<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />
<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />
Technical Function Data<br />
Breaker failure protection – ANSI 50BF<br />
Number of stages 2<br />
Current start<br />
0.1A to 4A (1A) / 0.5A to 20A (5A) (step 0.01A)<br />
Delay time<br />
0.05 to 1s (step 0.01s)<br />
Shortest release time<br />
approx. 10ms<br />
Timer tolerance<br />
± 1% of setting value or 10ms<br />
Automatic reclosure – ANSI 79<br />
Synchronism check – ANSI 25<br />
Number of automatic reclosures up to 8<br />
Program<br />
only 1-pole<br />
only 3-pole<br />
1 or 3-pole<br />
Voltage check<br />
discrimination between successful and<br />
non-successful reclose attempts<br />
Action times<br />
0.01 to 30 s (step 0.01s)<br />
Dead times<br />
0.01 to 1800 s (step 0.01s)<br />
Reclaim times<br />
0.5 to 30 s (step 0.01s)<br />
CLOSE command duration<br />
0.01 to 30 s (step 0.01s)<br />
Timer tolerance<br />
± 1% of setting value or 10ms<br />
Operating modes<br />
Line dead / busbar dead V 1 /V 2 <<br />
Synchronism V 1 >/V 2 ><br />
Permissible voltage difference 1 to 50 V (step 1V)<br />
Permissible frequence difference<br />
0.01 to 1 Hz (step 0.01 Hz)<br />
Permissible angle difference 1 to 60° (step 1)<br />
Supervision time<br />
0.01 to 30 s (step 0.01s)<br />
30 Siemens SIP 4.2 · 08/99