<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Technical Function Data<br />

Breaker failure protection – ANSI 50BF<br />

Number of stages 2<br />

Current start<br />

0.1A to 4A (1A) / 0.5A to 20A (5A) (step 0.01A)<br />

Delay time<br />

0.05 to 1s (step 0.01s)<br />

Shortest release time<br />

approx. 10ms<br />

Timer tolerance<br />

± 1% of setting value or 10ms<br />

Automatic reclosure – ANSI 79<br />

Synchronism check – ANSI 25<br />

Number of automatic reclosures up to 8<br />

Program<br />

only 1-pole<br />

only 3-pole<br />

1 or 3-pole<br />

Voltage check<br />

discrimination between successful and<br />

non-successful reclose attempts<br />

Action times<br />

0.01 to 30 s (step 0.01s)<br />

Dead times<br />

0.01 to 1800 s (step 0.01s)<br />

Reclaim times<br />

0.5 to 30 s (step 0.01s)<br />

CLOSE command duration<br />

0.01 to 30 s (step 0.01s)<br />

Timer tolerance<br />

± 1% of setting value or 10ms<br />

Operating modes<br />

Line dead / busbar dead V 1 /V 2 <<br />

Synchronism V 1 >/V 2 ><br />

Permissible voltage difference 1 to 50 V (step 1V)<br />

Permissible frequence difference<br />

0.01 to 1 Hz (step 0.01 Hz)<br />

Permissible angle difference 1 to 60° (step 1)<br />

Supervision time<br />

0.01 to 30 s (step 0.01s)<br />

30 Siemens SIP 4.2 · 08/99