11.03.2015 Views

Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW

Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW

Reverce cycle air/water heat pumps Range: from 195 kW to 660 kW

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Reverce</strong> <strong>cycle</strong> <strong>air</strong>/<strong>water</strong> <strong>heat</strong> <strong>pumps</strong><br />

<strong>Range</strong>: <strong>from</strong> <strong>195</strong> <strong>kW</strong> <strong>to</strong> <strong>660</strong> <strong>kW</strong><br />

• Semi-hermetic screw compressors<br />

• R134a refrigerant<br />

• Innovative defrosting system<br />

• 17 size in 4 versions


RECS HAS ALL IT TAKES TO REPLACE TRADITIONAL BOILERS<br />

Though efficiency and energy saving have been common features of <strong>air</strong>-conditioning systems for quite<br />

some, these concepts have been less prone <strong>to</strong> application in <strong>heat</strong>ing systems.<br />

RECS (Recovery Energy Climaveneta System), the new Climaveneta range of extremely efficient <strong>heat</strong><br />

<strong>pumps</strong> and the only ones <strong>to</strong> use R134a refrigerant, set out <strong>to</strong> replace traditional winter <strong>heat</strong>ing systems.<br />

SPECIAL FEATURES AND MAIN INNOVATIONS OF RECS<br />

-10°C EXTERNAL AIR TEMPERATURE<br />

With <strong>heat</strong> pump operation guaranteed at external <strong>air</strong><br />

temperatures as low as –10°C, the RECS range is a<br />

valid alternative <strong>to</strong> traditional <strong>air</strong>-conditioning and<br />

<strong>heat</strong>ing systems (chiller+boiler).<br />

INNOVATIVE DEFROSTING SYSTEM<br />

(Climaveneta patent)<br />

The RECS units incorporate an innovative<br />

<strong>cycle</strong> reversal defrosting system whose<br />

algorithms can be cus<strong>to</strong>mised according<br />

<strong>to</strong> individual requirements.<br />

EXCELLENT EURO/<strong>kW</strong> RATIO<br />

The Euro/<strong>kW</strong> ratio is comparable with a R407C unit but features<br />

the efficiency of a R134a unit. Only by using sophisticated construction<br />

technologies it is possible <strong>to</strong> combine high performance with low costs.<br />

The high efficiency of R134a refrigerant, the use of purpose-designed<br />

compressors and a sophisticated control unit have contributed <strong>to</strong>wards<br />

the development of compact and reliable units at extremely competitive<br />

costs even compared with the lowest performing units running on R407C.


55°C IN THE HEATING SYSTEM<br />

The RECS range offers users <strong>heat</strong>ing <strong>water</strong><br />

temperatures of up <strong>to</strong> 55°C even at low<br />

external <strong>air</strong> temperatures.<br />

This is valid engineering solution even<br />

for the most modern <strong>heat</strong>ing<br />

system applications.<br />

17 SIZES IN 4 VERSIONS<br />

FROM <strong>195</strong> KW TO <strong>660</strong> <strong>kW</strong><br />

The large number of sizes allows<br />

the range <strong>to</strong> perfectly satisfy<br />

all system requirements.<br />

All sizes are present in each of the 4 versions:<br />

B: Standard unit<br />

LT: Low external <strong>air</strong> temperature unit<br />

LN: Low-noise unit<br />

SL: Silenced unit.


COMPRESSORS<br />

An improved generation of screw compressors featuring an extremely compact structure and optimised for<br />

R134a has allowed the volumetric displacement <strong>to</strong> be substantially increased without modifying the shape<br />

of the compressor. Elevated cooling capacities can thus be achieved with improved volumetric efficiency.<br />

• Screw profile: dual ro<strong>to</strong>r design<br />

Compared with a traditional screw compressor,<br />

the profile has been modified so that the<br />

increased volumetric flow rate requires just<br />

a 10% increase in size, a fundamental aspect<br />

of ro<strong>to</strong>rs. It was therefore possible <strong>to</strong> modify<br />

the body without affecting the external shape<br />

of the compressor.<br />

• Roller bearings<br />

Thanks <strong>to</strong> the favourable <strong>to</strong>rque load<br />

and the reduced pressure difference,<br />

the bearings work in easier conditions<br />

and therefore last longer.<br />

SCREW PROFILE<br />

OIL<br />

SEPARATOR<br />

• Oil separa<strong>to</strong>r<br />

The compressors contain<br />

an integrated three-stage oil<br />

separa<strong>to</strong>r which can guarantee<br />

extremely high separation levels,<br />

in spite of the increase<br />

in volumetric flow.<br />

This is achieved thanks <strong>to</strong> the fact that<br />

the limited density of the vapour and<br />

the outlet temperature of the R134a<br />

allow outstanding oil separation.<br />

ROLLER<br />

BEARINGS<br />

NEW CONTROL UNIT<br />

The main characteristics of the new control unit concern the user interface, unit management,<br />

compatibility and Service functions.<br />

User interface<br />

Positioned in an easily accessible area<br />

on the outside of the unit and protected<br />

by a transparent cover.<br />

It integrates a graphics display with<br />

a multilanguage menu for reading and setting<br />

parameters, a synoptic panel which,<br />

by now a traditional feature of Climaveneta,<br />

offers an immediate view of compressor<br />

status.


Unit management<br />

Special control algorithms optimise energy saving and guarantee maximum system reliability: compressor<br />

starting/s<strong>to</strong>pping management with hourly rotation + FIFO, thermoregula<strong>to</strong>r management of available<br />

resources, variation and control of operating parameters, moni<strong>to</strong>ring of critical temperatures and phase<br />

sequences. The software, especially developed by Climaveneta, offers modulating control of unit capacity<br />

<strong>from</strong> 100% <strong>to</strong> a minimum which, depending on its size, can be as little as 12.5%.<br />

Interaction<br />

Ample opportunities of interaction with Climaveneta and De'Longhi supervision systems and many other BMS<br />

systems operating on the market:<br />

METASYS ® , MODBUS ® , LONWORKS ® , SIEMENS ® , TREND ® .<br />

"Sequencer MANAGER 3000" central control system<br />

Software which enables au<strong>to</strong>nomous control of a series of unit and easily interacting<br />

with the most modern BSM systems.<br />

FWS supervision<br />

The controller is also compatible with the innovative Climaveneta<br />

FWS (Field Web Server) supervision system.<br />

Service<br />

The new “black box” logs data relative <strong>to</strong> 200 variables, acquired<br />

every 30 seconds during the 10 minutes preceding an event,<br />

for 400 separate events.<br />

The software is compatible with the Climaveneta<br />

Service programme: through a remote Internet link it is possible<br />

<strong>to</strong> moni<strong>to</strong>r the unit, implement preventive and corrective action<br />

and consequently offer a more effective and higher quality of<br />

service.<br />

HEAT RECOVERY<br />

While producing cooling power, it is also possible <strong>to</strong> produce hot <strong>water</strong> at temperatures up <strong>to</strong> 55°C.<br />

If requested when ordering, two <strong>heat</strong> recovery systems are available: partial, which can recover<br />

approximately 20% of the available cooling power, and <strong>to</strong>tal, which can produce a <strong>heat</strong>ing power equal <strong>to</strong> the<br />

cooling power.<br />

SILENCED VERSIONS<br />

Two levels of noise reduction are available for all sizes:<br />

silent-running and very silent-running.<br />

The low noise levels are achieved by reducing fan speed<br />

and optimising the circuitry and generously sizing<br />

the coils <strong>to</strong> ensure correct operation.<br />

A dedicated control device allows the unit<br />

<strong>to</strong> work at ambient <strong>air</strong> temperatures of up <strong>to</strong> 46°C.<br />

The compressors and cooling circuit components<br />

are housed in a large closed and soundproofed chamber.<br />

ON-BOARD PUMPS (SIZE RECS 1052*-<strong>195</strong>2*)<br />

The units can be fitted with a pumping unit attachment which can be sized on request. It is powered directly<br />

by the unit and moni<strong>to</strong>red by the control unit. Special functions are available <strong>to</strong> manage pump commands,<br />

report faults and optimise operating times.


RECS 1052* 1152* 1352* 1552* 1752*<br />

1062 1162 1362 1562 1762<br />

Refrigeration only<br />

Cooling capacity (1) <strong>kW</strong> <strong>195</strong> 238 276 307 359<br />

Total power input (1) <strong>kW</strong> 74 96 109 114 139<br />

Total EER (1) 2,6 2,5 2,5 2,7 2,6<br />

Heating only<br />

Heating capacity (2) <strong>kW</strong> 212 259 301 332 389<br />

Total power input (2) <strong>kW</strong> 70 90 102 108 131<br />

Total COP (2) 3,0 3,0 3,0 3,1 3,0<br />

Sound power level (3) dB(A) 96 97 97 98 98<br />

Sound pressure level (4) dB(A) 77 78 78 78 78<br />

Dimensions A (5) mm 4610 4610 4610 5610 5610<br />

B (5) mm 2220 2220 2220 2220 2220<br />

H mm 2150 2150 2430 2430 2430<br />

Weight Kg 2910* 3450* 3590* 3860* 4100*<br />

2960 3470 3860 4140 4340<br />

H<br />

B<br />

A<br />

RECS 1052*-<strong>195</strong>2*<br />

1062 - 1962<br />

RECS 2022-2722


<strong>195</strong>2*<br />

1962<br />

2022 2222 2422 2622 2722<br />

385 454 492 522 585 <strong>660</strong><br />

155 170 181 187 215 223<br />

2,5 2,7 2,7 2,8 2,7 3,0<br />

418 491 531 568 613 695<br />

141 162 174 185 <strong>195</strong> 213<br />

3,0 3,0 3,0 3,1 3,1 3,3<br />

98 99 101 101 101 101<br />

78 79 80 80 80 80<br />

5610 6300 7200 7200 7200 8800<br />

2220 2260 2260 2260 2260 2260<br />

2430 2350 2350 2350 2350 2350<br />

4170*<br />

4640<br />

6080 6540 6690 6910 7500<br />

Data referred <strong>to</strong>:<br />

1) Refrigeration only:<br />

Evapora<strong>to</strong>r <strong>water</strong> (in/out) 12/7 °C<br />

Condenser <strong>air</strong> (in) 35 °C<br />

2) Heating only:<br />

Condenser <strong>water</strong> (in/out) 40/45 °C<br />

Evapora<strong>to</strong>r <strong>air</strong> (in)<br />

7°C - 87% H.R.<br />

3) Acoustic power measured according <strong>to</strong> ISO 3744 and<br />

Eurovent 8/1.<br />

4) Acoustic pressure measured in free field conditions on a<br />

reflecting plane. Average value on the condensing coil side,<br />

1 metre <strong>from</strong> the outer surface and 1 metre above the base<br />

of the unit.<br />

5) Free space required around the unit:<br />

Electrical panel side<br />

1500 mm<br />

Opposite side <strong>from</strong> electrical panel 1500 mm<br />

Condensation coil side<br />

2000 mm<br />

* Units with <strong>pumps</strong> on board


B 100 AS_105_202_B_CV_05_06_GB (V.02)<br />

CLIMAVENETA S.p.A.<br />

Via Sarson, 57/c<br />

36061 Bassano del Grappa (VI) - Italia<br />

Tel. +39 0424 509 500<br />

Fax +39 0424 509 509<br />

info@climaveneta.it<br />

www.climaveneta.it