Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW
Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW
Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Reverce</strong> <strong>cycle</strong> <strong>air</strong>/<strong>water</strong> <strong>heat</strong> <strong>pumps</strong><br />
<strong>Range</strong>: <strong>from</strong> <strong>195</strong> <strong>kW</strong> <strong>to</strong> <strong>660</strong> <strong>kW</strong><br />
• Semi-hermetic screw compressors<br />
• R134a refrigerant<br />
• Innovative defrosting system<br />
• 17 size in 4 versions
RECS HAS ALL IT TAKES TO REPLACE TRADITIONAL BOILERS<br />
Though efficiency and energy saving have been common features of <strong>air</strong>-conditioning systems for quite<br />
some, these concepts have been less prone <strong>to</strong> application in <strong>heat</strong>ing systems.<br />
RECS (Recovery Energy Climaveneta System), the new Climaveneta range of extremely efficient <strong>heat</strong><br />
<strong>pumps</strong> and the only ones <strong>to</strong> use R134a refrigerant, set out <strong>to</strong> replace traditional winter <strong>heat</strong>ing systems.<br />
SPECIAL FEATURES AND MAIN INNOVATIONS OF RECS<br />
-10°C EXTERNAL AIR TEMPERATURE<br />
With <strong>heat</strong> pump operation guaranteed at external <strong>air</strong><br />
temperatures as low as –10°C, the RECS range is a<br />
valid alternative <strong>to</strong> traditional <strong>air</strong>-conditioning and<br />
<strong>heat</strong>ing systems (chiller+boiler).<br />
INNOVATIVE DEFROSTING SYSTEM<br />
(Climaveneta patent)<br />
The RECS units incorporate an innovative<br />
<strong>cycle</strong> reversal defrosting system whose<br />
algorithms can be cus<strong>to</strong>mised according<br />
<strong>to</strong> individual requirements.<br />
EXCELLENT EURO/<strong>kW</strong> RATIO<br />
The Euro/<strong>kW</strong> ratio is comparable with a R407C unit but features<br />
the efficiency of a R134a unit. Only by using sophisticated construction<br />
technologies it is possible <strong>to</strong> combine high performance with low costs.<br />
The high efficiency of R134a refrigerant, the use of purpose-designed<br />
compressors and a sophisticated control unit have contributed <strong>to</strong>wards<br />
the development of compact and reliable units at extremely competitive<br />
costs even compared with the lowest performing units running on R407C.
55°C IN THE HEATING SYSTEM<br />
The RECS range offers users <strong>heat</strong>ing <strong>water</strong><br />
temperatures of up <strong>to</strong> 55°C even at low<br />
external <strong>air</strong> temperatures.<br />
This is valid engineering solution even<br />
for the most modern <strong>heat</strong>ing<br />
system applications.<br />
17 SIZES IN 4 VERSIONS<br />
FROM <strong>195</strong> KW TO <strong>660</strong> <strong>kW</strong><br />
The large number of sizes allows<br />
the range <strong>to</strong> perfectly satisfy<br />
all system requirements.<br />
All sizes are present in each of the 4 versions:<br />
B: Standard unit<br />
LT: Low external <strong>air</strong> temperature unit<br />
LN: Low-noise unit<br />
SL: Silenced unit.
COMPRESSORS<br />
An improved generation of screw compressors featuring an extremely compact structure and optimised for<br />
R134a has allowed the volumetric displacement <strong>to</strong> be substantially increased without modifying the shape<br />
of the compressor. Elevated cooling capacities can thus be achieved with improved volumetric efficiency.<br />
• Screw profile: dual ro<strong>to</strong>r design<br />
Compared with a traditional screw compressor,<br />
the profile has been modified so that the<br />
increased volumetric flow rate requires just<br />
a 10% increase in size, a fundamental aspect<br />
of ro<strong>to</strong>rs. It was therefore possible <strong>to</strong> modify<br />
the body without affecting the external shape<br />
of the compressor.<br />
• Roller bearings<br />
Thanks <strong>to</strong> the favourable <strong>to</strong>rque load<br />
and the reduced pressure difference,<br />
the bearings work in easier conditions<br />
and therefore last longer.<br />
SCREW PROFILE<br />
OIL<br />
SEPARATOR<br />
• Oil separa<strong>to</strong>r<br />
The compressors contain<br />
an integrated three-stage oil<br />
separa<strong>to</strong>r which can guarantee<br />
extremely high separation levels,<br />
in spite of the increase<br />
in volumetric flow.<br />
This is achieved thanks <strong>to</strong> the fact that<br />
the limited density of the vapour and<br />
the outlet temperature of the R134a<br />
allow outstanding oil separation.<br />
ROLLER<br />
BEARINGS<br />
NEW CONTROL UNIT<br />
The main characteristics of the new control unit concern the user interface, unit management,<br />
compatibility and Service functions.<br />
User interface<br />
Positioned in an easily accessible area<br />
on the outside of the unit and protected<br />
by a transparent cover.<br />
It integrates a graphics display with<br />
a multilanguage menu for reading and setting<br />
parameters, a synoptic panel which,<br />
by now a traditional feature of Climaveneta,<br />
offers an immediate view of compressor<br />
status.
Unit management<br />
Special control algorithms optimise energy saving and guarantee maximum system reliability: compressor<br />
starting/s<strong>to</strong>pping management with hourly rotation + FIFO, thermoregula<strong>to</strong>r management of available<br />
resources, variation and control of operating parameters, moni<strong>to</strong>ring of critical temperatures and phase<br />
sequences. The software, especially developed by Climaveneta, offers modulating control of unit capacity<br />
<strong>from</strong> 100% <strong>to</strong> a minimum which, depending on its size, can be as little as 12.5%.<br />
Interaction<br />
Ample opportunities of interaction with Climaveneta and De'Longhi supervision systems and many other BMS<br />
systems operating on the market:<br />
METASYS ® , MODBUS ® , LONWORKS ® , SIEMENS ® , TREND ® .<br />
"Sequencer MANAGER 3000" central control system<br />
Software which enables au<strong>to</strong>nomous control of a series of unit and easily interacting<br />
with the most modern BSM systems.<br />
FWS supervision<br />
The controller is also compatible with the innovative Climaveneta<br />
FWS (Field Web Server) supervision system.<br />
Service<br />
The new “black box” logs data relative <strong>to</strong> 200 variables, acquired<br />
every 30 seconds during the 10 minutes preceding an event,<br />
for 400 separate events.<br />
The software is compatible with the Climaveneta<br />
Service programme: through a remote Internet link it is possible<br />
<strong>to</strong> moni<strong>to</strong>r the unit, implement preventive and corrective action<br />
and consequently offer a more effective and higher quality of<br />
service.<br />
HEAT RECOVERY<br />
While producing cooling power, it is also possible <strong>to</strong> produce hot <strong>water</strong> at temperatures up <strong>to</strong> 55°C.<br />
If requested when ordering, two <strong>heat</strong> recovery systems are available: partial, which can recover<br />
approximately 20% of the available cooling power, and <strong>to</strong>tal, which can produce a <strong>heat</strong>ing power equal <strong>to</strong> the<br />
cooling power.<br />
SILENCED VERSIONS<br />
Two levels of noise reduction are available for all sizes:<br />
silent-running and very silent-running.<br />
The low noise levels are achieved by reducing fan speed<br />
and optimising the circuitry and generously sizing<br />
the coils <strong>to</strong> ensure correct operation.<br />
A dedicated control device allows the unit<br />
<strong>to</strong> work at ambient <strong>air</strong> temperatures of up <strong>to</strong> 46°C.<br />
The compressors and cooling circuit components<br />
are housed in a large closed and soundproofed chamber.<br />
ON-BOARD PUMPS (SIZE RECS 1052*-<strong>195</strong>2*)<br />
The units can be fitted with a pumping unit attachment which can be sized on request. It is powered directly<br />
by the unit and moni<strong>to</strong>red by the control unit. Special functions are available <strong>to</strong> manage pump commands,<br />
report faults and optimise operating times.
RECS 1052* 1152* 1352* 1552* 1752*<br />
1062 1162 1362 1562 1762<br />
Refrigeration only<br />
Cooling capacity (1) <strong>kW</strong> <strong>195</strong> 238 276 307 359<br />
Total power input (1) <strong>kW</strong> 74 96 109 114 139<br />
Total EER (1) 2,6 2,5 2,5 2,7 2,6<br />
Heating only<br />
Heating capacity (2) <strong>kW</strong> 212 259 301 332 389<br />
Total power input (2) <strong>kW</strong> 70 90 102 108 131<br />
Total COP (2) 3,0 3,0 3,0 3,1 3,0<br />
Sound power level (3) dB(A) 96 97 97 98 98<br />
Sound pressure level (4) dB(A) 77 78 78 78 78<br />
Dimensions A (5) mm 4610 4610 4610 5610 5610<br />
B (5) mm 2220 2220 2220 2220 2220<br />
H mm 2150 2150 2430 2430 2430<br />
Weight Kg 2910* 3450* 3590* 3860* 4100*<br />
2960 3470 3860 4140 4340<br />
H<br />
B<br />
A<br />
RECS 1052*-<strong>195</strong>2*<br />
1062 - 1962<br />
RECS 2022-2722
<strong>195</strong>2*<br />
1962<br />
2022 2222 2422 2622 2722<br />
385 454 492 522 585 <strong>660</strong><br />
155 170 181 187 215 223<br />
2,5 2,7 2,7 2,8 2,7 3,0<br />
418 491 531 568 613 695<br />
141 162 174 185 <strong>195</strong> 213<br />
3,0 3,0 3,0 3,1 3,1 3,3<br />
98 99 101 101 101 101<br />
78 79 80 80 80 80<br />
5610 6300 7200 7200 7200 8800<br />
2220 2260 2260 2260 2260 2260<br />
2430 2350 2350 2350 2350 2350<br />
4170*<br />
4640<br />
6080 6540 6690 6910 7500<br />
Data referred <strong>to</strong>:<br />
1) Refrigeration only:<br />
Evapora<strong>to</strong>r <strong>water</strong> (in/out) 12/7 °C<br />
Condenser <strong>air</strong> (in) 35 °C<br />
2) Heating only:<br />
Condenser <strong>water</strong> (in/out) 40/45 °C<br />
Evapora<strong>to</strong>r <strong>air</strong> (in)<br />
7°C - 87% H.R.<br />
3) Acoustic power measured according <strong>to</strong> ISO 3744 and<br />
Eurovent 8/1.<br />
4) Acoustic pressure measured in free field conditions on a<br />
reflecting plane. Average value on the condensing coil side,<br />
1 metre <strong>from</strong> the outer surface and 1 metre above the base<br />
of the unit.<br />
5) Free space required around the unit:<br />
Electrical panel side<br />
1500 mm<br />
Opposite side <strong>from</strong> electrical panel 1500 mm<br />
Condensation coil side<br />
2000 mm<br />
* Units with <strong>pumps</strong> on board
B 100 AS_105_202_B_CV_05_06_GB (V.02)<br />
CLIMAVENETA S.p.A.<br />
Via Sarson, 57/c<br />
36061 Bassano del Grappa (VI) - Italia<br />
Tel. +39 0424 509 500<br />
Fax +39 0424 509 509<br />
info@climaveneta.it<br />