Technical Function Data<br />

<strong>Distance</strong> protection – ANSI 21, 21N<br />

Fault locator<br />

<strong>Distance</strong> zones<br />

6, 1 as extended (overreach) zone<br />

all zones may be set <strong>for</strong>ward or/and reverse<br />

or ineffective<br />

Time stages<br />

6 <strong>for</strong> multi-phase faults<br />

3 <strong>for</strong> single-phase faults<br />

Characteristic<br />

(refer to ordering code)<br />

selectable seperately <strong>for</strong> phase and<br />

quadrilateral and/or<br />

ground (earth) faults<br />

MHO<br />

Time range<br />

0.00 to 30 s (step 0.01s) or deactivated<br />

Line angle ϕ L<br />

30° to 89° (step 1°)<br />

Quadrilateral reactance reach X<br />

0.05Ω to 250Ω (1A) / 0.01Ω to 50Ω (5A)<br />

(step 0.01Ω)<br />

Quadrilateral resistance reach R<br />

<strong>for</strong> phase-to-phase faults and<br />

0.05Ω to 250Ω (1A) / 0.01Ω to 50Ω (5A)<br />

phase-to-ground (earth) faults<br />

(step 0.01Ω)<br />

MHO impedance reach ZR<br />

0.05Ω to 200Ω (1A) / 0.01Ω to 40Ω (5A)<br />

(step 0.01Ω)<br />

Minimum phase current I<br />

0.10A to 4A (1A) / 0.50A to 20A (5A)<br />

(step 0.01A)<br />

Ground- (Earth-) fault pickup<br />

Neutral (residual) current 3 I 0<br />

Zero sequence voltage 3V 0<br />

Zero sequence compensation<br />

selectable input <strong>for</strong>mats<br />

Seperately selectable <strong>for</strong> zones<br />

0.05A to 4A (1A) / 0.25A to 20A (5A)<br />

(step 0.01A)<br />

1 to 100V (step 1V) or deactivated<br />

RG/RL and XG/XL<br />

k 0 and ϕ (k 0 )<br />

Z1<br />

higher zones<br />

RG/RL and XG/XL - 0.33 to 7 (step 0.01)<br />

k 0<br />

0 to 4 (step 0.001)<br />

ϕ (k 0 ) -135° to 135°<br />

Parallel line mutual compensation<br />

(refer to ordering code)<br />

RM/RL and XM/XL 0.00 to 8 (step 0.01)<br />

Load encroachment<br />

Minimum load resistance<br />

0.10Ω to 250Ω (1A) / 0.02Ω to 50Ω (5A)<br />

(step 0.01Ω) or deactivated<br />

Maximum load angle 20° to 60° (step 1°)<br />

Directional decision <strong>for</strong> all types of faults<br />

Directional sensitivity<br />

Tolerances<br />

Timer tolerance<br />

Operating times<br />

Minimum trip time<br />

Reset time<br />

with sound phase polarization and/or voltage<br />

memory<br />

dynamically unlimited<br />

<strong>for</strong> sinusodial quantities<br />

∆X<br />

X ≤ 5% <strong>for</strong> 30° ≤ϕ scc ≤ 90°<br />

∆R<br />

R ≤ 5% <strong>for</strong> 0° ≤ϕ scc ≤ 60°<br />

∆Z<br />

Z<br />

≤ 5% <strong>for</strong> -30° ≤(ϕ scc −ϕ line ) ≤+30°<br />

± 1% of set value or 10ms<br />

approx. 17ms at 50Hz<br />

approx. 15ms at 60Hz<br />

approx. 30ms<br />

Output of the distance to fault<br />

X, R (secondary) in Ω<br />

X, R (primary) in Ω<br />

distance in kilometers or miles<br />

distance in % of line length<br />

Start of calculation<br />

with trip, with pickup reset<br />

Reactance per unit length 0.005 to 6.5Ω /km (1A) / 0.001 to 1.3Ω /km (5A) or<br />

0.005 to 10Ω / mile (1A) / 0.001 to 2Ω / mile (5A)<br />

(step 0.001Ω / unit)<br />

Tolerance<br />

<strong>for</strong> sinusodial quantities<br />

≤ 2.5% line length <strong>for</strong> 30° ≤ϕ scc ≤ 90° and<br />

V scc /V N > 0.10<br />

Siemens SIP 4.2 · 08/99 25