GENSAL<br />

Salient Pole Generator Model<br />

This model is located at system bus #__ASU IPP_ IBUS.<br />

Machine #___80005___ I.<br />

This model uses CONs starting with #___________ J.<br />

and STATEs starting with # ___________ K.<br />

The machine MVA base is ____18.5_______for each of ____3___ units =<br />

___18.5___MBASE.<br />

ZSORCE for this machine is ____0.0______ + j ___0.12___ on the above MBASE.<br />

CONs # Value Description STATEs # Description<br />

J 5.5 T’ do (>0) (Seconds) K E’ q<br />

J + 1 0.03 T’’ do (>0) (Seconds) K + 1 ψkd<br />

J + 2 0.17 T’’ qo (>0) (Seconds) K + 2 ψ’’ q<br />

J + 3 1.67 Inertia H K + 3 Δ Speed ( p.u. )<br />

J + 4 1.0 Speed Damping D K + 4 Angle ( radians )<br />

J + 5 1.24 X d<br />

J + 6 0.67 X q<br />

J + 7 0.2 X’ d<br />

J + 8 0.12 X’’ d = X’’ q<br />

J + 9 0.08 X ι<br />

J + 10 0.154 S(1.0)<br />

J + 11 0.447 S(1.2)<br />

X d , X q , X’ d , X’’ d , X’’ q , X ι , H and D are in p.u., machine MVA base.<br />

X’’ q must be equal to X’’ d<br />

IBUS, ‘GENSAL’, I, T’ do , T’’ do , T’’ qo , H, D, X d , X q , X’ d , X’’ d , X ι , S(1.0), S(1.2)/<br />

Fig. 5-1 <strong>Ashlu</strong> IPP power plant excitation control system model.<br />

Regional System Planning 10