14.02.2015 Views

Louver Brochure Pottorff - All-Lite Architectural Products

Louver Brochure Pottorff - All-Lite Architectural Products

Louver Brochure Pottorff - All-Lite Architectural Products

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Louver</strong>s<br />

Penthouses<br />

Sunshades<br />

Grilles<br />

Sight Screens<br />

Selection<br />

Finishes<br />

Technical<br />

Information<br />

alllite.com


SELECTION GUIDE<br />

Water Penetration Ratings<br />

Model Blade Blade Blade Free Velocity Air Volume Page<br />

Depth Angle Style Area (fpm) (cfm)<br />

1<br />

United States Court House, WA<br />

Miami-Dade <strong>Louver</strong>s<br />

ECD-545-MD<br />

EFD-637-MD<br />

Wind-Driven Rain <strong>Louver</strong>s<br />

ECV-445<br />

ECD-445<br />

ECD-545<br />

ECD-635<br />

ECV-545<br />

ECV-645<br />

ECD-745<br />

EFJ-745<br />

Drainable <strong>Louver</strong>s<br />

EDD-445<br />

EDD-637<br />

EFD-245<br />

EFD-435<br />

EFD-437<br />

EFD-445<br />

EFD-637<br />

EFD-645<br />

ERD-645<br />

Drainable-Head <strong>Louver</strong>s<br />

EFJ-437-HP<br />

EFJ-637-HP<br />

Non-Drainable <strong>Louver</strong>s<br />

EFJ-245<br />

EFY-245<br />

EFJ-430<br />

EFK-430<br />

EFJ-437<br />

EFK-437<br />

EFJ-445<br />

EFK-445<br />

EFY-445<br />

EFK-637<br />

EFJ-645<br />

Operable <strong>Louver</strong>s<br />

EOD-445<br />

EOD-637<br />

EOJ-445<br />

EOJ-637<br />

Formed Metal <strong>Louver</strong>s<br />

SFJ-245<br />

SFJ-430<br />

SFD-445<br />

SFJ-445<br />

SFK-445<br />

SFV-445<br />

SFJ-630<br />

SFD-635<br />

SFJ-645<br />

SFK-645<br />

Acoustical <strong>Louver</strong>s<br />

EAA-645<br />

EAA-845<br />

SAJ-835<br />

SAJ-1235<br />

EAA-1245<br />

FAA-1245<br />

Combination <strong>Louver</strong>s<br />

EBE-445<br />

EBI-445<br />

EXD-437<br />

EXD-645<br />

Sight Screens<br />

HJ-445<br />

HJ-645<br />

HT-401<br />

HZ-200<br />

VT-250<br />

VT-654<br />

VV-400<br />

VV-500<br />

Grilles<br />

Sunshades<br />

Penthouses<br />

EFD-637-MDPH<br />

EPJ-445<br />

5"<br />

6"<br />

4"<br />

4"<br />

5"<br />

6"<br />

5"<br />

6"<br />

7"<br />

7"<br />

4"<br />

6"<br />

2"<br />

4"<br />

4"<br />

4"<br />

6"<br />

6"<br />

6"<br />

4"<br />

6"<br />

2"<br />

2"<br />

4"<br />

4"<br />

4"<br />

4"<br />

4"<br />

4"<br />

4"<br />

6"<br />

6"<br />

4"<br />

6"<br />

4"<br />

6"<br />

2"<br />

4"<br />

4"<br />

4"<br />

4"<br />

4"<br />

6"<br />

6"<br />

6"<br />

6"<br />

6"<br />

8"<br />

8"<br />

12"<br />

12"<br />

12"<br />

4"<br />

4"<br />

4"<br />

6"<br />

4"<br />

6"<br />

4"<br />

2-1/4"<br />

2"<br />

4"<br />

4"<br />

5"<br />

6"<br />

4"<br />

Horizontal<br />

Horizontal<br />

Vertical<br />

Horizontal<br />

Horizontal<br />

Horizontal<br />

Vertical<br />

Vertical<br />

Horizontal<br />

Horizontal<br />

Dual-Drainable<br />

Dual Drainable<br />

Thinline-Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Recessed-Drainable<br />

High Performance-J<br />

High Performance-J<br />

Thinline-J<br />

Thinline-Inverted Y<br />

J<br />

K<br />

J<br />

K<br />

J<br />

K<br />

Inverted Y<br />

K<br />

J<br />

Operable-Drainable<br />

Operable-Drainable<br />

Operable-J<br />

Operable-J<br />

J<br />

J<br />

Drainable<br />

J<br />

K<br />

Chevron<br />

J<br />

Drainable<br />

J<br />

K<br />

Extruded-Airfoil<br />

Extruded Airfoil<br />

Formed-J<br />

Formed-J<br />

Extruded-Airfoil<br />

Formed-Airfoil<br />

J-BD-Exhaust<br />

J-BD-Intake<br />

Combination<br />

Combination<br />

Horizontal-Inverted J<br />

Horizontal-Inverted J<br />

Horizontal Airfoil<br />

Horizontal-Cladding<br />

Vertical-Cladding<br />

Vertical-Cladding<br />

Vertical-V<br />

Vertical-V<br />

Extruded Aluminum<br />

Extruded Aluminum<br />

46%<br />

58%<br />

36%<br />

43%<br />

46%<br />

54%<br />

42%<br />

46%<br />

53%<br />

44%<br />

50%<br />

58%<br />

43%<br />

58%<br />

58%<br />

47%<br />

58%<br />

55%<br />

51%<br />

56%<br />

56%<br />

47%<br />

38%<br />

57%<br />

57%<br />

57%<br />

57%<br />

50%<br />

50%<br />

39%<br />

50%<br />

50%<br />

43%<br />

58%<br />

49%<br />

56%<br />

42%<br />

51%<br />

53%<br />

48%<br />

48%<br />

38%<br />

65%<br />

62%<br />

50%<br />

50%<br />

30%<br />

37%<br />

33%<br />

31%<br />

26%<br />

26%<br />

49%<br />

49%<br />

45%<br />

44%<br />

50%<br />

50%<br />

60%<br />

19%<br />

24%<br />

21%<br />

39%<br />

54%<br />

59%<br />

51%<br />

1250<br />

1097<br />

1250<br />

1250<br />

1250<br />

1217<br />

1250<br />

1250<br />

1197<br />

1250<br />

1026<br />

1113<br />

955<br />

966<br />

903<br />

990<br />

1113<br />

1050<br />

990<br />

912<br />

915<br />

583<br />

383<br />

889<br />

889<br />

721<br />

721<br />

689<br />

689<br />

745<br />

832<br />

800<br />

1024<br />

990<br />

683<br />

810<br />

603<br />

847<br />

715<br />

775<br />

775<br />

600<br />

825<br />

815<br />

800<br />

800<br />

980<br />

772<br />

808<br />

924<br />

999<br />

999<br />

689<br />

689<br />

1161<br />

1050<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

990<br />

689<br />

9250<br />

10191<br />

7125<br />

8585<br />

9250<br />

10508<br />

8375<br />

9250<br />

10018<br />

8755<br />

8311<br />

10242<br />

6494<br />

8984<br />

8398<br />

7425<br />

10242<br />

9240<br />

8059<br />

8220<br />

8226<br />

4373<br />

2336<br />

8090<br />

8090<br />

6547<br />

6547<br />

5549<br />

5549<br />

4589<br />

6673<br />

6416<br />

7096<br />

9108<br />

5396<br />

7282<br />

4040<br />

6945<br />

6092<br />

5991<br />

5991<br />

3648<br />

8580<br />

8044<br />

6400<br />

6400<br />

4704<br />

4564<br />

4293<br />

4528<br />

4196<br />

4196<br />

5396<br />

5396<br />

8359<br />

7455<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

9405<br />

5549<br />

2<br />

2<br />

3<br />

3<br />

3<br />

3<br />

3<br />

3<br />

3<br />

3<br />

4<br />

4<br />

4<br />

4<br />

4<br />

4<br />

4<br />

4<br />

4<br />

5<br />

5<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

6<br />

7<br />

7<br />

7<br />

7<br />

8<br />

8<br />

8<br />

8<br />

8<br />

8<br />

8<br />

8<br />

8<br />

8<br />

9<br />

9<br />

9<br />

9<br />

9<br />

9<br />

10<br />

10<br />

10<br />

10<br />

11<br />

11<br />

11<br />

11<br />

11<br />

11<br />

11<br />

11<br />

12<br />

13<br />

14<br />

14<br />

45°<br />

37-1/2°<br />

45°<br />

45°<br />

45°<br />

35°<br />

45°<br />

45°<br />

45°<br />

45°<br />

45°<br />

37-1/2°<br />

45°<br />

35°<br />

37-1/2°<br />

47°<br />

37-1/2°<br />

45°<br />

45°<br />

37-1/2°<br />

37-1/2°<br />

45°<br />

45°<br />

30°<br />

30°<br />

37-1/2°<br />

37-1/2°<br />

45°<br />

45°<br />

45°<br />

37-1/2°<br />

45°<br />

45°<br />

37-1/2°<br />

45°<br />

37-1/2°<br />

45°<br />

30°<br />

45°<br />

45°<br />

45°<br />

45°<br />

30°<br />

35°<br />

45°<br />

45°<br />

45°<br />

45°<br />

35°<br />

35°<br />

45°<br />

45°<br />

45°<br />

45°<br />

37-1/2°<br />

37-1/2°– 45°<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

—<br />

37-1/2°<br />

45°


Miami-Dade <strong>Louver</strong>s<br />

The ECD-545-MD and EFD-637-MD are engineered and tested to withstand extreme loads,<br />

debris impact, and cyclic fatigue failure associated with the severe weather effects of<br />

hurricanes (ECD-545-MD has Miami-Dade approval # 11-0429.02 and the EFD-637-MD has<br />

Miami-Dade approval # 11-0429.01).<br />

Constructed from 6063-T5 extruded aluminum, both models have single section assemblies up<br />

to 48" wide by 144" high. Specially designed water-resistant seam covers further enhance<br />

performance and aesthetics of these industry leading products. Single-section louvers are now<br />

available with the option of a factory-installed sleeve which allows louver installation without<br />

any mechanical anchoring to the building condition.<br />

Mosaic on<br />

Miami Beach, FL<br />

ECD-545-MD<br />

(Sight Proof)<br />

EFD-637-MD<br />

‹ 5" › ‹ 6" ›<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model ECD-545-MD shown hereon is<br />

licensed to bear the AMCA seal. The ratings shown are<br />

based on test and procedures performed in accordance<br />

with AMCA Publication 511 and comply with the requirements<br />

of the AMCA Certified Ratings Program. The AMCA<br />

Certified Ratings Seal applies to air performance, water<br />

penetration and wind-driven rain ratings.<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model EFD-637-MD shown hereon is<br />

licensed to bear the AMCA seal. The ratings shown are<br />

based on test and procedures performed in accordance<br />

with AMCA Publication 511 and comply with the requirements<br />

of the AMCA Certified Ratings Program. The AMCA<br />

Certified Ratings Seal applies to air performance and<br />

water penetration ratings.<br />

Maximum Size Wall Construction Installation Method<br />

Single Section - 48"w x 144"h<br />

Multiple Section - Unlimited width x 144"h<br />

Multiple Section - 48"w x Unlimited Height<br />

Structural steel mullion support<br />

required for installations more than<br />

one section wide.<br />

Installations of unlimited width and<br />

height available with additional<br />

engineer-approved support structure.<br />

<strong>All</strong> Types<br />

Steel<br />

Direct Connection - Clip angles*<br />

Masonry<br />

Tension or Shear Connection - Clip angles*<br />

Wood<br />

Direct Connection - Clip angles*<br />

<strong>All</strong> Types (Single Section Only)<br />

Flanged sleeve with continuous retaining angles<br />

(No anchors required)<br />

*Anchors supplied by others<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

Class<br />

Miami Dade<br />

Approval<br />

ECD-545-MD<br />

5"<br />

45°<br />

Horizontal<br />

0.081"<br />

46<br />

7.4<br />

1250<br />

9250<br />

0.22<br />

A (29 mph)<br />

#11-0429.02<br />

EFD-637-MD<br />

6"<br />

37.5°<br />

Horizontal<br />

0.081"<br />

58<br />

9.3<br />

1097<br />

10191<br />

0.17<br />

-<br />

#11-0429.01<br />

<strong>All</strong>-<strong>Lite</strong> architectural products are designed for use in most geographical areas within the United States. <strong>All</strong>-<strong>Lite</strong> can also design, modify or reinforce standard products for special requirements, such as high wind, heavy snow, industrial environments, special<br />

mounting conditions, etc. Consult your local representative for more information.<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />

The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of<br />

safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver size having 39-3/8” x 39-3/8” core area.<br />

2


Wind-Driven Rain <strong>Louver</strong>s<br />

Backed by AMCA certification our wind-driven rain louvers offer exceptional protection under the most severe conditions and are<br />

available in frame depths from 4" to 7". The closely spaced vertical blade design of the Florida Building Code approved<br />

ECV-645 provides our most effective wind-driven rain performance with 100% effectiveness at wind velocities up to 50 mph and<br />

rainfall up to 8 in/hr. When aesthetic requirements demand a more conventional horizontal blade profile our EFJ-745 is the ideal<br />

solution with 5" on center traditional J-blade fascia and 100% effectiveness @ 3 in/hr rainfall.<br />

ECV-445<br />

ECV-645<br />

ECV-545<br />

EFJ-745<br />

ECD-445<br />

ECD-545<br />

ECD-635<br />

ECD-745<br />

plan view<br />

‹ ›<br />

4"<br />

ECV-445<br />

‹ ›<br />

5"<br />

6"<br />

plan view<br />

ECV-645<br />

ECV-545<br />

‹ 7" › ‹<br />

4"<br />

5" › ‹ 7" ›<br />

6"<br />

Wind-Driven Rain Ratings<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Style<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Wind<br />

Velocity<br />

Rainfall<br />

(In/Hr)<br />

Ventilation<br />

Rate (cfm)<br />

Effectiveness<br />

Ratio (%)<br />

Class<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

Florida Building<br />

Code Approval<br />

ECV-445<br />

4"<br />

Vertical<br />

36<br />

5.7<br />

29 mph<br />

3<br />

4211<br />

99.8<br />

A<br />

1250<br />

7125<br />

0.76<br />

-<br />

ECD-445<br />

4"<br />

Horizontal<br />

43<br />

6.9<br />

29 mph<br />

3<br />

5587<br />

99.0<br />

A<br />

1250<br />

8585<br />

0.31<br />

-<br />

ECD-545<br />

5"<br />

Horizontal<br />

46<br />

7.4<br />

29/50 mph<br />

3/8<br />

9539/10594<br />

99.4/95.3<br />

A/B<br />

1250<br />

9250<br />

0.24<br />

#13619.1<br />

ECD-635<br />

6"<br />

Horizontal<br />

54<br />

8.6<br />

29 mph<br />

3<br />

6372<br />

96.6<br />

B<br />

1217<br />

10508<br />

0.29<br />

-<br />

ECV-545<br />

5"<br />

Vertical<br />

42<br />

6.7<br />

29/50 mph<br />

3/8<br />

7356/9485<br />

99.9/99.6<br />

A<br />

1250<br />

8375<br />

0.25<br />

-<br />

ECV-645<br />

6"<br />

Vertical<br />

46<br />

7.4<br />

50 mph<br />

8<br />

10,390<br />

100.0<br />

A<br />

1250<br />

9250<br />

0.15<br />

#13683.2<br />

ECD-745<br />

7"<br />

Horizontal<br />

53<br />

8.4<br />

29 mph<br />

3<br />

7244<br />

99.9<br />

A<br />

1197<br />

10018<br />

0.50<br />

-<br />

EFJ-745<br />

7"<br />

Horizontal<br />

44<br />

7.0<br />

29 mph<br />

3<br />

7211<br />

99.3<br />

A<br />

1250<br />

8755<br />

0.47<br />

-<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model ECV-645 and EFJ-745 shown hereon<br />

are licensed to bear the AMCA seal. The ratings shown are based<br />

on test and procedures performed in accordance with AMCA<br />

Publication 511 and comply with the requirements of the AMCA<br />

Certified Ratings Program. The AMCA Certified Ratings Seal<br />

applies to wind driven rain ratings.<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model ECV-445 shown hereon is licensed to<br />

bear the AMCA seal. The ratings shown are based on test and<br />

procedures performed in accordance with AMCA Publication 511<br />

and comply with the requirements of the AMCA Certified Ratings<br />

Program. The AMCA Certified Ratings Seal applies to wind driven<br />

rain and air performance ratings.<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model ECD-445, ECD-545, ECD-635, ECD-745 and<br />

ECV-545 shown hereon are licensed to bear the AMCA seal. The ratings<br />

shown are based on test and procedures performed in accordance with<br />

AMCA Publication 511 and comply with the requirements of the AMCA<br />

Certified Ratings Program. The AMCA Certified Ratings Seal applies to<br />

water penetration ratings, air performance and wind driven rain ratings.<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a<br />

simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area<br />

and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test<br />

provides a method for comparing louver models and designs as to their efficiency in resisting the penetration<br />

of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with<br />

a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted<br />

penetration during severe storm conditions. AMCA Wind Driven Rain Ratings based upon a test louver<br />

size having 39-3/8” x 39-3/8” core area.<br />

3<br />

<strong>All</strong>-<strong>Lite</strong> architectural products are designed for use in most geographical areas within the United States. <strong>All</strong>-<strong>Lite</strong> can also design, modify or reinforce standard products for special requirements, such as high<br />

wind, heavy snow, industrial environments, special mounting conditions, etc. Consult your local representative for more information.<br />

Dallas Cowboys Stadium, TX


Drainable <strong>Louver</strong>s<br />

Drainable blade louvers are designed to prevent water penetration in non-wind-driven rain<br />

applications by collecting water in the blade gutters and channeling it into frame downspouts<br />

and away from airflow paths. Our ERD-645 incorporates a recessed mullion and<br />

downspout that provides the appearance of a continuous drainable blade design.<br />

Columbus International<br />

Airport, OH<br />

EDD-445<br />

EDD-637<br />

EFD-435<br />

EFD-437<br />

EFD-637<br />

EFD-245<br />

EFD-445<br />

EFD-645<br />

ERD-645<br />

4"<br />

‹ 6" ›<br />

2"<br />

4" 4"<br />

‹ › ‹ 4"<br />

6"<br />

6"<br />

› ‹ › ‹ ›<br />

6"<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

Florida Building<br />

Code Approval<br />

EDD-445<br />

4"<br />

45°<br />

Dual-Drainable<br />

50<br />

8.1<br />

0.081"<br />

1026<br />

8311<br />

0.16<br />

-<br />

EDD-637<br />

EFD-245<br />

EFD-435<br />

EFD-437<br />

EFD-445<br />

EFD-637<br />

EFD-645<br />

ERD-645<br />

6"<br />

2"<br />

4"<br />

4"<br />

4"<br />

6"<br />

6"<br />

6"<br />

37.5°<br />

45°<br />

35°<br />

37.5°<br />

47°<br />

37.5°<br />

45°<br />

45°<br />

Dual-Drainable<br />

Thinline-Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Drainable<br />

Recessed-Drainable<br />

58<br />

43<br />

58<br />

58<br />

47<br />

58<br />

55<br />

51<br />

9.2<br />

6.8<br />

9.3<br />

9.3<br />

7.5<br />

9.2<br />

8.8<br />

8.1<br />

0.081"<br />

0.081"<br />

0.081"<br />

0.081"<br />

0.081"<br />

0.081"<br />

0.081"<br />

0.081"<br />

1113<br />

955<br />

966<br />

903<br />

990<br />

1113<br />

1050<br />

990<br />

10242<br />

6494<br />

8984<br />

8398<br />

7425<br />

10242<br />

9240<br />

8059<br />

0.15<br />

0.14<br />

0.12<br />

0.13<br />

0.14<br />

0.15<br />

0.15<br />

0.11<br />

-<br />

-<br />

-<br />

#13683.3<br />

#13683.4<br />

#13683.5<br />

#13683.6<br />

-<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that models EFD-435, EFD-437, EFD-445, EFD-637 and<br />

EFD-645 shown hereon are licensed to bear the AMCA seal. The ratings<br />

shown are based on test and procedures performed in accordance with<br />

AMCA Publication 511 and comply with the requirements of the AMCA<br />

Certified Ratings Program. The AMCA Certified Ratings Seal applies to air<br />

performance and water penetration ratings. Models EFD-245 and ERD-<br />

645 are not licensed to bear the AMCA seal.<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />

The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety<br />

below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />

4


Drainable Head <strong>Louver</strong>s<br />

Drainable head louvers blend the aesthetic appeal of a non-drainable blade with the high performance water penetration<br />

protection of a drainable blade louver. These louvers incorporate a drainable head member to capture water that<br />

cascades down the face of the building and channels it into downspouts and away from the airflow paths.<br />

These louvers are available in a wide array of anodized and painted<br />

finishes including custom color matching. They are available with<br />

an optional hidden vertical mullion.<br />

EFJ-437-HP<br />

EFJ-637-HP<br />

Pennsylvania State University, PA<br />

‹ 4" › ‹ 6" ›<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade Angle<br />

Blade Style<br />

Material/Free Area<br />

(6063-T5 Ext. Alum.)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

EFJ-437-HP<br />

4"<br />

37.5°<br />

High Performance - J<br />

0.081"<br />

56<br />

9.0<br />

912<br />

8220<br />

0.14<br />

EFJ-637-HP<br />

6"<br />

37.5°<br />

High Performance - J<br />

0.081"<br />

56<br />

9.0<br />

915<br />

8226<br />

0.12<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that model EFJ-437-HP shown hereon is licensed to<br />

bear the AMCA seal. The ratings shown are based on test and procedures<br />

performed in accordance with AMCA Publication 511 and<br />

comply with the requirements of the AMCA Certified Ratings<br />

Program. The AMCA Certified Ratings Seal applies to air performance<br />

and water penetration ratings. Model EFJ-637-HP is not<br />

licensed to bear the AMCA seal.<br />

5<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area<br />

and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration<br />

of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted<br />

penetration during severe storm conditions.<br />

Pennsylvania State University Chemical Laboratory, PA


Non-Drainable <strong>Louver</strong>s<br />

Available in a wide array of blade shapes and frame depths non-drainable louvers<br />

offer value and economy for exhaust applications or intake conditions where<br />

protection against water infiltration is not critical. Optional hidden mullions provide a<br />

continuous blade appearance on multiple section assemblies. Ideally suited for special<br />

shapes and transitional designs.<br />

Clayton Elementary<br />

School, GA<br />

EFY-245<br />

EFY-445<br />

EFJ-430<br />

EFK-430<br />

EFJ-437<br />

EFK-437<br />

EFK-637<br />

EFJ-245<br />

EFJ-445<br />

EFK-445<br />

EFJ-645<br />

4"<br />

(102)<br />

2"<br />

2"<br />

‹ 4" › ‹<br />

4"<br />

› 4"<br />

6"<br />

4"<br />

‹ 6" › ‹ ›<br />

6"<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

Florida Building Code<br />

Approval<br />

EFJ-245<br />

2"<br />

45°<br />

Thinline – J<br />

0.060"<br />

47<br />

7.5<br />

583<br />

4373<br />

0.06<br />

-<br />

EFY-245<br />

2"<br />

45°<br />

Thinline – Inverted<br />

0.060"<br />

38<br />

6.1<br />

383<br />

2336<br />

0.06<br />

-<br />

EFJ-430/EFK-430<br />

4"<br />

30°<br />

J/K<br />

0.081"<br />

57<br />

9.1<br />

889<br />

8090<br />

0.09<br />

-<br />

EFJ-437/EFK-437<br />

4"<br />

37.5°<br />

J/K<br />

0.081"<br />

57<br />

9.1<br />

721<br />

6547<br />

0.07<br />

#13683.7/13683.9<br />

EFJ-445/EFK-445<br />

4"<br />

45°<br />

J/K<br />

0.081"<br />

50<br />

8.0<br />

689<br />

5549<br />

0.08<br />

#13683.8/13683.10<br />

EFY-445<br />

6"<br />

45°<br />

Inverted Y<br />

0.081"<br />

39<br />

6.2<br />

745<br />

4589<br />

0.18<br />

-<br />

EFK-637<br />

6"<br />

37.5°<br />

K<br />

0.081"<br />

50<br />

8.0<br />

832<br />

6673<br />

0.05<br />

-<br />

EFJ-645<br />

6"<br />

45°<br />

J<br />

0.081"<br />

50<br />

8.0<br />

800<br />

6416<br />

0.10<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that models EFJ-437, EFK-437, EFJ-445, and EFK-445 shown hereon are licensed to bear the AMCA<br />

seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and<br />

comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to<br />

air performance and water penetration ratings. Models EFJ-245, EFY-245, EFJ-430, EFK-430, EFY-445, EFK-637, and<br />

EFJ-645 are not licensed to bear the AMCA seal.<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />

The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety<br />

below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />

6


Operable <strong>Louver</strong>s<br />

Operable blade louvers provide weather protection when open and positive shutoff when no airflow is required. These<br />

units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand crank; or<br />

automatically with electric or pneumatic actuators.<br />

EOJ-445<br />

EOD-445<br />

EOD-637<br />

EOJ-637<br />

‹ 4" › ‹ 4" › ‹ 6" › ‹ 6" ›<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

EOJ-445<br />

4"<br />

45°<br />

Operable-J<br />

0.081"<br />

49<br />

7.9<br />

683<br />

5396<br />

0.10<br />

EOD-445<br />

4"<br />

45°<br />

Operable - Drainable<br />

0.081"<br />

43<br />

6.9<br />

1024<br />

7096<br />

0.16<br />

EOD-637<br />

6"<br />

37.5°<br />

Operable - Drainable<br />

0.081"<br />

58<br />

9.2<br />

990<br />

9108<br />

0.11<br />

EOJ-637<br />

6"<br />

37.5°<br />

Operable -J<br />

0.081"<br />

56<br />

9.0<br />

810<br />

7282<br />

0.12<br />

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured<br />

through a 48"x 48" louver during a 15 minute period. The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab<br />

conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />

7


Formed Metal <strong>Louver</strong>s<br />

Typically formed from galvanized steel, these units offer an economical solution for basic<br />

ventilation requirements. Optionally available in a wide array of exotic metals including<br />

copper and stainless steel our formed metal louvers can also serve to accent building<br />

architecture or withstand corrosion in caustic environments.<br />

Valley Metro,<br />

Phoenix, AZ<br />

SFV-445<br />

SFJ-430<br />

SFJ-630<br />

SFK-445<br />

SFJ-245<br />

SFJ-445<br />

SFJ-645<br />

SFK-645<br />

SFD-445<br />

SFD-635<br />

2"<br />

4"<br />

4"<br />

‹ › ‹ 4"<br />

4"<br />

6"<br />

6"<br />

› ‹ › ‹ › ‹ ›<br />

6"<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Material<br />

(Galvanized Steel)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

SFJ-245<br />

4"<br />

45°<br />

J<br />

20GA<br />

42<br />

6.7<br />

603<br />

4040<br />

0.06<br />

SFJ-430<br />

4"<br />

30°<br />

J<br />

20GA<br />

51<br />

8.2<br />

847<br />

6945<br />

0.13<br />

SFD-445<br />

4"<br />

45°<br />

Drainable<br />

20GA<br />

53<br />

8.5<br />

715<br />

6092<br />

0.11<br />

SFJ-445/SFK-445<br />

4"<br />

45°<br />

J/K<br />

20GA<br />

48<br />

7.7<br />

775<br />

5991<br />

0.13<br />

SFV-445<br />

4"<br />

45°<br />

Chevron<br />

20GA<br />

38<br />

6.1<br />

600<br />

3648<br />

0.25<br />

SFJ-630<br />

6"<br />

45°<br />

J<br />

20GA<br />

65<br />

10.4<br />

825<br />

8580<br />

0.08<br />

SFD-635<br />

6"<br />

45°<br />

Drainable<br />

20GA<br />

62<br />

9.9<br />

815<br />

8044<br />

0.08<br />

SFJ-645/SFK-645<br />

6"<br />

45°<br />

J<br />

20GA<br />

50<br />

8.0<br />

800<br />

6400<br />

0.09<br />

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />

The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below<br />

the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />

8


Acoustical <strong>Louver</strong>s<br />

Recommended for installation in noisy environments, acoustical louvers incorporate insulated blades that restrict sound<br />

transmission through the louver over a wide range of frequencies. Our airfoil blade designs offer lower static pressure loss<br />

and softer aesthetics for critical airflow performance applications.<br />

SAJ-835<br />

SAJ-1235<br />

EAA-645<br />

EAA-845<br />

EAA-1245<br />

FAA-1245<br />

8"<br />

6"<br />

‹<br />

12"<br />

› ‹ 8" › ‹ 12" ›<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade Style<br />

Noise Reduction<br />

125 250 500 1K 2K 4K<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

EAA-645<br />

6"<br />

Extruded - Airfoil<br />

11<br />

11<br />

13<br />

16<br />

18<br />

17<br />

30<br />

4.8<br />

980<br />

4704<br />

0.10<br />

EAA-845<br />

8"<br />

Extruded - Airfoil<br />

8<br />

8<br />

10<br />

14<br />

15<br />

13<br />

37<br />

5.9<br />

772<br />

4564<br />

0.05<br />

SAJ-835<br />

8"<br />

Formed - J<br />

13<br />

13<br />

19<br />

26<br />

28<br />

23<br />

33<br />

5.3<br />

808<br />

4293<br />

0.07<br />

SAJ-1235<br />

12"<br />

Formed - J<br />

15<br />

17<br />

22<br />

27<br />

31<br />

28<br />

31<br />

4.9<br />

924<br />

4528<br />

0.08<br />

EAA-1245<br />

12"<br />

Extruded - Airfoil<br />

13<br />

14<br />

17<br />

19<br />

18<br />

17<br />

26<br />

4.2<br />

999<br />

4196<br />

0.09<br />

FAA-1245<br />

12"<br />

Formed - Airfoil<br />

13<br />

14<br />

17<br />

19<br />

18<br />

17<br />

26<br />

4.2<br />

999<br />

4196<br />

0.09<br />

Certified Ratings:<br />

<strong>All</strong>-<strong>Lite</strong> certifies that models SAJ-835, SAJ-1235, EAA-845 and FAA-1245, shown hereon is licensed to<br />

bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with<br />

AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The<br />

AMCA Certified Ratings Seal applies to air performance and water penetration ratings. Models EAA-645<br />

and EAA-1245 are not licensed to bear the AMCA seal.<br />

9<br />

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is<br />

measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall<br />

under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during<br />

severe storm conditions.<br />

West Refrigeration Plant, Washington D.C.


s<br />

s<br />

s<br />

s<br />

Combination <strong>Louver</strong>s<br />

EXD Combination louvers feature stationary front blades and operable rear blades to<br />

ensure proper weather protection when open as well as a consistent appearance in<br />

both the open and closed positions. Optional low leakage seals provide further<br />

environmental protection in the closed position. Operable blade louvers provide weather<br />

protection when open and positive shutoff when no airflow is required. These units incorporate<br />

center pivoted blades that can be controlled manually with a pull chain, hand quadrant or hand<br />

crank; or automatically with electric or pneumatic actuators.<br />

EBE-445 and EBI-445 incorporate backdraft damper blades for automatic shutoff when there<br />

is no airflow and can be used for either exhaust and intake applications.<br />

Loren Cook<br />

Facility, MO<br />

EBE-445<br />

EBI-445<br />

EXD-437<br />

EXD-645<br />

Fixed Blade<br />

Fixed Blade<br />

Fixed Blade<br />

Fixed Blade<br />

s<br />

s<br />

s<br />

s<br />

6"<br />

(152)<br />

Gravity<br />

Blade<br />

Gravity<br />

Blade<br />

Operable<br />

Blade<br />

Operable<br />

Blade<br />

‹ 4" › ‹ 4" › ‹ 4" › ‹ 6" ›<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

Depth<br />

Blade<br />

Angle<br />

Blade<br />

Style<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

Free Area<br />

(%) (Sq. Ft.)<br />

Velocity<br />

(fpm)<br />

Airflow<br />

(cfm)<br />

Pressure<br />

Drop (In. Wg.)<br />

EBE-445<br />

4"<br />

45°<br />

J-BD-Exhaust<br />

0.081"<br />

49<br />

7.9<br />

689<br />

5396<br />

0.10<br />

EBI-445<br />

4"<br />

45°<br />

J - BD-Intake<br />

0.081"<br />

49<br />

7.9<br />

689<br />

5396<br />

0.10<br />

EXD-437<br />

4"<br />

37.5°<br />

Combination<br />

0.081"<br />

45<br />

7.2<br />

1161<br />

8359<br />

0.16<br />

EXD-645<br />

4"<br />

37.5° - 45°<br />

Combination<br />

0.081"<br />

44<br />

7.1<br />

1050<br />

7455<br />

0.19<br />

The beginning point of water penetration is defined as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period.<br />

The water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. <strong>All</strong>-<strong>Lite</strong> recommends that intake louvers are selected with a reasonable margin of safety below<br />

the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.<br />

10


Sight Screens<br />

Whether the design calls for total sight concealment, partial screening, high volume airflow, specialty shapes, or thermal<br />

shading, our sight screens are engineered to meet the most stringent project parameters while satisfying exacting<br />

aesthetic requirements. The unique concealed support system of the HT-401 ensures proper structural support and a<br />

true continuous blade look without the use of unsightly frames or vertical angles.<br />

HJ-445<br />

HJ-645<br />

4"<br />

2<br />

HZ-200<br />

1 /4"<br />

‹ › ‹<br />

6"<br />

‹<br />

HT-401<br />

‹ 4" ›<br />

VT-250 VT-654 VV-500 VV-400<br />

2 1 /2 "<br />

‹ ›<br />

plan view<br />

‹ ›<br />

4"<br />

plan view<br />

‹ ›<br />

5"<br />

plan view<br />

‹ ›<br />

4"<br />

plan view<br />

Model<br />

Blade Depth<br />

Blade Style<br />

Free Area (%)<br />

HJ-445<br />

4"<br />

Horizontal - Inverted J<br />

50<br />

HJ-645<br />

6"<br />

Horizontal - Inverted J<br />

50<br />

HT-401<br />

4"<br />

Horizontal - Airfoil Tube<br />

60<br />

HZ-200<br />

2-1/4"<br />

Horizontal - Cladding<br />

19<br />

VT-250<br />

2-1/2"<br />

Vertical - Cladding<br />

24<br />

VT-654<br />

4"<br />

Vertical - Cladding<br />

21<br />

VV-400<br />

4"<br />

Vertical - V<br />

39<br />

VV-500<br />

5"<br />

Vertical - V<br />

54<br />

11<br />

Valet at Collins Park, FL


Grilles<br />

Custom designed to meet each project’s unique requirements, our extruded aluminum<br />

grilles are ideally suited for architectural accents, facades, screening and security barriers<br />

either inside or outside the building. In addition to traditional welded construction we can<br />

engineer unique and creative concealed fastening systems and hidden weld joints that<br />

offer improved aesthetics and superior structural integrity.<br />

Angle Grille<br />

Angle<br />

Bar<br />

Continuous<br />

Angle Grille Installed<br />

Offset<br />

Sentry<br />

Model<br />

Material/Free Area<br />

(6063-T5 Ext. Alum.)<br />

Minimum Size<br />

Maximum Size<br />

<strong>All</strong>-<strong>Lite</strong> Standard Grilles<br />

0.125" thick<br />

12" x 12"<br />

Single Section: 60" x 180"<br />

One Dimension must be 60"<br />

The illustrated designed for these Bar Grilles were created to a design load of 30lbs per square foot. Changes may be required to accommodate other design loads.<br />

12


Sunshades<br />

Our sunshades provide distinctive architectural style to a building’s exterior while considerably reducing glare. They<br />

do not cause snow load or water infiltration problems associated with solid membrane awnings. Sunshades also reduce<br />

heat from sunlight in the summer. This keeps the building cool and saves energy, ideal for sustainable or “green” building<br />

construction. Configured to meet each project’s individual requirements, our team can transform even the most complex<br />

concepts into a stunning reality. Our standard sunshade information is shown below.<br />

Blade Styles<br />

Airfoil Rectangular Tube J-Blade<br />

Model Depth<br />

Model Depth<br />

Model Depth<br />

SSA-445 4"<br />

SSR-445 4"<br />

SSJ-445 4"<br />

SSA-645 6"<br />

SSR-645 6"<br />

SSJ-645 6"<br />

SSA-845 8"<br />

SSR-845 8"<br />

Fascia<br />

Outriggers<br />

Round<br />

Rectangular<br />

Double Tapered Radius<br />

Flat Bar Radius<br />

Connections<br />

Concealed Connection<br />

Exposed Connection<br />

Curtain Wall Connection<br />

Shroud Connection<br />

Strut Connection<br />

13<br />

Gull Lake High School, MI


Penthouses<br />

Accommodating individual job requirements, penthouses are constructed to virtually any<br />

dimension. For added performance and flexibility, these units are available with most<br />

louver models and include mitered or box corner designs, insulated roof systems,<br />

operable and removable sections for equipment access as well as specialty screens and<br />

filtration options. The EFD-637-MD-PH is 6" deep with 37-1/2° horizontal blades and the<br />

EPJ-445 is 4" deep with 45° blades.<br />

U.S. Embassy, Kazakhstan<br />

EPJ-445<br />

Mitered Corner<br />

Boxed Corner<br />

‹<br />

‹<br />

Insulation<br />

Insulation<br />

‹<br />

Support Angle<br />

‹<br />

Support Angle<br />

‹<br />

Curb (by others)<br />

‹ ›<br />

‹ Throat Opening › Throat Opening<br />

‹<br />

Curb (by others)<br />

Beginning Point of Water Penetration Ratings<br />

Model<br />

EFD-637-MD-PH<br />

EPJ-445<br />

Depth<br />

6"<br />

4"<br />

Blade<br />

Angle<br />

37.5°<br />

45°<br />

Blade<br />

Style<br />

Horizontal<br />

J - Blade<br />

Material<br />

(6063-T5 Ext. Alum.)<br />

0.081"<br />

0.081"<br />

Free Area<br />

(%) (Sq. Ft.)<br />

59<br />

51<br />

9.3<br />

8.1<br />

Velocity<br />

(fpm)<br />

990<br />

689<br />

Airflow<br />

(cfm)<br />

9405<br />

5549<br />

Pressure<br />

Drop (In. Wg.)<br />

0.11<br />

0.08<br />

14


Finishes<br />

Underground Railroad<br />

Museum, OH<br />

Our superior performance paint systems are available in a wide range of colors and we can also custom color match to any of your specifications. Our<br />

expertise in applying architectural coatings assures you of a quality finish. With our options, you get the color you need when you need it!<br />

PRODUCT FACTS<br />

Finish Type Description/Application Color Selection Warranty<br />

2-coat 100% Fluoropolymer<br />

Newlar/Decaflon Meets AAMA<br />

2605. Dry film thickness 2 mil.<br />

Equivalent to Kynar 500 ® /Hylar<br />

5000 ® , Duranar ® , Fluoropon ®<br />

Our premier finish for extruded aluminum. Tough, long<br />

lasting, environmentally friendly powder coating has superior<br />

color retention and abrasive properties. Resists chalking,<br />

fading, chemical abrasion and weathering.<br />

Standard Colors: 20 standard<br />

colors plus Premium Pearl<br />

finishes. Custom colors are<br />

available. Consult factory.<br />

5 Years (consult<br />

factory for availability<br />

of extended warranty<br />

up to 20 years).<br />

2-coat Polyester Powder Coat<br />

Meets AAMA 2604. Dry film<br />

thickness 2 mil. Equivalent to<br />

Baked Enamel.<br />

Environmentally friendly powder coating has good color<br />

retention and abrasive properties. Resists chalking, fading,<br />

chemical abrasion and weathering.<br />

20 standard colors for<br />

aluminum products and acoustical<br />

louvers, 18 colors for steel. Custom<br />

colors are available. Consult factory.<br />

5 Years<br />

Integral Color Anodize<br />

AA-M10C22A42 (>0.7 mil)<br />

Electrochemically deposited inorganic color pigment which<br />

is sealed to convert an aluminum oxidation into a corrosion<br />

resistant finish. Some shade variation will occur.<br />

Champagne; Light, Medium or Dark<br />

Bronze; Black<br />

5 Years<br />

Clear Anodize 215 R-1<br />

AA-M10C22A41 (>0.7 mil)<br />

Electrochemically oxidized aluminum surface for uniform clear<br />

finish. More resistant to natural oxidizing. Improved luster and<br />

less glossy than mill finish.<br />

Clear<br />

5 Years<br />

Alkyd Prime Coat<br />

Preparation for field applied epoxy, vinyl, urethane, or<br />

other heavy-duty coatings. Must be finished within 60 months of<br />

application. Contamination can occur in transmit and in the field;<br />

requires field cleaning prior to painting.<br />

N/A<br />

N/A<br />

Mill<br />

Aluminum or Galvanized Steel. Normal weathering will occur.<br />

N/A<br />

N/A<br />

Finishes enhance louver appearance by matching or contrasting with adjacent surfaces and extend weather resistance.<br />

Color matching is available upon request.<br />

5101 Blue Mound Road, Fort Worth, Texas 76106 • Phone: 817-509-2300 • Fax: 817-831-3110 • www.alllite.com<br />

ALB March 2013

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!