PSS/E-29<br />
PSS2A<br />
IEEE Dual Input Stabilizer Model<br />
This model is located at system bus #__<strong>Ashlu</strong>_IPP_ IBUS.<br />
Machine #___80005____ I.<br />
This model uses CONs starting with #___________ J.<br />
and STATEs starting with # ___________ K.<br />
and VARs starting with # ___________ L.<br />
and ICONs starting with<br />
# ___________ IC.<br />
ICONs # Value Description<br />
IC 2 IC1, First Stabilizer Input Code:<br />
1 p.u. Rotor Speed Deviation<br />
2 p.u. Bus Frequency Deviation<br />
3 p.u. Generator Electrical Power on MBASE base<br />
4 p.u. Generator Accelerating Power<br />
5 p.u. Bus Voltage<br />
6. Derivative Of p.u. Bus Voltage<br />
IC + 1 0 REMBUS1, First Remote Bus Number<br />
IC + 2 3 IC1, First Stabilizer Input Code:<br />
1 p.u. Rotor Speed Deviation<br />
2 p.u. Bus Frequency Deviation<br />
3 p.u. Generator Electrical Power on MBASE base<br />
4 p.u. Generator Accelerating Power<br />
5 p.u. Bus Voltage<br />
6. Derivative Of p.u. Bus Voltage<br />
IC + 3 0 REMBUS2, Second Remote Bus Number<br />
IC + 4 5 M, Ramp Tracking Filter<br />
IC + 5 1 N, Ramp Tracking Filter<br />
CONs # Value Description<br />
J 10. T W1 (>0)<br />
J + 1 10. T W2<br />
J + 2 0. T 6<br />
J + 3 10. T W3 (>0)<br />
J + 4 0. T W4<br />