<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Function Data<br />

Pilot-(Tele-) protection <strong>for</strong> directional ground-(earth-) fault overcurrent protection – ANSI 85-67N<br />

Operating modes<br />

Transient blocking logic<br />

Send and receive signals<br />

directional comparison Pickup<br />

directional comparison Blocking<br />

directional comparison Unblocking<br />

<strong>for</strong> schemes with parallel lines<br />

suitable <strong>for</strong> 2- and 3- terminal lines<br />

Weak Infeed protection with undervoltage – ANSI 27WI<br />

Operating modes with carrier (signal) reception echo<br />

echo and trip with undervoltage<br />

Undervoltage phase-ground (-earth) 2V to 70V (step 1V)<br />

Time delay<br />

0.00s to 30s (step 0.01s)<br />

Echo impulse<br />

0.00s to 30s (step 0.01s)<br />

Tolerances<br />

Voltage threshold ≤ 5% of set value or 0.5V<br />

Timer<br />

± 1% of set value or 10ms<br />

Backup overcurrent protection – ANSI 50(N), 51(N)<br />

Operating modes<br />

Characteristic<br />

Instantaneous trip after switch-onto-fault<br />

active only with loss of VT secondary circuit<br />

always active<br />

2 definite time stages / 1 inverse time stage<br />

selectable <strong>for</strong> every stage<br />

Definite time overcurrent Pickup definite time stage 1, phase current 0.1A to 25A (1A) / 0.5A to 125A (5A)<br />

protection<br />

(step 0.01A)<br />

ANSI 50, 50N Pickup definite time stage 1, neutral (residual) 0.05A to 25A (1A)<br />

/ 0.25A to 125A (5A)<br />

current<br />

(step 0.01A)<br />

Pickup definite time stage 2, phase current<br />

0.1A to 25A (1A) / 0.5A to 125A (5A)<br />

(step 0.01A)<br />

Pickup definite time stage 2, neutral (residual)<br />

0.05A to 25A (1A) / 0.25A to 125A (5A)<br />

current<br />

(step 0.01A)<br />

Time delay <strong>for</strong> definite time stages<br />

0.00 to 30s (step 0.01s) or deactivated<br />

Tolerances<br />

Current starting<br />

≤ 3% of set value or 1% of I nom<br />

Delay times<br />

± 1% of set value or 10ms<br />

Operating time<br />

approx. 25ms<br />

Inverse time overcurrent Phase current starting 0.1A to 4A (1A) / 0.5A to 20A (5A)<br />

protection<br />

(step 0.01A)<br />

ANSI 51, 51N Neutral (residual) current starting 0.05A to 4A (1A) / 0.5A to 20A (5A)<br />

(step 0.01A)<br />

Tripping time characteristics Characteristics normal inverse<br />

according to IEC 60255-3<br />

very inverse<br />

extremely inverse<br />

long time inverse<br />

Time multiplier<br />

T p = 0.05 to 3s (step 0.01s) or deactivated<br />

Pickup threshold<br />

approx. 1.1 x I/I p<br />

Reset threshold<br />

approx. 1.05 x I/I p<br />

Tolerances<br />

Operating time <strong>for</strong> 2 ≤ I/I p ≤20<br />

≤ 5% of setpoint ±15ms<br />

28 Siemens SIP 4.2 · 08/99