<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Description<br />

Application<br />

The <strong>7SA522</strong> relay provides<br />

full scheme distance protection<br />

and incorporates all functions<br />

usually required <strong>for</strong> the<br />

protection of a power line.<br />

The relay is designed to provide<br />

fast and selective fault<br />

clearance on transmission<br />

and subtransmission overhead<br />

lines and cables. This<br />

contributes towards improved<br />

stability and availability<br />

of your electrical power<br />

transmission system. The power<br />

system star point can<br />

be solid or impedance grounded<br />

(earthed). The <strong>7SA522</strong> is<br />

suitable <strong>for</strong> single- and<br />

three-phase tripping applications<br />

with and without pilot-<br />

(tele-) protection schemes.<br />

The effect of apparent impedances<br />

in unfaulted fault<br />

loops is eliminated by a<br />

sophisticated and improved<br />

method which uses pattern<br />

recognition with symmetrical<br />

components and load compensation.<br />

The correct phase<br />

selection is essential <strong>for</strong> selective<br />

tripping and reliable<br />

fault location.<br />

During network power<br />

swings an improved power<br />

swing blocking feature prevents<br />

the distance protection<br />

from unwanted tripping and<br />

optionally provides controlled<br />

tripping in the event of loss<br />

of synchronism (out of step).<br />

This function guarantees power<br />

transmission even under<br />

critical network operating<br />

conditions.<br />

Maximum Lifetime and<br />

Reliability<br />

The <strong>7SA522</strong> hardware is based<br />

on 20 years of experience<br />

by Siemens with numerical<br />

protection. State-of-theart<br />

32 bit microprocessor<br />

technology is employed.<br />

Naturally the device complies<br />

with the latest standards and<br />

techniques <strong>for</strong> electromagnetic<br />

compatibility. The overall<br />

number of electronic components<br />

is substantially reduced<br />

by using large-scale integrated<br />

circuits.<br />

The relay software is designed<br />

in accordance with high<br />

level programming language<br />

techniques. The long experience<br />

in manufacturing numerical<br />

relays provide the basis<br />

<strong>for</strong> a modern software structure.<br />

This along with modern<br />

manufacturing techniques<br />

and quality controls ensure<br />

maximum lifetime and reliability.<br />

Cost-effective power<br />

system management<br />

The <strong>SIPROTEC</strong> 4 units are<br />

numerical relays which also<br />

provide control and monitoring<br />

functions and there<strong>for</strong>e<br />

support the user in view of a<br />

cost-effective power system<br />

management. They contribute<br />

towards the reliable<br />

supply of electric power to<br />

the customers.<br />

Local operation has been designed<br />

according to ergonomic<br />

criteria. Large, easy-toread<br />

displays are a major design<br />

aim.<br />

The <strong>SIPROTEC</strong> 4 units have<br />

a uni<strong>for</strong>m design and a degree<br />

of functionality which<br />

represents a whole new<br />

level of quality in protection<br />

and control. If the application<br />

requirements change the<br />

relays may be adapted<br />

quickly by entering new settings<br />

without any additional<br />

hardware costs.<br />

The use of powerful microcontrollers<br />

and the application<br />

of digital measured value<br />

conditioning and processing<br />

largely suppresses the influence<br />

of higher-frequency<br />

transients, harmonics and<br />

DC components.<br />

Back-up protection<br />

The unit can also be used as<br />

backup distance and overcurrent<br />

protection <strong>for</strong> all types<br />

of differential protection<br />

equipment.<br />

Add-on protective<br />

functions<br />

The <strong>7SA522</strong> incorporates several<br />

protective functions<br />

usually required <strong>for</strong> transmission<br />

line protection. These<br />

are<br />

− High-resistance earth fault<br />

protection<br />

− Phase overcurrent protection<br />

− STUB bus overcurrent stage<br />

− Overvoltage protection<br />

− Automatic reclosure<br />

− Synchrocheck<br />

− Circuit breaker failure protection.<br />

Programmable logic<br />

The integrated programmable<br />

logic functions allow the<br />

user to implement his own<br />

functions <strong>for</strong> the automation<br />

of a switchgear (interlocking)<br />

or a substation via a graphic<br />

user interface. The user can<br />

also generate user-defined<br />

messages and logical combinations<br />

of internal or external<br />

signals.<br />

Local and remote<br />

communication<br />

The <strong>SIPROTEC</strong> 4 units provide<br />

several serial communication<br />

interfaces <strong>for</strong> various<br />

tasks:<br />

− Front interface <strong>for</strong> connecting<br />

a PC<br />

− IEC system interface <strong>for</strong><br />

connecting to a control<br />

system via<br />

IEC 60870-5-103 or<br />

Profibus-FMS/DP,<br />

Modbus RTU,<br />

DNP3.0<br />

− Prepared <strong>for</strong> Ethernet<br />

(UCA)<br />

− Modem interface <strong>for</strong> connecting<br />

a PC via modem<br />

and/or starcoupler<br />

− Time synchronization via<br />

IRIG-B/SCADA (DCF 77)<br />

The <strong>7SA522</strong> relay has two<br />

additional optional interfaces<br />

<strong>for</strong> communication with the<br />

remote relay or process bus.<br />

It is there<strong>for</strong>e well prepared<br />

<strong>for</strong> future communication<br />

standards.<br />

Operational indications<br />

and fault indications with<br />

time stamp<br />

The <strong>SIPROTEC</strong> 4 units provide<br />

extensive data <strong>for</strong> fault<br />

analysis as well as control.<br />

All indications listed below<br />

are protected against power<br />

supply failure.<br />

− Fault event record<br />

The last eight fault cases<br />

are always stored in the<br />

unit. All fault recordings<br />

are time stamped with a<br />

resolution of 1 ms.<br />

− Operational indications<br />

All indications that are not<br />

directly associated with<br />

the fault (e.g. operating or<br />

switching actions) are stored<br />

in the status indication<br />

buffer. The time resolution<br />

is 1 ms.<br />