 70 m<br />

⎛ ⎞<br />

x 630 x 11<br />

⎝ 95 ⎠<br />

(The value in the denominator 630 x 11 I=<br />

Im i.e. the current level at which the<br />

instantaneous short-circuit magnetic trip <strong>of</strong> the 630 A circuit-breaker operates).<br />

The length <strong>of</strong> 15 metres is therefore fully protected by “instantaneous” overcurrent<br />

devices.<br />

Voltage drop<br />

From Figure G28 it can be seen that:<br />

b For the cable C1 (6 x 95mm2 per phase)<br />

-1 -1<br />

∆U<br />

0.42 (V A km ) x 1,374 (A) x 0.008 = = 1.54 V<br />

3<br />

∆U%<br />

100 = 1.54 = 0.38%<br />

400 x<br />

b For the circuit C6<br />

∆U<br />

0.21 (V A km ) x 433 (A) x 0.015 -1 -1<br />

= = 1.36 V<br />

3<br />

∆U%<br />

100 = 1.36 = 0.34%<br />

400 x<br />

At the circuit terminals <strong>of</strong> the LV/LV transformer the percentage volt-drop<br />

ΔU% = 0.72%<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G49<br />

© Schneider Electric - all rights reserved


2<br />

3<br />

4<br />

<strong>Chapter</strong> H<br />

LV switchgear: functions &<br />

selection<br />

Contents<br />

The basic functions <strong>of</strong> LV switchgear H2<br />

1.1 Electrical protection H2<br />

1.2 Isolation H3<br />

1.3 Switchgear control H4<br />

The switchgear H5<br />

2.1 Elementary switching devices H5<br />

2.2 Combined switchgear elements H9<br />

Choice <strong>of</strong> switchgear H 0<br />

3.1 Tabulated functional capabilities H10<br />

3.2 Switchgear selection H10<br />

Circuit-breaker H<br />

4.1 Standards and description H11<br />

4.2 Fundamental characteristics <strong>of</strong> a circuit-breaker H13<br />

4.3 Other characteristics <strong>of</strong> a circuit-breaker H15<br />

4.4 Selection <strong>of</strong> a circuit-breaker H18<br />

4.5 Coordination between circuit-breakers H22<br />

4.6 Discrimination MV/LV in a consumer’s substation H28<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

H2<br />

H - LV switchgear: functions & selection<br />

The role <strong>of</strong> switchgear is:<br />

b Electrical protection<br />

b Safe isolation from live parts<br />

b Local or remote switching<br />

Electrical protection assures:<br />

b Protection <strong>of</strong> circuit elements against the<br />

thermal and mechanical stresses <strong>of</strong> short-circuit<br />

currents<br />

b Protection <strong>of</strong> persons in the event <strong>of</strong><br />

insulation failure<br />

b Protection <strong>of</strong> appliances and apparatus being<br />

supplied (e.g. motors, etc.)<br />

The basic functions <strong>of</strong><br />

LV switchgear<br />

National and international standards define the manner in which electric circuits <strong>of</strong><br />

LV <strong>installation</strong>s must be realized, and the capabilities and limitations <strong>of</strong> the various<br />

switching devices which are collectively referred to as switchgear.<br />

The main functions <strong>of</strong> switchgear are:<br />

b Electrical protection<br />

b Electrical isolation <strong>of</strong> sections <strong>of</strong> an <strong>installation</strong><br />

b Local or remote switching<br />

These functions are summarized below in Figure H .<br />

Electrical protection at low voltage is (apart from fuses) normally incorporated in<br />

circuit-breakers, in the form <strong>of</strong> thermal-magnetic devices and/or residual-currentoperated<br />

tripping devices (less-commonly, residual voltage- operated devices<br />

- acceptable to, but not recommended by IEC).<br />

In addition to those functions shown in Figure H1, other functions, namely:<br />

b Over-voltage protection<br />

b Under-voltage protection<br />

are provided by specific devices (lightning and various other types <strong>of</strong> voltage-surge<br />

arrester, relays associated with contactors, remotely controlled circuit-breakers, and<br />

with combined circuit-breaker/isolators… and so on)<br />

Electrical protection Isolation Control<br />

against<br />

b Overload currents b Isolation clearly indicated b Functional switching<br />

b Short-circuit currents by an authorized fail-pro<strong>of</strong> b Emergency switching<br />

b Insulation failure mechanical indicator b Emergency stopping<br />

b A gap or interposed insulating b Switching <strong>of</strong>f for<br />

barrier between the open mechanical maintenance<br />

contacts, clearly visible<br />

Fig. H1 : Basic functions <strong>of</strong> LV switchgear<br />

. Electrical protection<br />

The aim is to avoid or to limit the destructive or dangerous consequences <strong>of</strong><br />

excessive (short-circuit) currents, or those due to overloading and insulation failure,<br />

and to separate the defective circuit from the rest <strong>of</strong> the <strong>installation</strong>.<br />

A distinction is made between the protection <strong>of</strong>:<br />

b The elements <strong>of</strong> the <strong>installation</strong> (cables, wires, switchgear…)<br />

b Persons and animals<br />

b Equipment and appliances supplied from the <strong>installation</strong><br />

The protection <strong>of</strong> circuits<br />

v Against overload; a condition <strong>of</strong> excessive current being drawn from a healthy<br />

(unfaulted) <strong>installation</strong><br />

v Against short-circuit currents due to complete failure <strong>of</strong> insulation between<br />

conductors <strong>of</strong> different phases or (in TN systems) between a phase and neutral (or<br />

PE) conductor<br />

Protection in these cases is provided either by fuses or circuit-breaker, in the<br />

distribution board at the origin <strong>of</strong> the final circuit (i.e. the circuit to which the load<br />

is connected). Certain derogations to this rule are authorized in some national<br />

standards, as noted in chapter H1 sub-clause 1.4.<br />

The protection <strong>of</strong> persons<br />

v Against insulation failures. According to the system <strong>of</strong> earthing for the <strong>installation</strong><br />

(TN, TT or IT) the protection will be provided by fuses or circuit-breakers, residual<br />

current devices, and/or permanent monitoring <strong>of</strong> the insulation resistance <strong>of</strong> the<br />

<strong>installation</strong> to earth<br />

The protection <strong>of</strong> electric motors<br />

v Against overheating, due, for example, to long term overloading, stalled rotor,<br />

single-phasing, etc. Thermal relays, specially <strong>design</strong>ed to match the particular<br />

characteristics <strong>of</strong> motors are used.<br />

Such relays may, if required, also protect the motor-circuit cable against overload.<br />

Short-circuit protection is provided either by type aM fuses or by a circuit-breaker<br />

from which the thermal (overload) protective element has been removed, or<br />

otherwise made inoperative.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

A state <strong>of</strong> isolation clearly indicated by an<br />

approved “fail-pro<strong>of</strong>” indicator, or the visible<br />

separation <strong>of</strong> contacts, are both deemed to<br />

satisfy the national standards <strong>of</strong> many countries<br />

(1) the concurrent opening <strong>of</strong> all live conductors, while not<br />

always obligatory, is however, strongly recommended (for<br />

reasons <strong>of</strong> greater safety and facility <strong>of</strong> operation). The neutral<br />

contact opens after the phase contacts, and closes before<br />

them (IEC 60947-1).<br />

The basic functions <strong>of</strong><br />

LV switchgear<br />

.2 Isolation<br />

The aim <strong>of</strong> isolation is to separate a circuit or apparatus (such as a motor, etc.) from<br />

the remainder <strong>of</strong> a system which is energized, in order that personnel may carry out<br />

work on the isolated part in perfect safety.<br />

In principle, all circuits <strong>of</strong> an LV <strong>installation</strong> shall have means to be isolated.<br />

In practice, in order to maintain an optimum continuity <strong>of</strong> service, it is preferred to<br />

provide a means <strong>of</strong> isolation at the origin <strong>of</strong> each circuit.<br />

An isolating device must fulfil the following requirements:<br />

b All poles <strong>of</strong> a circuit, including the neutral (except where the neutral is a PEN<br />

conductor) must open (1)<br />

b It must be provided with a locking system in open position with a key (e.g. by<br />

means <strong>of</strong> a padlock) in order to avoid an unauthorized reclosure by inadvertence<br />

b It must comply with a recognized national or international standard<br />

(e.g. IEC 60947-3) concerning clearance between contacts, creepage distances,<br />

overvoltage withstand capability, etc.:<br />

Other requirements apply:<br />

v Verification that the contacts <strong>of</strong> the isolating device are, in fact, open.<br />

The verification may be:<br />

- Either visual, where the device is suitably <strong>design</strong>ed to allow the contacts to be seen<br />

(some national standards impose this condition for an isolating device located at the<br />

origin <strong>of</strong> a LV <strong>installation</strong> supplied directly from a MV/LV transformer)<br />

- Or mechanical, by means <strong>of</strong> an indicator solidly welded to the operating shaft<br />

<strong>of</strong> the device. In this case the construction <strong>of</strong> the device must be such that, in the<br />

eventuality that the contacts become welded together in the closed position, the<br />

indicator cannot possibly indicate that it is in the open position<br />

v Leakage currents. With the isolating device open, leakage currents between the<br />

open contacts <strong>of</strong> each phase must not exceed:<br />

- 0.5 mA for a new device<br />

- 6.0 mA at the end <strong>of</strong> its useful life<br />

v Voltage-surge withstand capability, across open contacts. The isolating device,<br />

when open must withstand a 1.2/50 μs impulse, having a peak value <strong>of</strong> 6, 8 or 12 kV<br />

according to its service voltage, as shown in Figure H2. The device must satisfy<br />

these conditions for altitudes up to 2,000 metres. Correction factors are given in<br />

IEC 60664-1 for altitudes greater than 2,000 metres.<br />

Consequently, if tests are carried out at sea level, the test values must be increased<br />

by 23% to take into account the effect <strong>of</strong> altitude. See standard IEC 60947.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Service (nominal Impulse withstand<br />

voltage peak voltage category<br />

(V) (for 2,000 metres)<br />

(kV)<br />

III IV<br />

230/400 4 6<br />

400/690 6 8<br />

690/1,000 8 12<br />

Fig. H2 : Peak value <strong>of</strong> impulse voltage according to normal service voltage <strong>of</strong> test specimen.<br />

The degrees III and IV are degrees <strong>of</strong> pollution defined in IEC 60664-1<br />

H3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

H4<br />

H - LV switchgear: functions & selection<br />

Switchgear-control functions allow system<br />

operating personnel to modify a loaded system<br />

at any moment, according to requirements,<br />

and include:<br />

b Functional control (routine switching, etc.)<br />

b Emergency switching<br />

b Maintenance operations on the power system<br />

(1) One break in each phase and (where appropriate) one<br />

break in the neutral.<br />

(2) Taking into account stalled motors.<br />

(3) In a TN schema the PEN conductor must never be<br />

opened, since it functions as a protective earthing wire as well<br />

as the system neutral conductor.<br />

The basic functions <strong>of</strong><br />

LV switchgear<br />

.3 Switchgear control<br />

In broad terms “control” signifies any facility for safely modifying a load-carrying<br />

power system at all levels <strong>of</strong> an <strong>installation</strong>. The operation <strong>of</strong> switchgear is an<br />

important part <strong>of</strong> power-system control.<br />

Functional control<br />

This control relates to all switching operations in normal service conditions for<br />

energizing or de-energizing a part <strong>of</strong> a system or <strong>installation</strong>, or an individual piece<br />

<strong>of</strong> equipment, item <strong>of</strong> plant, etc.<br />

Switchgear intended for such duty must be installed at least:<br />

b At the origin <strong>of</strong> any <strong>installation</strong><br />

b At the final load circuit or circuits (one switch may control several loads)<br />

Marking (<strong>of</strong> the circuits being controlled) must be clear and unambiguous.<br />

In order to provide the maximum flexibility and continuity <strong>of</strong> operation, particularly<br />

where the switching device also constitutes the protection (e.g. a circuit-breaker or<br />

switch-fuse) it is preferable to include a switch at each level <strong>of</strong> distribution, i.e. on<br />

each outgoing way <strong>of</strong> all distribution and subdistribution boards.<br />

The manœuvre may be:<br />

b Either manual (by means <strong>of</strong> an operating lever on the switch) or<br />

b Electric, by push-button on the switch or at a remote location (load-shedding and<br />

reconnection, for example)<br />

These switches operate instantaneously (i.e. with no deliberate delay), and those<br />

that provide protection are invariably omni-polar (1) .<br />

The main circuit-breaker for the entire <strong>installation</strong>, as well as any circuit-breakers<br />

used for change-over (from one source to another) must be omni-polar units.<br />

Emergency switching - emergency stop<br />

An emergency switching is intended to de-energize a live circuit which is, or could<br />

become, dangerous (electric shock or fire).<br />

An emergency stop is intended to halt a movement which has become dangerous.<br />

In the two cases:<br />

b The emergency control device or its means <strong>of</strong> operation (local or at remote<br />

location(s)) such as a large red mushroom-headed emergency-stop pushbutton must<br />

be recognizable and readily accessible, in proximity to any position at which danger<br />

could arise or be seen<br />

b A single action must result in a complete switching-<strong>of</strong>f <strong>of</strong> all live conductors (2) (3)<br />

b A “break glass” emergency switching initiation device is authorized, but in<br />

unmanned <strong>installation</strong>s the re-energizing <strong>of</strong> the circuit can only be achieved by<br />

means <strong>of</strong> a key held by an authorized person<br />

It should be noted that in certain cases, an emergency system <strong>of</strong> braking, may<br />

require that the auxiliary supply to the braking-system circuits be maintained until<br />

final stoppage <strong>of</strong> the machinery.<br />

Switching-<strong>of</strong>f for mechanical maintenance work<br />

This operation assures the stopping <strong>of</strong> a machine and its impossibility to be<br />

inadvertently restarted while mechanical maintenance work is being carried out<br />

on the driven machinery. The shutdown is generally carried out at the functional<br />

switching device, with the use <strong>of</strong> a suitable safety lock and warning notice at the<br />

switch mechanism.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

Fig. H5 : Symbol for a disconnector (or isolator)<br />

Fig. H6 : Symbol for a load-break switch<br />

2 The switchgear<br />

2.1 Elementary switching devices<br />

Disconnector (or isolator) (see Fig. H )<br />

This switch is a manually-operated, lockable, two-position device (open/closed)<br />

which provides safe isolation <strong>of</strong> a circuit when locked in the open position. Its<br />

characteristics are defined in IEC 60947-3. A disconnector is not <strong>design</strong>ed to make<br />

or to break current (1) and no rated values for these functions are given in standards.<br />

It must, however, be capable <strong>of</strong> withstanding the passage <strong>of</strong> short-circuit currents<br />

and is assigned a rated short-time withstand capability, generally for 1 second,<br />

unless otherwise agreed between user and manufacturer. This capability is normally<br />

more than adequate for longer periods <strong>of</strong> (lower-valued) operational overcurrents,<br />

such as those <strong>of</strong> motor-starting. Standardized mechanical-endurance, overvoltage,<br />

and leakage-current tests, must also be satisfied.<br />

Load-breaking switch (see Fig. H6)<br />

This control switch is generally operated manually (but is sometimes provided with<br />

<strong>electrical</strong> tripping for operator convenience) and is a non-automatic two-position<br />

device (open/closed).<br />

It is used to close and open loaded circuits under normal unfaulted circuit conditions.<br />

It does not consequently, provide any protection for the circuit it controls.<br />

IEC standard 60947-3 defines:<br />

b The frequency <strong>of</strong> switch operation (600 close/open cycles per hour maximum)<br />

b Mechanical and <strong>electrical</strong> endurance (generally less than that <strong>of</strong> a contactor)<br />

b Current making and breaking ratings for normal and infrequent situations<br />

When closing a switch to energize a circuit there is always the possibility that<br />

an unsuspected short-circuit exists on the circuit. For this reason, load-break<br />

switches are assigned a fault-current making rating, i.e. successful closure against<br />

the electrodynamic forces <strong>of</strong> short-circuit current is assured. Such switches are<br />

commonly referred to as “fault-make load-break” switches. Upstream protective<br />

devices are relied upon to clear the short-circuit fault<br />

Category AC-23 includes occasional switching <strong>of</strong> individual motors. The switching<br />

<strong>of</strong> capacitors or <strong>of</strong> tungsten filament lamps shall be subject to agreement between<br />

manufacturer and user.<br />

The utilization categories referred to in Figure H7 do not apply to an equipment<br />

normally used to start, accelerate and/or stop individual motors.<br />

Example<br />

A 100 A load-break switch <strong>of</strong> category AC-23 (inductive load) must be able:<br />

b To make a current <strong>of</strong> 10 In (= 1,000 A) at a power factor <strong>of</strong> 0.35 lagging<br />

b To break a current <strong>of</strong> 8 In (= 800 A) at a power factor <strong>of</strong> 0.45 lagging<br />

b To withstand short duration short-circuit currents when closed<br />

Utilization category Typical applications Cos ϕ Making Breaking<br />

Frequent Infrequent current x In current x In<br />

operations operations<br />

AC-20A AC-20B Connecting and disconnecting - - -<br />

under no-load conditions<br />

AC-21A AC-21B Switching <strong>of</strong> resistive loads 0.95 1.5 1.5<br />

including moderate overloads<br />

AC-22A AC-22B Switching <strong>of</strong> mixed resistive 0.65 3 3<br />

and inductive loads, including<br />

moderate overloads<br />

AC-23A AC-23B Switching <strong>of</strong> motor loads or 0.45 for I y 100 A 10 8<br />

other highly inductive loads 0.35 for I > 100 A<br />

Fig. H7 : Utilization categories <strong>of</strong> LV AC switches according to IEC 60947-3<br />

(1) i.e. a LV disconnector is essentially a dead system<br />

switching device to be operated with no voltage on either side<br />

<strong>of</strong> it, particularly when closing, because <strong>of</strong> the possibility <strong>of</strong> an<br />

unsuspected short-circuit on the downstream side. Interlocking<br />

with an upstream switch or circuit-breaker is frequently used.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

H6<br />

H - LV switchgear: functions & selection<br />

Fig. H8 : Symbol for a bistable remote control switch<br />

Control<br />

circuit<br />

Fig. H9 : Symbol for a contactor<br />

Power<br />

circuit<br />

Two classes <strong>of</strong> LV cartridge fuse are very<br />

widely used:<br />

b For domestic and similar <strong>installation</strong>s type gG<br />

b For industrial <strong>installation</strong>s type gG, gM or aM<br />

Fig. H10 : Symbol for fuses<br />

(1) This term is not defined in IEC publications but is commonly<br />

used in some countries.<br />

2 The switchgear<br />

Remote control switch (see Fig. H8)<br />

This device is extensively used in the control <strong>of</strong> lighting circuits where the depression<br />

<strong>of</strong> a pushbutton (at a remote control position) will open an already-closed switch or<br />

close an opened switch in a bistable sequence.<br />

Typical applications are:<br />

b Two-way switching on stairways <strong>of</strong> large buildings<br />

b Stage-lighting schemes<br />

b Factory illumination, etc.<br />

Auxiliary devices are available to provide:<br />

b Remote indication <strong>of</strong> its state at any instant<br />

b Time-delay functions<br />

b Maintained-contact features<br />

Contactor (see Fig. H9)<br />

The contactor is a solenoid-operated switching device which is generally held<br />

closed by (a reduced) current through the closing solenoid (although various<br />

mechanically-latched types exist for specific duties). Contactors are <strong>design</strong>ed to<br />

carry out numerous close/open cycles and are commonly controlled remotely by<br />

on-<strong>of</strong>f pushbuttons. The large number <strong>of</strong> repetitive operating cycles is standardized in<br />

table VIII <strong>of</strong> IEC 60947-4-1 by:<br />

b The operating duration: 8 hours; uninterrupted; intermittent; temporary <strong>of</strong> 3, 10, 30,<br />

60 and 90 minutes<br />

b Utilization category: for example, a contactor <strong>of</strong> category AC3 can be used for the<br />

starting and stopping <strong>of</strong> a cage motor<br />

b The start-stop cycles (1 to 1,200 cyles per hour)<br />

b Mechanical endurance (number <strong>of</strong> <strong>of</strong>f-load manœuvres)<br />

b Electrical endurance (number <strong>of</strong> on-load manœuvres)<br />

b A rated current making and breaking performance according to the category <strong>of</strong><br />

utilization concerned<br />

Example:<br />

A 150 A contactor <strong>of</strong> category AC3 must have a minimum current-breaking capability<br />

<strong>of</strong> 8 In (= 1,200 A) and a minimum current-making rating <strong>of</strong> 10 In (= 1,500 A) at a<br />

power factor (lagging) <strong>of</strong> 0.35.<br />

Discontactor (1)<br />

A contactor equipped with a thermal-type relay for protection against overloading<br />

defines a “discontactor”. Discontactors are used extensively for remote push-button<br />

control <strong>of</strong> lighting circuits, etc., and may also be considered as an essential element<br />

in a motor controller, as noted in sub-clause 2.2. “combined switchgear elements”.<br />

The discontactor is not the equivalent <strong>of</strong> a circuit-breaker, since its short-circuit<br />

current breaking capability is limited to 8 or 10 In. For short-circuit protection<br />

therefore, it is necessary to include either fuses or a circuit-breaker in series with,<br />

and upstream <strong>of</strong>, the discontactor contacts.<br />

Fuses (see Fig. H10)<br />

The first letter indicates the breaking range:<br />

b “g” fuse-links (full-range breaking-capacity fuse-link)<br />

b “a” fuse-links (partial-range breaking-capacity fuse-link)<br />

The second letter indicates the utilization category; this letter defines with accuracy<br />

the time-current characteristics, conventional times and currents, gates.<br />

For example<br />

b “gG” indicates fuse-links with a full-range breaking capacity for general application<br />

b “gM” indicates fuse-links with a full-range breaking capacity for the protection <strong>of</strong><br />

motor circuits<br />

b “aM” indicates fuse-links with a partial range breaking capacity for the protection <strong>of</strong><br />

motor circuits<br />

Fuses exist with and without “fuse-blown” mechanical indicators. Fuses break a<br />

circuit by controlled melting <strong>of</strong> the fuse element when a current exceeds a given<br />

value for a corresponding period <strong>of</strong> time; the current/time relationship being<br />

presented in the form <strong>of</strong> a performance curve for each type <strong>of</strong> fuse. Standards define<br />

two classes <strong>of</strong> fuse:<br />

b Those intended for domestic <strong>installation</strong>s, manufactured in the form <strong>of</strong> a cartridge<br />

for rated currents up to 100 A and <strong>design</strong>ated type gG in IEC 60269-1 and 3<br />

b Those for industrial use, with cartridge types <strong>design</strong>ated gG (general use); and gM<br />

and aM (for motor-circuits) in IEC 60269-1 and 2<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

gM fuses require a separate overload relay, as<br />

described in the note at the end <strong>of</strong> sub-clause 2.1.<br />

1 hour<br />

t<br />

Inf I2<br />

Minimum<br />

pre-arcing<br />

time curve<br />

Fuse-blow<br />

curve<br />

Fig. H12 : Zones <strong>of</strong> fusing and non-fusing for gG and gM fuses<br />

(1) Ich for gM fuses<br />

I<br />

2 The switchgear<br />

The main differences between domestic and industrial fuses are the nominal<br />

voltage and current levels (which require much larger physical dimensions) and<br />

their fault-current breaking capabilities. Type gG fuse-links are <strong>of</strong>ten used for the<br />

protection <strong>of</strong> motor circuits, which is possible when their characteristics are capable<br />

<strong>of</strong> withstanding the motor-starting current without deterioration.<br />

A more recent development has been the adoption by the IEC <strong>of</strong> a fuse-type gM for<br />

motor protection, <strong>design</strong>ed to cover starting, and short-circuit conditions. This type <strong>of</strong><br />

fuse is more popular in some countries than in others, but at the present time the<br />

aM fuse in combination with a thermal overload relay is more-widely used.<br />

A gM fuse-link, which has a dual rating is characterized by two current values. The<br />

first value In denotes both the rated current <strong>of</strong> the fuse-link and the rated current <strong>of</strong><br />

the fuseholder; the second value Ich denotes the time-current characteristic <strong>of</strong> the<br />

fuse-link as defined by the gates in Tables II, III and VI <strong>of</strong> IEC 60269-1.<br />

These two ratings are separated by a letter which defines the applications.<br />

For example: In M Ich denotes a fuse intended to be used for protection <strong>of</strong><br />

motor circuits and having the characteristic G. The first value In corresponds to<br />

the maximum continuous current for the whole fuse and the second value Ich<br />

corresponds to the G characteristic <strong>of</strong> the fuse link. For further details see note at the<br />

end <strong>of</strong> sub-clause 2.1.<br />

An aM fuse-link is characterized by one current value In and time-current<br />

characteristic as shown in Figure H14 next page.<br />

Important: Some national standards use a gI (industrial) type fuse, similar in all main<br />

essentails to type gG fuses.<br />

Type gI fuses should never be used, however, in domestic and similar <strong>installation</strong>s.<br />

Fusing zones - conventional currents<br />

The conditions <strong>of</strong> fusing (melting) <strong>of</strong> a fuse are defined by standards, according to<br />

their class.<br />

Class gG fuses<br />

These fuses provide protection against overloads and short-circuits.<br />

Conventional non-fusing and fusing currents are standardized, as shown in<br />

Figure H12 and in Figure H13.<br />

b The conventional non-fusing current Inf is the value <strong>of</strong> current that the fusible<br />

element can carry for a specified time without melting.<br />

Example: A 32 A fuse carrying a current <strong>of</strong> 1.25 In (i.e. 40 A) must not melt in less<br />

than one hour (table H13)<br />

b The conventional fusing current If (= I2 in Fig. H12) is the value <strong>of</strong> current which<br />

will cause melting <strong>of</strong> the fusible element before the expiration <strong>of</strong> the specified time.<br />

Example: A 32 A fuse carrying a current <strong>of</strong> 1.6 In (i.e. 52.1 A) must melt in one hour<br />

or less<br />

IEC 60269-1 standardized tests require that a fuse-operating characteristic lies<br />

between the two limiting curves (shown in Figure H12) for the particular fuse under<br />

test. This means that two fuses which satisfy the test can have significantly different<br />

operating times at low levels <strong>of</strong> overloading.<br />

Rated current (1) Conventional non- Conventional Conventional<br />

In (A) fusing current fusing current time (h)<br />

Inf I2<br />

In y 4 A 1.5 In 2.1 In 1<br />

4 < In < 16 A 1.5 In 1.9 In 1<br />

16 < In y 63 A 1.25 In 1.6 In 1<br />

63 < In y 160 A 1.25 In 1.6 In 2<br />

160 < In y 400 A 1.25 In 1.6 In 3<br />

400 < In 1.25 In 1.6 In 4<br />

Fig. H13 : Zones <strong>of</strong> fusing and non-fusing for LV types gG and gM class fuses (IEC 60269-1<br />

and 60269-2-1)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

H8<br />

H - LV switchgear: functions & selection<br />

Class aM fuses protect against short-circuit<br />

currents only, and must always be associated<br />

with another device which protects against<br />

overload<br />

4 I n<br />

x I n<br />

Fig. H14 : Standardized zones <strong>of</strong> fusing for type aM fuses (all<br />

current ratings)<br />

I<br />

t<br />

Tf Ta<br />

Ttc<br />

0.005 s<br />

0.02 s<br />

0.01 s<br />

Tf: Fuse pre-arc fusing time<br />

Ta: Arcing time<br />

Ttc: Total fault-clearance time<br />

Fig. H15 : Current limitation by a fuse<br />

Mini m um<br />

pre-arcing<br />

time cu r v e<br />

Fuse- b l o wn<br />

cu r v e<br />

Prospective<br />

fault-current peak<br />

rms value <strong>of</strong> the AC<br />

component <strong>of</strong> the<br />

prospective fault curent<br />

Current peak<br />

limited by the fuse<br />

(1) For currents exceeding a certain level, depending on the<br />

fuse nominal current rating, as shown below in Figure H16.<br />

t<br />

2 The switchgear<br />

b The two examples given above for a 32 A fuse, together with the foregoing notes<br />

on standard test requirements, explain why these fuses have a poor performance in<br />

the low overload range<br />

b It is therefore necessary to install a cable larger in ampacity than that normally<br />

required for a circuit, in order to avoid the consequences <strong>of</strong> possible long term<br />

overloading (60% overload for up to one hour in the worst case)<br />

By way <strong>of</strong> comparison, a circuit-breaker <strong>of</strong> similar current rating:<br />

b Which passes 1.05 In must not trip in less than one hour; and<br />

b When passing 1.25 In it must trip in one hour, or less (25% overload for up to one<br />

hour in the worst case)<br />

Class aM (motor) fuses<br />

These fuses afford protection against short-circuit currents only and must necessarily<br />

be associated with other switchgear (such as discontactors or circuit-breakers) in<br />

order to ensure overload protection < 4 In. They are not therefore autonomous. Since<br />

aM fuses are not intended to protect against low values <strong>of</strong> overload current, no levels<br />

<strong>of</strong> conventional non-fusing and fusing currents are fixed. The characteristic curves for<br />

testing these fuses are given for values <strong>of</strong> fault current exceeding approximately 4 In<br />

(see Fig. H14), and fuses tested to IEC 60269 must give operating curves which fall<br />

within the shaded area.<br />

Note: the small “arrowheads” in the diagram indicate the current/time “gate” values<br />

for the different fuses to be tested (IEC 60269).<br />

Rated short-circuit breaking currents<br />

A characteristic <strong>of</strong> modern cartridge fuses is that, owing to the rapidity <strong>of</strong> fusion<br />

in the case <strong>of</strong> high short-circuit current levels (1) , a current cut-<strong>of</strong>f begins before<br />

the occurrence <strong>of</strong> the first major peak, so that the fault current never reaches its<br />

prospective peak value (see Fig. H1 ).<br />

This limitation <strong>of</strong> current reduces significantly the thermal and dynamic stresses<br />

which would otherwise occur, thereby minimizing danger and damage at the fault<br />

position. The rated short-circuit breaking current <strong>of</strong> the fuse is therefore based on the<br />

rms value <strong>of</strong> the AC component <strong>of</strong> the prospective fault current.<br />

No short-circuit current-making rating is assigned to fuses.<br />

Reminder<br />

Short-circuit currents initially contain DC components, the magnitude and duration <strong>of</strong><br />

which depend on the XL/R ratio <strong>of</strong> the fault current loop.<br />

Close to the source (MV/LV transformer) the relationship Ipeak / Irms (<strong>of</strong><br />

AC component) immediately following the instant <strong>of</strong> fault, can be as high as 2.5<br />

(standardized by IEC, and shown in Figure H16 next page).<br />

At lower levels <strong>of</strong> distribution in an <strong>installation</strong>, as previously noted, XL is small<br />

compared with R and so for final circuits Ipeak / Irms ~ 1.41, a condition which<br />

corresponds with Figure H15.<br />

The peak-current-limitation effect occurs only when the prospective rms<br />

AC component <strong>of</strong> fault current attains a certain level. For example, in the Figure H16<br />

graph, the 100 A fuse will begin to cut <strong>of</strong>f the peak at a prospective fault current<br />

(rms) <strong>of</strong> 2 kA (a). The same fuse for a condition <strong>of</strong> 20 kA rms prospective current<br />

will limit the peak current to 10 kA (b). Without a current-limiting fuse the peak<br />

current could attain 50 kA (c) in this particular case. As already mentioned, at lower<br />

distribution levels in an <strong>installation</strong>, R greatly predominates XL, and fault levels are<br />

generally low. This means that the level <strong>of</strong> fault current may not attain values high<br />

enough to cause peak current limitation. On the other hand, the DC transients (in this<br />

case) have an insignificant effect on the magnitude <strong>of</strong> the current peak, as previously<br />

mentioned.<br />

Note: On gM fuse ratings<br />

A gM type fuse is essentially a gG fuse, the fusible element <strong>of</strong> which corresponds to<br />

the current value Ich (ch = characteristic) which may be, for example, 63 A. This is<br />

the IEC testing value, so that its time/ current characteristic is identical to that <strong>of</strong> a<br />

63 A gG fuse.<br />

This value (63 A) is selected to withstand the high starting currents <strong>of</strong> a motor, the<br />

steady state operating current (In) <strong>of</strong> which may be in the 10-20 A range.<br />

This means that a physically smaller fuse barrel and metallic parts can be used,<br />

since the heat dissipation required in normal service is related to the lower figures<br />

(10-20 A). A standard gM fuse, suitable for this situation would be <strong>design</strong>ated 32M63<br />

(i.e. In M Ich).<br />

The first current rating In concerns the steady-load thermal performance <strong>of</strong> the<br />

fuselink, while the second current rating (Ich) relates to its (short-time) startingcurrent<br />

performance. It is evident that, although suitable for short-circuit protection,<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

Prospective fault<br />

current (kA) peak<br />

100<br />

50<br />

20<br />

10<br />

5<br />

2<br />

(a)<br />

Maximum possible current<br />

peak characteristic<br />

i.e. 2.5 Irms (IEC)<br />

Fig. H17 : Symbol for an automatic tripping switch-fuse<br />

(c)<br />

(b)<br />

160A<br />

100A<br />

50A<br />

1<br />

1 2 5 10 20 50 100<br />

AC component <strong>of</strong> prospective<br />

fault current (kA) rms<br />

Fig. H16 : Limited peak current versus prospective rms values<br />

<strong>of</strong> the AC component <strong>of</strong> fault current for LV fuses<br />

Fig. H18 : Symbol for a non-automatic fuse-switch<br />

Nominal<br />

fuse<br />

ratings<br />

Peak current<br />

cut-<strong>of</strong>f<br />

characteristic<br />

curves<br />

Fig. H20 : Symbol for a fuse disconnector + discontactor<br />

Fig. H21 : Symbol for a fuse-switch disconnector + discontactor<br />

2 The switchgear<br />

overload protection for the motor is not provided by the fuse, and so a separate<br />

thermal-type relay is always necessary when using gM fuses. The only advantage<br />

<strong>of</strong>fered by gM fuses, therefore, when compared with aM fuses, are reduced physical<br />

dimensions and slightly lower cost.<br />

2.2 Combined switchgear elements<br />

Single units <strong>of</strong> switchgear do not, in general, fulfil all the requirements <strong>of</strong> the three<br />

basic functions, viz: Protection, control and isolation.<br />

Where the <strong>installation</strong> <strong>of</strong> a circuit-breaker is not appropriate (notably where the<br />

switching rate is high, over extended periods) combinations <strong>of</strong> units specifically<br />

<strong>design</strong>ed for such a performance are employed. The most commonly-used<br />

combinations are described below.<br />

Switch and fuse combinations<br />

Two cases are distinguished:<br />

b The type in which the operation <strong>of</strong> one (or more) fuse(s) causes the switch to open.<br />

This is achieved by the use <strong>of</strong> fuses fitted with striker pins, and a system <strong>of</strong> switch<br />

tripping springs and toggle mechanisms (see Fig. H17)<br />

b The type in which a non-automatic switch is associated with a set <strong>of</strong> fuses in a<br />

common enclosure.<br />

In some countries, and in IEC 60947-3, the terms “switch-fuse” and “fuse-switch”<br />

have specific meanings, viz:<br />

v A switch-fuse comprises a switch (generally 2 breaks per pole) on the upstream<br />

side <strong>of</strong> three fixed fuse-bases, into which the fuse carriers are inserted (see Fig. H18)<br />

v A fuse-switch consists <strong>of</strong> three switch blades each constituting a double-break per<br />

phase.<br />

These blades are not continuous throughout their length, but each has a gap in the<br />

centre which is bridged by the fuse cartridge. Some <strong>design</strong>s have only a single break<br />

per phase, as shown in Figure H19.<br />

Fig. H19 : Symbol for a non-automatic switch-fuse<br />

The current range for these devices is limited to 100 A maximum at 400 V 3-phase,<br />

while their principal use is in domestic and similar <strong>installation</strong>s. To avoid confusion<br />

between the first group (i.e. automatic tripping) and the second group, the term<br />

“switch-fuse” should be qualified by the adjectives “automatic” or “non-automatic”.<br />

Fuse – disconnector + discontactor<br />

Fuse - switch-disconnector + discontactor<br />

As previously mentioned, a discontactor does not provide protection against shortcircuit<br />

faults. It is necessary, therefore, to add fuses (generally <strong>of</strong> type aM) to perform<br />

this function. The combination is used mainly for motor control circuits, where the<br />

disconnector or switch-disconnector allows safe operations such as:<br />

b The changing <strong>of</strong> fuse links (with the circuit isolated)<br />

b Work on the circuit downstream <strong>of</strong> the discontactor (risk <strong>of</strong> remote closure <strong>of</strong> the<br />

discontactor)<br />

The fuse-disconnector must be interlocked with the discontactor such that no opening<br />

or closing manœuvre <strong>of</strong> the fuse disconnector is possible unless the discontactor is<br />

open ( Figure H20), since the fuse disconnector has no load-switching capability.<br />

A fuse-switch-disconnector (evidently) requires no interlocking (Figure H21).<br />

The switch must be <strong>of</strong> class AC22 or AC23 if the circuit supplies a motor.<br />

Circuit-breaker + contactor<br />

Circuit-breaker + discontactor<br />

These combinations are used in remotely controlled distribution systems in which the<br />

rate <strong>of</strong> switching is high, or for control and protection <strong>of</strong> a circuit supplying motors.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H9<br />

© Schneider Electric - all rights reserved


H10<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

3 Choice <strong>of</strong> switchgear<br />

3.1 Tabulated functional capabilities<br />

After having studied the basic functions <strong>of</strong> LV switchgear (clause 1, Figure H1) and<br />

the different components <strong>of</strong> switchgear (clause 2), Figure H22 summarizes the<br />

capabilities <strong>of</strong> the various components to perform the basic functions.<br />

Isolation Control Electrical protection<br />

Switchgear Functional Emergency Emergency Switching for Overload Short-circuit Electric<br />

item switching stop mechanical shock<br />

(mechanical) maintenance<br />

Isolator (or b<br />

disconnector) (4)<br />

Switch (5) b b b (1) b (1) (2) b<br />

Residual b b b (1) b (1) (2) b b<br />

device<br />

(RCCB) (5)<br />

Switch- b b b (1) b (1) (2) b<br />

disconnector<br />

Contactor b b (1) b (1) (2) b b (3)<br />

Remote control b b (1) b<br />

switch<br />

Fuse b b b<br />

Circuit b b (1) b (1) (2) b b b<br />

breaker (5)<br />

Circuit-breaker b b b (1) b (1) (2) b b b<br />

disconnector (5)<br />

Residual b b b (1) b (1) (2) b b b b<br />

and overcurrent<br />

circuit-breaker<br />

(RCBO) (5)<br />

Point <strong>of</strong> Origin <strong>of</strong> each All points where, In general at the At the supply At the supply Origin <strong>of</strong> each Origin <strong>of</strong> each Origin <strong>of</strong> circuits<br />

<strong>installation</strong> circuit for operational incoming circuit point to each point to each circuit circuit where the<br />

(general reasons it may to every machine machine earthing system<br />

principle) be necessary distribution and/or on the is appropriate<br />

to stop the board machine TN-S, IT, TT<br />

process concerned<br />

(1) Where cut-<strong>of</strong>f <strong>of</strong> all active conductors is provided<br />

(2) It may be necessary to maintain supply to a braking system<br />

(3) If it is associated with a thermal relay (the combination is commonly referred to as a “discontactor”)<br />

(4) In certain countries a disconnector with visible contacts is mandatory at the origin <strong>of</strong> a LV <strong>installation</strong> supplied directly from a MV/LV transformer<br />

(5) Certain items <strong>of</strong> switchgear are suitable for isolation duties (e.g. RCCBs according to IEC 61008) without being explicitly marked as such<br />

Fig. H22 : Functions fulfilled by different items <strong>of</strong> switchgear<br />

3.2 Switchgear selection<br />

S<strong>of</strong>tware is being used more and more in the field <strong>of</strong> optimal selection <strong>of</strong> switchgear.<br />

Each circuit is considered one at a time, and a list is drawn up <strong>of</strong> the required<br />

protection functions and exploitation <strong>of</strong> the <strong>installation</strong>, among those mentioned in<br />

Figure H22 and summarized in Figure H1.<br />

A number <strong>of</strong> switchgear combinations are studied and compared with each other<br />

against relevant criteria, with the aim <strong>of</strong> achieving:<br />

b Satisfactory performance<br />

b Compatibility among the individual items; from the rated current In to the fault-level<br />

rating Icu<br />

b Compatibility with upstream switchgear or taking into account its contribution<br />

b Conformity with all regulations and specifications concerning safe and reliable<br />

circuit performance<br />

In order to determine the number <strong>of</strong> poles for an item <strong>of</strong> switchgear, reference is<br />

made to chapter G, clause 7 Fig. G64. Multifunction switchgear, initially more costly,<br />

reduces <strong>installation</strong> costs and problems <strong>of</strong> <strong>installation</strong> or exploitation. It is <strong>of</strong>ten found<br />

that such switchgear provides the best solution.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

The circuit-breaker/disconnector fulfills all <strong>of</strong> the<br />

basic switchgear functions, while, by means <strong>of</strong><br />

accessories, numerous other possibilities exist<br />

Industrial circuit-breakers must comply with<br />

IEC 60947-1 and 60947-2 or other equivalent<br />

standards.<br />

Domestic-type circuit-breakers must comply with<br />

IEC standard 60898, or an equivalent national<br />

standard<br />

Fig. H24 : Main parts <strong>of</strong> a circuit-breaker<br />

Power circuit terminals<br />

Contacts and arc-diving<br />

chamber<br />

Fool-pro<strong>of</strong> mechanical<br />

indicator<br />

Latching mechanism<br />

Trip mechanism and<br />

protective devices<br />

4 Circuit-breaker<br />

As shown in Figure H23 the circuit-breaker/ disconnector is the only item <strong>of</strong><br />

switchgear capable <strong>of</strong> simultaneously satisfying all the basic functions necessary in<br />

an <strong>electrical</strong> <strong>installation</strong>.<br />

Moreover, it can, by means <strong>of</strong> auxiliary units, provide a wide range <strong>of</strong> other functions,<br />

for example: indication (on-<strong>of</strong>f - tripped on fault); undervoltage tripping; remote<br />

control… etc. These features make a circuit-breaker/ disconnector the basic unit <strong>of</strong><br />

switchgear for any <strong>electrical</strong> <strong>installation</strong>.<br />

Functions Possible conditions<br />

Isolation b<br />

Control Functional b<br />

Emergency switching b (With the possibility <strong>of</strong> a tripping<br />

coil for remote control)<br />

Switching-<strong>of</strong>f for mechanical b<br />

maintenance<br />

Protection Overload b<br />

Short-circuit b<br />

Insulation fault b (With differential-current relay)<br />

Undervoltage b (With undervoltage-trip coil)<br />

Remote control b Added or incorporated<br />

Indication and measurement b (<strong>General</strong>ly optional with an<br />

electronic tripping device)<br />

Fig. H23 : Functions performed by a circuit-breaker/disconnector<br />

4.1 Standards and description<br />

Standards<br />

For industrial LV <strong>installation</strong>s the relevant IEC standards are, or are due to be:<br />

b 60947-1: general <strong>rules</strong><br />

b 60947-2: part 2: circuit-breakers<br />

b 60947-3: part 3: switches, disconnectors, switch-disconnectors and fuse<br />

combination units<br />

b 60947-4: part 4: contactors and motor starters<br />

b 60947-5: part 5: control-circuit devices and switching elements<br />

b 60947-6: part 6: multiple function switching devices<br />

b 60947-7: part 7: ancillary equipment<br />

For domestic and similar LV <strong>installation</strong>s, the appropriate standard is IEC 60898, or<br />

an equivalent national standard.<br />

Description<br />

Figure H24 shows schematically the main parts <strong>of</strong> a LV circuit-breaker and its four<br />

essential functions:<br />

b The circuit-breaking components, comprising the fixed and moving contacts and<br />

the arc-dividing chamber<br />

b The latching mechanism which becomes unlatched by the tripping device on<br />

detection <strong>of</strong> abnormal current conditions<br />

This mechanism is also linked to the operation handle <strong>of</strong> the breaker.<br />

b A trip-mechanism actuating device:<br />

v Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip<br />

detects an overload condition, while an electromagnetic striker pin operates at<br />

current levels reached in short-circuit conditions, or<br />

v An electronic relay operated from current transformers, one <strong>of</strong> which is installed on<br />

each phase<br />

b A space allocated to the several types <strong>of</strong> terminal currently used for the main<br />

power circuit conductors<br />

Domestic circuit-breakers (see Fig. H25 next page) complying with IEC 60898 and<br />

similar national standards perform the basic functions <strong>of</strong>:<br />

b Isolation<br />

b Protection against overcurrent<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H11<br />

© Schneider Electric - all rights reserved


H12<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

Fig. H25 : Domestic-type circuit-breaker providing overcurrent<br />

protection and circuit isolation features<br />

Fig. H26 : Domestic-type circuit-breaker as above (Fig. H25)<br />

with incorparated protection against electric shocks<br />

OF1 SD SDE OF2<br />

OF2<br />

SDE<br />

SD<br />

OF1<br />

Fig. H28 : Example <strong>of</strong> a modular (Compact NS) industrial type<br />

<strong>of</strong> circuit-breaker capable <strong>of</strong> numerous auxiliary functions<br />

4 Circuit-breaker<br />

Some models can be adapted to provide sensitive detection (30 mA) <strong>of</strong> earthleakage<br />

current with CB tripping, by the addition <strong>of</strong> a modular block, while other<br />

models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2<br />

Annex B) have this residual current feature incorporated as shown in Figure H26.<br />

Apart from the above-mentioned functions further features can be associated with<br />

the basic circuit-breaker by means <strong>of</strong> additional modules, as shown in Figure H27;<br />

notably remote control and indication (on-<strong>of</strong>f-fault).<br />

5<br />

4<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

2<br />

O-OFF O-OFF - O-OFF -<br />

Fig. H27 : “Multi 9” system <strong>of</strong> LV modular switchgear components<br />

Moulded-case type industrial circuit-breakers complying with IEC 60947-2 are now<br />

available, which, by means <strong>of</strong> associated adaptable blocks provide a similar range <strong>of</strong><br />

auxiliary functions to those described above (see Figure H28).<br />

Heavy-duty industrial circuit-breakers <strong>of</strong> large current ratings, complying with<br />

IEC 60947-2, have numerous built-in communication and electronic functions<br />

(see Figure H29).<br />

In addition to the protection functions, the Micrologic unit provides optimized<br />

functions such as measurement (including power quality functions), diagnosis,<br />

communication, control and monitoring.<br />

Fig. H29 : Examples <strong>of</strong> heavy-duty industrial circuit-breakers. The “Masterpact” provides many<br />

automation features in its “Micrologic” tripping module<br />

1


H - LV switchgear: functions & selection<br />

0.4 In<br />

Adjustment<br />

range<br />

Overload trip<br />

current setting<br />

Ir<br />

Rated current <strong>of</strong><br />

the tripping unit<br />

160 A 360 A 400 A 630 A<br />

(1) Current-level setting values which refer to the currentoperated<br />

thermal and “instantaneous” magnetic tripping<br />

devices for over-load and short-circuit protection.<br />

In<br />

Circuit breaker<br />

frame-size rating<br />

Fig. H30 : Example <strong>of</strong> a NS630N circuit-breaker equipped with<br />

a STR23SE trip unit adjusted to 0.9, to give Ir = 360 A<br />

4 Circuit-breaker<br />

4.2 Fundamental characteristics <strong>of</strong> a circuit-breaker<br />

The fundamental characteristics <strong>of</strong> a circuit-breaker are:<br />

b Its rated voltage Ue<br />

b Its rated current In<br />

b Its tripping-current-level adjustment ranges for overload protection (Ir (1) or Irth (1) )<br />

and for short-circuit protection (Im) (1)<br />

b Its short-circuit current breaking rating (Icu for industrial CBs; Icn for domestic-<br />

type CBs).<br />

Rated operational voltage (Ue)<br />

This is the voltage at which the circuit-breaker has been <strong>design</strong>ed to operate, in<br />

normal (undisturbed) conditions.<br />

Other values <strong>of</strong> voltage are also assigned to the circuit-breaker, corresponding to<br />

disturbed conditions, as noted in sub-clause 4.3.<br />

Rated current (In)<br />

This is the maximum value <strong>of</strong> current that a circuit-breaker, fitted with a specified<br />

overcurrent tripping relay, can carry indefinitely at an ambient temperature stated by<br />

the manufacturer, without exceeding the specified temperature limits <strong>of</strong> the current<br />

carrying parts.<br />

Example<br />

A circuit-breaker rated at In = 125 A for an ambient temperature <strong>of</strong> 40 °C will be<br />

equipped with a suitably calibrated overcurrent tripping relay (set at 125 A). The<br />

same circuit-breaker can be used at higher values <strong>of</strong> ambient temperature however,<br />

if suitably “derated”. Thus, the circuit-breaker in an ambient temperature <strong>of</strong> 50 °C<br />

could carry only 117 A indefinitely, or again, only 109 A at 60 °C, while complying<br />

with the specified temperature limit.<br />

Derating a circuit-breaker is achieved therefore, by reducing the trip-current setting<br />

<strong>of</strong> its overload relay, and marking the CB accordingly. The use <strong>of</strong> an electronic-type<br />

<strong>of</strong> tripping unit, <strong>design</strong>ed to withstand high temperatures, allows circuit-breakers<br />

(derated as described) to operate at 60 °C (or even at 70 °C) ambient.<br />

Note: In for circuit-breakers (in IEC 60947-2) is equal to Iu for switchgear generally,<br />

Iu being the rated uninterrupted current.<br />

Frame-size rating<br />

A circuit-breaker which can be fitted with overcurrent tripping units <strong>of</strong> different current<br />

level-setting ranges, is assigned a rating which corresponds to the highest currentlevel-setting<br />

tripping unit that can be fitted.<br />

Example<br />

A NS630N circuit-breaker can be equipped with 4 electronic trip units from 150 A to<br />

630 A. The size <strong>of</strong> the circuit-breaker is 630 A.<br />

Overload relay trip-current setting (Irth or Ir)<br />

Apart from small circuit-breakers which are very easily replaced, industrial circuitbreakers<br />

are equipped with removable, i.e. exchangeable, overcurrent-trip relays.<br />

Moreover, in order to adapt a circuit-breaker to the requirements <strong>of</strong> the circuit<br />

it controls, and to avoid the need to install over-sized cables, the trip relays are<br />

generally adjustable. The trip-current setting Ir or Irth (both <strong>design</strong>ations are<br />

in common use) is the current above which the circuit-breaker will trip. It also<br />

represents the maximum current that the circuit-breaker can carry without tripping.<br />

That value must be greater than the maximum load current IB, but less than the<br />

maximum current permitted in the circuit Iz (see chapter G, sub-clause 1.3).<br />

The thermal-trip relays are generally adjustable from 0.7 to 1.0 times In, but when<br />

electronic devices are used for this duty, the adjustment range is greater; typically 0.4<br />

to 1 times In.<br />

Example (see Fig. H30)<br />

A NS630N circuit-breaker equipped with a 400 A STR23SE overcurrent trip relay, set<br />

at 0.9, will have a trip-current setting:<br />

Ir = 400 x 0.9 = 360 A<br />

Note: For circuit-breakers equipped with non-adjustable overcurrent-trip relays,<br />

Ir = In. Example: for C60N 20 A circuit-breaker, Ir = In = 20 A.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H13<br />

© Schneider Electric - all rights reserved


H14<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

Short-circuit relay trip-current setting (Im)<br />

Fig. H31 : Tripping-current ranges <strong>of</strong> overload and short-circuit protective devices for LV circuit-breakers<br />

t (s )<br />

Ir Im Icu<br />

I(A<br />

Fig. H32 : Performance curve <strong>of</strong> a circuit-breaker thermalmagnetic<br />

protective scheme<br />

4 Circuit-breaker<br />

Type <strong>of</strong> Overload Short-circuit protection<br />

protective protection<br />

relay<br />

Short-circuit tripping relays (instantaneous or slightly time-delayed) are intended to<br />

trip the circuit-breaker rapidly on the occurrence <strong>of</strong> high values <strong>of</strong> fault current. Their<br />

tripping threshold Im is:<br />

b Either fixed by standards for domestic type CBs, e.g. IEC 60898, or,<br />

b Indicated by the manufacturer for industrial type CBs according to related<br />

standards, notably IEC 60947-2.<br />

For the latter circuit-breakers there exists a wide variety <strong>of</strong> tripping devices which<br />

allow a user to adapt the protective performance <strong>of</strong> the circuit-breaker to the<br />

particular requirements <strong>of</strong> a load (see Fig. H31, Fig. H32 and Fig. H33).<br />

Domestic Thermal- Ir = In Low setting Standard setting High setting circuit<br />

breakers magnetic type B type C type D<br />

IEC 60898 3 In y Im y 5 In 5 In y Im y 10 In 10 In y Im y 20 In (1)<br />

Modular Thermal- Ir = In Low setting Standard setting High setting<br />

industrial (2) magnetic fixed type B or Z type C type D or K<br />

circuit-breakers 3.2 In y fixed y 4.8 In 7 In y fixed y 10 In 10 In y fixed y 14 In<br />

Industrial (2) Thermal- Ir = In fixed Fixed: Im = 7 to 10 In<br />

circuit-breakers magnetic Adjustable: Adjustable:<br />

IEC 60947-2 0.7 In y Ir y In - Low setting : 2 to 5 In<br />

- Standard setting: 5 to 10 In<br />

Electronic Long delay Short-delay, adjustable<br />

0.4 In y Ir y In 1.5 Ir y Im y 10 Ir<br />

Instantaneous (I) fixed<br />

I = 12 to 15 In<br />

(1) 50 In in IEC 60898, which is considered to be unrealistically high by most European manufacturers (Merlin Gerin = 10 to 14 In).<br />

(2) For industrial use, IEC standards do not specify values. The above values are given only as being those in common use.<br />

t (s )<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Ir Im Ii Icu<br />

Fig. H33 : Performance curve <strong>of</strong> a circuit-breaker electronic protective scheme<br />

I(A<br />

Ir: Overload (thermal or long-delay) relay trip-current<br />

setting<br />

Im: Short-circuit (magnetic or short-delay) relay tripcurrent<br />

setting<br />

Ii: Short-circuit instantaneous relay trip-current setting.<br />

Icu: Breaking capacity


H - LV switchgear: functions & selection<br />

The short-circuit current-breaking performance<br />

<strong>of</strong> a LV circuit-breaker is related (approximately)<br />

to the cos ϕ <strong>of</strong> the fault-current loop. Standard<br />

values for this relationship have been<br />

established in some standards<br />

Familiarity with the following less-important<br />

characteristics <strong>of</strong> LV circuit-breakers is,<br />

however, <strong>of</strong>ten necessary when making a final<br />

choice.<br />

4 Circuit-breaker<br />

Isolating feature<br />

A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions<br />

prescribed for a disconnector (at its rated voltage) in the relevant standard (see<br />

sub-clause 1.2). In such a case it is referred to as a circuit-breaker-disconnector and<br />

marked on its front face with the symbol<br />

All Multi 9, Compact NS and Masterpact LV switchgear <strong>of</strong> Merlin Gerin manufacture<br />

is in this category.<br />

Rated short-circuit breaking capacity (Icu or Icn)<br />

The short-circuit current-breaking rating <strong>of</strong> a CB is the highest (prospective) value<br />

<strong>of</strong> current that the CB is capable <strong>of</strong> breaking without being damaged. The value<br />

<strong>of</strong> current quoted in the standards is the rms value <strong>of</strong> the AC component <strong>of</strong> the<br />

fault current, i.e. the DC transient component (which is always present in the worst<br />

possible case <strong>of</strong> short-circuit) is assumed to be zero for calculating the standardized<br />

value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is<br />

normally given in kA rms.<br />

Icu (rated ultimate s.c. breaking capacity) and Ics (rated service s.c. breaking<br />

capacity) are defined in IEC 60947-2 together with a table relating Ics with Icu for<br />

different categories <strong>of</strong> utilization A (instantaneous tripping) and B (time-delayed<br />

tripping) as discussed in subclause 4.3.<br />

Tests for proving the rated s.c. breaking capacities <strong>of</strong> CBs are governed by<br />

standards, and include:<br />

b Operating sequences, comprising a succession <strong>of</strong> operations, i.e. closing and<br />

opening on short-circuit<br />

b Current and voltage phase displacement. When the current is in phase with the<br />

supply voltage (cos ϕ for the circuit = 1), interruption <strong>of</strong> the current is easier than<br />

that at any other power factor. Breaking a current at low lagging values <strong>of</strong> cos ϕ is<br />

considerably more difficult to achieve; a zero power-factor circuit being (theoretically)<br />

the most onerous case.<br />

In practice, all power-system short-circuit fault currents are (more or less) at lagging<br />

power factors, and standards are based on values commonly considered to be<br />

representative <strong>of</strong> the majority <strong>of</strong> power systems. In general, the greater the level <strong>of</strong><br />

fault current (at a given voltage), the lower the power factor <strong>of</strong> the fault-current loop,<br />

for example, close to generators or large transformers.<br />

Figure H34 below extracted from IEC 60947-2 relates standardized values <strong>of</strong> cos ϕ<br />

to industrial circuit-breakers according to their rated Icu.<br />

b Following an open - time delay - close/open sequence to test the Icu capacity <strong>of</strong> a<br />

CB, further tests are made to ensure that:<br />

v The dielectric withstand capability<br />

v The disconnection (isolation) performance and<br />

v The correct operation <strong>of</strong> the overload protection<br />

have not been impaired by the test.<br />

4.3 Other characteristics <strong>of</strong> a circuit-breaker<br />

Rated insulation voltage (Ui)<br />

This is the value <strong>of</strong> voltage to which the dielectric tests voltage (generally greater<br />

than 2 Ui) and creepage distances are referred to.<br />

The maximum value <strong>of</strong> rated operational voltage must never exceed that <strong>of</strong> the rated<br />

insulation voltage, i.e. Ue y Ui.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Icu cos ϕ<br />

6 kA < Icu y 10 kA 0.5<br />

10 kA < Icu y 20 kA 0.3<br />

20 kA < Icu y 50 kA 0.25<br />

50 kA < Icu 0.2<br />

Fig. H34 : Icu related to power factor (cos ϕ) <strong>of</strong> fault-current circuit (IEC 60947-2)<br />

H15<br />

© Schneider Electric - all rights reserved


H16<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

t (s)<br />

Im<br />

Fig. H35 : Category A circuit-breaker<br />

t (s )<br />

Im<br />

Fig. H36 : Category B circuit-breaker<br />

In a correctly <strong>design</strong>ed <strong>installation</strong>, a circuitbreaker<br />

is never required to operate at its<br />

maximum breaking current Icu. For this reason<br />

a new characteristic Ics has been introduced.<br />

It is expressed in IEC 60947-2 as a percentage<br />

<strong>of</strong> Icu (25, 50, 75, 100%)<br />

(1) O represents an opening operation.<br />

CO represents a closing operation followed by an opening<br />

operation.<br />

I<br />

Icw<br />

Icu<br />

I(A)<br />

I(A )<br />

4 Circuit-breaker<br />

Rated impulse-withstand voltage (Uimp)<br />

This characteristic expresses, in kV peak (<strong>of</strong> a prescribed form and polarity) the value<br />

<strong>of</strong> voltage which the equipment is capable <strong>of</strong> withstanding without failure, under test<br />

conditions.<br />

<strong>General</strong>ly, for industrial circuit-breakers, Uimp = 8 kV and for domestic types,<br />

Uimp = 6 kV.<br />

Category (A or B) and rated short-time withstand current (Icw)<br />

As already briefly mentioned (sub-clause 4.2) there are two categories <strong>of</strong><br />

LV industrial switchgear, A and B, according to IEC 60947-2:<br />

b Those <strong>of</strong> category A, for which there is no deliberate delay in the operation <strong>of</strong> the<br />

“instantaneous” short-circuit magnetic tripping device (see Fig. H35), are generally<br />

moulded-case type circuit-breakers, and<br />

b Those <strong>of</strong> category B for which, in order to discriminate with other circuit-breakers<br />

on a time basis, it is possible to delay the tripping <strong>of</strong> the CB, where the fault-current<br />

level is lower than that <strong>of</strong> the short-time withstand current rating (Icw) <strong>of</strong> the CB<br />

(see Fig. H36). This is generally applied to large open-type circuit-breakers and<br />

to certain heavy-duty moulded-case types. Icw is the maximum current that the B<br />

category CB can withstand, thermally and electrodynamically, without sustaining<br />

damage, for a period <strong>of</strong> time given by the manufacturer.<br />

Rated making capacity (Icm)<br />

Icm is the highest instantaneous value <strong>of</strong> current that the circuit-breaker can<br />

establish at rated voltage in specified conditions. In AC systems this instantaneous<br />

peak value is related to Icu (i.e. to the rated breaking current) by the factor k, which<br />

depends on the power factor (cos ϕ) <strong>of</strong> the short-circuit current loop (as shown in<br />

Figure H37 ).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Icu cos ϕ Icm = kIcu<br />

6 kA < Icu y 10 kA 0.5 1.7 x Icu<br />

10 kA < Icu y 20 kA 0.3 2 x Icu<br />

20 kA < Icu y 50 kA 0.25 2.1 x Icu<br />

50 kA y Icu 0.2 2.2 x Icu<br />

Fig. H37 : Relation between rated breaking capacity Icu and rated making capacity Icm at<br />

different power-factor values <strong>of</strong> short-circuit current, as standardized in IEC 60947-2<br />

Example: A Masterpact NW08H2 circuit-breaker has a rated breaking capacity<br />

Icu <strong>of</strong> 100 kA. The peak value <strong>of</strong> its rated making capacity Icm will be<br />

100 x 2.2 = 220 kA.<br />

Rated service short-circuit breaking capacity (Ics)<br />

The rated breaking capacity (Icu) or (Icn) is the maximum fault-current a circuitbreaker<br />

can successfully interrupt without being damaged. The probability <strong>of</strong> such<br />

a current occurring is extremely low, and in normal circumstances the fault-currents<br />

are considerably less than the rated breaking capacity (Icu) <strong>of</strong> the CB. On the other<br />

hand it is important that high currents (<strong>of</strong> low probability) be interrupted under good<br />

conditions, so that the CB is immediately available for reclosure, after the faulty<br />

circuit has been repaired. It is for these reasons that a new characteristic (Ics) has<br />

been created, expressed as a percentage <strong>of</strong> Icu, viz: 25, 50, 75, 100% for industrial<br />

circuit-breakers. The standard test sequence is as follows:<br />

b O - CO - CO (1) (at Ics)<br />

b Tests carried out following this sequence are intended to verify that the CB is in a<br />

good state and available for normal service<br />

For domestic CBs, Ics = k Icn. The factor k values are given in IEC 60898 table XIV.<br />

In Europe it is the industrial practice to use a k factor <strong>of</strong> 100% so that Ics = Icu.


H - LV switchgear: functions & selection<br />

Many <strong>design</strong>s <strong>of</strong> LV circuit-breakers feature<br />

a short-circuit current limitation capability,<br />

whereby the current is reduced and prevented<br />

from reaching its (otherwise) maximum peak<br />

value (see Fig. H38). The current-limitation<br />

performance <strong>of</strong> these CBs is presented in<br />

the form <strong>of</strong> graphs, typified by that shown in<br />

Figure H39, diagram (a)<br />

Current limitation reduces both thermal and<br />

electrodynamic stresses on all circuit elements<br />

through which the current passes, thereby<br />

prolonging the useful life <strong>of</strong> these elements.<br />

Furthermore, the limitation feature allows<br />

“cascading” techniques to be used (see 4.5)<br />

thereby significantly reducing <strong>design</strong> and<br />

<strong>installation</strong> costs<br />

Icc<br />

Prospectice<br />

fault-current peak<br />

Limited<br />

current peak<br />

Limited<br />

current<br />

tc<br />

Fig. H38 : Prospective and actual currents<br />

Prospectice<br />

fault-current<br />

t<br />

4 Circuit-breaker<br />

Fault-current limitation<br />

The fault-current limitation capacity <strong>of</strong> a CB concerns its ability, more or less<br />

effective, in preventing the passage <strong>of</strong> the maximum prospective fault-current,<br />

permitting only a limited amount <strong>of</strong> current to flow, as shown in Figure H38.<br />

The current-limitation performance is given by the CB manufacturer in the form <strong>of</strong><br />

curves (see Fig. H39).<br />

b Diagram (a) shows the limited peak value <strong>of</strong> current plotted against the rms<br />

value <strong>of</strong> the AC component <strong>of</strong> the prospective fault current (“prospective” faultcurrent<br />

refers to the fault-current which would flow if the CB had no current-limiting<br />

capability)<br />

b Limitation <strong>of</strong> the current greatly reduces the thermal stresses (proportional I 2 t) and<br />

this is shown by the curve <strong>of</strong> diagram (b) <strong>of</strong> Figure H39, again, versus the rms value<br />

<strong>of</strong> the AC component <strong>of</strong> the prospective fault current.<br />

LV circuit-breakers for domestic and similar <strong>installation</strong>s are classified in certain<br />

standards (notably European Standard EN 60 898). CBs belonging to one class (<strong>of</strong><br />

current limiters) have standardized limiting I 2 t let-through characteristics defined by<br />

that class.<br />

In these cases, manufacturers do not normally provide characteristic performance<br />

curves.<br />

a)<br />

Limited<br />

current<br />

peak<br />

(kA)<br />

22<br />

Non-limited current<br />

characteristics<br />

Prospective AC<br />

component (rms)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

150 kA<br />

b)<br />

4,5.105<br />

2.105<br />

Limited<br />

current peak<br />

(A2 x s)<br />

Fig. H39 : Performance curves <strong>of</strong> a typical LV current-limiting circuit-breaker<br />

Prospective AC<br />

component (rms)<br />

150 kA<br />

The advantages <strong>of</strong> current limitation<br />

The use <strong>of</strong> current-limiting CBs affords numerous advantages:<br />

b Better conservation <strong>of</strong> <strong>installation</strong> networks: current-limiting CBs strongly attenuate<br />

all harmful effects associated with short-circuit currents<br />

b Reduction <strong>of</strong> thermal effects: Conductors (and therefore insulation) heating is<br />

significantly reduced, so that the life <strong>of</strong> cables is correspondingly increased<br />

b Reduction <strong>of</strong> mechanical effects: forces due to electromagnetic repulsion are lower,<br />

with less risk <strong>of</strong> deformation and possible rupture, excessive burning <strong>of</strong> contacts, etc.<br />

b Reduction <strong>of</strong> electromagnetic-interference effects:<br />

v Less influence on measuring instruments and associated circuits,<br />

telecommunication systems, etc.<br />

These circuit-breakers therefore contribute towards an improved exploitation <strong>of</strong>:<br />

b Cables and wiring<br />

b Prefabricated cable-trunking systems<br />

b Switchgear, thereby reducing the ageing <strong>of</strong> the <strong>installation</strong><br />

Example<br />

On a system having a prospective shortcircuit current <strong>of</strong> 150 kA rms, a Compact L<br />

circuit-breaker limits the peak current to less than 10% <strong>of</strong> the calculated prospective<br />

peak value, and the thermal effects to less than 1% <strong>of</strong> those calculated.<br />

Cascading <strong>of</strong> the several levels <strong>of</strong> distribution in an <strong>installation</strong>, downstream <strong>of</strong> a<br />

limiting CB, will also result in important savings.<br />

The technique <strong>of</strong> cascading, described in sub-clause 4.5 allows, in fact, substantial<br />

savings on switchgear (lower performance permissible downstream <strong>of</strong> the limiting<br />

CB(s)) enclosures, and <strong>design</strong> studies, <strong>of</strong> up to 20% (overall).<br />

Discriminative protection schemes and cascading are compatible, in the Compact<br />

NS range, up to the full short-circuit breaking capacity <strong>of</strong> the switchgear.<br />

H17<br />

© Schneider Electric - all rights reserved


H18<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

The choice <strong>of</strong> a range <strong>of</strong> circuit-breakers is<br />

determined by: the <strong>electrical</strong> characteristics <strong>of</strong><br />

the <strong>installation</strong>, the environment, the loads and<br />

a need for remote control, together with the type<br />

<strong>of</strong> telecommunications system envisaged<br />

Circuit-breakers with uncompensated thermal<br />

tripping units have a trip current level that<br />

depends on the surrounding temperature<br />

Ambient<br />

temperature<br />

Single CB<br />

in free air<br />

Fig. H40 : Ambient temperature<br />

Temperature <strong>of</strong> air<br />

surrouding the<br />

circuit breakers<br />

Circuit breakers installed<br />

in an enclosure<br />

Ambient<br />

temperature<br />

4 Circuit-breaker<br />

4.4 Selection <strong>of</strong> a circuit-breaker<br />

Choice <strong>of</strong> a circuit-breaker<br />

The choice <strong>of</strong> a CB is made in terms <strong>of</strong>:<br />

b Electrical characteristics <strong>of</strong> the <strong>installation</strong> for which the CB is intended<br />

b Its eventual environment: ambient temperature, in a kiosk or switchboard<br />

enclosure, climatic conditions, etc.<br />

b Short-circuit current breaking and making requirements<br />

b Operational specifications: discriminative tripping, requirements (or not) for<br />

remote control and indication and related auxiliary contacts, auxiliary tripping coils,<br />

connection<br />

b Installation regulations; in particular: protection <strong>of</strong> persons<br />

b Load characteristics, such as motors, fluorescent lighting, LV/LV transformers<br />

The following notes relate to the choice LV circuit-breaker for use in distribution<br />

systems.<br />

Choice <strong>of</strong> rated current in terms <strong>of</strong> ambient temperature<br />

The rated current <strong>of</strong> a circuit-breaker is defined for operation at a given ambient<br />

temperature, in general:<br />

b 30 °C for domestic-type CBs<br />

b 40 °C for industrial-type CBs<br />

Performance <strong>of</strong> these CBs in a different ambient temperature depends mainly on the<br />

technology <strong>of</strong> their tripping units (see Fig. H40).<br />

Uncompensated thermal magnetic tripping units<br />

Circuit-breakers with uncompensated thermal tripping elements have a trippingcurrent<br />

level that depends on the surrounding temperature. If the CB is installed<br />

in an enclosure, or in a hot location (boiler room, etc.), the current required to trip<br />

the CB on overload will be sensibly reduced. When the temperature in which the<br />

CB is located exceeds its reference temperature, it will therefore be “derated”. For<br />

this reason, CB manufacturers provide tables which indicate factors to apply at<br />

temperatures different to the CB reference temperature. It may be noted from typical<br />

examples <strong>of</strong> such tables (see Fig. H41) that a lower temperature than the reference<br />

value produces an up-rating <strong>of</strong> the CB. Moreover, small modular-type CBs mounted<br />

in juxtaposition, as shown typically in Figure H27, are usually mounted in a small<br />

closed metal case. In this situation, mutual heating, when passing normal load<br />

currents, generally requires them to be derated by a factor <strong>of</strong> 0.8.<br />

C60a, C60H: curve C. C60N: curves B and C (reference temperature: 30 °C)<br />

Rating (A) 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C<br />

1 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 0.85<br />

2 2.08 2.04 2.00 1.96 1.92 1.88 1.84 1.80 1.74<br />

3 3.18 3.09 3.00 2.91 2.82 2.70 2.61 2.49 2.37<br />

4 4.24 4.12 4.00 3.88 3.76 3.64 3.52 3.36 3.24<br />

6 6.24 6.12 6.00 5.88 5.76 5.64 5.52 5.40 5.30<br />

10 10.6 10.3 10.0 9.70 9.30 9.00 8.60 8.20 7.80<br />

16 16.8 16.5 16.0 15.5 15.2 14.7 14.2 13.8 13.5<br />

20 21.0 20.6 20.0 19.4 19.0 18.4 17.8 17.4 16.8<br />

25 26.2 25.7 25.0 24.2 23.7 23.0 22.2 21.5 20.7<br />

32 33.5 32.9 32.0 31.4 30.4 29.8 28.4 28.2 27.5<br />

40 42.0 41.2 40.0 38.8 38.0 36.8 35.6 34.4 33.2<br />

50 52.5 51.5 50.0 48.5 47.4 45.5 44.0 42.5 40.5<br />

63 66.2 64.9 63.0 61.1 58.0 56.7 54.2 51.7 49.2<br />

NS250N/H/L (reference temperature: 40 °C)<br />

Rating (A) 40 °C 45 °C 50 °C 55 °C 60 °C<br />

TM160D 160 156 152 147 144<br />

TM200D 200 195 190 185 180<br />

TM250D 250 244 238 231 225<br />

Fig. H41 : Examples <strong>of</strong> tables for the determination <strong>of</strong> derating/uprating factors to apply to CBs<br />

with uncompensated thermal tripping units, according to temperature<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

Electronic tripping units are highly stable in<br />

changing temperature levels<br />

4 Circuit-breaker<br />

Example<br />

What rating (In) should be selected for a C60 N?<br />

b Protecting a circuit, the maximum load current <strong>of</strong> which is estimated to be 34 A<br />

b Installed side-by-side with other CBs in a closed distribution box<br />

b In an ambient temperature <strong>of</strong> 50 °C<br />

A C60N circuit-breaker rated at 40 A would be derated to 35.6 A in ambient air at<br />

50 °C (see Fig. H41). To allow for mutual heating in the enclosed space, however, the<br />

0.8 factor noted above must be employed, so that, 35.6 x 0.8 = 28.5 A, which is not<br />

suitable for the 34 A load.<br />

A 50 A circuit-breaker would therefore be selected, giving a (derated) current rating<br />

<strong>of</strong> 44 x 0.8 = 35.2 A.<br />

Compensated thermal-magnetic tripping units<br />

These tripping units include a bi-metal compensating strip which allows the overload<br />

trip-current setting (Ir or Irth) to be adjusted, within a specified range, irrespective <strong>of</strong><br />

the ambient temperature.<br />

For example:<br />

b In certain countries, the TT system is standard on LV distribution systems, and<br />

domestic (and similar) <strong>installation</strong>s are protected at the service position by a circuitbreaker<br />

provided by the supply authority. This CB, besides affording protection<br />

against indirect-contact hazard, will trip on overload; in this case, if the consumer<br />

exceeds the current level stated in his supply contract with the power authority. The<br />

circuit-breaker (y 60 A) is compensated for a temperature range <strong>of</strong> - 5 °C to + 40 °C.<br />

b LV circuit-breakers at ratings y 630 A are commonly equipped with compensated<br />

tripping units for this range (- 5 °C to + 40 °C)<br />

Electronic tripping units<br />

An important advantage with electronic tripping units is their stable performance<br />

in changing temperature conditions. However, the switchgear itself <strong>of</strong>ten imposes<br />

operational limits in elevated temperatures, so that manufacturers generally provide<br />

an operating chart relating the maximum values <strong>of</strong> permissible trip-current levels to<br />

the ambient temperature (see Fig. H42).<br />

Masterpact NW20 version 40°C 45°C 50°C 55°C 60°C<br />

H1/H2/H3 Withdrawable with In (A) 2,000 2,000 2,000 1,980 1,890<br />

horizontal plugs Maximum 1 1 1 0.99 0.95<br />

adjustment Ir<br />

L1 Withdrawable with In (A) 2,000 200 1,900 1,850 1,800<br />

on-edge plugs Maximum 1 1 0.95 0.93 0.90<br />

adjustment Ir<br />

Coeff.<br />

1 2,000<br />

0.95 1,890<br />

0.90 1,800<br />

In (A)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

NW20 withdrawable with<br />

horizontal plugs<br />

NW20 L1 withdrawable<br />

with on edge plugs<br />

20 25 30 35 40 45 50 55 60<br />

Fig. H42 : Derating <strong>of</strong> Masterpact NW20 circuit-breaker, according to the temperature<br />

θ°C<br />

H19<br />

© Schneider Electric - all rights reserved


H20<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

The <strong>installation</strong> <strong>of</strong> a LV circuit-breaker requires<br />

that its short-circuit breaking capacity (or that <strong>of</strong><br />

the CB together with an associated device) be<br />

equal to or exceeds the calculated prospective<br />

short-circuit current at its point <strong>of</strong> <strong>installation</strong><br />

The circuit-breaker at the output <strong>of</strong> the smallest<br />

transformer must have a short-circuit capacity<br />

adequate for a fault current which is higher<br />

than that through any <strong>of</strong> the other transformer<br />

LV circuit-breakers<br />

4 Circuit-breaker<br />

Selection <strong>of</strong> an instantaneous, or short-time-delay, tripping<br />

threshold<br />

Figure H43 below summarizes the main characteristics <strong>of</strong> the instantaneous or<br />

short-time delay trip units.<br />

Type Tripping unit Applications<br />

t<br />

Low setting<br />

type B<br />

b Sources producing low short-circuitcurrent<br />

levels<br />

(standby generators)<br />

b Long lengths <strong>of</strong> line or cable<br />

t<br />

t<br />

t<br />

Fig. H43 : Different tripping units, instantaneous or short-time-delayed<br />

Selection <strong>of</strong> a circuit-breaker according to the short-circuit<br />

breaking capacity requirements<br />

The <strong>installation</strong> <strong>of</strong> a circuit-breaker in a LV <strong>installation</strong> must fulfil one <strong>of</strong> the two<br />

following conditions:<br />

b Either have a rated short-circuit breaking capacity Icu (or Icn) which is equal to or<br />

exceeds the prospective short-circuit current calculated for its point <strong>of</strong> <strong>installation</strong>, or<br />

b If this is not the case, be associated with another device which is located<br />

upstream, and which has the required short-circuit breaking capacity<br />

In the second case, the characteristics <strong>of</strong> the two devices must be co-ordinated<br />

such that the energy permitted to pass through the upstream device must not<br />

exceed that which the downstream device and all associated cables, wires and other<br />

components can withstand, without being damaged in any way. This technique is<br />

pr<strong>of</strong>itably employed in:<br />

b Associations <strong>of</strong> fuses and circuit-breakers<br />

b Associations <strong>of</strong> current-limiting circuit-breakers and standard circuit-breakers.<br />

The technique is known as “cascading” (see sub-clause 4.5 <strong>of</strong> this chapter)<br />

The selection <strong>of</strong> main and principal circuit-breakers<br />

A single transformer<br />

If the transformer is located in a consumer’s substation, certain national standards<br />

require a LV circuit-breaker in which the open contacts are clearly visible such as<br />

Compact NS withdrawable circuit-breaker.<br />

Example (see Fig. H44 opposite page)<br />

What type <strong>of</strong> circuit-breaker is suitable for the main circuit-breaker <strong>of</strong> an <strong>installation</strong><br />

supplied through a 250 kVA MV/LV (400 V) 3-phase transformer in a consumer’s<br />

substation?<br />

In transformer = 360 A<br />

Isc (3-phase) = 8.9 kA<br />

A Compact NS400N with an adjustable tripping-unit range <strong>of</strong> 160 A - 400 A and a<br />

short-circuit breaking capacity (Icu) <strong>of</strong> 45 kA would be a suitable choice for this duty.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I<br />

I<br />

I<br />

I<br />

Standard setting b Protection <strong>of</strong> circuits: general case<br />

type C<br />

High setting b Protection <strong>of</strong> circuits having high initial<br />

type D or K transient current levels<br />

(e.g. motors, transformers, resistive loads)<br />

12 In b Protection <strong>of</strong> motors in association with<br />

type MA discontactors<br />

(contactors with overload protection)


H - LV switchgear: functions & selection<br />

250 kVA<br />

20 kV/400 V<br />

Compact<br />

NS400N<br />

Fig. H44 : Example <strong>of</strong> a transformer in a consumer’s substation<br />

A1<br />

B1<br />

MV<br />

LV<br />

Tr1<br />

CBM<br />

CBP<br />

A2<br />

B2<br />

Fig. H45 : Transformers in parallel<br />

E<br />

MV<br />

LV<br />

Tr2<br />

CBM<br />

CBP<br />

A3<br />

B3<br />

MV<br />

LV<br />

Tr3<br />

CBM<br />

4 Circuit-breaker<br />

Several transformers in parallel (see Fig. H45)<br />

b The circuit-breakers CBP outgoing from the LV distribution board must each be<br />

capable <strong>of</strong> breaking the total fault current from all transformers connected to the<br />

busbars, viz: Isc1 + Isc2 + Isc3<br />

b The circuit-breakers CBM, each controlling the output <strong>of</strong> a transformer, must be<br />

capable <strong>of</strong> dealing with a maximum short-circuit current <strong>of</strong> (for example) Isc2 + Isc3<br />

only, for a short-circuit located on the upstream side <strong>of</strong> CBM1.<br />

From these considerations, it will be seen that the circuit-breaker <strong>of</strong> the smallest<br />

transformer will be subjected to the highest level <strong>of</strong> fault current in these<br />

circumstances, while the circuit-breaker <strong>of</strong> the largest transformer will pass the<br />

lowest level <strong>of</strong> short-circuit current<br />

b The ratings <strong>of</strong> CBMs must be chosen according to the kVA ratings <strong>of</strong> the<br />

associated transformers<br />

Note: The essential conditions for the successful operation <strong>of</strong> 3-phase transformers<br />

in parallel may be summarized as follows:<br />

1. the phase shift <strong>of</strong> the voltages, primary to secondary, must be the same in all units<br />

to be paralleled.<br />

2. the open-circuit voltage ratios, primary to secondary, must be the same in all units.<br />

3. the short-circuit impedance voltage (Zsc%) must be the same for all units.<br />

For example, a 750 kVA transformer with a Zsc = 6% will share the load correctly<br />

with a 1,000 kVA transformer having a Zsc <strong>of</strong> 6%, i.e. the transformers will be loaded<br />

automatically in proportion to their kVA ratings. For transformers having a ratio <strong>of</strong> kVA<br />

ratings exceeding 2, parallel operation is not recommended.<br />

Figure H46 indicates, for the most usual arrangement (2 or 3 transformers <strong>of</strong><br />

equal kVA ratings) the maximum short-circuit currents to which main and principal<br />

CBs (CBM and CBP respectively, in Figure H45) are subjected. It is based on the<br />

following hypotheses:<br />

b The short-circuit 3-phase power on the MV side <strong>of</strong> the transformer is 500 MVA<br />

b The transformers are standard 20/0.4 kV distribution-type units rated as listed<br />

b The cables from each transformer to its LV circuit-breaker comprise 5 metres <strong>of</strong><br />

single core conductors<br />

b Between each incoming-circuit CBM and each outgoing-circuit CBP there is<br />

1 metre <strong>of</strong> busbar<br />

b The switchgear is installed in a floormounted enclosed switchboard, in an ambientair<br />

temperature <strong>of</strong> 30 °C<br />

Moreover, this table shows selected circuit-breakers <strong>of</strong> M-G manufacture<br />

recommended for main and principal circuit-breakers in each case.<br />

Example (see Fig. H47 next page)<br />

b Circuit-breaker selection for CBM duty:<br />

For a 800 kVA transformer In = 1.126 A; Icu (minimum) = 38 kA (from Figure H46),<br />

the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA)<br />

b Circuit-breaker selection for CBP duty:<br />

The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the<br />

Figure H46 as 56 kA.<br />

A recommended choice for the three outgoing circuits 1, 2 and 3 would be currentlimiting<br />

circuit-breakers types NS400 L, NS250 L and NS100 L. The Icu rating in<br />

each case = 150 kA.<br />

Number and kVA ratings Minimum S.C breaking Main circuit-breakers (CBM) Minimum S.C breaking Rated current In <strong>of</strong><br />

<strong>of</strong> 20/0.4 kV transformers capacity <strong>of</strong> main CBs total discrimination with out capacity <strong>of</strong> principal CBs principal circuit-breaker<br />

(Icu) kA going circuit-breakers (CBP) (Icu) kA (CPB) 250A<br />

2 x 400 14 NW08N1/NS800N 27 NS250H<br />

3 x 400 28 NW08N1/NS800N 42 NS250H<br />

2 x 630 22 NW10N1/NS1000N 42 NS250H<br />

3 x 630 44 NW10N1/NS1000N 67 NS250H<br />

2 x 800 19 NW12N1/NS1250N 38 NS250H<br />

3 x 800 38 NW12N1/NS1250N 56 NS250H<br />

2 x 1,000 23 NW16N1/NS1600N 47 NS250H<br />

3 x 1,000 47 NW16N1/NS1600N 70 NS250H<br />

2 x 1,250 29 NW20N1/NS2000N 59 NS250H<br />

3 x 1,250 59 NW20N1/NS2000N 88 NS250L<br />

2 x 1,600 38 NW25N1/NS2500N 75 NS250L<br />

3 x 1,600 75 NW25N1/NS2500N 113 NS250L<br />

2 x 2,000 47 NW32N1/NS3200N 94 NS250L<br />

3 x 2,000 94 NW32N1/NS3200N 141 NS250L<br />

Fig. H46 : Maximum values <strong>of</strong> short-circuit current to be interrupted by main and principal circuit-breakers (CBM and CBP respectively), for several transformers in<br />

parallel<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

H21<br />

© Schneider Electric - all rights reserved


H22<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

Short-circuit fault-current levels at any point in<br />

an <strong>installation</strong> may be obtained from tables<br />

400 A<br />

CBP1<br />

100 A<br />

Fig. H47 : Transformers in parallel<br />

CBP2<br />

3 Tr<br />

800 kVA<br />

20 kV/400 V<br />

CBM<br />

200 A<br />

CBP3<br />

The technique <strong>of</strong> “cascading” uses the<br />

properties <strong>of</strong> current-limiting circuit-breakers<br />

to permit the <strong>installation</strong> <strong>of</strong> all downstream<br />

switchgear, cables and other circuit components<br />

<strong>of</strong> significantly lower performance than would<br />

otherwise be necessary, thereby simplifying and<br />

reducing the cost <strong>of</strong> an <strong>installation</strong><br />

4 Circuit-breaker<br />

These circuit-breakers provide the advantages <strong>of</strong>:<br />

v Absolute discrimination with the upstream (CBM) breakers<br />

v Exploitation <strong>of</strong> the “cascading” technique, with its associated savings for all<br />

downstream components<br />

Choice <strong>of</strong> outgoing-circuit CBs and final-circuit CBs<br />

Use <strong>of</strong> table G40<br />

From this table, the value <strong>of</strong> 3-phase short-circuit current can be determined rapidly<br />

for any point in the <strong>installation</strong>, knowing:<br />

b The value <strong>of</strong> short-circuit current at a point upstream <strong>of</strong> that intended for the CB<br />

concerned<br />

b The length, c.s.a., and the composition <strong>of</strong> the conductors between the two points<br />

A circuit-breaker rated for a short-circuit breaking capacity exceeding the tabulated<br />

value may then be selected.<br />

Detailed calculation <strong>of</strong> the short-circuit current level<br />

In order to calculate more precisely the short-circuit current, notably, when the shortcircuit<br />

current-breaking capacity <strong>of</strong> a CB is slightly less than that derived from the<br />

table, it is necessary to use the method indicated in chapter G clause 4.<br />

Two-pole circuit-breakers (for phase and neutral) with one protected pole only<br />

These CBs are generally provided with an overcurrent protective device on the<br />

phase pole only, and may be used in TT, TN-S and IT schemes. In an IT scheme,<br />

however, the following conditions must be respected:<br />

b Condition (B) <strong>of</strong> table G67 for the protection <strong>of</strong> the neutral conductor against<br />

overcurrent in the case <strong>of</strong> a double fault<br />

b Short-circuit current-breaking rating: A 2-pole phase-neutral CB must, by<br />

convention, be capable <strong>of</strong> breaking on one pole (at the phase-to-phase voltage) the<br />

current <strong>of</strong> a double fault equal to 15% <strong>of</strong> the 3-phase short-circuit current at the point<br />

<strong>of</strong> its <strong>installation</strong>, if that current is y 10 kA; or 25% <strong>of</strong> the 3-phase short-circuit current<br />

if it exceeds 10 kA<br />

b Protection against indirect contact: this protection is provided according to the<br />

<strong>rules</strong> for IT schemes<br />

Insufficient short-circuit current breaking rating<br />

In low-voltage distribution systems it sometimes happens, especially in heavy-duty<br />

networks, that the Isc calculated exceeds the Icu rating <strong>of</strong> the CBs available for<br />

<strong>installation</strong>, or system changes upstream result in lower level CB ratings being<br />

exceeded<br />

b Solution 1: Check whether or not appropriate CBs upstream <strong>of</strong> the CBs affected<br />

are <strong>of</strong> the current-limiting type, allowing the principle <strong>of</strong> cascading (described in subclause<br />

4.5) to be applied<br />

b Solution 2: Install a range <strong>of</strong> CBs having a higher rating. This solution is<br />

economically interesting only where one or two CBs are affected<br />

b Solution 3: Associate current-limiting fuses (gG or aM) with the CBs concerned, on<br />

the upstream side. This arrangement must, however, respect the following <strong>rules</strong>:<br />

v The fuse rating must be appropriate<br />

v No fuse in the neutral conductor, except in certain IT <strong>installation</strong>s where a double<br />

fault produces a current in the neutral which exceeds the short-circuit breaking rating<br />

<strong>of</strong> the CB. In this case, the blowing <strong>of</strong> the neutral fuse must cause the CB to trip on<br />

all phases<br />

4.5 Coordination between circuit-breakers<br />

Cascading<br />

Definition <strong>of</strong> the cascading technique<br />

By limiting the peak value <strong>of</strong> short-circuit current passing through it, a currentlimiting<br />

CB permits the use, in all circuits downstream <strong>of</strong> its location, <strong>of</strong> switchgear<br />

and circuit components having much lower short-circuit breaking capacities, and<br />

thermal and electromechanical withstand capabilities than would otherwise be<br />

necessary. Reduced physical size and lower performance requirements lead to<br />

substantial economy and to the simplification <strong>of</strong> <strong>installation</strong> work. It may be noted<br />

that, while a current-limiting circuit-breaker has the effect on downstream circuits<br />

<strong>of</strong> (apparently) increasing the source impedance during short-circuit conditions, it<br />

has no such effect in any other condition; for example, during the starting <strong>of</strong> a large<br />

motor (where a low source impedance is highly desirable). The range <strong>of</strong> Compact<br />

NS current-limiting circuit-breakers with powerful limiting performances is particularly<br />

interesting.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

In general, laboratory tests are necessary to<br />

ensure that the conditions <strong>of</strong> implementation<br />

required by national standards are met and<br />

compatible switchgear combinations must be<br />

provided by the manufacturer<br />

Discrimination may be total or partial, and<br />

based on the principles <strong>of</strong> current levels, or<br />

time-delays, or a combination <strong>of</strong> both. A more<br />

recent development is based on the logic<br />

techniques.<br />

A (patented) system by Merlin Gerin takes<br />

advantages <strong>of</strong> both current-limitation and<br />

discrimination<br />

4 Circuit-breaker<br />

Conditions <strong>of</strong> implementation<br />

Most national standards admit the cascading technique, on condition that the<br />

amount <strong>of</strong> energy “let through” by the limiting CB is less than the energy all<br />

downstream CBs and components are able to withstand without damage.<br />

In practice this can only be verified for CBs by tests performed in a laboratory. Such<br />

tests are carried out by manufacturers who provide the information in the form <strong>of</strong><br />

tables, so that users can confidently <strong>design</strong> a cascading scheme based on the<br />

combination <strong>of</strong> recommended circuit-breaker types. As an example, Figure H48<br />

indicates the cascading possibilities <strong>of</strong> circuit-breaker types C60, DT40N, C120 and<br />

NG125 when installed downstream <strong>of</strong> current-limiting CBs NS 250 N, H or L for a<br />

230/400 V or 240/415 V 3-phase <strong>installation</strong>.<br />

kA rms<br />

Short-circuit 150 NS250L<br />

breaking capacity 50 NS250H<br />

<strong>of</strong> the upstream 35 NS250N<br />

(limiter) CBs<br />

Possible short-circuit 150 NG125L<br />

breaking capacity <strong>of</strong> 70 NG125L<br />

the downstream CBs 40 C60L y 40 A C60L y 40 A<br />

(benefiting from the 36 NG125N NG125N<br />

cascading technique) 30 C60H C60N/H/L C60N/H<br />

C60L C60L 50-63 A<br />

25 C60N C120N/H<br />

C120N/H C120N/H<br />

20 DT40N DT40N DT40N<br />

Fig. H48 : Example <strong>of</strong> cascading possibilities on a 230/400 V or 240/415 V 3-phase <strong>installation</strong><br />

Advantages <strong>of</strong> cascading<br />

The current limitation benefits all downstream circuits that are controlled by the<br />

current-limiting CB concerned.<br />

The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in<br />

an <strong>installation</strong> where the downstream circuits would otherwise be inadequately rated.<br />

The result is:<br />

b Simplified short-circuit current calculations<br />

b Simplification, i.e. a wider choice <strong>of</strong> downstream switchgear and appliances<br />

b The use <strong>of</strong> lighter-duty switchgear and appliances, with consequently lower cost<br />

b Economy <strong>of</strong> space requirements, since light-duty equipment have generally a<br />

smaller volume<br />

Principles <strong>of</strong> discriminative tripping (selectivity)<br />

Discrimination is achieved by automatic protective devices if a fault condition, occurring<br />

at any point in the <strong>installation</strong>, is cleared by the protective device located immediately<br />

upstream <strong>of</strong> the fault, while all other protective devices remain unaffected (see<br />

Fig. H49).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

B<br />

Isc<br />

0<br />

Total discrimination<br />

Ir B<br />

Partial discrimination<br />

Isc B<br />

Isc<br />

0<br />

B only opens A and B open<br />

Ir B Is Isc B<br />

Isc<br />

Fig. H49 : Total and partial discrimination<br />

A<br />

Is = discrimination limit<br />

H23<br />

© Schneider Electric - all rights reserved


H24<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

t<br />

t<br />

Ir B<br />

Ir B<br />

Ir A<br />

Ir A<br />

B A<br />

B A<br />

B only opens<br />

Isc B Im A<br />

Fig. H50 : Total discrimination between CBs A and B<br />

Im A Is c B<br />

A and B open<br />

Is c A<br />

Fig. H51 : Partial discrimination between CBs A and B<br />

a)<br />

b)<br />

c)<br />

t<br />

t<br />

t<br />

B<br />

Ir B<br />

B A<br />

A<br />

Fig. H52 : Discrimination<br />

Ir A<br />

B A<br />

Im A<br />

delayed<br />

B<br />

A<br />

Isc B<br />

Isc B<br />

∆t<br />

Ii A<br />

instantaneous<br />

I<br />

I<br />

I<br />

I<br />

I<br />

4 Circuit-breaker<br />

Discrimination between circuit-breakers A and B is total if the maximum value <strong>of</strong><br />

short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting<br />

<strong>of</strong> circuit-breaker A (Im A). For this condition, B only will trip (see Fig. H50).<br />

Discrimination is partial if the maximum possible short-circuit current on circuit B<br />

exceeds the short-circuit trip-current setting <strong>of</strong> circuit-breaker A. For this maximum<br />

condition, both A and B will trip (see Fig. H51).<br />

Protection against overload : discrimination based on current levels<br />

(see Fig. H52a)<br />

This method is realized by setting successive tripping thresholds at stepped levels,<br />

from downstream relays (lower settings) towards the source (higher settings).<br />

Discrimination is total or partial, depending on particular conditions, as noted above.<br />

As a rule <strong>of</strong> thumb, discrimination is achieved when:<br />

b IrA/IrB > 2:<br />

Protection against low level short-circuit currents : discrimination based on<br />

stepped time delays (see Fig. H52b)<br />

This method is implemented by adjusting the time-delayed tripping units, such that<br />

downstream relays have the shortest operating times, with progressively longer<br />

delays towards the source.<br />

In the two-level arrangement shown, upstream circuit-breaker A is delayed<br />

sufficiently to ensure total discrimination with B (for example: Masterpact with<br />

electronic trip unit).<br />

Discrimination based on a combination <strong>of</strong> the two previous methods<br />

(see Fig. H52c)<br />

A time-delay added to a current level scheme can improve the overall discrimination<br />

performance.<br />

The upstream CB has two high-speed magnetic tripping thresholds:<br />

b Im A: delayed magnetic trip or short-delay electronic trip<br />

b Ii: instantaneous strip<br />

Discrimination is total if Isc B < Ii (instantaneous).<br />

Protection against high level short-circuit currents: discrimination based on<br />

arc-energy levels<br />

This technology implemented in the Compact NS range (current limiting circuit-<br />

breaker) is extremely effective for achievement <strong>of</strong> total discrimination.<br />

Principle: When a very high level short-circuit current is detected by the two circuits-<br />

breaker A and B, their contacts open simultaneously. As a result, the current is highly<br />

limited.<br />

b The very high arc-energy at level B induces the tripping <strong>of</strong> circuit-breaker B<br />

b Then, the arc-energy is limited at level A and is not sufficient to induce the tripping<br />

<strong>of</strong> A<br />

As a rule <strong>of</strong> thumb, the discrimination between Compact NS is total if the size ratio<br />

between A and B is greater than 2.5.<br />

Current-level discrimination<br />

Current-level discrimination is achieved with stepped current-level settings<br />

<strong>of</strong> the instantaneous magnetic-trip elements<br />

Current-level discrimination is achieved with circuits breakers, preferably currentlimiting,<br />

and stepped current-level settings <strong>of</strong> the instantaneous magnetic-trip<br />

elements.<br />

b The downstream circuit-breaker is not a current-limiter device<br />

Total discrimination in this situation is practically impossible because<br />

Isc A ≈ Isc B, so that both circuit-breakers will generally trip simultaneously. In this<br />

case discrimination is partial, and limited to the Im <strong>of</strong> the upstream circuit-breaker.<br />

See fig. H51.<br />

b The downstream circuit-breaker is a current-limiting device<br />

Improvement in discriminative tripping can be obtained by using a current limiter<br />

for circuit-breaker B. For a short-circuit downstream <strong>of</strong> B, the limited level <strong>of</strong> peak<br />

current IB would operate the (suitably adjusted) magnetic trip unit <strong>of</strong> B, but would be<br />

insufficient to cause circuit-breaker A to trip.<br />

Note: All LV breakers (considered here) have some inherent degree <strong>of</strong> current<br />

limitation, even those that are not classified as current-limiting. This accounts for<br />

the curved characteristic shown for the standard circuit-breaker A in Figure H53<br />

opposite page. Careful calculation and testing is necessary, however, to ensure<br />

satisfactory performance <strong>of</strong> this arrangement.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


H - LV switchgear: functions & selection<br />

Discrimination based on time-delayed tripping<br />

uses CBs referred to as “selective” (in some<br />

countries).<br />

Implementation <strong>of</strong> these CBs is relatively simple<br />

and consists in delaying the instant <strong>of</strong> tripping<br />

<strong>of</strong> the several series-connected circuit-breakers<br />

in a stepped time sequence<br />

(1) Short-delay<br />

4 Circuit-breaker<br />

Fault<br />

upstream<br />

<strong>of</strong> B<br />

Fault<br />

downstream<br />

<strong>of</strong> B<br />

b The upstream circuit-breaker is a high speed device with a short-delay (SD) feature<br />

These circuit-breakers are fitted with trip units which include a non-adjustable<br />

mechanical short-time-delay feature. The delay is sufficient to ensure total<br />

discrimination with any downstream high-speed CB at any value <strong>of</strong> short-circuit<br />

current up to Ii A (see Fig. H54).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I peak<br />

Fig. H53 : Downstream limiting circuit-breaker B<br />

t<br />

A<br />

Is c<br />

Fig. H54 : Use <strong>of</strong> a “selective” circuit-breaker upstream<br />

B<br />

A<br />

Current limitation<br />

curves<br />

(see note)<br />

B<br />

Only B opens A and B open<br />

Im A<br />

delayed<br />

Is c<br />

prospective (rms)<br />

Ii A<br />

instantaneous<br />

Example<br />

Circuit-breaker A: Compact NS250 N fitted with a trip unit which includes a SD<br />

feature.<br />

Ir = 250 A, magnetic trip set at 2,000 A<br />

Circuit-breaker B: Compact NS100N<br />

Ir = 100 A<br />

The Merlin Gerin distribution catalogue indicates a discrimination limit <strong>of</strong> 3,000 A (an<br />

improvement over the limit <strong>of</strong> 2,500 A obtained when using a standard tripping unit).<br />

Time-based discrimination<br />

This technique requires:<br />

b The introduction <strong>of</strong> time-delays into the tripping mechanisms <strong>of</strong> CBs<br />

b CBs with adequate thermal and mechanical withstand capabilities at the high<br />

current levels and time delays considered<br />

Two circuit-breakers A and B in series (i.e. carrying the same current) are<br />

discriminative if the current-breaking period <strong>of</strong> downstream circuit-breaker B is less<br />

than the non-tripping time <strong>of</strong> circuit-breaker A.<br />

I<br />

H25<br />

© Schneider Electric - all rights reserved


H26<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

4 Circuit-breaker<br />

Practical example <strong>of</strong> discrimination at several levels with Merlin Gerin<br />

Masterpact circuit-breakers (with electronic trip units)<br />

These CBs can be equipped with adjustable time-delays which allow 4 time-step<br />

selections, such as:<br />

b The delay corresponding to a given step is greater than the total current breaking<br />

time <strong>of</strong> the next lower step<br />

b The delay corresponding to the first step is greater than the total current-breaking<br />

time <strong>of</strong> a high-speed CB (Compact NS for example) or <strong>of</strong> fuses (see Fig. H55)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

t<br />

Ir B<br />

Fig. H55 : Discrimination by time delay<br />

B<br />

A<br />

Only B opens<br />

Non tripping<br />

time <strong>of</strong> A<br />

Current-breaking<br />

time for B<br />

Icc B<br />

Energy discrimination with current limitation<br />

I<br />

Icc<br />

Cascading between 2 devices is normally achieved by using the tripping <strong>of</strong> the<br />

upstream circuit-breaker A to help the downstream circuit-breaker B to break the<br />

current. The discrimination limit Is is consequently equal to the ultimate breaking<br />

current Icu B <strong>of</strong> circuit-breaker B acting alone, as cascading requires the tripping <strong>of</strong><br />

both devices.<br />

The energy discrimination technology implemented in Compact NS circuit-breakers<br />

allows to improve the discrimination limit to a value higher than the ultimate breaking<br />

current Icu B <strong>of</strong> the downstream circuit-breaker. The principle is as follows:<br />

b The downstream limiting circuit-breaker B sees a very high short-circuit current.<br />

The tripping is very fast ( 1.6<br />

b The ratio <strong>of</strong> rated currents <strong>of</strong> the two circuit-breakers is > 2.5


H - LV switchgear: functions & selection<br />

Discrimination schemes based on logic<br />

techniques are possible, using CBs equipped<br />

with electronic tripping units <strong>design</strong>ed for the<br />

purpose (Compact, Masterpact by MG) and<br />

interconnected with pilot wires<br />

4 Circuit-breaker<br />

Logic discrimination or “Zone Sequence Interlocking – ZSI”<br />

This discrimination system requires CBs equipped with electronic tripping units,<br />

<strong>design</strong>ed for this application, together with interconnecting pilot wires for data<br />

exchange between the CBs. With 2 levels A and B (see Fig. H56), circuit-breaker A<br />

is set to trip instantaneously, unless the relay <strong>of</strong> circuit-breaker B sends a signal to<br />

confirm that the fault is downstream <strong>of</strong> B. This signal causes the tripping unit <strong>of</strong> A to<br />

be delayed, thereby ensuring back-up protection in the event that B fails to clear the<br />

fault, and so on…<br />

This system (patented by Merlin Gerin) also allows rapid localization <strong>of</strong> the fault.<br />

Fig. H56 : Logic discrimination<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A<br />

B<br />

Inter-locking<br />

order<br />

Pilot wire<br />

4.6 Discrimination MV/LV in a consumer’s<br />

substation<br />

In general the transformer in a consumer’s substation is protected by MV fuses,<br />

suitably rated to match the transformer, in accordance with the principles laid down<br />

in IEC 60787 and IEC 60420, by following the advice <strong>of</strong> the fuse manufacturer.<br />

The basic requirement is that a MV fuse will not operate for LV faults occurring<br />

downstream <strong>of</strong> the transformer LV circuit-breaker, so that the tripping characteristic<br />

curve <strong>of</strong> the latter must be to the left <strong>of</strong> that <strong>of</strong> the MV fuse pre-arcing curve.<br />

This requirement generally fixes the maximum settings for the LV circuit-breaker<br />

protection:<br />

b Maximum short-circuit current-level setting <strong>of</strong> the magnetic tripping element<br />

b Maximum time-delay allowable for the short-circuit current tripping element<br />

(see Fig. H57)<br />

Fig. H57 : Example<br />

Full-load current<br />

1,760 A<br />

3-phase<br />

short-circuit<br />

current level<br />

31.4 kA<br />

63 A<br />

1,250 kVA<br />

20 kV / 400 V<br />

Compact<br />

NS2000<br />

set at 1,800 A<br />

H27<br />

© Schneider Electric - all rights reserved


H28<br />

© Schneider Electric - all rights reserved<br />

H - LV switchgear: functions & selection<br />

4 Circuit-breaker<br />

b Short-circuit level at MV terminals <strong>of</strong> transformer: 250 MVA<br />

b Transformer MV/LV: 1,250 kVA 20/0.4 kV<br />

b MV fuses: 63 A<br />

b Cabling, transformer - LV circuit-breaker: 10 metres single-core cables<br />

b LV circuit-breaker: Compact NS 2000 set at 1,800 A (Ir)<br />

What is the maximum short-circuit trip current setting and its maximum time delay<br />

allowable?<br />

The curves <strong>of</strong> Figure H58 show that discrimination is assured if the short-time delay<br />

tripping unit <strong>of</strong> the CB is set at:<br />

b A level y 6 Ir = 10.8 kA<br />

b A time-delay setting <strong>of</strong> step 1 or 2<br />

1,000<br />

200<br />

100<br />

10<br />

0.2<br />

0.1<br />

0.50<br />

0.01<br />

t<br />

(s)<br />

1,800 A<br />

Ir<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

NS 2000<br />

set at<br />

1,800 A<br />

1 4 6<br />

10 kA<br />

Fig. H58 : Curves <strong>of</strong> MV fuses and LV circuit-breaker<br />

8<br />

Minimum pre-arcing<br />

curve for 63 A HV fuses<br />

(current referred to the<br />

secondary side <strong>of</strong> the<br />

transformer)<br />

Isc maxi<br />

31.4 kA<br />

Step 4<br />

Step 3<br />

Step 2<br />

Step 1<br />

I


2<br />

3<br />

4<br />

<strong>Chapter</strong> J<br />

Protection against voltage surges<br />

in LV<br />

Contents<br />

<strong>General</strong> J2<br />

1.1 What is a voltage surge? J2<br />

1.2 The four voltage surge types J2<br />

1.3 Main characteristics <strong>of</strong> voltage surges J4<br />

1.4 Different propagation modes J5<br />

Overvoltage protection devices J6<br />

2.1 Primary protection devices (protection <strong>of</strong> <strong>installation</strong>s J6<br />

against lightning)<br />

2.2 Secondary protection devices (protection <strong>of</strong> internal J8<br />

<strong>installation</strong>s against lightning)<br />

Protection against voltage surges in LV J<br />

3.1 Surge protective device description J11<br />

3.2 Surge protective device standards J11<br />

3.3 Surge protective device data according to IEC 61643-1 standard J11<br />

3.4 Lightning protection standards J13<br />

3.5 Surge arrester <strong>installation</strong> standards J13<br />

Choosing a protection device J 4<br />

4.1 Protection devices according to the earthing system J14<br />

4.2 Internal architecture <strong>of</strong> surge arresters J15<br />

4.3 Installation <strong>rules</strong> J16<br />

4.4 Selection guide J17<br />

4.5 Choice <strong>of</strong> disconnector J22<br />

4.6 End-<strong>of</strong>-life indication <strong>of</strong> the surge arrester J22<br />

4.7 Application example: supermarket J23<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

J<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

J2<br />

J - Protection against voltage surges in LV<br />

<strong>General</strong><br />

. What is a voltage surge?<br />

A voltage surge is a voltage impulse or wave which is superposed on the rated<br />

network voltage (see Fig. J ).<br />

Voltage<br />

Fig. J1 : Voltage surge examples<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Lightning type impulse<br />

(duration = 100 µs)<br />

"Operating impulse"<br />

type dumped ring wave<br />

(F = 100 kHz to 1 MHz)<br />

This type <strong>of</strong> voltage surge is characterised by ( see Fig. J2):<br />

b The rise time (tf) measured in μs<br />

b The gradient S measured in kV/μs<br />

A voltage surge disturbs equipment and causes electromagnetic radiation.<br />

Furthermore, the duration <strong>of</strong> the voltage surge (T) causes a surge <strong>of</strong> energy in the<br />

<strong>electrical</strong> circuits which is likely to destroy the equipment.<br />

U max<br />

50 %<br />

Voltage (V or kV)<br />

Fig. J2 : Main overvoltage characteristics<br />

Rise time (tf)<br />

Voltage surge duration (T)<br />

.2 The four voltage surge types<br />

There are four types <strong>of</strong> voltage surges which may disturb <strong>electrical</strong> <strong>installation</strong>s and<br />

loads:<br />

b Atmospheric voltage surges<br />

b Operating voltage surges<br />

b Transient overvoltage at industrial frequency<br />

b Voltage surges caused by electrostatic discharge<br />

Atmospheric voltage surges<br />

Lightning risk – a few figures<br />

Between 2,000 and 5,000 storms are constantly forming around the earth. These<br />

storms are accompanied by lightning which constitutes a serious risk for both people<br />

and equipment. Strokes <strong>of</strong> lightning hit the ground at a rate <strong>of</strong> 30 to 100 strokes per<br />

second. Every year, the earth is struck by about 3 billion strokes <strong>of</strong> lightning.<br />

t<br />

Irms


J - Protection against voltage surges in LV<br />

Lightning comes from the discharge <strong>of</strong> <strong>electrical</strong><br />

charges accumulated in the cumulo-nimbus<br />

clouds which form a capacitor with the ground.<br />

Storm phenomena cause serious damage.<br />

Lightning is a high frequency <strong>electrical</strong><br />

phenomenon which produces voltage surges<br />

on all conductive elements, and especially on<br />

<strong>electrical</strong> loads and wires.<br />

<strong>General</strong><br />

b Throughout the world, every year, thousands <strong>of</strong> people are struck by lightning and<br />

countless animals are killed<br />

b Lightning also causes a large number <strong>of</strong> fires, most <strong>of</strong> which break out on farms<br />

(destroying buildings or putting them out <strong>of</strong> use)<br />

b Lightning also affects transformers, electricity meters, household appliances, and<br />

all <strong>electrical</strong> and electronic <strong>installation</strong>s in the residential sector and in industry.<br />

b Tall buildings are the ones most <strong>of</strong>ten struck by lightning<br />

b The cost <strong>of</strong> repairing damage caused by lightning is very high<br />

b It is difficult to evaluate the consequences <strong>of</strong> disturbance caused to computer or<br />

telecommunications networks, faults in PLC cycles and faults in regulation systems.<br />

Furthermore, the losses caused by a machine being put out <strong>of</strong> use can have financial<br />

consequences rising above the cost <strong>of</strong> the equipment destroyed by the lightning.<br />

Characteristics <strong>of</strong> lightning discharge<br />

Figure J3 shows the values given by the lighting protection committee (Technical<br />

Committee 81) <strong>of</strong> the I.E.C. As can be seen, 50 % <strong>of</strong> lightning strokes are <strong>of</strong> a force<br />

greater than 33 kA and 5 % are greater than 85 kA. The energy forces involved are<br />

thus very high.<br />

Beyond peak Current Gradient Total Number <strong>of</strong><br />

probability peak duration discharges<br />

P% I (kA) S (kA/μs) T (s) n<br />

95 7 9.1 0.001 1<br />

50 33 24 0.01 2<br />

5 85 65 1.1 6<br />

Fig. J3 : Lightning discharge values given by the IEC lightning protection committee<br />

It is important to define the probability <strong>of</strong> adequate protection when protecting a site.<br />

Furthermore, a lightning current is a high frequency (HF) impulse current reaching<br />

roughly a megahertz.<br />

The effects <strong>of</strong> lightning<br />

A lightning current is therefore a high frequency <strong>electrical</strong> current. As well as<br />

considerable induction and voltage surge effects, it causes the same effects as any<br />

other low frequency current on a conductor:<br />

b Thermal effects: fusion at the lightning impact points and joule effect, due to the<br />

circulation <strong>of</strong> the current, causing fires<br />

b Electrodynamic effects: when the lightning currents circulate in parallel conductors,<br />

they provoke attraction or repulsion forces between the wires, causing breaks or<br />

mechanical deformations (crushed or flattened wires)<br />

b Combustion effects: lightning can cause the air to expand and create overpressure<br />

which stretches over a distance <strong>of</strong> a dozen metres or so. A blast effect breaks windows<br />

or partitions and can project animals or people several metres away from their original<br />

position. This shock wave is at the same time transformed into a sound wave: thunder<br />

b Voltage surges conducted after an impact on overhead <strong>electrical</strong> or telephone lines<br />

b Voltage surges induced by the electromagnetic radiation effect <strong>of</strong> the lightning<br />

channel which acts as an antenna over several kilometres and is crossed by a<br />

considerable impulse current<br />

b The elevation <strong>of</strong> the earth potential by the circulation <strong>of</strong> the lightning current in the<br />

ground. This explains indirect strokes <strong>of</strong> lightning by step voltage and the breakdown<br />

<strong>of</strong> equipment<br />

Operating voltage surges<br />

A sudden change in the established operating conditions in an <strong>electrical</strong> network<br />

causes transient phenomena to occur. These are generally high frequency or<br />

damped oscillation voltage surge waves (see Fig. J1).<br />

They are said to have a slow gradient: their frequency varies from several ten to<br />

several hundred kilohertz.<br />

Operating voltage surges may be created by:<br />

b The opening <strong>of</strong> protection devices (fuse, circuit-breaker), and the opening or<br />

closing <strong>of</strong> control devices (relays, contactors, etc.)<br />

b Inductive circuits due to motors starting and stopping, or the opening <strong>of</strong><br />

transformers such as MV/LV substations<br />

b Capacitive circuits due to the connection <strong>of</strong> capacitor banks to the network<br />

b All devices that contain a coil, a capacitor or a transformer at the power supply<br />

inlet: relays, contactors, television sets, printers, computers, electric ovens, filters, etc.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

J3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

J4<br />

J - Protection against voltage surges in LV<br />

Three points must be kept in mind:<br />

b A direct or indirect lightning stroke may<br />

have destructive consequences on <strong>electrical</strong><br />

<strong>installation</strong>s several kilometres away from<br />

where it falls<br />

b Industrial or operating voltage surges also<br />

cause considerable damage<br />

b The fact that a site <strong>installation</strong> is underground<br />

in no way protects it although it does limit the<br />

risk <strong>of</strong> a direct strike<br />

<strong>General</strong><br />

Transient overvoltages at industrial frequency (see Fig. J4)<br />

These overvoltages have the same frequency as the network (50, 60 or 400 Hz); and<br />

can be caused by:<br />

b Phase/frame or phase/earth insulating faults on a network with an insulated or<br />

impedant neutral, or by the breakdown <strong>of</strong> the neutral conductor. When this happens,<br />

single phase devices will be supplied in 400 V instead <strong>of</strong> 230 V.<br />

b A cable breakdown. For example, a medium voltage cable which falls on a low<br />

voltage line.<br />

b The arcing <strong>of</strong> a high or medium voltage protective spark-gap causing a rise in earth<br />

potential during the action <strong>of</strong> the protection devices. These protection devices follow<br />

automatic switching cycles which will recreate a fault if it persists.<br />

Normal voltage<br />

230/400 V<br />

Fig. J4 : Transient overvoltage at industrial frequency<br />

Voltage surges caused by <strong>electrical</strong> discharge<br />

In a dry environment, <strong>electrical</strong> charges accumulate and create a very strong<br />

electrostatic field. For example, a person walking on carpet with insulating soles<br />

will become <strong>electrical</strong>ly charged to a voltage <strong>of</strong> several kilovolts. If the person walks<br />

close to a conductive structure, he will give <strong>of</strong>f an <strong>electrical</strong> discharge <strong>of</strong> several<br />

amperes in a very short rise time <strong>of</strong> a few nanoseconds. If the structure contains<br />

sensitive electronics, a computer for example, its components or circuit boards may<br />

be damaged.<br />

.3 Main characteristics <strong>of</strong> voltage surges<br />

Figure J5 below sums up the main characteristics <strong>of</strong> voltage surges.<br />

Type <strong>of</strong> voltage surge Voltage surge Duration Front gradient<br />

coefficient or frequency<br />

Industrial frequency y 1.7 Long Industrial frequency<br />

(insulation fault) 30 to 1,000 ms (50-60-400 Hz)<br />

Operation 2 to 4 Short Average<br />

1 to 100 ms 1 to 200 kHz<br />

Atmospheric > 4 Very short Very high<br />

1 to 100 μs 1 to 1,000 kV/μs<br />

Fig. J5 : Main characteristics <strong>of</strong> voltage surges<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Transient overvoltage<br />

Normal voltage<br />

230/400 V<br />

t


J - Protection against voltage surges in LV<br />

<strong>General</strong><br />

.4 Different propagation modes<br />

Common mode<br />

Common mode voltage surges occur between the live parts and the earth:<br />

phase/earth or neutral/earth (see Fig. J6).<br />

They are especially dangerous for devices whose frame is earthed due to the risk <strong>of</strong><br />

dielectric breakdown.<br />

Fig. J6 : Common mode<br />

Differential mode<br />

Fig. J7 : Differential mode<br />

Ph<br />

Ph<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N<br />

N<br />

Imc<br />

Voltage surge<br />

common mode<br />

Imd<br />

U voltage surge<br />

differential mode<br />

Imd<br />

Equipment<br />

Differential mode voltage surges circulate between live conductors: Phase to phase<br />

or phase to neutral (see Fig. J7). They are especially dangerous for electronic<br />

equipment, sensitive computer equipment, etc.<br />

Imc<br />

Equipment<br />

J5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

J<br />

J - Protection against voltage surges in LV<br />

2 Overvoltage protection devices<br />

Two major types <strong>of</strong> protection devices are used to suppress or limit voltage surges:<br />

they are referred to as primary protection devices and secondary protection devices.<br />

2.1 Primary protection devices (protection <strong>of</strong><br />

<strong>installation</strong>s against lightning)<br />

The purpose <strong>of</strong> primary protection devices is to protect <strong>installation</strong>s against direct<br />

strokes <strong>of</strong> lightning. They catch and run the lightning current into the ground. The<br />

principle is based on a protection area determined by a structure which is higher<br />

than the rest.<br />

The same applies to any peak effect produced by a pole, building or very high<br />

metallic structure.<br />

There are three types <strong>of</strong> primary protection:<br />

b Lightning conductors, which are the oldest and best known lightning protection<br />

device<br />

b Overhead earth wires<br />

b The meshed cage or Faraday cage<br />

The lightning conductor<br />

The lightning conductor is a tapered rod placed on top <strong>of</strong> the building. It is earthed by<br />

one or more conductors (<strong>of</strong>ten copper strips) (see Fig. J8).<br />

Copper strip<br />

down conductor<br />

Test clamp<br />

Fig. J8 : Example <strong>of</strong> protection using a lightning conductor<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Crow-foot earthing


J - Protection against voltage surges in LV<br />

2 Overvoltage protection devices<br />

The <strong>design</strong> and <strong>installation</strong> <strong>of</strong> a lightning conductor is the job <strong>of</strong> a specialist.<br />

Attention must be paid to the copper strip paths, the test clamps, the crow-foot<br />

earthing to help high frequency lightning currents run to the ground, and the<br />

distances in relation to the wiring system (gas, water, etc.).<br />

Furthermore, the flow <strong>of</strong> the lightning current to the ground will induce voltage<br />

surges, by electromagnetic radiation, in the <strong>electrical</strong> circuits and buildings to be<br />

protected. These may reach several dozen kilovolts. It is therefore necessary to<br />

symmetrically split the down conductor currents in two, four or more, in order to<br />

minimise electromagnetic effects.<br />

Overhead earth wires<br />

These wires are stretched over the structure to be protected (see Fig. J9). They are<br />

used for special structures: rocket launch pads, military applications and lightning<br />

protection cables for overhead high voltage power lines (see Fig. J10).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

h<br />

Fig. J9 : Example <strong>of</strong> lightning protection using overhead earth wires<br />

Fig. J10 : Lightning protection wires<br />

Tin plated copper 25 mm 2<br />

Frame grounded earth belt<br />

i/2<br />

d > 0.1 h<br />

i/2<br />

i<br />

Metal post<br />

Lightning<br />

protection<br />

cables<br />

J<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

J8<br />

J - Protection against voltage surges in LV<br />

Primary lightning conductor protection devices<br />

such as a meshed cage or overhead earth<br />

wires are used to protect against direct strokes<br />

<strong>of</strong> lighting.These protection devices do not<br />

prevent destructive secondary effects on<br />

equipment from occurring. For example, rises<br />

in earth potential and electromagnetic induction<br />

which are due to currents flowing to the earth.<br />

To reduce secondary effects, LV surge arresters<br />

must be added on telephone and <strong>electrical</strong><br />

power networks.<br />

Secondary protection devices are classed in<br />

two categories: Serial protection and parallel<br />

protection devices.<br />

Serial protection devices are specific to a<br />

system or application.<br />

Parallel protection devices are used for: Power<br />

supply network, telephone network, switching<br />

network (bus).<br />

2 Overvoltage protection devices<br />

The meshed cage (Faraday cage)<br />

This principle is used for very sensitive buildings housing computer or integrated<br />

circuit production equipment. It consists in symmetrically multiplying the number <strong>of</strong><br />

down strips outside the building. Horizontal links are added if the building is high; for<br />

example every two floors (see Fig. J11). The down conductors are earthed by frog’s<br />

foot earthing connections. The result is a series <strong>of</strong> interconnected 15 x 15 m or<br />

10 x 10 m meshes. This produces better equipotential bonding <strong>of</strong> the building and<br />

splits lightning currents, thus greatly reducing electromagnetic fields and induction.<br />

Fig. J11 : Example <strong>of</strong> protection using the meshed cage (Faraday cage) principle<br />

2.2 Secondary protection devices (protection <strong>of</strong><br />

internal <strong>installation</strong>s against lightning)<br />

These handle the effects <strong>of</strong> atmospheric, operating or industrial frequency voltage<br />

surges. They can be classified according to the way they are connected in an<br />

<strong>installation</strong>: serial or parallel protection.<br />

Serial protection device<br />

This is connected in series to the power supply wires <strong>of</strong> the system to be protected<br />

(see Fig. J12).<br />

Power supply<br />

Fig. J12 : Serial protection principle<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Serial<br />

protection<br />

Installation to be protected<br />

Transformers<br />

They reduce voltage surges by inductor effect and make certain harmonics<br />

disappear by coupling. This protection is not very effective.<br />

Filters<br />

Based on components such as resistors, inductance coils and capacitors they<br />

are suitable for voltage surges caused by industrial and operation disturbance<br />

corresponding to a clearly defined frequency band. This protection device is not<br />

suitable for atmospheric disturbance.<br />

Up


J - Protection against voltage surges in LV<br />

2 Overvoltage protection devices<br />

Wave absorbers<br />

They are essentially made up <strong>of</strong> air inductance coils which limit the voltage surges,<br />

and surge arresters which absorb the currents. They are extremely suitable for<br />

protecting sensitive electronic and computing equipment. They only act against<br />

voltage surges. They are nonetheless extremely cumbersome and expensive.<br />

Network conditioners and static uninterrupted power supplies (UPS)<br />

These devices are essentially used to protect highly sensitive equipment, such as<br />

computer equipment, which requires a high quality <strong>electrical</strong> power supply. They<br />

can be used to regulate the voltage and frequency, stop interference and ensure a<br />

continuous <strong>electrical</strong> power supply even in the event <strong>of</strong> a mains power failure (for<br />

the UPS). On the other hand, they are not protected against large, atmospheric type<br />

voltage surges against which it is still necessary to use surge arresters.<br />

Parallel protection device<br />

The principle<br />

The parallel protection is adapted to any <strong>installation</strong> power level (see Fig. J13).<br />

This type <strong>of</strong> overvoltage protection is the most commonly used.<br />

Power supply<br />

Parallel<br />

protection<br />

Fig. J13 : Parallel protection principle<br />

Main characteristics<br />

b The rated voltage <strong>of</strong> the protection device must correspond to the network voltage<br />

at the <strong>installation</strong> terminals<br />

b When there is no voltage surge, a leakage current should not go through the<br />

protection device which is on standby<br />

b When a voltage surge above the allowable voltage threshold <strong>of</strong> the <strong>installation</strong><br />

to be protected occurs, the protection device abruptly conducts the voltage surge<br />

current to the earth by limiting the voltage to the desired protection level Up<br />

(see Fig. J14).<br />

Up<br />

U (V)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Up<br />

0 I (A)<br />

Fig. J14 : Typical U/I curve <strong>of</strong> the ideal protection device<br />

Installation to<br />

be protected<br />

When the voltage surge disappears, the protection device stops conducting and<br />

returns to standby without a holding current. This is the ideal U/I characteristic curve:<br />

b The protection device response time (tr) must be as short as possible to protect the<br />

<strong>installation</strong> as quickly as possible<br />

b The protection device must have the capacity to be able to conduct the energy<br />

caused by the foreseeable voltage surge on the site to be protected<br />

b The surge arrester protection device must be able to withstand the rated current In.<br />

J9<br />

© Schneider Electric - all rights reserved


J10<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

2 Overvoltage protection devices<br />

The products used<br />

b Voltage limiters<br />

They are used in MV/LV substations at the transformer output, in IT earthing scheme.<br />

They can run voltage surges to the earth, especially industrial frequency surges<br />

(see Fig. J15)<br />

Fig. J15 : Voltage limiter<br />

Overvoltage<br />

limiter<br />

b LV surge arresters<br />

This term <strong>design</strong>ates very different devices as far as technology and use are<br />

concerned. Low voltage surge arresters come in the form <strong>of</strong> modules to be installed<br />

inside LV switchboard. There are also plug-in types and those that protect power<br />

outlets. They ensure secondary protection <strong>of</strong> nearby elements but have a small flow<br />

capacity. Some are even built into loads although they cannot protect against strong<br />

voltage surges<br />

b Low current surge arresters or overvoltage protectors<br />

These protect telephone or switching networks against voltage surges from the<br />

outside (lightning), as well as from the inside (polluting equipment, switchgear<br />

switching, etc.)<br />

Low current voltage surge arresters are also installed in distribution boxes or<br />

built into loads.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MV/LV<br />

PIM<br />

Permanent<br />

insulation<br />

monitor


J - Protection against voltage surges in LV<br />

3 Protection against voltage<br />

surges in LV<br />

3.1 Surge protective device description<br />

A surge protective device (SDP) is a device that limits transient voltage surges and<br />

runs current waves to ground to limit the amplitude <strong>of</strong> the voltage surge to a safe<br />

level for <strong>electrical</strong> <strong>installation</strong>s and equipment.<br />

The surge protective device includes one or several non linear components.<br />

The surge protective device eliminates voltage surges:<br />

b In common mode: Phase to earth or neutral to earth<br />

b In differential mode: Phase to phase or phase to neutral<br />

When a voltage surge exceeds the Uc threshold, the surge protective device (SDP)<br />

conducts the energy to earth in common mode. In differential mode the diverted<br />

energy is directed to another active conductor.<br />

The surge protective device has an internal thermal protection device which protects<br />

against burnout at its end <strong>of</strong> life. Gradually, over normal use after withstanding<br />

several voltage surges, the Surge Protective Device degrades into a conductive<br />

device. An indicator informs the user when end-<strong>of</strong>-life is close.<br />

Some Surge Protective Devices have a remote indication.<br />

In addition, protection against short-circuits is ensured by an external circuit-breaker.<br />

3.2 Surge protective device standards<br />

International standard IEC 61643-1 ed. 02/2005<br />

Surge protective devices connected to low-voltage power distribution systems.<br />

Three test classes are defined:<br />

b Class I tests: They are conducted using nominal discharge current (In), voltage<br />

impulse with 1.2/50 μs waveshape and impulse current Iimp.<br />

The class I tests is intended to simulate partial conducted lightning current impulses.<br />

SPDs subjected to class I test methods are generally recommended for locations<br />

at points <strong>of</strong> high exposure, e.g., line entrances to buildings protected by lightning<br />

protection systems.<br />

b Class II tests: They are conducted using nominal discharge current (In), voltage<br />

impulse with 1.2/50 μs waveshape<br />

b Class III tests: They are conducted using the combination waveform (1.2/50 and<br />

8/20 μs).<br />

SPDs tested to class II or III test methods are subjected to impulses <strong>of</strong> shorter<br />

duration. These SPDs are generally recommended for locations with lesser exposure.<br />

These 3 test classes cannot be compared, since each originates in a country and<br />

each has its own specificities. Moreover, each builder can refer to one <strong>of</strong> the 3 test<br />

classes.<br />

European standard EN 61643-11 2002<br />

Some requirements as per IEC 61643-1. Moreover SPDs are classified in three<br />

categories:<br />

Type 1: SPD tested to Class I<br />

Type 2: SPD tested to Class II<br />

Type 3: SPD tested to Class III<br />

3.3 Surge protective device data according to<br />

IEC 61643-1 standard<br />

b Surge protective device (SPD): A device that is intended to limit transient<br />

overvoltages and divert surge currents. It contains at least one nonlinear component.<br />

b Test classes: Surge arrester test classification.<br />

b In: Nominal discharge current; the crest value <strong>of</strong> the current through the SPD<br />

having a current waveshape <strong>of</strong> 8/20. This is used for the classification <strong>of</strong> the SPD for<br />

the class II test and also for preconditioning <strong>of</strong> the SPD for class I and II tests.<br />

b Imax: Maximum discharge current for class II test; crest value <strong>of</strong> a current through<br />

the SPD having an 8/20 waveshape and magnitude according to the test sequence<br />

<strong>of</strong> the class II operating duty test. Imax is greater than In.<br />

b Ic: Continuous operating current; current that flows in an SPD when supplied at<br />

its permament full withstand operating voltage (Uc) for each mode. Ic corresponds<br />

to the sum <strong>of</strong> the currents that flow in the SPD’s protection component and in all the<br />

internal circuits connected in parallel.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

J11<br />

© Schneider Electric - all rights reserved


J12<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

Maxi<br />

100 %<br />

50 %<br />

1,2<br />

V<br />

Fig. J17 : 1.2/50 μs wave<br />

50<br />

t<br />

3 Protection against voltage<br />

surges in LV<br />

b Iimp: Impulse current, it is defined by a current peak value Ipeak and the charge<br />

Q. Tested according to the test sequence <strong>of</strong> the operating duty test. This is used for<br />

the classification <strong>of</strong> the SPD for class I test.<br />

b Un: Rated network voltage.<br />

b Uc: Maximum continuous operating voltage; the maximum r.m.s. or d.c. voltage<br />

which may be continuously applied to the SPDs mode <strong>of</strong> protection. This is equal to<br />

the rated voltage.<br />

b Up: Voltage protection level; a parameter that characterizes the performance <strong>of</strong><br />

the SPD in limiting the voltage across its terminals, which is selected from a list <strong>of</strong><br />

preferred values. This value shall be greater than the highest value <strong>of</strong> the measured<br />

limiting voltages.<br />

The most common values for a 230/400 V network are:<br />

1 kV - 1.2 kV - 1.5 kV - 1.8 kV - 2 kV - 2.5 kV.<br />

b Ures: Residual voltage, the peak value <strong>of</strong> the voltage that appears between the<br />

terminals <strong>of</strong> an SPD due to the passage <strong>of</strong> discharge current.<br />

The SPD is characterised by Uc, Up, In and Imax (see Fig. J16)<br />

b To test the surge arrester, standardized voltage and current waves have been<br />

defined that are specific to each country:<br />

v Voltage wave<br />

e.g. 1.2/50 μs (see Fig. J17)<br />

v Current wave<br />

Example 8/20 μs (see Fig. J18)<br />

Fig. J18 : 8/20 μs wave<br />

U p<br />

U c<br />

Maxi<br />

100 %<br />

50 %<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

U<br />

I<br />

< 1 mA<br />

Fig. J16 : Voltage/current characteristics<br />

8<br />

20<br />

I n I max<br />

v Other possible wave characteristics:<br />

4/10 μs, 10/1000 μs, 30/60 μs, 10/350 μs...<br />

Comparison between different surge protective devices must be carried out using the<br />

same wave characteristics, in order to get relevant results.<br />

t<br />

I


J - Protection against voltage surges in LV<br />

(1) According to IEC 60038<br />

(2) In Canada and USA for voltages to earth higher than 300 V,<br />

the impulse withstand voltage corresponding to the<br />

next higher voltage in column one applies.<br />

Category I is addressed to particular equipment engineering.<br />

Category II is addressed to product committees for equipment<br />

for connection to the mains.<br />

Category III is addressed to product committees <strong>of</strong> <strong>installation</strong><br />

material and some special product committees.<br />

Category IV is addressed to supply authorities and system<br />

engineers (see also 443.2.2).<br />

3 Protection against voltage<br />

surges in LV<br />

3.4 Lightning protection standards<br />

The IEC 62305 series (part 1 to 5) restructures and updates the publications <strong>of</strong><br />

IEC 61024 series, IEC 61312 series and IEC 61663 series.<br />

The need for protection, the economic benefits <strong>of</strong> installing protection measures and<br />

the selection <strong>of</strong> adequate protection measures should be determined in terms <strong>of</strong> risk<br />

management. Risk management is the subject <strong>of</strong> IEC 62305-2.<br />

The criteria for <strong>design</strong>, <strong>installation</strong> and maintenance <strong>of</strong> lightning protection measures<br />

are considered in three separate groups:<br />

b The first group concerning protection measures to reduce physical damage and life<br />

hazard in a structure is given in IEC 62305-3.<br />

b The second group concerning protection measures to reduce failures <strong>of</strong> <strong>electrical</strong><br />

and electronic systems in a structure is given in IEC 62305-4.<br />

b The third group concerning protection measures to reduce physical damage and<br />

failures <strong>of</strong> services connected to a structure (mainly <strong>electrical</strong> and telecommunication<br />

lines) is given in IEC 62305-5.<br />

3.5 Surge arrester <strong>installation</strong> standards<br />

b International: IEC 61643-12 selection and application principles<br />

b International: IEC 60364 Electrical <strong>installation</strong>s <strong>of</strong> buildings<br />

v IEC 60364-4-443: protection for safety<br />

When an <strong>installation</strong> is supplied by, or includes, an overhead line, a protection device<br />

against atmospheric overvoltages must be foreseen if the keraunic level <strong>of</strong> the site<br />

being considered corresponds to the external influences condition AQ 1 (more than<br />

25 days per year with thunderstorms).<br />

v IEC 60364-4-443-4: selection <strong>of</strong> equipment in the <strong>installation</strong>.<br />

This section helps with the choice <strong>of</strong> the protection level Up for the surge arrester in<br />

function <strong>of</strong> the loads to be protected.<br />

Rated residual voltage <strong>of</strong> protection devices must not be higher than the value in the<br />

voltage impulse withstand category II (see Fig. J19):<br />

Nominal voltage <strong>of</strong> Required impulse withstand voltage for<br />

the <strong>installation</strong> (1) V kV<br />

Three-phase Single-phase Equipment at Equipment <strong>of</strong> Appliances Specially<br />

systems (2) systems with the origin <strong>of</strong> distribution and protected<br />

middle point the <strong>installation</strong> final circuits equipment<br />

(impulse (impulse (impulse (impulse<br />

withstand withstand withstand withstand<br />

category IV) category III) category II) category I)<br />

120-240 4 2.5 1.5 0.8<br />

230/400 (2) - 6 4 2.5 1.5<br />

277/480 (2)<br />

400/690 - 8 6 4 2.5<br />

1,000 - Values subject to system engineers<br />

Fig. J19 : Choosing equipment for the <strong>installation</strong> according to IEC 60364<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

J13<br />

© Schneider Electric - all rights reserved


J14<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

(1) These values are related to worst case fault conditions,<br />

therefore the tolerance <strong>of</strong> 10 % is not taken into account<br />

3 Protection against voltage<br />

surges in LV<br />

v IEC 60364-5-534: choosing and implementing <strong>electrical</strong> equipment<br />

This section describes surge arrester <strong>installation</strong> conditions:<br />

- According to earthing systems: The maximum continuous operating voltage Uc<br />

<strong>of</strong> SPDs shall be equal to or higher than shown in Fig. J20.<br />

SPDs connected<br />

between<br />

Line conductor and<br />

neutral conductor<br />

Each line conductor and<br />

PE conductor<br />

Neutral conductor and PE<br />

conductor<br />

Each line conductor and<br />

PEN conductor<br />

- At the origin <strong>of</strong> the <strong>installation</strong>: if the surge arrester is installed at the source <strong>of</strong><br />

an <strong>electrical</strong> <strong>installation</strong> supplied by the utility distribution network, its rated discharge<br />

current may be lower than 5 kA.<br />

If a surge arrester is installed downstream from an earth leakage protection device,<br />

an RCD <strong>of</strong> the s type, with immunity to impulse currents <strong>of</strong> less than 3 kA (8/20 μs),<br />

must be used.<br />

- Protection against overcurrent at 50 Hz and consequences <strong>of</strong> a SPD failure:<br />

protection against SPDs short-circuits is provided by the overcurrent protective<br />

devices F2 which are to be selected according to the maximum recommended rating<br />

for the overcurrent protective device given in the manufacturer's SPD instructions.<br />

- In the presence <strong>of</strong> lightning conductors: a surge arrester must be installed,<br />

additional specifications for surge arresters must be applied (see IEC 62305 part 4).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

System configuration <strong>of</strong> distribution network<br />

TT TN-C TN-S IT with<br />

distributed<br />

neutral<br />

IT without<br />

distributed<br />

neutral<br />

1.1 Uo NA 1.1 Uo 1.1 Uo NA<br />

1.1 Uo NA 1.1 Uo 3Uo (1) Line-to-line<br />

voltage (1)<br />

Uo (1) NA Uo (1) Uo (1) NA<br />

NA 1.1 Uo NA NA NA<br />

NA: not applicable<br />

NOTE 1: Uo is the line-to-neutral voltage <strong>of</strong> the low-voltage system.<br />

NOTE 2: This table is based on IEC 61643-1 amendment 1.<br />

Fig. J20 : Minimum required Uc <strong>of</strong> the SPD dependent on supply system configuration


J - Protection against voltage surges in LV<br />

4 Choosing a protection device<br />

When installing surge arresters, several elements must be considered, such as:<br />

b Cascading<br />

b Positioning with respect to residual current devices<br />

b The choice <strong>of</strong> disconnection circuit breakers<br />

The earthing system must also be taken into account.<br />

4.1 Protection devices according to the earthing<br />

system<br />

b Common mode overvoltage: basic protection involves the <strong>installation</strong> <strong>of</strong> a common<br />

mode surge arrester between phase and PE or phase and PEN, whatever type <strong>of</strong><br />

earthing system is used.<br />

b Differential mode overvoltage: in the TT and TN-S earthing systems, earthing the<br />

neutral leads to dissymmetry due to earthing impedances, which causes differential<br />

mode voltages to appear, whereas the overvoltage induced by a lightning strike is a<br />

common mode voltage.<br />

For example, let us consider a TT earthing system. A two-pole surge arrester is<br />

installed in common mode to protect the <strong>installation</strong> (see Fig. J21).<br />

Fig. J21 : Common mode protection only<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I<br />

I<br />

The neutral earthing resistor R1 used for the pylons has a lower resistance than the<br />

earthing resistor R2 used for the <strong>installation</strong>. The lightning current will flow through<br />

circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in<br />

series, causing a differential voltage equal to twice the residual voltage <strong>of</strong> the surge<br />

arrester (Up1 + Up2) to appear at the terminals <strong>of</strong> A and C at the entrance to the<br />

<strong>installation</strong> in extreme cases.<br />

To protect the loads between Ph and N effectively, the differential mode voltage<br />

(between A and C) must be reduced.<br />

Another earthing system is therefore used (see Fig. J22).<br />

The lightning current flows through circuit ABH which has a lower impedance than<br />

circuit ABCD, as the impedance <strong>of</strong> the component used between B and H is null (gas<br />

filled spark gap).<br />

In this case, the differential voltage is equal to the residual voltage <strong>of</strong> the surge<br />

arrester (Up2).<br />

Fig. J22 : Common + differentiel mode protection<br />

I<br />

I<br />

I<br />

I<br />

I<br />

J15<br />

© Schneider Electric - all rights reserved


J16<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

PE<br />

Main earth terminal<br />

Fig. J26 : Connection example<br />

Earthing conductor<br />

4 Choosing a protection device<br />

Mode Between TT TN-S TN-C IT<br />

Differential phase and neutral yes yes - -<br />

Common phase and earth yes yes yes yes<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

phase and earth yes yes - yes (if distributed<br />

neutral)<br />

Fig. J23 : Connections to be made according to the earthing systems used, in the case <strong>of</strong><br />

atmospheric overvoltages<br />

4.2 Internal architecture <strong>of</strong> surge arresters<br />

b 2P, 3P, 4P surge arresters (see Fig. J24):<br />

v They provide protection against common-mode overvoltages only<br />

v They are appropriate for TN-C and IT earthing systems.<br />

Fig. J24 : 2P, 3P, 4P surge arresters<br />

b 1P+N, 3P+N surge arresters (see Fig. J25):<br />

v They provide protection against common-mode and differential-mode overvoltages<br />

v They are appropriate for TT, TN-S, and IT earthing systems.<br />

Fig. J25 : 1P+N, 3P+N surge arresters<br />

b Single-pole (1P) surge arresters (see Fig. J26):<br />

v They are used to satisfy the demand <strong>of</strong> different assemblies (according to the<br />

manufacturer’s instructions) by supplying only one product.<br />

However, special dimensioning will be required for N - PE protection<br />

(for example 1+N and 3P+N)<br />

v The assembly must be validated by means <strong>of</strong> the tests specified in EN 61643-11.


J - Protection against voltage surges in LV<br />

Cascading protection requires a minimum<br />

distance <strong>of</strong> at least 10 m between the two<br />

protection devices.<br />

This is valid, whatever the field <strong>of</strong> application:<br />

domestic, tertiary or industrial.<br />

Fig. J27 : Cascading <strong>of</strong> surge arresters<br />

4 Choosing a protection device<br />

4.3 Installation <strong>rules</strong><br />

The overvoltage protection study <strong>of</strong> an <strong>installation</strong> may show that the site is highly<br />

exposed and that the equipment to be protected is sensitive. The surge arrester<br />

must be able to discharge high currents and have a low level <strong>of</strong> protection. This dual<br />

constraint cannot always be handled by a single surge arrester. A second one will<br />

therefore be required (see Fig. J27).<br />

The first device, P1 (incoming protection) will be placed at the incoming end <strong>of</strong> the<br />

<strong>installation</strong>.<br />

Its purpose will be to discharge the maximum amount <strong>of</strong> energy to earth with a<br />

level <strong>of</strong> protection y 2000 V that can be withstood by the electrotechnical equipment<br />

(contactors, motors, etc.).<br />

The second device (fine protection) will be placed in a distribution enclosure, as<br />

close as possible to the sensitive loads. It will have a low discharge capacity and a<br />

low level <strong>of</strong> protection that will limit overvoltages significantly and therefore protect<br />

sensitive loads (y 1500 V).<br />

Coordination <strong>of</strong> surge arresters<br />

I<br />

The fine-protection device P2 is installed in parallel with the incoming protection<br />

device P1.<br />

If the distance L is too small, at the incoming overvoltage, P2 with a protection<br />

level <strong>of</strong> U2 = 1500 V will operate before P1 with a level <strong>of</strong> U1 = 2000 V. P2 will not<br />

withstand an excessively high current. The protection devices must therefore be<br />

coordinated to ensure that P1 activates before P2. To do this, we shall experiment<br />

with the length L <strong>of</strong> the cable, i.e. the value <strong>of</strong> the self-inductance between the two<br />

protection devices. This self-inductance will block the current flow to P2 and cause a<br />

certain delay, which will force P1 to operate before P2. A metre <strong>of</strong> cable gives a selfinductance<br />

<strong>of</strong> approximately 1μH.<br />

The rule ∆U= Ldi<br />

causes a voltage drop <strong>of</strong> approximately 100 V/m/kA, 8/20 μs<br />

dt<br />

wave.<br />

For L = 10 m, we get UL1 = UL2 ≈ 1000 V.<br />

To ensure that P2 operates with a level <strong>of</strong> protection <strong>of</strong> 1500 V requires<br />

U1 = UL1 + UL2 + U2 = 1000 + 1000 + 1500 V = 3500 V.<br />

Consequently, P1 operates before 2000 V and therefore protects P2.<br />

Note: if the distance between the surge arrester at the incoming end <strong>of</strong> the<br />

<strong>installation</strong> and the equipment to be protected exceeds 30 m, cascading the surge<br />

arresters is recommended, as the residual voltage <strong>of</strong> the surge arrester may rise<br />

to double the residual voltage at the terminals <strong>of</strong> the incoming surge arrester; as in<br />

the above example, the fine protection surge arrester must be placed as close as<br />

possible to the loads to be protected.<br />

The first rule to be observed is to ensure that the connection between the surge<br />

arrester and its disconnection circuit breaker does not exceed 50 cm.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I<br />

Fig. J28 : Coordination <strong>of</strong> surge arresters<br />

I<br />

J17<br />

© Schneider Electric - all rights reserved


J18<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

1<br />

2<br />

3<br />

4 Choosing a protection device<br />

4.4 Selection guide<br />

Estimate the value <strong>of</strong> the equipment to be protected<br />

To estimate its value, consider:<br />

b The cost <strong>of</strong> the equipment in financial terms<br />

b The economic impact if the equipment goes down.<br />

b Domestic equipment:<br />

v audio-video, computers<br />

v household appliances<br />

v burglar alarm.<br />

b Sensitive equipment:<br />

v burglar alarm<br />

v fire alarm<br />

v access control<br />

v video surveillance.<br />

b Pr<strong>of</strong>essional equipment:<br />

v programmable machine<br />

v computer server<br />

v sound or light control system.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

b Building equipment:<br />

v automated heating or<br />

air-conditioning<br />

v lift.<br />

Determine the <strong>electrical</strong> architecture <strong>of</strong> buildings<br />

b Heavy equipment:<br />

v medical infrastructure<br />

v production infrastructure<br />

v heavy computer processing.<br />

Lightning protection can be calculated for an entire building or for part <strong>of</strong> a<br />

building that is <strong>electrical</strong>ly independent<br />

Depending on the size <strong>of</strong> the building and the extent <strong>of</strong> its <strong>electrical</strong> system, one or<br />

more surge arresters must be used in the various switchboards in the <strong>installation</strong>.<br />

b Detached house.<br />

b Apartment, small semi-detached house.<br />

b Communal part <strong>of</strong> a building.<br />

b Pr<strong>of</strong>essional premises.<br />

b Tertiary and industrial buildings:<br />

v single switchboard, main switchboard<br />

v distribution board<br />

v sensitive equipment more than 30 m from the switchboard.<br />

Understand the risk <strong>of</strong> the impact <strong>of</strong> lightning on the site<br />

Lightning is attracted by high points that conduct electricity. They can be:<br />

b Natural: tall trees, mountain crest, wet areas, ferrous soil<br />

b Artificial: chimney, aerial, pylon, lightning conductor.<br />

Indirect effects can be incurred within a fifty metre radius around the point <strong>of</strong> impact.<br />

Location <strong>of</strong> the building<br />

In an urban, peri-urban,<br />

grouped housing area.<br />

In an area where there is a<br />

particular hazard (pylon, tree,<br />

mountainous region, mountain<br />

crest, wet area or pond).<br />

In flat open country. In an exceptionally exposed area<br />

(lightning conductor on a building<br />

less than 50 metres away).


J - Protection against voltage surges in LV<br />

1<br />

Equipment to be<br />

protected<br />

2<br />

Determine the<br />

architecture <strong>of</strong> the<br />

building<br />

3<br />

Risk level <strong>of</strong><br />

the impact <strong>of</strong> a<br />

lightning strike<br />

Choice <strong>of</strong> type <strong>of</strong><br />

surge arrester<br />

Domestic equipment<br />

Type 2<br />

10 kA<br />

Detached house,<br />

Pr<strong>of</strong>essional<br />

premises<br />

Type 2<br />

40 kA<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Audio-video, computers,<br />

household appliances,<br />

burglar alarm, etc.<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Apartment, small<br />

semi-detached<br />

house<br />

Type 2<br />

10 kA<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Communal part <strong>of</strong> a<br />

building<br />

Note:<br />

Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level <strong>of</strong> and .<br />

Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and .<br />

Fig. J32 : Domestic equipment<br />

Lightning also propagates through<br />

telecommunications networks.<br />

It can damage all the equipment connected to<br />

these networks.<br />

4 Choosing a protection device<br />

Type 2<br />

40 kA<br />

Protection <strong>of</strong> telecommunications equipment<br />

Type 2<br />

65 kA<br />

Choice <strong>of</strong> surge arresters PRC<br />

Analogue telephone networks < 200 V b<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

J19<br />

© Schneider Electric - all rights reserved


J20<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

1<br />

Equipment to be<br />

protected<br />

2<br />

Determine the<br />

architecture <strong>of</strong> the<br />

building<br />

3<br />

Risk level <strong>of</strong><br />

the impact <strong>of</strong> a<br />

lightning strike<br />

Choice <strong>of</strong> type <strong>of</strong><br />

surge arrester<br />

Sensitive equipment: Building equipment:<br />

Type 2<br />

20 kA<br />

Single<br />

switchboard,<br />

main<br />

switchboard<br />

Type 2<br />

40 kA<br />

Type 2<br />

40 kA<br />

Burglar alarm,<br />

fire alarm,<br />

access control,<br />

video-surveillance, etc.<br />

Type 1<br />

25 kA<br />

or<br />

35 kA<br />

+<br />

Type 2<br />

40 kA<br />

Distribution<br />

board<br />

Type 2<br />

20 kA<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Automated heating or<br />

air-conditioning,<br />

lift, etc.<br />

Dedicated<br />

protection,<br />

more than<br />

30 m from a<br />

switchboard<br />

Note:<br />

Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level <strong>of</strong> and .<br />

Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and .<br />

Fig. J33 : Sensitive equipment, Building equipment<br />

4 Choosing a protection device<br />

Type 2<br />

8 kA


J - Protection against voltage surges in LV<br />

1<br />

Equipment to be<br />

protected<br />

2<br />

Determine the<br />

architecture <strong>of</strong> the<br />

building<br />

3<br />

Risk level <strong>of</strong><br />

the impact <strong>of</strong> a<br />

lightning strike<br />

Choice <strong>of</strong> type <strong>of</strong><br />

surge arrester<br />

Note:<br />

Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level <strong>of</strong> and .<br />

Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and .<br />

Fig. J34 : Pr<strong>of</strong>essional equipment<br />

Pr<strong>of</strong>essional equipment<br />

Type 2<br />

40 kA<br />

Single<br />

switchboard,<br />

main<br />

switchboard<br />

Type 2<br />

65 kA<br />

Type 2<br />

65 kA<br />

Programmable machine,<br />

server,<br />

sound or light control system,<br />

etc.<br />

Type 1<br />

25 kA<br />

or<br />

35 kA<br />

+<br />

Type 2<br />

40 kA<br />

4 Choosing a protection device<br />

Distribution<br />

board<br />

Type 2<br />

20 kA<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Dedicated<br />

protection,<br />

more than<br />

30 m from a<br />

switchboard<br />

Type 2<br />

8 kA<br />

J21<br />

© Schneider Electric - all rights reserved


J22<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

1<br />

Equipment to be<br />

protected<br />

2<br />

Determine the<br />

architecture <strong>of</strong> the<br />

building<br />

3<br />

Risk level <strong>of</strong><br />

the impact <strong>of</strong> a<br />

lightning strike<br />

Choice <strong>of</strong> type <strong>of</strong><br />

surge arrester<br />

Heavy equipment<br />

Type 2<br />

65 kA<br />

Single<br />

switchboard,<br />

main<br />

switchboard<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Type 1<br />

25 kA<br />

or<br />

35 kA<br />

+<br />

Type 2<br />

40 kA<br />

Medical, production,<br />

or heavy computer<br />

processing infrastructure,<br />

etc.<br />

Type 1<br />

25 kA<br />

or<br />

35 kA<br />

+<br />

Type 2<br />

40 kA<br />

Distribution<br />

board<br />

Type 2<br />

20 KA<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Dedicated<br />

protection,<br />

more than<br />

30 m from a<br />

switchboard<br />

Note:<br />

Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level <strong>of</strong> and .<br />

Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and .<br />

Fig. J35 : Heavy equipment<br />

Lightning can also propagate through<br />

telecommunications and computer networks.<br />

It can damage all the equipment connected<br />

to these networks: telephones, modems,<br />

computers, servers, etc.<br />

4 Choosing a protection device<br />

Type 2<br />

8 kA<br />

Protection <strong>of</strong> telecommunications and computer equipment<br />

Choice <strong>of</strong> surge arresters PRC PRI<br />

Analogue telephone networks < 200 V b<br />

Digital networks, analogue lines < 48 V<br />

Digital networks, analogue lines < 6 V<br />

VLV load supply < 48 V<br />

b<br />

b


J - Protection against voltage surges in LV<br />

4.5 Choice <strong>of</strong> disconnector<br />

The disconnector is necessary to ensure the safety <strong>of</strong> the <strong>installation</strong><br />

b One <strong>of</strong> the surge arrester parameters is the maximum current (Imax 8/20 μs<br />

wave) that it can withstand without degradation. If this current is exceeded, the surge<br />

arrester will be destroyed; it will be permanently short circuited and it is essential to<br />

replace it.<br />

The fault current must therefore be eliminated by an external disconnector installed<br />

upstream.<br />

The disconnector provides the complete protection required by a surge arrester<br />

<strong>installation</strong>, i.e.:<br />

v It must be able to withstand standard test waves:<br />

- it must not trip at 20 impulses at In<br />

- it can trip at Imax without being destroyed<br />

v the surge arrester disconnects if it short-circuits.<br />

b The ready-to-cable surge arresters with an integrated disconnection circuit breaker<br />

are:<br />

v Combi PRF1<br />

v Quick PF<br />

v Quick PRD.<br />

Surge arrester / disconnection circuit breaker correspondence<br />

table<br />

Types Isc Surge arresters 6 kA 10 kA 15 kA 25 kA 36 kA 50 kA 70 kA<br />

Type 1<br />

Type 2<br />

35 kA (1) PRF1 Master NH 160 A gL/gG fuse<br />

25 kA (1) PRF1 D125 NH 125 A gL/gG fuse<br />

65 kA (2) PF65, PRD65 C60N<br />

50 A<br />

Curve C<br />

40 kA (2) PF40, PRD40 C60N<br />

40 A<br />

Curve C<br />

20 kA (2) PF20, PRD20 C60N<br />

25 A<br />

Curve C<br />

8 kA (2) C60N<br />

20 A<br />

Curve C<br />

Isc: prospective short-circuit current at the point <strong>of</strong> <strong>installation</strong>.<br />

(1) Iimp.<br />

(2) Imax.<br />

Fig. J36 : Correspondence between surge arrester / disconnection circuit breaker<br />

4 Choosing a protection device<br />

NS160N 160 A NS160H<br />

160 A<br />

C60H<br />

50 A<br />

Curve C<br />

C60H<br />

40 A<br />

Curve C<br />

C60H<br />

25 A<br />

Curve C<br />

C60H<br />

20 A<br />

Curve C<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Contact us<br />

Contact us<br />

Contact us<br />

4.6 End-<strong>of</strong>-life indication <strong>of</strong> the surge arrester<br />

Various indication devices are provided to warn the user that the loads are no longer<br />

protected against atmospheric overvoltages.<br />

Type 1 surge arresters (with gas filled spark gap)<br />

PRF1 1P 260 V, Combi 1P+N and 3P+N and PRF1 Master<br />

These surge arresters have a light indicating that the module is in good working<br />

order. This indicator light requires a minimum operating voltage <strong>of</strong> 120 V AC.<br />

b The light does not come on:<br />

v if the operating voltage is y 120 V AC<br />

v if there is no network voltage<br />

v if the spark-over electronics are defective.<br />

J23<br />

© Schneider Electric - all rights reserved


J24<br />

© Schneider Electric - all rights reserved<br />

J - Protection against voltage surges in LV<br />

Fig. J37 : Example <strong>of</strong> indication for PRD<br />

Fig. J39 : Example <strong>of</strong> indication for Quick PRD<br />

4 Choosing a protection device<br />

Type 2 surge arresters (varistor, varistor + gas filled spark gap)<br />

PF, PRD<br />

At end <strong>of</strong> life, the surge arrester or the cartridge are destroyed.<br />

b This can occur in two ways:<br />

v internal end-<strong>of</strong>-life disconnection: the accumulated electric shocks cause the<br />

varistors to age, resulting in an increase in leakage current.<br />

Above 1 mA, a thermal runaway occurs and the surge arrester disconnects.<br />

v external end-<strong>of</strong>-life disconnection: this occurs in the event <strong>of</strong> an excessive<br />

overvoltage (direct lightning strike on the line); above the discharge capacity <strong>of</strong> the<br />

surge arrester, the varistor(s) are dead short-circuited to earth (or possibly between<br />

phase and neutral). This short-circuit is eliminated when the mandatory associated<br />

disconnection circuit breaker opens.<br />

Quick PRD and Quick PF<br />

Whatever the hazards <strong>of</strong> the power supply network, Quick PRD and Quick PF<br />

incorporate a perfectly coordinated disconnector.<br />

b In the event <strong>of</strong> lightning strikes < Imax: like all surge arresters, they have internal<br />

anti-ageing protection.<br />

b In the event <strong>of</strong> a lightning strike > Imax: Quick PRD and Quick PF are selfprotected<br />

by their integrated disconnector.<br />

b In the event <strong>of</strong> neutral disconnection or phase-neutral reversal occurring on the<br />

power supply:<br />

Quick PRD and Quick PF are self-protected by their integrated disconnector.<br />

To simplify maintenance work, Quick PRD is fitted with local indicators and draw-out<br />

cartridges that are mechanically combined with the disconnector.<br />

Quick PRD has indicator lights on the cartridges and on the integrated disconnector,<br />

so that the work to be carried out can quickly be located.<br />

For safety reasons, the disconnector opens automatically when a cartridge is<br />

removed. It cannot be set until the cartridge is plugged in.<br />

When changing the cartridge, a phase/neutral failsafe system ensures that it can be<br />

plugged in safely.<br />

Operating state continuous display<br />

Quick PRD has an integrated reporting contact to send information about the<br />

operating state <strong>of</strong> the surge arrester from a remote location.<br />

Monitoring the surge arresters installed throughout the <strong>installation</strong> makes it possible<br />

to be continuously aware <strong>of</strong> their operating state and to ensure that the protection<br />

devices are always in good working order.<br />

b A reporting contact gives the alert:<br />

v at end <strong>of</strong> life <strong>of</strong> a cartridge<br />

v if a cartridge is missing, as soon as it has been removed<br />

v if a fault occurs on the line (short-circuit, neutral disconnection, phase-neutral<br />

reversal)<br />

v in the event <strong>of</strong> local manual operation (handle down).<br />

Quick PF has an optional indication reporting auxiliary (SR) that sends information<br />

about the operating state <strong>of</strong> the surge arrester from a remote location.<br />

4.7 Application example: supermarket<br />

Solutions and schematic diagram<br />

b The surge arrester selection guide has made it possible to determine the precise<br />

value <strong>of</strong> the surge arrester at the incoming end <strong>of</strong> the <strong>installation</strong> and that <strong>of</strong> the<br />

associated disconnection circuit breaker.<br />

b As the sensitive devices (Uimp < 1.5 kV) are located more than 30 m from the<br />

incoming protection device, the fine protection surge arresters must be installed as<br />

close as possible to the loads.<br />

b To ensure better continuity <strong>of</strong> service for cold room areas:<br />

v"si" type residual current circuit breakers will be used to avoid nuisance tripping<br />

caused by the rise in earth potential as the lightning wave passes through.<br />

b For protection against atmospheric overvoltages:<br />

v install a surge arrester in the main switchboard<br />

v install a fine protection surge arrester in each switchboard (1 and 2) supplying the<br />

sensitive devices situated more than 30 m from the incoming surge arrester<br />

v install a surge arrester on the telecommunications network to protect the devices<br />

supplied, for example fire alarms, modems, telephones, faxes.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


J - Protection against voltage surges in LV<br />

Fig. J40 : Telecommunications network<br />

4 Choosing a protection device<br />

Main<br />

switchboard<br />

C60<br />

20 A<br />

PRD<br />

8 kA<br />

C60<br />

40 A<br />

PRD<br />

40 kA<br />

MV/LV transformer<br />

160 kVA<br />

Switchboard 1 Switchboard<br />

2<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

ID<br />

"si"<br />

ID<br />

"si"<br />

Heating Lighting Freezer Refrigerator<br />

Storeroom lighting Power outlets<br />

Fig. J39 : Application example : supermarket<br />

Function <strong>of</strong> the surge arrester protection<br />

C60<br />

20 A<br />

PRD<br />

8 kA<br />

Fire-fighting system Alarm<br />

IT system Checkout<br />

b Conduct the lightning current to earth, ensuring a level <strong>of</strong> protection Up compatible<br />

with the <strong>electrical</strong> equipment to be protected.<br />

b Limit the rise in earth potential and the magnetic field induced.<br />

Cabling recommendations<br />

b Ensure the equipotentiality <strong>of</strong> the earth terminations <strong>of</strong> the building.<br />

b Reduce the looped power supply cable areas.<br />

Installation recommendations<br />

b Install a surge arrester, Imax = 40 kA (8/20 μs) and a C60 disconnection circuit<br />

breaker rated at 20 A.<br />

b Install fine protection surge arresters, Imax = 8 kA (8/20 μs) and the associated<br />

C60 disconnection circuit breakers rated at 20 A.<br />

J25<br />

© Schneider Electric - all rights reserved


2<br />

3<br />

4<br />

5<br />

<strong>Chapter</strong> K<br />

Energy Efficiency in <strong>electrical</strong><br />

distribution<br />

Contents<br />

Introduction K2<br />

Energy efficiency and electricity K3<br />

2.1 The world is now ready for energy-efficient actions and programs. K3<br />

2.2 A new challenge: <strong>electrical</strong> data K4<br />

One process, several players K5<br />

3.1 Energy Efficiency needs an Enterprise approach K5<br />

3.2 Economic competitiveness study K6<br />

3.3 The varied pr<strong>of</strong>iles and missions <strong>of</strong> players in the company K8<br />

From <strong>electrical</strong> measurement to <strong>electrical</strong> information K 0<br />

4.1 Physical value acquisition K10<br />

4.2 Electrical data for real objectives K12<br />

4.3 Measurement starts with the "stand alone product" solution K13<br />

Communication and Information System k 6<br />

5.1 Communication network at product, equipment and site level<br />

5.2 From Network Monitoring and Control System<br />

K16<br />

to Intelligent Power Equipment K19<br />

5.3 e-Support becomes accessible K21<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

K2<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Certain information in this chapter is taken<br />

from guides published by Carbon Trust<br />

(www.carbontrust.co.uk) GPG119 and GPG231.<br />

Introduction<br />

Power monitoring and control system may be <strong>of</strong> high benefice for the owner <strong>of</strong> an<br />

<strong>electrical</strong> network as a strategic piece in the global “Energy Efficiency” approach.<br />

Calculating Total Cost <strong>of</strong> Ownership (TCO) <strong>of</strong> an <strong>electrical</strong> network not only includes<br />

the initial equipment investment but also its economic performance in operation.<br />

Safety staff, the <strong>electrical</strong> billing manager, the chief site electrician or the facility<br />

manager, are all becoming increasingly concerned. The pr<strong>of</strong>iles vary, but each <strong>of</strong><br />

these people's mission includes careful management <strong>of</strong> electricity, its procurement<br />

and the network that distributes it.<br />

Fewer expensive power outages for the company’s business, less consumption<br />

wastage, no more maintenance operations than necessary, these are the objectives<br />

that a decision making assistance system focused on Energy Efficiency must satisfy<br />

and make available to each person, whatever their pr<strong>of</strong>ile.<br />

Nowadays, entering the “Energy Efficiency” approach doesn’t mean setting-up a<br />

complex and expensive system. Some simple features are really affordable with a<br />

very good payback because they can be directly embedded in the power equipment.<br />

Once the <strong>electrical</strong> <strong>installation</strong> is equipped with measurement functions, it can share<br />

the communication medium <strong>of</strong> the user’s Intranet site. In addition operation won’t<br />

need specific skills and training. It will only require the use <strong>of</strong> license-free s<strong>of</strong>tware<br />

such as Intranet browsers.<br />

Upgradeability or e-services through Internet are also now a reality, based on new<br />

technologies that come from the Office and Communication world. Then being in<br />

a position <strong>of</strong> taking advantages <strong>of</strong> these new possibilities will be more and more a<br />

differentiating behavior.<br />

Forecasting - Anticipation<br />

Extensions<br />

Improvement<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

New Design Retr<strong>of</strong>it<br />

End <strong>of</strong> life<br />

Design <strong>installation</strong><br />

Maintenance optimization<br />

MV<br />

LV<br />

ASI<br />

Sheddable Offices<br />

HVAC<br />

MV<br />

LV<br />

MLVS 1 MLVS 2<br />

PROCESS<br />

Trunking<br />

Operation<br />

e-services


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

2 Energy efficiency and electricity<br />

2.1 The world is now ready for energy-efficient<br />

actions and programs.<br />

The first big movement was initiated by the Kyoto protocol in 1997, updated in 2006.<br />

This well known world wide agreement requires participating countries to collectively<br />

reduce greenhouse gas emissions to an annual average <strong>of</strong> about 5 percent below<br />

the 1990 level over the 2008-2012 period.<br />

The protocol is based on three primary market mechanisms:<br />

b The Clean Development Mechanism (CDM), arrangement for reductions to be<br />

"sponsored" in countries not bound by emission targets<br />

b Joint Implementation, program that allows industrialized countries to meet part<br />

<strong>of</strong> their required cuts in greenhouse-gas emissions by implementing projects that<br />

reduce emissions in other countries.<br />

b Emissions trading, mechanism through which Parties with emission commitments<br />

may trade units <strong>of</strong> their emission allowances with other Parties because they are<br />

ahead <strong>of</strong> their target. This is the so called “carbon market”.<br />

All geographic areas at country, regional and federal level have launched<br />

programs, actions, regulations:<br />

b regulations and standards enforced in Europe (Fig. K1),<br />

b vision and strong initiatives in Asia.<br />

b strong programs in the US<br />

Fig. K1 : European parliament and counsel directive 2006/32/CE dated 5 April 2006 relative to<br />

the energy efficiency for end users and energy services<br />

ISO 14001 that defines principles and processes to permanently reduce energy consumption<br />

and waste emission in any organization.<br />

Drivers to develop energy efficiency programs – especially on the <strong>electrical</strong> form <strong>of</strong><br />

energy - are getting stronger and stronger. Energy Efficiency plan is at the top <strong>of</strong> the<br />

agenda for a growing number <strong>of</strong> companies:<br />

b Buildings are the biggest energy consumers and a priority target,<br />

b With cost <strong>of</strong> energy multiplied by 2 in the last 3 years, electricity saving is<br />

becoming a significant source <strong>of</strong> productivity gain for the industry,<br />

b Saving energy is now a part <strong>of</strong> the Corporate Social Responsibility commitment <strong>of</strong><br />

most listed companies,<br />

b With production and distribution networks under increased pressure from rising<br />

demand and scarce resources, availability <strong>of</strong> electricity is a rising concern for<br />

Industry heavily impacted by the consequences <strong>of</strong> outages,<br />

b The residential sector is a key sector and more and more impacted.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

K<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Fig. K2 : The Schneider Electric Solutions for Power & Control<br />

2 Energy efficiency and electricity<br />

2.2 A new challenge: <strong>electrical</strong> data<br />

All <strong>of</strong> the features <strong>of</strong> the current developments lead to the appearance <strong>of</strong> a “New<br />

Electrical World” in which the key considerations will be:<br />

b controlling risks related to power outages<br />

b energy yield or efficiency and control <strong>of</strong> costs: MWh price increased between 2003<br />

and 2006 from 30€ up to 60€ for deregulated markets in Europe<br />

b renewable energy<br />

b the environment and sustainable development.<br />

Electricity usage will become smarter and more rational to contribute both to the<br />

competitiveness <strong>of</strong> companies, their energy independence and protection <strong>of</strong> the<br />

environment. These new ground-<strong>rules</strong> mean that corporate decision makers have<br />

to implement new resources, and in particular products and services to accompany<br />

electricity consumers in this approach.<br />

In particular, the setting up <strong>of</strong> a global information system in the company will allow<br />

comprehensive <strong>electrical</strong> performance data to be streamed, in real time and remotely<br />

for (Fig. K2):<br />

b Predicting <strong>electrical</strong> network non-availability,<br />

b Recording <strong>electrical</strong> quality,<br />

b Optimizing consumption per building, sector, unit, workshop, site, excessive<br />

consumption or abnormal variations. We will therefore have all <strong>of</strong> the data required<br />

to make direct savings on electricity billing. End users can therefore take advantage<br />

<strong>of</strong> <strong>electrical</strong> network monitoring to avoid any wastage and to supply energy where it<br />

is really necessary.<br />

b Organizing <strong>electrical</strong> equipment maintenance.<br />

b Better purchasing <strong>of</strong> <strong>electrical</strong> energy and in certain cases, better resale.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Fig. K3 : Step by step approach to organizing energy<br />

management<br />

Level<br />

4<br />

2<br />

0<br />

b Gain commitment<br />

b Identify stakeholder needs<br />

b Establish policy<br />

b Set objectives and targets<br />

b Prepare action plan<br />

b Allocate roles and<br />

responsabilities<br />

b Prioritise investments<br />

b Train<br />

b Consider business<br />

integration and barriers<br />

to implementation<br />

b Audit process<br />

b Distribute audit findings<br />

3 One process, several players<br />

3.1 Energy Efficiency needs an Enterprise approach<br />

An information system must be integrated in a global approach in the company.<br />

The following step by step approach to organizing energy management (as shown<br />

in figure K1) is a structured method for managing projects and achieving results. It<br />

can be applied to very simple as well as complex tasks and has proved itself to be<br />

both robust and practical.<br />

Refer to 6 Sigma philosophy - Define, Measure, Analyze, Improve, Control - you<br />

cannot fix what you do not measure.<br />

Gain commitment<br />

In order to achieve action towards lasting energy efficiency, it is essential to gain the<br />

commitment <strong>of</strong> the most senior members <strong>of</strong> the management team as individuals<br />

and part <strong>of</strong> the corporate body.<br />

Understanding begins with:<br />

b learning about current energy consumption levels and costs<br />

b mapping the ways in which energy is used<br />

b determining the standards for efficient consumption in the organization<br />

b analyzing the possibilities for saving costs through reducing energy consumption<br />

so that realistic targets can be set<br />

b recognizing the environmental effects <strong>of</strong> energy consumption.<br />

Plan and organize<br />

The first step should be to produce a suitable energy policy for the organization. By<br />

developing and publishing such a policy, senior managers promote their commitment<br />

to achieving excellence in energy management. They should do this in a way that<br />

harnesses the culture <strong>of</strong> the organization to best effect.<br />

Implement<br />

Everyone must have some involvement in implementing the energy policy. However,<br />

to facilitate a structured approach, start by assigning special responsibilities to some<br />

individuals and groups.<br />

Control and monitor<br />

Each project should have an owner – an individual or a team with overall<br />

responsibility for monitoring efforts and steering it to a successful conclusion. Again<br />

Information System linked to <strong>electrical</strong> energy use and its impact on the core activity<br />

<strong>of</strong> the company will support the owner’s actions.<br />

Senior executives should underline the importance <strong>of</strong> projects by requiring regular<br />

progress reports, and by publicizing and endorsing success, which can further<br />

support individual motivation and commitment.<br />

The energy management matrix:<br />

Energy policy Organising Motivation Informations systems Marketing Investment<br />

Energy policy, action<br />

plan and regular review<br />

have commitment <strong>of</strong> top<br />

management as part<br />

<strong>of</strong> an environmental<br />

strategy<br />

Unadopted energy policy<br />

set by energy manager<br />

or senior departmental<br />

manager<br />

Get<br />

commitment<br />

Understand<br />

Plan and<br />

organize<br />

Implement<br />

Control and<br />

monitor<br />

Energy management<br />

fully integrated into<br />

management structure.<br />

Clear delegation <strong>of</strong><br />

responsability for energy<br />

consumption<br />

Energy manager in<br />

post, reporting to<br />

ad-hoc committee, but<br />

line management and<br />

authority are unclear<br />

No explicit policy No energy management<br />

or any format delegation<br />

<strong>of</strong> responsibility for<br />

energy consumption<br />

Formal and informal Comprehensive system<br />

channels <strong>of</strong><br />

sets targets, monitors<br />

communication regularity consumption, identifies<br />

exploited by energy faults, quantifies savings<br />

manager and energy staff and provides budget<br />

at all levels<br />

tracking<br />

Contact with major<br />

users through ad-hoc<br />

committee chaired by<br />

senior departmental<br />

manager<br />

Monitoring and targeting<br />

reports based on supply<br />

meter data. Energy unit<br />

has ad-doc involvement<br />

in budget setting<br />

No contact with users No information system.<br />

No accounting for energy<br />

consumption<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Marketing the value <strong>of</strong><br />

energy efficiency and the<br />

performance <strong>of</strong> energy<br />

management both within<br />

the organisation and<br />

outside it<br />

Some ad-doc staff<br />

awareness training<br />

No promotion <strong>of</strong> energy<br />

efficiency<br />

Positive discrimination<br />

in favour <strong>of</strong> "green"<br />

schemes with detailed<br />

investment appraisal<br />

<strong>of</strong> all new-build<br />

and refurbishment<br />

opportunities<br />

Investment using short<br />

term pay back criteria<br />

only<br />

No investment in<br />

increasing energy<br />

efficiency in premises<br />

K<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

K<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

3.2 Economic competitiveness study<br />

Company data 00000 Automatic calculation Contributing factors Savings per Item<br />

Fig. K4 : Example for calculating the return on investment<br />

3 One process, several players<br />

An information system on energy efficiency related to <strong>electrical</strong> usage must also<br />

be looked at in terms <strong>of</strong> an economic study to ensure the growth <strong>of</strong> economic<br />

competitiveness.<br />

This study basically depends on allocating financial value to electricity consumption,<br />

to operating losses related to the non-availability <strong>of</strong> energy and to maintenance costs<br />

in order to better manage the <strong>electrical</strong> <strong>installation</strong>.<br />

Preliminary stage: review the current situation and build a financial study<br />

(Figure K4).<br />

The need for a measurement <strong>installation</strong> is justified by the gains that this generates.<br />

A solution that covers the full <strong>installation</strong> represents a major improvement in the<br />

company’s competitiveness, but it requires the team concerned to actually use this<br />

capacity.<br />

Example :<br />

The figure below is an example for calculating the return on investment – available in<br />

Excel on www.transparentready.com.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Savings / Investment per<br />

category<br />

Total savings or<br />

investment<br />

Background: your organisation’s characteristics<br />

Annual revenues 100,000,000<br />

Net pr<strong>of</strong>it (%) 10 %<br />

Annual work hours (hours/day x days/week x weeks/year) 1.950 hrs<br />

Average hourly wage (loaded rate) 75<br />

Annual <strong>electrical</strong> energy costs 1,000,000<br />

Interest rate 15 %<br />

Corporate tax rate 30 %<br />

Annual energy cost savings potential<br />

Reduction in energy usage (% estimated) 10 %<br />

Reduction in energy usage 100,000<br />

Reduction in demand charges 20,000<br />

Power factor penalties avoided 20,000<br />

Energy billing errors avoided 5,000<br />

Energy costs allocated to tenants 0<br />

Annual energy cost savings 145,000<br />

Downtime cost avoidance potential<br />

Number <strong>of</strong> downtime events per year 2<br />

Hours <strong>of</strong> downtime per event 1.5 hrs<br />

Hours to recovery per downtime event 2 hrs<br />

Employees idled per downtime event 250<br />

Manufacturing employees required for line start-up 10<br />

IS employees required for computer system recovery 2<br />

Reduction in equipment replacements (e.g., transformers) 25,000<br />

Reduction in scrapped products or parts 50,000<br />

Corporate pr<strong>of</strong>it increase 15,385<br />

Increase in productive work hours 56,250<br />

Reduction in computer system recovery hours 600<br />

Reduction in manufacturing line start-up costs 3,000<br />

Annual downtime cost avoidance 150,235<br />

Operations & maintenance savings potential<br />

Employees assigned to manually read meters 3<br />

Employees assigned to maintenance 2<br />

Employees assigned to energy data analysis 2<br />

Activity-based costing savings (e.g., equipment or process removal) 50,000<br />

Equipment maintenance savings 10,000<br />

Automatic meter reading 7,875<br />

Fewer maintenance inspections 2,250<br />

Fewer hours for data analysis 10,500<br />

Operations & maintenance savings 80,625<br />

Total annual gross savings potential 375,860<br />

Transparent Ready system investment<br />

Number <strong>of</strong> buildings where energy is to be managed 2<br />

Metering devices, main/critical feeders, per building 10<br />

Metering devices, non-critical feeders, per building 15<br />

Metering devices, simple energy usage, per building 15<br />

Device costs 125,000<br />

S<strong>of</strong>tware costs 15,000<br />

Computer equipment costs 8,000<br />

Installation 160,000<br />

Configuration 8,000<br />

Training 3,500<br />

Support contract 14,338<br />

Total system investment 333,838<br />

ROI summary<br />

Invested capital -333,838<br />

Gross annual savings 375,860<br />

Yearly depreciation -66,768<br />

Corporate tax -112,758<br />

Net annual savings (after taxes and depreciation) 196,334<br />

Payback period (before tax & dep) (in months) 11<br />

Payback period (after tax & dep) (in months) 20<br />

Net present value 324,304<br />

Discounted return on investment (NPV / Invested Capital) 97 %


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Invest in three steps<br />

1- Formulate priorities<br />

2- Define key <strong>electrical</strong> values<br />

3- Select components<br />

3 One process, several players<br />

Step 1 : formulate priorities<br />

Each industrial or tertiary site has its own requirements and a specific <strong>electrical</strong><br />

distribution architecture. According to the site’s requirements, determine the<br />

appropriate energy efficiency applications (Figure K ):<br />

Objective Application<br />

Consumption optimization Cost allocation<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Energy usage analysis<br />

Pumps & fans for Industry & Infrastructure<br />

Pumps & fans for Buildings<br />

Lighting control<br />

Energy purchasing optimization Peak demand reduction<br />

Improving the efficiency <strong>of</strong><br />

teams in charge <strong>of</strong> <strong>electrical</strong><br />

<strong>installation</strong> operation<br />

Improving energy availability<br />

and quality<br />

Electricity procurement optimization<br />

Sub-billing<br />

Electrical Distribution alarming and event logging<br />

Electrical Distribution network remote control<br />

Electrical Distribution network automation<br />

Asset optimization Statistical analysis <strong>of</strong> equipment usage - Power Factor<br />

Correction<br />

Fig. K5 : Objective and application<br />

Step 2 : define key <strong>electrical</strong> values<br />

b once we have formulated the priorities, we can define the key <strong>electrical</strong> values to<br />

be included in the measurement system<br />

b the parameters to take into account must allow us to detect a disturbance or a<br />

phenomenon as soon as it appears, in other words before it has a detrimental effect<br />

to the <strong>electrical</strong> <strong>installation</strong> and its current consumers<br />

b the method includes installing an appropriate device on each feeder concerned so<br />

as to be as ready as possible for requirements, and another at the site <strong>installation</strong><br />

head so as to have an overview. However, we also need to identify vital feeders for<br />

the company’s business and feeders on costly processes so as to take account <strong>of</strong><br />

this information in the solution.<br />

Example: if the application consumes a lot <strong>of</strong> electricity and is not sensitive to quality, the<br />

metering system involves the appropriate measurement products. In the same way, a highly<br />

sensitive application in terms <strong>of</strong> energy quality requires a different type <strong>of</strong> metering product.<br />

Step 3 : select components<br />

For existing <strong>installation</strong>s: some <strong>of</strong> your <strong>electrical</strong> equipment already includes<br />

measurement products.<br />

Example: protection relays <strong>of</strong>ten include measurement functions. You simply have to make them<br />

communicate via a Modbus series link to the intranet site.<br />

K<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

K<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Pr<strong>of</strong>ile Org Skill Role Data display When? Data format<br />

Security staff Site No specific technical<br />

<strong>electrical</strong> skills.<br />

Maintenance<br />

Manager<br />

Safety <strong>of</strong> people and<br />

property.<br />

Via an alarm screen<br />

in the central security<br />

station. By DECT*, GSM<br />

or general circulation.<br />

Site People management, With his team, ensuring MMS/SMS, PC on<br />

overall <strong>electrical</strong> network the correct technical Intranet, email.<br />

skills, has been in his operation in all areas<br />

position for 3 to 8 years, (refrigeration, air<br />

technician level with conditioning, electricity,<br />

strong decision making security, public safety<br />

independence. Delegates etc.). Priority is given<br />

electrotechnical problems to availability, he is<br />

to outside organizations challenged on overheads<br />

(e.g.: calculating and therefore on <strong>electrical</strong><br />

protection settings). consumption, decides<br />

on the involvement <strong>of</strong><br />

outside companies and<br />

contributes to investment<br />

dossiers.<br />

Site Manager Site Competency in corporate<br />

management and in<br />

executive management.<br />

EE Manager for<br />

a multinational<br />

company<br />

Site/HQ Buyer/ global energy<br />

purchasing contract<br />

negotiator.<br />

Fig. K6 : The varied pr<strong>of</strong>iles and missions <strong>of</strong> players in the company<br />

3 One process, several players<br />

3.3 The varied pr<strong>of</strong>iles and missions <strong>of</strong> players in<br />

the company<br />

The setting up <strong>of</strong> an information system allows access to important data from<br />

<strong>electrical</strong> equipment and must involve staff with a IT and <strong>electrical</strong> knowledge pr<strong>of</strong>ile<br />

which by definition is very varied in the company. (Figures K and K ).<br />

Example : the table below shows a few examples <strong>of</strong> the pr<strong>of</strong>iles in a hypermarket. There are<br />

others such as Facility Management staff, workshop production managers or factory production<br />

managers.<br />

Responsible for a<br />

pr<strong>of</strong>it centre. Ensures<br />

compliance with<br />

procedures by staff via a<br />

management chart with<br />

performance indicators.<br />

Challenged on margin<br />

and turnover and<br />

therefore on overheads.<br />

Responsible for the<br />

global energy bill for the<br />

company via subsidiaries<br />

throughout the world and<br />

challenges entities with<br />

one another.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Rarely, on event Application order for<br />

planned procedures<br />

according to the type <strong>of</strong><br />

<strong>electrical</strong> event and a<br />

warning to site managers<br />

according to a predefined<br />

list.<br />

Rarely, on event, periodic<br />

consultation <strong>of</strong> reports,<br />

frequent consultation <strong>of</strong><br />

information on request.<br />

The data is shared with<br />

his team:<br />

- measurement screens<br />

with assistance as to<br />

possible interpretation<br />

(limits etc.)<br />

- consumption screens<br />

(KWh and Euro),<br />

- time-stamped events,<br />

- address book for outside<br />

players,<br />

- <strong>electrical</strong> single-line<br />

diagram <strong>of</strong> the site,<br />

drawings <strong>of</strong> <strong>electrical</strong><br />

cabinets and a link to<br />

manufacturing notices,<br />

- financial report, data<br />

used for the investment<br />

dossier,<br />

- indicators to be filled<br />

in on <strong>electrical</strong> network<br />

performance.<br />

Economic report Monthly Financial aspects<br />

including <strong>electrical</strong><br />

consumption, the link<br />

between the turnover<br />

generating business<br />

and electricity, the cost<br />

<strong>of</strong> maintenance <strong>of</strong> the<br />

<strong>electrical</strong> network.<br />

Economic report Monthly Financial features<br />

including <strong>electrical</strong><br />

consumption for each <strong>of</strong><br />

the multinational entities.


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

- Major faults<br />

- Security<br />

- Shop<br />

Digital<br />

inputs<br />

- Major faults<br />

- Minor faults<br />

- Maintenance<br />

- Shop<br />

Communication<br />

Modbus<br />

Shop i<br />

PSTN<br />

Meters<br />

for kWh<br />

and kVAh<br />

- Data collection<br />

- Local communication to users (critical)<br />

- Communication to data Centre<br />

3 One process, several players<br />

- kWh<br />

- kWh1<br />

- kWh2<br />

- kWh3<br />

- Tariff alarm<br />

- Major faults<br />

- Minor faults<br />

- Tech. Mngr.<br />

- Shop<br />

- Finance shop<br />

- Major faults<br />

- Shop Mngr.<br />

- Shop<br />

Fig. K7 : Example: configuration <strong>of</strong> a shopping centre with various players in place<br />

- Finance<br />

shops<br />

- Cost CTRL<br />

- Country<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

WEB<br />

- Finance<br />

shops<br />

- Cy Mngr.<br />

- Country<br />

Data<br />

center<br />

- Tariff structure<br />

- Pr<strong>of</strong>iles Mngt<br />

- Bills computation<br />

- Compounded data<br />

- Report generation & mailing<br />

- Storage<br />

- kWh shops<br />

- Finance shops<br />

- All (Pulled)<br />

- Energy Mngr.<br />

- Country<br />

- Kwh Cy<br />

- Finance<br />

Country<br />

- Finance Cies<br />

- Cost CTRL<br />

- Corporate<br />

Country i, n shops<br />

- Energy<br />

purchaser<br />

- Country<br />

K<br />

© Schneider Electric - all rights reserved


K10<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information<br />

The energy efficiency performance in terms <strong>of</strong> electricity can only be expressed in<br />

terms <strong>of</strong> fundamental physical measurements – voltage, current, harmonics, etc.<br />

These physical measurements are then reprocessed to become digital data and then<br />

information.<br />

In the raw form, data are <strong>of</strong> little use. Unfortunately, some energy managers become<br />

totally immersed in data and see data collection and collation as their primary task.<br />

To gain value from data they must be transformed into information (used to support<br />

the knowledge development <strong>of</strong> all those managing energy) and understanding (used<br />

to action energy savings).<br />

The operational cycle is based on four processes: data collection; data analysis;<br />

communication; and action (Fig. K8). These elements apply to any information<br />

system. The cycle works under condition that an adequate communication network<br />

has been set up.<br />

Data analysis<br />

(data to information)<br />

Fig. K8 : The operational cycle<br />

The data processing level results in information that can be understood by the<br />

recipient pr<strong>of</strong>ile: the ability to interpret the data by the user remains a considerable<br />

challenge in terms <strong>of</strong> decision making.<br />

The data is then directly linked to loads that consume electricity – industrial process,<br />

lighting, air conditioning, etc. – and the service that these loads provide for the<br />

company – quantity <strong>of</strong> products manufactured, comfort <strong>of</strong> visitors to a supermarket,<br />

ambient temperature in a refrigerated room, etc.<br />

The information system is then ready to be used on a day to day basis by users to<br />

achieve energy efficiency objectives set by senior managers in the company.<br />

4.1 Physical value acquisition<br />

The quality <strong>of</strong> data starts with the measurement itself: at the right place, the right<br />

time and just the right amount.<br />

Basically, <strong>electrical</strong> measurement is based on voltage and current going through the<br />

conductors. These values lead to all the others: power, energy, power factor, etc.<br />

Firstly we will ensure consistency <strong>of</strong> the precision class <strong>of</strong> current transformers,<br />

voltage transformers and the precision <strong>of</strong> the measurement devices themselves. The<br />

precision class will be lower for higher voltages: an error in the measurement <strong>of</strong> high<br />

voltage for example represents a very large amount <strong>of</strong> energy.<br />

The total error is the quadratic sum <strong>of</strong> each error.<br />

2 2 2<br />

∑<strong>of</strong><br />

error = error + error + ... + error<br />

Example:<br />

a device with an error <strong>of</strong> 2% connected on a CT ’s with an error <strong>of</strong> 2% that means:<br />

2 2<br />

∑<strong>of</strong><br />

error = ( 2) + ( 2)<br />

= 2,828%<br />

That could mean a loss <strong>of</strong> 2 828 kWh for 100 000 kWh <strong>of</strong> consumption.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Communication<br />

(information to<br />

understanding)<br />

Data collection<br />

Action<br />

(understanding<br />

to results)


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

A CT is defined by:<br />

b its transformation ratio. For example: 50/5A<br />

b precision class Cl. Example: Cl=0.5 generally<br />

b precision power in VA to supply power to<br />

the measurement devices on the secondary.<br />

Example: 1.25 VA<br />

b limit precision factor indicated as a factor<br />

applied to In before saturation.<br />

Example: FLP (or Fs) =10 for measurement<br />

devices with a precision power that is in<br />

conformity.<br />

PM700 measurement unit<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information<br />

Voltage measurement<br />

In low voltage, the voltage measurement is directly made by the measurement<br />

device. When the voltage level becomes incompatible with the device capacity, for<br />

example in medium voltage, we have to put in voltage transformers.<br />

A VT (Voltage transformer) is defined by:<br />

b its primary voltage and secondary voltage<br />

b its apparent power<br />

b its precision class<br />

Current measurement<br />

Current measurement is made by split or closed-core CT’s placed around the phase<br />

and neutral conductors as appropriate.<br />

According to the required precision for measurement, the CT used for the protection<br />

relay also allows current measurement under normal conditions.<br />

In particular, to measure energy, we consider two objectives:<br />

b A contractual billing objective, e.g. between an electricity company and its client<br />

or even between an airport manager (sub-billing) and stores renting airport surface<br />

areas. In this case IEC 62053-21 for Classes 1 and 2 and IEC 62053-22 for Classes<br />

0.5S and 0.2S become applicable to measure active energy.<br />

The full measurement chain – CT, VT and measurement unit – can reach a precision<br />

class Cl <strong>of</strong> 1 in low voltage, Cl 0.5 in medium voltage and 0.2 in high voltage, or even<br />

0.1 in the future.<br />

b An internal cost allocation objective for the company, e.g. to break-down the<br />

cost <strong>of</strong> electricity for each product produced in a specific workshop. In this case <strong>of</strong><br />

a precision class between 1 and 2 for the whole chain (CT, VT and measurement<br />

station) is sufficient.<br />

It is recommended to match the full measurement chain precision with actual<br />

measurement requirements: there is no one single universal solution, but a good<br />

technical and economic compromise according to the requirement to be satisfied.<br />

Note that the measurement precision also has a cost, to be compared with the return<br />

on investment that we are expecting.<br />

<strong>General</strong>ly gains in terms <strong>of</strong> energy efficiency are even greater when the <strong>electrical</strong><br />

network has not been equipped in this way until this point. In addition, permanent<br />

modifications <strong>of</strong> the <strong>electrical</strong> network, according to the company’s activity, mainly<br />

cause us to search for significant and immediate optimizations straight away.<br />

Example:<br />

A class 1 analogue ammeter, rated 100 A, will display a measurement <strong>of</strong> +/-1 A<br />

at 100 A. However if it displays 2 A, the measurement is correct to within 1 A and<br />

therefore there is uncertainty <strong>of</strong> 50%.<br />

A class 1 energy measurement station such as PM710 Merlin Gerin – like all other<br />

Merlin Gerin Power Meter and Circuit Monitor Measurement Units – is accurate to<br />

1% throughout the measurement range as described in IEC standards 62053.<br />

Other physical measurements considerably enhance the data:<br />

b on/<strong>of</strong>f, open/closed operating position <strong>of</strong> devices, etc.<br />

b energy metering impulse<br />

b transformer, motor temperature<br />

b hours operation, quantity <strong>of</strong> switching operations<br />

b motor load<br />

b UPS battery load<br />

b event logged equipment failures<br />

b etc<br />

4.2 Electrical data for real objectives<br />

Electrical data is transformed into information that is usually intended to satisfy<br />

several objectives:<br />

b It can modify the behaviour <strong>of</strong> users to manage energy wisely and finally lowers<br />

overall energy costs.<br />

b It can contribute to field staff efficiency increase<br />

b It can contribute to decrease the cost <strong>of</strong> Energy<br />

b It can contribute to save energy by understanding how it is used and how assets<br />

and process can be optimized to be more energy efficient<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K11<br />

© Schneider Electric - all rights reserved


K12<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Fig. K9 : Facility utility costs parallel the visualisation <strong>of</strong> an<br />

iceberg<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information<br />

b It may help in optimizing and increasing the life duration <strong>of</strong> the assets associated to<br />

the <strong>electrical</strong> network<br />

b And finally it may be a master piece in increasing the productivity <strong>of</strong> the associated<br />

process (industrial process or even <strong>of</strong>fice, building management), by preventing, or<br />

reducing downtime, or insuring higher quality energy to the loads.<br />

Facility utility costs parallel the visualization <strong>of</strong> an iceberg (Fig. K9). While an iceberg<br />

seems large above the surface, the size is completely overwhelming beneath the<br />

surface. Similarly, <strong>electrical</strong> bills are brought to the surface each month when your<br />

power provider sends you a bill. Savings in this area are important and can be<br />

considerable enough to be the only justification needed for a power monitoring<br />

system. However, there are other less obvious yet more significant savings<br />

opportunities to be found below the surface if you have the right tools at your<br />

disposal.<br />

Modify the behaviour <strong>of</strong> energy users<br />

Using cost allocation reports, you can verify utility billing accuracy, distribute bills<br />

internally by department, make effective fact-based energy decisions and drive<br />

accountability in every level <strong>of</strong> your organization. Then providing ownership <strong>of</strong><br />

electricity costs to the appropriate level in an organization, you modify the behaviour<br />

<strong>of</strong> users to manage energy wisely and finally lowers overall energy costs.<br />

Increase field staff efficiency<br />

One <strong>of</strong> the big challenges <strong>of</strong> field staff in charge <strong>of</strong> the <strong>electrical</strong> network is to make<br />

the right decision and operate in the minimum time.<br />

The first need <strong>of</strong> such people is then to better know what happens on the network,<br />

and possibly to be informed everywhere on the concerned site.<br />

This site-wise transparency is a key feature that enables a field staff to:<br />

b Understand the <strong>electrical</strong> energy flows – check that the network is correctly set-up,<br />

balanced, what are the main consumers, at what period <strong>of</strong> the day, or the week…<br />

b Understand the network behaviour – a trip on a feeder is easier to understand<br />

when you have access to information from downstream loads.<br />

b Be spontaneously informed on events, even outside the concerned site by using<br />

today’s mobile communication<br />

b Going straight forward to the right location on the site with the right spare part, and<br />

with the understanding <strong>of</strong> the complete picture<br />

b Initiate a maintenance action taking into account the real usage <strong>of</strong> a device, not too<br />

early and not too late<br />

b Therefore, providing to the electrician a way to monitor the <strong>electrical</strong> network can<br />

appear as a powerful mean to optimize and in certain case drastically reduce the<br />

cost <strong>of</strong> power.<br />

Here are some examples <strong>of</strong> the main usage <strong>of</strong> the simplest monitoring systems:<br />

b Benchmark between zones to detect abnormal consumption.<br />

b Track unexpected consumption.<br />

b Ensure that power consumption is not higher that your competitors.<br />

b Choose the right Power delivery contract with the Power Utility.<br />

b Set-up simple load-shedding just focusing on optimizing manageable loads such<br />

as lights.<br />

b Be in a position to ask for damage compensation due to non-quality delivery<br />

from the Power Utilities – The process has been stopped because <strong>of</strong> a sag on the<br />

network.<br />

Implementing energy efficiency projects<br />

The Power monitoring system will deliver information that support a complete<br />

energy audit <strong>of</strong> a factility. Such audit can be the way to cover not only electricity<br />

but also Water, Air, Gas and Steam. Measures, benchmark and normalized energy<br />

consumption information will tell how efficient the industrial facilities and process<br />

are. Appropriate action plans can then be put in place. Their scope can be as wide<br />

as setting up control lighting, Building automation systems, variable speed drive,<br />

process automation, etc.<br />

Optimizing the assets<br />

One increasing fact is that <strong>electrical</strong> network evolves more and more and then a<br />

recurrent question occurs : Will my network support this new evolution?<br />

This is typically where a Monitoring system can help the network owner in making<br />

the right decision.<br />

By its logging activity, it can archive the real use <strong>of</strong> the assets and then evaluate<br />

quite accurately the spare capacity <strong>of</strong> a network, or a switchboard, a transformer…<br />

A better use <strong>of</strong> an asset may increase its life duration.<br />

Monitoring systems can provide accurate information <strong>of</strong> the exact use <strong>of</strong> an asset<br />

and then the maintenance team can decide the appropriate maintenance operation,<br />

not too late, or not too early.<br />

In some cases also, the monitoring <strong>of</strong> harmonics can be a positive factor for the life<br />

duration <strong>of</strong> some assets (such as motors or transformers).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Micrologic tripping unit for<br />

Masterpact<br />

TeSys U motor controller<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information<br />

Increasing the productivity by reducing the downtime<br />

Downtime is the nightmare <strong>of</strong> any people in charge <strong>of</strong> an <strong>electrical</strong> network. It may<br />

cause dramatic loss for the company, and the pressure for powering up again in the<br />

minimum time – and the associated stress for the operator – is very high.<br />

A monitoring and control system can help reducing the downtime very efficiently.<br />

Without speaking <strong>of</strong> a remote control system which are the most sophisticated<br />

system and which may be necessary for the most demanding application, a simple<br />

monitoring system can already provide relevant information that will highly contribute<br />

in reducing the downtime:<br />

b Making the operator spontaneously informed, even remote, even out <strong>of</strong> the<br />

concerned site (Using the mobile communication such as DECT network or GSM/<br />

SMS)<br />

b Providing a global view <strong>of</strong> the whole network status<br />

b Helping the identification <strong>of</strong> the faulty zone<br />

b Having remotely the detailed information attached to each event caught by the field<br />

devices (reason for trip for example)<br />

Then remote control <strong>of</strong> a device is a must but not necessary mandatory. In many<br />

cases, a visit <strong>of</strong> the faulty zone is necessary where local actions are possible.<br />

Increasing the productivity by improving the Energy Quality<br />

Some loads can be very sensitive to electricity quality, and operators may face<br />

unexpected situations if the Energy quality is not under control.<br />

Monitoring the Energy quality is then an appropriate way to prevent such event and /<br />

or to fix specific issue.<br />

4.3 Measurement starts with the “stand alone<br />

product” solution<br />

The choice <strong>of</strong> measurement products in <strong>electrical</strong> equipment is made according to<br />

your energy efficiency priorities and also current technological advances:<br />

b measurement and protection functions <strong>of</strong> the LV or MV <strong>electrical</strong> network are<br />

integrated in the same device,<br />

Example: Sepam metering and protection relays, Micrologic tripping unit for<br />

Masterpact, TeSys U motor controller, NRC12 capacitor bank controller, Galaxy<br />

UPSs<br />

b the measurement function is in the device, separate from the protection function,<br />

e.g. built on board the LV circuit breaker.<br />

Example: PowerLogic Circuit Monitor high performance metering unit<br />

The progress made in real time industrial electronics and IT are used in a single<br />

device:<br />

b to meet requirements for simplification <strong>of</strong> switchboards<br />

b to reduce acquisition costs and reduce the number <strong>of</strong> devices<br />

b to facilitate product developments by s<strong>of</strong>tware upgrade procedures<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K13<br />

© Schneider Electric - all rights reserved


K14<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Examples Power Meter, Circuit<br />

Monitor<br />

Keep control over power consumption<br />

Measurement units MV protection and<br />

measurement relays<br />

Below we give examples <strong>of</strong> measurements available via Modbus, RS485 or Ethernet<br />

Fig. K10:<br />

LV protection and<br />

measurement relays<br />

SEPAM Masterpact &<br />

Compact Micrologic<br />

trip units<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Capacitor bank<br />

regulators<br />

Insulation monitors<br />

Varlogic Vigilohm System<br />

Power, inst., max., min. b b b b -<br />

Energy, reset capability b b b - -<br />

Power factor, inst. b b b - -<br />

Cos φ inst. - - - b -<br />

Improve power supply availability<br />

Current, inst., max., min., unbalance b b b b -<br />

Current, wave form capture b b b - -<br />

Voltage, inst., max., min., unbalance b b b b -<br />

Voltage, wave form capture b b b - -<br />

Device status b b b b -<br />

Faults history b b b - -<br />

Frequency, inst., max., min. b b b - -<br />

THDu, THDi b b b b -<br />

Manage <strong>electrical</strong> <strong>installation</strong> better<br />

Load temperature, load and device<br />

thermal state<br />

b b - b -<br />

Insulating resistance - - - - b<br />

Motor controllers LV speeddrives LV s<strong>of</strong>tstarters MV s<strong>of</strong>tstarters UPSs<br />

Examples TeSys U ATV.1 ATS.8 Motorpact RVSS Galaxy<br />

Keep control over power consumption<br />

Power, inst., max., min. - b - b b<br />

Energy, reset capability - b b b -<br />

Power factor, inst. - - b b b<br />

Improve power supply availability<br />

Current, inst., max., min., unbalance b b b b b<br />

Current, wave form capture - - - b b<br />

Device status b b b b b<br />

Faults history b b b b -<br />

THDu, THDi - b - - -<br />

Manage <strong>electrical</strong> <strong>installation</strong> better<br />

Load temperature, load and device<br />

thermal state<br />

b b b b b<br />

Motor running hours - b b b -<br />

Battery follow up - - - - b<br />

Fig. K10 : Examples <strong>of</strong> measurements available via Modbus, RS485 or Ethernet<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Fig. K11 : Example <strong>of</strong> <strong>electrical</strong> network protected and<br />

monitored via the Intranet site<br />

Fig. K12 : A Test to stop all lighting B Test to stop air conditioning<br />

Here consumption during non-working hours seems excessive, consequently two decisions were taken:<br />

b reducing night time lighting<br />

b stopping air conditioning during weekends<br />

The new curve obtained shows a significant drop in consumption.<br />

4 From <strong>electrical</strong> measurement to<br />

<strong>electrical</strong> information<br />

Example <strong>of</strong> solutions for a medium-sized site:<br />

Analysesample Ltd. is a company specialized in analyzing industrial samples from<br />

regional factories: metals, plastics, etc., to certify their chemical characteristics.<br />

The company wants to carry out better control <strong>of</strong> its <strong>electrical</strong> consumption for the<br />

existing <strong>electrical</strong> furnaces, its air conditioning system and to ensure quality <strong>of</strong><br />

<strong>electrical</strong> supply for high-precision electronic devices used to analyze the samples.<br />

Electrical network protected and monitored via the Intranet site<br />

The solution implemented involves recovering power data via metering units that<br />

also allows measurement <strong>of</strong> basic <strong>electrical</strong> parameters as well as verification <strong>of</strong><br />

energy power quality. Connected to a web server, an Internet browser allows to use<br />

them very simply and export data in a Micros<strong>of</strong>t Excel type spreadsheet. Power<br />

curves can be plotted in real time by the spreadsheet (Fig. K11).<br />

Therefore no IT investment, either in s<strong>of</strong>tware or hardware, is necessary to use the<br />

data.<br />

For example to reduce the electricity bill and limit consumption during nighttime<br />

and weekends, we have to study trend curves supplied by the measurement units<br />

(Fig. K12).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K15<br />

© Schneider Electric - all rights reserved


K16<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

Most organisations will already have some level <strong>of</strong> energy information system, even<br />

if it is not identified or managed as one. It should be appreciated that in a changing<br />

working world, any information system will need to develop to meet its prime<br />

objective - supporting management decision making: a key point is to make the<br />

energy information visible at any level <strong>of</strong> the organization through the communication<br />

infrastructure.<br />

Energy data is important data, it is one <strong>of</strong> the company’s assets. The company has<br />

IT managers who are already in charge <strong>of</strong> managing its other IT systems. These<br />

are important players in the power monitoring system and above all in that for data<br />

exchange within the corporate organization.<br />

5.1 Communication network at product, equipment<br />

and site level<br />

The day-to-day working <strong>of</strong> the energy information system can be illustrated by a<br />

closed loop diagram (Fig. K13).<br />

Modbus*<br />

Data<br />

* Communication network<br />

Fig. K13 : System hierarchy<br />

Various resources are used to send data from metering and protection devices<br />

installed in the user’s <strong>electrical</strong> cabinets, e.g. via Schneider ElectricTransparent<br />

Ready.<br />

The Modbus communication protocol<br />

Modbus is an industrial messaging protocol between equipment that is<br />

interconnected via a physical transmission link e.g. RS 485 or Ethernet (via TCP/IP)<br />

or modem (GSM, Radio etc). This protocol is very widely implemented on metering<br />

and protection products for <strong>electrical</strong> networks.<br />

Initially created by Schneider Electric, Modbus is now a public resource managed<br />

by an independent organization Modbus-IDA – enabling total opening up <strong>of</strong> its<br />

specification. An industrial standard since 1979, Modbus allows millions <strong>of</strong> products<br />

to communicate with one another.<br />

The IETF, international authority managing the Internet, has approved the creation<br />

<strong>of</strong> a port (502) for products connected to the Internet/Intranet and using the Ethernet<br />

Modbus TCP/IP communication protocol.<br />

Modbus is a query/reply process between two pieces <strong>of</strong> equipment based on data<br />

reading and writing services (function codes).<br />

The query is emitted by a single “master”, the reply is sent only by the “slave”<br />

equipment identified in the query (Fig. K14).<br />

Each “slave” product connected to the Modbus network is set by the user with an ID<br />

number, called the Modbus address, between 1 and 247.<br />

The “master” – for example a web server included in an <strong>electrical</strong> cabinet<br />

– simultaneously queries all <strong>of</strong> the products with a message comprising its target’s<br />

address, function code, memory location in the product and quantity <strong>of</strong> information,<br />

at most 253 octets.<br />

Only a product set with the corresponding address answers the request for data.<br />

Exchange is only carried out on the initiative <strong>of</strong> the master (here the web server): this<br />

is the master-slave Modbus operating procedure.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Intranet*<br />

Information<br />

Communicating<br />

measurement device*<br />

Energy information systems<br />

Understanding


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

This query procedure followed by a reply, implies that the master will have all <strong>of</strong> the<br />

data available in a product when it is queried.<br />

The “master” manages all <strong>of</strong> the transaction queries successively if they are intended<br />

for the same product. This arrangement leads to the calculation <strong>of</strong> a maximum<br />

number <strong>of</strong> products connected to the master to optimize an acceptable response<br />

time for the query initiator, particularly when it is a low rate RS485 link.<br />

Fig. K14 : The function codes allow writing or reading <strong>of</strong> data.<br />

A transmission error s<strong>of</strong>tware detection mechanism called CRC16 allows a message with an<br />

error to be repeated and only the product concerned to respond.<br />

Your Intranet network<br />

Data exchange from industrial data basically uses web technologies implemented<br />

permanently on the corporate communication network, and more particularly on its<br />

Intranet.<br />

The IT infrastructure manages the cohabitation <strong>of</strong> s<strong>of</strong>tware applications: the<br />

company uses it to operate applications for the <strong>of</strong>fice, printing, data backup, for the<br />

corporate IT system, accounting, purchasing, ERP, production facility control, API,<br />

MES, etc. The cohabitation <strong>of</strong> data on the same communication network does not<br />

pose any particular technological problem.<br />

When several PC’s, printers and servers are connected to one another in the<br />

company’s buildings, very probably using the Ethernet local network and web<br />

services: this company is then immediately eligible to have energy efficiency data<br />

delivered by its <strong>electrical</strong> cabinets. Without any s<strong>of</strong>tware development, all they need<br />

is an Micros<strong>of</strong>t Internet Explorer type Internet browser.<br />

The data from these applications cross the local broadband Ethernet network up to<br />

1 Gb/s: the communication media generally used in this world is copper or optic fiber,<br />

which allows connection everywhere, in commercial or industrial buildings and in<br />

<strong>electrical</strong> premises.<br />

If the company also has an internal Intranet communication network for emailing<br />

and sharing web servers data, it uses an extremely common standardized<br />

communication protocol: TCP/IP.<br />

The TCP/IP communication protocol is <strong>design</strong>ed for widely used web services such<br />

as HTTP to access web pages, SMTP for electronic messaging between other<br />

services.<br />

Applications SNMP NTP RTPS DHCP TFTP FTP HTTP SMTP Modbus<br />

Transport UDP TCP<br />

Link IP<br />

Physical Ethernet 802.3 and Ethernet II<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

K17<br />

© Schneider Electric - all rights reserved


K18<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

Electrical data recorded in industrial web servers installed in <strong>electrical</strong> cabinets are<br />

sent using the same standardized TCP/IP protocol in order to limit the recurrent IT<br />

maintenance costs that are intrinsic in an IT network. This is the operating principle<br />

<strong>of</strong> Schneider Electric Transparent Ready TM for communication <strong>of</strong> data on energy<br />

efficiency. The <strong>electrical</strong> cabinet is autonomous without the need for any additional<br />

IT system on a PC, all <strong>of</strong> the data related to energy efficiency is recorded and can be<br />

circulated in the usual way via the intranet, GSM, fixed telephone link, etc.<br />

Security<br />

Employees that are well informed, more efficient and working in complete <strong>electrical</strong><br />

safety: they no longer need to go into <strong>electrical</strong> rooms or make standard checks<br />

on <strong>electrical</strong> devices - they just have to consult data. Under these conditions,<br />

communicative systems give the company’s employees immediate and significant<br />

gains and avoid worrying about making mistakes.<br />

It becomes possible for electricians, maintenance or production technicians, on-site<br />

or visiting managers to work together in complete safety.<br />

According to the sensitivity <strong>of</strong> data, the IT manager will simply give users the<br />

appropriate access rights.<br />

Marginal impact on local network maintenance<br />

The company’s IT manager has technical resources to add and monitor equipment<br />

to the local company network.<br />

Based on standard web services including the Modbus protocol on TCP/IP, and<br />

due to the low level <strong>of</strong> bandwidth requirement characteristic in <strong>electrical</strong> network<br />

monitoring systems as well as the use <strong>of</strong> technologies that are not impacted by<br />

viruses and worldwide IT standards, the IT manager does not have to make any<br />

specific investment to preserve the local network performance level or to protect<br />

against any additional security problems (virus, hacking, etc.).<br />

Empowering external partners<br />

According to the company’s security policy, it becomes possible to use support<br />

services <strong>of</strong> the usual partners in the <strong>electrical</strong> sector: contractors, utilities managers,<br />

panelbuilders, systems integrators or Schneider Electric Services can provide<br />

remote assistance and <strong>electrical</strong> data analysis to the company consuming electricity.<br />

The messaging web service can regularly send data by email or web pages can be<br />

remotely consulted using the appropriate techniques.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

Function<br />

levels<br />

<strong>General</strong><br />

purpose<br />

site<br />

monitoring<br />

Specialised<br />

network<br />

monitoring<br />

Basic<br />

monitoring<br />

1<br />

Eqt server<br />

Intelligent<br />

Power<br />

Equipment<br />

Web<br />

browser<br />

standard<br />

Other<br />

utilities<br />

Fig. K15 : Monitoring system positioning<br />

2<br />

Eqt server<br />

Power<br />

Equipment<br />

5 Communication and Information<br />

System<br />

5.2 From Network Monitoring and Control System to<br />

Intelligent Power Equipment<br />

Traditionally and for years, monitoring and control systems have been centralized<br />

and based on SCADA (Supervisory, Control and Data acquisition) automation<br />

systems.<br />

Deciding on investing in such system – noted (3) in Figure K15 – was really<br />

reserved for high demanding <strong>installation</strong>, because either they were big power<br />

consumers, or their process was very sensitive to Power non quality.<br />

Based on automation technology, such systems were very <strong>of</strong>ten <strong>design</strong>ed,<br />

customised by a system integrator, and then delivered on site. However the initial<br />

cost, the skills needed to correctly operate such system, and the cost <strong>of</strong> upgrades to<br />

follow the evolutions <strong>of</strong> the network may have discouraged potential users to invest.<br />

Then based on a dedicated solution for electrician, the other approach noted (2)<br />

is much more fitting the <strong>electrical</strong> network specific needs and really increases the<br />

payback <strong>of</strong> such system. However, due to its centralised architecture, the level cost<br />

<strong>of</strong> such solution may still appear high.<br />

On some sites Type (2) and (3) can cohabit, providing the most accurate information<br />

to the electrician when needed.<br />

Nowadays, a new concept <strong>of</strong> intelligent Power equipment – noted (1) – has come.<br />

considered as an entering step for going to level 2 or 3, due the ability <strong>of</strong> these<br />

solutions to co-exist on a site.<br />

Specialised<br />

monitoring<br />

such as<br />

Power Logic<br />

SMS<br />

Eqt gateway<br />

Power<br />

Equipment<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

Other<br />

utilities Process<br />

Standard network Sensitive <strong>electrical</strong> networks High demanding sites<br />

<strong>General</strong><br />

purpose<br />

monitoring<br />

system<br />

System<br />

complexity<br />

K19<br />

© Schneider Electric - all rights reserved


K20<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

Intelligent equipment based architecture (see Fig. K16)<br />

This new architecture has appeared recently due to Web technology capabilities, and<br />

can really be positioned as an entry point into monitoring systems.<br />

Based on Web technologies it takes the maximum benefits <strong>of</strong> standard<br />

communication services and protocols, and license-free s<strong>of</strong>tware.<br />

The access to electricity information can be done from everywhere in the site, and<br />

<strong>electrical</strong> staff can gain a lot in efficiency.<br />

Openness to the Internet is also <strong>of</strong>fered for out <strong>of</strong> the site services.<br />

Standard remote<br />

Web browser<br />

Internet<br />

Equipment server<br />

Gateway<br />

Electrician specialized centralised architecture (see Fig. K17)<br />

Dedicated to electrician, this architecture is based on a specific supervision<br />

centralised mean that fully match the needs for monitoring an <strong>electrical</strong> network.<br />

Then it <strong>of</strong>fers naturally a lower level <strong>of</strong> skill to set up and maintain it – all Electrical<br />

Distribution devices are already present in a dedicated library. Finally its purchase<br />

cost is really minimized, due the low level <strong>of</strong> system integrator effort.<br />

Fig. K17 : ED specialist monitoring system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1 2 3<br />

Circuit breakers<br />

Fig. K16 : Intelligent equipment architecture<br />

Gateway<br />

1 2 3<br />

Circuit breakers<br />

Modbus<br />

Standard local<br />

Web browser<br />

Intranet (Ethernet/IP)<br />

Modbus<br />

Meter 1<br />

Dedicated supervisor<br />

for electrician<br />

Modbus (SL or Ethernet/IP)<br />

Intelligence Power Equipment<br />

Meter 2 Meter 3<br />

Communicating Power Equipment<br />

Meter 1 Meter 2 Meter 3


K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

Conventional general purpose centralised architecture (see Fig. K18)<br />

Here is a typical architecture based on standard automation pieces such as SCADA<br />

systems, and gateways.<br />

Despite its real efficiency, such architecture suffered from some drawbacks such as :<br />

b The level <strong>of</strong> skills needed to operate it<br />

b The poor upgradability<br />

b And at the end the risky payback <strong>of</strong> such solutions<br />

They have however no equivalent for high demanding sites, and appears very<br />

relevant for central operation rooms.<br />

Gateway<br />

1 2 3<br />

Circuit breakers<br />

Fig. K18 : Real-time conventional monitoring and control system<br />

5.3 e-Support becomes accessible<br />

The setting up <strong>of</strong> an information system to support a global energy efficiency<br />

approach very quickly leads to economic gains, in general with an ROI <strong>of</strong> less than 2<br />

years for electricity.<br />

An additional benefit, that is still underestimated today, is the leverage that this leads<br />

to in terms <strong>of</strong> information technologies in the <strong>electrical</strong> sector. The <strong>electrical</strong> network<br />

can be analyzed from time to time by third parties – in particular using external<br />

competencies via the internet for very specific issues:<br />

b Electricity supply contracts. Changing <strong>of</strong> supplier at a given point in time, e.g.<br />

permanent economic analysis <strong>of</strong> the costs related to consumption becomes possible<br />

without having to wait for an annual review.<br />

b Total management <strong>of</strong> <strong>electrical</strong> data – via internet – to transform it into relevant<br />

information that is fed back via a personalized web portal. Consumer usage<br />

information is now a value-added commodity, available to a wide range <strong>of</strong> users. It's<br />

easy to post customer usage data on the Internet – making it useful to the users is<br />

another matter.<br />

b Complex <strong>electrical</strong> fault diagnosis to call in an electrotechnical expert, a rare<br />

resource that is easily accessible on the web.<br />

b Monitoring <strong>of</strong> consumption and generating alerts in the case <strong>of</strong> abnormal<br />

consumption peaks.<br />

b A maintenance service that is no more than necessary to meet pressure on<br />

overheads via facility management services.<br />

Energy efficiency is no longer an issue that the company has to face on its own,<br />

many e-partners can back up the approach as necessary – in particular when the<br />

measurement and decision making assistance stage is reached, on condition that<br />

the <strong>electrical</strong> network is metered and communicative via internet.<br />

Implementation can be gradual starting by making a few key pieces <strong>of</strong> equipment<br />

communicative and gradually extending the system so as to be more accurate or to<br />

give wider coverage <strong>of</strong> the <strong>installation</strong>.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Modbus<br />

Conventional<br />

supervisor<br />

Modbus (SL or Ethernet/IP)<br />

Communicating Power Equipment<br />

Meter 1 Meter 2 Meter 3<br />

K21<br />

© Schneider Electric - all rights reserved


K22<br />

© Schneider Electric - all rights reserved<br />

K - Energy Efficiency in <strong>electrical</strong> distribution<br />

5 Communication and Information<br />

System<br />

The company can choose its policy: ask one or more partners to analyze the data,<br />

do it itself or combine these options.<br />

The company may decide to manage its <strong>electrical</strong> energy itself, or ask a partner to<br />

monitor the quality to ensure active monitoring <strong>of</strong> performances in terms <strong>of</strong> aging.<br />

Example:<br />

Schneider Electric proposes e-Services that <strong>of</strong>fers load data visualization and analysis<br />

application in ASP mode. It simplifies processes for tenants with geographically diverse locations<br />

by providing convenient integrated billing and usage information for all locations combined.<br />

The system turns customer usage data into useful information, easily accessible to all internal<br />

users. It helps control costs by showing customers how their organizations use power.<br />

A wide range <strong>of</strong> functionality serves the needs <strong>of</strong> staff from the same platform:<br />

Data Access and Analysis , Historical and Estimated Bills, Rate Comparison, What-if Analysis<br />

- Assess the impact <strong>of</strong> operational changes, such as shifting energy between time periods or<br />

reducing usage by fixed amounts or percentages, Automatic Alarming, Memorized Reports,<br />

Benchmarking - Benchmark usage data from multiple facilities by applying normalization factors<br />

such as square footage, operating hours, and units <strong>of</strong> production. Multiple Commodities - Access<br />

usage data for gas and water as well as electricity etc.<br />

New York Chicago Los Angeles Seattle<br />

Ethernet/VPN Ethernet/VPN<br />

Reports<br />

Fig. K19 : Typical solution exemple<br />

Electricity<br />

Water & Gas<br />

Power Quality<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

WEB<br />

Energy Cost<br />

Analysis<br />

Normalize data using:<br />

- Temperature<br />

- Occupancy rates<br />

- Rooms<br />

- Other parameters<br />

WEB<br />

XML<br />

Corporate<br />

Database<br />

ODBC<br />

Weather info<br />

Utility tariffs & rates<br />

Real-time pricing<br />

Stores data including:<br />

- Occupancy rates<br />

- Square footage<br />

- Other parameters


2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

0<br />

<strong>Chapter</strong> L<br />

Power factor correction and<br />

harmonic filtering<br />

Contents<br />

Reactive energy and power factor L2<br />

1.1 The nature <strong>of</strong> reactive energy L2<br />

1.2 Equipment and appliances requiring reactive energy L2<br />

1.3 The power factor L3<br />

1.4 Practical values <strong>of</strong> power factor L4<br />

Why to improve the power factor? L5<br />

2.1 Reduction in the cost <strong>of</strong> electricity L5<br />

2.2 Technical/economic optimization L5<br />

How to improve the power factor? L7<br />

3.1 Theoretical principles L7<br />

3.2 By using what equipment? L7<br />

3.3 The choice between a fixed or automatically-regulated bank L9<br />

<strong>of</strong> capacitors<br />

Where to install power factor correction capacitors? L 0<br />

4.1 Global compensation L10<br />

4.2 Compensation by sector L10<br />

4.3 Individual compensation L11<br />

How to decide the optimum level <strong>of</strong> compensation? L 2<br />

5.1 <strong>General</strong> method L12<br />

5.2 Simplified method L12<br />

5.3 Method based on the avoidance <strong>of</strong> tariff penalties L14<br />

5.4 Method based on reduction <strong>of</strong> declared maximum apparent<br />

power (kVA) L14<br />

Compensation at the terminals <strong>of</strong> a transformer L 5<br />

6.1 Compensation to increase the available active power output L15<br />

6.2 Compensation <strong>of</strong> reactive energy absorbed by the transformer L16<br />

Power factor correction <strong>of</strong> induction motors L 8<br />

7.1 Connection <strong>of</strong> a capacitor bank and protection settings L18<br />

7.2 How self-excitation <strong>of</strong> an induction motor can be avoided L19<br />

Example <strong>of</strong> an <strong>installation</strong> before and L20<br />

after power-factor correction<br />

The effects <strong>of</strong> harmonics L2<br />

9.1 Problems arising from power-system harmonics L21<br />

9.2 Possible solutions L21<br />

9.3 Choosing the optimum solution L23<br />

Implementation <strong>of</strong> capacitor banks L24<br />

10.1 Capacitor elements L24<br />

10.2 Choice <strong>of</strong> protection, control devices and connecting cables L25<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

L2<br />

L - Power factor correction and<br />

harmonic filtering<br />

Alternating current systems supply two forms <strong>of</strong><br />

energy:<br />

b “Active” energy measured in kilowatt hours<br />

(kWh) which is converted into mechanical work,<br />

heat, light, etc<br />

b “Reactive” energy, which again takes two<br />

forms:<br />

v “Reactive” energy required by inductive<br />

circuits (transformers, motors, etc.),<br />

v “Reactive” energy supplied by capacitive<br />

circuits (cable capacitance, power capacitors,<br />

etc)<br />

Fig. L2 : Power consuming items that also require reactive<br />

energy<br />

Reactive energy and power<br />

factor<br />

. The nature <strong>of</strong> reactive energy<br />

All inductive (i.e. electromagnetic) machines and devices that operate on AC systems<br />

convert <strong>electrical</strong> energy from the power system generators into mechanical work<br />

and heat. This energy is measured by kWh meters, and is referred to as “active”<br />

or “wattful” energy. In order to perform this conversion, magnetic fields have to be<br />

established in the machines, and these fields are associated with another form <strong>of</strong><br />

energy to be supplied from the power system, known as “reactive” or “wattless”<br />

energy.<br />

The reason for this is that inductive circuit cyclically absorbs energy from the system<br />

(during the build-up <strong>of</strong> the magnetic fields) and re-injects that energy into the system<br />

(during the collapse <strong>of</strong> the magnetic fields) twice in every power-frequency cycle.<br />

An exactly similar phenomenon occurs with shunt capacitive elements in a power<br />

system, such as cable capacitance or banks <strong>of</strong> power capacitors, etc. In this case,<br />

energy is stored electrostatically. The cyclic charging and discharging <strong>of</strong> capacitive<br />

circuit reacts on the generators <strong>of</strong> the system in the same manner as that described<br />

above for inductive circuit, but the current flow to and from capacitive circuit in exact<br />

phase opposition to that <strong>of</strong> the inductive circuit. This feature is the basis on which<br />

power factor correction schemes depend.<br />

It should be noted that while this “wattless” current (more accurately, the “wattless”<br />

component <strong>of</strong> a load current) does not draw power from the system, it does cause<br />

power losses in transmission and distribution systems by heating the conductors.<br />

In practical power systems, “wattless” components <strong>of</strong> load currents are invariably<br />

inductive, while the impedances <strong>of</strong> transmission and distribution systems are<br />

predominantly inductively reactive. The combination <strong>of</strong> inductive current passing<br />

through an inductive reactance produces the worst possible conditions <strong>of</strong> voltage<br />

drop (i.e. in direct phase opposition to the system voltage).<br />

For these reasons (transmission power losses and voltage drop), the power-supply<br />

authorities reduce the amount <strong>of</strong> “wattless” (inductive) current as much as possible.<br />

“Wattless” (capacitive) currents have the reverse effect on voltage levels and produce<br />

voltage-rises in power systems.<br />

The power (kW) associated with “active” energy is usually represented by the letter P.<br />

The reactive power (kvar) is represented by Q. Inductively-reactive power is<br />

conventionally positive (+ Q) while capacitively-reactive power is shown as a<br />

negative quantity (- Q).<br />

The apparent power S (kVA) is a combination <strong>of</strong> P and Q (see Fig. L ).<br />

Sub-clause 1.3 shows the relationship between P, Q, and S.<br />

Q<br />

(kvar)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

S<br />

(kVA)<br />

P<br />

(kW)<br />

Fig. L1 : An electric motor requires active power P and reactive power Q from the power system<br />

.2 Equipement and appliances requiring reactive<br />

energy<br />

All AC equipement and appliances that include electromagnetic devices, or depend<br />

on magnetically-coupled windings, require some degree <strong>of</strong> reactive current to create<br />

magnetic flux.<br />

The most common items in this class are transformers and reactors, motors and<br />

discharge lamps (with magnetic ballasts) (see Fig. L2).<br />

The proportion <strong>of</strong> reactive power (kvar) with respect to active power (kW) when an<br />

item <strong>of</strong> equipement is fully loaded varies according to the item concerned being:<br />

b 65-75% for asynchronous motors<br />

b 5-10% for transformers


L - Power factor correction and<br />

harmonic filtering<br />

The power factor is the ratio <strong>of</strong> kW to kVA.<br />

The closer the power factor approaches its<br />

maximum possible value <strong>of</strong> 1, the greater the<br />

benefit to consumer and supplier.<br />

PF = P (kW) / S (kVA)<br />

P = Active power<br />

S = Apparent power<br />

Reactive energy and power<br />

factor<br />

.3 The power factor<br />

Definition <strong>of</strong> power factor<br />

The power factor <strong>of</strong> a load, which may be a single power-consuming item, or a<br />

number <strong>of</strong> items (for example an entire <strong>installation</strong>), is given by the ratio <strong>of</strong> P/S i.e.<br />

kW divided by kVA at any given moment.<br />

The value <strong>of</strong> a power factor will range from 0 to 1.<br />

If currents and voltages are perfectly sinusoidal signals, power factor equals cos ϕ.<br />

A power factor close to unity means that the reactive energy is small compared with<br />

the active energy, while a low value <strong>of</strong> power factor indicates the opposite condition.<br />

Power vector diagram<br />

b Active power P (in kW)<br />

v Single phase (1 phase and neutral): P = V I cos ϕ<br />

v Single phase (phase to phase): P = U I cos ϕ<br />

v Three phase (3 wires or 3 wires + neutral): P = 3U I cos ϕ<br />

b Reactive power Q (in kvar)<br />

v Single phase (1 phase and neutral): P = V I sin ϕ<br />

v Single phase (phase to phase): Q = U I sin ϕ<br />

v Three phase (3 wires or 3 wires + neutral): P = 3 U I sin ϕ<br />

b Apparent power S (in kVA)<br />

v Single phase (1 phase and neutral): S = V I<br />

v Single phase (phase to phase): S = U I<br />

v Three phase (3 wires or 3 wires + neutral): P = 3 U I<br />

where:<br />

V = Voltage between phase and neutral<br />

U = Voltage between phases<br />

I = Line current<br />

ϕ = Phase angle between vectors V and I.<br />

v For balanced and near-balanced loads on 4-wire systems<br />

Current and voltage vectors, and derivation <strong>of</strong> the power diagram<br />

The power “vector” diagram is a useful artifice, derived directly from the true rotating<br />

vector diagram <strong>of</strong> currents and voltage, as follows:<br />

The power-system voltages are taken as the reference quantities, and one phase<br />

only is considered on the assumption <strong>of</strong> balanced 3-phase loading.<br />

The reference phase voltage (V) is co-incident with the horizontal axis, and the<br />

current (I) <strong>of</strong> that phase will, for practically all power-system loads, lag the voltage by<br />

an angle ϕ.<br />

The component <strong>of</strong> I which is in phase with V is the “wattful” component <strong>of</strong> I and is<br />

equal to I cos ϕ, while VI cos ϕ equals the active power (in kW) in the circuit, if V is<br />

expressed in kV.<br />

The component <strong>of</strong> I which lags 90 degrees behind V is the wattless component <strong>of</strong><br />

I and is equal to I sin ϕ, while VI sin ϕ equals the reactive power (in kvar) in the<br />

circuit, if V is expressed in kV.<br />

If the vector I is multiplied by V, expressed in kV, then VI equals the apparent power<br />

(in kVA) for the circuit.<br />

The simple formula is obtained: S 2 = P 2 + Q 2<br />

The above kW, kvar and kVA values per phase, when multiplied by 3, can therefore<br />

conveniently represent the relationships <strong>of</strong> kVA, kW, kvar and power factor for a total<br />

3-phase load, as shown in Figure L3 .<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

ϕ<br />

Fig. L3 : Power diagram<br />

Q = VI sin ϕ (kvar)<br />

P = VI cos ϕ (kW)<br />

S = VI (kVA)<br />

V<br />

P = Active power<br />

Q = Reactive power<br />

S = Apparent power<br />

L3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

L4<br />

L - Power factor correction and<br />

harmonic filtering<br />

ϕ<br />

P = 56 kW<br />

S = 65 kVA<br />

Fig. L5 : Calculation power diagram<br />

Q = 33 kvar<br />

Reactive energy and power<br />

factor<br />

An example <strong>of</strong> power calculations (see Fig. L4 )<br />

Type <strong>of</strong> Apparent power Active power Reactive power<br />

circuit S (kVA) P (kW) Q (kvar)<br />

Single-phase (phase and neutral) S = VI P = VI cos ϕ Q = VI sin ϕ<br />

Single-phase (phase to phase) S = UI P = UI cos ϕ Q = UI sin ϕ<br />

Example 5 kW <strong>of</strong> load 10 kVA 5 kW 8.7 kvar<br />

cos ϕ = 0.5<br />

Three phase 3-wires or 3-wires + neutral S = 3 UI P = 3 UI cos ϕ Q = 3 UI sin ϕ<br />

Example Motor Pn = 51 kW 65 kVA 56 kW 33 kvar<br />

cos ϕ = 0.86<br />

ρ = 0.91 (motor efficiency)<br />

Fig. L4 : Example in the calculation <strong>of</strong> active and reactive power<br />

.4 Practical values <strong>of</strong> power factor<br />

The calculations for the three-phase example above are as follows:<br />

Pn = delivered shaft power = 51 kW<br />

P = active power consumed<br />

P = Pn<br />

ρ<br />

51<br />

= =<br />

0. 91<br />

56 kW<br />

S = apparent power<br />

S = P 56<br />

= = 6 5 kVA<br />

cos ϕ 0. 86<br />

So that, on referring to diagram Figure L5 or using a pocket calculator, the value <strong>of</strong><br />

tan ϕ corresponding to a cos ϕ <strong>of</strong> 0.86 is found to be 0.59<br />

Q = P tan ϕ = 56 x 0.59 = 33 kvar (see Figure L15).<br />

Alternatively<br />

2 2 2 2<br />

Q = S -P = 65 - 56 = 33 kvar<br />

Average power factor values for the most commonly-used equipment and<br />

appliances (see Fig. L6)<br />

Equipment and appliances cos ϕ tan ϕ<br />

b Common loaded at 0% 0.17 5.80<br />

induction motor 25% 0.55 1.52<br />

50% 0.73 0.94<br />

75% 0.80 0.75<br />

100% 0.85 0.62<br />

b Incandescent lamps 1.0 0<br />

b Fluorescent lamps (uncompensated) 0.5 1.73<br />

b Fluorescent lamps (compensated) 0.93 0.39<br />

b Discharge lamps 0.4 to 0.6 2.29 to 1.33<br />

b Ovens using resistance elements 1.0 0<br />

b Induction heating ovens (compensated) 0.85 0.62<br />

b Dielectric type heating ovens 0.85 0.62<br />

b Resistance-type soldering machines 0.8 to 0.9 0.75 to 0.48<br />

b Fixed 1-phase arc-welding set 0.5 1.73<br />

b Arc-welding motor-generating set 0.7 to 0.9 1.02 to 0.48<br />

b Arc-welding transformer-rectifier set 0.7 to 0.8 1.02 to 0.75<br />

b Arc furnace 0.8 0.75<br />

Fig. L6 : Values <strong>of</strong> cos ϕ and tan ϕ for commonly-used equipment<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

An improvement <strong>of</strong> the power factor <strong>of</strong> an<br />

<strong>installation</strong> presents several technical and<br />

economic advantages, notably in the reduction<br />

<strong>of</strong> electricity bills<br />

Power factor improvement allows the use <strong>of</strong><br />

smaller transformers, switchgear and cables,<br />

etc. as well as reducing power losses and<br />

voltage drop in an <strong>installation</strong><br />

2 Why to improve the power<br />

factor?<br />

2.1 Reduction in the cost <strong>of</strong> electricity<br />

Good management in the consumption <strong>of</strong> reactive energy brings economic<br />

advantages.<br />

These notes are based on an actual tariff structure commonly applied in Europe,<br />

<strong>design</strong>ed to encourage consumers to minimize their consumption <strong>of</strong> reactive energy.<br />

The <strong>installation</strong> <strong>of</strong> power-factor correction capacitors on <strong>installation</strong>s permits the<br />

consumer to reduce his electricity bill by maintaining the level <strong>of</strong> reactive-power<br />

consumption below a value contractually agreed with the power supply authority.<br />

In this particular tariff, reactive energy is billed according to the tan ϕ criterion.<br />

As previously noted:<br />

tan ϕ =<br />

Q (kvarh)<br />

P (kWh)<br />

The power supply authority delivers reactive energy for free:<br />

b If the reactive energy represents less than 40% <strong>of</strong> the active energy (tan ϕ < 0.4)<br />

for a maximum period <strong>of</strong> 16 hours each day (from 06-00 h to 22-00 h) during the<br />

most-heavily loaded period (<strong>of</strong>ten in winter)<br />

b Without limitation during light-load periods in winter, and in spring and summer.<br />

During the periods <strong>of</strong> limitation, reactive energy consumption exceeding 40% <strong>of</strong><br />

the active energy (i.e. tan ϕ > 0.4) is billed monthly at the current rates. Thus, the<br />

quantity <strong>of</strong> reactive energy billed in these periods will be:<br />

kvarh (to be billed) = kWh (tan ϕ > 0.4) where:<br />

v kWh is the active energy consumed during the periods <strong>of</strong> limitation<br />

v kWh tan ϕ is the total reactive energy during a period <strong>of</strong> limitation<br />

v 0.4 kWh is the amount <strong>of</strong> reactive energy delivered free during a period <strong>of</strong><br />

limitation<br />

tan ϕ = 0.4 corresponds to a power factor <strong>of</strong> 0.93 so that, if steps are taken to ensure<br />

that during the limitation periods the power factor never falls below 0.93,<br />

the consumer will have nothing to pay for the reactive power consumed.<br />

Against the financial advantages <strong>of</strong> reduced billing, the consumer must balance<br />

the cost <strong>of</strong> purchasing, installing and maintaining the power factor improvement<br />

capacitors and controlling switchgear, automatic control equipment (where stepped<br />

levels <strong>of</strong> compensation are required) together with the additional kWh consumed by<br />

the dielectric losses <strong>of</strong> the capacitors, etc. It may be found that it is more economic<br />

to provide partial compensation only, and that paying for some <strong>of</strong> the reactive energy<br />

consumed is less expensive than providing 100% compensation.<br />

The question <strong>of</strong> power-factor correction is a matter <strong>of</strong> optimization, except in very<br />

simple cases.<br />

2.2 Technical/economic optimization<br />

A high power factor allows the optimization <strong>of</strong> the components <strong>of</strong> an <strong>installation</strong>.<br />

Overating <strong>of</strong> certain equipment can be avoided, but to achieve the best results, the<br />

correction should be effected as close to the individual inductive items as possible.<br />

Reduction <strong>of</strong> cable size<br />

Figure L7 shows the required increase in the size <strong>of</strong> cables as the power factor is<br />

reduced from unity to 0.4, for the same active power transmitted.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Multiplying factor 1 1.25 1.67 2.5<br />

for the cross-sectional<br />

area <strong>of</strong> the cable core(s)<br />

cos ϕ 1 0.8 0.6 0.4<br />

Fig. L7 : Multiplying factor for cable size as a function <strong>of</strong> cos ϕ<br />

L<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

L<br />

L - Power factor correction and<br />

harmonic filtering<br />

(1) Since other benefits are obtained from a high value <strong>of</strong><br />

power factor, as previously noted.<br />

2 Why to improve the power<br />

factor?<br />

Reduction <strong>of</strong> losses (P, kW) in cables<br />

Losses in cables are proportional to the current squared, and are measured by the<br />

kWh meter <strong>of</strong> the <strong>installation</strong>. Reduction <strong>of</strong> the total current in a conductor by 10% for<br />

example, will reduce the losses by almost 20%.<br />

Reduction <strong>of</strong> voltage drop<br />

Power factor correction capacitors reduce or even cancel completely the (inductive)<br />

reactive current in upstream conductors, thereby reducing or eliminating voltage<br />

drops.<br />

Note: Over compensation will produce a voltage rise at the capacitor level.<br />

Increase in available power<br />

By improving the power factor <strong>of</strong> a load supplied from a transformer, the current<br />

through the transformer will be reduced, thereby allowing more load to be added. In<br />

practice, it may be less expensive to improve the power factor (1) , than to replace the<br />

transformer by a larger unit.<br />

This matter is further elaborated in clause 6.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

Improving the power factor <strong>of</strong> an <strong>installation</strong><br />

requires a bank <strong>of</strong> capacitors which acts as a<br />

source <strong>of</strong> reactive energy. This arrangement is<br />

said to provide reactive energy compensation<br />

a) Reactive current components only flow pattern<br />

IL - IC IC IL IL<br />

C L<br />

Load<br />

b) When IC = IL, all reactive power is supplied from the<br />

capacitor bank<br />

IL - IC = 0 IC IL IL<br />

C L<br />

c) With load current added to case (b)<br />

Load<br />

IR IC IR + IL IL IR<br />

C L<br />

Load<br />

Fig. L8 : Showing the essential features <strong>of</strong> power-factor<br />

correction<br />

ϕ'<br />

ϕ<br />

Qc<br />

Fig. L9 : Diagram showing the principle <strong>of</strong> compensation:<br />

Qc = P (tan ϕ - tan ϕ’)<br />

S'<br />

S<br />

Q'<br />

P<br />

R<br />

R<br />

R<br />

Q<br />

3 How to improve the power factor?<br />

3.1 Theoretical principles<br />

An inductive load having a low power factor requires the generators and<br />

transmission/distribution systems to pass reactive current (lagging the system<br />

voltage by 90 degrees) with associated power losses and exaggerated voltage<br />

drops, as noted in sub-clause 1.1. If a bank <strong>of</strong> shunt capacitors is added to the<br />

load, its (capacitive) reactive current will take the same path through the power<br />

system as that <strong>of</strong> the load reactive current. Since, as pointed out in sub-clause<br />

1.1, this capacitive current Ic (which leads the system voltage by 90 degrees) is<br />

in direct phase opposition to the load reactive current (IL), the two components<br />

flowing through the same path will cancel each other, such that if the capacitor bank<br />

is sufficiently large and Ic = IL there will be no reactive current flow in the system<br />

upstream <strong>of</strong> the capacitors.<br />

This is indicated in Figure L8 (a) and (b) which show the flow <strong>of</strong> the reactive<br />

components <strong>of</strong> current only.<br />

In this figure:<br />

R represents the active-power elements <strong>of</strong> the load<br />

L represents the (inductive) reactive-power elements <strong>of</strong> the load<br />

C represents the (capacitive) reactive-power elements <strong>of</strong> the power-factor correction<br />

equipment (i.e. capacitors).<br />

It will be seen from diagram (b) <strong>of</strong> Figure L9, that the capacitor bank C appears<br />

to be supplying all the reactive current <strong>of</strong> the load. For this reason, capacitors are<br />

sometimes referred to as “generators <strong>of</strong> lagging vars”.<br />

In diagram (c) <strong>of</strong> Figure L9, the active-power current component has been added,<br />

and shows that the (fully-compensated) load appears to the power system as having<br />

a power factor <strong>of</strong> 1.<br />

In general, it is not economical to fully compensate an <strong>installation</strong>.<br />

Figure L9 uses the power diagram discussed in sub-clause 1.3 (see Fig. L3) to<br />

illustrate the principle <strong>of</strong> compensation by reducing a large reactive power Q to a<br />

smaller value Q’ by means <strong>of</strong> a bank <strong>of</strong> capacitors having a reactive power Qc.<br />

In doing so, the magnitude <strong>of</strong> the apparent power S is seen to reduce to S’.<br />

Example:<br />

A motor consumes 100 kW at a power factor <strong>of</strong> 0.75 (i.e. tan ϕ = 0.88). To improve<br />

the power factor to 0.93 (i.e. tan ϕ = 0.4), the reactive power <strong>of</strong> the capacitor bank<br />

must be : Qc = 100 (0.88 - 0.4) = 48 kvar<br />

The selected level <strong>of</strong> compensation and the calculation <strong>of</strong> rating for the capacitor<br />

bank depend on the particular <strong>installation</strong>. The factors requiring attention are<br />

explained in a general way in clause 5, and in clauses 6 and 7 for transformers and<br />

motors.<br />

Note: Before starting a compensation project, a number <strong>of</strong> precautions should be<br />

observed. In particular, oversizing <strong>of</strong> motors should be avoided, as well as the noload<br />

running <strong>of</strong> motors. In this latter condition, the reactive energy consumed by a<br />

motor results in a very low power factor (≈ 0.17); this is because the kW taken by the<br />

motor (when it is unloaded) are very small.<br />

3.2 By using what equipment?<br />

Compensation at LV<br />

At low voltage, compensation is provided by:<br />

b Fixed-value capacitor<br />

b Equipment providing automatic regulation, or banks which allow continuous<br />

adjustment according to requirements, as loading <strong>of</strong> the <strong>installation</strong> changes<br />

Note: When the installed reactive power <strong>of</strong> compensation exceeds 800 kvar, and the<br />

load is continuous and stable, it is <strong>of</strong>ten found to be economically advantageous to<br />

instal capacitor banks at the medium voltage level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

L8<br />

L - Power factor correction and<br />

harmonic filtering<br />

Compensation can be carried out by a<br />

fixed value <strong>of</strong> capacitance in favourable<br />

circumstances<br />

Compensation is more-commonly effected by<br />

means <strong>of</strong> an automatically-controlled stepped<br />

bank <strong>of</strong> capacitors<br />

3 How to improve the power factor?<br />

Fixed capacitors (see Fig. L10)<br />

This arrangement employs one or more capacitor(s) to form a constant level <strong>of</strong><br />

compensation. Control may be:<br />

b Manual: by circuit-breaker or load-break switch<br />

b Semi-automatic: by contactor<br />

b Direct connection to an appliance and switched with it<br />

These capacitors are applied:<br />

b At the terminals <strong>of</strong> inductive devices (motors and transformers)<br />

b At busbars supplying numerous small motors and inductive appliance for which<br />

individual compensation would be too costly<br />

b In cases where the level <strong>of</strong> load is reasonably constant<br />

Fig. L10 : Example <strong>of</strong> fixed-value compensation capacitors<br />

Automatic capacitor banks (see Fig. L11)<br />

This kind <strong>of</strong> equipment provides automatic control <strong>of</strong> compensation, maintaining the<br />

power factor within close limits around a selected level. Such equipment is applied at<br />

points in an <strong>installation</strong> where the active-power and/or reactive-power variations are<br />

relatively large, for example:<br />

b At the busbars <strong>of</strong> a general power distribution board<br />

b At the terminals <strong>of</strong> a heavily-loaded feeder cable<br />

Fig. L11 : Example <strong>of</strong> automatic-compensation-regulating equipment<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

Automatically-regulated banks <strong>of</strong> capacitors<br />

allow an immediate adaptation <strong>of</strong> compensation<br />

to match the level <strong>of</strong> load<br />

3 How to improve the power factor?<br />

The principles <strong>of</strong>, and reasons, for using automatic<br />

compensation<br />

A bank <strong>of</strong> capacitors is divided into a number <strong>of</strong> sections, each <strong>of</strong> which is controlled<br />

by a contactor. Closure <strong>of</strong> a contactor switches its section into parallel operation with<br />

other sections already in service. The size <strong>of</strong> the bank can therefore be increased or<br />

decreased in steps, by the closure and opening <strong>of</strong> the controlling contactors.<br />

A control relay monitors the power factor <strong>of</strong> the controlled circuit(s) and is arranged<br />

to close and open appropriate contactors to maintain a reasonably constant<br />

system power factor (within the tolerance imposed by the size <strong>of</strong> each step <strong>of</strong><br />

compensation). The current transformer for the monitoring relay must evidently<br />

be placed on one phase <strong>of</strong> the incoming cable which supplies the circuit(s) being<br />

controlled, as shown in Figure L12.<br />

A Varset Fast capacitor bank is an automatic power factor correction equipment<br />

including static contactors (thyristors) instead <strong>of</strong> usual contactors. Static correction<br />

is particularly suitable for a certain number <strong>of</strong> <strong>installation</strong>s using equipment with fast<br />

cycle and/or sensitive to transient surges.<br />

The advantages <strong>of</strong> static contactors are :<br />

b Immediate response to all power factor fluctuation (response time 2 s or 40 ms<br />

according to regulator option)<br />

b Unlimited number <strong>of</strong> operations<br />

b Elimination <strong>of</strong> transient phenomena on the network on capacitor switching<br />

b Fully silent operation<br />

By closely matching compensation to that required by the load, the possibility <strong>of</strong><br />

producing overvoltages at times <strong>of</strong> low load will be avoided, thereby preventing<br />

an overvoltage condition, and possible damage to appliances and equipment.<br />

Overvoltages due to excessive reactive compensation depend partly on the value <strong>of</strong><br />

source impedance.<br />

CT In / 5 A cl 1<br />

Fig. L12 : The principle <strong>of</strong> automatic-compensation control<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Varmetric<br />

relay<br />

3.3 The choice between a fixed or automaticallyregulated<br />

bank <strong>of</strong> capacitors<br />

Commonly-applied <strong>rules</strong><br />

Where the kvar rating <strong>of</strong> the capacitors is less than, or equal to 15% <strong>of</strong> the supply<br />

transformer rating, a fixed value <strong>of</strong> compensation is appropriate. Above the 15%<br />

level, it is advisable to install an automatically-controlled bank <strong>of</strong> capacitors.<br />

The location <strong>of</strong> low-voltage capacitors in an <strong>installation</strong> constitutes the mode <strong>of</strong><br />

compensation, which may be global (one location for the entire <strong>installation</strong>), partial<br />

(section-by-section), local (at each individual device), or some combination <strong>of</strong> the<br />

latter two. In principle, the ideal compensation is applied at a point <strong>of</strong> consumption<br />

and at the level required at any instant.<br />

In practice, technical and economic factors govern the choice.<br />

L9<br />

© Schneider Electric - all rights reserved


L10<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

Where a load is continuous and stable, global<br />

compensation can be applied<br />

Compensation by sector is recommended<br />

when the <strong>installation</strong> is extensive, and where the<br />

load/time patterns differ from one part <strong>of</strong><br />

the <strong>installation</strong> to another<br />

no. 1<br />

no. 2 no. 2<br />

M M M M<br />

Fig. L14 : Compensation by sector<br />

4 Where to install correction<br />

capacitors?<br />

4.1 Global compensation (see Fig. L13)<br />

Principle<br />

The capacitor bank is connected to the busbars <strong>of</strong> the main LV distribution board for<br />

the <strong>installation</strong>, and remains in service during the period <strong>of</strong> normal load.<br />

Advantages<br />

The global type <strong>of</strong> compensation:<br />

b Reduces the tariff penalties for excessive consumption <strong>of</strong> kvars<br />

b Reduces the apparent power kVA demand, on which standing charges are usually<br />

based<br />

b Relieves the supply transformer, which is then able to accept more load if<br />

necessary<br />

Comments<br />

b Reactive current still flows in all conductors <strong>of</strong> cables leaving (i.e. downstream <strong>of</strong>)<br />

the main LV distribution board<br />

b For the above reason, the sizing <strong>of</strong> these cables, and power losses in them, are<br />

not improved by the global mode <strong>of</strong> compensation.<br />

Fig. L13 : Global compensation<br />

4.2 Compensation by sector (see Fig. L14)<br />

Principle<br />

Capacitor banks are connected to busbars <strong>of</strong> each local distribution board, as shown<br />

in Figure L14.<br />

A significant part <strong>of</strong> the <strong>installation</strong> benefits from this arrangement, notably the feeder<br />

cables from the main distribution board to each <strong>of</strong> the local distribution boards at<br />

which the compensation measures are applied.<br />

Advantages<br />

The compensation by sector:<br />

b Reduces the tariff penalties for excessive consumption <strong>of</strong> kvars<br />

b Reduces the apparent power kVA demand, on which standing charges are usually<br />

based<br />

b Relieves the supply transformer, which is then able to accept more load if<br />

necessary<br />

b The size <strong>of</strong> the cables supplying the local distribution boards may be reduced, or<br />

will have additional capacity for possible load increases<br />

b Losses in the same cables will be reduced<br />

Comments<br />

b Reactive current still flows in all cables downstream <strong>of</strong> the local distribution boards<br />

b For the above reason, the sizing <strong>of</strong> these cables, and the power losses in them,<br />

are not improved by compensation by sector<br />

b Where large changes in loads occur, there is always a risk <strong>of</strong> overcompensation<br />

and consequent overvoltage problems<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M M M M<br />

no.1


L - Power factor correction and<br />

harmonic filtering<br />

Individual compensation should be considered<br />

when the power <strong>of</strong> motor is significant with<br />

respect to power <strong>of</strong> the <strong>installation</strong><br />

4 Where to install correction<br />

capacitors?<br />

4.3 Individual compensation<br />

Principle<br />

Capacitors are connected directly to the terminals <strong>of</strong> inductive circuit (notably motors,<br />

see further in Clause 7). Individual compensation should be considered when the<br />

power <strong>of</strong> the motor is significant with respect to the declared power requirement<br />

(kVA) <strong>of</strong> the <strong>installation</strong>.<br />

The kvar rating <strong>of</strong> the capacitor bank is in the order <strong>of</strong> 25% <strong>of</strong> the kW rating <strong>of</strong> the<br />

motor. Complementary compensation at the origin <strong>of</strong> the <strong>installation</strong> (transformer)<br />

may also be beneficial.<br />

Advantages<br />

Individual compensation:<br />

b Reduces the tariff penalties for excessive consumption <strong>of</strong> kvars<br />

b Reduces the apparent power kVA demand<br />

b Reduces the size <strong>of</strong> all cables as well as the cable losses<br />

Comments<br />

b Significant reactive currents no longer exist in the <strong>installation</strong><br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L11<br />

© Schneider Electric - all rights reserved


L12<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

5 How to decide the optimum level<br />

<strong>of</strong> compensation?<br />

5.1 <strong>General</strong> method<br />

Listing <strong>of</strong> reactive power demands at the <strong>design</strong> stage<br />

This listing can be made in the same way (and at the same time) as that for the<br />

power loading described in chapter A. The levels <strong>of</strong> active and reactive power<br />

loading, at each level <strong>of</strong> the <strong>installation</strong> (generally at points <strong>of</strong> distribution and subdistribution<br />

<strong>of</strong> circuits) can then be determined.<br />

Technical-economic optimization for an existing <strong>installation</strong><br />

The optimum rating <strong>of</strong> compensation capacitors for an existing <strong>installation</strong> can be<br />

determined from the following principal considerations:<br />

b Electricity bills prior to the <strong>installation</strong> <strong>of</strong> capacitors<br />

b Future electricity bills anticipated following the <strong>installation</strong> <strong>of</strong> capacitors<br />

b Costs <strong>of</strong>:<br />

v Purchase <strong>of</strong> capacitors and control equipment (contactors, relaying, cabinets, etc.)<br />

v Installation and maintenance costs<br />

v Cost <strong>of</strong> dielectric heating losses in the capacitors, versus reduced losses in cables,<br />

transformer, etc., following the <strong>installation</strong> <strong>of</strong> capacitors<br />

Several simplified methods applied to typical tariffs (common in Europe) are shown<br />

in sub-clauses 5.3 and 5.4.<br />

5.2 Simplified method<br />

<strong>General</strong> principle<br />

An approximate calculation is generally adequate for most practical cases, and may<br />

be based on the assumption <strong>of</strong> a power factor <strong>of</strong> 0.8 (lagging) before compensation.<br />

In order to improve the power factor to a value sufficient to avoid tariff penalties (this<br />

depends on local tariff structures, but is assumed here to be 0.93) and to reduce<br />

losses, volt-drops, etc. in the <strong>installation</strong>, reference can be made to Figure L15 next<br />

page.<br />

From the figure, it can be seen that, to raise the power factor <strong>of</strong> the <strong>installation</strong> from<br />

0.8 to 0.93 will require 0.355 kvar per kW <strong>of</strong> load. The rating <strong>of</strong> a bank <strong>of</strong> capacitors<br />

at the busbars <strong>of</strong> the main distribution board <strong>of</strong> the <strong>installation</strong> would be<br />

Q (kvar) = 0.355 x P (kW).<br />

This simple approach allows a rapid determination <strong>of</strong> the compensation capacitors<br />

required, albeit in the global, partial or independent mode.<br />

Example<br />

It is required to improve the power factor <strong>of</strong> a 666 kVA <strong>installation</strong> from 0.75 to 0.928.<br />

The active power demand is 666 x 0.75 = 500 kW.<br />

In Figure L15, the intersection <strong>of</strong> the row cos ϕ = 0.75 (before correction) with<br />

the column cos ϕ = 0.93 (after correction) indicates a value <strong>of</strong> 0.487 kvar <strong>of</strong><br />

compensation per kW <strong>of</strong> load.<br />

For a load <strong>of</strong> 500 kW, therefore, 500 x 0.487 = 244 kvar <strong>of</strong> capacitive compensation<br />

is required.<br />

Note: this method is valid for any voltage level, i.e. is independent <strong>of</strong> voltage.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

5 How to decide the optimum level<br />

<strong>of</strong> compensation?<br />

Before kvar rating <strong>of</strong> capacitor bank to install per kW <strong>of</strong> load, to improve cos ϕ (the power factor) or tan ϕ,<br />

compensation to a given value<br />

tan ϕ 0.75 0.59 0.48 0.46 0.43 0.40 0.36 0.33 0.29 0.25 0.20 0.14 0.0<br />

tan ϕ cos ϕ cos ϕ 0.80 0.86 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1<br />

2.29 0.40 1.557 1.691 1.805 1.832 1.861 1.895 1.924 1.959 1.998 2.037 2.085 2.146 2.288<br />

2.22 0.41 1.474 1.625 1.742 1.769 1.798 1.831 1.840 1.896 1.935 1.973 2.021 2.082 2.225<br />

2.16 0.42 1.413 1.561 1.681 1.709 1.738 1.771 1.800 1.836 1.874 1.913 1.961 2.022 2.164<br />

2.10 0.43 1.356 1.499 1.624 1.651 1.680 1.713 1.742 1.778 1.816 1.855 1.903 1.964 2.107<br />

2.04 0.44 1.290 1.441 1.558 1.585 1.614 1.647 1.677 1.712 1.751 1.790 1.837 1.899 2.041<br />

1.98 0.45 1.230 1.384 1.501 1.532 1.561 1.592 1.628 1.659 1.695 1.737 1.784 1.846 1.988<br />

1.93 0.46 1.179 1.330 1.446 1.473 1.502 1.533 1.567 1.600 1.636 1.677 1.725 1.786 1.929<br />

1.88 0.47 1.130 1.278 1.397 1.425 1.454 1.485 1.519 1.532 1.588 1.629 1.677 1.758 1.881<br />

1.83 0.48 1.076 1.228 1.343 1.370 1.400 1.430 1.464 1.497 1.534 1.575 1.623 1.684 1.826<br />

1.78 0.49 1.030 1.179 1.297 1.326 1.355 1.386 1.420 1.453 1.489 1.530 1.578 1.639 1.782<br />

1.73 0.50 0.982 1.232 1.248 1.276 1.303 1.337 1.369 1.403 1.441 1.481 1.529 1.590 1.732<br />

1.69 0.51 0.936 1.087 1.202 1.230 1.257 1.291 1.323 1.357 1.395 1.435 1.483 1.544 1.686<br />

1.64 0.52 0.894 1.043 1.160 1.188 1.215 1.249 1.281 1.315 1.353 1.393 1.441 1.502 1.644<br />

1.60 0.53 0.850 1.000 1.116 1.144 1.171 1.205 1.237 1.271 1.309 1.349 1.397 1.458 1.600<br />

1.56 0.54 0.809 0.959 1.075 1.103 1.130 1.164 1.196 1.230 1.268 1.308 1.356 1.417 1.559<br />

1.52 0.55 0.769 0.918 1.035 1.063 1.090 1.124 1.156 1.190 1.228 1.268 1.316 1.377 1.519<br />

1.48 0.56 0.730 0.879 0.996 1.024 1.051 1.085 1.117 1.151 1.189 1.229 1.277 1.338 1.480<br />

1.44 0.57 0.692 0.841 0.958 0.986 1.013 1.047 1.079 1.113 1.151 1.191 1.239 1.300 1.442<br />

1.40 0.58 0.665 0.805 0.921 0.949 0.976 1.010 1.042 1.076 1.114 1.154 1.202 1.263 1.405<br />

1.37 0.59 0.618 0.768 0.884 0.912 0.939 0.973 1.005 1.039 1.077 1.117 1.165 1.226 1.368<br />

1.33 0.60 0.584 0.733 0.849 0.878 0.905 0.939 0.971 1.005 1.043 1.083 1.131 1.192 1.334<br />

1.30 0.61 0.549 0.699 0.815 0.843 0.870 0.904 0.936 0.970 1.008 1.048 1.096 1.157 1.299<br />

1.27 0.62 0.515 0.665 0.781 0.809 0.836 0.870 0.902 0.936 0.974 1.014 1.062 1.123 1.265<br />

1.23 0.63 0.483 0.633 0.749 0.777 0.804 0.838 0.870 0.904 0.942 0.982 1.030 1.091 1.233<br />

1.20 0.64 0.450 0.601 0.716 0.744 0.771 0.805 0.837 0.871 0.909 0.949 0.997 1.058 1.200<br />

1.17 0.65 0.419 0.569 0.685 0.713 0.740 0.774 0.806 0.840 0.878 0.918 0.966 1.007 1.169<br />

1.14 0.66 0.388 0.538 0.654 0.682 0.709 0.743 0.775 0.809 0.847 0.887 0.935 0.996 1.138<br />

1.11 0.67 0.358 0.508 0.624 0.652 0.679 0.713 0.745 0.779 0.817 0.857 0.905 0.966 1.108<br />

1.08 0.68 0.329 0.478 0.595 0.623 0.650 0.684 0.716 0.750 0.788 0.828 0.876 0.937 1.079<br />

1.05 0.69 0.299 0.449 0.565 0.593 0.620 0.654 0.686 0.720 0.758 0.798 0.840 0.907 1.049<br />

1.02 0.70 0.270 0.420 0.536 0.564 0.591 0.625 0.657 0.691 0.729 0.769 0.811 0.878 1.020<br />

0.99 0.71 0.242 0.392 0.508 0.536 0.563 0.597 0.629 0.663 0.701 0.741 0.783 0.850 0.992<br />

0.96 0.72 0.213 0.364 0.479 0.507 0.534 0.568 0.600 0.634 0.672 0.712 0.754 0.821 0.963<br />

0.94 0.73 0.186 0.336 0.452 0.480 0.507 0.541 0.573 0.607 0.645 0.685 0.727 0.794 0.936<br />

0.91 0.74 0.159 0.309 0.425 0.453 0.480 0.514 0.546 0.580 0.618 0.658 0.700 0.767 0.909<br />

0.88 0.75 0.132 0.82 0.398 0.426 0.453 0.487 0.519 0.553 0.591 0.631 0.673 0.740 0.882<br />

0.86 0.76 0.105 0.255 0.371 0.399 0.426 0.460 0.492 0.526 0.564 0.604 0.652 0.713 0.855<br />

0.83 0.77 0.079 0.229 0.345 0.373 0.400 0.434 0.466 0.500 0.538 0.578 0.620 0.687 0.829<br />

0.80 0.78 0.053 0.202 0.319 0.347 0.374 0.408 0.440 0.474 0.512 0.552 0.594 0.661 0.803<br />

0.78 0.79 0.026 0.176 0.292 0.320 0.347 0.381 0.413 0.447 0.485 0.525 0.567 0.634 0.776<br />

0.75 0.80 0.150 0.266 0.294 0.321 0.355 0.387 0.421 0.459 0.499 0.541 0.608 0.750<br />

0.72 0.81 0.124 0.240 0.268 0.295 0.329 0.361 0.395 0.433 0.473 0.515 0.582 0.724<br />

0.70 0.82 0.098 0.214 0.242 0.269 0.303 0.335 0.369 0.407 0.447 0.489 0.556 0.698<br />

0.67 0.83 0.072 0.188 0.216 0.243 0.277 0.309 0.343 0.381 0.421 0.463 0.530 0.672<br />

0.65 0.84 0.046 0.162 0.190 0.217 0.251 0.283 0.317 0.355 0.395 0.437 0.504 0.645<br />

0.62 0.85 0.020 0.136 0.164 0.191 0.225 0.257 0.291 0.329 0.369 0.417 0.478 0.620<br />

0.59 0.86 0.109 0.140 0.167 0.198 0.230 0.264 0.301 0.343 0.390 0.450 0.593<br />

0.57 0.87 0.083 0.114 0.141 0.172 0.204 0.238 0.275 0.317 0.364 0.424 0.567<br />

0.54 0.88 0.054 0.085 0.112 0.143 0.175 0.209 0.246 0.288 0.335 0.395 0.538<br />

0.51 0.89 0.028 0.059 0.086 0.117 0.149 0.183 0.230 0.262 0.309 0.369 0.512<br />

0.48 0.90 0.031 0.058 0.089 0.121 0.155 0.192 0.234 0.281 0.341 0.484<br />

Value selected as an example on section 5.2<br />

Value selected as an example on section 5.4<br />

Fig. L15 : kvar to be installed per kW <strong>of</strong> load, to improve the power factor <strong>of</strong> an <strong>installation</strong><br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L13<br />

© Schneider Electric - all rights reserved


L14<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

In the case <strong>of</strong> certain (common) types <strong>of</strong><br />

tariff, an examination <strong>of</strong> several bills covering<br />

the most heavily-loaded period <strong>of</strong> the year<br />

allows determination <strong>of</strong> the kvar level <strong>of</strong><br />

compensation required to avoid kvarh (reactiveenergy)<br />

charges. The pay-back period <strong>of</strong> a<br />

bank <strong>of</strong> power-factor-correction capacitors<br />

and associated equipment is generally about<br />

18 months<br />

For 2-part tariffs based partly on a declared value<br />

<strong>of</strong> kVA, Figure L17 allows determination <strong>of</strong> the<br />

kvar <strong>of</strong> compensation required to reduce the<br />

value <strong>of</strong> kVA declared, and to avoid exceeding it<br />

ϕ'<br />

ϕ<br />

Cos ϕ = 0.7<br />

Cos ϕ'= 0.95<br />

S = 122 kVA<br />

S' = 90 kVA<br />

Q = 87.1 kvar<br />

Qc = 56 kvar<br />

Q' = 28.1 kvar<br />

P = 85.4 kW<br />

Fig. L16 : Reduction <strong>of</strong> declared maximum kVA by powerfactor<br />

improvement<br />

(1) In the billing period, during the hours for which<br />

reactive energy is charged for the case considered above:<br />

15,996 kvarh<br />

Qc = =<br />

73 kvar<br />

220 h<br />

S'<br />

S<br />

Q'<br />

Qc<br />

Q<br />

5 How to decide the optimum level<br />

<strong>of</strong> compensation?<br />

5.3 Method based on the avoidance <strong>of</strong> tariff<br />

penalties<br />

The following method allows calculation <strong>of</strong> the rating <strong>of</strong> a proposed capacitor bank,<br />

based on billing details, where the tariff structure corresponds with (or is similar to)<br />

the one described in sub-clause 2.1 <strong>of</strong> this chapter.<br />

The method determines the minimum compensation required to avoid these charges<br />

which are based on kvarh consumption.<br />

The procedure is as follows:<br />

b Refer to the bills covering consumption for the 5 months <strong>of</strong> winter (in France these<br />

are November to March inclusive).<br />

Note: in tropical climates the summer months may constitute the period <strong>of</strong> heaviest<br />

loading and highest peaks (owing to extensive air conditioning loads) so that a<br />

consequent variation <strong>of</strong> high-tariff periods is necessary in this case. The remainder <strong>of</strong><br />

this example will assume Winter conditions in France.<br />

b Identify the line on the bills referring to “reactive-energy consumed” and “kvarh<br />

to be charged”. Choose the bill which shows the highest charge for kvarh (after<br />

checking that this was not due to some exceptional situation).<br />

For example: 15,966 kvarh in January.<br />

b Evaluate the total period <strong>of</strong> loaded operation <strong>of</strong> the <strong>installation</strong> for that month, for<br />

instance: 220 hours (22 days x 10 hours). The hours which must be counted are<br />

those occurring during the heaviest load and the highest peak loads occurring on<br />

the power system. These are given in the tariff documents, and are (commonly)<br />

during a 16-hour period each day, either from 06.00 h to 22.00 h or from 07.00 h to<br />

23.00 h according to the region. Outside these periods, no charge is made for kvarh<br />

consumption.<br />

b The necessary value <strong>of</strong> compensation in kvar = kvarh billed/number <strong>of</strong> hours <strong>of</strong><br />

operation (1) = Qc<br />

The rating <strong>of</strong> the installed capacitor bank is generally chosen to be slightly larger<br />

than that calculated.<br />

Certain manufacturers can provide “slide <strong>rules</strong>” especially <strong>design</strong>ed to facilitate<br />

these kinds <strong>of</strong> calculation, according to particular tariffs. These devices and<br />

accompanying documentation advice on suitable equipment and control schemes,<br />

as well as drawing attention to constraints imposed by harmonic voltages on the<br />

power system. Such voltages require either over dimensioned capacitors (in terms <strong>of</strong><br />

heat-dissipation, voltage and current ratings) and/or harmonic-suppression inductors<br />

or filters.<br />

5.4 Method based on reduction <strong>of</strong> declared<br />

maximum apparent power (kVA)<br />

For consumers whose tariffs are based on a fixed charge per kVA declared, plus a<br />

charge per kWh consumed, it is evident that a reduction in declared kVA would be<br />

beneficial. The diagram <strong>of</strong> Figure L16 shows that as the power factor improves, the<br />

kVA value diminishes for a given value <strong>of</strong> kW (P). The improvement <strong>of</strong> the power<br />

factor is aimed at (apart from other advantages previously mentioned) reducing the<br />

declared level and never exceeding it, thereby avoiding the payment <strong>of</strong> an excessive<br />

price per kVA during the periods <strong>of</strong> excess, and/or tripping <strong>of</strong> the the main circuitbreaker.<br />

Figure L15 (previous page) indicates the value <strong>of</strong> kvar <strong>of</strong> compensation per<br />

kW <strong>of</strong> load, required to improve from one value <strong>of</strong> power factor to another.<br />

Example:<br />

A supermarket has a declared load <strong>of</strong> 122 kVA at a power factor <strong>of</strong> 0.7 lagging, i.e.an<br />

active-power load <strong>of</strong> 85.4 kW. The particular contract for this consumer was based on<br />

stepped values <strong>of</strong> declared kVA (in steps <strong>of</strong> 6 kVA up to 108 kVA, and 12 kVA steps<br />

above that value, this is a common feature in many types <strong>of</strong> two-part tariff). In the<br />

case being considered, the consumer was billed on the basis <strong>of</strong><br />

132 kVA. Referring to Figure L15, it can be seen that a 60 kvar bank <strong>of</strong> capacitors<br />

will improve the power factor <strong>of</strong> the load from 0.7 to 0.95 (0.691 x 85.4 = 59 kvar<br />

in the figure). The declared value <strong>of</strong> kVA will then be 85.4<br />

= 9 0 kVA , i.e. an<br />

improvement <strong>of</strong> 30%.<br />

0.95<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

The <strong>installation</strong> <strong>of</strong> a capacitor bank can avoid<br />

the need to change a transformer in the event <strong>of</strong><br />

a load increase<br />

6 Compensation at the terminals<br />

<strong>of</strong> a transformer<br />

6.1 Compensation to increase the available active<br />

power output<br />

Steps similar to those taken to reduce the declared maximum kVA, i.e. improvement<br />

<strong>of</strong> the load power factor, as discussed in subclause 5.4, will maximise the available<br />

transformer capacity, i.e. to supply more active power.<br />

Cases can arise where the replacement <strong>of</strong> a transformer by a larger unit, to overcome<br />

a load growth, may be avoided by this means. Figure L17 shows directly the power<br />

(kW) capability <strong>of</strong> fully-loaded transformers at different load power factors, from<br />

which the increase <strong>of</strong> active-power output can be obtained as the value <strong>of</strong> power<br />

factor increases.<br />

Fig. L17 : Active-power capability <strong>of</strong> fully-loaded transformers, when supplying loads at different values <strong>of</strong> power factor<br />

Q<br />

P1<br />

tan ϕ cos ϕ Nominal rating <strong>of</strong> transformers (in kVA)<br />

100 160 250 315 400 500 630 800 1000 1250 1600 2000<br />

0.00 1 100 160 250 315 400 500 630 800 1000 1250 1600 2000<br />

0.20 0.98 98 157 245 309 392 490 617 784 980 1225 1568 1960<br />

0.29 0.96 96 154 240 302 384 480 605 768 960 1200 1536 1920<br />

0.36 0.94 94 150 235 296 376 470 592 752 940 1175 1504 1880<br />

0.43 0.92 92 147 230 290 368 460 580 736 920 1150 1472 1840<br />

0.48 0.90 90 144 225 284 360 450 567 720 900 1125 1440 1800<br />

0.54 0.88 88 141 220 277 352 440 554 704 880 1100 1408 1760<br />

0.59 0.86 86 138 215 271 344 430 541 688 860 1075 1376 1720<br />

0.65 0.84 84 134 210 265 336 420 529 672 840 1050 1344 1680<br />

0.70 0.82 82 131 205 258 328 410 517 656 820 1025 1312 1640<br />

0.75 0.80 80 128 200 252 320 400 504 640 800 1000 1280 1600<br />

0.80 0.78 78 125 195 246 312 390 491 624 780 975 1248 1560<br />

0.86 0.76 76 122 190 239 304 380 479 608 760 950 1216 1520<br />

0.91 0.74 74 118 185 233 296 370 466 592 740 925 1184 1480<br />

0.96 0.72 72 115 180 227 288 360 454 576 720 900 1152 1440<br />

1.02 0.70 70 112 175 220 280 350 441 560 700 875 1120 1400<br />

S1<br />

S<br />

S2 Q2<br />

Q1<br />

P2<br />

Q<br />

Q m<br />

Fig. L18 : Compensation Q allows the <strong>installation</strong>-load<br />

extension S2 to be added, without the need to replace the<br />

existing transformer, the output <strong>of</strong> which is limited to S<br />

P<br />

Example: (see Fig. L18 )<br />

An <strong>installation</strong> is supplied from a 630 kVA transformer loaded at 450 kW (P1) with a<br />

450<br />

mean power factor <strong>of</strong> 0.8 lagging. The apparent power S1=<br />

= 5 62 kVA<br />

0.8<br />

The corresponding reactive power<br />

2 2<br />

Q1= S1 − P1 = 337 kvar<br />

The anticipated load increase P2 = 100 kW at a power factor <strong>of</strong> 0.7 lagging.<br />

The apparent power 100<br />

S2<br />

= = 143 kVA<br />

The corresponding reactive 0.7 power<br />

2 2<br />

Q2 = S2 − P2 = 1 02 kvar<br />

What is the minimum value <strong>of</strong> capacitive kvar to be installed, in order to avoid a<br />

change <strong>of</strong> transformer?<br />

Total power now to be supplied:<br />

P = P1 + P2 = 550 kW<br />

The maximum reactive power capability <strong>of</strong> the 630 kVA transformer when delivering<br />

550 kW is:<br />

2 2<br />

2 2<br />

Qm = S − P Qm = 630 − 550 = 307 kvar<br />

Total reactive power required by the <strong>installation</strong> before compensation:<br />

Q1 + Q2 = 337 + 102 = 439 kvar<br />

So that the minimum size <strong>of</strong> capacitor bank to install:<br />

Qkvar = 439 - 307 = 132 kvar<br />

It should be noted that this calculation has not taken account <strong>of</strong> load peaks and their<br />

duration.<br />

The best possible improvement, i.e. correction which attains a power factor <strong>of</strong><br />

1 would permit a power reserve for the transformer <strong>of</strong> 630 - 550 = 80 kW.<br />

The capacitor bank would then have to be rated at 439 kvar.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L15<br />

© Schneider Electric - all rights reserved


L16<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

Where metering is carried out at the MV side<br />

<strong>of</strong> a transformer, the reactive-energy losses in<br />

the transformer may need to be compensated<br />

(depending on the tariff)<br />

Perfect transformer<br />

Primary<br />

winding<br />

Secondary<br />

winding<br />

Fig. L19 : Transformer reactances per phase<br />

Leakage reactance<br />

Magnetizing<br />

reactance<br />

The reactive power absorbed by a transformer<br />

cannot be neglected, and can amount to (about)<br />

5% <strong>of</strong> the transformer rating when supplying<br />

its full load. Compensation can be provided by<br />

a bank <strong>of</strong> capacitors. In transformers, reactive<br />

power is absorbed by both shunt (magnetizing)<br />

and series (leakage flux) reactances. Complete<br />

compensation can be provided by a bank <strong>of</strong><br />

shunt-connected LV capacitors<br />

I sin<br />

'<br />

I sin<br />

'<br />

I<br />

E<br />

Source<br />

XL<br />

V<br />

Load<br />

Fig. L20 : Reactive power absorption by series inductance<br />

I<br />

V<br />

E<br />

IXL<br />

6 Compensation at the terminals<br />

<strong>of</strong> a transformer<br />

6.2 Compensation <strong>of</strong> reactive energy absorbed by<br />

the transformer<br />

The nature <strong>of</strong> transformer inductive reactances<br />

All previous references have been to shunt connected devices such as those used<br />

in normal loads, and power factor-correcting capacitor banks etc. The reason for<br />

this is that shunt connected equipment requires (by far) the largest quantities <strong>of</strong><br />

reactive energy in power systems; however, series-connected reactances, such as<br />

the inductive reactances <strong>of</strong> power lines and the leakage reactance <strong>of</strong> transformer<br />

windings, etc., also absorb reactive energy.<br />

Where metering is carried out at the MV side <strong>of</strong> a transformer, the reactive-energy<br />

losses in the transformer may (depending on the tariff) need to be compensated. As<br />

far as reactive-energy losses only are concerned, a transformer may be represented<br />

by the elementary diagram <strong>of</strong> Figure L19. All reactance values are referred to<br />

the secondary side <strong>of</strong> the transformer, where the shunt branch represents the<br />

magnetizing-current path. The magnetizing current remains practically constant (at<br />

about 1.8% <strong>of</strong> full-load current) from no load to full load, in normal circumstances,<br />

i.e. with a constant primary voltage, so that a shunt capacitor <strong>of</strong> fixed value can be<br />

installed at the MV or LV side, to compensate for the reactive energy absorbed.<br />

Reactive-power absorption in series-connected<br />

(leakage flux) reactance XL<br />

A simple illustration <strong>of</strong> this phenomenon is given by the vector diagram <strong>of</strong><br />

Figure L20.<br />

The reactive-current component through the load = I sin ϕ so that QL = VI sin ϕ.<br />

The reactive-current component from the source = I sin ϕ’ so that QE = EI sin ϕ’.<br />

It can be seen that E > V and sin ϕ’ > sin ϕ.<br />

The difference between EI sin ϕ’ and VI sin ϕ gives the kvar per phase absorbed<br />

by XL.<br />

It can be shown that this kvar value is equal to I2XL (which is analogous to the I2R active power (kW) losses due to the series resistance <strong>of</strong> power lines, etc.).<br />

From the I2XL formula it is very simple to deduce the kvar absorbed at any load value<br />

for a given transformer, as follows:<br />

If per-unit values are used (instead <strong>of</strong> percentage values) direct multiplication <strong>of</strong> I<br />

and XL can be carried out.<br />

Example:<br />

A 630 kVA transformer with a short-circuit reactance voltage <strong>of</strong> 4% is fully loaded.<br />

What is its reactive-power (kvar) loss?<br />

4% = 0.04 pu Ipu = 1<br />

loss = I 2 XL = 1 2 x 0.04 = 0.04 pu kvar<br />

where 1 pu = 630 kVA<br />

The 3-phase kvar losses are 630 x 0.04 = 25.2 kvar (or, quite simply, 4% <strong>of</strong> 630 kVA).<br />

At half load i.e. I = 0.5 pu the losses will be<br />

0.5 2 x 0.04 = 0.01 pu = 630 x 0.01 = 6.3 kvar and so on...<br />

This example, and the vector diagram <strong>of</strong> Figure L20 show that:<br />

b The power factor at the primary side <strong>of</strong> a loaded transformer is different (normally<br />

lower) than that at the secondary side (due to the absorption <strong>of</strong> vars)<br />

b Full-load kvar losses due to leakage reactance are equal to the transformer<br />

percentage reactance (4% reactance means a kvar loss equal to 4% <strong>of</strong> the kVA rating<br />

<strong>of</strong> the transformer)<br />

b kvar losses due to leakage reactance vary according to the current<br />

(or kVA loading) squared<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

6 Compensation at the terminals<br />

<strong>of</strong> a transformer<br />

To determine the total kvar losses <strong>of</strong> a transformer the constant magnetizing-current<br />

circuit losses (approx. 1.8% <strong>of</strong> the transformer kVA rating) must be added to the<br />

foregoing “series” losses. Figure L21 shows the no-load and full-load kvar losses for<br />

typical distribution transformers. In principle, series inductances can be compensated<br />

by fixed series capacitors (as is commonly the case for long MV transmission lines).<br />

This arrangement is operationally difficult, however, so that, at the voltage levels<br />

covered by this guide, shunt compensation is always applied.<br />

In the case <strong>of</strong> MV metering, it is sufficient to raise the power factor to a point where<br />

the transformer plus load reactive-power consumption is below the level at which a<br />

billing charge is made. This level depends on the tariff, but <strong>of</strong>ten corresponds to a<br />

tan ϕ value <strong>of</strong> 0.31 (cos ϕ <strong>of</strong> 0.955).<br />

Rated power (kVA) Reactive power (kvar) to be compensated<br />

No load Full load<br />

100 2.5 6.1<br />

160 3.7 9.6<br />

250 5.3 14.7<br />

315 6.3 18.4<br />

400 7.6 22.9<br />

500 9.5 28.7<br />

630 11.3 35.7<br />

800 20 54.5<br />

1000 23.9 72.4<br />

1250 27.4 94.5<br />

1600 31.9 126<br />

2000 37.8 176<br />

Fig. L21 : Reactive power consumption <strong>of</strong> distribution transformers with 20 kV primary windings<br />

As a matter <strong>of</strong> interest, the kvar losses in a transformer can be completely<br />

compensated by adjusting the capacitor bank to give the load a (slightly) leading<br />

power factor. In such a case, all <strong>of</strong> the kvar <strong>of</strong> the transformer is being supplied from<br />

the capacitor bank, while the input to the MV side <strong>of</strong> the transformer is at unity power<br />

factor, as shown in Figure L22.<br />

Load<br />

current<br />

I<br />

ϕ<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

E (Input voltage)<br />

V (Load voltage)<br />

I0 Compensation current<br />

Fig. L22 : Overcompensation <strong>of</strong> load to completely compensate transformer reactive-power losses<br />

In practical terms, therefore, compensation for transformer-absorbed kvar is included<br />

in the capacitors primarily intended for powerfactor correction <strong>of</strong> the load, either<br />

globally, partially, or in the individual mode. Unlike most other kvar-absorbing items,<br />

the transformer absorption (i.e. the part due to the leakage reactance) changes<br />

significantly with variations <strong>of</strong> load level, so that, if individual compensation is applied<br />

to the transformer, then an average level <strong>of</strong> loading will have to be assumed.<br />

Fortunately, this kvar consumption generally forms only a relatively small part <strong>of</strong> the<br />

total reactive power <strong>of</strong> an <strong>installation</strong>, and so mismatching <strong>of</strong> compensation at times<br />

<strong>of</strong> load change is not likely to be a problem.<br />

Figure L21 indicates typical kvar loss values for the magnetizing circuit (“no-load<br />

kvar” columns), as well as for the total losses at full load, for a standard range <strong>of</strong><br />

distribution transformers supplied at 20 kV (which include the losses due to the<br />

leakage reactance).<br />

IXL<br />

L17<br />

© Schneider Electric - all rights reserved


L18<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

Individual motor compensation is recommended<br />

where the motor power (kVA) is large with<br />

respect to the declared power <strong>of</strong> the <strong>installation</strong><br />

Before<br />

compensation<br />

Transformer<br />

Active<br />

power<br />

Motor<br />

M M<br />

After<br />

compensation<br />

Power<br />

made<br />

available<br />

C<br />

Reactive<br />

power<br />

supplied<br />

by capacitor<br />

7 Power factor correction <strong>of</strong><br />

induction motors<br />

7.1 Connection <strong>of</strong> a capacitor bank and protection<br />

settings<br />

<strong>General</strong> precautions<br />

Because <strong>of</strong> the small kW consumption, the power factor <strong>of</strong> a motor is very low at noload<br />

or on light load. The reactive current <strong>of</strong> the motor remains practically constant at<br />

all loads, so that a number <strong>of</strong> unloaded motors constitute a consumption <strong>of</strong> reactive<br />

power which is generally detrimental to an <strong>installation</strong>, for reasons explained in<br />

preceding sections.<br />

Two good general <strong>rules</strong> therefore are that unloaded motors should be switched <strong>of</strong>f,<br />

and motors should not be oversized (since they will then be lightly loaded).<br />

Connection<br />

The bank <strong>of</strong> capacitors should be connected directly to the terminals <strong>of</strong> the motor.<br />

Special motors<br />

It is recommended that special motors (stepping, plugging, inching, reversing motors,<br />

etc.) should not be compensated.<br />

Effect on protection settings<br />

After applying compensation to a motor, the current to the motor-capacitor<br />

combination will be lower than before, assuming the same motor-driven load<br />

conditions. This is because a significant part <strong>of</strong> the reactive component <strong>of</strong> the motor<br />

current is being supplied from the capacitor, as shown in Figure L23.<br />

Where the overcurrent protection devices <strong>of</strong> the motor are located upstream <strong>of</strong> the<br />

motor capacitor connection (and this will always be the case for terminal-connected<br />

capacitors), the overcurrent relay settings must be reduced in the ratio:<br />

cos ϕ before compensation / cos ϕ after compensation<br />

For motors compensated in accordance with the kvar values indicated in Figure L24<br />

(maximum values recommended for avoidance <strong>of</strong> self-excitation <strong>of</strong> standard<br />

induction motors, as discussed in sub-clause 7.2), the above-mentioned ratio<br />

will have a value similar to that indicated for the corresponding motor speed in<br />

Figure L25.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3-phase motors 230/400 V<br />

Nominal power kvar to be installed<br />

Speed <strong>of</strong> rotation (rpm)<br />

kW hp 3000 1500 1000 750<br />

22 30 6 8 9 10<br />

30 40 7.5 10 11 12.5<br />

37 50 9 11 12.5 16<br />

45 60 11 13 14 17<br />

55 75 13 17 18 21<br />

75 100 17 22 25 28<br />

90 125 20 25 27 30<br />

110 150 24 29 33 37<br />

132 180 31 36 38 43<br />

160 218 35 41 44 52<br />

200 274 43 47 53 61<br />

250 340 52 57 63 71<br />

280 380 57 63 70 79<br />

355 482 67 76 86 98<br />

400 544 78 82 97 106<br />

450 610 87 93 107 117<br />

Figure L24 : Maximum kvar <strong>of</strong> power factor correction applicable to motor terminals without risk<br />

<strong>of</strong> self excitation<br />

Speed in rpm Reduction factor<br />

750 0.88<br />

1000 0.90<br />

1500 0.91<br />

3000 0.93<br />

Fig. L23 : Before compensation, the transformer supplies all<br />

the reactive power; after compensation, the capacitor supplies<br />

a large part <strong>of</strong> the reactive power Fig. L25 : Reduction factor for overcurrent protection after compensation


L - Power factor correction and<br />

harmonic filtering<br />

When a capacitor bank is connected to the<br />

terminals <strong>of</strong> an induction motor, it is important<br />

to check that the size <strong>of</strong> the bank is less than<br />

that at which self-excitation can occur<br />

Fig. L26 : Connection <strong>of</strong> the capacitor bank to the motor<br />

7 Power factor correction <strong>of</strong><br />

induction motors<br />

7.2 How self-excitation <strong>of</strong> an induction motor can be<br />

avoided<br />

When a motor is driving a high-inertia load, the motor will continue to rotate (unless<br />

deliberately braked) after the motor supply has been switched <strong>of</strong>f.<br />

The “magnetic inertia” <strong>of</strong> the rotor circuit means that an emf will be generated in the<br />

stator windings for a short period after switching <strong>of</strong>f, and would normally reduce to<br />

zero after 1 or 2 cycles, in the case <strong>of</strong> an uncompensated motor.<br />

Compensation capacitors however, constitute a 3-phase “wattless” load for this<br />

decaying emf, which causes capacitive currents to flow through the stator windings.<br />

These stator currents will produce a rotating magnetic field in the rotor which acts<br />

exactly along the same axis and in the same direction as that <strong>of</strong> the decaying<br />

magnetic field.<br />

The rotor flux consequently increases; the stator currents increase; and the voltage<br />

at the terminals <strong>of</strong> the motor increases; sometimes to dangerously-high levels. This<br />

phenomenon is known as self-excitation and is one reason why AC generators<br />

are not normally operated at leading power factors, i.e. there is a tendency to<br />

spontaneously (and uncontrollably) self excite.<br />

Notes:<br />

1. The characteristics <strong>of</strong> a motor being driven by the inertia <strong>of</strong> the load are not<br />

rigorously identical to its no-load characteristics. This assumption, however, is<br />

sufficiently accurate for practical purposes.<br />

2. With the motor acting as a generator, the currents circulating are largely reactive,<br />

so that the braking (retarding) effect on the motor is mainly due only to the load<br />

represented by the cooling fan in the motor.<br />

3. The (almost 90° lagging) current taken from the supply in normal circumstances by<br />

the unloaded motor, and the (almost 90° leading) current supplied to the capacitors<br />

by the motor acting as a generator, both have the same phase relationship<br />

to the terminalvoltage. It is for this reason that the two characteristics may be<br />

superimposed on the graph.<br />

In order to avoid self-excitation as described above, the kvar rating <strong>of</strong> the capacitor<br />

bank must be limited to the following maximum value:<br />

Qc y 0.9 x Io x Un x 3 where Io = the no-load current <strong>of</strong> the motor and Un =<br />

phase-to-phase nominal voltage <strong>of</strong> the motor in kV. Figure L24 previous page gives<br />

appropriate values <strong>of</strong> Qc corresponding to this criterion.<br />

Example<br />

A 75 kW, 3,000 rpm, 400 V, 3-phase motor may have a capacitor bank no larger<br />

than 17 kvar according to Figure L24. The table values are, in general, too small to<br />

adequately compensate the motor to the level <strong>of</strong> cos ϕ normally required. Additional<br />

compensation can, however, be applied to the system, for example an overall bank,<br />

installed for global compensation <strong>of</strong> a number <strong>of</strong> smaller appliances.<br />

High-inertia motors and/or loads<br />

In any <strong>installation</strong> where high-inertia motor driven loads exist, the circuit-breakers or<br />

contactors controlling such motors should, in the event <strong>of</strong> total loss <strong>of</strong> power supply,<br />

be rapidly tripped.<br />

If this precaution is not taken, then self excitation to very high voltages is likely to<br />

occur, since all other banks <strong>of</strong> capacitors in the <strong>installation</strong> will effectively be in<br />

parallel with those <strong>of</strong> the high-inertia motors.<br />

The protection scheme for these motors should therefore include an overvoltage<br />

tripping relay, together with reverse-power checking contacts (the motor will feed<br />

power to the rest <strong>of</strong> the <strong>installation</strong>, until the stored inertial energy is dissipated).<br />

If the capacitor bank associated with a high inertia motor is larger than that<br />

recommended in Figure L24, then it should be separately controlled by a circuitbreaker<br />

or contactor, which trips simultaneously with the main motor-controlling<br />

circuit-breaker or contactor, as shown in Figure L26.<br />

Closing <strong>of</strong> the main contactor is commonly subject to the capacitor contactor being<br />

previously closed.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L19<br />

© Schneider Electric - all rights reserved


L20<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

Installation before P.F. correction<br />

� � � (1)<br />

kVA=kW+kvar b kvarh are billed heavily above the declared<br />

level<br />

b Apparent power kVA is significantly greater<br />

� � �<br />

kVA=kW+kvar<br />

kVA than the kW demand<br />

kVA<br />

kW kvar<br />

b The corresponding excess current causes<br />

losses (kWh) which are billed<br />

b The <strong>installation</strong> must be over-dimensioned<br />

kW<br />

630 kVA<br />

400 V<br />

cos ϕ = 0.75<br />

workshop<br />

Characteristics <strong>of</strong> the <strong>installation</strong><br />

500 kW cos ϕ = 0.75<br />

b Transformer is overloaded<br />

b The power demand is<br />

S = P = 500 = 665 kVA<br />

cos ϕ 0.75<br />

S = apparent power<br />

b The current flowing into the <strong>installation</strong><br />

downstream <strong>of</strong> the circuit breaker is<br />

I = P = 960 A<br />

3U cos ϕ<br />

b Losses in cables are calculated as a<br />

function <strong>of</strong> the current squared: 960 2<br />

P=I 2 R<br />

cos ϕ = 0.75<br />

b Reactive energy is supplied through the<br />

transformer and via the <strong>installation</strong> wiring<br />

b The transformer, circuit breaker, and cables<br />

must be over-dimensioned<br />

8 Example <strong>of</strong> an <strong>installation</strong><br />

before and after power-factor<br />

correction<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Installation after P.F. correction<br />

630 kVA<br />

400 V<br />

cos ϕ = 0.75<br />

workshop<br />

Fig. K27 : Technical-economic comparison <strong>of</strong> an <strong>installation</strong> before and after power-factor correction<br />

(1) The arrows denote vector quantities.<br />

(2) Particularly in the pre-corrected case.<br />

b The consumption <strong>of</strong> kvarh is<br />

v Eliminated, or<br />

v Reduced, according to the cos ϕ required<br />

b The tariff penalties<br />

v For reactive energy where applicable<br />

v For the entire bill in some cases are<br />

eliminated<br />

b The fixed charge based on kVA demand is<br />

adjusted to be close to the active power kW<br />

demand<br />

Characteristics <strong>of</strong> the <strong>installation</strong><br />

500 kW cos ϕ = 0.928<br />

b Transformer no longer overloaded<br />

b The power-demand is 539 kVA<br />

b There is 14% spare-transformer capacity<br />

available<br />

b The current flowing into the <strong>installation</strong><br />

through the circuit breaker is 778 A<br />

250 kvar<br />

b The losses in the cables are<br />

reduced to 7782 = 65% <strong>of</strong> the former value,<br />

960 2<br />

thereby economizing in kWh consumed<br />

cos ϕ = 0.928<br />

b Reactive energy is supplied by the capacitor<br />

bank<br />

Capacitor bank rating is 250 kvar<br />

in 5 automatically-controlled steps <strong>of</strong> 50 kvar.<br />

Note: In fact, the cos ϕ <strong>of</strong> the workshop remains at 0.75 but cos ϕ for all the<br />

<strong>installation</strong> upstream <strong>of</strong> the capacitor bank to the transformer LV terminals<br />

is 0.928.<br />

As mentioned in Sub-clause 6.2 the cos ϕ at the HV side <strong>of</strong> the transformer<br />

will be slightly lower (2) , due to the reactive power losses in the transformer.


L - Power factor correction and<br />

harmonic filtering<br />

Harmonics are taken into account mainly by<br />

oversizing capacitors and including harmonicsuppression<br />

reactors in series with them<br />

Harmonic<br />

generator<br />

Ihar<br />

Filter<br />

Fig. L28 : Operation principle <strong>of</strong> passive filter<br />

9 The effects <strong>of</strong> harmonics<br />

9.1 Problems arising from power-system harmonics<br />

Equipment which uses power electronics components (variable-speed motor<br />

controllers, thyristor-controlled rectifiers, etc.) have considerably increased the<br />

problems caused by harmonics in power supply systems.<br />

Harmonics have existed from the earliest days <strong>of</strong> the industry and were (and still<br />

are) caused by the non-linear magnetizing impedances <strong>of</strong> transformers, reactors,<br />

fluorescent lamp ballasts, etc.<br />

Harmonics on symmetrical 3-phase power systems are generally odd-numbered: 3 rd ,<br />

5 th , 7 th , 9 th ..., and the magnitude decreases as the order <strong>of</strong> the harmonic increases.<br />

A number <strong>of</strong> features may be used in various ways to reduce specific harmonics to<br />

negligible values - total elimination is not possible. In this section, practical means <strong>of</strong><br />

reducing the influence <strong>of</strong> harmonics are recommended, with particular reference to<br />

capacitor banks.<br />

Capacitors are especially sensitive to harmonic components <strong>of</strong> the supply voltage<br />

due to the fact that capacitive reactance decreases as the frequency increases.<br />

In practice, this means that a relatively small percentage <strong>of</strong> harmonic voltage can<br />

cause a significant current to flow in the capacitor circuit.<br />

The presence <strong>of</strong> harmonic components causes the (normally sinusoidal) wave form<br />

<strong>of</strong> voltage or current to be distorted; the greater the harmonic content, the greater the<br />

degree <strong>of</strong> distortion.<br />

If the natural frequency <strong>of</strong> the capacitor bank/ power-system reactance combination<br />

is close to a particular harmonic, then partial resonance will occur, with amplified<br />

values <strong>of</strong> voltage and current at the harmonic frequency concerned. In this particular<br />

case, the elevated current will cause overheating <strong>of</strong> the capacitor, with degradation<br />

<strong>of</strong> the dielectric, which may result in its eventual failure.<br />

Several solutions to these problems are available. This can be accomplished by<br />

b Shunt connected harmonic filter and/or harmonic-suppression reactors or<br />

b Active power filters or<br />

b Hybrid filters<br />

9.2 Possible solutions<br />

Passive filter (see Fig. L28)<br />

Countering the effects <strong>of</strong> harmonics<br />

The presence <strong>of</strong> harmonics in the supply voltage results in abnormally high current<br />

levels through the capacitors. An allowance is made for this by <strong>design</strong>ing for an r.m.s.<br />

value <strong>of</strong> current equal to 1.3 times the nominal rated current. All series elements,<br />

such as connections, fuses, switches, etc., associated with the capacitors are<br />

similarly oversized, between 1.3 to 1.5 times nominal rating.<br />

Harmonic distortion <strong>of</strong> the voltage wave frequently produces a “peaky” wave form,<br />

in which the peak value <strong>of</strong> the normal sinusoidal wave is increased. This possibility,<br />

together with other overvoltage conditions likely to occur when countering the effects<br />

<strong>of</strong> resonance, as described below, are taken into account by increasing the insulation<br />

level above that <strong>of</strong> “standard” capacitors. In many instances, these two counter<br />

measures are all that is necessary to achieve satisfactory operation.<br />

Countering the effects <strong>of</strong> resonance<br />

Capacitors are linear reactive devices, and consequently do not generate harmonics.<br />

The <strong>installation</strong> <strong>of</strong> capacitors in a power system (in which the impedances are<br />

predominantly inductive) can, however, result in total or partial resonance occurring<br />

at one <strong>of</strong> the harmonic frequencies.<br />

The harmonic order ho <strong>of</strong> the natural resonant frequency between the system<br />

inductance and the capacitor bank is given by<br />

h o = Ssc<br />

Q<br />

where<br />

Ssc = the level <strong>of</strong> system short-circuit kVA at the point <strong>of</strong> connection <strong>of</strong> the capacitor<br />

Q = capacitor bank rating in kvar; and ho = the harmonic order <strong>of</strong> the natural<br />

frequency fo i.e. fo<br />

for a 50 Hz system, or fo<br />

for a 60 Hz system.<br />

50<br />

60<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L21<br />

© Schneider Electric - all rights reserved


L22<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

Harmonic<br />

generator<br />

Fig. L29 : Operation principle <strong>of</strong> active filter<br />

Ihar<br />

Ihar<br />

Harmonic<br />

generator<br />

Active<br />

filter<br />

Active<br />

filter<br />

Iact<br />

Hybride filter<br />

Fig. L30 : Operation principle <strong>of</strong> hybrid filter<br />

Is<br />

Iact<br />

Linear<br />

load<br />

Is<br />

Linear<br />

load<br />

9 The effects <strong>of</strong> harmonics<br />

For example: h o = Ssc<br />

Q may give a value for h o <strong>of</strong> 2.93 which shows that the<br />

natural frequency <strong>of</strong> the capacitor/system-inductance combination is close to the 3rd harmonic frequency <strong>of</strong> the system.<br />

f<br />

From ho<br />

= o it can be seen that fo = 50 ho = 50 x 2.93 = 146.5 Hz<br />

50<br />

The closer a natural frequency approaches one <strong>of</strong> the harmonics present on the<br />

system, the greater will be the (undesirable) effect. In the above example, strong<br />

resonant conditions with the 3rd harmonic component <strong>of</strong> a distorted wave would<br />

certainly occur.<br />

In such cases, steps are taken to change the natural frequency to a value which will<br />

not resonate with any <strong>of</strong> the harmonics known to be present. This is achieved by the<br />

addition <strong>of</strong> a harmonic-suppression inductor connected in series with the capacitor<br />

bank.<br />

On 50 Hz systems, these reactors are <strong>of</strong>ten adjusted to bring the resonant frequency<br />

<strong>of</strong> the combination, i.e. the capacitor bank + reactors to 190 Hz. The reactors are<br />

adjusted to 228 Hz for a 60 Hz system. These frequencies correspond to a value<br />

for h o <strong>of</strong> 3.8 for a 50 Hz system, i.e. approximately mid-way between the 3 rd and 5 th<br />

harmonics.<br />

In this arrangement, the presence <strong>of</strong> the reactor increases the fundamental<br />

frequency (50 Hz or 60 Hz) current by a small amount (7-8%) and therefore the<br />

voltage across the capacitor in the same proportion.<br />

This feature is taken into account, for example, by using capacitors which are<br />

<strong>design</strong>ed for 440 V operation on 400 V systems.<br />

Active filter (see Fig. L29)<br />

Active filters are based on power electronic technology. They are generally installed<br />

in parallel with the non linear load.<br />

Active filters analyse the harmonics drawn by the load and then inject the same<br />

harmonic current to the load with the appropriate phase. As a result, the harmonic<br />

currents are totally neutralised at the point considered. This means they no longer<br />

flow upstream and are no longer supplied by the source.<br />

A main advantage <strong>of</strong> active conditioners is that they continue to guarantee efficient<br />

harmonic compensation even when changes are made to the <strong>installation</strong>. They are<br />

also exceptionally easy to use as they feature:<br />

b Auto-configuration to harmonic loads whatever their order <strong>of</strong> magnitude<br />

b Elimination <strong>of</strong> overload risks<br />

b Compatibility with <strong>electrical</strong> generator sets<br />

b Connection to any point <strong>of</strong> the <strong>electrical</strong> network<br />

b Several conditioners can be used in the same <strong>installation</strong> to increase depollution<br />

efficiency (for example when a new machine is installed)<br />

Active filters may provide also power factor correction.<br />

Hybrid filter (see Fig. L30)<br />

This type <strong>of</strong> filter combines advantages <strong>of</strong> passive and active filter. One frequency<br />

can be filtered by passive filter and all the other frequencies are filtered by active<br />

filter.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

9 The effects <strong>of</strong> harmonics<br />

9.3 Choosing the optimum solution<br />

Figure L31 below shows the criteria that can be taken into account to select the<br />

most suitable technology depending on the application.<br />

Passive filter Active filter Hybrid filter<br />

Applications Industrial Tertiary Industrial<br />

… with total power <strong>of</strong> non greater than lower than greater than<br />

linear loads (variable speed 200 kVA 200 kVA 200 kVA<br />

drive, UPS, rectifier…)<br />

Power factor correction No<br />

Necessity <strong>of</strong> reducing the<br />

harmonic distorsion in<br />

voltage for sensitive loads<br />

Necessity <strong>of</strong> reducing<br />

the harmonic distorsion<br />

in current to avoid cable<br />

overload<br />

Necessity <strong>of</strong> being in No<br />

accordance with strict<br />

limits <strong>of</strong> harmonic<br />

rejected<br />

Fig. L31 : Selection <strong>of</strong> the most suitable technology depending on the application<br />

For passive filter, a choice is made from the following parameters:<br />

b Gh = the sum <strong>of</strong> the kVA ratings <strong>of</strong> all harmonic-generating devices (static<br />

converters, inverters, speed controllers, etc.) connected to the busbars from which<br />

the capacitor bank is supplied. If the ratings <strong>of</strong> some <strong>of</strong> these devices are quoted in<br />

kW only, assume an average power factor <strong>of</strong> 0.7 to obtain the kVA ratings<br />

b Ssc = the 3-phase short-circuit level in kVA at the terminals <strong>of</strong> the capacitor bank<br />

b Sn = the sum <strong>of</strong> the kVA ratings <strong>of</strong> all transformers supplying (i.e. directly<br />

connected to) the system level <strong>of</strong> which the busbars form a part<br />

If a number <strong>of</strong> transformers are operating in parallel, the removal from service <strong>of</strong> one<br />

or more, will significantly change the values <strong>of</strong> Ssc and Sn. From these parameters,<br />

a choice <strong>of</strong> capacitor specification which will ensure an acceptable level <strong>of</strong> operation<br />

with the system harmonic voltages and currents, can be made, by reference to<br />

Figure L32.<br />

b <strong>General</strong> rule valid for any size <strong>of</strong> transformer<br />

Ssc<br />

Gh i<br />

120<br />

Ssc Ssc<br />

i Gh i<br />

120 70<br />

Ssc<br />

Gh ><br />

70<br />

Standard capacitors Capacitor voltage rating Capacitor voltage rating<br />

increased by 10% increased by 10%<br />

(except 230 V units) + harmonic-suppression reactor<br />

b Simplified rule if transformer(s) rating Sn y 2 MVA<br />

Gh i 0.15 Sn 0.15 Sn < Gh i 0.25 Sn 0.25 Sn < Gh i 0.60 Sn Gh > 0.60 Sn<br />

Standard capacitors Capacitor voltage rating Capacitor voltage rating Filters<br />

increased by 10% increased by 10%<br />

(except 230 V units) + harmonic suppression<br />

reactor<br />

Fig. L32 : Choice <strong>of</strong> solutions for limiting harmonics associated with a LV capacitor bank supplied<br />

via transformer(s)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L23<br />

© Schneider Electric - all rights reserved


L24<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

(1) Merlin-Gerin <strong>design</strong>ation<br />

10 Implementation <strong>of</strong> capacitor<br />

banks<br />

10.1 Capacitor elements<br />

Technology<br />

The capacitors are dry-type units (i.e. are not impregnated by liquid dielectric)<br />

comprising metallized polypropylene self-healing film in the form <strong>of</strong> a two-film roll.<br />

They are protected by a high-quality system (overpressure disconnector used with<br />

a high breaking capacity fuse) which switches <strong>of</strong>f the capacitor if an internal fault<br />

occurs.<br />

The protection scheme operates as follows:<br />

b A short-circuit through the dielectric will blow the fuse<br />

b Current levels greater than normal, but insufficient to blow the fuse sometimes<br />

occur, e.g. due to a microscopic flow in the dielectric film. Such “faults” <strong>of</strong>ten re-seal<br />

due to local heating caused by the leakage current, i.e. the units are said to be “selfhealing”<br />

b If the leakage current persists, the defect may develop into a short-circuit, and the<br />

fuse will blow<br />

b Gas produced by vaporizing <strong>of</strong> the metallisation at the faulty location will gradually<br />

build up a pressure within the plastic container, and will eventually operate a<br />

pressure-sensitive device to short-circuit the unit, thereby causing the fuse to blow<br />

Capacitors are made <strong>of</strong> insulating material providing them with double insulation and<br />

avoiding the need for a ground connection (see Fig. L33).<br />

a)<br />

b)<br />

HRC fuse<br />

Discharge<br />

resistor<br />

Metallic<br />

disc<br />

Overpressure disconnect<br />

device<br />

Electrical characteristics<br />

Standard IEC 60439-1, NFC 54-104, VDE 0560 CSA<br />

Standards, UL tests<br />

Operating range Rated voltage 400 V<br />

Rated frequency 50 Hz<br />

Capacitance tolerance - 5% to + 10%<br />

Temperature range Maximum temperature 55 °C<br />

(up to 65 kvar) Average temperature over<br />

24 h<br />

45 °C<br />

Average annual<br />

temperature<br />

35 °C<br />

Minimum temperature - 25 °C<br />

Insulation level 50 Hz 1 min withstand voltage : 6 kV<br />

1.2/50 μs impulse withstand voltage : 25 kV<br />

Permissible current overload Classic range (1) Comfort range (1)<br />

30% 50%<br />

Permissible voltage overload 10% 20%<br />

Fig. L33 : Capacitor element, (a) cross-section, (b) <strong>electrical</strong> characteristics<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


L - Power factor correction and<br />

harmonic filtering<br />

(1) Merlin-Gerin <strong>design</strong>ation<br />

(2) Harmony capacitor banks are equipped with a harmonic<br />

suppression reactor.<br />

10 Implementation <strong>of</strong> capacitor<br />

banks<br />

10.2 Choice <strong>of</strong> protection, control devices and<br />

connecting cables<br />

The choice <strong>of</strong> upstream cables and protection and control devices depends on the<br />

current loading.<br />

For capacitors, the current is a function <strong>of</strong>:<br />

b The applied voltage and its harmonics<br />

b The capacitance value<br />

The nominal current In <strong>of</strong> a 3-phase capacitor bank is equal to:<br />

In =<br />

Un 3<br />

Q<br />

with:<br />

v Q: kvar rating<br />

v Un: Phase-to-phase voltage (kV)<br />

The permitted range <strong>of</strong> applied voltage at fundamental frequency, plus harmonic<br />

components, together with manufacturing tolerances <strong>of</strong> actual capacitance (for a<br />

declared nominal value) can result in a 50% increase above the calculated value <strong>of</strong><br />

current. Approximately 30% <strong>of</strong> this increase is due to the voltage increases, while a<br />

further 15% is due to the range <strong>of</strong> manufacturing tolerances, so that<br />

1.3 x 1.15 = 1.5<br />

All components carrying the capacitor current therefore, must be adequate to cover<br />

this “worst-case” condition, in an ambient temperature <strong>of</strong> 50 °C maximum. In the<br />

case where temperatures higher than 50 °C occur in enclosures, etc. derating <strong>of</strong> the<br />

components will be necessary.<br />

Protection<br />

The size <strong>of</strong> the circuit-breaker can be chosen in order to allow the setting <strong>of</strong> long<br />

time delay at:<br />

b 1.36 x In for Classic range (1)<br />

b 1.50 x In for Comfort range (1)<br />

b 1.12 x In for Harmony range (1) (tuned at 2.7 f) (2)<br />

b 1.19 x In for Harmony range (1) (tuned at 3.8 f)<br />

b 1.31 x In for Harmony range (1) (tuned at 4.3 f)<br />

Short time delay setting (short-circuit protection) must be insensitive to inrush<br />

current. The setting will be 10 x In for Classic, Comfort and Harmony range (1) .<br />

Example 1<br />

50 kvar – 400V – 50 Hz – Classic range<br />

50, 000<br />

In = = 72 A<br />

( 400 x 1.732)<br />

Long time delay setting: 1.36 x 72 = 98 A<br />

Short time delay setting: 10 x In = 720 A<br />

Example 2<br />

50 kvar – 400V – 50 Hz – Harmony range (tuned at 4.3 f)<br />

In = 72 A<br />

Long time delay setting: 1.31 x 72 = 94 A<br />

Short time delay setting: 10 x In = 720 A<br />

Upstream cables<br />

Figure L34 next page gives the minimum cross section area <strong>of</strong> the upstream cable<br />

for Rectiphase capacitors.<br />

Cables for control<br />

The minimum cross section area <strong>of</strong> these cables will be 1.5 mm 2 for 230 V.<br />

For the secondary side <strong>of</strong> the transformer, the recommended cross section<br />

area is u 2.5 mm 2 .<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

L25<br />

© Schneider Electric - all rights reserved


L26<br />

© Schneider Electric - all rights reserved<br />

L - Power factor correction and<br />

harmonic filtering<br />

(1) Minimum cross-section not allowing for any correction<br />

factors (<strong>installation</strong> mode, temperature, etc.). The calculations<br />

were made for single-pole cables laid in open air at 30 °C.<br />

10 Implementation <strong>of</strong> capacitor<br />

banks<br />

Fig L34 : Cross-section <strong>of</strong> cables connecting medium and high power capacitor banks (1)<br />

Voltage transients<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Bank power Copper Aluminium<br />

(kvar) cross- section cross- section<br />

230 V 400 V (mm 2 ) (mm 2 )<br />

5 10 2.5 16<br />

10 20 4 16<br />

15 30 6 16<br />

20 40 10 16<br />

25 50 16 25<br />

30 60 25 35<br />

40 80 35 50<br />

50 100 50 70<br />

60 120 70 95<br />

70 140 95 120<br />

90-100 180 120 185<br />

200 150 240<br />

120 240 185 2 x 95<br />

150 250 240 2 x 120<br />

300 2 x 95 2 x 150<br />

180-210 360 2 x 120 2 x 185<br />

245 420 2 x 150 2 x 240<br />

280 480 2 x 185 2 x 300<br />

315 540 2 x 240 3 x 185<br />

350 600 2 x 300 3 x 240<br />

385 660 3 x 150 3 x 240<br />

420 720 3 x 185 3 x 300<br />

High-frequency voltage and current transients occur when switching a capacitor<br />

bank into service. The maximum voltage peak does not exceed (in the absence <strong>of</strong><br />

harmonics) twice the peak value <strong>of</strong> the rated voltage when switching uncharged<br />

capacitors.<br />

In the case <strong>of</strong> a capacitor being already charged at the instant <strong>of</strong> switch closure,<br />

however, the voltage transient can reach a maximum value approaching 3 times the<br />

normal rated peak value.<br />

This maximum condition occurs only if:<br />

b The existing voltage at the capacitor is equal to the peak value <strong>of</strong> rated voltage,<br />

and<br />

b The switch contacts close at the instant <strong>of</strong> peak supply voltage, and<br />

b The polarity <strong>of</strong> the power-supply voltage is opposite to that <strong>of</strong> the charged<br />

capacitor<br />

In such a situation, the current transient will be at its maximum possible value, viz:<br />

Twice that <strong>of</strong> its maximum when closing on to an initially uncharged capacitor, as<br />

previously noted.<br />

For any other values <strong>of</strong> voltage and polarity on the pre-charged capacitor, the<br />

transient peaks <strong>of</strong> voltage and current will be less than those mentioned above.<br />

In the particular case <strong>of</strong> peak rated voltage on the capacitor having the same polarity<br />

as that <strong>of</strong> the supply voltage, and closing the switch at the instant <strong>of</strong> supply-voltage<br />

peak, there would be no voltage or current transients.<br />

Where automatic switching <strong>of</strong> stepped banks <strong>of</strong> capacitors is considered, therefore,<br />

care must be taken to ensure that a section <strong>of</strong> capacitors about to be energized is<br />

fully discharged.<br />

The discharge delay time may be shortened, if necessary, by using discharge<br />

resistors <strong>of</strong> a lower resistance value.


2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

<strong>Chapter</strong> M<br />

Harmonic management<br />

Contents<br />

The problem: why is it necessary to detect M2<br />

and eliminate harmonics?<br />

Standards M3<br />

<strong>General</strong> M4<br />

Main effects <strong>of</strong> harmonics in <strong>installation</strong>s M6<br />

4.1 Resonance M6<br />

4.2 Increased losses M6<br />

4.3 Overloads on equipment M7<br />

4.4 Disturbances affecting sensitive loads M9<br />

4.5 Economic impact M10<br />

Essential indicators <strong>of</strong> harmonic distortion M<br />

and measurement principles<br />

5.1 Power factor M11<br />

5.2 Crest factor M11<br />

5.3 Power values and harmonics M11<br />

5.4 Harmonic spectrum and harmonic distortion M12<br />

5.5 Total harmonic distortion (THD) M12<br />

5.6 Usefulness <strong>of</strong> the various indicators M13<br />

Measuring the indicators M 4<br />

6.1 Devices used to measure the indicators M14<br />

6.2 Procedures for harmonic analysis <strong>of</strong> distribution networks M14<br />

6.3 Keeping a close eye on harmonics M15<br />

Detection devices M 6<br />

Solutions to attenuate harmonics M 7<br />

8.1 Basic solutions M17<br />

8.2 Harmonic filtering M18<br />

8.3 The method M20<br />

8.4 Specific products M20<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

M2<br />

M - Harmonic management<br />

The problem: why is it necessary<br />

to detect and eliminate harmonics?<br />

Disturbances caused by harmonics<br />

Harmonics flowing in distribution networks downgrade the quality <strong>of</strong> <strong>electrical</strong> power.<br />

This can have a number <strong>of</strong> negative effects:<br />

b Overloads on distribution networks due to the increase in rms current<br />

b Overloads in neutral conductors due to the cumulative increase in third-order<br />

harmonics created by single-phase loads<br />

b Overloads, vibration and premature ageing <strong>of</strong> generators, transformers and motors<br />

as well as increased transformer hum<br />

b Overloads and premature ageing <strong>of</strong> power-factor correction capacitors<br />

b Distortion <strong>of</strong> the supply voltage that can disturb sensitive loads<br />

b Disturbances in communication networks and on telephone lines<br />

Economic impact <strong>of</strong> disturbances<br />

Harmonics have a major economic impact:<br />

b Premature ageing <strong>of</strong> equipment means it must be replaced sooner unless<br />

oversized right from the start<br />

b Overloads on the distribution network can require higher subscribed power levels<br />

and increase losses<br />

b Distortion <strong>of</strong> current waveforms provokes nuisance tripping that can stop<br />

production<br />

Increasingly serious consequences<br />

Only ten years ago, harmonics were not yet considered a real problem because<br />

their effects on distribution networks were generally minor. However, the massive<br />

introduction <strong>of</strong> power electronics in equipment has made the phenomenon far more<br />

serious in all sectors <strong>of</strong> economic activity.<br />

In addition, the equipment causing the harmonics is <strong>of</strong>ten vital to the company or<br />

organisation.<br />

Which harmonics must be measured and eliminated?<br />

The most frequently encountered harmonics in three-phase distribution networks<br />

are the odd orders. Harmonic amplitudes normally decrease as the frequency<br />

increases. Above order 50, harmonics are negligible and measurements are no<br />

longer meaningful. Sufficiently accurate measurements are obtained by measuring<br />

harmonics up to order 30.<br />

Utilities monitor harmonic orders 3, 5, 7, 11 and 13. <strong>General</strong>ly speaking, harmonic<br />

conditioning <strong>of</strong> the lowest orders (up to 13) is sufficient. More comprehensive<br />

conditioning takes into account harmonic orders up to 25.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

Fig. M1 : Maximum permissible harmonic levels<br />

2 Standards<br />

Harmonic emissions are subject to various standards and regulations:<br />

b Compatibility standards for distribution networks<br />

b Emissions standards applying to the equipment causing harmonics<br />

b Recommendations issued by utilities and applicable to <strong>installation</strong>s<br />

In view <strong>of</strong> rapidly attenuating the effects <strong>of</strong> harmonics, a triple system <strong>of</strong> standards<br />

and regulations is currently in force based on the documents listed below.<br />

Standards governing compatibility between distribution networks and<br />

products<br />

These standards determine the necessary compatibility between distribution<br />

networks and products:<br />

b The harmonics caused by a device must not disturb the distribution network<br />

beyond certain limits<br />

b Each device must be capable <strong>of</strong> operating normally in the presence <strong>of</strong><br />

disturbances up to specific levels<br />

b Standard IEC 61000-2-2 for public low-voltage power supply systems<br />

b Standard IEC 61000-2-4 for LV and MV industrial <strong>installation</strong>s<br />

Standards governing the quality <strong>of</strong> distribution networks<br />

b Standard EN 50160 stipulates the characteristics <strong>of</strong> electricity supplied by public<br />

distribution networks<br />

b Standard IEEE 519 presents a joint approach between Utilities and customers<br />

to limit the impact <strong>of</strong> non-linear loads. What is more, Utilities encourage preventive<br />

action in view <strong>of</strong> reducing the deterioration <strong>of</strong> power quality, temperature rise and the<br />

reduction <strong>of</strong> power factor. They will be increasingly inclined to charge customers for<br />

major sources <strong>of</strong> harmonics<br />

Standards governing equipment<br />

b Standard IEC 61000-3-2 or EN 61000-3-2 for low-voltage equipment with rated<br />

current under 16 A<br />

b Standard IEC 61000-3-12 for low-voltage equipment with rated current higher than<br />

16 A and lower than 75 A<br />

Maximum permissible harmonic levels<br />

International studies have collected data resulting in an estimation <strong>of</strong> typical<br />

harmonic contents <strong>of</strong>ten encountered in <strong>electrical</strong> distribution networks. Figure M1<br />

presents the levels that, in the opinion <strong>of</strong> many utilities, should not be exceeded.<br />

Odd harmonic orders Odd harmonic orders Even harmonic orders<br />

non-multiples <strong>of</strong> multiples <strong>of</strong><br />

Order h LV MV EMV Order h LV MV EMV Order h LV MV EMV<br />

5 6 6 2 3 5 2.5 1.5 2 2 1.5 1.5<br />

7 5 5 2 9 1.5 1.5 1 4 1 1 1<br />

11 3.5 3.5 1.5 15 0.3 0.3 0.3 6 0.5 0.5 0.5<br />

13 3 3 1.5 21 0.2 0.2 0.2 8 0.5 0.2 0.2<br />

17 2 2 1 > 21 0.2 0.2 0.2 10 0.5 0.2 0.2<br />

19 1.5 1.5 1 12 0.2 0.2 0.2<br />

23 1.5 1 0.7 > 12 0.2 0.2 0.2<br />

25 1.5 1 0.7<br />

> 25 0.2 0.2 0.1<br />

+ 25/h + 25/h + 25/h<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

M<br />

M - Harmonic management<br />

3 <strong>General</strong><br />

The presence <strong>of</strong> harmonics indicates a distorted current or voltage wave. The<br />

distortion <strong>of</strong> the current or voltage wave means that the distribution <strong>of</strong> <strong>electrical</strong><br />

energy is disturbed and power quality is not optimum.<br />

Harmonic currents are caused by non-linear loads connected to the distribution<br />

network. The flow <strong>of</strong> harmonic currents causes harmonic voltages via distributionnetwork<br />

impedances and consequently distortion <strong>of</strong> the supply voltage.<br />

Origin <strong>of</strong> harmonics<br />

Devices and systems that cause harmonics are present in all sectors, i.e. industrial,<br />

commercial and residential. Harmonics are caused by non-linear loads (i.e. loads<br />

that draw current with a waveform that is not the same as that <strong>of</strong> the supply voltage).<br />

Examples <strong>of</strong> non-linear loads are:<br />

b Industrial equipment (welding machines, arc furnaces, induction furnaces,<br />

rectifiers)<br />

b Variable-speed drives for asynchronous or DC motors<br />

b UPSs<br />

b Office equipment (computers, photocopy machines, fax machines, etc.)<br />

b Home appliances (television sets, micro-wave ovens, fluorescent lighting)<br />

b Certain devices involving magnetic saturation (transformers)<br />

Disturbances caused by non-linear loads: harmonic current and voltage<br />

Non-linear loads draw harmonic currents that flow in the distribution network.<br />

Harmonic voltages are caused by the flow <strong>of</strong> harmonic currents through the<br />

impedances <strong>of</strong> the supply circuits (transformer and distribution network for situations<br />

similar to that shown in Figure M2).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

A<br />

Z h B<br />

I h<br />

Non-linear<br />

load<br />

Fig. M2 : Single-line diagram showing the impedance <strong>of</strong> the supply circuit for a harmonic <strong>of</strong> order h<br />

The reactance <strong>of</strong> a conductor increases as a function <strong>of</strong> the frequency <strong>of</strong> the current<br />

flowing through the conductor. For each harmonic current (order h), there is therefore<br />

an impedance Zh in the supply circuit.<br />

When the harmonic current <strong>of</strong> order h flows through impedance Zh, it creates a<br />

harmonic voltage Uh, where Uh = Zh x Ih (Ohm law). The voltage at point B is<br />

therefore distorted. All devices supplied via point B receive a distorted voltage.<br />

For a given harmonic current, the distortion is proportional to the impedance in the<br />

distribution network.<br />

Flow <strong>of</strong> harmonic currents in distribution networks<br />

The non-linear loads can be considered to reinject the harmonic currents upstream<br />

into the distribution network, toward the source.<br />

Figures M3 and M next page show an <strong>installation</strong> disturbed by harmonics. Figure<br />

M3 shows the flow <strong>of</strong> the current at 50 Hz in the <strong>installation</strong> and Figure M4 shows<br />

the harmonic current (order h).


M - Harmonic management<br />

3 <strong>General</strong><br />

Fig. M3 : Installation supplying a non-linear load, where only the phenomena concerning the<br />

50 Hz frequency (fundamental frequency) are shown<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Z h<br />

Z l<br />

I 50 Hz<br />

Non-linear<br />

load<br />

Fig. M4 : Same <strong>installation</strong>, where only the phenomena concerning the frequency <strong>of</strong> harmonic<br />

order h are shown<br />

V h<br />

I h<br />

Non-linear<br />

load<br />

V h = Harmonic voltage<br />

= Z h x I h<br />

Supply <strong>of</strong> the non-linear load creates the flow <strong>of</strong> a current I 50Hz (shown in<br />

figure M3), to which is added each <strong>of</strong> the harmonic currents Ih (shown in figure M4),<br />

corresponding to each harmonic order h.<br />

Still considering that the loads reinject harmonic current upstream into the<br />

distribution network, it is possible to create a diagram showing the harmonic currents<br />

in the network (see Fig. M ).<br />

Backup power<br />

supply<br />

G<br />

Power-factor<br />

correction<br />

MV/LV<br />

Harmonic<br />

disturbances to<br />

distribution network<br />

and other users<br />

A<br />

Ih a<br />

Ih b<br />

Ih d<br />

Ih e<br />

(do not create<br />

harmonics)<br />

Rectifier<br />

Arc furnace<br />

Welding machine<br />

Variable-speed drive<br />

Fluorescent or<br />

discharge lamps<br />

Devices drawing rectified<br />

current (televisions,<br />

computer hardware, etc.)<br />

Linear loads<br />

Note in the diagram that though certain loads create harmonic currents in the distribution<br />

network, other loads can absorb the harmonic currents.<br />

Fig. M5 : Flow <strong>of</strong> harmonic currents in a distribution network<br />

Harmonics have major economic effects in <strong>installation</strong>s:<br />

b Increases in energy costs<br />

b Premature ageing <strong>of</strong> equipment<br />

b Production losses<br />

M<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

M<br />

M - Harmonic management<br />

I h<br />

Non-linear<br />

load<br />

C<br />

Capacitor<br />

bank<br />

Fig. M6 : Diagram <strong>of</strong> an <strong>installation</strong><br />

Ls C R Ih<br />

Z<br />

Linear<br />

load<br />

Fig. M7 : Equivalent diagram <strong>of</strong> the <strong>installation</strong> shown in<br />

Figure M6<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

4.1 Resonance<br />

The simultaneous use <strong>of</strong> capacitive and inductive devices in distribution networks<br />

results in parallel or series resonance manifested by very high or very low<br />

impedance values respectively. The variations in impedance modify the current and<br />

voltage in the distribution network. Here, only parallel resonance phenomena, the<br />

most common, will be discussed.<br />

Consider the following simplified diagram (see Fig. M ) representing an <strong>installation</strong><br />

made up <strong>of</strong>:<br />

b A supply transformer<br />

b Linear loads<br />

b Non-linear loads drawing harmonic currents<br />

b Power factor correction capacitors<br />

For harmonic analysis, the equivalent diagram (see Fig. M7) is shown below.<br />

Impedance Z is calculated by:<br />

jLs<br />

Z =<br />

1-LsC 2<br />

ω<br />

ω<br />

neglecting R and where:<br />

Ls = Supply inductance (upstream network + transformer + line)<br />

C = Capacitance <strong>of</strong> the power factor correction capacitors<br />

R = Resistance <strong>of</strong> the linear loads<br />

Ih = Harmonic current<br />

Resonance occurs when the denominator 1-LsCw 2 tends toward zero. The<br />

corresponding frequency is called the resonance frequency <strong>of</strong> the circuit. At that<br />

frequency, impedance is at its maximum and high amounts <strong>of</strong> harmonic voltages<br />

appear with the resulting major distortion in the voltage. The voltage distortion is<br />

accompanied, in the Ls+C circuit, by the flow <strong>of</strong> harmonic currents greater than<br />

those drawn by the loads.<br />

The distribution network and the power factor correction capacitors are subjected to<br />

high harmonic currents and the resulting risk <strong>of</strong> overloads. To avoid resonance, antiharmonic<br />

coils can be installed in series with the capacitors.<br />

4.2 Increased losses<br />

Losses in conductors<br />

The active power transmitted to a load is a function <strong>of</strong> the fundamental component I1<br />

<strong>of</strong> the current.<br />

When the current drawn by the load contains harmonics, the rms value <strong>of</strong> the<br />

current, Irms, is greater than the fundamental I1.<br />

The definition <strong>of</strong> THD being:<br />

THD =<br />

2<br />

⎛ Irms⎞<br />

⎜ ⎟ −1<br />

⎝ I1<br />

⎠<br />

it may be deduced that: Irms = I1<br />

+ THD 2<br />

1<br />

Figure M8 (next page) shows, as a function <strong>of</strong> the harmonic distortion:<br />

b The increase in the rms current Irms for a load drawing a given fundamental<br />

current<br />

b The increase in Joule losses, not taking into account the skin effect<br />

(The reference point in the graph is 1 for Irms and Joules losses, the case when<br />

there are no harmonics)<br />

The harmonic currents provoke an increase in the Joule losses in all conductors in<br />

which they flow and additional temperature rise in transformers, devices, cables, etc.<br />

Losses in asynchronous machines<br />

The harmonic voltages (order h) supplied to asynchronous machines provoke in the<br />

rotor the flow <strong>of</strong> currents with frequencies higher than 50 Hz that are the cause <strong>of</strong><br />

additional losses.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

2.2<br />

2<br />

1.8<br />

1.6<br />

1.4<br />

1.2<br />

1<br />

0.8<br />

0 20 40 60 80 100 120<br />

Joules losses<br />

Irms<br />

Fig. M8 : Increase in rms current and Joule losses as a function <strong>of</strong> the THD<br />

Orders <strong>of</strong> magnitude<br />

b A virtually rectangular supply voltage provokes a 20% increase in losses<br />

b A supply voltage with harmonics u5 = 8% (<strong>of</strong> U1, the fundamental voltage),<br />

u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic distortion THDu equal to 10%,<br />

results in additional losses <strong>of</strong> 6%<br />

Losses in transformers<br />

Harmonic currents flowing in transformers provoke an increase in the “copper”<br />

losses due to the Joule effect and increased “iron” losses due to eddy currents. The<br />

harmonic voltages are responsible for “iron” losses due to hysteresis.<br />

It is generally considered that losses in windings increase as the square <strong>of</strong> the THDi<br />

and that core losses increase linearly with the THDu.<br />

In utility-distribution transformers, where distortion levels are limited, losses increase<br />

between 10 and 15%.<br />

Losses in capacitors<br />

The harmonic voltages applied to capacitors provoke the flow <strong>of</strong> currents<br />

proportional to the frequency <strong>of</strong> the harmonics. These currents cause additional<br />

losses.<br />

Example<br />

A supply voltage has the following harmonics:<br />

Fundamental voltage U1, harmonic voltages u5 = 8% (<strong>of</strong> U1), u7 = 5%, u11 = 3%,<br />

u13 = 1%, i.e. total harmonic distortion THDu equal to 10%. The amperage <strong>of</strong> the<br />

current is multiplied by 1.19. Joule losses are multiplied by 1.19 2 , i.e. 1.4.<br />

4.3 Overloads on equipment<br />

Generators<br />

Generators supplying non-linear loads must be derated due to the additional losses<br />

caused by harmonic currents.<br />

The level <strong>of</strong> derating is approximately 10% for a generator where the overall load<br />

is made up <strong>of</strong> 30% <strong>of</strong> non-linear loads. It is therefore necessary to oversize the<br />

generator.<br />

Uninterruptible power systems (UPS)<br />

The current drawn by computer systems has a very high crest factor. A UPS sized<br />

taking into account exclusively the rms current may not be capable <strong>of</strong> supplying the<br />

necessary peak current and may be overloaded.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

THD<br />

(%)<br />

M7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

M8<br />

M - Harmonic management<br />

(1) In fact, the current waveform is similar to a rectangular<br />

waveform. This is the case for all current rectifiers (three-phase<br />

rectifiers, induction furnaces).<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

Transformers<br />

b The curve presented below (see Fig. M9) shows the typical derating required for a<br />

transformer supplying electronic loads<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Example<br />

If the transformer supplies an overall load comprising 40% <strong>of</strong> electronic loads, it must<br />

be derated by 40%.<br />

b Standard UTE C15-112 provides a derating factor for transformers as a function <strong>of</strong><br />

the harmonic currents.<br />

k =<br />

kVA<br />

(%)<br />

0<br />

Th = Ih<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1<br />

⎛ 40 ⎞<br />

1.6 2<br />

1+ 0.1 ⎜ ∑h Th ⎟<br />

⎝ h= 2 ⎠<br />

I<br />

1<br />

Typical values:<br />

b Current with a rectangular waveform (1/h spectrum (1) ): k = 0.86<br />

b Frequency-converter current (THD ≈ 50%): k = 0.80<br />

Asynchronous machines<br />

Standard IEC 60892 defines a weighted harmonic factor (Harmonic voltage factor)<br />

for which the equation and maximum value are provided below.<br />

HVF =<br />

0 20 40 60 80 100<br />

Fig. M9 : Derating required for a transformer supplying electronic loads<br />

13 U h<br />

∑ 0.02<br />

2<br />

h i<br />

h= 2<br />

Example<br />

A supply voltage has a fundamental voltage U1 and harmonic voltages u3 = 2% <strong>of</strong><br />

U1, u5 = 3%, u7 = 1%. The THDu is 3.7% and the MVF is 0.018. The MVF value<br />

is very close to the maximum value above which the machine must be derated.<br />

Practically speaking, for supply to the machine, a THDu <strong>of</strong> 10% must not be<br />

exceeded.<br />

Capacitors<br />

%<br />

Electronic<br />

load<br />

According to IEC 60831-1 standard, the rms current flowing in the capacitors must<br />

not exceed 1.3 times the rated current.<br />

Using the example mentioned above, the fundamental voltage U1, harmonic voltages<br />

voltages u5 = 8% u5 (<strong>of</strong> = U1), 8% u7 (<strong>of</strong> = U1), 5%, u7 u11 = 5%, = 3%, u11 u13 = 3%, = 1%, u13 i.e. = total 1%, harmonic i.e. total harmonic<br />

distortion THDu equal to 10%, the result is Irms<br />

= 1. 19,<br />

, at the rated voltage. For a<br />

I1<br />

, at the rated voltage. For a<br />

voltage equal equal to to 1.1 1.1 times the the rated voltage, the current limit Irms<br />

= 1. 3 is reached<br />

and it is necessary to resize the capacitors.<br />

I1


M - Harmonic management<br />

I r<br />

I s<br />

I t<br />

I n<br />

Load<br />

Load<br />

Load<br />

Fig. M10 : Flow <strong>of</strong> currents in the various conductors<br />

connected to a three-phase source<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

Neutral conductors<br />

Consider a system made up <strong>of</strong> a balanced three-phase source and three identical<br />

single-phase loads connected between the phases and the neutral (see Fig. M10).<br />

Figure M11 shows an example <strong>of</strong> the currents flowing in the three phases and the<br />

resulting current in the neutral conductor.<br />

In this example, the current in the neutral conductor has an rms value that is higher<br />

than the rms value <strong>of</strong> the current in a phase by a factor equal to the square root <strong>of</strong> 3.<br />

The neutral conductor must therefore be sized accordingly.<br />

Ir<br />

Is<br />

It<br />

In<br />

(A)<br />

Fig. M11 : Example <strong>of</strong> the currents flowing in the various conductors connected to a three-phase<br />

load (In = Ir + Is + It)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0<br />

20 40<br />

4.4 Disturbances affecting sensitive loads<br />

Effects <strong>of</strong> distortion in the supply voltage<br />

t<br />

t<br />

t<br />

t<br />

t (ms)<br />

Distortion <strong>of</strong> the supply voltage can disturb the operation <strong>of</strong> sensitive devices:<br />

b Regulation devices (temperature)<br />

b Computer hardware<br />

b Control and monitoring devices (protection relays)<br />

Distortion <strong>of</strong> telephone signals<br />

Harmonics cause disturbances in control circuits (low current levels). The level <strong>of</strong><br />

distortion depends on the distance that the power and control cables run in parallel,<br />

the distance between the cables and the frequency <strong>of</strong> the harmonics.<br />

M9<br />

© Schneider Electric - all rights reserved


M10<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

4.5 Economic impact<br />

Energy losses<br />

Harmonics cause additional losses (Joule effect) in conductors and equipment.<br />

Higher subscription costs<br />

The presence <strong>of</strong> harmonic currents can require a higher subscribed power level and<br />

consequently higher costs.<br />

What is more, utilities will be increasingly inclined to charge customers for major<br />

sources <strong>of</strong> harmonics.<br />

Oversizing <strong>of</strong> equipment<br />

b Derating <strong>of</strong> power sources (generators, transformers and UPSs) means they must<br />

be oversized<br />

b Conductors must be sized taking into account the flow <strong>of</strong> harmonic currents.<br />

In addition, due the the skin effect, the resistance <strong>of</strong> these conductors increases<br />

with frequency. To avoid excessive losses due to the Joule effect, it is necessary to<br />

oversize conductors<br />

b Flow <strong>of</strong> harmonics in the neutral conductor means that it must be oversized as well<br />

Reduced service life <strong>of</strong> equipment<br />

When the level <strong>of</strong> distortion in the supply voltage approaches 10%, the duration<br />

<strong>of</strong> the service life <strong>of</strong> equipment is significantly reduced. The reduction has been<br />

estimated at:<br />

b 32.5% for single-phase machines<br />

b 18% for three-phase machines<br />

b 5% for transformers<br />

To maintain the service lives corresponding to the rated load, equipment must be<br />

oversized.<br />

Nuisance tripping and <strong>installation</strong> shutdown<br />

Circuit-breakers in the <strong>installation</strong> are subjected to current peaks caused by<br />

harmonics.<br />

These current peaks cause nuisance tripping with the resulting production losses, as<br />

well as the costs corresponding to the time required to start the <strong>installation</strong> up again.<br />

Examples<br />

Given the economic consequences for the <strong>installation</strong>s mentioned below, it was<br />

necessary to install harmonic filters.<br />

Computer centre for an insurance company<br />

In this centre, nuisance tripping <strong>of</strong> a circuit-breaker was calculated to have cost<br />

100 k€ per hour <strong>of</strong> down time.<br />

Pharmaceutical laboratory<br />

Harmonics caused the failure <strong>of</strong> a generator set and the interruption <strong>of</strong> a longduration<br />

test on a new medication. The consequences were a loss estimated at<br />

17 M€.<br />

Metallurgy factory<br />

A set <strong>of</strong> induction furnaces caused the overload and destruction <strong>of</strong> three<br />

transformers ranging from 1500 to 2500 kVA over a single year. The cost <strong>of</strong> the<br />

interruptions in production were estimated at 20 k€ per hour.<br />

Factory producing garden furniture<br />

The failure <strong>of</strong> variable-speed drives resulted in production shutdowns estimated at<br />

10 k€ per hour.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

5 Essential indicators <strong>of</strong> harmonic<br />

distortion and measurement<br />

principles<br />

A number <strong>of</strong> indicators are used to quantify and evaluate the harmonic distortion<br />

in current and voltage waveforms, namely:<br />

b Power factor<br />

b Crest factor<br />

b Distortion power<br />

b Harmonic spectrum<br />

b Harmonic-distortion values<br />

These indicators are indispensable in determining any necessary corrective action.<br />

5.1 Power factor<br />

Definition<br />

The power factor PF is the ratio between the active power P and the apparent<br />

power S.<br />

PF P<br />

=<br />

S<br />

Among electricians, there is <strong>of</strong>ten confusion with:<br />

P1<br />

cos<br />

ϕ =<br />

S1<br />

Where<br />

Where<br />

P1 = active power <strong>of</strong> the fundamental<br />

S1 = apparent power <strong>of</strong> the fundamental<br />

The cos ϕ concerns exclusively the fundamental frequency and therefore differs<br />

from the power factor PF when there are harmonics in the <strong>installation</strong>.<br />

Interpreting the power factor<br />

An initial indication that there are significant amounts <strong>of</strong> harmonics is a measured<br />

power factor PF that is different (lower) than the measured cos ϕ.<br />

5.2 Crest factor<br />

Definition<br />

The crest factor is the ratio between the value <strong>of</strong> the peak current or voltage (Im or<br />

Um) and its rms value.<br />

b For a sinusoidal signal, the crest factor is therefore equal to 2.<br />

b For a non-sinusoidal signal, the crest factor can be either greater than or less<br />

than 2.<br />

In the latter case, the crest factor signals divergent peak values with respect to the<br />

rms value.<br />

Interpretation <strong>of</strong> the crest factor<br />

The typical crest factor for the current drawn by non-linear loads is much higher<br />

than 2. It is generally between 1.5 and 2 and can even reach 5 in critical cases.<br />

A high crest factor signals high transient overcurrents which, when detected by<br />

protection devices, can cause nuisance tripping.<br />

5.3 Power values and harmonics<br />

Active power<br />

The active power P <strong>of</strong> a signal comprising harmonics is the sum <strong>of</strong> the active<br />

powers resulting from the currents and voltages <strong>of</strong> the same order.<br />

Reactive power<br />

Reactive power is defined exclusively in terms <strong>of</strong> the fundamental, i.e.<br />

Q = U1 x I1 x sinϕ1 Distortion power<br />

When harmonics are present, the distortion power D is defined as<br />

D = (S 2 - P 2 - Q 2 ) 1/2 where S is the apparent power.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M11<br />

© Schneider Electric - all rights reserved


M12<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

1<br />

100<br />

33<br />

20<br />

U(t)<br />

H %<br />

0<br />

1<br />

2 3 4 5 6<br />

Fig. M12 : Harmonic spectrum <strong>of</strong> a rectangular signal, for a<br />

voltage U (t)<br />

t<br />

h<br />

5 Essential indicators <strong>of</strong> harmonic<br />

distortion and measurement<br />

principles<br />

5.4 Harmonic spectrum and harmonic distortion<br />

Principle<br />

Each type <strong>of</strong> device causing harmonics draws a particular form <strong>of</strong> harmonic current<br />

(amplitude and phase displacement).<br />

These values, notably the amplitude for each harmonic order, are essential for<br />

analysis.<br />

Individual harmonic distortion (or harmonic distortion <strong>of</strong><br />

order h)<br />

The individual harmonic distortion is defined as the percentage <strong>of</strong> harmonics for<br />

order h with respect to the fundamental.<br />

u % 100 Uh<br />

h(<br />

) =<br />

U1<br />

or<br />

I<br />

i h % 100 h<br />

( ) =<br />

I1<br />

Harmonic spectrum<br />

By representing the amplitude <strong>of</strong> each harmonic order with respect to its frequency, it<br />

is possible to obtain a graph called the harmonic spectrum.<br />

Figure M12 shows an example <strong>of</strong> the harmonic spectrum for a rectangular signal.<br />

Rms value<br />

The rms value <strong>of</strong> the voltage and current can be calculated as a function <strong>of</strong> the rms<br />

value <strong>of</strong> the various harmonic orders.<br />

∞<br />

∑ h<br />

=<br />

2<br />

h 1<br />

Irms = I<br />

and<br />

∞<br />

rms = ∑ h<br />

=<br />

2<br />

U U<br />

h 1<br />

5.5 Total harmonic distortion (THD)<br />

The term THD means Total Harmonic Distortion and is a widely used notion in<br />

defining the level <strong>of</strong> harmonic content in alternating signals.<br />

Definition <strong>of</strong> THD<br />

For a signal y, the THD is defined as:<br />

∞<br />

∑yh<br />

h=<br />

THD =<br />

y<br />

2<br />

2<br />

1<br />

This complies with the definition given in standard IEC 61000-2-2.<br />

Note that the value can exceed 1.<br />

According to the standard, the variable h can be limited to 50. The THD is the means<br />

to express as a single number the distortion affecting a current or voltage flowing at a<br />

given point in the <strong>installation</strong>.<br />

The THD is generally expressed as a percentage.<br />

Current or voltage THD<br />

For current harmonics, the equation is:<br />

∞<br />

∑Ih<br />

h=<br />

THDi =<br />

I<br />

2<br />

2<br />

1<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

1.2<br />

1<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

PF<br />

cos ϕ<br />

0<br />

50<br />

Figure L13 Fig. shows M13 : a Variation graph <strong>of</strong> in<br />

PF<br />

THDu = 0<br />

cosϕ<br />

100<br />

150<br />

THDi<br />

(%)<br />

as a function <strong>of</strong> THDI.<br />

as a function <strong>of</strong> the THDi, where<br />

5 Essential indicators <strong>of</strong> harmonic<br />

distortion and measurement<br />

principles<br />

The equation below is equivalent to the above, but easier and more direct when the<br />

total rms value is available:<br />

THDi = ⎛ ⎞<br />

⎜ ⎟<br />

⎝ ⎠<br />

−<br />

2<br />

Irms<br />

1<br />

I1<br />

For voltage harmonics, the equation is:<br />

THDu<br />

=<br />

∞<br />

∑Uh h=<br />

U<br />

2<br />

2<br />

1<br />

Relation between power factor and THD (see Fig. M13)<br />

When the voltage is sinusoidal or virtually sinusoidal, it may be said that:<br />

P ≈ P1 = U 1. I1.cosϕ1 Consequently : PF = P<br />

S<br />

as:<br />

I<br />

I<br />

1 =<br />

rms<br />

U 1. I1.cosϕ<br />

≈<br />

1<br />

U 1. Irms<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1<br />

2<br />

1+ THDi<br />

cosϕ<br />

hence: PF ≈ 1<br />

2<br />

1+ THDi<br />

Figure M13 L13 shows a graph <strong>of</strong> PF<br />

as a function <strong>of</strong> THDi. THDI.<br />

cosϕ<br />

5.6 Usefulness <strong>of</strong> the various indicators<br />

The THDu characterises the distortion <strong>of</strong> the voltage wave.<br />

Below are a number <strong>of</strong> THDu values and the corresponding phenomena in the<br />

<strong>installation</strong>:<br />

b THDu under 5% - normal situation, no risk <strong>of</strong> malfunctions<br />

b 5 to 8% - significant harmonic pollution, some malfunctions are possible<br />

b Higher than 8% - major harmonic pollution, malfunctions are probable. In-depth<br />

analysis and the <strong>installation</strong> <strong>of</strong> attenuation devices are required<br />

The THDi characterises the distortion <strong>of</strong> the current wave.<br />

The disturbing device is located by measuring the THDi on the incomer and each<br />

outgoer <strong>of</strong> the various circuits and thus following the harmonic trail.<br />

Below are a number <strong>of</strong> THDi values and the corresponding phenomena in the<br />

<strong>installation</strong>:<br />

b THDi under 10% - normal situation, no risk <strong>of</strong> malfunctions<br />

b 10 to 50% - significant harmonic pollution with a risk <strong>of</strong> temperature rise and the<br />

resulting need to oversize cables and sources<br />

b Higher than 50% - major harmonic pollution, malfunctions are probable. In-depth<br />

analysis and the <strong>installation</strong> <strong>of</strong> attenuation devices are required<br />

Power factor PF<br />

Used to evaluate the necessary oversizing for the power source <strong>of</strong> the <strong>installation</strong>.<br />

Crest factor<br />

Used to characterise the aptitude <strong>of</strong> a generator (or UPS) to supply high<br />

instantaneous currents. For example, computer equipment draws highly distorted<br />

current for which the crest factor can reach 3 to 5.<br />

Spectrum (decomposition <strong>of</strong> the signal into frequencies)<br />

It provides a different representation <strong>of</strong> <strong>electrical</strong> signals and can be used to evaluate<br />

their distortion.<br />

M13<br />

© Schneider Electric - all rights reserved


M14<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

6 Measuring the indicators<br />

6.1 Devices used to measure the indicators<br />

Device selection<br />

The traditional observation and measurement methods include:<br />

b Observations using an oscilloscope<br />

An initial indication on the distortion affecting a signal can be obtained by viewing the<br />

current or the voltage on an oscilloscope.<br />

The waveform, when it diverges from a sinusoidal, clearly indicates the presence <strong>of</strong><br />

harmonics. Current and voltage peaks can be viewed.<br />

Note, however, that this method does not <strong>of</strong>fer precise quantification <strong>of</strong> the harmonic<br />

components<br />

b Analogue spectral analysers<br />

They are made up <strong>of</strong> passband filters coupled with an rms voltmeter. They <strong>of</strong>fer<br />

mediocre performance and do not provide information on phase displacement.<br />

Only the recent digital analysers can determine sufficiently precisely the<br />

values <strong>of</strong> all the mentioned indicators.<br />

Functions <strong>of</strong> digital analysers<br />

The microprocessors in digital analysers:<br />

b Calculate the values <strong>of</strong> the harmonic indicators (power factor, crest factor,<br />

distortion power, THD)<br />

b Carry out various complementary functions (corrections, statistical detection,<br />

measurement management, display, communication, etc.)<br />

b In multi-channel analysers, supply virtually in real time the simultaneous spectral<br />

decomposition <strong>of</strong> the currents and voltages<br />

Analyser operation and data processing<br />

The analogue signals are converted into a series <strong>of</strong> numerical values.<br />

Using this data, an algorithm implementing the Fast Fourier Transform (FFT)<br />

calculates the amplitudes and the phases <strong>of</strong> the harmonics over a large number <strong>of</strong><br />

time windows.<br />

Most digital analysers measure harmonics up to order 20 or 25 when calculating the<br />

THD.<br />

Processing <strong>of</strong> the successive values calculated using the FFT (smoothing,<br />

classification, statistics) can be carried out by the measurement device or by external<br />

s<strong>of</strong>tware.<br />

6.2 Procedures for harmonic analysis <strong>of</strong> distribution<br />

networks<br />

Measurements are carried out on industrial or commercial site:<br />

b Preventively, to obtain an overall idea on distribution-network status (network map)<br />

b In view <strong>of</strong> corrective action:<br />

v To determine the origin <strong>of</strong> a disturbance and determine the solutions required to<br />

eliminate it<br />

v To check the validity <strong>of</strong> a solution (followed by modifications in the distribution<br />

network to check the reduction in harmonics)<br />

Operating mode<br />

The current and voltage are studied:<br />

b At the supply source<br />

b On the busbars <strong>of</strong> the main distribution switchboard (or on the MV busbars)<br />

b On each outgoing circuit in the main distribution switchboard (or on the<br />

MV busbars)<br />

For the measurements, it is necessary to know the precise operating conditions<br />

<strong>of</strong> the <strong>installation</strong> and particularly the status <strong>of</strong> the capacitor banks (operating, not<br />

operating, the number <strong>of</strong> disconnected steps).<br />

Analysis results<br />

b Determine any necessary derating <strong>of</strong> equipment in the <strong>installation</strong> or<br />

b Quantify any necessary harmonic protection and filtering systems to be installed in<br />

the distribution network<br />

b Enable comparison between the measured values and the reference values <strong>of</strong> the<br />

utility (maximum harmonic values, acceptable values, reference values)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

6 Measuring the indicators<br />

Use <strong>of</strong> measurement devices<br />

Measurement devices serve to show both the instantaneous and long-term effects <strong>of</strong><br />

harmonics. Analysis requires values spanning durations ranging from a few seconds<br />

to several minutes over observation periods <strong>of</strong> a number <strong>of</strong> days.<br />

The required values include:<br />

b The amplitudes <strong>of</strong> the harmonic currents and voltages<br />

b The individual harmonic content <strong>of</strong> each harmonic order <strong>of</strong> the current and voltage<br />

b The THD for the current and voltage<br />

b Where applicable, the phase displacement between the harmonic voltage and<br />

current <strong>of</strong> the same harmonic order and the phase <strong>of</strong> the harmonics with respect to a<br />

common reference (e.g. the fundamental voltage)<br />

6.3 Keeping a close eye on harmonics<br />

The harmonic indicators can be measured:<br />

b Either by devices permanently installed in the distribution network<br />

b Or by an expert present at least a half day on the site (limited perception)<br />

Permanent devices are preferable<br />

For a number <strong>of</strong> reasons, the <strong>installation</strong> <strong>of</strong> permanent measurement devices in the<br />

distribution network is preferable.<br />

b The presence <strong>of</strong> an expert is limited in time. Only a number <strong>of</strong> measurements at<br />

different points in the <strong>installation</strong> and over a sufficiently long period (one week to a<br />

month) provide an overall view <strong>of</strong> operation and take into account all the situations<br />

that can occur following:<br />

v Fluctuations in the supply source<br />

v Variations in the operation <strong>of</strong> the <strong>installation</strong><br />

v The addition <strong>of</strong> new equipment in the <strong>installation</strong><br />

b Measurement devices installed in the distribution network prepare and facilitate the<br />

diagnosis <strong>of</strong> the experts, thus reducing the number and duration <strong>of</strong> their visits<br />

b Permanent measurement devices detect any new disturbances arising following<br />

the <strong>installation</strong> <strong>of</strong> new equipment, the implementation <strong>of</strong> new operating modes or<br />

fluctuations in the supply network<br />

Take advantage <strong>of</strong> built-in measurement and detection devices<br />

Measurement and detection devices built into the <strong>electrical</strong> distribution equipment:<br />

b For an overall evaluation <strong>of</strong> network status (preventive analysis), avoid:<br />

v Renting measurement equipment<br />

v Calling in experts<br />

v Having to connect and disconnect the measurement equipment.<br />

For the overall evaluation <strong>of</strong> network status, the analysis on the main low-voltage<br />

distribution switchboards (MLVS) can <strong>of</strong>ten be carried out by the incoming device<br />

and/or the measurement devices equipping each outgoing circuit<br />

b For corrective action, are the means to:<br />

v Determine the operating conditions at the time <strong>of</strong> the incident<br />

v Draw up a map <strong>of</strong> the distribution network and evaluate the implemented solution<br />

The diagnosis is improved by the use <strong>of</strong> equipment intended for the studied problem.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M15<br />

© Schneider Electric - all rights reserved


M16<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

PowerLogic System with Power Meter and<br />

Circuit Monitor, Micrologic <strong>of</strong>fer a complete<br />

range <strong>of</strong> devices for the detection <strong>of</strong> harmonic<br />

distortion<br />

Fig. M14 : Circuit monitor<br />

Fig. M15 : Micrologic H control unit with harmonic metering for<br />

Masterpact NT and NW circuit-breakers<br />

7 Detection devices<br />

Measurements are the first step in gaining control over harmonic pollution.<br />

Depending on the conditions in each <strong>installation</strong>, different types <strong>of</strong> equipment<br />

provide the necessary solution.<br />

Power-monitoring units<br />

Power Meter and Circuit Monitor in the PowerLogic System<br />

These products <strong>of</strong>fer high-performance measurement capabilities for low and<br />

medium-voltage distribution networks. They are digital units that include powerquality<br />

monitoring functions.<br />

PowerLogic System is a complete <strong>of</strong>fer comprising Power Meter (PM) and Circuit<br />

Monitor (CM). This highly modular <strong>of</strong>fer covers needs ranging from the most simple<br />

(Power Meter) up to highly complex requirements (Circuit Monitor). These products<br />

can be used in new or existing <strong>installation</strong>s where the level <strong>of</strong> power quality must be<br />

excellent. The operating mode can be local and/or remote.<br />

Depending on its position in the distribution network, a Power Meter provides an initial<br />

indication on power quality. The main measurements carried out by a Power Meter are:<br />

b Current and voltage THD<br />

b Power factor<br />

Depending on the version, these measurements can be combined with timestamping<br />

and alarm functions.<br />

A Circuit Monitor (see Fig. M14) carries out a detailed analysis <strong>of</strong> power quality<br />

and also analyses disturbances on the distribution network. The main functions <strong>of</strong> a<br />

Circuit Monitor are:<br />

b Measurement <strong>of</strong> over 100 <strong>electrical</strong> parameters<br />

b Storage in memory and time-stamping <strong>of</strong> minimum and maximum values for each<br />

<strong>electrical</strong> parameter<br />

b Alarm functions tripped by <strong>electrical</strong> parameter values<br />

b Recording <strong>of</strong> event data<br />

b Recording <strong>of</strong> current and voltage disturbances<br />

b Harmonic analysis<br />

b Waveform capture (disturbance monitoring)<br />

Micrologic - a power-monitoring unit built into the circuit-breaker<br />

For new <strong>installation</strong>s, the Micrologic H control unit (see Fig. M15), an integral part<br />

<strong>of</strong> Masterpact power circuit-breakers, is particularly useful for measurements at the<br />

head <strong>of</strong> an <strong>installation</strong> or on large outgoing circuits.<br />

The Micrologic H control unit <strong>of</strong>fers precise analysis <strong>of</strong> power quality and detailed<br />

diagnostics on events. It is <strong>design</strong>ed for operation in conjunction with a switchboard<br />

display unit or a supervisor. It can:<br />

b Measure current, voltage, active and reactive power<br />

b Measure current and voltage THD<br />

b Display the amplitude and phase <strong>of</strong> current and voltage harmonics up to the 51 st order<br />

b Carry out waveform capture (disturbance monitoring)<br />

The functions <strong>of</strong>fered by the Micrologic H control unit are equivalent to those <strong>of</strong> a<br />

Circuit Monitor.<br />

Operation <strong>of</strong> power-monitoring units<br />

S<strong>of</strong>tware for remote operation and analysis<br />

In the more general framework <strong>of</strong> a distribution network requiring monitoring,<br />

the possibility <strong>of</strong> interconnecting these various devices can be <strong>of</strong>fered in a<br />

communication network, thus making it possible to centralise information and obtain<br />

an overall view <strong>of</strong> disturbances throughout the distribution network.<br />

Depending on the application, the operator can then carry out measurements in real<br />

time, calculate demand values, run waveform captures, anticipate on alarms, etc.<br />

The power-monitoring units transmit all the available data over either a Modbus,<br />

Digipact or Ethernet network.<br />

The essential goal <strong>of</strong> this system is to assist in identifying and planning maintenance<br />

work. It is an effective means to reduce servicing time and the cost <strong>of</strong> temporarily<br />

installing devices for on-site measurements or the sizing <strong>of</strong> equipment (filters).<br />

Supervision s<strong>of</strong>tware SMS<br />

SMS is a very complete s<strong>of</strong>tware used to analyse distribution networks, in conjunction<br />

with the products in the PowerLogic System. Installed on a standard PC, it can:<br />

b Display measurements in real time<br />

b Display historical logs over a given period<br />

b Select the manner in which data is presented (tables, various curves)<br />

b Carry out statistical processing <strong>of</strong> data (display bar charts)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


M - Harmonic management<br />

8 Solutions to attenuate<br />

harmonics<br />

There are three different types <strong>of</strong> solutions to attenuate harmonics:<br />

b Modifications in the <strong>installation</strong><br />

b Special devices in the supply system<br />

b Filtering<br />

8.1 Basic solutions<br />

To limit the propagation <strong>of</strong> harmonics in the distribution network, different solutions<br />

are available and should be taken into account particularly when <strong>design</strong>ing a new<br />

<strong>installation</strong>.<br />

Position the non-linear loads upstream in the system<br />

Overall harmonic disturbances increase as the short-circuit power decreases.<br />

All economic considerations aside, it is preferable to connect the non-linear loads as<br />

far upstream as possible (see Fig. M16).<br />

Fig. M16 : Non-linear loads positioned as far upstream as possible (recommended layout)<br />

Group the non-linear loads<br />

When preparing the single-line diagram, the non-linear devices should be separated<br />

from the others (see Fig. M17). The two groups <strong>of</strong> devices should be supplied by<br />

different sets <strong>of</strong> busbars.<br />

Yes<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Z 1<br />

Non-linear<br />

loads<br />

Line impedances<br />

No<br />

Sensitive<br />

loads<br />

Non-linear<br />

load 1<br />

Non-linear<br />

load 2<br />

Fig. M17 : Grouping <strong>of</strong> non-linear loads and connection as far upstream as possible<br />

(recommended layout)<br />

Create separate sources<br />

In attempting to limit harmonics, an additional improvement can be obtained by<br />

creating a source via a separate transformer as indicated in the Figure M18 next<br />

page.<br />

The disadvantage is the increase in the cost <strong>of</strong> the <strong>installation</strong>.<br />

Z 2<br />

Where impedance<br />

Z 1 < Z 2<br />

Sensitive<br />

loads<br />

M17<br />

© Schneider Electric - all rights reserved


M18<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

8 Solutions to attenuate<br />

harmonics<br />

MV<br />

network<br />

Fig. M18 : Supply <strong>of</strong> non-linear loads via a separate transformer<br />

Transformers with special connections<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Non-linear<br />

loads<br />

Linear<br />

loads<br />

Different transformer connections can eliminate certain harmonic orders, as<br />

indicated in the examples below:<br />

b A Dyd connection suppresses 5 th and 7 th harmonics (see Fig. M19)<br />

b A Dy connection suppresses the 3 rd harmonic<br />

b A DZ 5 connection suppresses the 5 th harmonic<br />

h11, h13<br />

h5, h7, h11, h13<br />

h5, h7, h11, h13<br />

Fig. M19 : A Dyd transformer blocks propagation <strong>of</strong> the 5 th and 7 th harmonics to the upstream<br />

network<br />

Install reactors<br />

When variable-speed drives are supplied, it is possible to smooth the current<br />

by installing line reactors. By increasing the impedance <strong>of</strong> the supply circuit, the<br />

harmonic current is limited.<br />

Installation <strong>of</strong> harmonic suppression reactors on capacitor banks increases the<br />

impedance <strong>of</strong> the reactor/capacitor combination for high-order harmonics.<br />

This avoids resonance and protects the capacitors.<br />

Select the suitable system earthing arrangement<br />

TNC system<br />

In the TNC system, a single conductor (PEN) provides protection in the event <strong>of</strong> an<br />

earth fault and the flow <strong>of</strong> unbalance currents.<br />

Under steady-state conditions, the harmonic currents flow in the PEN. The latter,<br />

however, has a certain impedance with as a result slight differences in potential (a<br />

few volts) between devices that can cause electronic equipment to malfunction.<br />

The TNC system must therefore be reserved for the supply <strong>of</strong> power circuits at the<br />

head <strong>of</strong> the <strong>installation</strong> and must not be used to supply sensitive loads.<br />

TNS system<br />

This system is recommended if harmonics are present.<br />

The neutral conductor and the protection conductor PE are completely separate and<br />

the potential throughout the distribution network is therefore more uniform.<br />

8.2 Harmonic filtering<br />

In cases where the preventive action presented above is insufficient, it is necessary<br />

to equip the <strong>installation</strong> with filtering systems.<br />

There are three types <strong>of</strong> filters:<br />

b Passive<br />

b Active<br />

b Hybrid


M - Harmonic management<br />

I har<br />

Non-linear<br />

load<br />

Fig. M20 : Operating principle <strong>of</strong> a passive filter<br />

I har<br />

Non-linear<br />

load<br />

Filter<br />

AHC<br />

Fig. M22 : Operating principle <strong>of</strong> a hybrid filter<br />

Is<br />

Iact<br />

Fig. M21 : Operating principle <strong>of</strong> an active filter<br />

I har<br />

Non-linear<br />

load<br />

AHC<br />

Iact<br />

Hybride filter<br />

Linear<br />

load<br />

Is<br />

Linear<br />

load<br />

8 Solutions to attenuate<br />

harmonics<br />

Passive filters<br />

Typical applications<br />

b Industrial <strong>installation</strong>s with a set <strong>of</strong> non-linear loads representing more than<br />

200 kVA (variable-speed drives, UPSs, rectifiers, etc.)<br />

b Installations requiring power-factor correction<br />

b Installations where voltage distortion must be reduced to avoid disturbing sensitive<br />

loads<br />

b Installations where current distortion must be reduced to avoid overloads<br />

Operating principle<br />

An LC circuit, tuned to each harmonic order to be filtered, is installed in parallel with<br />

the non-linear load (see Fig. M20). This bypass circuit absorbs the harmonics, thus<br />

avoiding their flow in the distribution network.<br />

<strong>General</strong>ly speaking, the passive filter is tuned to a harmonic order close to the order<br />

to be eliminated. Several parallel-connected branches <strong>of</strong> filters can be used if a<br />

significant reduction in the distortion <strong>of</strong> a number <strong>of</strong> harmonic orders is required.<br />

Active filters (active harmonic conditioner)<br />

Typical applications<br />

b Commercial <strong>installation</strong>s with a set <strong>of</strong> non-linear loads representing less than<br />

200 kVA (variable-speed drives, UPSs, <strong>of</strong>fice equipment, etc.)<br />

b Installations where current distortion must be reduced to avoid overloads.<br />

Operating principle<br />

These systems, comprising power electronics and installed in series or parallel with<br />

the non-linear load, compensate the harmonic current or voltage drawn by the load.<br />

Figure M21 shows a parallel-connected active harmonic conditioner (AHC)<br />

compensating the harmonic current (Ihar = -Iact).<br />

The AHC injects in opposite phase the harmonics drawn by the non-linear load, such<br />

that the line current Is remains sinusoidal.<br />

Hybrid filters<br />

Typical applications<br />

b Industrial <strong>installation</strong>s with a set <strong>of</strong> non-linear loads representing more than<br />

200 kVA (variable-speed drives, UPSs, rectifiers, etc.)<br />

b Installations requiring power-factor correction<br />

b Installations where voltage distortion must be reduced to avoid disturbing sensitive<br />

loads<br />

b Installations where current distortion must be reduced to avoid overloads<br />

b Installations where strict limits on harmonic emissions must be met<br />

Operating principle<br />

Passive and active filters are combined in a single system to constitute a hybrid filter<br />

(see Fig. M22). This new filtering solution <strong>of</strong>fers the advantages <strong>of</strong> both types <strong>of</strong><br />

filters and covers a wide range <strong>of</strong> power and performance levels.<br />

Selection criteria<br />

Passive filter<br />

It <strong>of</strong>fers both power-factor correction and high current-filtering capacity.<br />

Passive filters also reduce the harmonic voltages in <strong>installation</strong>s where the supply<br />

voltage is disturbed. If the level <strong>of</strong> reactive power supplied is high, it is advised to turn<br />

<strong>of</strong>f the passive filter at times when the percent load is low.<br />

Preliminary studies for a filter must take into account the possible presence <strong>of</strong> a<br />

power factor correction capacitor bank which may have to be eliminated.<br />

Active harmonic conditioners<br />

They filter harmonics over a wide range <strong>of</strong> frequencies and can adapt to any type <strong>of</strong><br />

load.<br />

On the other hand, power ratings are low.<br />

Hybrid filters<br />

They combine the performance <strong>of</strong> both active and passive filters.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

M19<br />

© Schneider Electric - all rights reserved


M20<br />

© Schneider Electric - all rights reserved<br />

M - Harmonic management<br />

A complete set <strong>of</strong> services can be <strong>of</strong>fered to<br />

eliminate harmonics:<br />

b Installation analysis<br />

b Measurement and monitoring systems<br />

b Filtering solutions<br />

8 Solutions to attenuate<br />

harmonics<br />

8.3 The method<br />

The best solution, in both technical and financial terms, is based on the results <strong>of</strong> an<br />

in-depth study.<br />

Harmonic audit <strong>of</strong> MV and LV networks<br />

By calling on an expert, you are guaranteed that the proposed solution will produce<br />

effective results (e.g. a guaranteed maximum THDu).<br />

A harmonic audit is carried out by an engineer specialised in the disturbances<br />

affecting <strong>electrical</strong> distribution networks and equipped with powerful analysis and<br />

simulation equipment and s<strong>of</strong>tware.<br />

The steps in an audit are the following:<br />

b Measurement <strong>of</strong> disturbances affecting current and phase-to-phase and phaseto-neutral<br />

voltages at the supply source, the disturbed outgoing circuits and the<br />

non-linear loads<br />

b Computer modelling <strong>of</strong> the phenomena to obtain a precise explanation <strong>of</strong> the<br />

causes and determine the best solutions<br />

b A complete audit report presenting:<br />

v The current levels <strong>of</strong> disturbances<br />

v The maximum permissible levels <strong>of</strong> disturbances (IEC 61000, IEC 34, etc.)<br />

b A proposal containing solutions with guaranteed levels <strong>of</strong> performance<br />

b Finally, implementation <strong>of</strong> the selected solution, using the necessary means and<br />

resources.<br />

The entire audit process is certified ISO 9002.<br />

8.4 Specific products<br />

Passive filters<br />

Passive filters are made up <strong>of</strong> coils and capacitors set up in resonant circuits tuned<br />

to the specific harmonic order that must be eliminated.<br />

A system may comprise a number <strong>of</strong> filters to eliminate several harmonic orders.<br />

Suitable for 400 V three-phase voltages, the power ratings can reach:<br />

b 265 kvar / 470 A for harmonic order 5<br />

b 145 kvar / 225 A for harmonic order 7<br />

b 105 kvar / 145 A for harmonic order 11<br />

Passive filters can be created for all voltage and current levels.<br />

Active filters<br />

b SineWave active harmonic conditioners<br />

v Suitable for 400 V three-phase voltages, they can deliver between 20 and 120 A<br />

per phase<br />

v SineWave covers all harmonic orders from 2 to 25. Conditioning can be total or<br />

target specific harmonic orders<br />

v Attenuation: THDi load / THDi upstream greater than 10 at rated capacity<br />

v Functions include power factor correction, conditioning <strong>of</strong> zero-sequence<br />

harmonics, diagnostics and maintenance system, parallel connection, remote<br />

control, Ibus/RS485 communication interface<br />

b Accusine active filters<br />

v Suitable for 400 and 480 V three-phase voltages, they can filter between 50 and 30<br />

A per phase<br />

v All harmonic orders up to 50 are filtered<br />

v Functions include power factor correction, parallel connection, instantaneous<br />

response to load variations<br />

Hybrid filters<br />

These filters combine the advantages <strong>of</strong> both a passive filter and the SineWave<br />

active harmonic conditioner in a single system.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

a -<br />

b -<br />

Fig. N35 : Compact fluorescent lamps [a] standard,<br />

[b] induction<br />

4 Lighting circuits<br />

A source <strong>of</strong> comfort and productivity, lighting represents 15% <strong>of</strong> the quantity <strong>of</strong><br />

electricity consumed in industry and 40% in buildings. The quality <strong>of</strong> lighting (light<br />

stability and continuity <strong>of</strong> service) depends on the quality <strong>of</strong> the <strong>electrical</strong> energy<br />

thus consumed. The supply <strong>of</strong> <strong>electrical</strong> power to lighting networks has therefore<br />

assumed great importance.<br />

To help with their <strong>design</strong> and simplify the selection <strong>of</strong> appropriate protection devices,<br />

an analysis <strong>of</strong> the different lamp technologies is presented. The distinctive features<br />

<strong>of</strong> lighting circuits and their impact on control and protection devices are discussed.<br />

Recommendations relative to the difficulties <strong>of</strong> lighting circuit implementation are given.<br />

4.1 The different lamp technologies<br />

Artificial luminous radiation can be produced from <strong>electrical</strong> energy according to two<br />

principles: incandescence and electroluminescence.<br />

Incandescence is the production <strong>of</strong> light via temperature elevation. The most<br />

common example is a filament heated to white state by the circulation <strong>of</strong> an <strong>electrical</strong><br />

current. The energy supplied is transformed into heat by the Joule effect and into<br />

luminous flux.<br />

Luminescence is the phenomenon <strong>of</strong> emission by a material <strong>of</strong> visible or almost<br />

visible luminous radiation. A gas (or vapors) subjected to an <strong>electrical</strong> discharge<br />

emits luminous radiation (Electroluminescence <strong>of</strong> gases).<br />

Since this gas does not conduct at normal temperature and pressure, the discharge<br />

is produced by generating charged particles which permit ionization <strong>of</strong> the gas. The<br />

nature, pressure and temperature <strong>of</strong> the gas determine the light spectrum.<br />

Photoluminescence is the luminescence <strong>of</strong> a material exposed to visible or almost<br />

visible radiation (ultraviolet, infrared).<br />

When the substance absorbs ultraviolet radiation and emits visible radiation which<br />

stops a short time after energization, this is fluorescence.<br />

Incandescent lamps<br />

Incandescent lamps are historically the oldest and the most <strong>of</strong>ten found in common<br />

use.<br />

They are based on the principle <strong>of</strong> a filament rendered incandescent in a vacuum or<br />

neutral atmosphere which prevents combustion.<br />

A distinction is made between:<br />

b Standard bulbs<br />

These contain a tungsten filament and are filled with an inert gas (nitrogen and<br />

argon or krypton).<br />

b Halogen bulbs<br />

These also contain a tungsten filament, but are filled with a halogen compound<br />

and an inert gas (krypton or xenon). This halogen compound is responsible for the<br />

phenomenon <strong>of</strong> filament regeneration, which increases the service life <strong>of</strong> the lamps<br />

and avoids them blackening. It also enables a higher filament temperature and<br />

therefore greater luminosity in smaller-size bulbs.<br />

The main disadvantage <strong>of</strong> incandescent lamps is their significant heat dissipation,<br />

resulting in poor luminous efficiency.<br />

Fluorescent lamps<br />

This family covers fluorescent tubes and compact fluorescent lamps. Their<br />

technology is usually known as “low-pressure mercury”.<br />

In fluorescent tubes, an <strong>electrical</strong> discharge causes electrons to collide with<br />

ions <strong>of</strong> mercury vapor, resulting in ultraviolet radiation due to energization <strong>of</strong> the<br />

mercury atoms. The fluorescent material, which covers the inside <strong>of</strong> the tubes, then<br />

transforms this radiation into visible light.<br />

Fluorescent tubes dissipate less heat and have a longer service life than<br />

incandescent lamps, but they do need an ignition device called a “starter” and a<br />

device to limit the current in the arc after ignition. This device called “ballast” is<br />

usually a choke placed in series with the arc.<br />

Compact fluorescent lamps are based on the same principle as a fluorescent tube.<br />

The starter and ballast functions are provided by an electronic circuit (integrated in<br />

the lamp) which enables the use <strong>of</strong> smaller tubes folded back on themselves.<br />

Compact fluorescent lamps (see Fig. N35) were developed to replace incandescent<br />

lamps: They <strong>of</strong>fer significant energy savings (15 W against 75 W for the same level <strong>of</strong><br />

brightness) and an increased service life.<br />

Lamps known as “induction” type or “without electrodes” operate on the principle <strong>of</strong><br />

ionization <strong>of</strong> the gas present in the tube by a very high frequency electromagnetic<br />

field (up to 1 GHz). Their service life can be as long as 100,000 hrs.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N27<br />

© Schneider Electric - all rights reserved


N28<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Fig. N36 : Discharge lamps<br />

Discharge lamps (see Fig. N36)<br />

The light is produced by an <strong>electrical</strong> discharge created between two electrodes within<br />

a gas in a quartz bulb. All these lamps therefore require a ballast to limit the current in<br />

the arc. A number <strong>of</strong> technologies have been developed for different applications.<br />

Low-pressure sodium vapor lamps have the best light output, however the color<br />

rendering is very poor since they only have a monochromatic orange radiation.<br />

High-pressure sodium vapor lamps produce a white light with an orange tinge.<br />

In high-pressure mercury vapor lamps, the discharge is produced in a quartz or<br />

ceramic bulb at high pressure. These lamps are called “fluorescent mercury discharge<br />

lamps”. They produce a characteristically bluish white light.<br />

Metal halide lamps are the latest technology. They produce a color with a broad color<br />

spectrum. The use <strong>of</strong> a ceramic tube <strong>of</strong>fers better luminous efficiency and better color<br />

stability.<br />

Light Emitting Diodes (LED)<br />

The principle <strong>of</strong> light emitting diodes is the emission <strong>of</strong> light by a semi-conductor<br />

as an <strong>electrical</strong> current passes through it. LEDs are commonly found in numerous<br />

applications, but the recent development <strong>of</strong> white or blue diodes with a high light<br />

output opens new perspectives, especially for signaling (traffic lights, exit signs or<br />

emergency lighting).<br />

LEDs are low-voltage and low-current devices, thus suitable for battery-supply.<br />

A converter is required for a line power supply.<br />

The advantage <strong>of</strong> LEDs is their low energy consumption. As a result, they operate<br />

at a very low temperature, giving them a very long service life. Conversely, a simple<br />

diode has a weak light intensity. A high-power lighting <strong>installation</strong> therefore requires<br />

connection <strong>of</strong> a large number <strong>of</strong> units in series and parallel.<br />

Technology Application Advantages Disadvantages<br />

Standard - Domestic use - Direct connection without - Low luminous efficiency and<br />

incandescent - Localized decorative intermediate switchgear high electricity consumption<br />

lighting - Reasonable purchase price - Significant heat dissipation<br />

- Compact size - Short service life<br />

- Instantaneous lighting<br />

- Good color rendering<br />

Halogen - Spot lighting - Direct connection - Average luminous efficiency<br />

incandescent - Intense lighting - Instantaneous efficiency<br />

- Excellent color rendering<br />

Fluorescent tube - Shops, <strong>of</strong>fices, workshops - High luminous efficiency - Low light intensity <strong>of</strong> single unit<br />

- Outdoors - Average color rendering - Sensitive to extreme temperatures<br />

Compact - Domestic use - Good luminous efficiency - High initial investment<br />

fluorescent lamp - Offices - Good color rendering compared to incandescent lamps<br />

- Replacement <strong>of</strong><br />

incandescent lamps<br />

HP mercury vapor - Workshops, halls, hangars - Good luminous efficiency - Lighting and relighting time<br />

- Factory floors - Acceptable color rendering <strong>of</strong> a few minutes<br />

- Compact size<br />

- Long service life<br />

High-pressure - Outdoors - Very good luminous efficiency - Lighting and relighting time<br />

sodium - Large halls <strong>of</strong> a few minutes<br />

Low-pressure - Outdoors - Good visibility in foggy weather - Long lighting time (5 min.)<br />

sodium - Emergency lighting - Economical to use - Mediocre color rendering<br />

Metal halide - Large areas - Good luminous efficiency - Lighting and relighting time<br />

- Halls with high ceilings - Good color rendering <strong>of</strong> a few minutes<br />

- Long service life<br />

LED - Signaling (3-color traffic - Insensitive to the number <strong>of</strong> - Limited number <strong>of</strong> colors<br />

lights, “exit” signs and switching operations - Low brightness <strong>of</strong> single unit<br />

emergency lighting) - Low energy consumption<br />

- Low temperature<br />

Technology Power (watt) Efficiency (lumen/watt) Service life (hours)<br />

Standard incandescent 3 – 1,000 10 – 15 1,000 – 2,000<br />

Halogen incandescent 5 – 500 15 – 25 2,000 – 4,000<br />

Fluorescent tube 4 – 56 50 – 100 7,500 – 24,000<br />

Compact fluorescent lamp 5 – 40 50 – 80 10,000 – 20,000<br />

HP mercury vapor 40 – 1,000 25 – 55 16,000 – 24,000<br />

High-pressure sodium 35 – 1,000 40 – 140 16,000 – 24,000<br />

Low-pressure sodium 35 – 180 100 – 185 14,000 – 18,000<br />

Metal halide 30 – 2,000 50 – 115 6,000 – 20,000<br />

LED 0.05 – 0.1 10 – 30 40,000 – 100,000<br />

Fig. N37 : Usage and technical characteristics <strong>of</strong> lighting devices<br />

4 Lighting circuits<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

a]<br />

300<br />

200<br />

100<br />

0<br />

-100<br />

-200<br />

-300<br />

0<br />

b]<br />

300<br />

200<br />

100<br />

0<br />

-100<br />

-200<br />

0.01 0.02<br />

-300<br />

0 0.01 0.02<br />

t (s)<br />

t (s)<br />

Fig. N38 : Shape <strong>of</strong> the voltage supplied by a light dimmer at<br />

50% <strong>of</strong> maximum voltage with the following techniques:<br />

a] “cut-on control”<br />

b] “cut-<strong>of</strong>f control”<br />

4 Lighting circuits<br />

4.2 Electrical characteristics <strong>of</strong> lamps<br />

Incandescent lamps with direct power supply<br />

Due to the very high temperature <strong>of</strong> the filament during operation (up to 2,500 °C),<br />

its resistance varies greatly depending on whether the lamp is on or <strong>of</strong>f. As the cold<br />

resistance is low, a current peak occurs on ignition that can reach 10 to 15 times the<br />

nominal current for a few milliseconds or even several milliseconds.<br />

This constraint affects both ordinary lamps and halogen lamps: it imposes a<br />

reduction in the maximum number <strong>of</strong> lamps that can be powered by devices such as<br />

remote-control switches, modular contactors and relays for busbar trunking.<br />

Extra Low Voltage (ELV) halogen lamps<br />

b Some low-power halogen lamps are supplied with ELV 12 or 24 V, via a<br />

transformer or an electronic converter. With a transformer, the magnetization<br />

phenomenon combines with the filament resistance variation phenomenon at<br />

switch-on. The inrush current can reach 50 to 75 times the nominal current for a few<br />

milliseconds. The use <strong>of</strong> dimmer switches placed upstream significantly reduces this<br />

constraint.<br />

b Electronic converters, with the same power rating, are more expensive than<br />

solutions with a transformer. This commercial handicap is compensated by a greater<br />

ease <strong>of</strong> <strong>installation</strong> since their low heat dissipation means they can be fixed on a<br />

flammable support. Moreover, they usually have built-in thermal protection.<br />

New ELV halogen lamps are now available with a transformer integrated in their<br />

base. They can be supplied directly from the LV line supply and can replace normal<br />

lamps without any special adaptation.<br />

Dimming for incandescent lamps<br />

This can be obtained by varying the voltage applied to the lampere<br />

This voltage variation is usually performed by a device such as a Triac dimmer<br />

switch, by varying its firing angle in the line voltage period. The wave form <strong>of</strong> the<br />

voltage applied to the lamp is illustrated in Figure N38a. This technique known<br />

as “cut-on control” is suitable for supplying power to resistive or inductive circuits.<br />

Another technique suitable for supplying power to capacitive circuits has been<br />

developed with MOS or IGBT electronic components. This techniques varies the<br />

voltage by blocking the current before the end <strong>of</strong> the half-period (see Fig. N38b) and<br />

is known as “cut-<strong>of</strong>f control”.<br />

Switching on the lamp gradually can also reduce, or even eliminate, the current peak<br />

on ignition.<br />

As the lamp current is distorted by the electronic switching, harmonic currents<br />

are produced. The 3<br />

N29<br />

rd harmonic order is predominant, and the percentage <strong>of</strong> 3rd harmonic current related to the maximum fundamental current (at maximum power)<br />

is represented on Figure N39.<br />

Note that in practice, the power applied to the lamp by a dimmer switch can only vary<br />

in the range between 15 and 85% <strong>of</strong> the maximum power <strong>of</strong> the lampere<br />

50.0<br />

45.0<br />

40.0<br />

35.0<br />

30.0<br />

25.0<br />

20.0<br />

15.0<br />

10.0<br />

5.0<br />

0<br />

i3 (%)<br />

0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0<br />

Fig. N39 : Percentage <strong>of</strong> 3 rd harmonic current as a function <strong>of</strong> the power applied to an<br />

incandescent lamp using an electronic dimmer switch<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Power (%)<br />

© Schneider Electric - all rights reserved


N30<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Fig. N40 : Magnetic ballasts<br />

4 Lighting circuits<br />

According to IEC standard 61000-3-2 setting harmonic emission limits for electric or<br />

electronic systems with current y 16 A, the following arrangements apply:<br />

b Independent dimmers for incandescent lamps with a rated power less than or<br />

equal to 1 kW have no limits applied<br />

b Otherwise, or for incandescent lighting equipment with built-in dimmer or dimmer<br />

built in an enclosure, the maximum permissible 3 rd harmonic current is equal to<br />

2.30 A<br />

Fluorescent lamps with magnetic ballast<br />

Fluorescent tubes and discharge lamps require the intensity <strong>of</strong> the arc to be limited,<br />

and this function is fulfilled by a choke (or magnetic ballast) placed in series with the<br />

bulb itself (see Fig. N40).<br />

This arrangement is most commonly used in domestic applications with a limited<br />

number <strong>of</strong> tubes. No particular constraint applies to the switches.<br />

Dimmer switches are not compatible with magnetic ballasts: the cancellation <strong>of</strong> the<br />

voltage for a fraction <strong>of</strong> the period interrupts the discharge and totally extinguishes<br />

the lampere<br />

The starter has a dual function: preheating the tube electrodes, and then generating<br />

an overvoltage to ignite the tube. This overvoltage is generated by the opening <strong>of</strong> a<br />

contact (controlled by a thermal switch) which interrupts the current circulating in the<br />

magnetic ballast.<br />

During operation <strong>of</strong> the starter (approx. 1 s), the current drawn by the luminaire is<br />

approximately twice the nominal current.<br />

Since the current drawn by the tube and ballast assembly is essentially inductive, the<br />

power factor is very low (on average between 0.4 and 0.5). In <strong>installation</strong>s consisting<br />

<strong>of</strong> a large number <strong>of</strong> tubes, it is necessary to provide compensation to improve the<br />

power factor.<br />

For large lighting <strong>installation</strong>s, centralized compensation with capacitor banks is a<br />

possible solution, but more <strong>of</strong>ten this compensation is included at the level <strong>of</strong> each<br />

luminaire in a variety <strong>of</strong> different layouts (see Fig. N41).<br />

a] Ballast b] C Ballast c]<br />

a<br />

C Lamp a<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Lamp<br />

a<br />

C<br />

Ballast<br />

Lamp<br />

Ballast Lamp<br />

Compensation layout Application Comments<br />

Without compensation Domestic Single connection<br />

Parallel [a] Offices, workshops,<br />

superstores<br />

Risk <strong>of</strong> overcurrents for control devices<br />

Series [b] Choose capacitors with high<br />

operating voltage (450 to 480 V)<br />

Duo [c] Avoids flicker<br />

Fig. N41 : The various compensation layouts: a] parallel; b] series; c] dual series also called<br />

“duo” and their fields <strong>of</strong> application<br />

The compensation capacitors are therefore sized so that the global power factor is<br />

greater than 0.85. In the most common case <strong>of</strong> parallel compensation, its capacity<br />

is on average 1 µF for 10 W <strong>of</strong> active power, for any type <strong>of</strong> lampere However, this<br />

compensation is incompatible with dimmer switches.<br />

Constraints affecting compensation<br />

The layout for parallel compensation creates constraints on ignition <strong>of</strong> the lampere<br />

Since the capacitor is initially discharged, switch-on produces an overcurrent.<br />

An overvoltage also appears, due to the oscillations in the circuit made up <strong>of</strong> the<br />

capacitor and the power supply inductance.<br />

The following example can be used to determine the orders <strong>of</strong> magnitude.


N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

Assuming an assembly <strong>of</strong> 50 fluorescent tubes <strong>of</strong> 36 W each:<br />

b Total active power: 1,800 W<br />

b Apparent power: 2 kVA<br />

b Total rms current: 9 A<br />

b Peak current: 13 A<br />

With:<br />

b A total capacity: C = 175 µF<br />

b A line inductance (corresponding to a short-circuit current <strong>of</strong> 5 kA): L = 150 µH<br />

The maximum peak current at switch-on equals:<br />

-6<br />

C<br />

x 10<br />

Ic = Vmax<br />

= 230 2 = A<br />

L<br />

-6<br />

x 10<br />

175<br />

350<br />

150<br />

The theoretical peak current at switch-on can therefore reach 27 times the peak<br />

current during normal operation.<br />

The shape <strong>of</strong> the voltage and current at ignition is given in Figure N42 for switch<br />

closing at the line supply voltage peak.<br />

There is therefore a risk <strong>of</strong> contact welding in electromechanical control devices<br />

(remote-control switch, contactor, circuit-breaker) or destruction <strong>of</strong> solid state<br />

switches with semi-conductors.<br />

600<br />

400<br />

200<br />

0<br />

-200<br />

-400<br />

-600<br />

0<br />

300<br />

200<br />

100<br />

0<br />

-100<br />

-200<br />

(V)<br />

(A)<br />

-300<br />

0<br />

Fig. N42 : Power supply voltage at switch-on and inrush current<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0.02 0.04 0.06<br />

0.02 0.04 0.06<br />

In reality, the constraints are usually less severe, due to the impedance <strong>of</strong> the cables.<br />

Ignition <strong>of</strong> fluorescent tubes in groups implies one specific constraint. When a group<br />

<strong>of</strong> tubes is already switched on, the compensation capacitors in these tubes which<br />

are already energized participate in the inrush current at the moment <strong>of</strong> ignition <strong>of</strong><br />

a second group <strong>of</strong> tubes: they “amplify” the current peak in the control switch at the<br />

moment <strong>of</strong> ignition <strong>of</strong> the second group.<br />

t (s)<br />

t (s)<br />

N31<br />

© Schneider Electric - all rights reserved


N32<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Fig. N44 : Electronic ballast<br />

4 Lighting circuits<br />

The table in Figure N43, resulting from measurements, specifies the magnitude <strong>of</strong><br />

the first current peak, for different values <strong>of</strong> prospective short-circuit current Isc. It is<br />

seen that the current peak can be multiplied by 2 or 3, depending on the number <strong>of</strong><br />

tubes already in use at the moment <strong>of</strong> connection <strong>of</strong> the last group <strong>of</strong> tubes.<br />

Number <strong>of</strong> tubes Number <strong>of</strong> tubes Inrush current peak (A)<br />

already in use connected Isc = 1,500 A Isc = 3,000 A Isc = 6,000 A<br />

0 14 233 250 320<br />

14 14 558 556 575<br />

28 14 608 607 624<br />

42 14 618 616 632<br />

Fig. N43 : Magnitude <strong>of</strong> the current peak in the control switch <strong>of</strong> the moment <strong>of</strong> ignition <strong>of</strong> a<br />

second group <strong>of</strong> tubes<br />

Nonetheless, sequential ignition <strong>of</strong> each group <strong>of</strong> tubes is recommended so as to<br />

reduce the current peak in the main switch.<br />

The most recent magnetic ballasts are known as “low-loss”. The magnetic circuit has<br />

been optimized, but the operating principle remains the same. This new generation<br />

<strong>of</strong> ballasts is coming into widespread use, under the influence <strong>of</strong> new regulations<br />

(European Directive, Energy Policy Act - USA).<br />

In these conditions, the use <strong>of</strong> electronic ballasts is likely to increase, to the<br />

detriment <strong>of</strong> magnetic ballasts.<br />

Fluorescent lamps with electronic ballast<br />

Electronic ballasts are used as a replacement for magnetic ballasts to supply power<br />

to fluorescent tubes (including compact fluorescent lamps) and discharge lamps.<br />

They also provide the “starter” function and do not need any compensation capacity.<br />

The principle <strong>of</strong> the electronic ballast (see Fig. N44) consists <strong>of</strong> supplying the lamp<br />

arc via an electronic device that generates a rectangular form AC voltage with a<br />

frequency between 20 and 60 kHz.<br />

Supplying the arc with a high-frequency voltage can totally eliminate the flicker<br />

phenomenon and strobe effects. The electronic ballast is totally silent.<br />

During the preheating period <strong>of</strong> a discharge lamp, this ballast supplies the lamp with<br />

increasing voltage, imposing an almost constant current. In steady state, it regulates<br />

the voltage applied to the lamp independently <strong>of</strong> any fluctuations in the line voltage.<br />

Since the arc is supplied in optimum voltage conditions, this results in energy<br />

savings <strong>of</strong> 5 to 10% and increased lamp service life. Moreover, the efficiency <strong>of</strong> the<br />

electronic ballast can exceed 93%, whereas the average efficiency <strong>of</strong> a magnetic<br />

device is only 85%.<br />

The power factor is high (> 0.9).<br />

The electronic ballast is also used to provide the light dimming function. Varying the<br />

frequency in fact varies the current magnitude in the arc and hence the luminous<br />

intensity.<br />

Inrush current<br />

The main constraint that electronic ballasts bring to line supplies is the high<br />

inrush current on switch-on linked to the initial load <strong>of</strong> the smoothing capacitors<br />

(see Fig. N45).<br />

Technology Max. inrush current Duration<br />

Rectifier with PFC 30 to 100 In y 1 ms<br />

Rectifier with choke 10 to 30 In y 5 ms<br />

Magnetic ballast y 13 In 5 to 10 ms<br />

Fig. N45 : Orders <strong>of</strong> magnitude <strong>of</strong> the inrush current maximum values, depending on the<br />

technologies used<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

In reality, due to the wiring impedances, the inrush currents for an assembly <strong>of</strong> lamps<br />

is much lower than these values, in the order <strong>of</strong> 5 to 10 In for less than 5 ms.<br />

Unlike magnetic ballasts, this inrush current is not accompanied by an overvoltage.<br />

Harmonic currents<br />

For ballasts associated with high-power discharge lamps, the current drawn from<br />

the line supply has a low total harmonic distortion (< 20% in general and < 10% for<br />

the most sophisticated devices). Conversely, devices associated with low-power<br />

lamps, in particular compact fluorescent lamps, draw a very distorted current<br />

(see Fig. N46). The total harmonic distortion can be as high as 150%. In these<br />

conditions, the rms current drawn from the line supply equals 1.8 times the current<br />

corresponding to the lamp active power, which corresponds to a power factor <strong>of</strong> 0.55.<br />

0.6<br />

0.4<br />

0.2<br />

0<br />

-0.2<br />

-0.4<br />

(A)<br />

-0.6<br />

0<br />

Fig. N46 : Shape <strong>of</strong> the current drawn by a compact fluorescent lamp<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0.02<br />

In order to balance the load between the different phases, lighting circuits are usually<br />

connected between phases and neutral in a balanced way. In these conditions,<br />

the high level <strong>of</strong> third harmonic and harmonics that are multiple <strong>of</strong> 3 can cause an<br />

overload <strong>of</strong> the neutral conductor. The least favorable situation leads to a neutral<br />

current which may reach 3 times the current in each phase.<br />

Harmonic emission limits for electric or electronic systems are set by IEC standard<br />

61000-3-2. For simplification, the limits for lighting equipment are given here only for<br />

harmonic orders 3 and 5 which are the most relevant (see Fig. N47).<br />

Harmonic Active input Active input power y 25W<br />

order power > 25W one <strong>of</strong> the 2 sets <strong>of</strong> limits apply:<br />

% <strong>of</strong> fundamental % <strong>of</strong> fundamental Harmonic current relative<br />

current current to active power<br />

3 30 86 3.4 mA/W<br />

5 10 61 1.9 mA/W<br />

Fig. N47 : Maximum permissible harmonic current<br />

Leakage currents<br />

Electronic ballasts usually have capacitors placed between the power supply<br />

conductors and the earth. These interference-suppressing capacitors are responsible<br />

for the circulation <strong>of</strong> a permanent leakage current in the order <strong>of</strong> 0.5 to 1 mA per<br />

ballast. This therefore results in a limit being placed on the number <strong>of</strong> ballasts that<br />

can be supplied by a Residual Current Differential Safety Device (RCD).<br />

At switch-on, the initial load <strong>of</strong> these capacitors can also cause the circulation <strong>of</strong> a<br />

current peak whose magnitude can reach several amps for 10 µs. This current peak<br />

may cause unwanted tripping <strong>of</strong> unsuitable devices.<br />

t (s)<br />

N33<br />

© Schneider Electric - all rights reserved


N34<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

High-frequency emissions<br />

Electronic ballasts are responsible for high-frequency conducted and radiated<br />

emissions.<br />

The very steep rising edges applied to the ballast output conductors cause current<br />

pulses circulating in the stray capacities to earth. As a result, stray currents circulate<br />

in the earth conductor and the power supply conductors. Due to the high frequency<br />

<strong>of</strong> these currents, there is also electromagnetic radiation. To limit these HF emissions,<br />

the lamp should be placed in the immediate proximity <strong>of</strong> the ballast, thus reducing<br />

the length <strong>of</strong> the most strongly radiating conductors.<br />

The different power supply modes (see Fig. N48)<br />

Technology Power supply mode Other device<br />

Standard incandescent Direct power supply Dimmer switch<br />

Halogen incandescent<br />

ELV halogen incandescent Transformer Electronic converter<br />

Fluorescent tube Magnetic ballast and starter Electronic ballast<br />

Electronic dimmer +<br />

ballast<br />

Compact fluorescent lamp Built-in electronic ballast<br />

Mercury vapor Magnetic ballast Electronic ballast<br />

High-pressure sodium<br />

Low-pressure sodium<br />

Metal halide<br />

Fig. N48 : Different power supply modes<br />

4.3 Constraints related to lighting devices and<br />

recommendations<br />

The current actually drawn by luminaires<br />

The risk<br />

This characteristic is the first one that should be defined when creating an<br />

<strong>installation</strong>, otherwise it is highly probable that overload protection devices will trip<br />

and users may <strong>of</strong>ten find themselves in the dark.<br />

It is evident that their determination should take into account the consumption <strong>of</strong><br />

all components, especially for fluorescent lighting <strong>installation</strong>s, since the power<br />

consumed by the ballasts has to be added to that <strong>of</strong> the tubes and bulbs.<br />

The solution<br />

For incandescent lighting, it should be remembered that the line voltage can be more<br />

than 10% <strong>of</strong> its nominal value, which would then cause an increase in the current<br />

drawn.<br />

For fluorescent lighting, unless otherwise specified, the power <strong>of</strong> the magnetic<br />

ballasts can be assessed at 25% <strong>of</strong> that <strong>of</strong> the bulbs. For electronic ballasts, this<br />

power is lower, in the order <strong>of</strong> 5 to 10%.<br />

The thresholds for the overcurrent protection devices should therefore be calculated<br />

as a function <strong>of</strong> the total power and the power factor, calculated for each circuit.<br />

Overcurrents at switch-on<br />

The risk<br />

The devices used for control and protection <strong>of</strong> lighting circuits are those such as<br />

relays, triac, remote-control switches, contactors or circuit-breakers.<br />

The main constraint applied to these devices is the current peak on energization.<br />

This current peak depends on the technology <strong>of</strong> the lamps used, but also on the<br />

<strong>installation</strong> characteristics (supply transformer power, length <strong>of</strong> cables, number <strong>of</strong><br />

lamps) and the moment <strong>of</strong> energization in the line voltage period. A high current<br />

peak, however fleeting, can cause the contacts on an electromechanical control<br />

device to weld together or the destruction <strong>of</strong> a solid state device with semiconductors.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

Two solutions<br />

Because <strong>of</strong> the inrush current, the majority <strong>of</strong> ordinary relays are incompatible with<br />

lighting device power supply. The following recommendations are therefore usually<br />

made:<br />

b Limit the number <strong>of</strong> lamps to be connected to a single device so that their total<br />

power is less than the maximum permissible power for the device<br />

b Check with the manufacturers what operating limits they suggest for the devices.<br />

This precaution is particularly important when replacing incandescent lamps with<br />

compact fluorescent lamps<br />

By way <strong>of</strong> example, the table in Figure N49 indicates the maximum number <strong>of</strong><br />

compensated fluorescent tubes that can be controlled by different devices with<br />

16 A rating. Note that the number <strong>of</strong> controlled tubes is well below the number<br />

corresponding to the maximum power for the devices.<br />

Tube unit power Number <strong>of</strong> tubes Maximum number <strong>of</strong> tubes that can be<br />

requirement corresponding controlled by<br />

(W) to the power Contactors Remote Circuit-<br />

16 A x 230 V GC16 A control breakers<br />

CT16 A switches C60-16 A<br />

TL16 A<br />

18 204 15 50 112<br />

36 102 15 25 56<br />

58 63 10 16 34<br />

Fig. N49 : The number <strong>of</strong> controlled tubes is well below the number corresponding to the<br />

maximum power for the devices<br />

But a technique exists to limit the current peak on energization <strong>of</strong> circuits with<br />

capacitive behavior (magnetic ballasts with parallel compensation and electronic<br />

ballasts). It consists <strong>of</strong> ensuring that activation occurs at the moment when the line<br />

voltage passes through zero. Only solid state switches with semi-conductors <strong>of</strong>fer<br />

this possibility (see Fig. N50a). This technique has proved to be particularly useful<br />

when <strong>design</strong>ing new lighting circuits.<br />

More recently, hybrid technology devices have been developed that combine a solid<br />

state switch (activation on voltage passage through zero) and an electromechanical<br />

contactor short-circuiting the solid state switch (reduction <strong>of</strong> losses in the semiconductors)<br />

(see Fig. N50b).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

a b c<br />

Fig. N50 : “Standard” CT+ contactor [a], CT+ contactor with manual override, pushbutton for<br />

selection <strong>of</strong> operating mode and indicator lamp showing the active operating mode [b], and TL +<br />

remote-control switch [c] (Merlin Gerin brand)<br />

N35<br />

© Schneider Electric - all rights reserved


N36<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Modular contactors and impulse relays do<br />

not use the same technologies. Their rating is<br />

determined according to different standards.<br />

For example, for a given rating, an impulse<br />

relay is more efficient than a modular<br />

contactor for the control <strong>of</strong> light fittings with<br />

a strong inrush current, or with a low power<br />

factor (non-compensated inductive circuit).<br />

Type<br />

<strong>of</strong> lamp<br />

Unit power<br />

and capacitance <strong>of</strong> power factor<br />

correction capacitor<br />

4 Lighting circuits<br />

Choice <strong>of</strong> relay rating according to lamp type<br />

b Figure 51 below shows the maximum number <strong>of</strong> light fittings for each relay,<br />

according to the type, power and configuration <strong>of</strong> a given lamp. As an indication, the<br />

total acceptable power is also mentioned.<br />

b These values are given for a 230 V circuit with 2 active conductors (single-phase<br />

phase/neutral or two-phase phase/phase). For 110 V circuits, divide the values in the<br />

table by 2.<br />

b To obtain the equivalent values for the whole <strong>of</strong> a 230 V three-phase circuit,<br />

multiply the number <strong>of</strong> lamps and the total acceptable power:<br />

v by 3 (1.73) for circuits without neutral;<br />

v by 3 for circuits with neutral.<br />

Note: The power ratings <strong>of</strong> the lamps most commonly used are shown in bold.<br />

Maximum number <strong>of</strong> light fittings for a single-phase circuit<br />

and maximum power output per circuit<br />

TL impulse relay CT contactor<br />

16 A 32 A 16 A 25 A 40 A 63 A<br />

Basic incandescent lamps<br />

LV halogen lamps<br />

Replacement mercury vapour lamps (without ballast)<br />

40 W 40 1500 W 106 4000 W 38 1550 W 57 2300 W 115 4600 W<br />

60 W 25 to 66 to 30 to 45 to 85 to 125<br />

75 W 20 1600 W 53 4200 W 25 2000 W 38 2850 W 70 5250 W 100<br />

100 W 16 42 19 28 50 73<br />

150 W 10 28 12 18 35 50<br />

200 W 8 21 10 14 26 37<br />

300 W 5 1500 W 13 4000 W 7 2100 W 10 3000 W 18 5500 W<br />

500 W 3 8 4 6 10 to 15<br />

1000 W 1 4 2 3 6 6000 W 8<br />

1500 W<br />

ELV 12 or 24 V halogen lamps<br />

1 2 1 2 4 5<br />

With ferromagnetic transformer 20 W 70 1350 W 180 3600 W 15 300 W 23 450 W 42 850 W<br />

50 W 28 to 74 to 10 to 15 to 27 to 42<br />

75 W 19 1450 W 50 3750 W 8 600 W 12 900 W 23 1950 W 35<br />

100 W 14 37 6 8 18 27<br />

With electronic transformer 20 W 60 1200 W 160 3200 W 62 1250 W 90 1850 W 182 3650 W<br />

50 W 25 to 65 to 25 to 39 to 76 to 114<br />

75 W 18 1400 W 44 3350 W 20 1600 W 28 2250 W 53 4200 W 78<br />

100 W<br />

Fluorescent tubes with starter and ferromagnetic ballast<br />

14 33 16 22 42 60<br />

1 tube<br />

15 W 83 1250 W 213 3200 W 22 330 W 30 450 W 70 1050 W<br />

without compensation (1)<br />

18 W<br />

20 W<br />

70<br />

62<br />

to<br />

1300 W<br />

186<br />

160<br />

to<br />

3350 W<br />

22<br />

22<br />

to<br />

850 W<br />

30<br />

30<br />

to<br />

1200 W<br />

70<br />

70<br />

to<br />

2400 W<br />

100<br />

100<br />

36 W 35 93 20 28 60 90<br />

40 W 31 81 20 28 60 90<br />

58 W 21 55 13 17 35 56<br />

65 W 20 50 13 17 35 56<br />

80 W 16 41 10 15 30 48<br />

115 W 11 29 7 10 20 32<br />

1 tube<br />

15 W 5 µF 60 900 W 160 2400 W 15 200 W 20 300 W 40 600 W<br />

with parallel compensation (2) 18 W 5 µF 50 133 15 to 20 to 40 to 60<br />

20 W 5 µF 45 120 15 800 W 20 1200 W 40 2400 W 60<br />

36 W 5 µF 25 66 15 20 40 60<br />

40 W 5 µF 22 60 15 20 40 60<br />

58 W 7 µF 16 42 10 15 30 43<br />

65 W 7 µF 13 37 10 15 30 43<br />

80 W 7 µF 11 30 10 15 30 43<br />

115 W 16 µF 7 20 5 7 14 20<br />

2 or 4 tubes<br />

2 x 18 W 56 2000 W 148 5300 W 30 1100 W 46 1650 W 80 2900 W<br />

with series compensation<br />

4 x 18 W<br />

2 x 36 W<br />

28<br />

28<br />

74<br />

74<br />

16<br />

16<br />

to<br />

1500 W<br />

24<br />

24<br />

to<br />

2400 W<br />

44<br />

44<br />

to<br />

3800 W<br />

68<br />

68<br />

2 x 58 W 17 45 10 16 27 42<br />

2 x 65 W 15 40 10 16 27 42<br />

2 x 80 W 12 33 9 13 22 34<br />

2 x 115 W 8 23 6 10 16 25<br />

Fluorescent tubes with electronic ballast<br />

1 or 2 tubes 18 W 80 1450 W 212 3800 W 74 1300 W 111 2000 W 222 4000 W<br />

36 W 40 to 106 to 38 to 58 to 117 to 176<br />

58 W 26 1550 W 69 4000 W 25 1400 W 37 2200 W 74 4400 W 111<br />

2 x 18 W 40 106 36 55 111 166<br />

2 x 36 W 20 53 20 30 60 90<br />

2 x 58 W 13 34 12 19 38 57<br />

Fig. N51 : Maximum number <strong>of</strong> light fittings for each relay, according to the type, power and configuration <strong>of</strong> a given lamp (Continued on opposite page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

172 6900 W<br />

to<br />

7500 W<br />

25 7500 W<br />

to<br />

8000 W<br />

63 1250 W<br />

to<br />

2850 W<br />

275 5500 W<br />

to<br />

6000 W<br />

100 1500 W<br />

to<br />

3850 W<br />

60 900 W<br />

to<br />

3500 W<br />

123 4450 W<br />

to<br />

5900 W<br />

333 6000 W<br />

to<br />

6600 W


N - Characteristics <strong>of</strong> particular sources and loads<br />

Type<br />

<strong>of</strong> lamp<br />

Unit power<br />

and capacitance <strong>of</strong> power factor<br />

correction capacitor<br />

4 Lighting circuits<br />

Maximum number <strong>of</strong> light fittings for a single-phase circuit<br />

and maximum power output per circuit<br />

TL impulse relay CT contactor<br />

16 A 32 A 16 A 25 A 40 A 63 A<br />

Compact fluorescent lamps<br />

With external electronic ballast 5 W 240 1200 W 630 3150 W 210 1050 W 330 1650 W 670 3350 W not tested<br />

7 W 171 to 457 to 150 to 222 to 478 to<br />

9 W 138 1450 W 366 3800 W 122 1300 W 194 2000 W 383 4000 W<br />

11 W 118 318 104 163 327<br />

18 W 77 202 66 105 216<br />

26 W 55 146 50 76 153<br />

With integral electronic ballast 5 W 170 850 W 390 1950 W 160 800 W 230 1150 W 470 2350 W 710 3550 W<br />

(replacement for incandescent 7 W 121 to 285 to 114 to 164 to 335 to 514 to<br />

lamps)<br />

9 W 100 1050 W 233 2400 W 94 900 W 133 1300 W 266 2600 W 411 3950 W<br />

11 W 86 200 78 109 222 340<br />

18 W 55 127 48 69 138 213<br />

26 W 40 92 34 50 100 151<br />

High-pressure mercury vapour lamps with ferromagnetic ballast without ignitor<br />

Replacement high-pressure sodium vapour lamps with ferromagnetic ballast with integral ignitor (3)<br />

Without compensation (1) 50 W not tested,<br />

15 750 W 20 1000 W 34 1700 W 53 2650 W<br />

80 W infrequent use<br />

10 to 15 to 27 to 40 to<br />

125 / 110 W (3) 8 1000 W 10 1600 W 20 2800 W 28 4200 W<br />

250 / 220 W (3) 4 6 10 15<br />

400 / 350 W (3) 2 4 6 10<br />

700 W 1 2 4 6<br />

With parallel compensation (2) 50 W 7 µF 10 500 W 15 750 W 28 1400 W 43 2150 W<br />

80 W 8 µF 9 to 13 to 25 to 38 to<br />

125 / 110 W (3) 10 µF 9 1400 W 10 1600 W 20 3500 W 30 5000 W<br />

250 / 220 W (3) 18 µF 4 6 11 17<br />

400 / 350 W (3) 25 µF 3 4 8 12<br />

700 W 40 µF 2 2 5 7<br />

1000 W 60 µF 0 1 3 5<br />

Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor<br />

Without compensation (1) 35 W not tested,<br />

5 270 W 9 320 W 14 500 W 24 850 W<br />

55 W infrequent use<br />

5 to 9 to 14 to 24 to<br />

90 W 3 360 W 6 720 W 9 1100 W 19 1800 W<br />

135 W 2 4 6 10<br />

180 W 2 4 6 10<br />

With parallel compensation (2) 35 W 20 µF 38 1350 W 102 3600 W 3 100 W 5 175 W 10 350 W 15 550 W<br />

55 W 20 µF 24 63 3 to 5 to 10 to 15 to<br />

90 W 26 µF 15 40 2 180 W 4 360 W 8 720 W 11 1100 W<br />

135 W 40 µF 10 26 1 2 5 7<br />

180 W 45 µF 7 18 1 2 4 6<br />

High-pressure sodium vapour lamps<br />

Metal-iodide lamps<br />

With ferromagnetic ballast with 35 W not tested,<br />

16 600 W 24 850 W 42 1450 W 64 2250 W<br />

external ignitor, without 70 W infrequent use<br />

8 12 to 20 to 32 to<br />

compensation (1)<br />

150 W 4 7 1200 W 13 2000 W 18 3200 W<br />

250 W 2 4 8 11<br />

400 W 1 3 5 8<br />

1000 W 0 1 2 3<br />

With ferromagnetic ballast with 35 W 6 µF 34 1200 W 88 3100 W 12 450 W 18 650 W 31 1100 W 50 1750 W<br />

external ignitor and parallel 70 W 12 µF 17 to 45 to 6 to 9 to 16 to 25 to<br />

compensation (2)<br />

150 W 20 µF 8 1350 W 22 3400 W 4 1000 W 6 2000 W 10 4000 W 15 6000 W<br />

250 W 32 µF 5 13 3 4 7 10<br />

400 W 45 µF 3 8 2 3 5 7<br />

1000 W 60 µF 1 3 1 2 3 5<br />

2000 W 85 µF 0 1 0 1 2 3<br />

With electronic ballast 35 W 38 1350 W 87 3100 W 24 850 W 38 1350 W 68 2400 W 102 3600 W<br />

70 W 29 to 77 to 18 to 29 to 51 to 76 to<br />

150 W 14 2200 W 33 5000 W 9 1350 W 14 2200 W 26 4000 W 40 6000 W<br />

(1) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number <strong>of</strong> lamps in this<br />

configuration.<br />

(2) The total capacitance <strong>of</strong> the power factor correction capacitors in parallel in a circuit limits the number <strong>of</strong> lamps that can be controlled by a contactor. The total<br />

downstream capacitance <strong>of</strong> a modular contactor <strong>of</strong> rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 µF respectively. Allow for these limits to calculate the<br />

maximum acceptable number <strong>of</strong> lamps if the capacitance values are different from those in the table.<br />

(3) High-pressure mercury vapour lamps without ignitor, <strong>of</strong> power 125, 250 and 400 W, are gradually being replaced by high-pressure sodium vapour lamps with integral<br />

ignitor, and respective power <strong>of</strong> 110, 220 and 350 W.<br />

Fig. N51 : Maximum number <strong>of</strong> light fittings for each relay, according to the type, power and configuration <strong>of</strong> a given lamp (Concluded)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N37<br />

© Schneider Electric - all rights reserved


N38<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Lamp<br />

power (W)<br />

Fig. N52 : Fluorescent tubes with electronic ballast - Vac = 230 V<br />

Protection <strong>of</strong> lamp circuits: Maximum number <strong>of</strong> lamps and MCB rating versus<br />

lamp type, unit power and MCB tripping curve<br />

During start up <strong>of</strong> discharge lamps (with their ballast), the inrush current drawn by<br />

each lamp may be in the order <strong>of</strong>:<br />

b 25 x circuit start current for the first 3 ms<br />

b 7 x circuit start current for the following 2 s<br />

For fluorescent lamps with High Frequency Electronic control ballast, the protective<br />

device ratings must cope with 25 x inrush for 250 to 350 µs.<br />

However due to the circuit resistance the total inrush current seen by the MCB is<br />

lower than the summation <strong>of</strong> all individual lamp inrush current if directly connected to<br />

the MCB.<br />

The tables below (see Fig. N52 to NXX) take into account:<br />

b Circuits cables have a length <strong>of</strong> 20 meters from distribution board to the first lamp<br />

and 7 meters between each additional fittings.<br />

b MCB rating is given to protect the lamp circuit in accordance with the cable cross<br />

section, and without unwanted tripping upon lamp starting.<br />

b MCB tripping curve (C = instantaneous trip setting 5 to 10 In, D = instantaneous<br />

trip setting 10 to 14 In).<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C & D tripping curve<br />

14/18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

14 x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

14 x3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

14 x4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

18 x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

18 x4 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10<br />

21/24 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

21/24 x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

28 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

28 x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

35/36/39 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

35/36 x2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10<br />

38/39 x2 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10<br />

40/42 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

40/42 x2 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 16<br />

49/50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

49/50 x2 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16<br />

54/55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10<br />

54/55 x2 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16<br />

60 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

Lamp<br />

power (W)<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C & D tripping curve<br />

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

11 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

13 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

14 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

15 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

17 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

21 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

23 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10<br />

Fig. N53 : Compact fluorescent lamps - Vac = 230 V<br />

4 Lighting circuits<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

Lamp<br />

power (W)<br />

4 Lighting circuits<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

80 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

125 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20 20<br />

250 6 10 10 16 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 16 20 25 25 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63<br />

1000 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -<br />

MCB rating D tripping curve<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

80 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

125 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16 20 20<br />

250 6 6 10 10 10 10 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63<br />

1000 10 20 25 32 40 40 50 63 63 - - - - - - - - - - -<br />

Fig. N54 : High pressure mercury vapour (with ferromagnetic ballast and PF correction) - Vac = 230 V<br />

Lamp<br />

power (W)<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

Ferromagnetic ballast<br />

18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16 16<br />

131 6 6 6 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20<br />

135 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 20 20 20<br />

180 6 6 10 10 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25<br />

Electronic ballast<br />

36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

91 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 10 16 16 16 16<br />

MCB rating D tripping curve<br />

Ferromagnetic ballast<br />

18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16<br />

131 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16 20<br />

135 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 20 20 20<br />

180 6 6 6 6 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25<br />

Electronic ballast<br />

36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16 16<br />

Fig. N55 : Low pressure sodium (with PF correction) - Vac = 230 V<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N39<br />

© Schneider Electric - all rights reserved


N40<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Lamp<br />

power (W)<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

Ferromagnetic ballast<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

100 6 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16<br />

150 6 6 10 10 10 10 10 10 6 16 16 16 16 16 16 20 20 20 25 25<br />

250 6 10 16 16 16 20 20 20 20 20 20 25 25 25 32 32 32 32 40 40<br />

400 10 16 20 25 32 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63<br />

1000 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -<br />

Electronic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10<br />

100 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16<br />

MCB rating D tripping curve<br />

Ferromagnetic ballast<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

100 6 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16<br />

150 6 6 6 6 6 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25<br />

250 6 6 10 10 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63<br />

1000 10 20 32 32 40 40 50 63 63 - - - - - - - - - - -<br />

Electronic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10<br />

100 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16 16 16<br />

Fig. N56 : High pressure sodium (with PF correction) - Vac = 230 V<br />

Lamp<br />

power (W)<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

Ferromagnetic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

70 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

150 6 6 10 10 10 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25<br />

250 6 10 16 16 16 20 20 20 20 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 16 20 25 25 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63<br />

1000 16 32 40 50 50 50 50 63 63 63 63 63 63 63 63 63 63 63 63 63<br />

1800/2000 25 50 63 63 63 - - - - - - - - - - - - - - -<br />

Electronic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

70 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10<br />

150 6 6 6 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20 20 20<br />

MCB rating D tripping curve<br />

Ferromagnetic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

70 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16<br />

150 6 6 6 6 6 10 10 10 10 16 16 16 16 16 16 20 20 20 25 25<br />

250 6 6 10 10 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63<br />

1000 16 20 32 32 40 50 50 63 63 - - - - - - - - - - -<br />

1800 16 32 40 50 63 63 - - - - - - - - - - - - - -<br />

2000 20 32 40 50 63 - - - - - - - - - - - - - - -<br />

Electronic ballast<br />

35 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

70 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10<br />

150 6 6 6 6 6 6 6 10 10 10 16 16 16 16 16 16 16 20 20 20<br />

Fig. N57 : Metal halide (with PF correction) - Vac = 230 V<br />

Lamp<br />

power (W)<br />

Fig. N58 : Metal halide (with ferromagnetic ballast and PF correction) - Vac = 400 V<br />

4 Lighting circuits<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

1800 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -<br />

2000 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -<br />

MCB rating D tripping curve<br />

1800 16 20 32 32 32 32 50 63 63 - - - - - - - - - - -<br />

2000 16 25 32 32 32 32 50 63 - - - - - - - - - - - -<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

Fig. N60 : s.i. residual current devices with immunity against<br />

impulse currents (Merlin Gerin brand)<br />

4 Lighting circuits<br />

Overload <strong>of</strong> the neutral conductor<br />

The risk<br />

In an <strong>installation</strong> including, for example, numerous fluorescent tubes with electronic<br />

ballasts supplied between phases and neutral, a high percentage <strong>of</strong> 3 rd harmonic<br />

current can cause an overload <strong>of</strong> the neutral conductor. Figure N59 below gives an<br />

overview <strong>of</strong> typical H3 level created by lighting.<br />

Lamp type Typical power Setting mode Typical H3 level<br />

Incandescend lamp 100 W Light dimmer 5 to 45 %<br />

with dimmer<br />

ELV halogen lamp 25 W Electronic ELV 5 %<br />

transformer<br />

Fluorescent tube 100 W Magnetic ballast 10 %<br />

< 25 W Electronic ballast 85 %<br />

> 25 W + PFC 30 %<br />

Discharge lamp 100 W Magnetic ballast 10 %<br />

Electrical ballast 30 %<br />

Fig. N59 : Overview <strong>of</strong> typical H3 level created by lighting<br />

The solution<br />

Firstly, the use <strong>of</strong> a neutral conductor with a small cross-section (half) should be<br />

prohibited, as requested by Installation standard IEC 60364, section 523–5–3.<br />

As far as overcurrent protection devices are concerned, it is necessary to provide<br />

4-pole circuit-breakers with protected neutral (except with the TN-C system for which<br />

the PEN, a combined neutral and protection conductor, should not be cut).<br />

This type <strong>of</strong> device can also be used for the breaking <strong>of</strong> all poles necessary to supply<br />

luminaires at the phase-to-phase voltage in the event <strong>of</strong> a fault.<br />

A breaking device should therefore interrupt the phase and Neutral circuit<br />

simultaneously.<br />

Leakage currents to earth<br />

The risk<br />

At switch-on, the earth capacitances <strong>of</strong> the electronic ballasts are responsible for<br />

residual current peaks that are likely to cause unintentional tripping <strong>of</strong> protection<br />

devices.<br />

Two solutions<br />

The use <strong>of</strong> Residual Current Devices providing immunity against this type <strong>of</strong> impulse<br />

current is recommended, even essential, when equipping an existing <strong>installation</strong><br />

(see Fig. N60).<br />

For a new <strong>installation</strong>, it is sensible to provide solid state or hybrid control devices<br />

(contactors and remote-control switches) that reduce these impulse currents<br />

(activation on voltage passage through zero).<br />

Overvoltages<br />

The risk<br />

As illustrated in earlier sections, switching on a lighting circuit causes a transient state<br />

which is manifested by a significant overcurrent. This overcurrent is accompanied by a<br />

strong voltage fluctuation applied to the load terminals connected to the same circuit.<br />

These voltage fluctuations can be detrimental to correct operation <strong>of</strong> sensitive loads<br />

(micro-computers, temperature controllers, etc.)<br />

The Solution<br />

It is advisable to separate the power supply for these sensitive loads from the lighting<br />

circuit power supply.<br />

Sensitivity <strong>of</strong> lighting devices to line voltage disturbances<br />

Short interruptions<br />

b The risk<br />

Discharge lamps require a relighting time <strong>of</strong> a few minutes after their power supply<br />

has been switched <strong>of</strong>f.<br />

b The solution<br />

Partial lighting with instantaneous relighting (incandescent lamps or fluorescent<br />

tubes, or “hot restrike” discharge lamps) should be provided if safety requirements so<br />

dictate. Its power supply circuit is, depending on current regulations, usually distinct<br />

from the main lighting circuit.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N41<br />

© Schneider Electric - all rights reserved


N42<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

Voltage fluctuations<br />

b The risk<br />

The majority <strong>of</strong> lighting devices (with the exception <strong>of</strong> lamps supplied by electronic<br />

ballasts) are sensitive to rapid fluctuations in the supply voltage. These fluctuations<br />

cause a flicker phenomenon which is unpleasant for users and may even cause<br />

significant problems. These problems depend on both the frequency <strong>of</strong> variations<br />

and their magnitude.<br />

Standard IEC 61000-2-2 (“compatibility levels for low-frequency conducted<br />

disturbances”) specifies the maximum permissible magnitude <strong>of</strong> voltage variations as<br />

a function <strong>of</strong> the number <strong>of</strong> variations per second or per minute.<br />

These voltage fluctuations are caused mainly by high-power fluctuating loads (arc<br />

furnaces, welding machines, starting motors).<br />

b The solution<br />

Special methods can be used to reduce voltage fluctuations. Nonetheless, it is<br />

advisable, wherever possible, to supply lighting circuits via a separate line supply.<br />

The use <strong>of</strong> electronic ballasts is recommended for demanding applications<br />

(hospitals, clean rooms, inspection rooms, computer rooms, etc).<br />

Developments in control and protection equipment<br />

The use <strong>of</strong> light dimmers is more and more common. The constraints on ignition are<br />

therefore reduced and derating <strong>of</strong> control and protection equipment is less important.<br />

New protection devices adapted to the constraints on lighting circuits are being<br />

introduced, for example Merlin Gerin brand circuit-breakers and modular residual<br />

current circuit-breakers with special immunity, such as s.i. type ID switches and<br />

Vigi circuit-breakers. As control and protection equipment evolves, some now <strong>of</strong>fer<br />

remote control, 24-hour management, lighting control, reduced consumption, etc.<br />

4.4 Lighting <strong>of</strong> public areas<br />

Normal lighting<br />

Regulations governing the minimum requirements for buildings receiving the public in<br />

most European countries are as follows:<br />

b Installations which illuminates areas accessible to the public must be controlled<br />

and protected independently from <strong>installation</strong>s providing illumination to other areas<br />

b Loss <strong>of</strong> supply on a final lighting circuit (i.e. fuse blown or CB tripped) must not<br />

result in total loss <strong>of</strong> illumination in an area which is capable <strong>of</strong> accommodating more<br />

than 50 persons<br />

b Protection by Residual Current Devices (RCD) must be divided amongst several<br />

devices (i.e. more than on device must be used)<br />

Emergency lighting and other systems<br />

When we refer to emergency lighting, we mean the auxiliary lighting that is triggered<br />

when the standard lighting fails.<br />

Emergency lighting is subdivided as follows (EN-1838):<br />

Safety lighting<br />

It originates from the emergency lighting and is intended to provide lighting for people to<br />

evacuate an area safely or for those who try to fi nish a potentially dangerous operation before<br />

leaving the area. It is intended to illuminate the means <strong>of</strong> evacuation and ensure continuous<br />

visibility and ready usage in safety when standard or emergency lighting is needed.<br />

Safety lighting may be further subdivided as follows:<br />

Safety lighting for escape routes<br />

It originates from the safety lighting, and is<br />

intended to ensure that the escape means<br />

can be clearly identifi ed and used safely<br />

when the area is busy.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Anti-panic lighting in extended areas<br />

It originates from the safety lighting, and is<br />

intended to avoid panic and to provide the<br />

necessary lighting to allow people to reach<br />

a possible escape route area.<br />

Emergency lighting and safety signs for escape routes<br />

The emergency lighting and safety signs for escape routes are very important for all<br />

those who <strong>design</strong> emergency systems. Their suitable choice helps improve safety<br />

levels and allows emergency situations to be handled better.


N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

Standard EN 1838 ("Lighting applications. Emergency lighting") gives some<br />

fundamental concepts concerning what is meant by emergency lighting for escape<br />

routes:<br />

"The intention behind lighting escape routes is to allow safe exit by the occupants,<br />

providing them with suffi cient visibility and directions on the escape route …"<br />

The concept referred to above is very simple:<br />

The safety signs and escape route lighting must be two separate things.<br />

Functions and operation <strong>of</strong> the luminaires<br />

The manufacturing specifi cations are covered by standard EN 60598-2-22,<br />

"Particular Requirements - Luminaires for Emergency Lighting", which must be read<br />

with EN 60598-1, "Luminaires – Part 1: <strong>General</strong> Requirements and Tests".<br />

Duration<br />

A basic requirement is to determine the duration required for the emergency lighting.<br />

<strong>General</strong>ly it is 1 hour but some countries may have different duration requirements<br />

according to statutory technical standards.<br />

Operation<br />

We should clarify the different types <strong>of</strong> emergency luminaires:<br />

b Non-maintained luminaires<br />

v The lamp will only switch on if there is a fault in the standard lighting<br />

v The lamp will be powered by the battery during failure<br />

v The battery will be automatically recharged when the mains power supply is<br />

restored<br />

b Maintained luminaires<br />

v The lamp can be switched on in continuous mode<br />

v A power supply unit is required with the mains, especially for powering the lamp,<br />

which can be disconnected when the area is not busy<br />

v The lamp will be powered by the battery during failure.<br />

Design<br />

The integration <strong>of</strong> emergency lighting with standard lighting must comply strictly with<br />

<strong>electrical</strong> system standards in the <strong>design</strong> <strong>of</strong> a building or particular place.<br />

All regulations and laws must be complied with in order to <strong>design</strong> a system which is<br />

up to standard (see Fig. N61).<br />

The main functions <strong>of</strong> an emergency lighting system<br />

when standard lighting fails are the following:<br />

b Provide sufficient emergency<br />

lighting along the escape paths<br />

so that people can safely find<br />

their ways to the exits.<br />

Fig. N61 : The main functions <strong>of</strong> an emergency lighting system<br />

European standards<br />

The <strong>design</strong> <strong>of</strong> emergency lighting systems is regulated by a number <strong>of</strong> legislative<br />

provisions that are updated and implemented from time to time by new<br />

documentation published on request by the authorities that deal with European and<br />

international technical standards and regulations.<br />

Each country has its own laws and regulations, in addition to technical standards<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

b Clearly show the escape<br />

route using clear signs.<br />

b Ensure that alarms and<br />

the fire safety equipment<br />

present along the way out<br />

are easily identifiable.<br />

N43<br />

© Schneider Electric - all rights reserved


N44<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

4 Lighting circuits<br />

which govern different sectors. Basically they describe the places that must be<br />

provided with emergency lighting as well as its technical specifi cations. The<br />

<strong>design</strong>er's job is to ensure that the <strong>design</strong> project complies with these standards.<br />

EN 1838<br />

A very important document on a European level regarding emergency lighting is the<br />

Standard EN 1838, "Lighting applications. Emergency lighting".<br />

This standard presents specifi c requirements and constraints regarding the<br />

operation and the function <strong>of</strong> emergency lighting systems.<br />

CEN and CENELEC standards<br />

With the CEN (Comité Européen de Normalisation) and CENELEC standards<br />

(Comité Européen de Normalisation Electrotechnique), we are in a standardised<br />

environment <strong>of</strong> particular interest to the technician and the <strong>design</strong>er. A number<br />

<strong>of</strong> sections deal with emergencies. An initial distinction should be made between<br />

luminaire standards and <strong>installation</strong> standards.<br />

EN 60598-2-22 and EN-60598-1<br />

Emergency lighting luminaires are subject to European standard EN 60598-2-<br />

22, "Particular Requirements - Luminaires for Emergency Lighting", which is an<br />

integrative text (<strong>of</strong> specifi cations and analysis) <strong>of</strong> the Standard EN-60598-1,<br />

Luminaires – "Part 1: <strong>General</strong> Requirements and Tests".<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

The asynchronous (i.e. induction) motor is<br />

robust and reliable, and very widely used.<br />

95% <strong>of</strong> motors installed around the world are<br />

asynchronous. The protection <strong>of</strong> these motors<br />

is consequently a matter <strong>of</strong> great importance<br />

in numerous applications.<br />

td<br />

1 to 10s<br />

20 to<br />

30 ms<br />

t<br />

I" = 8 to 12 In<br />

Id = 5 to 8 In<br />

In = rated current <strong>of</strong> the motor<br />

In Id I"<br />

Fig. N62 : Direct on-line starting current characteristics <strong>of</strong> an<br />

induction motor<br />

I<br />

5 Asynchronous motors<br />

The consequence <strong>of</strong> an incorrectly protected motor can include the following:<br />

b For persons:<br />

v Asphyxiation due to the blockage <strong>of</strong> motor ventilation<br />

v Electrocution due to insulation failure in the motor<br />

v Accident due to non stopping <strong>of</strong> the motor following the failure <strong>of</strong> the control circuit<br />

in case <strong>of</strong> incorrect overcurrent protection<br />

b For the driven machine and the process<br />

v Shaft couplings and axles, etc, damaged due to a stalled rotor<br />

v Loss <strong>of</strong> production<br />

v Manufacturing time delayed<br />

b For the motor<br />

v Motor windings burnt out due to stalled rotor<br />

v Cost <strong>of</strong> dismantling and reinstalling or replacement <strong>of</strong> motor<br />

v Cost <strong>of</strong> repairs to the motor<br />

Therefore, the safety <strong>of</strong> persons and goods, and reliability and availability levels are<br />

highly dependant on the choice <strong>of</strong> protective equipment.<br />

In economic terms, the overall cost <strong>of</strong> failure must be considered. This cost<br />

is increasing with the size <strong>of</strong> the motor and with the difficulties <strong>of</strong> access and<br />

replacement. Loss <strong>of</strong> production is a further, and evidently important factor.<br />

Specific features <strong>of</strong> motor performance influence the power supply circuits required<br />

for satisfactory operation<br />

A motor power-supply circuit presents certain constraints not normally encountered<br />

in other (common) distribution circuits, owing to the particular characteristics, specific<br />

to motors, such as:<br />

b High start-up current (see Fig. N62) which is mostly reactive, and can therefore be<br />

the cause <strong>of</strong> important voltage drop<br />

b Number and frequency <strong>of</strong> start-up operations are generally high<br />

b The high start-up current means that motor overload protective devices must have<br />

operating characteristics which avoid tripping during the starting period<br />

5.1 Functions for the motor circuit<br />

Functions generally provided are:<br />

b Basic functions including:<br />

v Isolating facility<br />

v Motor control (local or remote)<br />

v Protection against short-circuits<br />

v Protection against overload<br />

b Complementary protections including:<br />

v Thermal protection by direct winding temperature measurement<br />

v Thermal protection by indirect winding temperature determination<br />

v Permanent insulation-resistance monitoring<br />

v Specific motor protection functions<br />

b Specific control equipment including:<br />

v Electromechanical starters<br />

v Control and Protective Switching devices (CPS)<br />

v S<strong>of</strong>t-start controllers<br />

v Variable speed drives<br />

Basic functions<br />

Isolating facility<br />

It is necessary to isolate the circuits, partially or totally, from their power supply<br />

network for satety <strong>of</strong> personnel during maintenance work. “Isolation” function is<br />

provided by disconnectors. This function can be included in other devices <strong>design</strong>ed<br />

to provide isolation such as disconnector/circuit-breaker.<br />

Motor control<br />

The motor control function is to make and break the motor current. In case <strong>of</strong> manual<br />

control, this function can be provided by motor-circuit-breakers or switches.<br />

In case <strong>of</strong> remote control, this function can be provided by contactors, starters or CPS.<br />

The control function can also be initiated by other means:<br />

b Overload protection<br />

b Complementary protection<br />

b Under voltage release (needed for a lot <strong>of</strong> machines)<br />

The control function can also be provided by specific control equipment.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N45<br />

© Schneider Electric - all rights reserved


N46<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

5 Asynchronous motors<br />

Protection against short-circuits<br />

b Phase-to-phase short-circuit<br />

This type <strong>of</strong> fault inside the machine is very rare. It is generally due to mechanical<br />

incident <strong>of</strong> the power supply cable <strong>of</strong> the motor.<br />

b Phase-to-earth short-circuit<br />

The deterioration <strong>of</strong> winding insulation is the main cause. The resulting fault current<br />

depends on the system <strong>of</strong> earthing. For the TN system, the resulting fault current is<br />

very high and in most cases the motor will be deteriorated. For the other systems <strong>of</strong><br />

earthing, protection <strong>of</strong> the motor can be achieved by earth fault protection.<br />

For short-circuit protection, it is recommended to pay special attention to avoid<br />

unexpected tripping during the starting period <strong>of</strong> the motor. The inrush current <strong>of</strong> a<br />

standard motor is about 6 to 8 times its rated current but during a fault the current<br />

can be as high as 15 times the rated current. So, the starting current must not be<br />

seen as a fault by the protection. In addition, a fault occuring in a motor circuit must<br />

not disturb any upstream circuit. As a consequence, discrimination/selectivity <strong>of</strong><br />

magnetic protections must be respected with all parts <strong>of</strong> the <strong>installation</strong>.<br />

Protection against overload<br />

Mechanical overloads due to the driven machine are the main origins <strong>of</strong> the overload<br />

for a motor application. They cause overload current and motor overheating. The life<br />

<strong>of</strong> the motor can be reduced and sometimes, the motor can be deteriorated. So, it is<br />

necessary to detect motor overload. This protection can be provided by:<br />

b Specific thermal overload relay<br />

b Specific thermal-magnetic circuit-breaker commonly referred to as “motor circuitbreaker”<br />

b Complementary protection (see below) like thermal sensor or electronic<br />

multifunction relay<br />

b Electronic s<strong>of</strong>t start controllers or variable speed drives (see below)<br />

Complementary protections<br />

b Thermal protection by direct winding temperature measurement<br />

Provided by thermal sensors incorporated inside the windings <strong>of</strong> the motor and<br />

associated relays.<br />

b Thermal protection by indirect winding temperature determination<br />

Provided by multifunction relays through current measurement and taking into<br />

account the characteristics <strong>of</strong> the motors (e.g.: thermal time constant).<br />

b Permanent insulation-resistance monitoring relays or residual current differential<br />

relays<br />

They provide detection and protection against earth leakage current and short-circuit<br />

to earth, allowing maintenance operation before destruction <strong>of</strong> the motor.<br />

b Specific motor protection functions<br />

Such as protection against too long starting period or stalled rotor, protection<br />

against unbalanced, loss or permutation <strong>of</strong> phases, earth fault protection, no load<br />

protection, rotor blocked (during start or after)…; pre alarm overheating indication,<br />

communication, can also be provided by multifunction relays.<br />

Specific control equipment<br />

b Electromechanical starters (star-delta, auto-transformer, rheostatic rotor<br />

starters,…)<br />

They are generally used for application with no load during the starting period (pump,<br />

fan, small centrifuge, machine-tool, etc.)<br />

v Advantages<br />

Good torque/current ratio; great reduction <strong>of</strong> inrush current.<br />

v Disadvantages<br />

Low torque during the starting period; no easy adjustment; power cut <strong>of</strong>f during the<br />

transition and transient phenomenon; 6 motor connection cables needed.<br />

b Control and Protective Switching devices (CPS)<br />

They provide all the basic functions listed before within a single unit and also some<br />

complementary functions and the possibility <strong>of</strong> communication. These devices also<br />

provide continuity <strong>of</strong> service in case <strong>of</strong> short-circuit.<br />

b S<strong>of</strong>t-start controllers<br />

Used for applications with pump, fan, compressor, conveyor.<br />

v Advantages<br />

Reduced inrush current, voltage drop and mechanical stress during the motor start;<br />

built-in thermal protection; small size device; possibility <strong>of</strong> communication<br />

v Disadvantages<br />

Low torque during the starting period; thermal dissipation.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

5 Asynchronous motors<br />

b Variable speed drives<br />

They are used for applications with pump, fan, compressor, conveyor, machine with<br />

high load torque, machine with high inertia.<br />

v Advantages<br />

Continuous speed variation (adjustment typically from 2 to 130% <strong>of</strong> nominal speed),<br />

overspeed is possible; accurate control <strong>of</strong> acceleration and deceleration; high<br />

torque during the starting and stopping periods; low inrush current, built-in thermal<br />

protection, possibility <strong>of</strong> communication.<br />

v Disadvantages<br />

Thermal dissipation, volume, cost.<br />

5.2 Standards<br />

The motor control and protection can be achieved in different way:<br />

b By using an association <strong>of</strong> a SCPD (Short-Circuit-Protective-Device) and<br />

electromechanical devices such as<br />

v An electromechanical starters fulfilling the standard IEC 60947-4-1<br />

v A semiconductor starter fulfilling the standard IEC 60947-4-2<br />

v A variable speed drives fulfilling the standard series IEC 61800<br />

b By using a CPS, single device covering all the basic functions, and fulfilling the<br />

standard IEC 60947-6-2<br />

In this document, only the motor circuits including association <strong>of</strong> electromechanical<br />

devices such as, starters and protection against short-circuit, are considered. The<br />

devices meeting the standard 60947-6-2, the semiconductor starters and the variable<br />

speed drives will be considered only for specific points.<br />

A motor circuit will meet the <strong>rules</strong> <strong>of</strong> the IEC 60947-4-1 and mainly:<br />

b The co-ordination between the devices <strong>of</strong> the motor circuit<br />

b The tripping class <strong>of</strong> the thermal relays<br />

b The category <strong>of</strong> utilization <strong>of</strong> the contactors<br />

b The insulation co-ordination<br />

Note: The first and last points are satisfied inherently by the devices meeting the<br />

IEC 60947-6-2 because they provide a continuity <strong>of</strong> service.<br />

Standardization <strong>of</strong> the association circuit-breaker + contactor<br />

+ thermal relay<br />

Utilization category <strong>of</strong> the contactors<br />

Standard IEC 60947-4-1 gives utilization categories which considerably facilitate<br />

the choice <strong>of</strong> a suitable contactor for a given service duty. The utilization categories<br />

advise on:<br />

b A range <strong>of</strong> functions for which the contactor must be adapted<br />

b The required current breaking and making capabilities<br />

b Standard values for on-load durability tests, according to the utilization category.<br />

Figure N63 gives some typical examples <strong>of</strong> the utilization categories covered.<br />

Utilization category Application characteristics<br />

AC-1 Non-inductive (or slightly inductive) loads:<br />

cos ϕ u 0.95 (heating, distribution)<br />

AC-2 Starting and switching <strong>of</strong>f <strong>of</strong> slip-ring motors<br />

AC-3 Cage motors: Starting, and switching <strong>of</strong>f motors<br />

during running<br />

AC-4 Cage motors: Starting, plugging, inching<br />

Fig. N63 : Utilization categories for contactors<br />

Note: These utilization categories are adapted to the devices meeting the other<br />

standards. For example AC-3 becomes AC-53 for the semiconductor starters<br />

(IEC 60947-4-2) and becomes AC-43 for CPS’s (IEC 60947-6-2).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N47<br />

© Schneider Electric - all rights reserved


N48<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Among the many possible methods <strong>of</strong><br />

protecting a motor, the association <strong>of</strong> a<br />

circuit breaker + contactor + thermal relay (1)<br />

provides many advantages<br />

(1) The combination <strong>of</strong> a contactor with a thermal relay is<br />

commonly referred to as a “discontactor”<br />

5 Asynchronous motors<br />

The types <strong>of</strong> co-ordination<br />

For each association <strong>of</strong> devices, a type <strong>of</strong> co-ordination is given, according to the<br />

state <strong>of</strong> the constituant parts following a circuit-breaker trip out on fault, or the<br />

opening <strong>of</strong> a contactor on overload.<br />

The standard IEC 947-4-1 defines two types <strong>of</strong> co-ordination, type 1 and type 2,<br />

which set maximum allowable limits <strong>of</strong> deterioration <strong>of</strong> switchgear, in case <strong>of</strong> shortcircuit.<br />

Whatever the type <strong>of</strong> co-ordination, it is required that the contactor or the starter must<br />

never present a danger for the personnel and for the <strong>installation</strong>. The specificities <strong>of</strong><br />

each type are:<br />

b Type 1<br />

Deterioration <strong>of</strong> the starter is acceptable after a short-circuit and the operation <strong>of</strong> the<br />

starter may be recovered after reparing or replacing some parts.<br />

b Type 2<br />

Burning and the risk <strong>of</strong> welding <strong>of</strong> the contacts <strong>of</strong> the contactor are the only risks<br />

allowed.<br />

Which type to choose?<br />

The type <strong>of</strong> co-ordination to adopt depends on the parameters <strong>of</strong> exploitation and must<br />

be chosen to satisfy (optimally) the needs <strong>of</strong> the user and the cost <strong>of</strong> <strong>installation</strong>.<br />

b Type 1<br />

v Qualified maintenance service<br />

v Volume and cost <strong>of</strong> switchgear reduced<br />

v May not be suitable for further service without repair or replacement <strong>of</strong> parts after<br />

a short-circuit<br />

b Type 2<br />

v Only light maintenance measures for further use after a short-circuit<br />

5.3 Applications<br />

The control and protection <strong>of</strong> a motor can consist <strong>of</strong> one, two, three or four different<br />

devices which provide one or several functions.<br />

In the case <strong>of</strong> the combination <strong>of</strong> several devices, co-ordination between them<br />

is essential in order to provide optimized protection <strong>of</strong> the motor application.<br />

To protect a motor circuit, many parameters must be taken into account. They<br />

depend on:<br />

b The application (type <strong>of</strong> driven machine, safety <strong>of</strong> operation, number <strong>of</strong> operations,<br />

etc.)<br />

b The continuity performance requested by the application<br />

b The standards to be enforced to provide security and safety.<br />

The <strong>electrical</strong> functions to be provided are quite different:<br />

b Start, normal operation and stop without unexpected tripping while maintaining<br />

control requirements, number <strong>of</strong> operations, durability and safety requirements<br />

(emergency stops), as well as circuit and motor protection, disconnection (isolation)<br />

for safety <strong>of</strong> personnel during maintenance work.<br />

Basic protection schemes: circuit-breaker + contactor<br />

+ thermal relay<br />

Avantages<br />

The combination <strong>of</strong> devices facilitates <strong>installation</strong> work, as well as operation and<br />

maintenance, by:<br />

b The reduction <strong>of</strong> the maintenance work load: the circuit-breaker avoids the need to<br />

replace blown fuses and the necessity <strong>of</strong> maintaining a stock (<strong>of</strong> different sizes and<br />

types)<br />

b Better continuity performance: the <strong>installation</strong> can be re-energized immediately<br />

following the elimination <strong>of</strong> a fault and after checking <strong>of</strong> the starter<br />

b Additional complementary devices sometimes required on a motor circuit are<br />

easily accomodated<br />

b Tripping <strong>of</strong> all three phases is assured (thereby avoiding the possibility <strong>of</strong> “single<br />

phasing”)<br />

b Full load current switching possibility (by circuit-breaker) in the event <strong>of</strong> contactor<br />

failure, e.g. contact welding<br />

b Interlocking<br />

b Diverse remote indications<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

Circuit<br />

breaker<br />

Magnetic<br />

relay<br />

Contactor<br />

Thermal<br />

relay<br />

Cable<br />

Motor<br />

End <strong>of</strong><br />

start-up<br />

period<br />

1 to<br />

10 s<br />

20 to<br />

30 ms<br />

Fig. N64 : Tripping characteristics <strong>of</strong> a circuit-breaker + contactor + thermal relay (1)<br />

(1) In the majority <strong>of</strong> cases, short-circuit faults occur at the<br />

motor, so that the current is limited by the cable and the wiring<br />

<strong>of</strong> the starter and are called impedant short-circuits<br />

t<br />

In Is<br />

5 Asynchronous motors<br />

b Better protection for the starter in case <strong>of</strong> overcurrent and in particular for impedant<br />

short-circuit (1) corresponding to currents up to about 30 times In <strong>of</strong> motor (see Fig. N64).<br />

b Possibility <strong>of</strong> adding RCD:<br />

v Prevention <strong>of</strong> risk <strong>of</strong> fire (sensitivity 500 mA)<br />

v Protection against destruction <strong>of</strong> the motor (short-circuit <strong>of</strong> laminations) by the<br />

early detection <strong>of</strong> earth fault currents (sensitivity 300 mA to 30 A)<br />

I" magn.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

1.05 to 1.20 In<br />

Operating curve<br />

<strong>of</strong> thermal relay<br />

Cable thermal withstand limit<br />

Limit <strong>of</strong> thermal relay constraint<br />

Short circuit current breaking capacity<br />

<strong>of</strong> the association (CB + contactor)<br />

Operating curve <strong>of</strong> the<br />

MA type circuit breaker<br />

I<br />

Short circuit current breaking capacity<br />

<strong>of</strong> the CB<br />

Conclusion<br />

The combination <strong>of</strong> a circuit-breaker + contactor + thermal relay for the control and<br />

protection <strong>of</strong> motor circuits is eminently appropriate when:<br />

b The maintenance service for an <strong>installation</strong> is reduced, which is generally the case<br />

in tertiary and small and medium sized industrial sites<br />

b The job specification calls for complementary functions<br />

b There is an operational requirement for a load breaking facility in the event <strong>of</strong> need<br />

<strong>of</strong> maintenance.<br />

Key points in the successful combination <strong>of</strong> a circuit-breaker<br />

and a discontactor<br />

Standards define precisely the elements which must be taken into account to<br />

achieve a correct coordination <strong>of</strong> type 2:<br />

b Absolute compatibility between the thermal relay <strong>of</strong> the discontactor and the<br />

magnetic trip <strong>of</strong> the circuit-breaker. In Figure N65 the thermal relay is protected if<br />

its limit boundary for thermal withstand is placed to the right <strong>of</strong> the circuit-breaker<br />

magnetic trip characteristic curve. In the case <strong>of</strong> a motor control circuit-breaker<br />

incorporating both magnetic and thermal relay devices, coordination is provided by<br />

<strong>design</strong>.<br />

Compact<br />

type MA<br />

Icc ext.<br />

t<br />

2<br />

1<br />

1 Operating curve <strong>of</strong> the MA type circuit breaker<br />

2 Operating curve <strong>of</strong> thermal relay<br />

3 Limit <strong>of</strong> thermal relay constraint<br />

Fig. N65 : The thermal-withstand limit <strong>of</strong> the thermal relay must be to the right <strong>of</strong> the CB<br />

magnetic-trip characteristic<br />

3<br />

I<br />

N49<br />

© Schneider Electric - all rights reserved


N50<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

It is not possible to predict the short-circuit<br />

current-breaking capacity <strong>of</strong> a circuit-breaker<br />

+ contactor combination. Only laboratory tests<br />

by manufacturers allow to do it. So, Schneider<br />

Electric can give table with combination <strong>of</strong><br />

Multi 9 and Compact type MA circuit-breakers<br />

with different types <strong>of</strong> starters<br />

M<br />

Fig. N66 : Circuit-breaker and contactor mounted side by side<br />

M<br />

Fig. N67 : Circuit-breaker and contactor mounted separately<br />

Fig. N68 : Overheating protection by thermal sensors<br />

5 Asynchronous motors<br />

b The overcurrent breaking capability <strong>of</strong> the contactor must be greater than the<br />

current corresponding to the setting <strong>of</strong> the circuit-breaker magnetic trip relay.<br />

b When submitted to a short-circuit current, the contactor and its thermal relay must<br />

perform in accordance with the requirements corresponding to the specified type <strong>of</strong><br />

co-ordination.<br />

Short-circuit current-breaking capacity <strong>of</strong> a circuit-breaker<br />

+ contactor combination<br />

At the selection stage, the short-circuit current-breaking capacity which must be<br />

compared to the prospective short-circuit current is:<br />

b Either, that <strong>of</strong> the circuit-breaker + contactor combination if the circuit-breaker<br />

and the contactor are physically close together (see Fig. N66) (same drawer or<br />

compartment <strong>of</strong> a motor control cabinet). A short-circuit downstream <strong>of</strong> the<br />

combination will be limited to some extent by the impedances <strong>of</strong> the contactor and<br />

the thermal relay. The combination can therefore be used on a circuit for which<br />

the prospective short-circuit current level exceeds the rated short-circuit currentbreaking<br />

capacity <strong>of</strong> the circuit-breaker. This feature very <strong>of</strong>ten presents a significant<br />

economic advantage<br />

b Or that <strong>of</strong> the circuit-breaker only, for the case where the contactor is separated<br />

(see Fig. N67) with the risk <strong>of</strong> short-circuit between the contactor and the circuitbreaker.<br />

Choice <strong>of</strong> instantaneous magnetic-trip relay for the circuitbreaker<br />

The operating threshold must never be less than 12 In for this relay, in order to avoid<br />

unexpected tripping due to the first current peak during motor starting.<br />

Complementary protections<br />

Complementary protections are:<br />

b Thermal sensors in the motor (windings, bearings, cooling-air ducts, etc.)<br />

b Multifunction protections (association <strong>of</strong> functions)<br />

b Insulation-failure detection devices on running or stationary motor<br />

Thermal sensors<br />

Thermal sensors are used to detect abnormal temperature rise in the motor by direct<br />

measurement. The thermal sensors are generally embedded in the stator windings<br />

(for LV motors), the signal being processed by an associated control device acting to<br />

trip the contactor or the circuit-breaker (see Fig. N68).<br />

Mutifunction motor protection relay<br />

The multifunction relay, associated with a number <strong>of</strong> sensors and indication modules,<br />

provides protection for motor and also for some functions, protection <strong>of</strong> the driven<br />

machine such as:<br />

b Thermal overload<br />

b Stalled rotor, or starting period too long<br />

b Overheating<br />

b Unbalanced phase current, loss <strong>of</strong> one phase, inverse rotation<br />

b Earth fault (by RCD)<br />

b Running at no-load, blocked rotor on starting<br />

The avantages are essentially:<br />

b A comprehensive protection, providing a reliable, high performance and permanent<br />

monitoring/control function<br />

b Efficient monitoring <strong>of</strong> all motor-operating schedules<br />

b Alarm and control indications<br />

b Possibility <strong>of</strong> communication via communication buses<br />

Example: Telemecanique LT6 relay with permanent monitoring/control function<br />

and communication by bus, or multifunction control unit LUCM and communication<br />

module for TeSys model U.<br />

Preventive protection <strong>of</strong> stationary motors<br />

This protection concerns the monitoring <strong>of</strong> the insulation resistance level <strong>of</strong> a<br />

stationary motor, thereby avoiding the undesirable consequences <strong>of</strong> insulation failure<br />

during operation such as:<br />

b Failure to start or to perform correctly for motor used on emergency systems<br />

b Loss <strong>of</strong> production<br />

This type <strong>of</strong> protection is essential for emergency systems motors, especially when<br />

installed in humid and/or dusty locations. Such protection avoids the destruction <strong>of</strong><br />

a motor by short-circuit to earth during starting (one <strong>of</strong> the most frequently-occuring<br />

incidents) by giving a warning informing that maintenance work is necessary to<br />

restore the motor to a satisfactory operationnal condition.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


N - Characteristics <strong>of</strong> particular sources and loads<br />

5 Asynchronous motors<br />

Example <strong>of</strong> application:<br />

Motors driving pumps for “sprinklers” fire-protection systems or irrigation pumps for<br />

seasonal operation.<br />

A Vigilohm SN21 (Merlin Gerin) monitors the insulation <strong>of</strong> a motor, and signals<br />

audibly and visually any abnormal reduction <strong>of</strong> the insulation resistance level.<br />

Furthermore, this relay can prevent any attempt to start the motor, if necessary<br />

(see Fig. N69).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

SM21<br />

MERLIN GERIN<br />

Fig. N69 : Preventive protection <strong>of</strong> stationary motors<br />

Fig. N70 : Example using relay RH99M<br />

RH99M<br />

SM20<br />

M E R L IN G E R IN<br />

IN OUT<br />

Limitative protections<br />

Residual current diffential protective devices (RCDs) can be very sensitive and<br />

detect low values <strong>of</strong> leakage current which occur when the insulation to earth <strong>of</strong> an<br />

<strong>installation</strong> deteriorates (by physical damage, contamination, excessive humidity,<br />

and so on). Some versions <strong>of</strong> RCDs, with dry contacts, specially <strong>design</strong>ed for such<br />

applications, provide the following:<br />

b To avoid the destruction <strong>of</strong> a motor (by perforation and short-circuiting <strong>of</strong> the<br />

laminations <strong>of</strong> the stator) caused by an eventual arcing fault to earth. This protection<br />

can detect incipient fault conditions by operating at leakage currents in the range <strong>of</strong><br />

300 mA to 30 A, according to the size <strong>of</strong> the motor (approx sensitivity: 5% In)<br />

b To reduce the risk <strong>of</strong> fire: sensitivity y 500 mA<br />

For example, RH99M relay (Merlin Gerin) provides (see Fig. N70):<br />

b 5 sensitivities (0.3; 1; 3; 10; 30 A)<br />

b Possibility <strong>of</strong> discrimination or to take account <strong>of</strong> particular operation by virtue <strong>of</strong> 3<br />

possible time delays (0, 90, 250 ms)<br />

b Automatic breaking if the circuit from the current transformer to the relay is broken<br />

b Protection against unwanted trippings<br />

b Protection against DC leakage currents (type A RCD)<br />

N51<br />

© Schneider Electric - all rights reserved


N52<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

5 Asynchronous motors<br />

The importance <strong>of</strong> limiting the voltage drop at the motor terminals during<br />

start-up<br />

In order to have a motor starting and accelerating to its normal speed in the<br />

appropriate time, the torque <strong>of</strong> the motor must exceed the load torque by at least<br />

70%. However, the starting current is much higher than the full-load current <strong>of</strong><br />

the motor. As a result, if the voltage drop is very high, the motor torque will be<br />

excessively reduced (motor torque is proportional to U 2 ) and it will result, for extreme<br />

case, in failure to start.<br />

Example:<br />

b With 400 V maintained at the terminals <strong>of</strong> a motor, its torque would be 2.1 times<br />

that <strong>of</strong> the load torque<br />

b For a voltage drop <strong>of</strong> 10% during start-up, the motor torque would be<br />

2.1 x 0.9 2 = 1.7 times the load torque, and the motor would accelerate to its rated<br />

speed normally<br />

b For a voltage drop <strong>of</strong> 15% during start-up, the motor torque would be<br />

2.1 x 0.85 2 = 1.5 times the load torque, so that the motor starting time would<br />

be longer than normal<br />

In general, a maximum allowable voltage drop <strong>of</strong> 10% is recommended during<br />

start-up <strong>of</strong> the motor.<br />

5.4 Maximum rating <strong>of</strong> motors installed for<br />

consumers supplied at LV<br />

The disturbances caused on LV distribution networks during the start-up <strong>of</strong> large<br />

direct-on-line AC motors can cause considerable nuisance to neighbouring<br />

consumers, so that most power-supply utilities have strict <strong>rules</strong> intended to limit such<br />

disturbances to tolerable levels. The amount <strong>of</strong> disturbance created by a given motor<br />

depends on the “strength” <strong>of</strong> the network, i.e. on the short-circuit fault level at the<br />

point concerned. The higher the fault level, the “stronger” the system and the lower<br />

the disturbance (principally voltage drop) experienced by neibouring consumers. For<br />

distribution networks in many countries, typical values <strong>of</strong> maximum allowable starting<br />

currents and corresponding maximum power ratings for direct-on-line motors are<br />

shown in Figures N71 and N72 below.<br />

Type <strong>of</strong> motor Location Maximum starting current (A)<br />

Overhead-line network Underground-cable network<br />

Single phase Dwellings 45 45<br />

Others 100 200<br />

Three phase Dwellings 60 60<br />

Others 125 250<br />

Fig. N71 : Maximum permitted values <strong>of</strong> starting current for direct-on-line LV motors (230/400 V)<br />

Location Type <strong>of</strong> motor<br />

Single phase 230 V Three phase 400 V<br />

(kW) Direct-on-line starting Other methods<br />

at full load (kW) <strong>of</strong> starting (kW)<br />

Dwellings 1.4 5.5 11<br />

Others Overhead 3 11 22<br />

line network<br />

Underground 5.5 22 45<br />

cable network<br />

Fig. N72 : Maximum permitted power ratings for LV direct-on-line starting motors<br />

Since, even in areas supplied by one power utility only, “weak” areas <strong>of</strong> the network<br />

exist as well as “strong” areas, it is always advisable to secure the agreement <strong>of</strong> the<br />

power supplier before acquiring the motors for a new project.<br />

Other (but generally more costly) alternative starting arrangements exist, which<br />

reduce the large starting currents <strong>of</strong> direct-on-line motors to acceptable levels; for<br />

example, star-delta starters, slip-ring motor, “s<strong>of</strong>t start” electronic devices, etc.<br />

5.5 Reactive-energy compensation (power-factor<br />

correction)<br />

The method to correct the power factor is indicated in chapter L.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


2<br />

3<br />

<strong>Chapter</strong> P<br />

Residential and other special<br />

locations<br />

Contents<br />

Residential and similar premises P<br />

1.1 <strong>General</strong> P1<br />

1.2 Distribution boards components P1<br />

1.3 Protection <strong>of</strong> people P4<br />

1.4 Circuits P6<br />

1.5 Protection against overvoltages and lightning P7<br />

Bathrooms and showers P8<br />

2.1 Classification <strong>of</strong> zones P8<br />

2.2 Equipotential bonding P11<br />

2.3 Requirements prescribed for each zone P11<br />

Recommendations applicable to special <strong>installation</strong>s P 2<br />

and locations<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

P<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

P2<br />

P - Residential and other special locations<br />

Electrical <strong>installation</strong>s for residential premises<br />

need a high standard <strong>of</strong> safety and reliability<br />

The power distribution utility connects the LV<br />

neutral point to its MV/LV distribution tranformer<br />

to earth.<br />

All LV <strong>installation</strong>s must be protected by RCDs.<br />

All exposed conductive parts must be bonded<br />

together and connected to the earth.<br />

The quality <strong>of</strong> <strong>electrical</strong> equipment used in<br />

residential premises is commonly ensured by a<br />

mark <strong>of</strong> conformity situated on the front <strong>of</strong> each<br />

item<br />

Fig. P1 : Presentation <strong>of</strong> realizable functions on a consumer unit<br />

Enclosure<br />

Residential and similar premises<br />

. <strong>General</strong><br />

Related standards<br />

Most countries have national regulations and-or standards governing the <strong>rules</strong><br />

to be strictly observed in the <strong>design</strong> and realization <strong>of</strong> <strong>electrical</strong> <strong>installation</strong>s for<br />

residential and similar premises. The relevant international standard is the publication<br />

IEC 60364.<br />

The power network<br />

The vast majority <strong>of</strong> power distribution utilities connect the low voltage neutral point<br />

<strong>of</strong> their MV/LV distribution transformers to earth.<br />

The protection <strong>of</strong> persons against electric shock therefore depends, in such case, on<br />

the principle discussed in chapter F. The measures required depend on whether the<br />

TT, TN or IT scheme <strong>of</strong> earthing is adopted.<br />

RCDs are essential for TT and IT earthed <strong>installation</strong>s. For TN <strong>installation</strong>s, high<br />

speed overcurrent devices or RCDs may provide protection against direct contact<br />

<strong>of</strong> the <strong>electrical</strong> circuits. To extend the protection to flexible leads beyond the fixed<br />

socket outlets and to ensure protection against fires <strong>of</strong> <strong>electrical</strong> origin RCDs shall<br />

be installed.<br />

.2 Distribution boards components (see Fig. P )<br />

Distribution boards (generally only one in residential premises) usually include<br />

the meter(s) and in some cases (notably where the supply utilities impose a TT<br />

earthing system and/or tariff conditions which limit the maximum permitted current<br />

consumption) an incoming supply differential circuit-breaker which includes an<br />

overcurrent trip. This circuit-breaker is freely accessible to the consumer.<br />

Service connection<br />

Lightning protection<br />

Overcurrent<br />

protection<br />

and isolation<br />

Protection against<br />

direct and indirect<br />

contact,<br />

and protection<br />

against fire<br />

Remote control<br />

Energy management<br />

Incoming-supply<br />

circuit breaker<br />

MCB phase and neutral<br />

Remote control switch<br />

TL 16 A<br />

Programmable thermostat<br />

THP<br />

Programmable time switch<br />

IHP<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Differential<br />

MCB<br />

Distribution board<br />

Combi surge arrester<br />

Differential load<br />

switch<br />

Load shedding switch<br />

CDSt<br />

Contactors, <strong>of</strong>f-peak<br />

or manual control CT


P - Residential and other special locations<br />

Fig. P3 : Incoming-supply circuit-breaker<br />

Fig. P4 : Control and distribution board<br />

If, in a TT scheme, the value <strong>of</strong> 80 Ω for the<br />

resistance <strong>of</strong> the electrode can not be met then,<br />

30 mA RCDs must be installed to take over the<br />

function <strong>of</strong> the earth leakage protection <strong>of</strong> the<br />

incoming supply circuit-breaker<br />

Residential and similar premises<br />

On <strong>installation</strong>s which are TN earthed, the supply utilities usually protect the<br />

<strong>installation</strong> simply by means <strong>of</strong> sealed fuse cut-outs immediately upstream <strong>of</strong> the<br />

meter(s) (see Fig. P2). The consumer has no access to these fuses.<br />

Fuse … or …<br />

The incoming supply circuit-breaker (see Fig. P3)<br />

The consumer is allowed to operate this CB if necessary (e.g to reclose it if the<br />

current consumption has exceeded the authorized limit; to open it in case <strong>of</strong><br />

emergency or for isolation purposes).<br />

The rated residual current <strong>of</strong> the incoming circuit-breaker in the earth leakage<br />

protection shall be 300 mA.<br />

If If the <strong>installation</strong> is TT, the earth electrode resistance shall be less than<br />

50 V<br />

R<br />

300 mA 166<br />

� � � .. . In practice, the earth electrode resistance <strong>of</strong> a new <strong>installation</strong><br />

shall be less than 80 Ω Ω� Ω ( R<br />

2 )..<br />

The control and distribution board (consumer unit) (see Fig. P4)<br />

This board comprises:<br />

b A control panel for mounting (where appropriate) the incoming supply circuitbreaker<br />

and other control auxiliaries, as required<br />

b A distribution panel for housing 1, 2 or 3 rows (<strong>of</strong> 24 multi 9 units) or similar MCBs<br />

or fuse units, etc.<br />

b Installation accessories for fixing conductors, and rails for mounting MCBs, fuses<br />

bases, etc, neutral busbar and earthing bar, and so on<br />

b Service cable ducts or conduits, surface mounted or in cable chases embedded in<br />

the wall<br />

Note: to facilitate future modifications to the <strong>installation</strong>, it is recommended to keep<br />

all relevant documents (photos, diagrams, characteristics, etc.) in a suitable location<br />

close to the distribution board.<br />

The board should be installed at a height such that the operating handles,<br />

indicating dials (<strong>of</strong> meters) etc., are between 1 metre and 1.80 metres from the floor<br />

(1.30 metres in situations where handicapped or elderly people are concerned).<br />

Lightning arresters<br />

The <strong>installation</strong> <strong>of</strong> lightning arresters at the service position <strong>of</strong> a LV <strong>installation</strong> is<br />

strongly recommended for <strong>installation</strong>s which include sensitive (e.g electronic)<br />

equipment.<br />

These devices must automatically disconnect themselves from the <strong>installation</strong> in<br />

case <strong>of</strong> failure or be protected by a MCB. In the case <strong>of</strong> residential <strong>installation</strong>s, the<br />

use <strong>of</strong> a 300 mA differential incoming supply circuit-breaker type S (i.e slightly timedelayed)<br />

will provide effective earth leakage protection, while, at the same time, will<br />

not trip unnecessarily each time a lightning arrester discharges the current (<strong>of</strong> an<br />

overvoltage-surge) to earth.<br />

Resistance value <strong>of</strong> the earth electrode<br />

In the case where the resistance to earth exceeds 80 Ω, one or several 30 mA RCDs<br />

should be used in place <strong>of</strong> the earth leakage protection <strong>of</strong> the incoming supply<br />

circuit-breaker.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Meter<br />

Circuit breaker<br />

depending on<br />

earthing system<br />

Fig. P2 : Components <strong>of</strong> a control and distribution board<br />

Distribution<br />

board<br />

P3<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

P4<br />

P - Residential and other special locations<br />

Where utility power supply systems and<br />

consumers’ <strong>installation</strong>s form a TT earthed<br />

system, the governing standards impose the use<br />

<strong>of</strong> RCDs to ensure the protection <strong>of</strong> persons<br />

Residential and similar premises<br />

.3 Protection <strong>of</strong> people<br />

On TT earthed systems, the protection <strong>of</strong> persons is ensured by the following<br />

measures:<br />

b Protection against indirect contact hazards by RCDs (see Fig. P5) <strong>of</strong> medium<br />

sensitivity (300 mA) at the origin <strong>of</strong> the <strong>installation</strong> (incorporated in the incoming<br />

supply circuit-breaker or, on the incoming feed to the distribution board). This<br />

measure is associated with a consumer installed earth electrode to which must be<br />

connected the protective earth conductor (PE) from the exposed conductive parts <strong>of</strong><br />

all class I insulated appliances and equipment, as well as those from the earthing<br />

pins <strong>of</strong> all socket outlets<br />

b When the CB at the origin <strong>of</strong> an <strong>installation</strong> has no RCD protection, the protection<br />

<strong>of</strong> persons shall be ensured by class II level <strong>of</strong> insulation on all circuits upstream<br />

<strong>of</strong> the first RCDs. In the case where the distribution board is metallic, care shall be<br />

taken that all live parts are double insulated (supplementary clearances or insulation,<br />

use <strong>of</strong> covers, etc.) and wiring reliably fixed<br />

b Obligatory protection by 30 mA sensitive RCDs <strong>of</strong> socket outlet circuits, and<br />

circuits feeding bathroom, laundry rooms, and so on (for details <strong>of</strong> this latter<br />

obligation, refer to clause 3 <strong>of</strong> this chapter)<br />

Diverse<br />

circuits<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Socket-outlets<br />

circuit<br />

300 mA<br />

30 mA 30 mA<br />

Bathroom and/or<br />

shower room<br />

Fig. P5 : Installation with incoming-supply circuit-breaker having instantaneous differential<br />

protection<br />

Incoming supply circuit-breaker with instantaneous differential<br />

relay<br />

In this case:<br />

b An insulation fault to earth could result in a shutdown <strong>of</strong> the entire <strong>installation</strong><br />

b Where a lightning arrester is installed, its operation (i.e. discharging a voltage<br />

surge to earth) could appear to an RCD as an earth fault, with a consequent<br />

shutdown <strong>of</strong> the <strong>installation</strong><br />

Recommendation <strong>of</strong> suitable Merlin Gerin components<br />

b Incoming supply circuit-breaker with 300 mA differential and<br />

b High sensitivity 30 mA RCD (for example differential circuit-breaker 1P + N type<br />

Declic Vigi) on the circuits supplying socket outlets<br />

b High sensitivity 30 mA RCD (for example differential load switch type ID’clic) on<br />

circuits to bathrooms, shower rooms, laundry rooms, etc. (lighting, heating, socket<br />

outlets)<br />

Incoming supply circuit-breaker with type S time delayed<br />

differential relay<br />

This type <strong>of</strong> CB affords protection against fault to earth, but by virtue <strong>of</strong> a short time<br />

delay, provides a measure <strong>of</strong> discrimination with downstream instantaneous RCDs.<br />

Tripping <strong>of</strong> the incoming supply CB and its consequences (on deep freezers, for<br />

example) is thereby made less probable in the event <strong>of</strong> lightning, or other causes <strong>of</strong><br />

voltage surges. The discharge <strong>of</strong> voltage surge current to earth, through the surge<br />

arrester, will leave the type S circuit-breaker unaffected.


P - Residential and other special locations<br />

1<br />

Diverse<br />

circuits<br />

2<br />

5 3 4<br />

300 mA 30 mA 30 mA 30 mA<br />

High-risk circuit<br />

(dish-washing<br />

machine)<br />

Socket-outlet<br />

circuit<br />

Bathroom and/or<br />

shower room<br />

Fig. P7 : Installation with incoming-supply circuit-breaker<br />

having no differential protection<br />

Residential and similar premises<br />

Recommendation <strong>of</strong> suitable Merlin Gerin components (see Fig. P6)<br />

b Incoming supply circuit-breaker with 300 mA differential type S and<br />

b High sensitivity 30 mA RCD (for example differential circuit-breaker 1P + N type<br />

Declic Vigi) on the circuits supplying washing machines and dish-washing machine<br />

b High sensitivity 30 mA RCD (for example differential load switch type ID’clic) on<br />

circuits to bathrooms, shower rooms, laundry rooms, etc. (lighting, heating, socket<br />

outlets)<br />

Diverse<br />

circuits<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

High-risk location<br />

(laundry room)<br />

300 mA - type S<br />

30 mA 30 mA 30 mA<br />

Socketoutlet<br />

circuit<br />

Bathroom and/or<br />

shower room<br />

Fig. P6 : Installation with incoming-supply circuit-breaker having short time delay differential<br />

protection, type S<br />

Incoming supply circuit-breaker without differential protection<br />

In this case the protection <strong>of</strong> persons must be ensured by:<br />

b Class II level <strong>of</strong> insulation up to the downstream terminals <strong>of</strong> the RCDs<br />

b All outgoing circuits from the distribution board must be protected by 30 mA or<br />

300 mA RCDs according to the type <strong>of</strong> circuit concerned as discussed in chapter F.<br />

Where a voltage surge arrester is installed upstream <strong>of</strong> the distribution board<br />

(to protect sensitive electronic equipment such as microprocessors, videocassette<br />

recorders, TV sets, electronic cash registers, etc.) it is imperative that the<br />

device automatically disconnects itself from the <strong>installation</strong> following a rare (but<br />

always possible) failure. Some devices employ replaceable fusing elements; the<br />

recommended method however as shown in Figure P7, is to use a circuit-breaker.<br />

Recommendation <strong>of</strong> suitable Merlin Gerin components<br />

Figure P7 refers:<br />

1. Incoming-supply circuit-breaker without differential protection<br />

2. Automatic disconnection device (if a lightning arrester is installed)<br />

3. 30 mA RCD (for example differential circuit-breaker 1P + N type Declic Vigi) on<br />

each circuit supplying one or more socket-outlets<br />

4. 30 mA RCD (for example differential load swith type ID’clic) on circuits to<br />

bathrooms and shower rooms (lighting, heating and socket-outlets) or a 30 mA<br />

differential circuit-breaker per circuit<br />

5. 300 mA RCD (for example differential load swith) on all the other circuits<br />

P5<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

P6<br />

P - Residential and other special locations<br />

The distribution and division <strong>of</strong> circuits provides<br />

comfort and facilitates rapid location <strong>of</strong> fault<br />

Socketoutlets<br />

Lighting Heating<br />

Washing<br />

machine<br />

Cooking<br />

apparatus<br />

.4 Circuits<br />

Subdivision<br />

National standards commonly recommend the subdivision <strong>of</strong> circuits according to the<br />

number <strong>of</strong> utilization categories in the <strong>installation</strong> concerned (see Fig. P8):<br />

b At least 1 circuit for lighting. Each circuit supplying a maximum <strong>of</strong> 8 lighting points<br />

b At least 1 circuit for socket-outlets rated 10/16 A, each circuit supplying a maximum<br />

<strong>of</strong> 8 sockets. These sockets may be single or double units (a double unit is made up<br />

<strong>of</strong> two 10/16 A sockets mounted on a common base in an embedded box, identical<br />

to that <strong>of</strong> a single unit<br />

b 1 circuit for each appliance such as water heater, washing machine, dish-washing<br />

machine, cooker, refrigerator, etc. Recommended numbers <strong>of</strong> 10/16 A (or similar)<br />

socket-outlets and fixed lighting points, according to the use for which the various<br />

rooms <strong>of</strong> a dwelling are intended, are indicated in Figure P9<br />

Fig. P8 : Circuit division according to utilization Fig P9 : Recommended minimum number <strong>of</strong> lighting and power points in residential premises<br />

The inclusion <strong>of</strong> a protective conductor in all<br />

circuits is required by IEC and most national<br />

standards<br />

Residential and similar premises<br />

Room function Minimum number Minimum number<br />

<strong>of</strong> fixed lighting points <strong>of</strong> 0/ 6 A socket-outlets<br />

Living room 1 5<br />

Bedroom, lounge, 1 3<br />

bureau, dining room<br />

Kitchen 2 4 (1)<br />

Bathroom, shower room 2 1 or 2<br />

Entrance hall, box room 1 1<br />

WC, storage space 1 -<br />

Laundry room - 1<br />

(1) Of which 2 above the working surface and 1 for a specialized circuit: in addition<br />

an independent socket-outlet <strong>of</strong> 16 A or 20 A for a cooker and a junction box or<br />

socket-outlet for a 32 A specialized circuit<br />

Protective conductors<br />

IEC and most national standards require that each circuit includes a protective<br />

conductor. This practice is strongly recommended where class I insulated appliances<br />

and equipment are installed, which is the general case.<br />

The protective conductors must connect the earthing-pin contact in each socketoutlet,<br />

and the earthing terminal in class I equipment, to the main earthing terminal<br />

at the origin <strong>of</strong> the <strong>installation</strong>.<br />

Furthermore, 10/16 A (or similarly sized) socket-outlets must be provided with<br />

shuttered contact orifices.<br />

Cross-sectional-area (c.s.a.) <strong>of</strong> conductors (see Fig. P 0)<br />

The c.s.a. <strong>of</strong> conductors and the rated current <strong>of</strong> the associated protective device<br />

depend on the current magnitude <strong>of</strong> the circuit, the ambient temperature, the kind <strong>of</strong><br />

<strong>installation</strong>, and the influence <strong>of</strong> neighbouring circuits (refer to chapter G)<br />

Moreover, the conductors for the phase wires, the neutral and the protective<br />

conductors <strong>of</strong> a given circuit must all be <strong>of</strong> equal c.s.a. (assuming the same material<br />

for the conductors concerned, i.e. all copper or all aluminium).<br />

Fig. P10 : Circuit-breaker 1 phase + N - 2 x 9 mm spaces<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


P - Residential and other special locations<br />

Residential and similar premises<br />

Figure P indicates the c.s.a. required for commonly-used appliances<br />

Protective devices 1 phase + N in 2 x 9 mm spaces comply with requirements for<br />

isolation, and for marking <strong>of</strong> circuit current rating and conductor sizes.<br />

Type <strong>of</strong> circuit c. s. a. <strong>of</strong> the Maximum power Protective device<br />

single-phase 230 V conductors<br />

ph + N or ph + N + PE<br />

Fixed lighting 1.5 mm 2 2,300 W Circuit-breaker 16 A<br />

(2.5 mm 2 ) Fuse 10 A<br />

10/16 A 2.5 mm 2 4,600 W Circuit-breaker 25 A<br />

(4 mm 2 ) Fuse 20 A<br />

Individual-load circuits<br />

Water heater 2.5 mm 2 4,600 W Circuit-breaker 25 A<br />

(4 mm 2 ) Fuse 20 A<br />

Dish-washing machine 2.5 mm 2 4,600 W Circuit-breaker 25 A<br />

(4 mm 2 ) Fuse 20 A<br />

Clothes-washing machine 2.5 mm 2 4,600 W Circuit-breaker 25 A<br />

(4 mm 2 ) Fuse 20 A<br />

Cooker or hotplate (1) 6 mm 2 7,300 W Circuit-breaker 40 A<br />

(10 mm 2 ) Fuse 32 A<br />

Electric space heater 1.5 mm 2 2,300 W Circuit-breaker 16 A<br />

(2.5 mm 2 ) Fuse 10 A<br />

(1) In a 230/400 V 3-phase circuit, the c. s. a. is 4 mm 2 for copper or 6 mm 2 for aluminium, and protection is provided by a 32 A<br />

circuit-breaker or by 25 A fuses.<br />

Fig. P11 : C. s. a. <strong>of</strong> conductors and current rating <strong>of</strong> the protective devices in residential <strong>installation</strong>s (the c. s. a. <strong>of</strong> aluminium conductors are shown in brackets)<br />

.5 Protection against overvoltages and lightning<br />

The choice <strong>of</strong> surge arrester is described in chapter J<br />

Installation <strong>rules</strong><br />

Three principal <strong>rules</strong> must be respected:<br />

1 - It is imperative that the three lengths <strong>of</strong> cable used for the <strong>installation</strong> <strong>of</strong> the surge<br />

arrester each be less than 50 cm i.e.:<br />

b the live conductors connected to the isolating switch<br />

b from the isolating switch to the surge arrester<br />

b from the surge arrester to the main distribution board (MDB) earth bar (not<br />

to be confused with the main protective-earth (PE) conductor or the main earth<br />

terminal for the <strong>installation</strong>.The MDB earth bar must evidently be located in the<br />

same cabinet as the surge arrester.<br />

2 - It is necessary to use an isolating switch <strong>of</strong> a type recommended by the<br />

manufacturer <strong>of</strong> the surge arrester.<br />

3 - In the interest <strong>of</strong> a good continuity <strong>of</strong> supply it is recommended that the<br />

circuit-breaker be <strong>of</strong> the time-delayed or selective type.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

P7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

P<br />

P - Residential and other special locations<br />

2 Bathrooms and showers<br />

Bathrooms and showers rooms are areas <strong>of</strong> high risk, because <strong>of</strong> the very low<br />

resistance <strong>of</strong> the human body when wet or immersed in water.<br />

Precaution to be taken are therefore correspondingly rigorous, and the regulations<br />

are more severe than those for most other locations.<br />

The relevant standard is IEC 60364-7-701.<br />

Precautions to observe are based on three aspects:<br />

b The definition <strong>of</strong> zones, numbered 0,1, 2, 3 in which the placement (or exclusion)<br />

<strong>of</strong> any <strong>electrical</strong> device is strictly limited or forbidden and, where permitted, the<br />

<strong>electrical</strong> and mechanical protection is prescribed<br />

b The establishment <strong>of</strong> an equipotential bond between all exposed and extraneous<br />

metal parts in the zones concerned<br />

b The strict adherence to the requirements prescribed for each particular zones, as<br />

tabled in clause 3<br />

2.1 Classification <strong>of</strong> zones<br />

Sub-clause 701.32 <strong>of</strong> IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the<br />

following diagrams (see Fig. P12 below to Fig P1 opposite and next pages):<br />

Zone 1*<br />

Zone 0<br />

Zone 1<br />

Zone 1<br />

Zone 0<br />

Zone 2 Zone 3<br />

0.60 m 2.40 m<br />

Zone 2<br />

0.60 m<br />

(*) Zone 1 is above the bath as shown in the vertical cross-section<br />

Fig. P12 : Zones 0, 1, 2 and 3 in proximity to a bath-tub<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Zone 1*<br />

Zone 0<br />

Zone 3<br />

2.40 m<br />

0.60 m<br />

Zone 2 Zone 3<br />

2.25 m<br />

2.40 m


P - Residential and other special locations<br />

2 Bathrooms and showers<br />

Zone 0<br />

Zone 1<br />

0.60 m<br />

Zone 3<br />

2.40 m<br />

Zone 1 Zone 2<br />

Zone 3<br />

Zone 1<br />

Zone 0<br />

Zone 2<br />

0.60 m<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

2.40 m<br />

Zone 0<br />

Zone 1<br />

0.60 m<br />

2.25 m<br />

Fig. P13 : Zones 0, 1, 2 and 3 in proximity <strong>of</strong> a shower with basin<br />

Zone 1<br />

Zone 2<br />

Zone 3<br />

Zone 1<br />

0.60 m<br />

Fixed shower<br />

head (1)<br />

0.60 m<br />

Zone<br />

2<br />

2.40 m<br />

Zone 3<br />

Zone 2<br />

Fixed shower<br />

head (1)<br />

0.60 m<br />

Zone 1<br />

0.60 m<br />

Zone 2<br />

Zone 3<br />

2.25 m<br />

2.40 m<br />

Zone 3<br />

2.40 m<br />

(1) When the shower head is at the end <strong>of</strong> a flexible tube, the vertical central axis <strong>of</strong><br />

a zone passes through the fixed end <strong>of</strong> the flexible tube<br />

Fig. P14 : Zones 0, 1, 2 and 3 in proximity <strong>of</strong> a shower without basin<br />

Prefabricated<br />

shower<br />

cabinet<br />

0.60 m<br />

0.60 m<br />

Fig. P15 : No switch or socket-outlet is permitted within 60 cm <strong>of</strong> the door opening <strong>of</strong> a shower<br />

cabinet<br />

P<br />

© Schneider Electric - all rights reserved


P10<br />

© Schneider Electric - all rights reserved<br />

P - Residential and other special locations<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

AD 3<br />

BB 2<br />

BC 3<br />

AD 3<br />

BB 3<br />

BC 3<br />

AD 7<br />

BB 3<br />

BC 3<br />

Fig. P16 : Individual showers with dressing cubicles<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

h < 1.10m<br />

AD 5<br />

1.10m < h < 2.25m<br />

AD 3<br />

BB 3<br />

BC 3<br />

AD 7<br />

BB 3<br />

BC 3<br />

Zone 3<br />

Dressing cubicles (zone 2)<br />

Shower cabinets (zone 1)<br />

Dressing cubicles<br />

Zone 1<br />

Fig. P17 : Individual showers with separate individual dressing cubicles<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

AD 3<br />

BB 2<br />

BC 3<br />

h < 1.10m<br />

AD 5<br />

1.10m < h < 2.25m<br />

AD 3<br />

BB 3<br />

BC 3<br />

Fig. P18 : Communal showers and common dressing room<br />

Zone 2<br />

2 Bathrooms and showers<br />

Zone 2<br />

Dressing room<br />

Zone 2<br />

Zone 1<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

AD 3<br />

BB 2<br />

BC 3<br />

WC<br />

WC<br />

AD 3<br />

BB 2<br />

BC 3<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

h < 1.10m<br />

AD 5<br />

1.10m < h < 2.25m<br />

AD 3<br />

BB 3<br />

BC 3<br />

Classes<br />

<strong>of</strong> external<br />

influences<br />

AD 7<br />

BB 3<br />

BC 3<br />

Note: Classes <strong>of</strong> external influences (see Fig. E46).<br />

AD 3<br />

BB 2<br />

BC 3<br />

h < 1.10m<br />

AD 5<br />

1.10m < h < 2.25m<br />

AD 3<br />

BB 3<br />

BC 3


P - Residential and other special locations<br />

2 Bathrooms and showers<br />

2.2 Equipotential bonding (see Fig. P1 )<br />

Water-drainage<br />

piping<br />

Socket-outlet<br />

Lighting<br />

Gaz<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

To the earth<br />

electrode<br />

Metal bath Equipotential conductors<br />

for a bathroom<br />

Fig. P19 : Supplementary equipotential bonding in a bathroom<br />

Metal<br />

door-frame<br />

2.3 Requirements prescribed for each zone<br />

Metallic pipes<br />

h i 2 m<br />

Radiator<br />

The table <strong>of</strong> clause 3 describes the application <strong>of</strong> the principles mentioned in the<br />

foregoing text and in other similar or related cases<br />

P11<br />

© Schneider Electric - all rights reserved


P12<br />

© Schneider Electric - all rights reserved<br />

P - Residential and other special locations<br />

3 Recommendations applicable to<br />

special <strong>installation</strong>s and locations<br />

Figure P20 below summarizes the main requirements prescribed in many national<br />

and international standards.<br />

Note: Section in brackets refer to sections <strong>of</strong> IEC 60364-7<br />

Locations Protection principles IP Wiring Switchgear Socket-outlets Installation<br />

level and cables materials<br />

Domestic dwellings b TT or TN-S systems 20 Switch operating handles Protection by<br />

and other habitations b Differential protection and similar devices on 30 mA RCDs<br />

v 300 mA if the earth electrode distribution panels,<br />

resistance is y 80 ohms instantaneous to be mounted<br />

or short time delay (type S) between 1 metre and<br />

v 30 mA if the earth electrode 1.80 metre above the floor<br />

resistance is u 500 ohms<br />

b surge arrester at the origin <strong>of</strong> the<br />

<strong>installation</strong> if<br />

v supply is from overhead line with bare<br />

conductors, and if<br />

v the keraunic level > 25<br />

b a protective earth (PE) conductor<br />

on all circuits<br />

Bathrooms or shower Supplementary equipotential bonding<br />

rooms (section 701) in zones 0, 1, 2 and 3<br />

Zone 0 SELV 12 V only 27 Class II Special appliances<br />

limited to<br />

strict minimum<br />

Zone 1 SELV 12 V 25 Class II Special aplliances<br />

limited to Water heater<br />

strict minimum<br />

Zone 2 SELV 12 V or 30 mA RCD 24 Class II Special appliances<br />

limited to Water heater<br />

strict minimum Class II luminaires<br />

Zone 3 21 Only socket-outlets protected by :<br />

b 30 mA RCD or<br />

b Electrical separation or<br />

b SELV 50 V<br />

Swimming baths Supplementary equipotential bonding<br />

(section 702) in zones 0, 1, and 2<br />

Zone 0 SELV 12 V 28 Class II Special appliances<br />

limited to<br />

strict minimum<br />

Zone 1 25 Class II Special appliances<br />

limited to<br />

strict minimum<br />

Zone 2 22 Only socket-outlets protected by :<br />

(indoor) b 30 mA RCD or<br />

24 b <strong>electrical</strong> separation or<br />

(outdoor) b SELV 50 V<br />

Saunas 24 Class II Adapted to temperature<br />

(section 703)<br />

Work sites Conventional voltage limit UL 44 Mechanically Protection by<br />

(section 704) reduced to 25 V protected 30 mA RCDs<br />

Agricultural and Conventional voltage limit UL 35 Protection by<br />

horticultural reduced to 25 V 30 mA RCDs<br />

establishments Protection against fire risks<br />

(section 705) by 500 mA RCDs<br />

Restricted conductive 2x Protection <strong>of</strong>:<br />

locations (section 706) b Portable tools by:<br />

v SELV or<br />

v Electrical separation<br />

b Hand-held lamps<br />

v By SELV<br />

b Fixed equipement by<br />

v SELV<br />

v Electrical separation<br />

v 30 mA RCDs<br />

v Special supplementary<br />

equipotential bonding<br />

Fig. P20 : Main requirements prescribed in many national and international standards (continued on opposite page)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008


P - Residential and other special locations<br />

3 Recommendations applicable to<br />

special <strong>installation</strong>s and locations<br />

Locations Protection principles IP Wiring Switchgear Socket-outlets Installation<br />

level and cables materials<br />

Fountains Protection by 30 mA RCDs and<br />

(section 702) equipotential bonding <strong>of</strong> all exposed<br />

and extraneous conductive parts<br />

Data processing TN-S system recommended<br />

(section 707) TT system if leakage current is limited.<br />

Protective conductor 10 mm 2 minimum<br />

in aluminium. Smaller sizes (in copper)<br />

must be doubled.<br />

Caravan park 55 Flexible cable <strong>of</strong> Socket-outlets<br />

(section 708) 25 metres shall be placed<br />

length at a height <strong>of</strong><br />

0.80 m to 1.50 m<br />

from the ground.<br />

Protection <strong>of</strong><br />

circuits by<br />

30 mA RCDs<br />

(one per 6<br />

socket-outlets)<br />

Marinas and pleasure The cable length for connection to Protection <strong>of</strong><br />

craft (section 709) pleasure craft must not exceeded 25 m circuits by<br />

30 mA RCDs<br />

(one per 6<br />

socket-outlets)<br />

Medical locations IT medical system equipotential bonding Protection by<br />

(section 710) 30 mA RCDs<br />

Exhibitions, shows and TT or TN-S systems 4x Protection by<br />

stands (section 711) 30 mA RCDs<br />

Balneotherapy Individual: see section 701<br />

(cure-centre baths) (volumes 0 and 1)<br />

Collective: see section 702<br />

(volumes 0 and 1)<br />

Motor-fuel filling Explosion risks in security zones Limited to the<br />

stations necessary minimum<br />

Motor vehicules Protection by RCDs or by<br />

<strong>electrical</strong> separation<br />

External lighting 23 Protection by<br />

<strong>installation</strong>s 30 mA RCDs<br />

(section 714)<br />

Mobile or transportable The use <strong>of</strong> TN-C system is not 30 mA RCDs<br />

units (section 717) permitted inside any unit must be used for<br />

all socket-outlets<br />

supplying<br />

equipment<br />

outside the unit<br />

Fig. P20 : Main requirements prescribed in many national and international standards (concluded)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

P13<br />

© Schneider Electric - all rights reserved


2<br />

3<br />

4<br />

5<br />

<strong>Chapter</strong> Q<br />

EMC guidelines<br />

Contents<br />

Electrical distribution Q2<br />

Earthing principles and structures Q3<br />

Implementation Q5<br />

3.1 Equipotential bonding inside and outside buildings Q5<br />

3.2 Improving equipotential conditions Q5<br />

3.3 Separating cables Q7<br />

3.4 False floor Q7<br />

3.5 Cable running Q8<br />

3.6 Implementation <strong>of</strong> shielded cables Q11<br />

3.7 Communication networks Q11<br />

3.8 Implementation <strong>of</strong> surge arrestors Q12<br />

3.9 Cabinet cabling Q13<br />

3.10 Standards Q13<br />

Coupling mechanisms and counter-measures Q 4<br />

4.1 <strong>General</strong> Q14<br />

4.2 Common-mode impedance coupling Q15<br />

4.3 Capacitive coupling Q16<br />

4.4 Inductive coupling Q17<br />

4.5 Radiated coupling Q18<br />

Wiring recommendations Q20<br />

5.1 Signal classes Q20<br />

5.2 Wiring recommendations Q20<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Q<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

Q2<br />

Q - EMC guidelines<br />

Fig. Q1 : Main characteristics <strong>of</strong> system earthing<br />

Electrical distribution<br />

The system earthing arrangement must be properly selected to ensure the<br />

safety <strong>of</strong> life and property. The behaviour <strong>of</strong> the different systems with respect<br />

to EMC considerations must be taken into account. Figure Q below presents a<br />

summary <strong>of</strong> their main characteristics.<br />

European standards (see EN 50174-2 § 6.4 and EN 50310 § 6.3) recommend the<br />

TN-S system which causes the fewest EMC problems for <strong>installation</strong>s comprising<br />

information-technology equipment (including telecom equipment).<br />

TT TN-S IT TN-C<br />

Safety <strong>of</strong> persons Good Good<br />

RCD mandatory Continuity <strong>of</strong> the PE conductor must be ensured throughout the <strong>installation</strong><br />

Safety <strong>of</strong> property Good Poor Good Poor<br />

Medium fault current High fault current Low current for first fault High fault current<br />

(< a few dozen amperes) (around 1 kA) (< a few dozen mA), (around 1 kA)<br />

but high for second fault<br />

Availability <strong>of</strong> energy Good Good Excellent Good<br />

EMC behaviour Good Excellent Poor (to be avoided) Poor<br />

- Risk <strong>of</strong> overvoltages - Few equipotential - Risk <strong>of</strong> overvoltages (should never be used)<br />

- Equipotential problems - Common-mode filters - Neutral and PE are<br />

problems - Need to manage and surge arrestors the same<br />

- Need to manage devices with high must handle the phase- - Circulation <strong>of</strong> disturbed<br />

devices with high leakage currents to-phase voltages currents in exposed<br />

leakage currents - High fault currents - RCDs subject to conductive parts (high<br />

(transient disturbances) nuisance tripping if magnetic-field radiation)<br />

common-mode - High fault currents<br />

capacitors are present (transient disturbances)<br />

- Equivalent to<br />

TN system for second<br />

fault<br />

When an <strong>installation</strong> includes high-power equipment (motors, air-conditioning, lifts,<br />

power electronics, etc.), it is advised to install one or more transformers specifically<br />

for these systems. Electrical distribution must be organised in a star system and all<br />

outgoing circuits must exit the main low-voltage switchboard (MLVS).<br />

Electronic systems (control/monitoring, regulation, measurement instruments, etc.)<br />

must be supplied by a dedicated transformer in a TN-S system.<br />

Figure Q2 below illustrate these recommendations.<br />

Disturbing<br />

devices<br />

Transformer<br />

Sensitive<br />

devices<br />

Disturbing<br />

devices<br />

Not recommended Preferable Excellent<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Sensitive<br />

devices<br />

Fig. Q2 : Recommendations <strong>of</strong> separated distributions<br />

Lighting<br />

Air conditioning<br />

Disturbing<br />

devices<br />

Sensitive<br />

devices


Q - EMC guidelines<br />

2 Earthing principles and<br />

structures<br />

This section deals with the earthing and equipotential bonding <strong>of</strong> information-technology<br />

devices and other similar devices requiring interconnections for signalling purposes.<br />

Earthing networks are <strong>design</strong>ed to fulfil a number <strong>of</strong> functions. They can be<br />

independent or operate together to provide one or more <strong>of</strong> the following:<br />

b Safety <strong>of</strong> persons with respect to <strong>electrical</strong> hazards<br />

b Protection <strong>of</strong> equipment with respect to <strong>electrical</strong> hazards<br />

b A reference value for reliable, high-quality signals<br />

b Satisfactory EMC performance<br />

The system earthing arrangement is generally <strong>design</strong>ed and installed in view <strong>of</strong><br />

obtaining a low impedance capable <strong>of</strong> diverting fault currents and HF currents away<br />

from electronic devices and systems. There are different types <strong>of</strong> system earthing<br />

arrangements and some require that specific conditions be met. These conditions<br />

are not always met in typical <strong>installation</strong>s. The recommendations presented in this<br />

section are intended for such <strong>installation</strong>s.<br />

For pr<strong>of</strong>essional and industrial <strong>installation</strong>s, a common bonding network (CBN) may<br />

be useful to ensure better EMC performance with respect to the following points:<br />

b Digital systems and new technologies<br />

b Compliance with the EMC requirements <strong>of</strong> EEC 89/336 (emission and immunity)<br />

b The wide number <strong>of</strong> <strong>electrical</strong> applications<br />

b A high level <strong>of</strong> system safety and security, as well as reliability and/or availability<br />

For residential premises, however, where the use <strong>of</strong> <strong>electrical</strong> devices is limited, an<br />

isolated bonding network (IBN) or, even better, a mesh IBN may be a solution.<br />

It is now recognised that independent, dedicated earth electrodes, each serving a<br />

separate earthing network, are a solution that is not acceptable in terms <strong>of</strong> EMC,<br />

but also represent a serious safety hazard. In certain countries, the national building<br />

codes forbid such systems.<br />

Use <strong>of</strong> a separate “clean” earthing network for electronics and a “dirty” earthing<br />

network for energy is not recommended in view <strong>of</strong> obtaining correct EMC, even<br />

when a single electrode is used (see Fig. Q and Fig. Q4). In the event <strong>of</strong> a lightning<br />

strike, a fault current or HF disturbances as well as transient currents will flow in the<br />

<strong>installation</strong>. Consequently, transient voltages will be created and result in failures or<br />

damage to the <strong>installation</strong>. If <strong>installation</strong> and maintenance are carried out properly,<br />

this approach may be dependable (at power frequencies), but it is generally not<br />

suitable for EMC purposes and is not recommended for general use.<br />

"Clean"<br />

earthing network<br />

Fig. Q3 : Independent earth electrodes, a solution generally not acceptable for safety and EMC<br />

reasons<br />

"Clean"<br />

earthing network<br />

Fig. Q4 : Installation with a single earth electrode<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Electrical<br />

earthing network<br />

Separate earth electrodes<br />

Electrical<br />

earthing network<br />

Single earth electrode<br />

Surge arrestors<br />

Surge arrestors<br />

Q<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved Q4<br />

Q - EMC guidelines<br />

Fig. Q6 : Each level has a mesh and the meshes are<br />

interconnected at several points between levels. Certain<br />

ground-floor meshes are reinforced to meet the needs <strong>of</strong><br />

certain areas<br />

2 Earthing principles and<br />

structures<br />

The recommended configuration for the earthing network and electrodes is two or<br />

three dimensional (see Fig. Q5). This approach is advised for general use, both<br />

in terms <strong>of</strong> safety and EMC. This recommendation does not exclude other special<br />

configurations that, when correctly maintained, are also suitable.<br />

Fig. Q5 : Installation with multiple earth electrodes<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Equipotential bonding required for<br />

multi-level buildings<br />

"Electrical" and "communication"<br />

earthing as needed<br />

Surge arrestors<br />

Multiple interconnected earth electrodes<br />

In a typical <strong>installation</strong> for a multi-level building, each level should have its<br />

own earthing network (generally a mesh) and all the networks must be both<br />

interconnected and connected to the earth electrode. At least two connections are<br />

required (built in redundancy) to ensure that, if one conductor breaks, no section <strong>of</strong><br />

the earthing network is isolated.<br />

Practically speaking, more than two connections are made to obtain better symmetry<br />

in current flow, thus reducing differences in voltage and the overall impedance<br />

between the various levels in the building.<br />

The many parallel paths have different resonance frequencies. If one path has a high<br />

impedance, it is most probably shunted by another path with a different resonance<br />

frequency. On the whole, over a wide frequency spectrum (dozens <strong>of</strong> Hz and MHz), a<br />

large number <strong>of</strong> paths results in a low-impedance system (see Fig. Q6).<br />

Each room in the building should have earthing-network conductors for equipotential<br />

bonding <strong>of</strong> devices and systems, cableways, trunking systems and structures. This<br />

system can be reinforced by connecting metal pipes, gutters, supports, frames, etc.<br />

In certain special cases, such as control rooms or computers installed on false floors,<br />

ground reference plane or earthing strips in areas for electronic systems can be used<br />

to improve earthing <strong>of</strong> sensitive devices and protection interconnection cables.


Q - EMC guidelines<br />

3 Implementation<br />

3.1 Equipotential bonding inside and outside<br />

buildings<br />

The fundamental goals <strong>of</strong> earthing and bonding are the following:<br />

b Safety<br />

By limiting the touch voltage and the return path <strong>of</strong> fault currents<br />

b EMC<br />

By avoiding differences in potential and providing a screening effect.<br />

Stray currents are inevitably propagated in an earthing network. It is impossible to<br />

eliminate all the sources <strong>of</strong> disturbances for a site. Earth loops are also inevitable.<br />

When a magnetic field affects a site, e.g. the field created by lightning, differences in<br />

potential are created in the loops formed by the various conductors and the currents<br />

flowing in the earthing system. Consequently, the earthing network is directly<br />

affected by any counter-measures taken outside the building.<br />

As long as the currents flow in the earthing system and not in the electronic circuits,<br />

they do no damage. However, when earthing networks are not equipotential, e.g.<br />

when they are star connected to the earth electrode, the HF stray currents will flow<br />

wherever they can, including in control wires. Equipment can be disturbed, damaged<br />

or even destroyed.<br />

The only inexpensive means to divide the currents in an earthing system and<br />

maintain satisfactory equipotential characteristics is to interconnect the earthing<br />

networks. This contributes to better equipotential bonding within the earthing<br />

system, but does not remove the need for protective conductors. To meet legal<br />

requirements in terms <strong>of</strong> the safety <strong>of</strong> persons, sufficiently sized and identified<br />

protective conductors must remain in place between each piece <strong>of</strong> equipment and<br />

the earthing terminal. What is more, with the possible exception <strong>of</strong> a building with a<br />

steel structure, a large number <strong>of</strong> conductors for the surge-arrestor or the lightningprotection<br />

network must be directly connected to the earth electrode.<br />

The fundamental difference between a protective conductor (PE) and a surgearrestor<br />

down-lead is that the first conducts internal currents to the neutral <strong>of</strong> the<br />

MV/LV transformer whereas the second carries external current (from outside the<br />

<strong>installation</strong>) to the earth electrode.<br />

In a building, it is advised to connect an earthing network to all accessible conducting<br />

structures, namely metal beams and door frames, pipes, etc. It is generally sufficient<br />

to connect metal trunking, cable trays and lintels, pipes, ventilation ducts, etc. at<br />

as many points as possible. In places where there is a large amount <strong>of</strong> equipment<br />

and the size <strong>of</strong> the mesh in the bonding network is greater than four metres, an<br />

equipotential conductor should be added. The size and type <strong>of</strong> conductor are not <strong>of</strong><br />

critical importance.<br />

It is imperative to interconnect the earthing networks <strong>of</strong> buildings that have shared<br />

cable connections. Interconnection <strong>of</strong> the earthing networks must take place via a<br />

number <strong>of</strong> conductors and all the internal metal structures <strong>of</strong> the buildings or linking<br />

the buildings (on the condition that they are not interrupted).<br />

In a given building, the various earthing networks (electronics, computing, telecom,<br />

etc.) must be interconnected to form a single equipotential bonding network.<br />

This earthing-network must be as meshed as possible. If the earthing network is<br />

equipotential, the differences in potential between communicating devices will be low<br />

and a large number <strong>of</strong> EMC problems disappear. Differences in potential are also<br />

reduced in the event <strong>of</strong> insulation faults or lightning strikes.<br />

If equipotential conditions between buildings cannot be achieved or if the distance<br />

between buildings is greater than ten metres, it is highly recommended to use<br />

optical fibre for communication links and galvanic insulators for measurement and<br />

communication systems.<br />

These measures are mandatory if the <strong>electrical</strong> supply system uses the IT or<br />

TN-C system.<br />

3.2 Improving equipotential conditions<br />

Bonding networks<br />

Even though the ideal bonding network would be made <strong>of</strong> sheet metal or a fine<br />

mesh, experience has shown that for most disturbances, a three-metre mesh size is<br />

sufficient to create a mesh bonding network.<br />

Examples <strong>of</strong> different bonding networks are shown in Figure Q7 next page. The<br />

minimum recommended structure comprises a conductor (e.g. copper cable or strip)<br />

surrounding the room.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Q<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

Q<br />

Q - EMC guidelines<br />

Trunk<br />

BN: Bonding network<br />

CBN: Common bonding network<br />

IBN: Isolated bonding network<br />

Fig. Q7 : Examples <strong>of</strong> bonding networks<br />

IBN<br />

Mesh IBN<br />

Tree structure<br />

Star (IBN)<br />

3 Implementation<br />

PE<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IBN<br />

CBN<br />

Mesh BN<br />

Mesh BN<br />

Local mesh Local mesh<br />

IBN<br />

The length <strong>of</strong> connections between a structural element and the bonding network<br />

does not exceed 50 centimetres and an additional connection should be installed<br />

in parallel at a certain distance from the first. The inductance <strong>of</strong> the connection<br />

between the earthing bar <strong>of</strong> the <strong>electrical</strong> enclosure for a set <strong>of</strong> equipment and the<br />

bonding network (see below) should be less than one µHenry (0.5 µH, if possible).<br />

For example, it is possible to use a single 50 cm conductor or two parallel conductors<br />

one meter long, installed at a minimum distance from one another (at least 50 cm) to<br />

reduce the mutual inductance between the two conductors.<br />

Where possible, connection to the bonding network should be at an intersection to<br />

divide the HF currents by four without lengthening the connection. The pr<strong>of</strong>ile <strong>of</strong> the<br />

bonding conductors is not important, but a flat pr<strong>of</strong>ile is preferable. The conductor<br />

should also be as short as possible.<br />

Parallel earthing conductor (PEC)<br />

The purpose <strong>of</strong> a parallel earthing conductor is to reduce the common-mode current<br />

flowing in the conductors that also carry the differential-mode signal (the commonmode<br />

impedance and the surface area <strong>of</strong> the loop are reduced).<br />

The parallel earthing conductor must be <strong>design</strong>ed to handle high currents when it<br />

is used for protection against lightning or for the return <strong>of</strong> high fault currents. When<br />

cable shielding is used as a parallel earthing conductor, it cannot handle such high<br />

currents and the solution is to run the cable along metal structural elements or<br />

cableways which then act as other parallel earthing conductors for the entire cable.<br />

Another possibility is to run the shielded cable next to a large parallel earthing<br />

conductor with both the shielded cable and the parallel earthing conductor connected<br />

at each end to the local earthing terminal <strong>of</strong> the equipment or the device.<br />

For very long distances, additional connections to the network are advised for<br />

the parallel earthing conductor, at irregular distances between the devices. These<br />

additional connections form a shorter return path for the disturbing currents flowing<br />

through the parallel earthing conductor. For U-shaped trays, shielding and tubes, the<br />

additional connections should be external to maintain the separation with the interior<br />

(“screening” effect).<br />

Bonding conductors<br />

Bonding conductors may be metal strips, flat braids or round conductors. For highfrequency<br />

systems, metal strips and flat braids are preferable (skin effect) because a<br />

round conductor has a higher impedance than a flat conductor with the same cross<br />

section. Where possible, the length to width ratio should not exceed 5.


Q - EMC guidelines<br />

3 Implementation<br />

3.3 Separating cables<br />

The physical separation <strong>of</strong> high and low-current cables is very important for EMC,<br />

particularly if low-current cables are not shielded or the shielding is not connected<br />

to the exposed conductive parts (ECPs). The sensitivity <strong>of</strong> electronic equipment is in<br />

large part determined by the accompanying cable system.<br />

If there is no separation (different types <strong>of</strong> cables in separate cableways, minimum<br />

distance between high and low-current cables, types <strong>of</strong> cableways, etc.),<br />

electromagnetic coupling is at its maximum. Under these conditions, electronic<br />

equipment is sensitive to EMC disturbances flowing in the affected cables.<br />

Use <strong>of</strong> busbar trunking systems such as Canalis or busbar ducts for high power<br />

ratings is strongly advised. The levels <strong>of</strong> radiated magnetic fields using these types <strong>of</strong><br />

trunking systems is 10 to 20 times lower than standard cables or conductors.<br />

The recommendations in the “Cable running” and “Wiring recommendations”<br />

sections should be taken into account.<br />

3.4 False floors<br />

The inclusion <strong>of</strong> the floors in the mesh contributes to equipotentiality <strong>of</strong> the area and<br />

consequently to the distribution and dilution <strong>of</strong> disturbing LF currents.<br />

The screening effect <strong>of</strong> a false floor is directly related to its equipotentiality. If the<br />

contact between the floor plates is poor (rubber antistatic joints, for example) or if<br />

the contact between the support brackets is faulty (pollution, corrosion, mildew, etc.<br />

or if there are no support brackets), it is necessary to add an equipotential mesh. In<br />

this case, it is sufficient to ensure effective <strong>electrical</strong> connections between the metal<br />

support columns. Small spring clips are available on the market to connect the metal<br />

columns to the equipotential mesh. Ideally, each column should be connected, but<br />

it is <strong>of</strong>ten sufficient to connect every other column in each direction. A mesh 1.5 to<br />

2 metres is size is suitable in most cases. The recommended cross-sectional area <strong>of</strong><br />

the copper is 10 mm2 or more. In general, a flat braid is used. To reduce the effects <strong>of</strong><br />

corrosion, it is advised to use tin-plated copper (see Fig. Q8).<br />

Perforated floor plates act like normal floor plates when they have a cellular steel<br />

structure.<br />

Preventive maintenance is required for the floor plates approximately every five years<br />

(depending on the type <strong>of</strong> floor plate and the environment, including humidity, dust<br />

and corrosion). Rubber or polymer antistatic joints must be maintained, similar to the<br />

bearing surfaces <strong>of</strong> the floor plates (cleaning with a suitable product).<br />

Spring clips<br />

Metal support columns<br />

Fig. Q8 : False floor implementation<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

u 10 mm 2<br />

False floor<br />

Q7<br />

© Schneider Electric - all rights reserved


© Schneider Electric - all rights reserved<br />

Q8<br />

Q - EMC guidelines<br />

3 Implementation<br />

3. Cable running<br />

Selection <strong>of</strong> materials and their shape depends on the following criteria:<br />

b Severity <strong>of</strong> the EM environment along cableways (proximity <strong>of</strong> sources <strong>of</strong><br />

conducted or radiated EM disturbances)<br />

b Authorised level <strong>of</strong> conducted and radiated emissions<br />

b Type <strong>of</strong> cables (shielded?, twisted?, optical fibre?)<br />

b EMI withstand capacity <strong>of</strong> the equipment connected to the wiring system<br />

b Other environmental constraints (chemical, mechanical, climatic, fire, etc.)<br />

b Future extensions planned for the wiring system<br />

Non-metal cableways are suitable in the following cases:<br />

b A continuous, low-level EM environment<br />

b A wiring system with a low emission level<br />

b Situations where metal cableways should be avoided (chemical environment)<br />

b Systems using optical fibres<br />

For metal cableways, it is the shape (flat, U-shape, tube, etc.) rather than the crosssectional<br />

area that determines the characteristic impedance. Closed shapes are<br />

better than open shapes because they reduce common-mode coupling. Cableways<br />

<strong>of</strong>ten have slots for cable straps. The smaller the better. The types <strong>of</strong> slots causing<br />

the fewest problems are those cut parallel and at some distance from the cables.<br />

Slots cut perpendicular to the cables are not recommended (see Fig. Q9).<br />

Fig. Q10 : Installation <strong>of</strong> different types <strong>of</strong> cables<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Mediocre OK Better<br />

Fig. Q9 : CEM performance <strong>of</strong> various types <strong>of</strong> metal cableways<br />

In certain cases, a poor cableway in EMI terms may be suitable if the<br />

EM environment is low, if shielded cables or optical fibres are employed, or separate<br />

cableways are used for the different types <strong>of</strong> cables (power, data processing, etc.).<br />

It is a good idea to reserve space inside the cableway for a given quantity <strong>of</strong><br />

additional cables. The height <strong>of</strong> the cables must be lower than the partitions <strong>of</strong> the<br />

cableway as shown below. Covers also improve the EMC performance <strong>of</strong> cableways.<br />

In U-shaped cableways, the magnetic field decreases in the two corners.<br />

That explains why deep cableways are preferable (see Fig. Q10).<br />

NO!<br />

YES!<br />

Area protected against external EM field<br />

Different types <strong>of</strong> cables (power and low-level connections) should not be installed in<br />

the same bundle or in the same cableway. Cableways should never be filled to more<br />

than half capacity.


Q - EMC guidelines<br />

3 Implementation<br />

It is recommended to electromagnetically separate groups from one another, either<br />

using shielding or by installing the cables in different cableways. The quality <strong>of</strong> the<br />

shielding determines the distance between groups. If there is no shielding, sufficient<br />

distances must be maintained (see Fig. Q11).<br />

The distance between power and control cables must be at least 5 times the radius<br />

<strong>of</strong> the larger power cable.<br />

Forbidden Correct Ideal<br />

Power cables<br />

Auxiliary circuits (relay contacts)<br />

Control (digital)<br />

Measurements (analogue)<br />

Note: All metal parts must be <strong>electrical</strong>ly interconnected<br />

Fig. Q11 : Recommendation to install groups <strong>of</strong> cables in metal cableways<br />

Metal building components can be used for EMC purposes. Steel beams (L, H, U<br />

or T shaped) <strong>of</strong>ten form an uninterrupted earthed structure with large transversal<br />

sections and surfaces with numerous intermediate earthing connections. Cables<br />

should if possible be run along such beams. Inside corners are better than the<br />

outside surfaces (see Fig. Q12).<br />

Fig. Q12 : Recommendation to install cables in steel beams<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Recommended<br />

Acceptable<br />

Not recommended<br />

Both ends <strong>of</strong> metal cableways must always be connected to local earth electrodes.<br />

For very long cableways, additional connections to the earthing system are<br />

recommended between connected devices. Where possible, the distance between<br />

these earthing connections should be irregular (for symmetrical wiring systems) to<br />

avoid resonance at identical frequencies. All connections to the earthing system<br />

should be short.<br />

Metal and non-metal cableways are available. Metal solutions <strong>of</strong>fer better<br />

EMC characteristics. A cableway (cable trays, conduits, cable brackets, etc.) must<br />

<strong>of</strong>fer a continuous, conducting metal structure from beginning to end.<br />

An aluminium cableway has a lower DC resistance than a steel cableway <strong>of</strong> the<br />

same size, but the transfer impedance (Zt) <strong>of</strong> steel drops at a lower frequency,<br />

particularly when the steel has a high relative permeability µ r. Care must be taken<br />

when different types <strong>of</strong> metal are used because direct <strong>electrical</strong> connection is not<br />

authorised in certain cases to avoid corrosion. That could be a disadvantage in terms<br />

<strong>of</strong> EMC.<br />

When devices connected to the wiring system using unshielded cables are not<br />

affected by low-frequency disturbances, the EMC <strong>of</strong> non-metal cableways can be<br />

improved by adding a parallel earthing conductor (PEC) inside the cableway. Both<br />

ends must be connected to the local earthing system. Connections should be made<br />

to a metal part with low impedance (e.g. a large metal panel <strong>of</strong> the device case).<br />

The PEC should be <strong>design</strong>ed to handle high fault and common-mode currents.<br />

Q9<br />

© Schneider Electric - all rights reserved


Q10<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

3 Implementation<br />

Implementation<br />

When a metal cableway is made up <strong>of</strong> a number <strong>of</strong> short sections, care is required to<br />

ensure continuity by correctly bonding the different parts. The parts should preferably<br />

be welded along all edges. Riveted, bolted or screwed connections are authorised as<br />

long as the contact surfaces conduct current (no paint or insulating coatings) and are<br />

protected against corrosion. Tightening torques must be observed to ensure correct<br />

pressure for the <strong>electrical</strong> contact between two parts.<br />

When a particular shape <strong>of</strong> cableway is selected, it should be used for the entire<br />

length. All interconnections must have a low impedance. A single wire connection<br />

between two parts <strong>of</strong> the cableway produces a high local impedance that cancels its<br />

EMC performance.<br />

Starting at a few MHz, a ten-centimetre connection between two parts <strong>of</strong> the cableway<br />

reduces the attenuation factor by more than a factor <strong>of</strong> ten (see Fig. Q13).<br />

Fig. Q13 : Metal cableways assembly<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

NO!<br />

NOT RECOMMENDED<br />

YES!<br />

Each time modifications or extensions are made, it is very important to make sure<br />

they are carried out according to EMC <strong>rules</strong> (e.g. never replace a metal cableway by<br />

a plastic version!).<br />

Covers for metal cableways must meet the same requirements as those applying to<br />

the cableways themselves. A cover should have a large number <strong>of</strong> contacts along the<br />

entire length. If that is not possible, it must be connected to the cableway at least at<br />

the two ends using short connections (e.g. braided or meshed connections).<br />

When cableways must be interrupted to pass through a wall (e.g. firewalls), lowimpedance<br />

connections must be used between the two parts (see Fig. Q14).<br />

Mediocre OK Better<br />

Fig. Q14 : Recommendation for metal cableways assembly to pass through a wall


Q - EMC guidelines<br />

Fig. Q15 : Implementation <strong>of</strong> shielded cables<br />

All bonding connections must be made to bare metal<br />

Not acceptable<br />

Bonding wire<br />

Poorly connected shielding = reduced effectiveness<br />

Correct<br />

Equipotential metal panel<br />

3 Implementation<br />

3. Implementation <strong>of</strong> shielded cables<br />

When the decision is made to use shielded cables, it is also necessary to determine<br />

how the shielding will be bonded (type <strong>of</strong> earthing, connector, cable entry, etc.),<br />

otherwise the benefits are considerably reduced. To be effective, the shielding should<br />

be bonded over 360°. Figure Q1 below show different ways <strong>of</strong> earthing the cable<br />

shielding.<br />

For computer equipment and digital links, the shielding should be connected at each<br />

end <strong>of</strong> the cable.<br />

Connection <strong>of</strong> the shielding is very important for EMC and the following points should<br />

be noted.<br />

If the shielded cable connects equipment located in the same equipotential bonding<br />

area, the shielding must be connected to the exposed conductive parts (ECP) at<br />

both ends. If the connected equipment is not in the same equipotential bonding area,<br />

there are a number <strong>of</strong> possibilities.<br />

b Connection <strong>of</strong> only one end to the ECPs is dangerous. If an insulation fault occurs,<br />

the voltage in the shielding can be fatal for an operator or destroy equipment. In<br />

addition, at high frequencies, the shielding is not effective.<br />

b Connection <strong>of</strong> both ends to the ECPs can be dangerous if an insulation fault<br />

occurs. A high current flows in the shielding and can damage it. To limit this problem,<br />

a parallel earthing conductor (PEC) must be run next to the shielded cable. The size<br />

<strong>of</strong> the PEC depends on the short-circuit current in the given part <strong>of</strong> the <strong>installation</strong>.<br />

It is clear that if the <strong>installation</strong> has a well meshed earthing network, this problem<br />

does not arise.<br />

Collar, clamp, etc.<br />

Acceptable<br />

Ideal<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Collar, clamp, etc.<br />

Bonding bar<br />

connected<br />

to the chassis<br />

Cable gland = circumferential contact to<br />

equipotential metal panel<br />

3.7 Communication networks<br />

Communication networks cover large distances and interconnect equipment<br />

installed in rooms that may have distribution systems with different system earthing<br />

arrangements. In addition, if the various sites are not equipotential, high transient<br />

currents and major differences in potential may occur between the various devices<br />

connected to the networks. As noted above, this is the case when insulation<br />

faults and lightning strikes occur. The dielectric withstand capacity (between live<br />

conductors and exposed conductive parts) <strong>of</strong> communication cards installed in<br />

PCs or PLCs generally does not exceed 500 V. At best, the withstand capacity can<br />

reach 1.5 kV. In meshed <strong>installation</strong>s with the TN-S system and relatively small<br />

communication networks, this level <strong>of</strong> withstand capacity is acceptable. In all cases,<br />

however, protection against lightning strikes (common and differential modes) is<br />

recommended.<br />

Q11<br />

© Schneider Electric - all rights reserved


Q12<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

i<br />

VL1<br />

V arrestor<br />

VL2<br />

i<br />

Earthing bar<br />

Protected<br />

device<br />

Fig. Q16 : The protected device must be connected to the surge-arrestor terminals<br />

Earthing bar<br />

SA<br />

Isc<br />

prot<br />

SA<br />

3 Implementation<br />

The type <strong>of</strong> communication cable employed is an important parameter. It must<br />

be suited to the type <strong>of</strong> transmission. To create a reliable communication link, the<br />

following parameters must be taken into account:<br />

b Characteristic impedance<br />

b Twisted pairs or other arrangement<br />

b Resistance and capacitance per unit length<br />

b Signal attenutation per unit length<br />

b The type(s) <strong>of</strong> shielding used<br />

In addition, it is important to use symmetrical (differential) transmission links because<br />

they <strong>of</strong>fer higher performance in terms <strong>of</strong> EMC.<br />

In environments with severe EM conditions, however, or for wide communication<br />

networks between <strong>installation</strong>s that are not or are only slightly equipotential, in<br />

conjunction with IT, TT or TN-C systems, it is highly recommended to use optical<br />

fibre links.<br />

For safety reasons, the optical fibre must not have metal parts (risk <strong>of</strong> electric shock<br />

if the fibre links two areas with different potentials).<br />

3.8 Implementation <strong>of</strong> surge arrestors<br />

The wiring <strong>of</strong> surge arrestors is as important as the selection <strong>of</strong> the surge arrestor<br />

itself. Figures Q1 and Q17a below shows that the connection cables <strong>of</strong> the surge<br />

arrestor and its disconnection circuit-breaker must not exceed 50 centimetres to<br />

ensure effective protection.<br />

Common mode<br />

impedance<br />

1 m <strong>of</strong> cable = 1 µH<br />

L1 = 0.5 m = 0.5 µH<br />

L2 = 1.5 m = 1.5 µH<br />

di lightning = 10 kA<br />

dt = 10 µs<br />

V arrestor = 1,200 V<br />

Protected<br />

outgoers<br />

Common-mode impedance length y 50 cm<br />

Surge Arrestor<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Device withstand in common mode: 2,000 V<br />

V PROT = VL1 + VL2 + V arrestor<br />

where<br />

di<br />

10 kA<br />

VL1 = L1 = 0.5 µH x = 500 V<br />

dt<br />

10 µs<br />

di<br />

10 kA<br />

VL2 = L2 = 1.5 µH x = 1,500 V<br />

dt<br />

10 µs<br />

V PROT = 500 V + 1,500 V + 1,200 V = 3,200 V !<br />

L1 + L2 must therefore not exceed 0.5 m<br />

Protected<br />

outgoers<br />

Earthing bar<br />

Fig. Q17a : Examples <strong>of</strong> assemblies combining surge arrestors (SA) and disconnection circuit-breakers to reduce the common-mode impedances and the area <strong>of</strong><br />

upstream-downstream loops<br />

Isc<br />

prot<br />

SA


Q - EMC guidelines<br />

Fig. Q17b : The protected device must be connected to the surge-arrestor terminals<br />

3 Implementation<br />

3.9 Cabinet cabling (Fig. Q18)<br />

Each cabinet must be equipped with an earthing bar or a ground reference metal<br />

sheet. All shielded cables and external protection circuits must be connected to this<br />

point. Anyone <strong>of</strong> the cabinet metal sheets or the DIN rail can be used as the ground<br />

reference.<br />

Plastic cabinets are not recommended. In this case, the DIN rail must be used as<br />

ground reference.<br />

3.10 Standards<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Potential<br />

Reference Plate<br />

It is absolutely essential to specify the standards and recommendations that must be<br />

taken into account for <strong>installation</strong>s.<br />

Below are several documents that may be used:<br />

b EN 50174-1 Information technology - Cabling <strong>installation</strong>. Part 1:<br />

Specification and quality assurance<br />

b EN 50174-2 Information technology - Cabling <strong>installation</strong>. Part 2: Installation<br />

planning and practices inside buildings<br />

Q13<br />

© Schneider Electric - all rights reserved


Q14<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

4 Coupling mechanisms and<br />

counter-measures<br />

4.1 <strong>General</strong><br />

An EM interference phenomenon may be summed up in Figure Q18 below.<br />

Source Coupling<br />

Victim<br />

Origin <strong>of</strong><br />

emitted disturbances<br />

Example:<br />

Walkie-talkie TV set<br />

Fig. Q18 : EM interference phenomenon<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Means by which<br />

disturbances are<br />

transmitted<br />

Radiated waves<br />

Equipment likely<br />

to be disturbed<br />

The different sources <strong>of</strong> disturbances are:<br />

b Radio-frequency emissions<br />

v Wireless communication systems (radio, TV, CB, radio telephones, remote controls)<br />

v Radar<br />

b Electrical equipment<br />

v High-power industrial equipment (induction furnaces, welding machines, stator<br />

control systems)<br />

v Office equipment (computers and electronic circuits, photocopy machines, large<br />

monitors)<br />

v Discharge lamps (neon, fluorescent, flash, etc.)<br />

v Electromechanical components (relays, contactors, solenoids, current interruption<br />

devices)<br />

b Power systems<br />

v Power transmission and distribution systems<br />

v Electrical transportation systems<br />

b Lightning<br />

b Electrostatic discharges (ESD)<br />

b Electromagnetic nuclear pulses (EMNP)<br />

The potential victims are:<br />

b Radio and television receivers, radar, wireless communication systems<br />

b Analogue systems (sensors, measurement acquisition, amplifiers, monitors)<br />

b Digital systems (computers, computer communications, peripheral equipment)<br />

The different types <strong>of</strong> coupling are:<br />

b Common-mode impedance (galvanic) coupling<br />

b Capacitive coupling<br />

b Inductive coupling<br />

b Radiated coupling (cable to cable, field to cable, antenna to antenna)


Q - EMC guidelines<br />

4 Coupling mechanisms and<br />

counter-measures<br />

4.2 Common-mode impedance coupling<br />

Definition<br />

Two or more devices are interconnected by the power supply and communication<br />

cables (see Fig. Q19). When external currents (lightning, fault currents, disturbances)<br />

flow via these common-mode impedances, an undesirable voltage appears between<br />

points A and B which are supposed to be equipotential. This stray voltage can<br />

disturb low-level or fast electronic circuits.<br />

All cables, including the protective conductors, have an impedance, particularly at<br />

high frequencies.<br />

Stray<br />

overvoltage<br />

Z1<br />

Fig. Q19 : Definition <strong>of</strong> common-mode impedance coupling<br />

Examples (see Fig. Q20)<br />

Device 1<br />

b Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast<br />

or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load<br />

changes, chopping circuits, harmonic currents, power factor correction capacitor<br />

banks, etc.)<br />

b A common return path for a number <strong>of</strong> <strong>electrical</strong> sources<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Z sign.<br />

I2<br />

A B<br />

I1<br />

Z2<br />

Device 2<br />

ECPs ECPs<br />

Signal line<br />

The exposed conductive parts (ECP) <strong>of</strong> devices 1 and 2 are connected to a common<br />

earthing terminal via connections with impedances Z1 and Z2.<br />

The stray overvoltage flows to the earth via Z1. The potential <strong>of</strong> device 1 increases<br />

to Z1 I1. The difference in potential with device 2 (initial potential = 0) results in the<br />

appearance <strong>of</strong> current I2.<br />

I2<br />

Z1<br />

Z1 I1= ( Zsign + Z2)<br />

I2<br />

⇒ =<br />

I1<br />

Zsign + Z2<br />

( )<br />

I<br />

Current I2, present on the signal line, disturbs device 2.<br />

Device 1 Device 2<br />

Signal cable<br />

Disturbing<br />

current<br />

Difference in<br />

potential<br />

ZMC<br />

Disturbed<br />

cable<br />

Fig. Q20 : Example <strong>of</strong> common-mode impedance coupling<br />

Fault<br />

currents<br />

Lightning<br />

strike<br />

Q15<br />

© Schneider Electric - all rights reserved


Q16<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

U<br />

Vsource<br />

Vvictim<br />

Fig. Q22 : Typical result <strong>of</strong> capacitive coupling (capacitive<br />

cross-talk)<br />

t<br />

t<br />

4 Coupling mechanisms and<br />

counter-measures<br />

Counter-measures (see Fig. Q21)<br />

If they cannot be eliminated, common-mode impedances must at least be as low as<br />

possible. To reduce the effects <strong>of</strong> common-mode impedances, it is necessary to:<br />

b Reduce impedances:<br />

v Mesh the common references,<br />

v Use short cables or flat braids which, for equal sizes, have a lower impedance than<br />

round cables,<br />

v Install functional equipotential bonding between devices.<br />

b Reduce the level <strong>of</strong> the disturbing currents by adding common-mode filtering and<br />

differential-mode inductors<br />

Stray<br />

overvoltage<br />

Z1<br />

Device 1<br />

If the impedance <strong>of</strong> the parallel earthing conductor PEC (Z sup) is very low<br />

compared to Z sign, most <strong>of</strong> the disturbing current flows via the PEC, i.e. not<br />

via the signal line as in the previous case.<br />

The difference in potential between devices 1 and 2 becomes very low and the<br />

disturbance acceptable.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I1<br />

Z sign.<br />

I2<br />

Z sup.<br />

Fig. Q21 : Counter-measures <strong>of</strong> common-mode impedance coupling<br />

4.3 Capacitive coupling<br />

Definition<br />

Z2<br />

Device 2<br />

The level <strong>of</strong> disturbance depends on the voltage variations (dv/dt) and the value <strong>of</strong><br />

the coupling capacitance between the disturber and the victim.<br />

Capacitive coupling increases with:<br />

b The frequency<br />

b The proximity <strong>of</strong> the disturber to the victim and the length <strong>of</strong> the parallel cables<br />

b The height <strong>of</strong> the cables with respect to a ground referencing plane<br />

b The input impedance <strong>of</strong> the victim circuit (circuits with a high input impedance are<br />

more vulnerable)<br />

b The insulation <strong>of</strong> the victim cable (ε r <strong>of</strong> the cable insulation), particularly for tightly<br />

coupled pairs<br />

Figure Q22 shows the results <strong>of</strong> capacitive coupling (cross-talk) between two cables.<br />

Examples (see Fig. Q23 opposite page)<br />

b Nearby cables subjected to rapid voltage variations (dv/dt)<br />

b Start-up <strong>of</strong> fluorescent lamps<br />

b High-voltage switch-mode power supplies (photocopy machines, etc.)<br />

b Coupling capacitance between the primary and secondary windings <strong>of</strong><br />

transformers<br />

b Cross-talk between cables<br />

PEC


Q - EMC guidelines<br />

Source<br />

Metal shielding<br />

Fig. Q24 : Cable shielding with perforations reduces capacitive<br />

coupling<br />

C<br />

Victim<br />

4 Coupling mechanisms and<br />

counter-measures<br />

Differential mode Common mode<br />

Vs<br />

DM<br />

Source<br />

Counter-measures (see Fig. Q24)<br />

b Limit the length <strong>of</strong> parallel runs <strong>of</strong> disturbers and victims to the strict minimum<br />

b Increase the distance between the disturber and the victim<br />

b For two-wire connections, run the two wires as close together as possible<br />

b Position a PEC bonded at both ends and between the disturber and the victim<br />

b Use two or four-wire cables rather than individual conductors<br />

b Use symmetrical transmission systems on correctly implemented, symmetrical<br />

wiring systems<br />

b Shield the disturbing cables, the victim cables or both (the shielding must be<br />

bonded)<br />

b Reduce the dv/dt <strong>of</strong> the disturber by increasing the signal rise time where possible<br />

4.4 Inductive coupling<br />

Definition<br />

Iv<br />

DM<br />

Victim<br />

Vs DM: Source <strong>of</strong> the disturbing voltage (differential mode)<br />

Iv DM: Disturbing current on victim side (differential mode)<br />

Vs CM: Source <strong>of</strong> the disturbing voltage (common mode)<br />

Iv CM: Disturbing current on victim side (common mode)<br />

Fig. Q23 : Example <strong>of</strong> capacitive coupling<br />

The disturber and the victim are coupled by a magnetic field. The level <strong>of</strong> disturbance<br />

depends on the current variations (di/dt) and the mutual coupling inductance.<br />

Inductive coupling increases with:<br />

b The frequency<br />

b The proximity <strong>of</strong> the disturber to the victim and the length <strong>of</strong> the parallel cables,<br />

b The height <strong>of</strong> the cables with respect to a ground referencing plane,<br />

b The load impedance <strong>of</strong> the disturbing circuit.<br />

Examples (see Fig. Q25 next page)<br />

b Nearby cables subjected to rapid current variations (di/dt)<br />

b Short-circuits<br />

b Fault currents<br />

b Lightning strikes<br />

b Stator control systems<br />

b Welding machines<br />

b Inductors<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Vs<br />

CM<br />

Source Victim<br />

Iv<br />

CM<br />

Q17<br />

© Schneider Electric - all rights reserved


Q18<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

4 Coupling mechanisms and<br />

counter-measures<br />

Counter-measures<br />

b Limit the length <strong>of</strong> parallel runs <strong>of</strong> disturbers and victims to the strict minimum<br />

b Increase the distance between the disturber and the victim<br />

b For two-wire connections, run the two wires as close together as possible<br />

b Use multi-core or touching single-core cables, preferably in a triangular layout<br />

b Position a PEC bonded at both ends and between the disturber and the victim<br />

b Use symmetrical transmission systems on correctly implemented, symmetrical<br />

wiring systems<br />

b Shield the disturbing cables, the victim cables or both (the shielding must be<br />

bonded)<br />

b Reduce the dv/dt <strong>of</strong> the disturber by increasing the signal rise time where possible<br />

(series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on<br />

the disturbing and/or victim cable)<br />

4.5 Radiated coupling<br />

Definition<br />

i<br />

Disturbing<br />

cable<br />

H<br />

Victim pair<br />

Victim loop<br />

Differential mode Common mode<br />

Fig. Q25 : Example <strong>of</strong> inductive coupling<br />

The disturber and the victim are coupled by a medium (e.g. air). The level <strong>of</strong><br />

disturbance depends on the power <strong>of</strong> the radiating source and the effectiveness<br />

<strong>of</strong> the emitting and receiving antenna. An electromagnetic field comprises both an<br />

<strong>electrical</strong> field and a magnetic field. The two fields are correlated. It is possible to<br />

analyse separately the <strong>electrical</strong> and magnetic components.<br />

The <strong>electrical</strong> field (E field) and the magnetic field (H field) are coupled in wiring<br />

systems via the wires and loops (see Fig. Q26).<br />

E field<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

i<br />

i<br />

Disturbing<br />

cable<br />

Field-to-cable coupling Field-to-loop coupling<br />

Fig. Q26 : Definition <strong>of</strong> radiated coupling<br />

H<br />

H field<br />

V<br />

Victim loop


Q - EMC guidelines<br />

4 Coupling mechanisms and<br />

counter-measures<br />

When a cable is subjected to a variable <strong>electrical</strong> field, a current is generated in the<br />

cable. This phenomenon is called field-to-cable coupling.<br />

Similarly, when a variable magnetic field flows through a loop, it creates a counter<br />

electromotive force that produces a voltage between the two ends <strong>of</strong> the loop. This<br />

phenomenon is called field-to-loop coupling.<br />

Examples (see Fig. Q27)<br />

b Radio-transmission equipment (walkie-talkies, radio and TV transmitters, mobile<br />

services)<br />

b Radar<br />

b Automobile ignition systems<br />

b Arc-welding machines<br />

b Induction furnaces<br />

b Power switching systems<br />

b Electrostatic discharges (ESD)<br />

b Lighting<br />

Device<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

h<br />

Ground reference plane<br />

i<br />

EM field<br />

Signal<br />

cable<br />

Device 1 Device 2<br />

Example <strong>of</strong> field-to-cable coupling Example <strong>of</strong> field-to-loop coupling<br />

Fig. Q27 : Examples <strong>of</strong> radiated coupling<br />

Counter-measures<br />

E field<br />

h<br />

Area <strong>of</strong> the<br />

earth loop<br />

To minimise the effects <strong>of</strong> radiated coupling, the measures below are required.<br />

For field-to-cable coupling<br />

b Reduce the antenna effect <strong>of</strong> the victim by reducing the height (h) <strong>of</strong> the cable with<br />

respect to the ground referencing plane<br />

b Place the cable in an uninterrupted, bonded metal cableway (tube, trunking, cable<br />

tray)<br />

b Use shielded cables that are correctly installed and bonded<br />

b Add PECs<br />

b Place filters or ferrite rings on the victim cable<br />

For field-to-loop coupling<br />

b Reduce the surface <strong>of</strong> the victim loop by reducing the height (h) and the length<br />

<strong>of</strong> the cable. Use the solutions for field-to-cable coupling. Use the Faraday cage<br />

principle.<br />

Radiated coupling can be eliminated using the Faraday cage principle. A possible<br />

solution is a shielded cable with both ends <strong>of</strong> the shielding connected to the metal<br />

case <strong>of</strong> the device. The exposed conductive parts must be bonded to enhance<br />

effectiveness at high frequencies.<br />

Radiated coupling decreases with the distance and when symmetrical transmission<br />

links are used.<br />

Q19<br />

© Schneider Electric - all rights reserved


Q20<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

Unshielded cables <strong>of</strong><br />

different groups<br />

NO!<br />

h<br />

YES!<br />

Risk <strong>of</strong> cross-talk in common mode if e < 3 h<br />

Sensitive<br />

cable<br />

Disturbing<br />

cable<br />

e<br />

Shielded cables <strong>of</strong><br />

different groups<br />

Sensitive<br />

cable<br />

Disturbing<br />

cable<br />

30 cm u 1 m<br />

NO! YES!<br />

Ground<br />

reference<br />

plane<br />

Cross incompatible<br />

cables at right angles<br />

Fig. Q29 : Wiring recommendations for cables carrying<br />

different types <strong>of</strong> signals<br />

NO! YES!<br />

Standard cable<br />

Poorly implemented<br />

ribbon cable<br />

Digital connection<br />

Analogue pair<br />

Bonding wires<br />

Fig. Q30 : Use <strong>of</strong> cables and ribbon cable<br />

Two distinct pairs<br />

Correctly implemented<br />

ribbon cable<br />

5 Wiring recommendations<br />

5.1 Signal classes (see Fig. Q28)<br />

1 - Power connections<br />

(supply + PE)<br />

4 - Analogue link<br />

(sensor)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Device<br />

Fig. Q28 : Internal signals can be grouped in four classes<br />

2 - Relay<br />

connections<br />

3 - Digital link<br />

(bus)<br />

Four classes <strong>of</strong> internal signals are:<br />

b Class 1<br />

Mains power lines, power circuits with a high di/dt, switch-mode converters, powerregulation<br />

control devices.<br />

This class is not very sensitive, but disturbs the other classes (particularly in<br />

common mode).<br />

b Class 2<br />

Relay contacts.<br />

This class is not very sensitive, but disturbs the other classes (switching, arcs when<br />

contacts open).<br />

b Class 3<br />

Digital circuits (HF switching).<br />

This class is sensitive to pulses, but also disturbs the following class.<br />

b Class 4<br />

Analogue input/output circuits (low-level measurements, active sensor supply<br />

circuits). This class is sensitive.<br />

It is a good idea to use conductors with a specific colour for each class to<br />

facilitate identification and separate the classes. This is useful during <strong>design</strong> and<br />

troubleshooting.<br />

5.2 Wiring recommendations<br />

Cables carrying different types <strong>of</strong> signals must be physically separated<br />

(see Fig. Q29 above)<br />

Disturbing cables (classes 1 and 2) must be placed at some distance from the<br />

sensitive cables (classes 3 and 4) (see Fig. Q29 and Fig. Q30)<br />

In general, a 10 cm separation between cables laid flat on sheet metal is sufficient<br />

(for both common and differential modes). If there is enough space, a distance <strong>of</strong><br />

30 cm is preferable. If cables must be crossed, this should be done at right angles to<br />

avoid cross-talk (even if they touch). There are no distance requirements if the cables<br />

are separated by a metal partition that is equipotential with respect to the ECPs.<br />

However, the height <strong>of</strong> the partition must be greater than the diameter <strong>of</strong> the cables.


Q - EMC guidelines<br />

Power +<br />

analogue<br />

NO! YES!<br />

Digital +<br />

relay contacts<br />

Power connections<br />

Relay I/O connections<br />

Power +<br />

relay contacts<br />

Shielding<br />

Fig. Q31 : Incompatible signals = different cables<br />

NO! YES!<br />

Digital connections<br />

Analogue connections<br />

Digital +<br />

analogue<br />

Digital connections<br />

Analogue connections<br />

Fig. Q33 : Segregation applies to connectors as well!<br />

5 Wiring recommendations<br />

A cable should carry the signals <strong>of</strong> a single group (see Fig. Q31)<br />

If it is necessary to use a cable to carry the signals <strong>of</strong> different groups, internal<br />

shielding is necessary to limit cross-talk (differential mode). The shielding, preferably<br />

braided, must be bonded at each end for groups 1, 2 and 3.<br />

It is advised to overshield disturbing and sensitive cables (see Fig. Q32)<br />

The overshielding acts as a HF protection (common and differential modes) if it<br />

is bonded at each end using a circumferential connector, a collar or a clampere<br />

However, a simple bonding wire is not sufficient.<br />

Electronic<br />

control<br />

device<br />

Electronic<br />

control<br />

device<br />

Shielded pair<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

NO!<br />

Unshielded cable for stator control<br />

YES!<br />

Shielded pair + overshielding<br />

Shielded cable for stator control<br />

Electromechanical<br />

device<br />

Electromechanical<br />

device<br />

Fig. Q32 : Shielding and overshielding for disturbing and/or sensitive cables<br />

Sensor<br />

Bonded using a clamp<br />

Sensor<br />

Avoid using a single connector for different groups (see Fig. Q33)<br />

Except where necessary for groups 1 and 2 (differential mode). If a single connector<br />

is used for both analogue and digital signals, the two groups must be separated by at<br />

least one set <strong>of</strong> contacts connected to 0 V used as a barrier.<br />

All free conductors (reserve) must always be bonded at each end<br />

(see Fig. Q34)<br />

For group 4, these connections are not advised for lines with very low voltage<br />

and frequency levels (risk <strong>of</strong> creating signal noise, by magnetic induction, at the<br />

transmission frequencies).<br />

Wires not<br />

equipotentially<br />

bonded<br />

NO! YES!<br />

Electronic<br />

system<br />

Equipotential sheet metal panel<br />

Fig. Q34 : Free wires must be equipotentially bonded<br />

Electronic<br />

system<br />

Equipotential sheet metal panel<br />

Q21<br />

© Schneider Electric - all rights reserved


Q22<br />

© Schneider Electric - all rights reserved<br />

Q - EMC guidelines<br />

NO! YES!<br />

Power or disturbing cables<br />

Relay cables<br />

Measurement or sensitive cables<br />

Fig. Q37 : Cable distribution in cable trays<br />

Metal tray<br />

5 Wiring recommendations<br />

The two conductors must be installed as close together as possible<br />

(see Fig. Q35)<br />

This is particularly important for low-level sensors. Even for relay signals with a<br />

common, the active conductors should be accompanied by at least one common<br />

conductor per bundle. For analogue and digital signals, twisted pairs are a minimum<br />

requirement. A twisted pair (differential mode) guarantees that the two wires remain<br />

together along their entire length.<br />

PCB with<br />

relay contact<br />

I/Os<br />

- +<br />

Power supply<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

NO! YES!<br />

Area <strong>of</strong><br />

loop too large<br />

PCB with<br />

relay contact<br />

I/Os<br />

Fig. Q35 : The two wires <strong>of</strong> a pair must always be run close together<br />

- +<br />

Power supply<br />

Group-1 cables do not need to be shielded if they are filtered<br />

But they should be made <strong>of</strong> twisted pairs to ensure compliance with the previous<br />

section.<br />

Cables must always be positioned along their entire length against the bonded<br />

metal parts <strong>of</strong> devices (see Fig. Q36)<br />

For example: Covers, metal trunking, structure, etc. In order to take advantage <strong>of</strong> the<br />

dependable, inexpensive and significant reduction effect (common mode) and anticross-talk<br />

effect (differential mode).<br />

Power<br />

supply<br />

NO! YES!<br />

Chassis 1<br />

Chassis 2<br />

Chassis 3<br />

I/O interface<br />

Power<br />

supply<br />

Chassis 1<br />

Chassis 2<br />

Chassis 3<br />

I/O interface<br />

All metal parts (frame, structure, enclosures, etc.) are equipotential<br />

Fig. Q36 : Run wires along their entire length against the bonded metal parts<br />

The use <strong>of</strong> correctly bonded metal trunking considerably improves<br />

internal EMC (see Fig. Q37)


Schneider Electric Industries SAS<br />

Head Office<br />

89, bd Franklin Roosevelt<br />

92506 Rueil-Malmaison Cedex<br />

FRANCE<br />

EIGED306001EN<br />

ART. 822690<br />

As standards, specifications and <strong>design</strong>s change from time, please ask for confirmation <strong>of</strong> the<br />

information given in this publication.<br />

ISBN 978-2-9531643-0-5<br />

This document has been<br />

printed on ecological paper<br />

9 782953 164305<br />

03/2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!