24.03.2015 Views

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission ...

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission ...

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>SIPROTEC</strong> 4<br />

<strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong><br />

<strong>Transmission</strong> Lines<br />

<strong>Protection</strong> Systems<br />

Catalog SIP 4.2 • 1999


<strong>SIPROTEC</strong> 4<br />

<strong>7SA522</strong><br />

<strong>Protection</strong> Systems<br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong><br />

<strong>for</strong> <strong>Transmission</strong> Lines<br />

Description/Overview Pages 2 to 11<br />

Functions Pages 12 to 17<br />

Typical fields application Pages 18 to 20<br />

Firmware V4<br />

Catalog SIP 4.2 • 1999<br />

Technical data Pages 21 to 31<br />

Selection and<br />

ordering data Pages 32 and 33<br />

© Siemens AG 1999<br />

Accessories Page 34<br />

Trip time curves Page 35<br />

Connection diagrams Pages 36 to 41<br />

Advantages to you<br />

Cost-effectiveness,<br />

high degree of automation<br />

User-friendly operation<br />

Low planning and engineering<br />

ef<strong>for</strong>t<br />

Fast, flexible mounting,<br />

reduced wiring<br />

Simple, short commissioning<br />

Simple spare part stocking,<br />

high flexibility<br />

High reliability and availability<br />

State-of-the-art technology<br />

Compliance with international<br />

standards<br />

Integration in the overall system<br />

<strong>SIPROTEC</strong> 4-SICAM-SIMATIC <br />

Dimension drawings Pages 42 to 44


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Description<br />

Application<br />

The <strong>7SA522</strong> relay provides<br />

full scheme distance protection<br />

and incorporates all functions<br />

usually required <strong>for</strong> the<br />

protection of a power line.<br />

The relay is designed to provide<br />

fast and selective fault<br />

clearance on transmission<br />

and subtransmission overhead<br />

lines and cables. This<br />

contributes towards improved<br />

stability and availability<br />

of your electrical power<br />

transmission system. The power<br />

system star point can<br />

be solid or impedance grounded<br />

(earthed). The <strong>7SA522</strong> is<br />

suitable <strong>for</strong> single- and<br />

three-phase tripping applications<br />

with and without pilot-<br />

(tele-) protection schemes.<br />

The effect of apparent impedances<br />

in unfaulted fault<br />

loops is eliminated by a<br />

sophisticated and improved<br />

method which uses pattern<br />

recognition with symmetrical<br />

components and load compensation.<br />

The correct phase<br />

selection is essential <strong>for</strong> selective<br />

tripping and reliable<br />

fault location.<br />

During network power<br />

swings an improved power<br />

swing blocking feature prevents<br />

the distance protection<br />

from unwanted tripping and<br />

optionally provides controlled<br />

tripping in the event of loss<br />

of synchronism (out of step).<br />

This function guarantees power<br />

transmission even under<br />

critical network operating<br />

conditions.<br />

Maximum Lifetime and<br />

Reliability<br />

The <strong>7SA522</strong> hardware is based<br />

on 20 years of experience<br />

by Siemens with numerical<br />

protection. State-of-theart<br />

32 bit microprocessor<br />

technology is employed.<br />

Naturally the device complies<br />

with the latest standards and<br />

techniques <strong>for</strong> electromagnetic<br />

compatibility. The overall<br />

number of electronic components<br />

is substantially reduced<br />

by using large-scale integrated<br />

circuits.<br />

The relay software is designed<br />

in accordance with high<br />

level programming language<br />

techniques. The long experience<br />

in manufacturing numerical<br />

relays provide the basis<br />

<strong>for</strong> a modern software structure.<br />

This along with modern<br />

manufacturing techniques<br />

and quality controls ensure<br />

maximum lifetime and reliability.<br />

Cost-effective power<br />

system management<br />

The <strong>SIPROTEC</strong> 4 units are<br />

numerical relays which also<br />

provide control and monitoring<br />

functions and there<strong>for</strong>e<br />

support the user in view of a<br />

cost-effective power system<br />

management. They contribute<br />

towards the reliable<br />

supply of electric power to<br />

the customers.<br />

Local operation has been designed<br />

according to ergonomic<br />

criteria. Large, easy-toread<br />

displays are a major design<br />

aim.<br />

The <strong>SIPROTEC</strong> 4 units have<br />

a uni<strong>for</strong>m design and a degree<br />

of functionality which<br />

represents a whole new<br />

level of quality in protection<br />

and control. If the application<br />

requirements change the<br />

relays may be adapted<br />

quickly by entering new settings<br />

without any additional<br />

hardware costs.<br />

The use of powerful microcontrollers<br />

and the application<br />

of digital measured value<br />

conditioning and processing<br />

largely suppresses the influence<br />

of higher-frequency<br />

transients, harmonics and<br />

DC components.<br />

Back-up protection<br />

The unit can also be used as<br />

backup distance and overcurrent<br />

protection <strong>for</strong> all types<br />

of differential protection<br />

equipment.<br />

Add-on protective<br />

functions<br />

The <strong>7SA522</strong> incorporates several<br />

protective functions<br />

usually required <strong>for</strong> transmission<br />

line protection. These<br />

are<br />

− High-resistance earth fault<br />

protection<br />

− Phase overcurrent protection<br />

− STUB bus overcurrent stage<br />

− Overvoltage protection<br />

− Automatic reclosure<br />

− Synchrocheck<br />

− Circuit breaker failure protection.<br />

Programmable logic<br />

The integrated programmable<br />

logic functions allow the<br />

user to implement his own<br />

functions <strong>for</strong> the automation<br />

of a switchgear (interlocking)<br />

or a substation via a graphic<br />

user interface. The user can<br />

also generate user-defined<br />

messages and logical combinations<br />

of internal or external<br />

signals.<br />

Local and remote<br />

communication<br />

The <strong>SIPROTEC</strong> 4 units provide<br />

several serial communication<br />

interfaces <strong>for</strong> various<br />

tasks:<br />

− Front interface <strong>for</strong> connecting<br />

a PC<br />

− IEC system interface <strong>for</strong><br />

connecting to a control<br />

system via<br />

IEC 60870-5-103 or<br />

Profibus-FMS/DP,<br />

Modbus RTU,<br />

DNP3.0<br />

− Prepared <strong>for</strong> Ethernet<br />

(UCA)<br />

− Modem interface <strong>for</strong> connecting<br />

a PC via modem<br />

and/or starcoupler<br />

− Time synchronization via<br />

IRIG-B/SCADA (DCF 77)<br />

The <strong>7SA522</strong> relay has two<br />

additional optional interfaces<br />

<strong>for</strong> communication with the<br />

remote relay or process bus.<br />

It is there<strong>for</strong>e well prepared<br />

<strong>for</strong> future communication<br />

standards.<br />

Operational indications<br />

and fault indications with<br />

time stamp<br />

The <strong>SIPROTEC</strong> 4 units provide<br />

extensive data <strong>for</strong> fault<br />

analysis as well as control.<br />

All indications listed below<br />

are protected against power<br />

supply failure.<br />

− Fault event record<br />

The last eight fault cases<br />

are always stored in the<br />

unit. All fault recordings<br />

are time stamped with a<br />

resolution of 1 ms.<br />

− Operational indications<br />

All indications that are not<br />

directly associated with<br />

the fault (e.g. operating or<br />

switching actions) are stored<br />

in the status indication<br />

buffer. The time resolution<br />

is 1 ms.<br />

2 Siemens SIP 4.2 · 08/99


Operational measured<br />

values<br />

The large scope of measured<br />

and limit values permits improved<br />

system management<br />

as well as simplified commissioning.<br />

Control<br />

The integrated control functions<br />

permit control of circuit<br />

breakers or isolators (electrically<br />

operated/motorized disconnectors)<br />

via the integrated<br />

operator panel, binary inputs,<br />

DIGSI 4 or the substation<br />

control system (e.g.<br />

SICAM).<br />

A full range of control execution<br />

functions is provided.<br />

Time synchronization<br />

A battery backed clock is always<br />

provided and can be<br />

synchronized via a synchronization<br />

signal (DCF77,<br />

IRIG-B via satellite receiver),<br />

binary input, system interface<br />

or SCADA (e.g. SICAM).<br />

A date and time is assigned<br />

to every indication.<br />

Assignable binary inputs<br />

and outputs<br />

Binary inputs, outputs and<br />

LED’s can be assigned to<br />

per<strong>for</strong>m specific functions as<br />

defined by the user.<br />

Selectable function keys<br />

Four function keys can be assigned<br />

to permit the user to<br />

per<strong>for</strong>m frequently recurring<br />

actions very quickly and<br />

simply.<br />

Typical applications are, <strong>for</strong><br />

example, jumps to a given<br />

position in the menu tree in<br />

order to display the list of<br />

operating indications or to<br />

per<strong>for</strong>m automatic functions,<br />

such as ”Switching of circuit-breaker”.<br />

Continuous self-monitoring<br />

The hardware and software<br />

components are continuously<br />

monitored. If abnormal conditions<br />

are detected, the unit<br />

signals them immediately. In<br />

this way, a high level of safety,<br />

reliability and availability is<br />

achieved.<br />

Reliable battery<br />

monitoring<br />

The internal battery is used<br />

to back-up the clock, switching<br />

statistics, status and<br />

fault indications and fault recording<br />

in the event of a power<br />

supply failure. Its function<br />

is checked by the processor<br />

at regular intervals. If<br />

the capacity of the battery is<br />

found to be declining, an<br />

alarm is generated. Routine<br />

replacement is there<strong>for</strong>e not<br />

necessary. All setting parameters<br />

are stored in the<br />

Flash-EPROM, and there<strong>for</strong>e<br />

not lost if the power supply<br />

or battery fails.<br />

User-friendly local<br />

operation<br />

Many advantages can already<br />

be found on the clear and<br />

user-friendly front panel:<br />

Positioning and grouping of<br />

the keys support the natural<br />

operating process.<br />

A large non-reflective back-lit<br />

display provides clear<br />

in<strong>for</strong>mation display.<br />

Programmable (freely assignable)<br />

LED’s <strong>for</strong> important<br />

messages are provided. Arrow<br />

keys ensure an easy navigation<br />

in the function tree.<br />

Operator-friendly input of the<br />

set values via the numeric<br />

keys or DIGSI 4 is provided as<br />

well as four programmable<br />

keys <strong>for</strong> frequently used<br />

functions at the push of a button.<br />

<strong>Distance</strong><br />

Fault<br />

Locator<br />

Gnd<br />

O/C<br />

Directional<br />

Ground<br />

Overcurrent<br />

STUB<br />

O/C<br />

21<br />

21N<br />

FL<br />

50N<br />

51N<br />

67N<br />

5050N-2<br />

5151N-2<br />

50STUB<br />

52<br />

68<br />

68T<br />

Power<br />

Swing<br />

85-21<br />

Pilot<br />

Dist.<br />

Local/Tele Ctrl.<br />

Commands<br />

CB Indications<br />

Trip Circuit<br />

supervision<br />

27WI 85-67N 50HS 50BF 59 25<br />

Weak<br />

infeed<br />

Lockout<br />

Pilot<br />

Gnd<br />

Operat.<br />

values<br />

Switch<br />

onto-<br />

Flt. O/C<br />

Bkr.<br />

fail.<br />

CFC Logic<br />

Synchrocheck<br />

74TC<br />

Pilot schemes can use<br />

one channel or two<br />

redundant channels to<br />

theremoteend<br />

86<br />

79 Autoreclosure<br />

Overvoltage<br />

Supervision<br />

Note:Pilotschemes=Teleprotection<br />

Serial Communication<br />

Interfaces<br />

Figure 1<br />

Single line diagram<br />

Siemens SIP 4.2 · 08/99 3


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Description<br />

Local operation<br />

All operator actions can be<br />

executed and in<strong>for</strong>mation<br />

displayed via an integrated<br />

user interface.<br />

Figure 2<br />

Front view <strong>SIPROTEC</strong> 4 <strong>7SA522</strong><br />

On the LCD display,<br />

substation and device in<strong>for</strong>mation<br />

can be displayed<br />

as text in various lists.<br />

Frequently displayed in<strong>for</strong>mation<br />

includes measured<br />

analog values, binary in<strong>for</strong>mation<br />

about the state of the<br />

switchgear and the device,<br />

protection in<strong>for</strong>- mation, general<br />

indications and alarms.<br />

<br />

<br />

<br />

<br />

14 assignable (configurable)<br />

LEDs are used to display<br />

plant or device in<strong>for</strong>mation.<br />

The LEDs can be labelled<br />

according to user requirements.<br />

An LED reset key resets<br />

the LEDs.<br />

<br />

RS232 operator interface<br />

<br />

<br />

4 configurable function keys<br />

permit the user to execute<br />

frequently used actions simply<br />

and fast. Typical applications<br />

include jumps to certain<br />

points in the menu tree<br />

to display the operational<br />

measured values, or execution<br />

of automatic functions<br />

such as: ”Operate the circuit-breaker”.<br />

Numerical keys <strong>for</strong> easy data entry<br />

Keys <strong>for</strong> navigation<br />

4 Siemens SIP 4.2 · 08/99


Description<br />

Connection techniques<br />

and housing with many<br />

advantages<br />

1/2 and 1/1-rack sizes: These<br />

are the available housing<br />

widths of the <strong>SIPROTEC</strong> 4<br />

<strong>7SA522</strong> relays, referred to a<br />

19" module frame system.<br />

This means that previous<br />

models can always be replaced.<br />

The space required in<br />

the switchgear cubicle is the<br />

same. The height is a uni<strong>for</strong>m<br />

243 mm (9.57 inches)<br />

<strong>for</strong> all housing widths. All<br />

cables can be connected<br />

with or without ring lugs.<br />

Plug-in terminals are available<br />

as an option.<br />

Figure 3<br />

Housing widths 1/2 x 19’‘ and 1/1 x 19’‘<br />

Figure 5<br />

Rear view with terminal covers and<br />

wiring<br />

Figure 4<br />

Rear view with screw terminals and serial<br />

interfaces<br />

Siemens SIP 4.2 · 08/99 5


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

DIGSI 4 Operating Program<br />

DIGSI 4<br />

The PC operating program<br />

DIGSI 4 is the interface between<br />

the user and the<br />

<strong>SIPROTEC</strong> 4 units. It has a<br />

modern PC operator interface<br />

in accordance with the<br />

Windows ® versions 95/98/<br />

NT4.0. With DIGSI 4 the<br />

<strong>SIPROTEC</strong> 4 units can be<br />

configured and interrogated -<br />

it is a tailored program <strong>for</strong> the<br />

electrical supply industries.<br />

Figure 6<br />

DIGSI 4 – Main menu<br />

Figure 7<br />

DIGSI 4 – Device configuration<br />

DIGSI 4 matrix<br />

The DIGSI 4 matrix provides<br />

the user with an overall view<br />

of the unit configuration at a<br />

glance. For example, all LEDs<br />

and the configuration of the<br />

binary inputs and output relays<br />

are displayed in a single<br />

chart. And with one click of<br />

the mouse button connections<br />

can be made.<br />

Figure 8<br />

DIGSI 4 – Configuration matrix<br />

6 Siemens SIP 4.2 · 08/99


DIGSI 4 Operating Program<br />

Convenient protection<br />

functions setting:<br />

Secondary or Primary<br />

The settings can be entered<br />

and displayed as secondary<br />

or primary values. Switching<br />

between secondary and primary<br />

is done by clicking on<br />

the corresponding symbol in<br />

the tool bar.<br />

Commissioning<br />

Special attention has been<br />

paid to commissioning. All<br />

binary inputs and output contacts<br />

can be displayed and<br />

activated directly. This can<br />

simplify the wiring check<br />

significantly <strong>for</strong> the user.<br />

CFC: Programming logic<br />

With the help of the CFC graphic<br />

tool (Continuous Function<br />

Chart) interlocks and<br />

switching sequences can be<br />

configured simply via drag<br />

and drop of logic symbols; no<br />

special knowledge of software<br />

is required. Logical elements,<br />

such as AND, OR,<br />

flip-flops and timer elements<br />

are available. The user can<br />

also generate user-defined<br />

annunciations and logical<br />

combinations of internal or<br />

external signals.<br />

Figure 9<br />

CFC (Continuous Function Chart)<br />

<br />

The new DIGSI 4<br />

Easy to learn<br />

Clear layout of routing matrix<br />

Substation, feeder and equipment<br />

data management<br />

Password protection<br />

Linked with the SICAM/SIMATIC<br />

software environment<br />

Windows standards<br />

<br />

Siemens SIP 4.2 · 08/99 7


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

System <strong>SIPROTEC</strong> 4/SICAM<br />

<strong>SIPROTEC</strong> 4 as an integral part<br />

of SICAM energy automation<br />

system<br />

<strong>SIPROTEC</strong> 4 is tailor-made <strong>for</strong> use<br />

in the SIMATIC-based SICAM<br />

energy automation system. The<br />

SICAM family consists of the following<br />

components:<br />

− SICAM RTU, the modern telecontrol<br />

system with automation<br />

and programmable logic functions<br />

− SICAM SAS, the modern integration<br />

of switchgear automation<br />

and in<strong>for</strong>mation technology<br />

− SICAM PCC, the in<strong>for</strong>mation<br />

and communication technology<br />

on a PC basis<br />

Database<br />

SICAM WinCC<br />

DIGSI 4<br />

SICAM plusTOOLS<br />

Bay control units<br />

SICAM/<strong>SIPROTEC</strong> 4<br />

Software<br />

Data<br />

management<br />

Communication<br />

Various communication<br />

protocols<br />

SCADA<br />

CPU<br />

Central I/O<br />

<strong>Protection</strong> devices<br />

Data management and communication<br />

is one of the strong points<br />

of the SICAM and <strong>SIPROTEC</strong> 4<br />

system. Powerful engineering<br />

tools (SICAM plus TOOLS based<br />

on STEP7 and SICAM Win CC)<br />

make working with SICAM convenient.<br />

The <strong>SIPROTEC</strong> 4 units<br />

are optimally matched <strong>for</strong> use in<br />

SICAM SAS and SICAM PCC.<br />

With SICAM and <strong>SIPROTEC</strong> 4<br />

continuity exists at three central<br />

points:<br />

− Data management<br />

− Software architecture<br />

− Communication.<br />

Figure 10<br />

SICAM/<strong>SIPROTEC</strong> 4 architecture<br />

IEC 60870-5-103/Profibus-FMS<br />

Rear of unit<br />

<strong>SIPROTEC</strong> 4<br />

Front interface<br />

Service<br />

Bus<br />

Rear of unit<br />

<strong>SIPROTEC</strong> 4<br />

Front interface<br />

Systems<br />

control<br />

Rear of unit<br />

<strong>SIPROTEC</strong> 4<br />

Front interface<br />

Office<br />

Modem<br />

access<br />

All central system components<br />

(SICAM and <strong>SIPROTEC</strong> 4 CPUs,<br />

SICAM WinCC, SICAM plus<br />

TOOLS, bay controllers and protection<br />

equipment), as well as the<br />

DIGSI 4 operating program, are<br />

established on the same basis.<br />

The ability to link SICAM/SIPRO-<br />

TEC and other components of the<br />

substation control, protection and<br />

automation is assured via open<br />

interfaces, such as<br />

IEC 60870-5-103 or PROFIBUS.<br />

Service interface<br />

The service interface can be used<br />

asa2 nd operating interface.<br />

DIGSI 4 offers the additional possibility<br />

of accessing bay controllers<br />

via modem. Thus the full<br />

range of DIGSI 4 functionality is<br />

available at the office desk or<br />

when travelling (by laptop and modem).<br />

This permits rapid and extensive<br />

access <strong>for</strong> the service personnel.<br />

All settings and control<br />

commands are available and it is<br />

possible to read the operational<br />

and fault event logs, fault records<br />

as well as ope- rational measured<br />

values.<br />

Figure 11<br />

Systems control bus and service bus<br />

Star coupler<br />

All <strong>SIPROTEC</strong> units operate also<br />

with the proven star coupler. The<br />

star coupler is used <strong>for</strong> simple<br />

applications which also give the<br />

user an alternative method of<br />

retrieving in<strong>for</strong>mation remotely.<br />

Service vehicle<br />

8 Siemens SIP 4.2 · 08/99


<strong>SIPROTEC</strong> 4/SICAM system<br />

SICAM WinCC<br />

Operation and monitoring<br />

archive, configuration station<br />

Telecontrol interafce to<br />

system control centers<br />

(e.g. IEC 60870-5-101)<br />

Automation<br />

systems<br />

(e.g. SIMATIC)<br />

Time synchronisation<br />

DCF77, GPS<br />

DIGSI 4<br />

SICAM SC<br />

IEC 60870-5-103<br />

Profibus FMS<br />

IEC 60870-5-103<br />

2) 2) 1) 2) 1) 2)<br />

1)<br />

6MD63<br />

<strong>Protection</strong><br />

<strong>Protection</strong>/control<br />

Control<br />

7SJ61/62<br />

7SJ61/62 6MD/7SJ63 6MB525 7SJ61/62 6MD63 7SJ63<br />

1) <strong>Protection</strong> and control 2) <strong>Protection</strong> and control<br />

in seperate units.<br />

in one unit.<br />

7SJ600<br />

7SA511<br />

7UT51<br />

SD51<br />

7SJ51<br />

6MB525<br />

Figure 12<br />

SICAM SAS communication structure<br />

Figure 13<br />

Communication via star coupler<br />

Siemens SIP 4.2 · 08/99 9


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Communication<br />

Digital communication<br />

With respect to communication,<br />

particular emphasis is<br />

placed on the customer requirements<br />

in energy automation:<br />

− Every data item is timestamped<br />

at the source, i.e.<br />

where it originates.<br />

− The communication system<br />

automatically handles<br />

the transfer of large data<br />

blocks (e.g. fault recordings<br />

or parameter data<br />

files). The user has access<br />

to these features without<br />

any additional programming<br />

ef<strong>for</strong>t.<br />

− For the safe execution of a<br />

control command the corresponding<br />

data telegram<br />

is initially acknowledged by<br />

the device which will execute<br />

the command. After<br />

the release and execution<br />

of the command a feedback<br />

signal is generated.<br />

At every stage of the control<br />

command execution<br />

particular conditions are<br />

checked. If these are not<br />

satisfied, command execution<br />

may be terminated in a<br />

controlled manner.<br />

Local PC interface<br />

The PC interface accessible<br />

from the front of the unit permits<br />

quick access to all parameters<br />

and fault event data.<br />

The use of the DIGSI 4 operating<br />

program is particularly<br />

advantageous during commissioning.<br />

Remote relay interface (**)<br />

Most pilot- (tele-) protection<br />

schemes could be implemented<br />

using digital serial communication.<br />

The <strong>7SA522</strong> is<br />

capable of remote relay<br />

communication via direct<br />

links or multiplexed digital<br />

communication networks.<br />

Safe bus architecture <strong>for</strong><br />

substation control<br />

interface<br />

RS485 bus<br />

With this data transmission<br />

via copper conductors,<br />

electromagnetic fault influences<br />

are largely eliminated<br />

(*) available with next firmware release<br />

(**) in preparation<br />

1) Optical Link Module<br />

by the use of twisted-pair<br />

conductors. Upon failure of<br />

a unit, the remaining system<br />

continues to operate<br />

without any problem.<br />

Fiber optic double ring<br />

circuit<br />

The fiber optic double ring<br />

circuit is almost immune to<br />

electromagnetic interference.<br />

Upon failure of a section<br />

between two units, the<br />

communication system continues<br />

to operate without<br />

disturbance. It is generally<br />

impossible to communicate<br />

with a unit that has failed. If<br />

a unit were to fail, there is<br />

no effect on the communication<br />

with the rest of the<br />

system.<br />

Retrofitting: Modules <strong>for</strong><br />

every type of communication<br />

Communication modules are<br />

available <strong>for</strong> the entire<br />

<strong>SIPROTEC</strong> 4 unit range. This<br />

ensures that a range of communication<br />

protocols can be<br />

used. No external converter<br />

is required.<br />

IEC 60870-5-103<br />

IEC 60870-5-103 is an internationally<br />

standardized protocol<br />

<strong>for</strong> efficient communication<br />

with protection relays. IEC<br />

60870-5-103 is supported by<br />

a number of protection device<br />

manufacturers and is<br />

used world-wide.<br />

PROFIBUS-FMS (*)<br />

PROFIBUS-FMS is an internationally<br />

standardized communication<br />

system (EN 50170)<br />

<strong>for</strong> communication problem<br />

solving. Profibus is supported<br />

internationally by several<br />

hundred manufacturers and<br />

has to date been used in<br />

more than 1,000,000 applications<br />

all over the world.<br />

Connection to a SIMATIC<br />

S5/S7 programmable controller<br />

is made on the basis of<br />

the data obtained (e.g. fault<br />

recording, fault data, measured<br />

values and control functionality)<br />

via the SICAM<br />

energy automation system.<br />

Figure 14<br />

IEC 60870-5-103 star type RS232 copper conductor connection or fiber<br />

optic connection<br />

Figure 15<br />

Profibus: Optical double ring circuit<br />

OLM 1)<br />

Figure 16<br />

Profibus: RS485 copper conductor connection<br />

10 Siemens SIP 4.2 · 08/99


Communication<br />

Profibus DP (*)<br />

Profibus DP is an industrial<br />

communications standard<br />

and is supported by a<br />

number of PLC and protection<br />

device manufacturers.<br />

Modbus RTU (*)<br />

Modbus RTU is a recognized<br />

industrial communications<br />

standard and is supported by<br />

a number of PLC and protection<br />

device manufacturers.<br />

DNP 3.0 (*)<br />

DNP 3.0 (Distributed Network<br />

Protocol version 3) is a<br />

communications protocol<br />

based on messages. The<br />

<strong>SIPROTEC</strong> 4 units are fully<br />

Level 1 and Level 2 compliant<br />

with DNP 3.0. DNP 3.0 is<br />

supported by a number of<br />

protection device manufacturers.<br />

Figure 17<br />

Optical fiber communication module<br />

Ethernet UCA (**)<br />

UCA (Utility Communications<br />

Architecture) is a developing<br />

communications protocol<br />

specifically designed <strong>for</strong> substation<br />

automation. When it<br />

becomes an international<br />

standard, the <strong>SIPROTEC</strong> 4<br />

units are prepared to support<br />

it. Simply plug in a new communication<br />

module.<br />

Figure 18<br />

RS232/RS485 electrical communication module<br />

Figure 19<br />

Fiber optical double ring communication module<br />

(*) available with next firmware release<br />

(**) in preparation<br />

Siemens SIP 4.2 · 08/99 11


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Functions<br />

<strong>Distance</strong> protection<br />

(ANSI 21, 21N)<br />

Full-scheme design<br />

The main function of the<br />

<strong>7SA522</strong> is a full-scheme distance<br />

protection. By parallel<br />

calculation and monitoring of<br />

all six impedance loops a<br />

high degree of sensitivity and<br />

selectivity is achieved <strong>for</strong> all<br />

types of faults. The shortest<br />

tripping time is less than one<br />

cycle. Single- and three- pole<br />

tripping is possible.<br />

MHO and quadrilateral<br />

characteristics<br />

The <strong>7SA522</strong> relay provides<br />

quadrilateral as well as MHO<br />

zone characteristics. Both<br />

characteristics can be used<br />

separately <strong>for</strong> phase and<br />

ground faults. Resistance<br />

ground faults can <strong>for</strong> instance<br />

be covered with the<br />

quadrilateral characteristic<br />

and phase faults with the<br />

mho characteristic.<br />

Load bias<br />

In order to guarantee a reliable<br />

discrimination between<br />

load operation and short circuit<br />

– especially on long high<br />

loaded lines – the relay is<br />

equipped with a selectable<br />

load encroachment characteristic.<br />

Impedances within this<br />

load encroachment characteristic<br />

will prevent the distance<br />

zones from unwanted<br />

tripping.<br />

Absolute phase-selectivity<br />

The <strong>7SA522</strong> distance protection<br />

incorporates a well proven<br />

highly sophisticated phase<br />

selection algorithm. The<br />

pickup of unfaulted loops is<br />

eliminated to prevent the<br />

adverse influence of currents<br />

and voltages in the fault free<br />

loops. This phase selection<br />

algorithm achieves single<br />

pole tripping and correct distance<br />

measurement in a<br />

wide application range.<br />

Parallel line compensation<br />

The influence of wrong distance<br />

measurement due to<br />

parallel lines can be compensated<br />

by feeding the neutral<br />

current of the parallel line to<br />

the relay. Parallel line compensation<br />

can be used <strong>for</strong> distance<br />

protection as well as<br />

<strong>for</strong> the fault locator.<br />

6 zone packages<br />

Five independent distance<br />

zones and one separate<br />

overreach zone <strong>for</strong> zone<br />

extension schemes are<br />

available. Each distance zone<br />

has separate time stages,<br />

partly valid <strong>for</strong> single phase<br />

or multi-phase faults.<br />

Ground faults are detected<br />

by monitoring the neutral<br />

current 3I 0 and the zero sequence<br />

voltage 3V 0 .<br />

Quadrilateral<br />

The quadrilateral tripping<br />

characteristic permits separate<br />

setting of the reactance<br />

X and the resistance R. The<br />

resistance section R can be<br />

set separately <strong>for</strong> faults with<br />

and without ground involvement.<br />

This characteristic has<br />

there<strong>for</strong>e an optimal per<strong>for</strong>mance<br />

in case of faults with<br />

fault resistance. The distance<br />

zones can be set <strong>for</strong>ward, reverse<br />

or non-directional.<br />

Sound phase polarization and<br />

voltage memory provides a<br />

dynamically unlimited directional<br />

sensitivity.<br />

MHO<br />

The mho tripping characteristic<br />

provides sound phase respectively<br />

memory polarization<br />

<strong>for</strong> all distance zones.<br />

The example in figure 21<br />

shows the characteristic <strong>for</strong> a<br />

<strong>for</strong>ward fault where the mho<br />

circle expands to the source<br />

impedance but never more<br />

than the selected impedance<br />

reach. This mho circle expansion<br />

guarantees safe and selective<br />

operation <strong>for</strong> all types<br />

of faults even <strong>for</strong> close-in<br />

faults.<br />

Insensitive to measuring<br />

value distortion<br />

Digital filtering of the<br />

measured values makes the<br />

protection unit insensitive to<br />

disturbances in the measured<br />

quantities. In particular<br />

the influence of DC components,<br />

capacitive voltage<br />

trans<strong>for</strong>mers and frequency<br />

changes are reduced.<br />

reverse<br />

Load<br />

<strong>for</strong>wards<br />

Z3<br />

Figure 21<br />

<strong>Distance</strong> protection: MHO characteristic<br />

X<br />

ϕ<br />

Line<br />

Z2<br />

Z1B<br />

α<br />

Z1<br />

reverse<br />

Figure 20<br />

<strong>Distance</strong> protection: quadrilateral characteristic<br />

Load<br />

X<br />

Z3 (if revers)<br />

Fuse failure monitoring<br />

The loss of the secondary<br />

V.T. circuit voltage blocks the<br />

distance protection<br />

automatically and prevents<br />

the relay from unwanted<br />

tripping. The secondary V.T.<br />

voltage is supervised by the<br />

integrated fuse failure<br />

monitor. A pickup of the fuse<br />

failure monitor as well as the<br />

ϕ<br />

Z1<br />

Line<br />

Z2<br />

Z4<br />

Z1B<br />

Z5<br />

Z4<br />

Z5<br />

Load<br />

<strong>for</strong>wards<br />

Load<br />

V.T.-mcb binary input block<br />

the distance protection and<br />

can activate the backup<br />

overcurrent protection.<br />

R<br />

R<br />

12 Siemens SIP 4.2 · 08/99


Functions<br />

Fault locator<br />

The integrated fault locator calculates<br />

the fault impedance<br />

and the distance-to-fault. The<br />

result is displayed in ohms, miles,<br />

kilometers or in percent of<br />

the line length. Parallel line and<br />

load current compensation is<br />

also available.<br />

Power swing detection<br />

(ANSI 68, 68T)<br />

Dynamic occurrences, <strong>for</strong> instance<br />

short circuits, load fluctuations,<br />

autoreclosures or<br />

switching operations can cause<br />

power swings in the transmission<br />

network. During power<br />

swings, large currents along<br />

with small voltages can cause<br />

unwanted tripping of distance<br />

protection relays. To avoid uncontrolled<br />

tripping of the distance<br />

protection and to achieve<br />

controlled tripping in the event<br />

of loss of synchronism the<br />

<strong>7SA522</strong> relay is equipped with<br />

an efficient power swing detection<br />

function. Power swings<br />

can be detected under symmetrical<br />

load conditions as well as<br />

during single pole autoreclosures.<br />

Pilot- (Tele-) protection <strong>for</strong><br />

distance protection<br />

(ANSI 85-21)<br />

A pilot protection function is<br />

available <strong>for</strong> fast clearance of<br />

faults up to 100% of the line<br />

length. The following operating<br />

modes may be selected:<br />

− PUTT, permissive underreaching<br />

zone transfer trip<br />

− POTT, permissive overreaching<br />

zone transfer trip<br />

− UNBLOCKING<br />

− BLOCKING<br />

− DUTT, direct underreaching<br />

zone transfer trip (together<br />

with Direct Transfer Trip<br />

function)<br />

The carrier send and receive<br />

signals are available as binary<br />

inputs and outputs and can be<br />

assigned freely to each physical<br />

relay input or output. At<br />

least one channel is required<br />

<strong>for</strong> each direction.<br />

Common transmission channels<br />

are power-line carrier, microwave<br />

radio and fiber-optic<br />

links.<br />

Figure 22<br />

Power swing current and voltage wave <strong>for</strong>ms<br />

A serial remote relay interface<br />

is in preparation <strong>for</strong> direct connection<br />

to a digital communication<br />

network<br />

<strong>7SA522</strong> also permits the transfer<br />

of phase-selective signals.<br />

This function requires three<br />

channels <strong>for</strong> each direction.<br />

This feature is particularly advantageous<br />

as it permits to<br />

execute reliable single-pole tripping,<br />

even if two single-phase<br />

faults occur on different lines.<br />

The transmission methods are<br />

suitable also <strong>for</strong> lines with three<br />

ends (three-terminal lines). Phase-selective<br />

transmission is<br />

also possible with multi-end<br />

applications, if some user specific<br />

linkages are implemented<br />

by way of the integrated CFC<br />

LOGIC. During disturbances in<br />

the transmission receiver or on<br />

the transmission circuit, the pilot<br />

protection function can be<br />

blocked by a binary input signal<br />

without loosing the zone selectivity.<br />

The control of the overreach<br />

zone Z1B (zone extension -<br />

can be switched over to the autoreclosure<br />

function. A transient<br />

blocking function (Current<br />

reversal guard) is provided to<br />

overcome current reversals resulting<br />

from the clearance of<br />

short circuits on parallel lines.<br />

Figure 23<br />

Power swing circle diagram<br />

Direct transfer tripping<br />

There are various conditions<br />

on the power system which<br />

necessitate the remote tripping<br />

of the circuit breaker<br />

from the protection position.<br />

The <strong>7SA522</strong> relay is equipped<br />

with phase-selective intertripping<br />

signal inputs and<br />

outputs.<br />

Siemens SIP 4.2 · 08/99 13


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Functions<br />

Weak infeed protection:<br />

echo and/or trip<br />

(ANSI 27 WI)<br />

To prevent delayed tripping<br />

of permissive schemes<br />

during weak or zero infeed<br />

situations, an echo function<br />

is provided. If no fault<br />

detector is picked up at the<br />

weak infeed end of the line,<br />

the signal received here is<br />

returned as echo to allow<br />

accelerated tripping at the<br />

strong infeed end of the line.<br />

It is also possible to initiate<br />

tripping at the weak infeed<br />

end. A phase-selective 1-pole<br />

or 3-pole trip is issued if a<br />

permissive trip signal (POTT<br />

or Unblocking) is received<br />

and a if the phase-ground<br />

(earth) voltage drops correspondingly.<br />

Directional ground (earth)<br />

fault overcurrent protection<br />

<strong>for</strong> high-resistance<br />

faults<br />

(ANSI 50N, 51N, 67N)<br />

In grounded (earthed) networks<br />

the sensitivity of the<br />

ground distance protection<br />

may not cover ground faults<br />

with high fault resistances.<br />

The <strong>7SA522</strong> protection relay<br />

has there<strong>for</strong>e protection<br />

functions <strong>for</strong> high-resistance<br />

ground faults of this nature.<br />

The ground fault overcurrent<br />

protection can be used with<br />

3 definite time stages and<br />

one inverse time stage<br />

(IDMT). A 4 th definite time<br />

stage can be applied instead<br />

of the one inverse time<br />

stage.<br />

The available ANSI/ IEEE inverse-time<br />

curves are:<br />

• Inverse<br />

• Short inverse<br />

• Long inverse<br />

• Moderately inverse<br />

• Very inverse<br />

• Extremely inverse<br />

• Definite inverse<br />

An additional logarithmic inverse<br />

time characteristic is<br />

also available.<br />

The direction decision is per<strong>for</strong>med<br />

with the neutral current<br />

and the zero sequence<br />

voltage or with the negative<br />

sequence components V2<br />

and I2. In addition or as an<br />

alternative to the directional<br />

determination with zero<br />

sequence voltage, the starpoint<br />

current of a grounded<br />

power trans<strong>for</strong>mer may also<br />

be used <strong>for</strong> polarization. Dual<br />

polarization applications can<br />

there<strong>for</strong>e be fulfilled. Each<br />

overcurrent stage can be set<br />

in <strong>for</strong>ward or reverse direction<br />

or <strong>for</strong> both directions<br />

(non-directional).<br />

As an option the <strong>7SA522</strong><br />

relay can be provided with a<br />

sensitive neutral (residual)<br />

current trans<strong>for</strong>mer. This<br />

feature provides a measuring<br />

range <strong>for</strong> the neutral (residual)<br />

current from 5mA to 100A<br />

with a nominal relay current<br />

of 1A and from 5 mA to 500A<br />

with a nominal relay current<br />

of 5A. Thus the ground fault<br />

overcurrent protection can be<br />

applied with extreme<br />

sensitivity.<br />

The function is equipped<br />

with special digital filter algorithms,<br />

providing the elimination<br />

of higher harmonics.<br />

This feature is particularly important<br />

<strong>for</strong> low zero sequence<br />

fault currents which usually<br />

have a high content of 3 rd<br />

and 5 th harmonic. Inrush stabilization<br />

and instantaneous<br />

switch-onto-fault trip can be<br />

activated separately <strong>for</strong> each<br />

stage as well.<br />

Different operating modes<br />

can be selected. The ground<br />

fault protection may be<br />

blocked during the dead time<br />

of single-pole autoreclose cycles<br />

or during pickup of the<br />

distance protection.<br />

Pilot protection <strong>for</strong><br />

directional ground (earth)<br />

fault protection<br />

(ANSI 85-67N)<br />

The directional ground fault<br />

overcurrent protection can be<br />

combined with one of the following<br />

pilot schemes:<br />

• Directional comparison<br />

• BLOCKING<br />

• UNBLOCKING.<br />

The transient blocking function<br />

(current revresal guard)<br />

is also provided to overcome<br />

current reversals resulting<br />

from the clearance of short<br />

circuits on parallel lines.<br />

The pilot functions <strong>for</strong> distance<br />

protection and <strong>for</strong><br />

ground (earth) fault protection<br />

can use the same signalling<br />

channel or two separate<br />

and redundant channels.<br />

Backup overcurrent<br />

protection<br />

(ANSI 50, 50N, 51, 51N)<br />

The <strong>7SA522</strong> provides a<br />

backup overcurrent protection.<br />

Two definite time<br />

stages and one inverse time<br />

stage (IDMTL) are available,<br />

separately <strong>for</strong> phase currents<br />

and <strong>for</strong> the neutral (residual)<br />

current. Two operating<br />

modes are selectable. The<br />

function can run in parallel to<br />

the distance protection or<br />

only during interruption of<br />

the voltage in the secondary<br />

VT circuit (emergency operation).<br />

The secondary voltage interruption<br />

can be detected by<br />

the integrated Fuse Failure<br />

monitor or via a binary input<br />

Figure 24<br />

Normal inverse<br />

of a VT miniature circuit<br />

breaker (VT m.c.b. trip).<br />

The available ANSI/ IEEE inverse-time<br />

curves are:<br />

• Inverse<br />

• Short inverse<br />

• Long inverse<br />

• Moderately inverse<br />

• Very inverse<br />

• Extremely inverse<br />

• Definite inverse<br />

STUB bus overcurrent<br />

protection<br />

(ANSI 50(N)-STUB)<br />

The STUB bus overcurrent<br />

protection is a separate<br />

definite time overcurrent<br />

stage. It can be activated<br />

from a binary input signalling<br />

the open line isolator (disconnector).<br />

Settings are available <strong>for</strong><br />

phase and ground (earth)<br />

faults.<br />

t =<br />

( I / I<br />

P)<br />

014 .<br />

⋅ T<br />

002 .<br />

P<br />

− 1<br />

14 Siemens SIP 4.2 · 08/99


Functions<br />

Instantaneous high-speed<br />

switch-onto-fault overcurrent<br />

protection<br />

(ANSI 50HS)<br />

Instantaneous tripping is possible<br />

when energizing a faulty<br />

line. On definite large-fault<br />

currents, the high-speed<br />

switch-onto-fault overcurrent<br />

stage can initiate very fast 3-<br />

pole tripping.<br />

With lower fault currents, instantaneous<br />

tripping after<br />

switch-onto-fault is also possible<br />

with the overreach distance<br />

zone Z1B or just with<br />

pickup in any zone.<br />

The switch-onto-fault initiation<br />

can be detected via the<br />

binary input ”manual close”<br />

or automatically via measurement.<br />

Overvoltage protection<br />

(ANSI 59)<br />

Impermissible overvoltages<br />

can occur on long transmission<br />

lines without or with low<br />

load. The <strong>7SA522</strong> protection<br />

relay contains an overvoltage<br />

protection function. Two stages<br />

are available: One phasesegregated<br />

stage and one<br />

zero-sequence voltage stage.<br />

The residual voltage from a<br />

broken-delta VT winding can<br />

be directly measured via the<br />

V4-voltage trans<strong>for</strong>mer input<br />

(Ven-voltage) or can be<br />

calculated internally as 3V 0 .<br />

Tripping can be per<strong>for</strong>med at<br />

the local circuit breaker or at<br />

the remote end of the line by<br />

sending an intertripping signal.<br />

Breaker failure protection<br />

(ANSI 50BF)<br />

The <strong>7SA522</strong> relay incorporates<br />

a two-stage circuit-breaker<br />

failure protection to detect<br />

failures of tripping commands<br />

execution, <strong>for</strong> example<br />

due to a defective circuitbreaker.<br />

The current detection<br />

logic is phase-segregated<br />

and can there<strong>for</strong>e also be<br />

used in single-pole tripping<br />

schemes. If the fault current<br />

has not been interrupted after<br />

a settable time delay is<br />

expired, a retrip command or<br />

the busbar trip command is<br />

generated. The breaker failure<br />

protection can be initiated<br />

by all integrated protection<br />

functions as well as by external<br />

devices via binary input<br />

signals.<br />

Automatic reclosing<br />

(ANSI 79)<br />

The <strong>7SA522</strong> relay is equipped<br />

with an automatic reclosing<br />

function (AR). The function<br />

includes several operating<br />

modes:<br />

• 3-pole auto reclosing <strong>for</strong> all<br />

types of faults; different<br />

dead times are available depending<br />

the type of fault<br />

• 1-pole auto reclosing <strong>for</strong> 1-<br />

phase faults, no reclosing<br />

<strong>for</strong> multi-phase faults<br />

• 1-pole auto reclosing <strong>for</strong> 1-<br />

phase faults and <strong>for</strong> 2-phase<br />

faults without earth, no -<br />

reclosing <strong>for</strong> multi-phase<br />

faults<br />

• 1-pole auto reclosing <strong>for</strong> 1-<br />

phase and 3-pole auto reclosing<br />

<strong>for</strong> multi-phase faults<br />

• 1-pole auto reclosing <strong>for</strong> 1-<br />

phase faults and 2-phase<br />

faults without earth and 3-<br />

pole auto reclosing <strong>for</strong> other<br />

faults<br />

• Multiple-shot auto reclosing<br />

• Interaction with an external<br />

device <strong>for</strong> automatic reclosing<br />

via binary inputs and<br />

outputs<br />

• Control of the integrated AR<br />

function by external protection<br />

• Interaction with the internal<br />

or an external synchronism<br />

check<br />

• Monitoring of the circuitbreaker<br />

auxiliary contacts<br />

• Voltage check <strong>for</strong> discrimination<br />

between successful<br />

and non-successful reclose<br />

attempts<br />

In addition to the above mentioned<br />

operating modes, several<br />

other operating principles<br />

can be per<strong>for</strong>med by<br />

means of the integrated programmable<br />

logic (CFC).<br />

Synchronism check<br />

(ANSI 25)<br />

The synchronism and voltage<br />

check function will ensure<br />

that the stability of the network<br />

will not be endangered<br />

when a line is switched onto<br />

a busbar. For this purpose a<br />

synchronism check function<br />

is provided. After verification<br />

of the network synchronism<br />

the function enables the<br />

CLOSE command. Alternatively<br />

reclosing can be enabled<br />

<strong>for</strong> different criteria, e.g.<br />

checking that the busbar or<br />

line is not carrying a voltage<br />

(dead line or dead bus).<br />

Fuse-failure monitoring<br />

and other supervision<br />

functions<br />

The <strong>7SA522</strong> relay provides<br />

comprehensive monitoring<br />

functions covering both hardware<br />

and software. Furthermore,<br />

the measured values<br />

are continuously checked <strong>for</strong><br />

plausibility. Thus the current<br />

and voltage trans<strong>for</strong>mers are<br />

also included in this monitoring<br />

system.<br />

If any measured voltage is<br />

not present due to short circuit<br />

or conductor breakage in<br />

the voltage trans<strong>for</strong>mer secondary<br />

circuit the distance<br />

protection would react in an<br />

unwanted trip due to this<br />

loss of voltage. This secondary<br />

voltage interruption can be<br />

detected by means of the integrated<br />

Fuse-failure monitor.<br />

Immediate blocking of distance<br />

protection and switching<br />

to the backup-emergency<br />

overcurrent protection<br />

is provided <strong>for</strong> all types of secondary<br />

voltage failures.<br />

Additional measurement supervision<br />

functions are<br />

• Balance of voltages and currents<br />

• Broken-conductor supervision<br />

• Summation of currents and<br />

voltages<br />

• Phase-sequence supervision<br />

Trip circuit supervision<br />

(ANSI 74TC)<br />

One or two binary inputs <strong>for</strong><br />

each circuit breaker pole can<br />

be used <strong>for</strong> monitoring the<br />

circuit-breaker trip coils including<br />

the connecting cables.<br />

An alarm signal is issued<br />

whenever the circuit is interrupted.<br />

Lockout (ANSI 86)<br />

A given tripping command<br />

can be held until it is reset<br />

via a binary input. Thereby<br />

the circuit breaker can be<br />

locked to prevent restarting<br />

until the cause of the disturbance<br />

is clarified. The lockout<br />

state can be removed by<br />

conscious manual resetting.<br />

A prerequisite is that the<br />

close coil — as usual — at<br />

the circuit breaker is locked<br />

with pending tripping command.<br />

Siemens SIP 4.2 · 08/99 15


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Functions<br />

Measured values<br />

The RMS values are<br />

calculated from the acquired<br />

current and voltage signals<br />

along with the power factor,<br />

the frequency, the real and<br />

reactive power. Measured<br />

values are displayed as primary<br />

or secondary values or<br />

in percent of the specific line<br />

nominal current and voltage.<br />

The following values are<br />

available <strong>for</strong> measured value<br />

processing:<br />

• Currents 3x I phase ,3I 0 , I G ,<br />

3I0 par<br />

• Voltages 3x V phase-ground ,3x<br />

V phase-phase ,3V 0 ,V en ,V sync<br />

• Symmetrical components<br />

I 1 , I 2 ,V 1 ,V 2<br />

• Real power P (Watt),<br />

Reactive power Q (Var),<br />

Apparent power S (VA)<br />

• Power factor PF (= cosϕ)<br />

• Frequency f<br />

• Load (in service) impedances,<br />

primary and secondary<br />

3x (R phase-ground ,X phase-ground ) ,<br />

3x (R phase-phase ,X phase-phase )<br />

• Limit-value monitoring<br />

Limit values are monitored<br />

by means of the CFC. Commands<br />

can be derived from<br />

this limit value indication.<br />

Commissioning and test<br />

functions<br />

Special attention has been<br />

paid to commissioning. All binary<br />

inputs and outputs can<br />

be displayed and set directly.<br />

This can simplify the wiring<br />

check process significantly<br />

<strong>for</strong> the user.<br />

The measured values can be<br />

displayed via DIGSI 4 on the<br />

PC screen as primary, secondary<br />

and/or percentage values<br />

simultaneously. This provides<br />

a complete overview of<br />

the actual system conditions.<br />

• The <strong>7SA522</strong> provides a circuit<br />

breaker test function.<br />

Single- and three pole tripping<br />

commands can be generated<br />

manually followed by<br />

a reclosing command. The<br />

pole open time can be set<br />

separately to the auto reclosing<br />

dead time.<br />

4 predefined setting<br />

groups<br />

The settings of the <strong>7SA522</strong><br />

relay can be adapted quickly<br />

to suit changing network<br />

configurations. The relay<br />

includes 4 setting groups<br />

which can be predefined<br />

during commissioning or<br />

even changed by remote via<br />

a DIGSI 4 modem link. The<br />

setting groups can be<br />

activated via binary inputs,<br />

via DIGSI 4 (local or remote),<br />

via the integrated keypad or<br />

via the serial substation<br />

control interface.<br />

Operational measured values are clearly<br />

arranged on the LCD display<br />

Some fault indications are displayed<br />

automtically on the LCD display<br />

Region-specific default<br />

settings<br />

The <strong>SIPROTEC</strong> 4 relays<br />

<strong>7SA522</strong> can be supplied in<br />

regional versions. The user<br />

purchases only the functions<br />

required. The available functions<br />

are matched to the technical<br />

requirements of the regions<br />

(see table).<br />

Function Region World Region US Region GE<br />

Frequency<br />

50 Hz/60 Hz<br />

Line length<br />

km/miles<br />

Inverse-time characteristic<br />

<strong>for</strong> backup overcurrent<br />

preset to 50 Hz preset to 60 Hz preset to 50 Hz<br />

preset to km preset to miles preset to km<br />

IEC, ANSI 1)<br />

preset to IEC<br />

ANSI 1)<br />

IEC<br />

Inverse-time characteristic<br />

<strong>for</strong> ground (earth) overcurrent<br />

IEC, ANSI 1) , ANSI 1)<br />

Logarithmic inverse<br />

preset to IEC<br />

IEC<br />

STUB-Bus overcurrent stage –<br />

1)<br />

Disc-emulation with inverse time characteristic is generally combined with ANSI curves<br />

16 Siemens SIP 4.2 · 08/99


Control and automatic functions<br />

Control<br />

In addition to the protection<br />

functions, the <strong>SIPROTEC</strong> 4<br />

units also support all control<br />

and monitoring functions required<br />

<strong>for</strong> operating mediumvoltage<br />

or high-voltage substations.<br />

The main application<br />

is reliable control of<br />

switching and other processes.<br />

The status of primary<br />

equipment or auxiliary devices<br />

can be obtained from<br />

auxiliary contacts and communicated<br />

to the <strong>7SA522</strong> via<br />

binary inputs. There<strong>for</strong>e it is<br />

possible to detect and indicate<br />

both the OPEN and<br />

CLOSED position or a faulty<br />

or intermediate circuit-breaker<br />

or auxiliary contact position.<br />

The switchgear or circuit-breaker<br />

can be controlled<br />

via:<br />

− integrated operator panel<br />

− binary inputs<br />

− substation control system<br />

− DIGSI 4.<br />

Automation<br />

With the integrated logic, the<br />

user can set specific functions<br />

<strong>for</strong> the automation of<br />

the switchgear or substation<br />

by means of a graphic interface<br />

(CFC). Functions are activated<br />

by means of function<br />

keys, binary inputs or via the<br />

communication interface.<br />

Switching authority<br />

The following hierarchy of<br />

switching authority is applicable:<br />

”LOCAL”, DIGSI 4 PC<br />

program, ”REMOTE”. The<br />

switching authority is determined<br />

according to parameters<br />

or by DIGSI 4. If the<br />

”LOCAL” mode is selected,<br />

only local switching operations<br />

are possible. Every<br />

switching operation and<br />

change of breaker position is<br />

stored in the status indication<br />

memory. The switch<br />

command source, switching<br />

device, cause (i.e. spontaneous<br />

change or command)<br />

and result of a switching<br />

operation are retained.<br />

Command processing<br />

The <strong>7SA522</strong> offers all functions<br />

required <strong>for</strong> command<br />

processing, including the<br />

processing of single and<br />

double commands with or<br />

without feedback as well as<br />

sophisticated monitoring of<br />

the control hardware and<br />

software. Control actions<br />

using functions such as runtime<br />

monitoring and automatic<br />

command termination<br />

after output check of the external<br />

process are also provided<br />

by <strong>7SA522</strong>. Typical<br />

applications are:<br />

• Single and double commands<br />

using 1, 1 plus 1<br />

common or 2 trip contacts<br />

• User-definable bay interlocks<br />

• Operating sequences combining<br />

several switching<br />

operations such as control<br />

of circuit-breakers, isolators<br />

(disconnector switches) and<br />

earthing switches<br />

• Derived triggering of switching<br />

operations, indications<br />

or alarms by logical combination<br />

of existing in<strong>for</strong>mation.<br />

Assignment of command<br />

feedback<br />

The positions of the circuitbreaker<br />

or switching devices<br />

are captured by feedback.<br />

These indication inputs are<br />

logically assigned to the corresponding<br />

command outputs.<br />

The unit can there<strong>for</strong>e<br />

distinguish whether the indication<br />

changes as a consequence<br />

of switching operation<br />

or due to a spontaneous<br />

change of state (intermediate<br />

position).<br />

Figure 25<br />

Chatter disable<br />

The chatter disable feature<br />

evaluates whether the number<br />

of status changes of an<br />

indication input exceeds a<br />

specified figure in a configured<br />

period of time. If so, the<br />

indication input is blocked <strong>for</strong><br />

a certain period, so that the<br />

event list will not record excessive<br />

operations.<br />

Filter time<br />

All binary control indications<br />

can be subjected to a filter<br />

time (indication delay) to<br />

prevent spurious operation.<br />

Indication filtering and<br />

delay<br />

Indications can be filtered or<br />

delayed. Filtering serves to<br />

suppress brief changes at<br />

the indication input. The indication<br />

is passed on only if<br />

the indication voltage is still<br />

present after a set period of<br />

time. In the case of indication<br />

delay, there is a delay <strong>for</strong> a<br />

preset time. The in<strong>for</strong>mation<br />

is passed on only if the indication<br />

voltage is still present<br />

after this time.<br />

Indication derivation<br />

A further indication (or a<br />

command) can be derived<br />

from an existing indication.<br />

Group indications can also be<br />

<strong>for</strong>med. The volume of in<strong>for</strong>mation<br />

to the system interface<br />

can thus be reduced and<br />

restricted to the most important<br />

signals.<br />

Data transmission lockout<br />

A data transmission lockout<br />

can be activated, so as to<br />

prevent transfer of in<strong>for</strong>mation<br />

to the control center<br />

during work on a circuit bay.<br />

Test mode<br />

During commissioning a test<br />

mode can be selected; all<br />

indications then have a test<br />

mode suffix <strong>for</strong> transmission<br />

to the control system.<br />

Siemens SIP 4.2 · 08/99 17


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Typical connections<br />

Typical connection of<br />

current and voltage<br />

trans<strong>for</strong>mers<br />

The typical AC connection has<br />

3 phase current trans<strong>for</strong>mers<br />

and 3 phase-ground (earth)<br />

voltage trans<strong>for</strong>mers. The<br />

neutral (residual) current (I N =<br />

3I 0 ) is measured via the I4-<br />

current trans<strong>for</strong>mer as the<br />

sum of the three phase currents.<br />

The zero sequence voltage<br />

3V 0 is not measured externally<br />

but calculated by the<br />

microprocessor.<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

52<br />

Circuit<br />

breaker<br />

I N<br />

V N<br />

Flush mounting<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

Busbar<br />

I A(L1)<br />

I B(L2)<br />

I C(L3)<br />

V A(L1)<br />

V B(L2)<br />

I 4<br />

V 4<br />

V C(L3)<br />

R13<br />

R14<br />

Line<br />

Figure 26<br />

Voltage trans<strong>for</strong>mer connections:<br />

Separate open<br />

delta trans<strong>for</strong>mer<br />

The three phase-to-ground<br />

(earth) voltage trans<strong>for</strong>mers<br />

are typically connected as illustrated.<br />

The V4 voltage<br />

trans<strong>for</strong>mer measures the<br />

zero sequence voltage 3V 0<br />

(Ven) via a separate VT (open<br />

delta connection). This ensures<br />

an additional voltage supervision.<br />

The V4 trans<strong>for</strong>mer can also<br />

be connected to a separate<br />

voltage trans<strong>for</strong>mer <strong>for</strong> free<br />

assignable voltage measurement<br />

(Vx).<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Circuit<br />

breaker<br />

52<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

V A(L1)<br />

V B(L2)<br />

V C(L3)<br />

V 4<br />

Busbar<br />

Line<br />

Figure 27<br />

18 Siemens SIP 4.2 · 08/99


Typical connections<br />

VT connection to the<br />

busbar<br />

The three phase-to-ground<br />

(earth) voltage trans<strong>for</strong>mers<br />

are connected typically. The<br />

V4 voltage trans<strong>for</strong>mer is connected<br />

to a busbar VT <strong>for</strong> synchronism<br />

check and/or voltage-supervised<br />

automatic reclosing.<br />

Any phase-to-phase<br />

or phase-to-ground (earth) voltage<br />

can be used <strong>for</strong> busbar<br />

voltage sensing.<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Busbar<br />

R15<br />

R16<br />

R17<br />

V A(L1)<br />

V B(L2)<br />

R18<br />

V C(L3)<br />

Circuit<br />

breaker<br />

52<br />

R13<br />

R14<br />

V 4<br />

Line<br />

Figure 28<br />

Mutual parallel line<br />

compensation<br />

The three-phase current trans<strong>for</strong>mers<br />

are typically connected<br />

as illustrated. The I4-CT is<br />

connected to the neutral (residual)<br />

current of the parallel<br />

line <strong>for</strong> mutual parallel line<br />

compensation.<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Busbar<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

I A(L1)<br />

I B(L2)<br />

I C(L3)<br />

I 4<br />

52<br />

Circuit<br />

breaker<br />

52<br />

Circuit<br />

breaker<br />

Line<br />

Parallel line<br />

Figure 29<br />

Siemens SIP 4.2 · 08/99 19


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Typical connections<br />

Additional polarizing <strong>for</strong><br />

directional ground- (earth)<br />

fault protection<br />

The three-phase current trans<strong>for</strong>mers<br />

are typically connected<br />

as illustrated. The I4-CT is<br />

connected as polarizing current<br />

to a grounded (earthed)<br />

power trans<strong>for</strong>mer. This<br />

ensures dual polarization <strong>for</strong><br />

the directional ground- (earth)<br />

fault protection<br />

(ANSI 67N).<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

I A(L1)<br />

I B(L2)<br />

I C(L3)<br />

I 4<br />

Busbar<br />

52<br />

Circuit<br />

breaker<br />

Figure 30<br />

Separate neutral (residual)<br />

current measurement<br />

The three-phase current trans<strong>for</strong>mers<br />

are connected typically.<br />

The starpoint points in<br />

line direction. The I4-CT is<br />

connected to a separate neutral<br />

(residual) current CT, thus<br />

permitting a high sensitive 3I 0<br />

measurement <strong>for</strong> high resistance<br />

ground (earth) faults.<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

I A(L1)<br />

I B(L2)<br />

I C(L3)<br />

Busbar<br />

Note: Terminal Q7 must be<br />

connected to that CT terminal<br />

pointing in the same direction<br />

as the starpoint of the phase<br />

current CTs.<br />

52<br />

Circuit<br />

breaker<br />

Q8 I 4<br />

Flux balancing or<br />

other neutral CT<br />

Figure 31<br />

20 Siemens SIP 4.2 · 08/99


Technical Device Data<br />

Analog input circuits<br />

Rated frequency<br />

Rated current I nom<br />

Rated voltage<br />

Power consumption<br />

in CT circuits with I nom = 1A<br />

in CT circuits with I nom = 5A<br />

in the CT circuit <strong>for</strong> high sensitive ground (earth)<br />

fault protection (refer to ordering code) at 1A<br />

in VT circuits<br />

Thermal overload capability<br />

in CT circuits<br />

in the CT circuit <strong>for</strong> high sensitive ground (earth)<br />

fault protection (refer to ordering code)<br />

in VT circuits<br />

Dynamic overload capability<br />

in CT circuits<br />

in the CT circuit <strong>for</strong> high sensitive earth fault<br />

protection (refer to ordering code)<br />

50Hz or 60Hz (selectable)<br />

1 A or 5 A (selectable)<br />

80 V to 125 V (selectable)<br />

approx. 0.05 VA<br />

approx. 0.30 VA<br />

approx. 0.05 VA<br />

approx. 0.1VA<br />

100 x I Nom <strong>for</strong>1s<br />

30 x I Nom <strong>for</strong> 10 s<br />

4xI Nom continuous<br />

300 A <strong>for</strong> 1 s<br />

100 A <strong>for</strong> 10 s<br />

15 A continuous<br />

230 V continuous per phase<br />

250 x I Nom (one half cycle)<br />

Power Supply<br />

Rated auxiliary voltage<br />

24 V to 48 V DC<br />

60Vto125VDC<br />

110Vto250VDC<br />

and 115 V AC with 50 Hz / 60 Hz<br />

Permitted tolerance of the rated auxiliary voltage -20% to +20%<br />

Max. superimposed AC voltage (peak to peak) ≤ 15%<br />

Power consumption<br />

during normal operation<br />

approx. 8 W<br />

during pickup with all inputs and outputs activated approx. 18 W<br />

Bridging time during auxiliary voltage failure<br />

Vaux ≥ 110 V<br />

≥ 50 ms<br />

Binary Inputs<br />

Quantity<br />

Function can be assigned<br />

Minimum operating voltage<br />

Range is selectable with jumpers <strong>for</strong> each<br />

binary input<br />

Maximum operating voltage<br />

Current consumption, energized<br />

8 or 16 or 24 (refer to ordering code)<br />

17 V or 73 V or 154 V DC, bipolar<br />

(3 operating ranges)<br />

300 V DC<br />

approx. 1.8 mA<br />

Output contacts<br />

Quantity<br />

Function can be assigned<br />

Switching capacity<br />

make<br />

break<br />

break (<strong>for</strong> resistive load)<br />

break (<strong>for</strong> τ = L/R ≤ 50 ms)<br />

Switching voltage<br />

Permissible current<br />

8 or 16 or 24 (refer to ordering code)<br />

1000 W/VA<br />

30 VA<br />

40 W<br />

25 VA<br />

250 V<br />

30 A <strong>for</strong> 0.5 s<br />

5 A continuous<br />

LED displays<br />

Quantity<br />

RUN (green) 1<br />

ERROR (red) 1<br />

Indication (red), function can be assigned 14<br />

Siemens SIP 4.2 · 08/99 21


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Device Data<br />

Mechanical construction<br />

Housing<br />

7XP20<br />

Dimension 1/2 x 19’‘ or 1/1 x 19’‘<br />

refer to ordering code and see dimension drawings<br />

Degree of protection to EN 60 529<br />

For the front of the housing IP 51<br />

For the rear of the housing<br />

flush mounting version IP 50<br />

surface mounting version IP 51<br />

For the terminals<br />

IP 2x with terminal cover put on<br />

Weight<br />

Flush mounting<br />

1/2 x 19‘’ 6 kg<br />

1/1 x 19’‘ 10 kg<br />

Surface mounting<br />

1/2 x 19‘’ 11 kg<br />

1/1 x 19’‘ 19 kg<br />

Serial interface / front of unit<br />

Operating interface 1 <strong>for</strong> DIGSI 4<br />

Connection non isolated, RS 232,<br />

front panel, 9-pin subminiature connector<br />

Baud rate<br />

4800 Baud to 115200 Baud<br />

Serial interfaces / rear of unit<br />

Time synchronization<br />

with IRIG-B signal / DCF77 / SCADA or binary input<br />

impulse<br />

Connection<br />

9-pin subminiature connector<br />

Voltage levels<br />

5 V or 12 V or 24 V<br />

Service interface (refer to ordering code) <strong>for</strong> DIGSI 4 / Modem / Service<br />

(Operating interface 2) Isolated RS232/RS485 9-pin subminiature connector<br />

Dielectric test<br />

500 V/ 50 Hz<br />

<strong>Distance</strong> <strong>for</strong> RS232<br />

max. 15 m<br />

<strong>Distance</strong> <strong>for</strong> RS485<br />

max. 1000 m<br />

Fiber-optic<br />

integrated ST-connector<br />

Optical wavelength<br />

λ=820 nm<br />

Permissible attenuation<br />

max. 8dB <strong>for</strong> glass-fiber 62.5/125µm<br />

<strong>Distance</strong><br />

max. 1.5 km<br />

System interface (refer to ordering code) IEC60870-5-103<br />

Profibus FMS (*)<br />

Profibus DP (*)<br />

Modbus RTU (*)<br />

DNP 3.0 (*)<br />

Isolated RS232/RS485<br />

9-pin subminiature connector<br />

Baud rate<br />

4800 Baud to 38400 Baud<br />

Dielectric test<br />

500 V/50HZ<br />

<strong>Distance</strong> <strong>for</strong> RS232<br />

max. 15 m<br />

<strong>Distance</strong> <strong>for</strong> RS485<br />

max. 1000m<br />

Profibus RS485<br />

Dielectric test<br />

500 V/50Hz<br />

Baud rate<br />

max. 12 MBaud<br />

<strong>Distance</strong><br />

1000 m at 93.75 kBaud; 100 m at 12MBaud<br />

Fiber-optic<br />

integrated ST-connector<br />

single or double ring<br />

Baud rate<br />

max. 1.5 Mbaud<br />

Optical wavelength<br />

λ = 820nm<br />

Permissible attenuation<br />

max. 8dB <strong>for</strong> glass-fiber 62.5/125µm<br />

<strong>Distance</strong><br />

max. 1.5 km<br />

Remote <strong>Relay</strong> interfaces Quantity max. 2 (**)<br />

*) available with next firmware release<br />

**) in preparation<br />

22 Siemens SIP 4.2 · 08/99


Technical Device Data<br />

Electrical tests<br />

Standards<br />

IEC 60255 (product standards)<br />

ANSI/IEEE C37.90.0/.1/.2<br />

UL 508<br />

For further regulations see “Individual functions”<br />

Insulating tests<br />

Standards IEC 60255-5<br />

Voltage test (100% test)<br />

All circuits except <strong>for</strong> auxiliary supply, binary inputs<br />

and communication interfaces<br />

Auxiliary voltage and binary inputs (100% test)<br />

RS485/RS232 rear side communication interfaces<br />

and time synchronization interface (100% test)<br />

Surge voltage test (type test)<br />

All circuits except <strong>for</strong> communication interfaces<br />

and time synchronization interface, class III<br />

2,5 kV (rms.), 50Hz / 60 Hz<br />

3,5 kV DC<br />

500 V (rms.), 50 Hz / 60 Hz<br />

5 kV (peak); 1.2/50 µs; 0.5 J<br />

3 positive and 3 negative surges at intervals of 5 s<br />

EMC tests <strong>for</strong> noise immunity<br />

Standards<br />

IEC 60255-6, 60255-22 (Product standards)<br />

EN 50082-2 (Basic specification)<br />

(Type tests) DIN 57 435 part 303<br />

High frequency test 2.5 kV (peak); 1 MHz; τ = 15 ms; 400 surges per s;<br />

IEC 60255-22-1, class III and DIN 57 435<br />

test duration 2 s<br />

part 303, class III<br />

Discharge of static electricity<br />

8 kV contact discharge; 15 kV air discharge; both<br />

IEC 60255-22-2 class IV<br />

EN 61000-4-2, class IV<br />

polarities; 150 pF; R j = 330 Ω<br />

Exposure to RF field, non modulated<br />

10 V/m; 27 MHz to 500 MHz<br />

IEC 60255-22-3 (report) class III<br />

Exposure to RF field, amplitude-modulated<br />

10 V/m; 80 MHz to 1000 MHz; 80% AM; 1 kHz<br />

IEC 61000-4-3, class III<br />

Exposure to RF field, pulse-modulated<br />

10 V/m; 900 Mhz; repetition frequency 200 Hz;<br />

IEC 61000-4-3/ ENV 50204, class III duty cycle 50 %<br />

Fast transients, Bursts<br />

4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;<br />

IEC 60255-22-4 and<br />

repetition frequency 300 ms; both polarities;<br />

IEC 61000-4-4, class IV<br />

Rj =50Ω; test duration 1 min<br />

High-energy surge voltages (SURGE),<br />

IEC 61000-4-5 installation class III<br />

Auxiliary supply common (longitudinal) mode: 2kV; 12Ω, 9µF<br />

differential(transversal) mode: 1kV; 2Ω, 18µF<br />

Measurements inputs, binary inputs, binary outputs common (longitude) mode: 2kV; 42Ω,0.5µF<br />

differential(transversal) mode: 1kV; 42Ω, 0.5µF<br />

Conducted RF, amplitude-modulated<br />

10 V; 150 kHz to 80 Mhz; 80 % AM; 1kHz<br />

IEC 61000-4-6, class III<br />

Magnetic field with power frequency<br />

30 A/m continuous;<br />

IEC 61000-4-8, class IV<br />

300 A/m <strong>for</strong> 3 s; 50 Hz<br />

IEC 60255-6<br />

0.5 mT; 50 Hz<br />

Oscillatory Surge Withstand Capability<br />

2,5 to 3 kV (peak); 1 to 1,5 Mhz<br />

ANSI/IEEE C37.90.1<br />

damped wave; 50 surges per second;<br />

Duration 2 s; Ri = 150Ω to 200Ω<br />

Fast Transient Surge Withstand Capability<br />

4 kV to 5 kV; 10/150 ns; 50 impulses per second;<br />

ANSI/IEEE C37.90.1 both polarities; Duration 2s;Rj =80Ω<br />

Radiated Electromagnetic Interference<br />

35 V/m; 25 MHz to 1000 Mhz<br />

IEEE C37.90.2<br />

Damped oscillations<br />

2.5 kV (peak value), polarity alternating 100 kHz,<br />

IEC 60894, IEC 61000-4-12<br />

1 Mhz, 10 Mhz and 50 Mhz, Rj = 200Ω<br />

EMC tests <strong>for</strong> interference emission<br />

(Type test)<br />

Standard<br />

EN 50081-1 (Basic specification)<br />

Radio interference voltage on lines,<br />

only auxiliary supply<br />

IEC-CISPR 22<br />

Interference field strenght<br />

IEC-CISPR 22<br />

150kHz to 30 Mhz<br />

class B<br />

30 Mhz to 1000 MHZ<br />

class B<br />

Siemens SIP 4.2 · 08/99 23


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Device Data<br />

Mechanical dynamic tests<br />

Vibration, shock stress and vibration<br />

during earthquake<br />

Standards IEC 60255-21 and IEC 60068-2<br />

Vibration<br />

IEC 60255-21-1, class 2<br />

IEC 60068-2-6<br />

Shock<br />

IEC 60255-21-2, class 1<br />

IEC 60068-2-27<br />

Vibration during earthquake<br />

IEC 60255-21-2, class 1<br />

IEC 60068-3-3<br />

Vibration and shock stress<br />

during transport<br />

Standards IEC 60255-21 and IEC 60068-2<br />

Vibration<br />

IEC 60255-21-1, class 2<br />

IEC 60255-2-6<br />

Shock<br />

IEC 60255-21-2, class 1<br />

IEC 60068-2-27<br />

Repetitive shock<br />

IEC 60255-21-2, class 1<br />

IEC 60068-2-29<br />

sinusoidal<br />

10 Hz to 60 Hz: ±0.075 mm amplitude;<br />

60 Hz to 150 Hz: 1 g acceleration<br />

frequency sweep 1 octave/min<br />

20 cycles in 3 othogonal axes<br />

half-sinusoidal<br />

acceleration 5 g, duration 11 ms, 3 shocks each in<br />

both directions of the 3 axes<br />

sinusoidal<br />

1 Hz to 8 Hz:±3,5 mm amplitude (horizontal axis)<br />

1 Hz to 8 Hz:±1.5 mm amplitude (vertical axis)<br />

8 Hz to 35 Hz: 1g acceleration (horizontal axis)<br />

8 Hz to 35 Hz: 0.5 g acceleration (vertical axis)<br />

frequency sweep 1 octave/min<br />

1 cycle in 3 orthogonal axes<br />

sinusoidal<br />

5 Hz to 8 Hz:±7.5 mm amplitude;<br />

8 Hz to 150 Hz: 2 g acceleration<br />

frequency sweep 1 octave/min<br />

20 cycles in 3 orthogonal axes<br />

half-sinusoidal<br />

acceleration 15 g, duration 11 ms, 3 shocks each<br />

in both directions of the 3 axes<br />

half-sinusoidal<br />

acceleration 10 g, duration 16 ms, 1000 shocks<br />

each in both directions of the 3 axes<br />

Climatic stress tests<br />

Temperatures<br />

Humidity<br />

Temperature during service<br />

-5°C to +55°C<br />

Temporary permissible temperature limit during service -20°C to +70 °C<br />

(The legibility of the display may be affected<br />

above 55°C)<br />

Temperature limit during storage<br />

-25°C to +55°C<br />

Temperature limit during transport<br />

-25°C to +70°C<br />

(Storage and transport with standard factory packaging)<br />

Permissible humidity stress<br />

yearly average ≤ 75% relative humidity; on 56 days<br />

in the year up to 93% relative humidity; moisture<br />

condensation during operation is not permitted<br />

CE con<strong>for</strong>mity<br />

This product is in con<strong>for</strong>mity with the directive of the Con<strong>for</strong>mity is proved by tests that had been<br />

Council of the European Communities on the<br />

per<strong>for</strong>med according to Article 10 of the<br />

approximation of the laws of the member states Council Directive in accordance with the<br />

relating to electromagnetic compatibility generic standards EN 50081 and EN 50082<br />

(EMC Council Directive 89/336/EEC) and concerning (<strong>for</strong> EMC directive) and the standards EN 60255-6<br />

electrical equipment <strong>for</strong> application within specified (<strong>for</strong> low-voltage directive) by Siemens AG.<br />

voltage limits (low-voltage directive 73/23 EEC).<br />

The device is designed in accordance with the<br />

international standards of IEC 60255.<br />

Further applicable standards:<br />

ANSI/IEEE C37.90.0 and C37.90.1<br />

24 Siemens SIP 4.2 · 08/99


Technical Function Data<br />

<strong>Distance</strong> protection – ANSI 21, 21N<br />

Fault locator<br />

<strong>Distance</strong> zones<br />

6, 1 as extended (overreach) zone<br />

all zones may be set <strong>for</strong>ward or/and reverse<br />

or ineffective<br />

Time stages<br />

6 <strong>for</strong> multi-phase faults<br />

3 <strong>for</strong> single-phase faults<br />

Characteristic<br />

(refer to ordering code)<br />

selectable seperately <strong>for</strong> phase and<br />

quadrilateral and/or<br />

ground (earth) faults<br />

MHO<br />

Time range<br />

0.00 to 30 s (step 0.01s) or deactivated<br />

Line angle ϕ L<br />

30° to 89° (step 1°)<br />

Quadrilateral reactance reach X<br />

0.05Ω to 250Ω (1A) / 0.01Ω to 50Ω (5A)<br />

(step 0.01Ω)<br />

Quadrilateral resistance reach R<br />

<strong>for</strong> phase-to-phase faults and<br />

0.05Ω to 250Ω (1A) / 0.01Ω to 50Ω (5A)<br />

phase-to-ground (earth) faults<br />

(step 0.01Ω)<br />

MHO impedance reach ZR<br />

0.05Ω to 200Ω (1A) / 0.01Ω to 40Ω (5A)<br />

(step 0.01Ω)<br />

Minimum phase current I<br />

0.10A to 4A (1A) / 0.50A to 20A (5A)<br />

(step 0.01A)<br />

Ground- (Earth-) fault pickup<br />

Neutral (residual) current 3 I 0<br />

Zero sequence voltage 3V 0<br />

Zero sequence compensation<br />

selectable input <strong>for</strong>mats<br />

Seperately selectable <strong>for</strong> zones<br />

0.05A to 4A (1A) / 0.25A to 20A (5A)<br />

(step 0.01A)<br />

1 to 100V (step 1V) or deactivated<br />

RG/RL and XG/XL<br />

k 0 and ϕ (k 0 )<br />

Z1<br />

higher zones<br />

RG/RL and XG/XL - 0.33 to 7 (step 0.01)<br />

k 0<br />

0 to 4 (step 0.001)<br />

ϕ (k 0 ) -135° to 135°<br />

Parallel line mutual compensation<br />

(refer to ordering code)<br />

RM/RL and XM/XL 0.00 to 8 (step 0.01)<br />

Load encroachment<br />

Minimum load resistance<br />

0.10Ω to 250Ω (1A) / 0.02Ω to 50Ω (5A)<br />

(step 0.01Ω) or deactivated<br />

Maximum load angle 20° to 60° (step 1°)<br />

Directional decision <strong>for</strong> all types of faults<br />

Directional sensitivity<br />

Tolerances<br />

Timer tolerance<br />

Operating times<br />

Minimum trip time<br />

Reset time<br />

with sound phase polarization and/or voltage<br />

memory<br />

dynamically unlimited<br />

<strong>for</strong> sinusodial quantities<br />

∆X<br />

X ≤ 5% <strong>for</strong> 30° ≤ϕ scc ≤ 90°<br />

∆R<br />

R ≤ 5% <strong>for</strong> 0° ≤ϕ scc ≤ 60°<br />

∆Z<br />

Z<br />

≤ 5% <strong>for</strong> -30° ≤(ϕ scc −ϕ line ) ≤+30°<br />

± 1% of set value or 10ms<br />

approx. 17ms at 50Hz<br />

approx. 15ms at 60Hz<br />

approx. 30ms<br />

Output of the distance to fault<br />

X, R (secondary) in Ω<br />

X, R (primary) in Ω<br />

distance in kilometers or miles<br />

distance in % of line length<br />

Start of calculation<br />

with trip, with pickup reset<br />

Reactance per unit length 0.005 to 6.5Ω /km (1A) / 0.001 to 1.3Ω /km (5A) or<br />

0.005 to 10Ω / mile (1A) / 0.001 to 2Ω / mile (5A)<br />

(step 0.001Ω / unit)<br />

Tolerance<br />

<strong>for</strong> sinusodial quantities<br />

≤ 2.5% line length <strong>for</strong> 30° ≤ϕ scc ≤ 90° and<br />

V scc /V N > 0.10<br />

Siemens SIP 4.2 · 08/99 25


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Function Data<br />

Power swing detection – ANSI 68, 68T<br />

Power swing detection principle<br />

Max. detectable power swing frequency<br />

Operating modes<br />

Power swing blocking programs<br />

Detection of faults during power swing blocking<br />

measurement of the rate of impedance vector<br />

change and scanning of the vector course<br />

approx. 7 Hz<br />

power swing blocking and/or<br />

power swing tripping (out of step tripping)<br />

all zones blocked<br />

Z1/Z1B blocked<br />

Z2 to Z5 blocked<br />

Z1, Z1B, Z2 blocked<br />

stop power swing blocking <strong>for</strong> all types of faults<br />

Pilot- (Tele-) protection <strong>for</strong> distance protection – ANSI 85-21<br />

Direct transfer trip<br />

Operating modes<br />

Transient blocking logic<br />

(current reversal guard)<br />

Send and receive signals<br />

Trip time delay<br />

Timer tolerance<br />

POTT<br />

PUTT, DUTT<br />

directional comparison Blocking<br />

directional comparison Unblocking<br />

directional comparison hybrid (POTT and echo<br />

with Weak Infeed protection)<br />

<strong>for</strong> overreaching schemes<br />

suitable <strong>for</strong> 2- and 3- terminal lines<br />

phase segregated signals <strong>for</strong> selective single phase<br />

tripping selectable<br />

0.00 to 30s (step 0.01s) or deactivated<br />

± 1% of set value or 10ms<br />

Ground- (Earth-) fault overcurrent protection – ANSI 50N, 51N, 67N<br />

Characteristic<br />

Inrush restraint<br />

Instantaneous trip after switch-onto-fault<br />

Influence of harmonics<br />

Stages 1 and 2<br />

Stages 3 and 4<br />

3 definite time stages / 1 inverse time stage or<br />

4 definite time stages<br />

Selectable <strong>for</strong> every stage<br />

Selectable <strong>for</strong> every stage<br />

3 rd and higher harmonics are completely<br />

suppressed by digital filtering<br />

2 nd and higher harmonics are completely<br />

suppressed by digital filtering<br />

Definite time ground (earth) Pickup definite time stage 1, 3I 0 0.5A to 25A (1A) / 2.5A to 125A (5A)<br />

overcurrent protection<br />

(step 0.01A)<br />

ANSI 50N Pickup definite time stage 2, 3I 0 0.2A to 25A (1A) / 1A to 125A (5A)<br />

(step 0.01A)<br />

Pickup definite time stage 3, 3I 0<br />

0.05A to 25A (1A) / 0.25A to 125A (5A)<br />

(step 0.01A)<br />

with normal neutral (residual) current CT<br />

(refer to ordering code)<br />

0.003A to 25A (1A) / 0.015A to 125A (5A)<br />

(step 0.01A)<br />

with high sensitive neutral (residual) current CT<br />

(refer to ordering code)<br />

Pickup definite time stage 4, 3I 0<br />

Time delay <strong>for</strong> definite time stages<br />

Tolerances<br />

Current starting<br />

Delay times<br />

Pickup times<br />

Definite time stages 1 and 2<br />

Definite time stages 3 and 4<br />

0.05A to 4A (1A) / 0.25A to 20A (5A)<br />

(step 0.01A)<br />

with normal neutral (residual) current CT<br />

(refer to ordering code)<br />

0.003A to 4A (1A) / 0.015A to 20A (5A)<br />

(step 0.01A)<br />

with high sensitive neutral (residual) current CT<br />

(refer to ordering code)<br />

0.00 to 30s (step 0.01s) or deactivated<br />

≤ 3% of set value or 1% of I nom<br />

± 1% of set value or 10ms<br />

approx. 30ms<br />

approx. 40ms<br />

26 Siemens SIP 4.2 · 08/99


Technical Function Data<br />

Inverse time ground (earth) Current starting 3I 0 0.05A to 4A (1A) / 0.25A to 20A (5A)<br />

overcurrent protection<br />

(step 0.01A)<br />

ANSI 51N<br />

with normal neutral (residual) current CT<br />

(refer to ordering code)<br />

0.003A to 4A (1A) / 0.015A to 20A (5A)<br />

(step 0.01A)<br />

with high sensitive neutral (residual) current CT<br />

(refer to ordering code)<br />

Tripping time characteristics Characteristics normal inverse<br />

according to IEC 60255-3<br />

very inverse<br />

extremely inverse<br />

long time inverse<br />

Time multiplier<br />

T p = 0.05 to 3s (step 0.01s) or deactivated<br />

Pickup threshold<br />

approx. 1.1 x I/I p<br />

Reset threshold<br />

approx. 1.05 x I/I p<br />

Tolerances<br />

Operating time <strong>for</strong> 2 ≤ I/I p ≤ 20<br />

≤ 5% of setpoint ± 15ms<br />

Tripping time characteristics Characteristics inverse<br />

according to ANSI/IEEE<br />

short inverse<br />

long inverse<br />

moderately inverse<br />

very inverse<br />

extremely inverse<br />

definite inverse<br />

Time dial<br />

0.50 to 15 (step 0.01) or deactivated<br />

Pickup threshold<br />

approx. 1.1 x M<br />

Reset threshold<br />

approx. 1.05 x M<br />

Tolerances<br />

Operating time <strong>for</strong> 2 ≤Μ≤20<br />

≤ 5% of setpoint ± 15ms<br />

Tripping time according to<br />

Logarithmic inverse characteristic<br />

Characteristic t[s] = T 3I0p max -T 3I0p ⋅ln 3 I<br />

3<br />

Pickup threshold 1.1 to 4.0 x I/Ip (step 0.1)<br />

0<br />

I<br />

0 p<br />

Directional decision Polarizing quantities <strong>for</strong> directional decision 3I 0 and 3V 0 or<br />

ANSI 67N<br />

3I 0 and 3V 0 and I g (grounded power trans<strong>for</strong>mer) or<br />

3I 2 and 3V 2 (negative sequece)<br />

Zero sequence voltage 3V 0<br />

0.5 to 10V (step 0.1V)<br />

Ground current I g of grounded power trans<strong>for</strong>mer 0.05A to 1A (1A) / 0.25A to 5A (5A) (step 0.01A)<br />

Negative sequence voltage 3V 2<br />

0.5 to 10V (step 0.1V)<br />

Negative sequence current 3I 2<br />

0.05A to 1A (1A) / 0.25A to 5A (5A) (step 0.01A)<br />

Inrush restraint 2 nd harmonic ratio 10 to 45% of fundamental (step 1%)<br />

Maximum current, overriding inrush restraint<br />

0.5A to 25A (1A) / 2.5A to 125A (5A) (step 0.01A)<br />

Siemens SIP 4.2 · 08/99 27


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Function Data<br />

Pilot-(Tele-) protection <strong>for</strong> directional ground-(earth-) fault overcurrent protection – ANSI 85-67N<br />

Operating modes<br />

Transient blocking logic<br />

Send and receive signals<br />

directional comparison Pickup<br />

directional comparison Blocking<br />

directional comparison Unblocking<br />

<strong>for</strong> schemes with parallel lines<br />

suitable <strong>for</strong> 2- and 3- terminal lines<br />

Weak Infeed protection with undervoltage – ANSI 27WI<br />

Operating modes with carrier (signal) reception echo<br />

echo and trip with undervoltage<br />

Undervoltage phase-ground (-earth) 2V to 70V (step 1V)<br />

Time delay<br />

0.00s to 30s (step 0.01s)<br />

Echo impulse<br />

0.00s to 30s (step 0.01s)<br />

Tolerances<br />

Voltage threshold ≤ 5% of set value or 0.5V<br />

Timer<br />

± 1% of set value or 10ms<br />

Backup overcurrent protection – ANSI 50(N), 51(N)<br />

Operating modes<br />

Characteristic<br />

Instantaneous trip after switch-onto-fault<br />

active only with loss of VT secondary circuit<br />

always active<br />

2 definite time stages / 1 inverse time stage<br />

selectable <strong>for</strong> every stage<br />

Definite time overcurrent Pickup definite time stage 1, phase current 0.1A to 25A (1A) / 0.5A to 125A (5A)<br />

protection<br />

(step 0.01A)<br />

ANSI 50, 50N Pickup definite time stage 1, neutral (residual) 0.05A to 25A (1A)<br />

/ 0.25A to 125A (5A)<br />

current<br />

(step 0.01A)<br />

Pickup definite time stage 2, phase current<br />

0.1A to 25A (1A) / 0.5A to 125A (5A)<br />

(step 0.01A)<br />

Pickup definite time stage 2, neutral (residual)<br />

0.05A to 25A (1A) / 0.25A to 125A (5A)<br />

current<br />

(step 0.01A)<br />

Time delay <strong>for</strong> definite time stages<br />

0.00 to 30s (step 0.01s) or deactivated<br />

Tolerances<br />

Current starting<br />

≤ 3% of set value or 1% of I nom<br />

Delay times<br />

± 1% of set value or 10ms<br />

Operating time<br />

approx. 25ms<br />

Inverse time overcurrent Phase current starting 0.1A to 4A (1A) / 0.5A to 20A (5A)<br />

protection<br />

(step 0.01A)<br />

ANSI 51, 51N Neutral (residual) current starting 0.05A to 4A (1A) / 0.5A to 20A (5A)<br />

(step 0.01A)<br />

Tripping time characteristics Characteristics normal inverse<br />

according to IEC 60255-3<br />

very inverse<br />

extremely inverse<br />

long time inverse<br />

Time multiplier<br />

T p = 0.05 to 3s (step 0.01s) or deactivated<br />

Pickup threshold<br />

approx. 1.1 x I/I p<br />

Reset threshold<br />

approx. 1.05 x I/I p<br />

Tolerances<br />

Operating time <strong>for</strong> 2 ≤ I/I p ≤20<br />

≤ 5% of setpoint ±15ms<br />

28 Siemens SIP 4.2 · 08/99


Technical Function Data<br />

Tripping time characteristics Characteristics inverse<br />

according to ANSI/IEEE<br />

short inverse<br />

long inverse<br />

moderately inverse<br />

very inverse<br />

extremely inverse<br />

definite inverse<br />

Time dial<br />

0.50 to 15 (step 0.01) or deactivated<br />

Pickup threshold<br />

approx. 1.1 x M<br />

Reset threshold<br />

approx. 1.05 x M<br />

Tolerances<br />

Operating time <strong>for</strong> 2 ≤ M ≤ 20<br />

≤ 5% of setpoint ±15ms<br />

STUB bus overcurrent protection – ANSI 50(N)-STUB<br />

Operating modes<br />

Characteristic<br />

Instantaneous trip after switch-onto-fault<br />

Pickup phase current<br />

Pickup neutral (residual) current<br />

active only with open isolator position<br />

(signalled via binary input)<br />

1 definite time stage<br />

selectable<br />

0.1A to 25A (1A) / 0.5A to 125A (5A)<br />

(step 0.01A)<br />

0.05A to 25A (1A) / 0.25 to 125A (5A)<br />

(step 0.01A)<br />

Time delay, separate <strong>for</strong> phase and<br />

0.00 to 30s (step 0.01s) or deactivated<br />

ground (earth) stage<br />

Reset ratio approx. 0.95<br />

Tolerances<br />

Current starting<br />

≤ 3% of set value or 1% of I nom<br />

Delay times<br />

± 1% of set value or 10ms<br />

Instantaneous high speed switch-onto-fault overcurrent protection – ANSI 50HS<br />

Operating mode<br />

active only after CB closing; instantaneous<br />

trip after pickup<br />

Pickup current<br />

1A to 25A (1A) / 5A to 125A (5A)<br />

(step 0.01A)<br />

Reset ratio approx. 0.95<br />

Tolerances<br />

Current starting<br />

≤ 3% of set value or 1% of I nom<br />

Operating time<br />

approx. 13ms<br />

Overvoltage protection – ANSI 59<br />

Measured quantities<br />

3 phase-ground (-earth) voltages and<br />

zero sequence voltage 3V 0<br />

(zero sequence voltage can be measured via<br />

separate VT or can be calculated internally)<br />

Operating modes<br />

local trip and/or<br />

carrier trip impulse <strong>for</strong> remote end trip<br />

Pickup phase-ground (-earth) voltage<br />

1V to 170V (step 0.1V)<br />

Pickup zero sequence voltage 3V 0<br />

1V to 300V (step 0.1V)<br />

Trip time delay, separate <strong>for</strong> phase-ground<br />

0.00 to 30s (step 0.01s) or deactivated<br />

(-earth) and zero sequence voltage<br />

Carrier send impulse<br />

0.05s to 0.5s (step 0.01s)<br />

Reset ratio 0.95<br />

Tolerances<br />

Pickup<br />

≤ 3% of set value or 1V<br />

Timers<br />

± 1% of set value or 10ms<br />

Operating time<br />

phase-ground (earth) voltage<br />

approx. 30ms<br />

zero sequence voltage<br />

approx. 65ms<br />

Siemens SIP 4.2 · 08/99 29


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Function Data<br />

Breaker failure protection – ANSI 50BF<br />

Number of stages 2<br />

Current start<br />

0.1A to 4A (1A) / 0.5A to 20A (5A) (step 0.01A)<br />

Delay time<br />

0.05 to 1s (step 0.01s)<br />

Shortest release time<br />

approx. 10ms<br />

Timer tolerance<br />

± 1% of setting value or 10ms<br />

Automatic reclosure – ANSI 79<br />

Synchronism check – ANSI 25<br />

Number of automatic reclosures up to 8<br />

Program<br />

only 1-pole<br />

only 3-pole<br />

1 or 3-pole<br />

Voltage check<br />

discrimination between successful and<br />

non-successful reclose attempts<br />

Action times<br />

0.01 to 30 s (step 0.01s)<br />

Dead times<br />

0.01 to 1800 s (step 0.01s)<br />

Reclaim times<br />

0.5 to 30 s (step 0.01s)<br />

CLOSE command duration<br />

0.01 to 30 s (step 0.01s)<br />

Timer tolerance<br />

± 1% of setting value or 10ms<br />

Operating modes<br />

Line dead / busbar dead V 1 /V 2 <<br />

Synchronism V 1 >/V 2 ><br />

Permissible voltage difference 1 to 50 V (step 1V)<br />

Permissible frequence difference<br />

0.01 to 1 Hz (step 0.01 Hz)<br />

Permissible angle difference 1 to 60° (step 1)<br />

Supervision time<br />

0.01 to 30 s (step 0.01s)<br />

30 Siemens SIP 4.2 · 08/99


Technical Function Data<br />

Operational measured values<br />

Currents<br />

primary, secondary and percent<br />

3xI phase<br />

3I 0 , I 1 , I 2 , I G ,3I 0par<br />

Tolerances<br />

10 to 50% V nom typically ≤1% of 50% V nom<br />

50 to 200%V nom typically ≤1% of measured value<br />

Voltages<br />

primary, secondary and percent<br />

3xV phase-ground, 3xV phase-phase<br />

3V 0 ,V 1 ,V 2 ,V SYNC ,V en<br />

Tolerances<br />

10 to 50% I nom typically ≤1% of 50% I nom<br />

50 to 200% I nom<br />

typically ≤1% of measured value<br />

Power and direction of power flow<br />

primary and percent<br />

P, real power in W<br />

Q, reactive power in Var<br />

S, apparent power in VA<br />

Frequency<br />

f<br />

Power factor<br />

PF<br />

Load impedances with direction<br />

primary and secondary<br />

3x(R phase-ground ,X phase-ground )<br />

3x(R phase-phase ,X phase-phase )<br />

Tolerances<br />

P: typically ≤ 3%<br />

<strong>for</strong> |cos ϕ| = 0.7 to 1 and<br />

V/V nom , I/I nom = 50 to 120%<br />

Q: typically ≤ 3%<br />

<strong>for</strong> |sin ϕ| = 0.7 to 1 and<br />

V/V nom , I/I nom = 50 to 120%<br />

S: typically ≤ 2%<br />

<strong>for</strong> V/V nom ,I/I nom = 50 to 120%<br />

f: ≤ 20mHz<br />

PF: ≤ 3%<br />

<strong>for</strong> |cos ϕ| = 0.7 to 1<br />

Oscillographic fault recording<br />

Measured analog channels<br />

3 x I phase<br />

,3I 0<br />

,3I 0par<br />

3xV phase ,3V 0 ,V SYNC ,V en<br />

Binary channels<br />

pickup and trip in<strong>for</strong>mation, other signals can be<br />

freely configured<br />

Maximum number of available recordings 8<br />

Sampling interval<br />

20 samples per cycle<br />

Storage time<br />

total of 5s<br />

pre-event and post-event recording time and<br />

event storage time settable<br />

Additional functions<br />

Measurement supervision<br />

current summation<br />

current balance<br />

voltage summation<br />

voltage phase sequence<br />

fuse failure monitor<br />

Annunciations<br />

Event logging buffer length 200<br />

Fault logging<br />

storage of signals of the last 8 faults,<br />

buffer length 200<br />

Switching statistics<br />

phase segregated summation of circuit<br />

breaker operations<br />

summated tripping current per phase<br />

tripping current of the last trip<br />

Circuit breaker test<br />

trip-/close-cycle 3phase<br />

trip-/close-cycle per phase<br />

Setting range<br />

Dead time <strong>for</strong> CB trip-close-cycle<br />

0.00 to 30s (step 0.01s)<br />

Commissioning aids<br />

operational measured values<br />

circuit breaker test<br />

read binary inputs<br />

initiate binary inputs<br />

set binary outputs<br />

set serial interface outputs<br />

Siemens SIP 4.2 · 08/99 31


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Selection and ordering data<br />

Current trans<strong>for</strong>mer<br />

Phase = 1A, Ground (Earth) = 1A (min. = 0.05A) 1<br />

Phase = 1A, Ground (Earth) = high sensitive 1A (min. = 0.005A) 1) 2<br />

Phase = 5A, Ground (Earth) = 5A (min. = 0.25A) 5<br />

Phase = 5A, Ground (Earth) = high sensitive 5A (min. = 0.005A) 1) 6<br />

1) Position 7=2orposition 7=6isnotavailable with Position 14 = K, M, N, Q<br />

Position 7 8 9 10 11 12 13 14 15 16<br />

7<br />

S<br />

A<br />

5<br />

2<br />

2<br />

<br />

7<br />

–<br />

<br />

<br />

<br />

<br />

<br />

–<br />

<br />

<br />

<br />

<br />

Auxiliary Voltage (Power supply, Binary indication voltage)<br />

24V to 48V DC, binary input threshold 17V 2<br />

60V to 125V, binary input threshold 17V 4<br />

110V to 250V DC, 115 V AC, binary input threshold 73V 5<br />

220V to 250V DC, 115V AC, binary input threshold 154V 6<br />

8<br />

Housing and quantity of binary inputs (BI) and outputs (BO)<br />

1/2 x 19’‘, 8 BI, 16 BO, Flush-mounting housing with screw terminals A<br />

1/1 x 19’‘, 16 BI, 24 BO, Flush-mounting housing with screw terminals C<br />

1/1 x 19’‘, 24 BI, 32 BO, Flush-mounting housing with screw terminals D<br />

1/2 x 19’‘, 8 BI, 16 BO, Surface-mounting housing with screw terminals 2) E<br />

1/1 x 19’‘, 16 BI, 24 BO, Surface-mounting housing with screw terminals 2) G<br />

1/1 x 19’‘, 24 BI, 32 BO, Surface-mounting housing with screw terminals 2) H<br />

1/2 x 19’‘, 8 BI, 16 BO, Flush-mounting housing with plug-in terminals J<br />

1/1 x 19’‘, 16 BI, 24 BO, Flush-mounting housing with plug-in terminals L<br />

1/1 x 19’‘, 24 BI, 32 BO, Flush-mounting housing with plug-in terminals M<br />

2) Position 11 =5orposition 11 =6isnotavailable with position 9 = E, G, H<br />

9<br />

Region and operating language<br />

Region GE, language german<br />

Region World, language UK-english<br />

Region US, language US-english<br />

Other languages on request<br />

10<br />

A<br />

B<br />

C<br />

System interface <strong>for</strong> substation control (on rear of device)<br />

No system interface 0<br />

IEC 60870-5-103, electrical RS232 1<br />

IEC 60870-5-103, electrical RS485 2<br />

IEC 60870-5-103, fiber optical 820 nm, ST-connector 3<br />

PROFIBUS FMS Slave, electrical RS485 (*) 4<br />

PROFIBUS FMS, optical fiber, single ring, ST-connector 2) (*) 5<br />

PROFIBUS FMS, optical fiber, double ring, ST-connector 2) (*) 6<br />

Other protocols on request<br />

2) Position 11 =5orposition 11 =6isnotavailable with position 9 = E, G, H<br />

11<br />

Service interface (2 nd operating interface) <strong>for</strong> DIGSI / Modem (on rear of device)<br />

No 2 nd operating interface 0<br />

Electrical RS232 1<br />

Electrical RS485 2<br />

Optical fiber 820nm, ST-connector 3<br />

With remote relay interface (in preparation)<br />

12<br />

*) available with next firmware release<br />

32 Siemens SIP 4.2 · 08/99


Selection and ordering data<br />

Position 13 14 15 16<br />

Trip mode<br />

Trip mode 3pole 0<br />

Trip mode 1- and 3pole 4<br />

<br />

<br />

<br />

<br />

13<br />

<strong>Distance</strong> characteristic (ANSI 21, 21N), Power Swing (ANSI 68)<br />

Parallel Line Compensation<br />

14<br />

Quadrilateral without Power Swing without Parallel Line Comp. C<br />

Quadrilateral and/or MHO without Power Swing without Parallel Line Comp. E<br />

Quadrilateral with Power Swing without Parallel Line Comp.. F<br />

Quadrilateral and/or MHO with Power Swing without Parallel Line Comp. H<br />

Quadrilateral without Power Swing with Parallel Line Comp. 1) K<br />

Quadrilateral and/or MHO without Power Swing with Parallel Line Comp. 1) M<br />

Quadrilateral with Power Swing with Parallel Line Comp. 1) N<br />

Quadrilateral and/or MHO with Power Swing with Parallel Line Comp. 1) Q<br />

1) Position 7=2orPosition 7=6isnotavailable with Position 14 = K, M, N, Q<br />

Autoreclosure (AR, ANSI 79), Synchrocheck (Sync., ANSI 25)<br />

15<br />

Breaker Failure protection (BF, ANSI 50BF), Overvoltage protection (OV, ANSI 59)<br />

Without AR without Sync. without BF without OV A<br />

Without AR without Sync. without BF with OV B<br />

Without AR without Sync. with BF without OV (*) C<br />

Without AR without Sync. with BF with OV (*) D<br />

Without AR with Sync. without BF without OV (*) E<br />

Without AR with Sync. without BF with OV (*) F<br />

Without AR with Sync. with BF without OV (*) G<br />

Without AR with Sync. with BF with OV (*) H<br />

With AR without Sync. without BF without OV (*) J<br />

With AR without Sync. without BF with OV (*) K<br />

With AR without Sync. with BF without OV (*) L<br />

With AR without Sync. with BF with OV (*) M<br />

With AR with Sync. without BF without OV (*) N<br />

With AR with Sync. without BF with OV (*) P<br />

With AR with Sync. with BF without OV (*) Q<br />

With AR with Sync. with BF with OV (*) R<br />

Ground (Earth) Fault Overcurrent protection (ANSI 50N, 51N, 67N)<br />

Without 0<br />

With 4<br />

16<br />

*) available with next firmware release<br />

Siemens SIP 4.2 · 08/99 33


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Accesories<br />

Description Order No. Size of<br />

package<br />

Supplier<br />

Fig<br />

Fig. 32<br />

Mounting rail<br />

<strong>for</strong> 19”rack<br />

Fig. 33<br />

2-pin connector<br />

Fig. 34<br />

3-pin connector<br />

Connector 2-pin<br />

Connector 3-pin<br />

C73334-A1-C35-1<br />

C73334-A1-C36-1<br />

Crimp connector 827039-1<br />

CI2 0.5-1 mm 2<br />

Crimp connector 827396-1<br />

CI2 0.5-1 mm 2<br />

Crimp connector 827040-1<br />

CI2 1-2.5 mm 2<br />

Crimp connector 827397-1<br />

CI2 1-2.5 mm 2<br />

Crimp connector 163083-7<br />

Type III+ 0.75-1.5 mm 2<br />

Crimp connector 163084-2<br />

Type III+ 0.75-1.5 mm 2<br />

Crimping tool <strong>for</strong> Typ III+<br />

Crimping tool <strong>for</strong> CI2<br />

0-169422-1<br />

0-825582-0<br />

1<br />

1<br />

4000<br />

taped on reel<br />

1<br />

4000<br />

taped on reel<br />

1<br />

Siemens<br />

Siemens<br />

AMP 1)<br />

AMP 1)<br />

AMP 1)<br />

AMP 1)<br />

4000 AMP 1)<br />

taped on reel<br />

1<br />

AMP 1)<br />

1<br />

1<br />

AMP 1)<br />

AMP 1)<br />

19”mounting rail C73165-A63-D200-1 Siemens 32<br />

33<br />

34<br />

Short-circuiting links<br />

- <strong>for</strong> current terminals<br />

- all other terminals<br />

Terminal cover<br />

- large<br />

- small<br />

(included)<br />

C73334-A1-C33-1<br />

C73334-A1-C34-1<br />

C73334-A1-C31-1<br />

C73334-A1-C32-1<br />

1<br />

1<br />

1<br />

1<br />

Siemens<br />

Siemens<br />

Siemens<br />

Siemens<br />

35<br />

36<br />

5<br />

5<br />

Fig. 35<br />

Short circuit link <strong>for</strong> current<br />

contacts<br />

Fig. 36<br />

Short circuit link <strong>for</strong> voltage/<br />

signal contacts<br />

1) AMP Deutschland GmbH<br />

Amperesstr. 7-11<br />

D-63225 Langen<br />

Phone:: +49 6103 709-0<br />

Fax +49 6103 709-223<br />

Please check with your local<br />

representative <strong>for</strong> local supplier<br />

Product Description Versions Order Number<br />

DIGSI 4<br />

Software <strong>for</strong> operation and usage<br />

of protection devices of Siemens<br />

MS Windows program, running under MS Windows<br />

NT 4, MS Windows 95<br />

Including device templates, online manual<br />

Professional<br />

7XS5402 – 0AA00<br />

Complete version: Basis version and DIGRA 4, DIGSI REMOTE 4,<br />

SIMATIC CFC 4, Display Editor 4 and Graphic Tools 4 with license<br />

<strong>for</strong> 10 purchase. 1 copper connection cable included<br />

Basis<br />

Complete version with license <strong>for</strong> 10 PCs, 1 copper connection<br />

cable included<br />

7XS5400 – 0AA00<br />

Copper connection cable<br />

Demo version<br />

Functionality of Basis version without the availability of<br />

communication with relays<br />

between PC and relay<br />

(9-pin female to 9-pin male)<br />

7XS5401 – 0AA00<br />

7XV5100-4<br />

Two-channel binary signal transducer<br />

The bidirectional transducer registers binary<br />

in<strong>for</strong>mation at two binary inputs and <strong>for</strong>wards<br />

it via fibre-optic cable to a second transducer,<br />

which outputs the signals via contacts.<br />

<strong>Distance</strong>s of about 3 km can be realized directly<br />

via multimode fibre-optic cables. The repeater<br />

7XV5451 is available <strong>for</strong> distances up to 14 km<br />

via monomode fibre-optic cable. Because of serial<br />

transmission connection can also be made by<br />

standby modem or a digital network via the<br />

asynchronous RS232 interface.<br />

Plastic housing, <strong>for</strong> snap mount on 35 mm DIN EN 50022 rail<br />

Auxiliary voltage supply DC 24 to 250V and AC110 to 220V with<br />

alarm relay<br />

2 binary inputs, 2 trips,<br />

1 alarm relay with potential free contacts<br />

Connector to a second transducer via fibre optic cable with<br />

820nm,<br />

FSMA-plug to connect to the fibre-optic cable 62,5 µm/125 µm<br />

Connection to a second transducer via a communication system<br />

with a RS232 interface, 9-pole. SUB-D socket<br />

7XV5653-0AA00<br />

Instruction Manual <strong>7SA522</strong> V4.00, English C53000-G1176-C119<br />

Instruction Manual <strong>7SA522</strong> V4.00, US English C53000-G1140-C119<br />

<strong>7SA522</strong> Advertising sheet English E50001-U321-A133-X-7600<br />

<strong>SIPROTEC</strong> Overview sheet English E50001-U321-A118-X-7600<br />

34 Siemens SIP 4.2 · 08/99


Trip time curves<br />

The figures 37 and 38 show<br />

the tripping time curves <strong>for</strong><br />

the distance protection function.<br />

These curves apply to<br />

lines with a Source Impedance<br />

Ratio (SIR) up to 20.<br />

The tripping time includes<br />

the output contact closing<br />

time.<br />

The curves are based on a<br />

line with conventional VT’s,<br />

no pre-fault load and faults<br />

without fault resistance.<br />

Trip time (ms)<br />

35<br />

30<br />

25<br />

20<br />

15<br />

f=50Hz,SIR


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Connection diagrams according to IEC Standard<br />

Figure 37<br />

Housing 1/2 x 19’‘, Basic Version <strong>7SA522</strong>*-*A, <strong>7SA522</strong>*-*E and <strong>7SA522</strong>*-*J<br />

with 8 Binary Inputs and 16 Binary Outputs<br />

Flush mounting<br />

Surface mounting<br />

25<br />

50<br />

24<br />

49<br />

23<br />

48<br />

22<br />

47<br />

20<br />

45<br />

19<br />

44<br />

21<br />

46<br />

43<br />

18<br />

42<br />

17<br />

41<br />

40<br />

14<br />

39<br />

38<br />

13<br />

37<br />

12<br />

36<br />

11<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

I L1<br />

I L2<br />

I L3<br />

I 4<br />

V L1<br />

V L2<br />

V L3<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

BO12<br />

BO 13<br />

BO 14<br />

BO 15<br />

=<br />

(~)<br />

Serial<br />

Interfaces<br />

+<br />

-<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

K3<br />

K4<br />

K1<br />

K2<br />

88<br />

63<br />

87<br />

62<br />

86<br />

61<br />

85<br />

60<br />

84<br />

59<br />

83<br />

58<br />

74<br />

99<br />

73<br />

98<br />

97<br />

72<br />

96<br />

71<br />

95<br />

70<br />

94<br />

69<br />

90<br />

65<br />

L+(15)<br />

L-(16)<br />

Service interface<br />

DIGSI, Modem<br />

C<br />

System/Scada<br />

interface<br />

B<br />

Front interface<br />

Time<br />

synchronization<br />

A<br />

Figure 38<br />

Serial interfaces<br />

36 Siemens SIP 4.2 · 08/99


Connection diagrams according to IEC Standard<br />

Figure 39<br />

Housing 1/1 x 19’‘, Medium Version <strong>7SA522</strong>*-*C, <strong>7SA522</strong>*-*G and <strong>7SA522</strong>*-*L<br />

with 16 Binary Inputs and 24 Binary Outputs<br />

Surface mounting<br />

Flush mounting<br />

50<br />

100<br />

49<br />

99<br />

48<br />

98<br />

47<br />

97<br />

45<br />

95<br />

44<br />

94<br />

46<br />

96<br />

75<br />

25<br />

74<br />

24<br />

73<br />

23<br />

72<br />

22<br />

71<br />

21<br />

70<br />

20<br />

69<br />

19<br />

90<br />

40<br />

89<br />

39<br />

86<br />

36<br />

85<br />

35<br />

84<br />

34<br />

83<br />

33<br />

82<br />

32<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

P17<br />

P18<br />

N1<br />

N2<br />

N3<br />

N4<br />

N5<br />

N6<br />

N7<br />

N8<br />

N9<br />

N10<br />

N11<br />

N12<br />

I L1<br />

I L2<br />

I L3<br />

I 4<br />

V L1<br />

V L2<br />

V L3<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

BI 9<br />

BI 10<br />

BI 11<br />

BI 12<br />

BI 13<br />

BI 14<br />

BI 15<br />

BI 16<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

BO12<br />

BO 13<br />

BO 14<br />

BO 15<br />

BO16<br />

NC or NO<br />

with Jumper<br />

BO 17<br />

BO 18<br />

BO 19<br />

BO 20<br />

BO 21<br />

BO 22<br />

BO 23<br />

=<br />

(~)<br />

Serial<br />

Interfaces<br />

+<br />

-<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

P3<br />

P4<br />

P5<br />

P6<br />

P7<br />

P8<br />

P9<br />

P10<br />

P11<br />

P12<br />

P13<br />

P14<br />

P15<br />

P16<br />

K3<br />

K4<br />

K1<br />

K2<br />

173<br />

123<br />

172<br />

122<br />

171<br />

121<br />

170<br />

120<br />

169<br />

119<br />

168<br />

118<br />

149<br />

199<br />

148<br />

198<br />

197<br />

147<br />

196<br />

146<br />

195<br />

145<br />

194<br />

144<br />

190<br />

140<br />

189<br />

139<br />

188<br />

138<br />

187<br />

137<br />

186<br />

136<br />

185<br />

135<br />

184<br />

134<br />

174<br />

124<br />

L+ (37)<br />

L- (38)<br />

Note: <strong>for</strong> serial interfaces see Figure 38<br />

Siemens SIP 4.2 · 08/99 37


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Connection diagrams according to IEC Standard<br />

Figure 40<br />

Housing 1/1 x 19’‘, Maximum Version <strong>7SA522</strong>*-*D, <strong>7SA522</strong>*-*H and <strong>7SA522</strong>*-*M with<br />

24 Binary Inputs and 32 Binary Outputs<br />

Surface mounting<br />

Flush mounting<br />

50<br />

100<br />

49<br />

99<br />

48<br />

98<br />

47<br />

97<br />

45<br />

95<br />

44<br />

94<br />

46<br />

96<br />

75<br />

25<br />

74<br />

24<br />

73<br />

23<br />

72<br />

22<br />

71<br />

21<br />

70<br />

20<br />

69<br />

19<br />

90<br />

40<br />

89<br />

39<br />

86<br />

36<br />

85<br />

35<br />

84<br />

34<br />

83<br />

33<br />

82<br />

32<br />

68<br />

18<br />

67<br />

17<br />

66<br />

16<br />

65<br />

15<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

P17<br />

P18<br />

N1<br />

N2<br />

N3<br />

N4<br />

N5<br />

N6<br />

N7<br />

N8<br />

N9<br />

N10<br />

N11<br />

N12<br />

H17<br />

H18<br />

G1<br />

G2<br />

G3<br />

G4<br />

G5<br />

G6<br />

I L1<br />

I L2<br />

I L3<br />

I 4<br />

V L1<br />

V L2<br />

V L3<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

BI 9<br />

BI 10<br />

BI 11<br />

BI 12<br />

BI 13<br />

BI 14<br />

BI 15<br />

BI 16<br />

BI 17<br />

BI 18<br />

BI 19<br />

BI 20<br />

BI 21<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

BO12<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

BO 13<br />

BO 14<br />

BO 15<br />

BO16<br />

NC or NO<br />

with Jumper<br />

BO 17<br />

BO 18<br />

BO 19<br />

BO 20<br />

BO 21<br />

BO 22<br />

BO 23<br />

BO24<br />

NC or NO<br />

with Jumper<br />

BO 25<br />

BO 26<br />

BO 27<br />

BO 28<br />

BO 29<br />

BO 30<br />

BO 31<br />

=<br />

(~)<br />

+<br />

-<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

P3<br />

P4<br />

P5<br />

P6<br />

P7<br />

P8<br />

P9<br />

P10<br />

P11<br />

P12<br />

P13<br />

P14<br />

P15<br />

P16<br />

H3<br />

H4<br />

H5<br />

H6<br />

H7<br />

H8<br />

H9<br />

H10<br />

H11<br />

H12<br />

H13<br />

H14<br />

H15<br />

H16<br />

K3<br />

K4<br />

K1<br />

K2<br />

173<br />

123<br />

172<br />

122<br />

171<br />

121<br />

170<br />

120<br />

169<br />

119<br />

168<br />

118<br />

149<br />

199<br />

148<br />

198<br />

197<br />

147<br />

196<br />

146<br />

195<br />

145<br />

194<br />

144<br />

190<br />

140<br />

189<br />

139<br />

188<br />

138<br />

187<br />

137<br />

186<br />

136<br />

185<br />

135<br />

184<br />

134<br />

166<br />

116<br />

165<br />

115<br />

164<br />

114<br />

163<br />

113<br />

162<br />

112<br />

161<br />

111<br />

160<br />

110<br />

174<br />

124<br />

L+ (37)<br />

L- (38)<br />

64<br />

14<br />

63<br />

13<br />

62<br />

12<br />

G7<br />

G8<br />

G9<br />

G10<br />

G11<br />

G12<br />

BI 22<br />

BI 23<br />

BI 24<br />

Serial<br />

Interfaces<br />

Note: <strong>for</strong> serial interfaces see Figure 38<br />

38 Siemens SIP 4.2 · 08/99


Connection diagrams according to ANSI Standard<br />

Figure 41<br />

Housing ½ x 19’‘, Basic Version <strong>7SA522</strong>*-*A, <strong>7SA522</strong>*-*E and <strong>7SA522</strong>*-*J with<br />

8 Binary Inputs and 16 Binary Outputs<br />

Surface mounting<br />

25<br />

50<br />

24<br />

49<br />

23<br />

48<br />

22<br />

47<br />

20<br />

45<br />

19<br />

44<br />

21<br />

46<br />

43<br />

18<br />

42<br />

17<br />

41<br />

40<br />

14<br />

39<br />

38<br />

13<br />

37<br />

12<br />

36<br />

11<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

I A<br />

I B<br />

I C<br />

I 4<br />

V A<br />

V B<br />

V C<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

=<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

BO12<br />

BO 13<br />

BO 14<br />

BO 15<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

(~)<br />

Serial<br />

Interfaces<br />

Flush mounting<br />

+<br />

-<br />

K3<br />

K4<br />

K1<br />

K2<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

88<br />

63<br />

87<br />

62<br />

86<br />

61<br />

85<br />

60<br />

84<br />

59<br />

83<br />

58<br />

74<br />

99<br />

73<br />

98<br />

97<br />

72<br />

96<br />

71<br />

95<br />

70<br />

94<br />

69<br />

90<br />

65<br />

L+(15)<br />

L-(16)<br />

Service interface<br />

DIGSI, Modem<br />

C<br />

System/Scada<br />

interface<br />

B<br />

Front interface<br />

Time<br />

synchronization<br />

A<br />

Figure 42<br />

Serial interfaces<br />

Siemens SIP 4.2 · 08/99 39


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Connection diagrams according to ANSI Standard<br />

Figure 43<br />

Housing 1/1 x 19’‘, Medium Version <strong>7SA522</strong>*-*C, <strong>7SA522</strong>*-*G and <strong>7SA522</strong>*-*L<br />

with 16 Binary Inputs and 24 Binary Outputs<br />

Surface mounting<br />

Flush mounting<br />

50<br />

100<br />

49<br />

99<br />

48<br />

98<br />

47<br />

97<br />

45<br />

95<br />

44<br />

94<br />

46<br />

96<br />

75<br />

25<br />

74<br />

24<br />

73<br />

23<br />

72<br />

22<br />

71<br />

21<br />

70<br />

20<br />

69<br />

19<br />

90<br />

40<br />

89<br />

39<br />

86<br />

36<br />

85<br />

35<br />

84<br />

34<br />

83<br />

33<br />

82<br />

32<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

P17<br />

P18<br />

N1<br />

N2<br />

N3<br />

N4<br />

N5<br />

N6<br />

N7<br />

N8<br />

N9<br />

N10<br />

N11<br />

N12<br />

I A<br />

I B<br />

I C<br />

I 4<br />

V A<br />

V B<br />

V C<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

BI 9<br />

BI 10<br />

BI 11<br />

BI 12<br />

BI 13<br />

BI 14<br />

BI 15<br />

BI 16<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

=<br />

BO12<br />

BO 13<br />

BO 14<br />

BO 15<br />

BO16<br />

NC or NO<br />

with Jumper<br />

BO 17<br />

BO 18<br />

BO 19<br />

BO 20<br />

BO 21<br />

BO 22<br />

BO 23<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

(~)<br />

Serial<br />

Interfaces<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

P3<br />

P4<br />

P5<br />

P6<br />

P7<br />

P8<br />

P9<br />

P10<br />

P11<br />

P12<br />

P13<br />

P14<br />

P15<br />

P16<br />

K3<br />

K4<br />

+<br />

K1<br />

- K2<br />

173<br />

123<br />

172<br />

122<br />

171<br />

121<br />

170<br />

120<br />

169<br />

119<br />

168<br />

118<br />

149<br />

199<br />

148<br />

198<br />

197<br />

147<br />

196<br />

146<br />

195<br />

145<br />

194<br />

144<br />

190<br />

140<br />

189<br />

139<br />

188<br />

138<br />

187<br />

137<br />

186<br />

136<br />

185<br />

135<br />

184<br />

134<br />

174<br />

124<br />

L+ (37)<br />

L-(38)<br />

Note: <strong>for</strong> serial interfaces see Figure 42<br />

40 Siemens SIP 4.2 · 08/99


Connection diagrams according to ANSI Standard<br />

Figure 44<br />

Housing 1/1 x 19’‘, Maximum Version <strong>7SA522</strong>*-*D, <strong>7SA522</strong>*-*H and <strong>7SA522</strong>*-*M<br />

with 24 Binary Inputs and 32 Binary Outputs<br />

Surface mounting<br />

Flush mounting<br />

50<br />

100<br />

49<br />

99<br />

48<br />

98<br />

47<br />

97<br />

45<br />

95<br />

44<br />

94<br />

46<br />

96<br />

75<br />

25<br />

74<br />

24<br />

73<br />

23<br />

72<br />

22<br />

71<br />

21<br />

70<br />

20<br />

69<br />

19<br />

90<br />

40<br />

89<br />

39<br />

86<br />

36<br />

85<br />

35<br />

84<br />

34<br />

83<br />

33<br />

82<br />

32<br />

68<br />

18<br />

67<br />

17<br />

66<br />

16<br />

65<br />

15<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

K17<br />

K18<br />

J1<br />

J2<br />

J3<br />

J4<br />

J5<br />

J6<br />

J7<br />

J8<br />

J9<br />

J10<br />

J11<br />

J12<br />

P17<br />

P18<br />

N1<br />

N2<br />

N3<br />

N4<br />

N5<br />

N6<br />

N7<br />

N8<br />

N9<br />

N10<br />

N11<br />

N12<br />

H17<br />

H18<br />

G1<br />

G2<br />

G3<br />

G4<br />

G5<br />

G6<br />

I A<br />

I B<br />

I C<br />

I 4<br />

V A<br />

V B<br />

V C<br />

V 4<br />

BI 1<br />

BI 2<br />

BI 3<br />

BI 4<br />

BI 5<br />

BI 6<br />

BI 7<br />

BI 8<br />

BI 9<br />

BI 10<br />

BI 11<br />

BI 12<br />

BI 13<br />

BI 14<br />

BI 15<br />

BI 16<br />

BI 17<br />

BI 18<br />

BI 19<br />

BI 20<br />

BI 21<br />

Fast BO1<br />

Fast BO2<br />

Fast BO3<br />

Fast BO4<br />

Fast BO5<br />

Fast BO6<br />

Fast BO7<br />

BO8<br />

BO9<br />

BO10<br />

BO11<br />

Live status contact<br />

NC or NO with Jumper<br />

=<br />

BO12<br />

BO 13<br />

BO 14<br />

BO 15<br />

BO16<br />

NC or NO<br />

with Jumper<br />

BO 17<br />

BO 18<br />

BO 19<br />

BO 20<br />

BO 21<br />

BO 22<br />

BO 23<br />

BO24<br />

NC or NO<br />

with Jumper<br />

BO 25<br />

BO 26<br />

BO 27<br />

BO 28<br />

BO 29<br />

BO 30<br />

BO 31<br />

=<br />

(~)<br />

+<br />

-<br />

K5<br />

K6<br />

K7<br />

K8<br />

K9<br />

K10<br />

K11<br />

K12<br />

K13<br />

K14<br />

K15<br />

K16<br />

R1<br />

R2<br />

R3<br />

R4<br />

R5<br />

R6<br />

R7<br />

R8<br />

R9<br />

R10<br />

R11<br />

R12<br />

P3<br />

P4<br />

P5<br />

P6<br />

P7<br />

P8<br />

P9<br />

P10<br />

P11<br />

P12<br />

P13<br />

P14<br />

P15<br />

P16<br />

H3<br />

H4<br />

H5<br />

H6<br />

H7<br />

H8<br />

H9<br />

H10<br />

H11<br />

H12<br />

H13<br />

H14<br />

H15<br />

H16<br />

K3<br />

K4<br />

K1<br />

K2<br />

173<br />

123<br />

172<br />

122<br />

171<br />

121<br />

170<br />

120<br />

169<br />

119<br />

168<br />

118<br />

149<br />

199<br />

148<br />

198<br />

197<br />

147<br />

196<br />

146<br />

195<br />

145<br />

194<br />

144<br />

190<br />

140<br />

189<br />

139<br />

188<br />

138<br />

187<br />

137<br />

186<br />

136<br />

185<br />

135<br />

184<br />

134<br />

166<br />

116<br />

165<br />

115<br />

164<br />

114<br />

163<br />

113<br />

162<br />

112<br />

161<br />

111<br />

160<br />

110<br />

174<br />

124<br />

L+ (37)<br />

L- (38)<br />

64<br />

14<br />

63<br />

13<br />

62<br />

12<br />

G7<br />

G8<br />

G9<br />

G10<br />

G11<br />

G12<br />

BI 22<br />

BI 23<br />

BI 24<br />

Serial<br />

Interfaces<br />

Note: <strong>for</strong> serial interfaces see Figure 42<br />

Siemens SIP 4.2 · 08/99 41


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Dimension drawings<br />

Figure 45<br />

Flush mounting 1/2 x 19’‘ with screw and<br />

plug-in terminals<br />

225 (8.86)<br />

220 (8.66)<br />

221 +2 (8.70 + 0.079 )<br />

255.8 ±0.3 (10.07 ± 0.012 )<br />

245 +1(9.64 +0.039)<br />

5(0.20)orM4<br />

6(0.24)<br />

4.3<br />

(0.17)<br />

13.2<br />

(0.52)<br />

7.3<br />

(0.29)<br />

180 ± 0.5 (7.09 ± 0.020 )<br />

206.5 ± 0.3 (8.13 ± 0.012 )<br />

Housing 1/2 x 19’‘<br />

Rear view<br />

Housing 1/2 x 19’‘<br />

Panel cutout<br />

29.5<br />

(1.16)<br />

172 (6.77) 34<br />

(1.34)<br />

29.5<br />

(1.16)<br />

172 (6.77)<br />

29<br />

(1.14)<br />

30<br />

(1.18)<br />

266 (10.47)<br />

244 (9.61)<br />

266 (10.47)<br />

244 (9.61)<br />

2<br />

(0.08)<br />

2<br />

(0.08)<br />

34<br />

(1.34)<br />

Side view with<br />

screw terminals<br />

Side view with<br />

plug-in terminals<br />

Note:<br />

Dimensions are indicated in millimeters;<br />

values stated in brackets are inches<br />

42 Siemens SIP 4.2 · 08/99


Dimension drawings<br />

Figure 46<br />

Flush mounting 1/1 x 19’‘ with screw and<br />

plug-in terminals<br />

450 (17.72)<br />

445 (17.52)<br />

446 +2 (17.56 + 0.079 )<br />

255.8 ± 0.3 (10.07 ± 0.012)<br />

245 + 1(9.64 + 0.039)<br />

5 (0.20)<br />

or M4<br />

6 (0.24)<br />

6 (0.24)<br />

5 (0.20)<br />

or M4<br />

5 (0.20)<br />

or M4<br />

6 (0.24)<br />

6 (0.24)<br />

5 (0.20)<br />

or M4<br />

4.3<br />

(0.17)<br />

7.3<br />

(0.29)<br />

216.1 ± 0.3 (8.51 ± 0.012 )<br />

425.5 ± 0.3 (16.75 ± 0.012 )<br />

13.2<br />

(0.52) 13.2<br />

(0.52)<br />

13.2<br />

(0.52)<br />

Housing 1/1 x 19’‘<br />

Rear view<br />

Housing 1/1 x 19’‘<br />

Panel cutout<br />

29.5<br />

(1.16)<br />

172 (6.77) 34<br />

(1.34)<br />

29.5<br />

(1.16)<br />

172 (6.77)<br />

29<br />

(1.14)<br />

30<br />

(1.18)<br />

266 (10.47)<br />

244 (9.61)<br />

266 (10.47)<br />

244 (9.61)<br />

2<br />

(0.08)<br />

2<br />

(0.08)<br />

34<br />

(1.34)<br />

Side view with<br />

screw terminals<br />

Side view with<br />

plug-in terminals<br />

Note:<br />

Dimensions are indicated in millimeters;<br />

values stated in brackets are inches<br />

Siemens SIP 4.2 · 08/99 43


<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Dimension drawings<br />

Figure 47<br />

Surface mounting 1/1 and 1/2 x 19’‘<br />

260 (10.24)<br />

29.5<br />

(1.16)<br />

25<br />

(0.98)<br />

266 (10.47)<br />

71<br />

(2.80)<br />

72<br />

(2.83)<br />

52<br />

(2.05)<br />

Side view<br />

240 (9.45)<br />

219 (8.62) 10.5<br />

(0.41)<br />

51 75<br />

101<br />

465 (18.31)<br />

444 (17.48)<br />

150<br />

10.5<br />

(0.41)<br />

76 100<br />

151<br />

200<br />

225 (8.86)<br />

280 (11.02)<br />

320 (12.60)<br />

344 (13.54)<br />

450 (17.72)<br />

280 (11.02)<br />

320 (12.60)<br />

344 (13.54)<br />

1 25<br />

1 50<br />

9 (0.35)<br />

26 50<br />

9 (0.35)<br />

51 100<br />

Front view<br />

Housing 1/2 x 19’‘<br />

Front view<br />

Housing 1/1 x 19’‘<br />

Note:<br />

Dimensions are indicated in millimeters;<br />

values stated in brackets are inches<br />

44 Siemens SIP 4.2 · 08/99


Appendix<br />

Explanation of ANSI numbers, IEC designation<br />

ANSI IEC ANSI Standard <strong>7SA522</strong><br />

number<br />

14 Underspeed device. A device that functions when the speed of a machine<br />

–<br />

falls below a determined value.<br />

21<br />

<strong>Distance</strong> relay. A relay that functions when the circuit admittance, impedance,<br />

or reactance increases or decreases beyond a predetermined value.<br />

Phase distance measurement<br />

21N<br />

Ground distance measurement<br />

FL<br />

Fault locator<br />

25 Synchronizing or synchronism-check device. A device that operates when<br />

two ac circuits are within the desired limits of frequency, phase angle and voltage<br />

to permit or cause the paralleling of these two circuits.<br />

Synchro-check function<br />

27<br />

27WI<br />

U< Undervoltage relay. A relay that operates when its input voltage is less than a<br />

predetermined value.<br />

32 Directional power relay. A relay that operates on a predetermined value of power<br />

flow in a given direction or upon reverse power flow such as that resulting from the<br />

motoring of a generator upon loss of its prime mover.<br />

33 Position switch. A switch that makes or breakes contact when the main device<br />

or piece of apparatus that has no device function number reaches a given position.<br />

34 Master sequence device. A device such as a motor opoerated multicontact switch,<br />

or the equivalent, or a programming device, such as a computer, that establishes<br />

or determines the operating sequence of the major devices in equipment during<br />

starting and stopping or during other sequencial switching operations.<br />

37 I< Undercurrent or underpower relay. A relay that functions when the current or<br />

power flow decreases below a predetermined value.<br />

46 I2 Reverse-phase or phase-balance current relay. A relay that functions when the<br />

polyphase currents are of reverse-phase sequence or when the polyphase currents<br />

are unbalanced, or contain negative phase-sequence components above a given<br />

amount.<br />

47 Phase-sequence or phase-balance voltage relay. A relay that functions upon a<br />

predetermined value of polyphase voltage in the desired phase sequence, when<br />

the polyphase voltages are unbalanced, or when the negative phase-sequence voltage.<br />

48 Incomplete sequence relay. A relay that generally returns the equipment to the<br />

normal, or off, position and locks it out if the normal starting, operating, or stopping<br />

sequence is not properly completed within a predetermined time.<br />

49 Machine or trans<strong>for</strong>mer thermal relay. A relay that functions when the temperature<br />

of a machine armature winding or other load-carrying winding or element of a machine<br />

or power trans<strong>for</strong>mer exceeds a predetermined value.<br />

50 I>>, I> Instantaneous overcurrent relay. A relay that functions instantaneously on an<br />

excessive value of current<br />

50N 3I 0 >>>,<br />

3I 0 >>, 3I 0><br />

50N-2 3I 0 ><br />

50BF<br />

50HS<br />

50 STUB<br />

50N STUB<br />

51<br />

51N<br />

51N-2<br />

I ph<br />

I>>><br />

I ph STUB<br />

3I 0 STUB<br />

I p ,3I 0p<br />

3I0p<br />

3I 0p<br />

AC time overcurrent relay. A relay that functions when the ac input current exceeds<br />

a predetermined value, and in which the input current and operating time are inversely<br />

related d through a substantial portion of the per<strong>for</strong>mance range.<br />

52 AC circuit breaker. A device that is used to close and interrupt an ac power circuit under<br />

normal conditions or the interrupt this circuit under fault or emergency conditions.<br />

55 cos ϕ Power factor relay. A relay that operates when the power factor in an ac circuit<br />

rises above or falls below a predetermined value.<br />

Phase-Ground undervoltage in<br />

combination with Weak Infeed<br />

trip function<br />

–<br />

Application of programmable logic<br />

Application of programmable logic<br />

Application of programmable<br />

logic. Operating measured value<br />

and limit value module<br />

1. Measured value supervision:<br />

current symmetry / balance<br />

2. Application of programmable<br />

logic: Operating measured value<br />

and limit value module<br />

1. Measured value supervision:<br />

voltage symmetry / balance<br />

2. Application of programmable<br />

logic: Operating measured value<br />

and limit value module<br />

Application of programmable logic<br />

–<br />

Phase-overcurrent time protection<br />

as backup<br />

Ground overcurrent time protection<br />

(directional)<br />

Ground-overcurrent time protection<br />

as backup stage<br />

Breaker failure protection<br />

Instantaneous high speed<br />

s-o-t-f protection<br />

STUB-bus overcurrent stage,<br />

phase and ground<br />

Phase-overcurrent inverse time<br />

protection as backup<br />

Ground overcurrent inverse time<br />

protection (directional)<br />

Ground-overcurrent inverse time<br />

protection as backup stage<br />

–<br />

Application of programmable<br />

logic. Operating measured value<br />

and limit value module<br />

Siemens SIP 4.2 · 08/99 45


Appendix<br />

Explanation of ANSI numbers, IEC designation<br />

ANSI IEC ANSI standard <strong>7SA522</strong><br />

number<br />

59 U>>, U> Overvoltage relay. A relay that operates when its input voltage is more than a<br />

predetermined value.<br />

Phase-ground and zero sequence<br />

overvoltage<br />

62 Time-delay stopping or opening relay. A time-delay relay that serves in conjunction<br />

with the dvice that initiates the shutdown, stopping or opening operation in an<br />

automatic sequence or protective relay system.<br />

64 U T > Ground detector relay. A relay that operates upon failure of machine or other<br />

apparatus insulation to ground.<br />

66 Notching or jogging device. A device that functions to allow that only a specified<br />

number of operations of a given device or equipment, or a specified number of<br />

successive operations within a given time of each other. It is also a device that<br />

functions to energize a circuit periodically or <strong>for</strong> fractions of specified time intervals,<br />

or that is used to permit intermittent acceleration or jogging of a machine at low<br />

speeds <strong>for</strong> mechanical positioning.<br />

67 AC directional overcurrent relay. A relay that functions on a desired value of ac<br />

overcurrent flowing in a predetermined direction<br />

Application of programmable<br />

logic<br />

Ground fault detection<br />

67 N Directional ground-fault time<br />

overcurrent<br />

68<br />

Blocking relay is a relay that initiates a pilot signal <strong>for</strong> blocking or tripping on external<br />

faults in a transmission line or in other apparatus under predetermined conditions, or<br />

cooperates with other devices to block tripping or to block reclosing on an out-of-step<br />

condition or on power swings<br />

Power swing blocking<br />

68 T<br />

Power swing tripping<br />

74<br />

74 TC<br />

Alarm relay. A relay other than an annunciator, as covered under device function 30,<br />

that is used to operate, or that operates in connection with, a visual or audible alarm.<br />

Trip circuit supervision<br />

79 AC reclosing relay. A relay that controls the automatic reclosing and locking out of an<br />

ac circuit interrupter.<br />

Auto reclosing function<br />

81 Frequency relay. A relay that responds to frequency of an electrical quantity, operating<br />

when the frequency or rate of change of frequency exceeds or is less than a<br />

predetermined value.<br />

85<br />

85-21<br />

Teleprotection<br />

Carrier or pilot-wire receiver relay is a relay that is operated or restrained by a signal<br />

used in connection with carrier-current or dc pilot-wire fault directional relaying.<br />

–<br />

Application of programmable<br />

logic: Operating measured value<br />

and limit value module<br />

Pilot schemes <strong>for</strong> distance<br />

protection<br />

85-67N<br />

86 Lockout relay. A hand or electrically reset auxiliary relay that is operated upon the<br />

occurence of abnormal conditions to maintain associated equipment or devices<br />

inoperative until it is reset<br />

87 Differential protective relay. A protective relay that functions on a percentage, phase<br />

angle, or other quantitive difference between two currents or some other electrical<br />

quantities.<br />

Pilot schemes <strong>for</strong> directional<br />

ground fault protection<br />

Trip signal lock-out<br />

see product range 7SD or 7UT<br />

46 Siemens SIP 4.2 · 08/99


List of abbreviations used<br />

A, B, C Phase designation according to ANSI<br />

AMZ curves<br />

Inverse time overcurrent protection<br />

IDMT characteristics<br />

ANSI<br />

American National Standard Institute<br />

AR<br />

Auto-reclosure<br />

ARC<br />

Auto-reclosure<br />

BI<br />

Binary Input<br />

BO<br />

Binary Output<br />

CFC<br />

Continuous Function Chart<br />

DCF77<br />

Time synchronizing signal in Germany<br />

DO<br />

Digital Output<br />

EF<br />

Earth Fault detection<br />

Flash-EPROM<br />

Electrically Programmable and Erasable Memory<br />

FO<br />

Fiber Optic Conductor<br />

GPS<br />

Global Position System<br />

IBS<br />

Commissioning<br />

IEC<br />

International Electrotechnical Commission<br />

IRIG B<br />

Time synchronizing signal via GPS<br />

L1, L2, L3 Phase designation according to IEC<br />

LED<br />

Light Emitting Diode<br />

MHO<br />

Circle characteristic in the impedance plane<br />

NC<br />

Normally Closed output relay contact, e.g. contacts are closed if relay is not activated<br />

NO<br />

Normally Open output relay contact, e.g. contacts are open if relay is not activated<br />

OLM<br />

Optical Link Module<br />

PLC<br />

Programmable Logic Control<br />

PLC<br />

Power Line Carrier<br />

R<br />

<strong>Relay</strong><br />

SC<br />

Substation Controller<br />

SCADA<br />

Supervisory Control and Data Aquisition<br />

SICAM<br />

Substation In<strong>for</strong>mation Control Automation and Monitoring System<br />

SIMATIC<br />

SIEMENS Automation Technology<br />

<strong>SIPROTEC</strong><br />

SIEMENS PROTECTION<br />

SIR<br />

Source to line impedance ratio<br />

Ratio of the source impedance behind a relay terminal to the line impedance.<br />

UMZ curves<br />

Definite time overcurrent protection<br />

DT characteristics<br />

Siemens SIP 4.2 · 08/99 47


Siemens Companies and Representatives<br />

Siemens AG Power <strong>Transmission</strong> and Distribution<br />

Europe<br />

Austria<br />

Siemens AG Österreich<br />

Siemensstr. 88 - 92<br />

A-1211 Wien<br />

Mrs. Strobach<br />

Phone:+43-1-1707-22522<br />

Fax:+43-1-1707-53075<br />

Belgium<br />

Siemens S. A.<br />

Chaussée de Charlerois<br />

116<br />

B-1060 Brüssel<br />

Mr. Belvaux<br />

Phone:+32-2-53621-2595<br />

Fax:+32-2-53621-6900<br />

Czech. Republic<br />

Siemens s. r. O.<br />

Na Strzi 40<br />

CZ-140 00 Prag 4<br />

Mr. Slechta<br />

Phone:+420-2-61095209<br />

Fax:+420-2-61095252<br />

Denmark<br />

Siemens A / sincerely<br />

Borupvang 3<br />

DK-2750 Ballerup<br />

Mr. Jensen<br />

Phone:+45-4477 4309<br />

Fax:+45-4477 4020<br />

Finland<br />

Siemens Osakeyhtiö<br />

Majurinkatu 1<br />

FIN-02601 Espoo<br />

Mr. Tuukkanen<br />

Phone:+358-9-5105 3846<br />

Fax:+358-9-5105 3530<br />

France<br />

Siemens S. A.<br />

39-47, boulevard Ornano<br />

F 93527 Saint Denis<br />

Mr. Cieslak<br />

Phone:+33-1-4922 3469<br />

Fax:+33-1-4922 3090<br />

Great Britain<br />

Siemens plc<br />

William Siemens House<br />

Princess Road<br />

Manchester M20 2UR<br />

Mr. Denning<br />

Phone:+44-1-614465130<br />

Fax:+44-1-614465105<br />

Greece<br />

Siemens A. E.<br />

Artemidos 8<br />

GR-151 10 Athen<br />

Mr. Roubis<br />

Phone:+30-1-6864530<br />

Fax:+30-1-6864703<br />

Italy<br />

Siemens S.p. A.<br />

Via Fabio Filzi 29<br />

I-20 124 Mailand<br />

Mr. Mormile<br />

Phone:+39-02-66762854<br />

Fax:+39-02-66762347<br />

Ireland<br />

Siemens Ltd.<br />

8 Raglan Road<br />

Ballsbridge<br />

Dublin 4<br />

Mr. Kernan<br />

Phone:+353-1-603 2430<br />

Fax:+353-1-603 2499<br />

Netherlands<br />

Siemens Nederland N.V.<br />

Prinses Beatrixlaan 26<br />

NL-2500 BB Den Haag<br />

Mr. Langedijk<br />

Phone:+31-70-333 3126<br />

Fax:+31-70-333 3225<br />

Norway<br />

Siemens A / sincerely<br />

Ostre Aker vei 90<br />

N-0518 Oslo<br />

Mr. Gravermoen<br />

Phone:+47-22-633140<br />

Fax:+47-22-633796<br />

Poland<br />

Siemens Sp.z.o.o.<br />

ul. Zupnicza 11<br />

PL-03-821 Warschau<br />

Mr. Dombrowski<br />

Phone:+48-22-8709120<br />

Fax:+48-22-6709139<br />

Portugal<br />

Siemens S. A.<br />

Apartado 60300<br />

P-2700 Amadora<br />

Mr. Pissarro<br />

Phone:+351-1-417 8253<br />

Fax:+351-1-417 8071<br />

Slovenia<br />

Branch office: Siemens<br />

Austria<br />

Spain<br />

Siemens S.A.<br />

Apartado 155<br />

E 28 020 Madrid<br />

Mr. Martin<br />

Phone:+34-1-5147562<br />

Fax:+34-1-5147037<br />

Switzerland<br />

Siemens-Albis AG<br />

Freilagerstr. 28 - 40<br />

CH-8047 Zürich<br />

Mr. Horisberger<br />

Phone:+41-1-495-3566<br />

Fax:+41-1-495-3253<br />

Turkey<br />

SIMKO Ticaret ve Sanayi<br />

AS<br />

Meclisi Mebusan<br />

Caddesi125<br />

80040 Findikli-Istanbul<br />

Mr. Uzuner<br />

Phone:+90-0216-4593741<br />

Fax:+90-0216-4592155<br />

Africa<br />

Egypt<br />

Siemens Ltd.<br />

Cairo, P.O.Box 775 /<br />

11511<br />

26, El Batal Ahmed<br />

Abdel Aziz Str.<br />

Mohandessin<br />

Mr. Aly Abou-Zied<br />

Phone:+20-2-3499727,<br />

Fax:+20-2-3446774<br />

South Africa<br />

Siemens Ltd., PT & D<br />

26 Electron Ave.,<br />

Isando 1600<br />

Mr. A Matthe<br />

Phone:+27-11-921 2499<br />

Fax:+27-11-921 7100<br />

Australia<br />

Siemens Ltd., PT & D<br />

Sydney Office<br />

383 Pacific Highway<br />

Artarmon N.S.W. 2064<br />

Mr. Fomin<br />

Phone:+61-2-9950 8649<br />

Fax:+61-2-9950 8733<br />

North America<br />

USA<br />

Siemens<br />

Power <strong>Transmission</strong> &<br />

Distribution, LLC<br />

7000 Siemens Rd.<br />

Wendell , NC 27591<br />

Mr. C. Pretorius<br />

Phone:+1-919-365 2196<br />

Fax: +1-919-365 2552<br />

Mexico<br />

Siemens S.A. DE C.V.<br />

Pte. 116 No. 590,<br />

Col. Ind. Vallejo<br />

02300 Mexico D.F.<br />

Mr. Loredo<br />

Phone:+52-5-3282012<br />

Fax:+52-5-3282241<br />

South America<br />

Brazil<br />

Siemens S.A.<br />

Coronel Bento Bicudo,<br />

111 Lapa<br />

05069-900 Sao Paulo -SP<br />

Mr. Muramoto<br />

Phone: +55-11-833 4079<br />

Fax:+55-11-833 4391<br />

Columbia<br />

Siemens S.A., GDH<br />

Santafe de Bogota,D.C.<br />

Cra 65 No. 11-83<br />

Conmuta<br />

Mr. Walter Bing-Zaremba<br />

Phone:+57-1-294 2222<br />

Fax:+57-1-294 2500<br />

Asia<br />

China<br />

Siemens Ltd., PT & D<br />

No. 7, Wangjin<br />

Zhonghuan Nanlu,<br />

Chaoyang District<br />

Beijing, 100015<br />

Mr. Sure En Lee<br />

Phone:+86-10-6436 1888<br />

ext. 3806<br />

Fax:+86-10-64381464<br />

Hong Kong<br />

Siemens Ltd., PTD 58/F<br />

Central Plaza<br />

18 Harbour Road<br />

Wanchai, Hong Kong<br />

Mr. Humphrey S.K. Ling<br />

Phone:+852-2583 3388<br />

Fax:+852-28029908<br />

India<br />

Siemens Ltd., PTD / ZLS<br />

4A, Ring Road, I.P. Estate<br />

New Delhi 110 002<br />

Mr. A. K. Dixit<br />

Phone:+91-11-3719877<br />

Fax:+91-11-3739161<br />

Indonesia<br />

P.T. Siemens Indonesia<br />

Jl. Jend. A. Yani<br />

Pulo Mas, Jakarta 13210<br />

P.O.Box 2469<br />

Jakarta 10001<br />

Mr. Volker Schenk<br />

Phone:+62-21-4729 153<br />

Fax: +62-21-471 5055,<br />

472 9201<br />

Korea<br />

Siemens Ltd<br />

10th Floor Asia Tower<br />

Bldg<br />

726, Yeoksam-dong,<br />

Kangman-gu<br />

Seoul 100-630, Korea<br />

Mr. Kim Se-ho<br />

Phone: +82-2-5277 805<br />

Malaysia<br />

Siemens<br />

Electrical Engineering<br />

Sdn Bhd<br />

13 th Floor, CP Tower<br />

11 Section 16/11, Jalan<br />

Damansara<br />

46350 Petaling Jaya<br />

Selangor Darul Ehsan<br />

Mr. Vind Sidhu<br />

Phone:+60-3-751 3929<br />

(direct)<br />

Phone:+60-3-7513888<br />

(switchb.)<br />

Fax:+60-3-757 0380<br />

Phillipines<br />

Siemens Inc.<br />

14 F Centerpoint building<br />

Orligas Center, Pasig City<br />

Makati 1229, Metro Manila<br />

Mr. De Guzmann<br />

Phone.:+63-2-637 0900<br />

Fax:+63-2-633 5592<br />

Singapore<br />

Power Automation<br />

89 Science Park, #04-13<br />

The Ruther<strong>for</strong>d,<br />

Singapore 112861<br />

Mr. Au<br />

Phone:+65-872 2688<br />

Fax:+65-872 3692<br />

Taiwan<br />

Siemens Ltd., PT & D<br />

Dept.<br />

19th Floor, 333, Tun-Hua<br />

S. Road,<br />

Sec. 2, (P.O.Box 26-755)<br />

Taipei<br />

Mr. Frances Peng<br />

Phone:+886-2-23788900<br />

ext.832<br />

Fax:+886-2-2378 8958<br />

Thailand<br />

Siemens Limited, EV SP<br />

Dept.<br />

Charn Issara Tower II,<br />

32ndFloor<br />

2922/283 New Petchburi<br />

Road<br />

Bangkapi, Huaykwang<br />

Bangkok 10320<br />

Mr. Chaturawit sincerely.<br />

Phone:+66-2-715-4815<br />

Fax:+66-2-715-4785<br />

Vietnam<br />

Siemens AG, Representation<br />

5B Ton Duc Thang Str.<br />

District 1<br />

Ho Chi Minh City<br />

Ms. Hung<br />

Phone:+84-8825 1900<br />

Fax:+84-8825 1580<br />

48 Siemens SIP 4.2 · 08/99


Conditions of Sale and Delivery · Export Regulations<br />

Trademarks<br />

Conditions of Sale and Delivery<br />

Subject to the<br />

General Conditions of Supply<br />

and Delivery<br />

<strong>for</strong> Products and Services of<br />

the Electrical and Electronic<br />

Industry and to any other conditions<br />

agreed upon with the<br />

recipients of catalogs.<br />

<br />

Technical data, dimensions<br />

and weights are subject to<br />

change unless otherwise stated<br />

on the individual pages of<br />

this catalog.<br />

The illustrations are <strong>for</strong> reference<br />

only.<br />

We reserve the right to adjust<br />

the prices and shall charge<br />

the price applying on the<br />

date of delivery.<br />

A En 1.91a<br />

Export Regulations<br />

Trademarks<br />

Siemens Online<br />

In accordance with the<br />

present provisions of the<br />

German Export List and the<br />

US Commercial Control List,<br />

export licences are not<br />

required <strong>for</strong> the products<br />

listed in this catalog.<br />

An export licence may<br />

however be required due to<br />

country-specific application<br />

and final destination of the<br />

products.<br />

Relevant are the export<br />

criteria stated in the delivery<br />

note and the invoice<br />

subject to a possible export<br />

and reexport licence.<br />

Subject to change without<br />

notice.<br />

All product designations used<br />

are trademarks or product<br />

names of Siemens AG or of<br />

other suppliers.<br />

The Power <strong>Transmission</strong> and<br />

Distribution Group can also<br />

be found in the Internet:<br />

http://www.ev.siemens.de<br />

Siemens SIP 4.2 · 08/99 49


Responsible <strong>for</strong><br />

Technical contents: Michael Claus,<br />

Product Manager <strong>Distance</strong> <strong>Protection</strong><br />

Siemens AG, EV S V13, Nuremberg, Germany<br />

Ordering No: E50417-K1176-C114–A<br />

Printed in Germany


Power <strong>Transmission</strong> and<br />

Distribution Group<br />

<strong>Protection</strong> and Substation<br />

Control Systems Division<br />

P.O. Box 48 06<br />

D-90026 Nuremberg<br />

http://www.ev.siemens.de<br />

Siemens Aktiengesellschaft Subject to change without notice Ordering No: E50417-K1176-C114–A<br />

Printed in Germany

Hooray! Your file is uploaded and ready to be published.