SELECTION GUIDE<br />
Water Penetration Ratings<br />
Model Blade Blade Blade Free Velocity Air Volume Page<br />
Depth Angle Style Area (fpm) (cfm)<br />
1<br />
United States Court House, WA<br />
Miami-Dade <strong>Louver</strong>s<br />
ECD-545-MD<br />
EFD-637-MD<br />
Wind-Driven Rain <strong>Louver</strong>s<br />
ECV-445<br />
ECD-445<br />
ECD-545<br />
ECD-635<br />
ECV-545<br />
ECV-645<br />
ECD-745<br />
EFJ-745<br />
Drainable <strong>Louver</strong>s<br />
EDD-445<br />
EDD-637<br />
EFD-245<br />
EFD-435<br />
EFD-437<br />
EFD-445<br />
EFD-637<br />
EFD-645<br />
ERD-645<br />
Drainable-Head <strong>Louver</strong>s<br />
EFJ-437-HP<br />
EFJ-637-HP<br />
Non-Drainable <strong>Louver</strong>s<br />
EFJ-245<br />
EFY-245<br />
EFJ-430<br />
EFK-430<br />
EFJ-437<br />
EFK-437<br />
EFJ-445<br />
EFK-445<br />
EFY-445<br />
EFK-637<br />
EFJ-645<br />
Operable <strong>Louver</strong>s<br />
EOD-445<br />
EOD-637<br />
EOJ-445<br />
EOJ-637<br />
Formed Metal <strong>Louver</strong>s<br />
SFJ-245<br />
SFJ-430<br />
SFD-445<br />
SFJ-445<br />
SFK-445<br />
SFV-445<br />
SFJ-630<br />
SFD-635<br />
SFJ-645<br />
SFK-645<br />
Acoustical <strong>Louver</strong>s<br />
EAA-645<br />
EAA-845<br />
SAJ-835<br />
SAJ-1235<br />
EAA-1245<br />
FAA-1245<br />
Combination <strong>Louver</strong>s<br />
EBE-445<br />
EBI-445<br />
EXD-437<br />
EXD-645<br />
Sight Screens<br />
HJ-445<br />
HJ-645<br />
HT-401<br />
HZ-200<br />
VT-250<br />
VT-654<br />
VV-400<br />
VV-500<br />
Grilles<br />
Sunshades<br />
Penthouses<br />
EFD-637-MDPH<br />
EPJ-445<br />
5"<br />
6"<br />
4"<br />
4"<br />
5"<br />
6"<br />
5"<br />
6"<br />
7"<br />
7"<br />
4"<br />
6"<br />
2"<br />
4"<br />
4"<br />
4"<br />
6"<br />
6"<br />
6"<br />
4"<br />
6"<br />
2"<br />
2"<br />
4"<br />
4"<br />
4"<br />
4"<br />
4"<br />
4"<br />
4"<br />
6"<br />
6"<br />
4"<br />
6"<br />
4"<br />
6"<br />
2"<br />
4"<br />
4"<br />
4"<br />
4"<br />
4"<br />
6"<br />
6"<br />
6"<br />
6"<br />
6"<br />
8"<br />
8"<br />
12"<br />
12"<br />
12"<br />
4"<br />
4"<br />
4"<br />
6"<br />
4"<br />
6"<br />
4"<br />
2-1/4"<br />
2"<br />
4"<br />
4"<br />
5"<br />
6"<br />
4"<br />
Horizontal<br />
Horizontal<br />
Vertical<br />
Horizontal<br />
Horizontal<br />
Horizontal<br />
Vertical<br />
Vertical<br />
Horizontal<br />
Horizontal<br />
Dual-Drainable<br />
Dual Drainable<br />
Thinline-Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Recessed-Drainable<br />
High Performance-J<br />
High Performance-J<br />
Thinline-J<br />
Thinline-Inverted Y<br />
J<br />
K<br />
J<br />
K<br />
J<br />
K<br />
Inverted Y<br />
K<br />
J<br />
Operable-Drainable<br />
Operable-Drainable<br />
Operable-J<br />
Operable-J<br />
J<br />
J<br />
Drainable<br />
J<br />
K<br />
Chevron<br />
J<br />
Drainable<br />
J<br />
K<br />
Extruded-Airfoil<br />
Extruded Airfoil<br />
Formed-J<br />
Formed-J<br />
Extruded-Airfoil<br />
Formed-Airfoil<br />
J-BD-Exhaust<br />
J-BD-Intake<br />
Combination<br />
Combination<br />
Horizontal-Inverted J<br />
Horizontal-Inverted J<br />
Horizontal Airfoil<br />
Horizontal-Cladding<br />
Vertical-Cladding<br />
Vertical-Cladding<br />
Vertical-V<br />
Vertical-V<br />
Extruded Aluminum<br />
Extruded Aluminum<br />
46%<br />
58%<br />
36%<br />
43%<br />
46%<br />
54%<br />
42%<br />
46%<br />
53%<br />
44%<br />
50%<br />
58%<br />
43%<br />
58%<br />
58%<br />
47%<br />
58%<br />
55%<br />
51%<br />
56%<br />
56%<br />
47%<br />
38%<br />
57%<br />
57%<br />
57%<br />
57%<br />
50%<br />
50%<br />
39%<br />
50%<br />
50%<br />
43%<br />
58%<br />
49%<br />
56%<br />
42%<br />
51%<br />
53%<br />
48%<br />
48%<br />
38%<br />
65%<br />
62%<br />
50%<br />
50%<br />
30%<br />
37%<br />
33%<br />
31%<br />
26%<br />
26%<br />
49%<br />
49%<br />
45%<br />
44%<br />
50%<br />
50%<br />
60%<br />
19%<br />
24%<br />
21%<br />
39%<br />
54%<br />
59%<br />
51%<br />
1250<br />
1097<br />
1250<br />
1250<br />
1250<br />
1217<br />
1250<br />
1250<br />
1197<br />
1250<br />
1026<br />
1113<br />
955<br />
966<br />
903<br />
990<br />
1113<br />
1050<br />
990<br />
912<br />
915<br />
583<br />
383<br />
889<br />
889<br />
721<br />
721<br />
689<br />
689<br />
745<br />
832<br />
800<br />
1024<br />
990<br />
683<br />
810<br />
603<br />
847<br />
715<br />
775<br />
775<br />
600<br />
825<br />
815<br />
800<br />
800<br />
980<br />
772<br />
808<br />
924<br />
999<br />
999<br />
689<br />
689<br />
1161<br />
1050<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
990<br />
689<br />
9250<br />
10191<br />
7125<br />
8585<br />
9250<br />
10508<br />
8375<br />
9250<br />
10018<br />
8755<br />
8311<br />
10242<br />
6494<br />
8984<br />
8398<br />
7425<br />
10242<br />
9240<br />
8059<br />
8220<br />
8226<br />
4373<br />
2336<br />
8090<br />
8090<br />
6547<br />
6547<br />
5549<br />
5549<br />
4589<br />
6673<br />
6416<br />
7096<br />
9108<br />
5396<br />
7282<br />
4040<br />
6945<br />
6092<br />
5991<br />
5991<br />
3648<br />
8580<br />
8044<br />
6400<br />
6400<br />
4704<br />
4564<br />
4293<br />
4528<br />
4196<br />
4196<br />
5396<br />
5396<br />
8359<br />
7455<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
9405<br />
5549<br />
2<br />
2<br />
3<br />
3<br />
3<br />
3<br />
3<br />
3<br />
3<br />
3<br />
4<br />
4<br />
4<br />
4<br />
4<br />
4<br />
4<br />
4<br />
4<br />
5<br />
5<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
6<br />
7<br />
7<br />
7<br />
7<br />
8<br />
8<br />
8<br />
8<br />
8<br />
8<br />
8<br />
8<br />
8<br />
8<br />
9<br />
9<br />
9<br />
9<br />
9<br />
9<br />
10<br />
10<br />
10<br />
10<br />
11<br />
11<br />
11<br />
11<br />
11<br />
11<br />
11<br />
11<br />
12<br />
13<br />
14<br />
14<br />
45°<br />
37-1/2°<br />
45°<br />
45°<br />
45°<br />
35°<br />
45°<br />
45°<br />
45°<br />
45°<br />
45°<br />
37-1/2°<br />
45°<br />
35°<br />
37-1/2°<br />
47°<br />
37-1/2°<br />
45°<br />
45°<br />
37-1/2°<br />
37-1/2°<br />
45°<br />
45°<br />
30°<br />
30°<br />
37-1/2°<br />
37-1/2°<br />
45°<br />
45°<br />
45°<br />
37-1/2°<br />
45°<br />
45°<br />
37-1/2°<br />
45°<br />
37-1/2°<br />
45°<br />
30°<br />
45°<br />
45°<br />
45°<br />
45°<br />
30°<br />
35°<br />
45°<br />
45°<br />
45°<br />
45°<br />
35°<br />
35°<br />
45°<br />
45°<br />
45°<br />
45°<br />
37-1/2°<br />
37-1/2°– 45°<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
37-1/2°<br />
45°
Miami-Dade <strong>Louver</strong>s<br />
The ECD-545-MD and EFD-637-MD are engineered and tested to withstand extreme loads,<br />
debris impact, and cyclic fatigue failure associated with the severe weather effects of<br />
hurricanes (ECD-545-MD has Miami-Dade approval # 11-0429.02 and the EFD-637-MD has<br />
Miami-Dade approval # 11-0429.01).<br />
Constructed from 6063-T5 extruded aluminum, both models have single section assemblies up<br />
to 48" wide by 144" high. Specially designed water-resistant seam covers further enhance<br />
performance and aesthetics of these industry leading products. Single-section louvers are now<br />
available with the option of a factory-installed sleeve which allows louver installation without<br />
any mechanical anchoring to the building condition.<br />
Mosaic on<br />
Miami Beach, FL<br />
ECD-545-MD<br />
(Sight Proof)<br />
EFD-637-MD<br />
‹ 5" › ‹ 6" ›<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model ECD-545-MD shown hereon is<br />
licensed to bear the AMCA seal. The ratings shown are<br />
based on test and procedures performed in accordance<br />
with AMCA Publication 511 and comply with the requirements<br />
of the AMCA Certified Ratings Program. The AMCA<br />
Certified Ratings Seal applies to air performance, water<br />
penetration and wind-driven rain ratings.<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model EFD-637-MD shown hereon is<br />
licensed to bear the AMCA seal. The ratings shown are<br />
based on test and procedures performed in accordance<br />
with AMCA Publication 511 and comply with the requirements<br />
of the AMCA Certified Ratings Program. The AMCA<br />
Certified Ratings Seal applies to air performance and<br />
water penetration ratings.<br />
Maximum Size Wall Construction Installation Method<br />
Single Section - 48"w x 144"h<br />
Multiple Section - Unlimited width x 144"h<br />
Multiple Section - 48"w x Unlimited Height<br />
Structural steel mullion support<br />
required for installations more than<br />
one section wide.<br />
Installations of unlimited width and<br />
height available with additional<br />
engineer-approved support structure.<br />
<strong>All</strong> Types<br />
Steel<br />
Direct Connection - Clip angles*<br />
Masonry<br />
Tension or Shear Connection - Clip angles*<br />
Wood<br />
Direct Connection - Clip angles*<br />
<strong>All</strong> Types (Single Section Only)<br />
Flanged sleeve with continuous retaining angles<br />
(No anchors required)<br />
*Anchors supplied by others<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
Class<br />
Miami Dade<br />
Approval<br />
ECD-545-MD<br />
5"<br />
45°<br />
Horizontal<br />
0.081"<br />
46<br />
7.4<br />
1250<br />
9250<br />
0.22<br />
A (29 mph)<br />
#11-0429.02<br />
EFD-637-MD<br />
6"<br />
37.5°<br />
Horizontal<br />
0.081"<br />
58<br />
9.3<br />
1097<br />
10191<br />
0.17<br />
-<br />
#11-0429.01<br />
<strong>All</strong>-<strong>Lite</strong> architectural products are designed for use in most geographical areas within the United States. <strong>All</strong>-<strong>Lite</strong> can also design, modify or reinforce standard products for special requirements, such as high wind, heavy snow, industrial environments, special<br />
mounting conditions, etc. Consult your local representative for more information.<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />
The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of<br />
safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver size having 39-3/8” x 39-3/8” core area.<br />
2
Wind-Driven Rain <strong>Louver</strong>s<br />
Backed by AMCA certification our wind-driven rain louvers offer exceptional protection under the most severe conditions and are<br />
available in frame depths from 4" to 7". The closely spaced vertical blade design of the Florida Building Code approved<br />
ECV-645 provides our most effective wind-driven rain performance with 100% effectiveness at wind velocities up to 50 mph and<br />
rainfall up to 8 in/hr. When aesthetic requirements demand a more conventional horizontal blade profile our EFJ-745 is the ideal<br />
solution with 5" on center traditional J-blade fascia and 100% effectiveness @ 3 in/hr rainfall.<br />
ECV-445<br />
ECV-645<br />
ECV-545<br />
EFJ-745<br />
ECD-445<br />
ECD-545<br />
ECD-635<br />
ECD-745<br />
plan view<br />
‹ ›<br />
4"<br />
ECV-445<br />
‹ ›<br />
5"<br />
6"<br />
plan view<br />
ECV-645<br />
ECV-545<br />
‹ 7" › ‹<br />
4"<br />
5" › ‹ 7" ›<br />
6"<br />
Wind-Driven Rain Ratings<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Style<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Wind<br />
Velocity<br />
Rainfall<br />
(In/Hr)<br />
Ventilation<br />
Rate (cfm)<br />
Effectiveness<br />
Ratio (%)<br />
Class<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
Florida Building<br />
Code Approval<br />
ECV-445<br />
4"<br />
Vertical<br />
36<br />
5.7<br />
29 mph<br />
3<br />
4211<br />
99.8<br />
A<br />
1250<br />
7125<br />
0.76<br />
-<br />
ECD-445<br />
4"<br />
Horizontal<br />
43<br />
6.9<br />
29 mph<br />
3<br />
5587<br />
99.0<br />
A<br />
1250<br />
8585<br />
0.31<br />
-<br />
ECD-545<br />
5"<br />
Horizontal<br />
46<br />
7.4<br />
29/50 mph<br />
3/8<br />
9539/10594<br />
99.4/95.3<br />
A/B<br />
1250<br />
9250<br />
0.24<br />
#13619.1<br />
ECD-635<br />
6"<br />
Horizontal<br />
54<br />
8.6<br />
29 mph<br />
3<br />
6372<br />
96.6<br />
B<br />
1217<br />
10508<br />
0.29<br />
-<br />
ECV-545<br />
5"<br />
Vertical<br />
42<br />
6.7<br />
29/50 mph<br />
3/8<br />
7356/9485<br />
99.9/99.6<br />
A<br />
1250<br />
8375<br />
0.25<br />
-<br />
ECV-645<br />
6"<br />
Vertical<br />
46<br />
7.4<br />
50 mph<br />
8<br />
10,390<br />
100.0<br />
A<br />
1250<br />
9250<br />
0.15<br />
#13683.2<br />
ECD-745<br />
7"<br />
Horizontal<br />
53<br />
8.4<br />
29 mph<br />
3<br />
7244<br />
99.9<br />
A<br />
1197<br />
10018<br />
0.50<br />
-<br />
EFJ-745<br />
7"<br />
Horizontal<br />
44<br />
7.0<br />
29 mph<br />
3<br />
7211<br />
99.3<br />
A<br />
1250<br />
8755<br />
0.47<br />
-<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model ECV-645 and EFJ-745 shown hereon<br />
are licensed to bear the AMCA seal. The ratings shown are based<br />
on test and procedures performed in accordance with AMCA<br />
Publication 511 and comply with the requirements of the AMCA<br />
Certified Ratings Program. The AMCA Certified Ratings Seal<br />
applies to wind driven rain ratings.<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model ECV-445 shown hereon is licensed to<br />
bear the AMCA seal. The ratings shown are based on test and<br />
procedures performed in accordance with AMCA Publication 511<br />
and comply with the requirements of the AMCA Certified Ratings<br />
Program. The AMCA Certified Ratings Seal applies to wind driven<br />
rain and air performance ratings.<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model ECD-445, ECD-545, ECD-635, ECD-745 and<br />
ECV-545 shown hereon are licensed to bear the AMCA seal. The ratings<br />
shown are based on test and procedures performed in accordance with<br />
AMCA Publication 511 and comply with the requirements of the AMCA<br />
Certified Ratings Program. The AMCA Certified Ratings Seal applies to<br />
water penetration ratings, air performance and wind driven rain ratings.<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a<br />
simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area<br />
and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test<br />
provides a method for comparing louver models and designs as to their efficiency in resisting the penetration<br />
of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with<br />
a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted<br />
penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver<br />
size having 39-3/8” x 39-3/8” core area.<br />
3<br />
<strong>All</strong>-<strong>Lite</strong> architectural products are designed for use in most geographical areas within the United States. <strong>All</strong>-<strong>Lite</strong> can also design, modify or reinforce standard products for special requirements, such as high<br />
wind, heavy snow, industrial environments, special mounting conditions, etc. Consult your local representative for more information.<br />
Dallas Cowboys Stadium, TX
Drainable <strong>Louver</strong>s<br />
Drainable blade louvers are designed to prevent water penetration in non-wind-driven rain<br />
applications by collecting water in the blade gutters and channeling it into frame downspouts<br />
and away from airflow paths. Our ERD-645 incorporates a recessed mullion and<br />
downspout that provides the appearance of a continuous drainable blade design.<br />
Columbus International<br />
Airport, OH<br />
EDD-445<br />
EDD-637<br />
EFD-435<br />
EFD-437<br />
EFD-637<br />
EFD-245<br />
EFD-445<br />
EFD-645<br />
ERD-645<br />
4"<br />
‹ 6" ›<br />
2"<br />
4" 4"<br />
‹ › ‹ 4"<br />
6"<br />
6"<br />
› ‹ › ‹ ›<br />
6"<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
Florida Building<br />
Code Approval<br />
EDD-445<br />
4"<br />
45°<br />
Dual-Drainable<br />
50<br />
8.1<br />
0.081"<br />
1026<br />
8311<br />
0.16<br />
-<br />
EDD-637<br />
EFD-245<br />
EFD-435<br />
EFD-437<br />
EFD-445<br />
EFD-637<br />
EFD-645<br />
ERD-645<br />
6"<br />
2"<br />
4"<br />
4"<br />
4"<br />
6"<br />
6"<br />
6"<br />
37.5°<br />
45°<br />
35°<br />
37.5°<br />
47°<br />
37.5°<br />
45°<br />
45°<br />
Dual-Drainable<br />
Thinline-Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Drainable<br />
Recessed-Drainable<br />
58<br />
43<br />
58<br />
58<br />
47<br />
58<br />
55<br />
51<br />
9.2<br />
6.8<br />
9.3<br />
9.3<br />
7.5<br />
9.2<br />
8.8<br />
8.1<br />
0.081"<br />
0.081"<br />
0.081"<br />
0.081"<br />
0.081"<br />
0.081"<br />
0.081"<br />
0.081"<br />
1113<br />
955<br />
966<br />
903<br />
990<br />
1113<br />
1050<br />
990<br />
10242<br />
6494<br />
8984<br />
8398<br />
7425<br />
10242<br />
9240<br />
8059<br />
0.15<br />
0.14<br />
0.12<br />
0.13<br />
0.14<br />
0.15<br />
0.15<br />
0.11<br />
-<br />
-<br />
-<br />
#13683.3<br />
#13683.4<br />
#13683.5<br />
#13683.6<br />
-<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that models EFD-435, EFD-437, EFD-445, EFD-637 and<br />
EFD-645 shown hereon are licensed to bear the AMCA seal. The ratings<br />
shown are based on test and procedures performed in accordance with<br />
AMCA Publication 511 and comply with the requirements of the AMCA<br />
Certified Ratings Program. The AMCA Certified Ratings Seal applies to air<br />
performance and water penetration ratings. Models EFD-245 and ERD-<br />
645 are not licensed to bear the AMCA seal.<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />
The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety<br />
below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />
4
Drainable Head <strong>Louver</strong>s<br />
Drainable head louvers blend the aesthetic appeal of a non-drainable blade with the high performance water penetration<br />
protection of a drainable blade louver. These louvers incorporate a drainable head member to capture water that<br />
cascades down the face of the building and channels it into downspouts and away from the airflow paths.<br />
These louvers are available in a wide array of anodized and painted<br />
finishes including custom color matching. They are available with<br />
an optional hidden vertical mullion.<br />
EFJ-437-HP<br />
EFJ-637-HP<br />
Pennsylvania State University, PA<br />
‹ 4" › ‹ 6" ›<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade Angle<br />
Blade Style<br />
Material/Free Area<br />
(6063-T5 Ext. Alum.)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
EFJ-437-HP<br />
4"<br />
37.5°<br />
High Performance - J<br />
0.081"<br />
56<br />
9.0<br />
912<br />
8220<br />
0.14<br />
EFJ-637-HP<br />
6"<br />
37.5°<br />
High Performance - J<br />
0.081"<br />
56<br />
9.0<br />
915<br />
8226<br />
0.12<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that model EFJ-437-HP shown hereon is licensed to<br />
bear the AMCA seal. The ratings shown are based on test and procedures<br />
performed in accordance with AMCA Publication 511 and<br />
comply with the requirements of the AMCA Certified Ratings<br />
Program. The AMCA Certified Ratings Seal applies to air performance<br />
and water penetration ratings. Model EFJ-637-HP is not<br />
licensed to bear the AMCA seal.<br />
5<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area<br />
and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration<br />
of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted<br />
penetration during severe storm conditions.<br />
Pennsylvania State University Chemical Laboratory, PA
Non-Drainable <strong>Louver</strong>s<br />
Available in a wide array of blade shapes and frame depths non-drainable louvers<br />
offer value and economy for exhaust applications or intake conditions where<br />
protection against water infiltration is not critical. Optional hidden mullions provide a<br />
continuous blade appearance on multiple section assemblies. Ideally suited for special<br />
shapes and transitional designs.<br />
Clayton Elementary<br />
School, GA<br />
EFY-245<br />
EFY-445<br />
EFJ-430<br />
EFK-430<br />
EFJ-437<br />
EFK-437<br />
EFK-637<br />
EFJ-245<br />
EFJ-445<br />
EFK-445<br />
EFJ-645<br />
4"<br />
(102)<br />
2"<br />
2"<br />
‹ 4" › ‹<br />
4"<br />
› 4"<br />
6"<br />
4"<br />
‹ 6" › ‹ ›<br />
6"<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
Florida Building Code<br />
Approval<br />
EFJ-245<br />
2"<br />
45°<br />
Thinline – J<br />
0.060"<br />
47<br />
7.5<br />
583<br />
4373<br />
0.06<br />
-<br />
EFY-245<br />
2"<br />
45°<br />
Thinline – Inverted<br />
0.060"<br />
38<br />
6.1<br />
383<br />
2336<br />
0.06<br />
-<br />
EFJ-430/EFK-430<br />
4"<br />
30°<br />
J/K<br />
0.081"<br />
57<br />
9.1<br />
889<br />
8090<br />
0.09<br />
-<br />
EFJ-437/EFK-437<br />
4"<br />
37.5°<br />
J/K<br />
0.081"<br />
57<br />
9.1<br />
721<br />
6547<br />
0.07<br />
#13683.7/13683.9<br />
EFJ-445/EFK-445<br />
4"<br />
45°<br />
J/K<br />
0.081"<br />
50<br />
8.0<br />
689<br />
5549<br />
0.08<br />
#13683.8/13683.10<br />
EFY-445<br />
6"<br />
45°<br />
Inverted Y<br />
0.081"<br />
39<br />
6.2<br />
745<br />
4589<br />
0.18<br />
-<br />
EFK-637<br />
6"<br />
37.5°<br />
K<br />
0.081"<br />
50<br />
8.0<br />
832<br />
6673<br />
0.05<br />
-<br />
EFJ-645<br />
6"<br />
45°<br />
J<br />
0.081"<br />
50<br />
8.0<br />
800<br />
6416<br />
0.10<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that models EFJ-437, EFK-437, EFJ-445, and EFK-445 shown hereon are licensed to bear the AMCA<br />
seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and<br />
comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to<br />
air performance and water penetration ratings. Models EFJ-245, EFY-245, EFJ-430, EFK-430, EFY-445, EFK-637, and<br />
EFJ-645 are not licensed to bear the AMCA seal.<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />
The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety<br />
below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />
6
Operable <strong>Louver</strong>s<br />
Operable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These<br />
units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or<br />
automatically with electric or pneumatic actuators.<br />
EOJ-445<br />
EOD-445<br />
EOD-637<br />
EOJ-637<br />
‹ 4" › ‹ 4" › ‹ 6" › ‹ 6" ›<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
EOJ-445<br />
4"<br />
45°<br />
Operable-J<br />
0.081"<br />
49<br />
7.9<br />
683<br />
5396<br />
0.10<br />
EOD-445<br />
4"<br />
45°<br />
Operable - Drainable<br />
0.081"<br />
43<br />
6.9<br />
1024<br />
7096<br />
0.16<br />
EOD-637<br />
6"<br />
37.5°<br />
Operable - Drainable<br />
0.081"<br />
58<br />
9.2<br />
990<br />
9108<br />
0.11<br />
EOJ-637<br />
6"<br />
37.5°<br />
Operable -J<br />
0.081"<br />
56<br />
9.0<br />
810<br />
7282<br />
0.12<br />
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured<br />
through a 48"x 48" louver during a 15 minute period. The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab<br />
conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />
7
Formed Metal <strong>Louver</strong>s<br />
Typically formed from galvanized steel, these units offer an economical solution for basic<br />
ventilation requirements. Optionally available in a wide array of exotic metals including<br />
copper and stainless steel our formed metal louvers can also serve to accent building<br />
architecture or withstand corrosion in caustic environments.<br />
Valley Metro,<br />
Phoenix, AZ<br />
SFV-445<br />
SFJ-430<br />
SFJ-630<br />
SFK-445<br />
SFJ-245<br />
SFJ-445<br />
SFJ-645<br />
SFK-645<br />
SFD-445<br />
SFD-635<br />
2"<br />
4"<br />
4"<br />
‹ › ‹ 4"<br />
4"<br />
6"<br />
6"<br />
› ‹ › ‹ › ‹ ›<br />
6"<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Material<br />
(Galvanized Steel)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
SFJ-245<br />
4"<br />
45°<br />
J<br />
20GA<br />
42<br />
6.7<br />
603<br />
4040<br />
0.06<br />
SFJ-430<br />
4"<br />
30°<br />
J<br />
20GA<br />
51<br />
8.2<br />
847<br />
6945<br />
0.13<br />
SFD-445<br />
4"<br />
45°<br />
Drainable<br />
20GA<br />
53<br />
8.5<br />
715<br />
6092<br />
0.11<br />
SFJ-445/SFK-445<br />
4"<br />
45°<br />
J/K<br />
20GA<br />
48<br />
7.7<br />
775<br />
5991<br />
0.13<br />
SFV-445<br />
4"<br />
45°<br />
Chevron<br />
20GA<br />
38<br />
6.1<br />
600<br />
3648<br />
0.25<br />
SFJ-630<br />
6"<br />
45°<br />
J<br />
20GA<br />
65<br />
10.4<br />
825<br />
8580<br />
0.08<br />
SFD-635<br />
6"<br />
45°<br />
Drainable<br />
20GA<br />
62<br />
9.9<br />
815<br />
8044<br />
0.08<br />
SFJ-645/SFK-645<br />
6"<br />
45°<br />
J<br />
20GA<br />
50<br />
8.0<br />
800<br />
6400<br />
0.09<br />
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />
The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below<br />
the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />
8
Acoustical <strong>Louver</strong>s<br />
Recommended for installation in noisy environments, acoustical louvers incorporate insulated blades that restrict sound<br />
transmission through the louver over a wide range of frequencies. Our airfoil blade designs offer lower static pressure loss<br />
and softer aesthetics for critical airflow performance applications.<br />
SAJ-835<br />
SAJ-1235<br />
EAA-645<br />
EAA-845<br />
EAA-1245<br />
FAA-1245<br />
8"<br />
6"<br />
‹<br />
12"<br />
› ‹ 8" › ‹ 12" ›<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade Style<br />
Noise Reduction<br />
125 250 500 1K 2K 4K<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
EAA-645<br />
6"<br />
Extruded - Airfoil<br />
11<br />
11<br />
13<br />
16<br />
18<br />
17<br />
30<br />
4.8<br />
980<br />
4704<br />
0.10<br />
EAA-845<br />
8"<br />
Extruded - Airfoil<br />
8<br />
8<br />
10<br />
14<br />
15<br />
13<br />
37<br />
5.9<br />
772<br />
4564<br />
0.05<br />
SAJ-835<br />
8"<br />
Formed - J<br />
13<br />
13<br />
19<br />
26<br />
28<br />
23<br />
33<br />
5.3<br />
808<br />
4293<br />
0.07<br />
SAJ-1235<br />
12"<br />
Formed - J<br />
15<br />
17<br />
22<br />
27<br />
31<br />
28<br />
31<br />
4.9<br />
924<br />
4528<br />
0.08<br />
EAA-1245<br />
12"<br />
Extruded - Airfoil<br />
13<br />
14<br />
17<br />
19<br />
18<br />
17<br />
26<br />
4.2<br />
999<br />
4196<br />
0.09<br />
FAA-1245<br />
12"<br />
Formed - Airfoil<br />
13<br />
14<br />
17<br />
19<br />
18<br />
17<br />
26<br />
4.2<br />
999<br />
4196<br />
0.09<br />
Certified Ratings:<br />
<strong>All</strong>-<strong>Lite</strong> certifies that models SAJ-835, SAJ-1235, EAA-845 and FAA-1245, shown hereon is licensed to<br />
bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with<br />
AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The<br />
AMCA Certified Ratings Seal applies to air performance and water penetration ratings. Models EAA-645<br />
and EAA-1245 are not licensed to bear the AMCA seal.<br />
9<br />
AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is<br />
measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall<br />
under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during<br />
severe storm conditions.<br />
West Refrigeration Plant, Washington D.C.
s<br />
s<br />
s<br />
s<br />
Combination <strong>Louver</strong>s<br />
EXD Combination louvers feature stationary front blades and operable rear blades to<br />
ensure proper weather protection when open as well as a consistent appearance in<br />
both the open and closed positions. Optional low leakage seals provide further<br />
environmental protection in the closed position. Operable blade louvers provide weather<br />
protection when open and positive shutoff when no airflow is required. These units incorporate<br />
center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand<br />
crank; or automatically with electric or pneumatic actuators.<br />
EBE-445 and EBI-445 incorporate backdraft damper blades for automatic shutoff when there<br />
is no airflow and can be used for either exhaust and intake applications.<br />
Loren Cook<br />
Facility, MO<br />
EBE-445<br />
EBI-445<br />
EXD-437<br />
EXD-645<br />
Fixed Blade<br />
Fixed Blade<br />
Fixed Blade<br />
Fixed Blade<br />
s<br />
s<br />
s<br />
s<br />
6"<br />
(152)<br />
Gravity<br />
Blade<br />
Gravity<br />
Blade<br />
Operable<br />
Blade<br />
Operable<br />
Blade<br />
‹ 4" › ‹ 4" › ‹ 4" › ‹ 6" ›<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
Depth<br />
Blade<br />
Angle<br />
Blade<br />
Style<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
Free Area<br />
(%) (Sq. Ft.)<br />
Velocity<br />
(fpm)<br />
Airflow<br />
(cfm)<br />
Pressure<br />
Drop (In. Wg.)<br />
EBE-445<br />
4"<br />
45°<br />
J-BD-Exhaust<br />
0.081"<br />
49<br />
7.9<br />
689<br />
5396<br />
0.10<br />
EBI-445<br />
4"<br />
45°<br />
J - BD-Intake<br />
0.081"<br />
49<br />
7.9<br />
689<br />
5396<br />
0.10<br />
EXD-437<br />
4"<br />
37.5°<br />
Combination<br />
0.081"<br />
45<br />
7.2<br />
1161<br />
8359<br />
0.16<br />
EXD-645<br />
4"<br />
37.5° - 45°<br />
Combination<br />
0.081"<br />
44<br />
7.1<br />
1050<br />
7455<br />
0.19<br />
The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />
The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below<br />
the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />
10
Sight Screens<br />
Whether the design calls for total sight concealment, partial screening, high volume airflow, specialty shapes, or thermal<br />
shading, our sight screens are engineered to meet the most stringent project parameters while satisfying exacting<br />
aesthetic requirements. The unique concealed support system of the HT-401 ensures proper structural support and a<br />
true continuous blade look without the use of unsightly frames or vertical angles.<br />
HJ-445<br />
HJ-645<br />
4"<br />
2<br />
HZ-200<br />
1 /4"<br />
‹ › ‹<br />
6"<br />
‹<br />
HT-401<br />
‹ 4" ›<br />
VT-250 VT-654 VV-500 VV-400<br />
2 1 /2 "<br />
‹ ›<br />
plan view<br />
‹ ›<br />
4"<br />
plan view<br />
‹ ›<br />
5"<br />
plan view<br />
‹ ›<br />
4"<br />
plan view<br />
Model<br />
Blade Depth<br />
Blade Style<br />
Free Area (%)<br />
HJ-445<br />
4"<br />
Horizontal - Inverted J<br />
50<br />
HJ-645<br />
6"<br />
Horizontal - Inverted J<br />
50<br />
HT-401<br />
4"<br />
Horizontal - Airfoil Tube<br />
60<br />
HZ-200<br />
2-1/4"<br />
Horizontal - Cladding<br />
19<br />
VT-250<br />
2-1/2"<br />
Vertical - Cladding<br />
24<br />
VT-654<br />
4"<br />
Vertical - Cladding<br />
21<br />
VV-400<br />
4"<br />
Vertical - V<br />
39<br />
VV-500<br />
5"<br />
Vertical - V<br />
54<br />
11<br />
Valet at Collins Park, FL
Grilles<br />
Custom designed to meet each project’s unique requirements, our extruded aluminum<br />
grilles are ideally suited for architectural accents, facades, screening and security barriers<br />
either inside or outside the building. In addition to traditional welded construction we can<br />
engineer unique and creative concealed fastening systems and hidden weld joints that<br />
offer improved aesthetics and superior structural integrity.<br />
Angle Grille<br />
Angle<br />
Bar<br />
Continuous<br />
Angle Grille Installed<br />
Offset<br />
Sentry<br />
Model<br />
Material/Free Area<br />
(6063-T5 Ext. Alum.)<br />
Minimum Size<br />
Maximum Size<br />
<strong>All</strong>-<strong>Lite</strong> Standard Grilles<br />
0.125" thick<br />
12" x 12"<br />
Single Section: 60" x 180"<br />
One Dimension must be 60"<br />
The illustrated designed for these Bar Grilles were created to a design load of 30lbs per square foot. Changes may be required to accommodate other design loads.<br />
12
Sunshades<br />
Our sunshades provide distinctive architectural style to a building’s exterior while considerably reducing glare. They<br />
do not cause snow load or water infiltration problems associated with solid membrane awnings. Sunshades also reduce<br />
heat from sunlight in the summer. This keeps the building cool and saves energy, ideal for sustainable or “green” building<br />
construction. Configured to meet each project’s individual requirements, our team can transform even the most complex<br />
concepts into a stunning reality. Our standard sunshade information is shown below.<br />
Blade Styles<br />
Airfoil Rectangular Tube J-Blade<br />
Model Depth<br />
Model Depth<br />
Model Depth<br />
SSA-445 4"<br />
SSR-445 4"<br />
SSJ-445 4"<br />
SSA-645 6"<br />
SSR-645 6"<br />
SSJ-645 6"<br />
SSA-845 8"<br />
SSR-845 8"<br />
Fascia<br />
Outriggers<br />
Round<br />
Rectangular<br />
Double Tapered Radius<br />
Flat Bar Radius<br />
Connections<br />
Concealed Connection<br />
Exposed Connection<br />
Curtain Wall Connection<br />
Shroud Connection<br />
Strut Connection<br />
13<br />
Gull Lake High School, MI
Penthouses<br />
Accommodating individual job requirements, penthouses are constructed to virtually any<br />
dimension. For added performance and flexibility, these units are available with most<br />
louver models and include mitered or box corner designs, insulated roof systems,<br />
operable and removable sections for equipment access as well as specialty screens and<br />
filtration options. The EFD-637-MD-PH is 6" deep with 37-1/2° horizontal blades and the<br />
EPJ-445 is 4" deep with 45° blades.<br />
U.S. Embassy, Kazakhstan<br />
EPJ-445<br />
Mitered Corner<br />
Boxed Corner<br />
‹<br />
‹<br />
Insulation<br />
Insulation<br />
‹<br />
Support Angle<br />
‹<br />
Support Angle<br />
‹<br />
Curb (by others)<br />
‹ ›<br />
‹ Throat Opening › Throat Opening<br />
‹<br />
Curb (by others)<br />
Beginning Point of Water Penetration Ratings<br />
Model<br />
EFD-637-MD-PH<br />
EPJ-445<br />
Depth<br />
6"<br />
4"<br />
Blade<br />
Angle<br />
37.5°<br />
45°<br />
Blade<br />
Style<br />
Horizontal<br />
J - Blade<br />
Material<br />
(6063-T5 Ext. Alum.)<br />
0.081"<br />
0.081"<br />
Free Area<br />
(%) (Sq. Ft.)<br />
59<br />
51<br />
9.3<br />
8.1<br />
Velocity<br />
(fpm)<br />
990<br />
689<br />
Airflow<br />
(cfm)<br />
9405<br />
5549<br />
Pressure<br />
Drop (In. Wg.)<br />
0.11<br />
0.08<br />
14
Finishes<br />
Underground Railroad<br />
Museum, OH<br />
Our superior performance paint systems are available in a wide range of colors and we can also custom color match to any of your specifications. Our<br />
expertise in applying architectural coatings assures you of a quality finish. With our options, you get the color you need when you need it!<br />
PRODUCT FACTS<br />
Finish Type Description/Application Color Selection Warranty<br />
2-coat 100% Fluoropolymer<br />
Newlar/Decaflon Meets AAMA<br />
2605. Dry film thickness 2 mil.<br />
Equivalent to Kynar 500 ® /Hylar<br />
5000 ® , Duranar ® , Fluoropon ®<br />
Our premier finish for extruded aluminum. Tough, long<br />
lasting, environmentally friendly powder coating has superior<br />
color retention and abrasive properties. Resists chalking,<br />
fading, chemical abrasion and weathering.<br />
Standard Colors: 20 standard<br />
colors plus Premium Pearl<br />
finishes. Custom colors are<br />
available. Consult factory.<br />
5 Years (consult<br />
factory for availability<br />
of extended warranty<br />
up to 20 years).<br />
2-coat Polyester Powder Coat<br />
Meets AAMA 2604. Dry film<br />
thickness 2 mil. Equivalent to<br />
Baked Enamel.<br />
Environmentally friendly powder coating has good color<br />
retention and abrasive properties. Resists chalking, fading,<br />
chemical abrasion and weathering.<br />
20 standard colors for<br />
aluminum products and acoustical<br />
louvers, 18 colors for steel. Custom<br />
colors are available. Consult factory.<br />
5 Years<br />
Integral Color Anodize<br />
AA-M10C22A42 (>0.7 mil)<br />
Electrochemically deposited inorganic color pigment which<br />
is sealed to convert an aluminum oxidation into a corrosion<br />
resistant finish. Some shade variation will occur.<br />
Champagne; Light, Medium or Dark<br />
Bronze; Black<br />
5 Years<br />
Clear Anodize 215 R-1<br />
AA-M10C22A41 (>0.7 mil)<br />
Electrochemically oxidized aluminum surface for uniform clear<br />
finish. More resistant to natural oxidizing. Improved luster and<br />
less glossy than mill finish.<br />
Clear<br />
5 Years<br />
Alkyd Prime Coat<br />
Preparation for field applied epoxy, vinyl, urethane, or<br />
other heavy-duty coatings. Must be finished within 60 months of<br />
application. Contamination can occur in transmit and in the field;<br />
requires field cleaning prior to painting.<br />
N/A<br />
N/A<br />
Mill<br />
Aluminum or Galvanized Steel. Normal weathering will occur.<br />
N/A<br />
N/A<br />
Finishes enhance louver appearance by matching or contrasting with adjacent surfaces and extend weather resistance.<br />
Color matching is available upon request.<br />
5101 Blue Mound Road, Fort Worth, Texas 76106 • Phone: 817-509-2300 • Fax: 817-831-3110 • www.alllite.com<br />
ALB March 2013