Description<br />
Application<br />
The <strong>7SA522</strong> relay provides<br />
full scheme distance protection<br />
and incorporates all functions<br />
usually required <strong>for</strong> the<br />
protection of a power line.<br />
The relay is designed to provide<br />
fast and selective fault<br />
clearance on transmission<br />
and subtransmission overhead<br />
lines and cables. This<br />
contributes towards improved<br />
stability and availability<br />
of your electrical power<br />
transmission system. The power<br />
system star point can<br />
be solid or impedance grounded<br />
(earthed). The <strong>7SA522</strong> is<br />
suitable <strong>for</strong> single- and<br />
three-phase tripping applications<br />
with and without pilot-<br />
(tele-) protection schemes.<br />
The effect of apparent impedances<br />
in unfaulted fault<br />
loops is eliminated by a<br />
sophisticated and improved<br />
method which uses pattern<br />
recognition with symmetrical<br />
components and load compensation.<br />
The correct phase<br />
selection is essential <strong>for</strong> selective<br />
tripping and reliable<br />
fault location.<br />
During network power<br />
swings an improved power<br />
swing blocking feature prevents<br />
the distance protection<br />
from unwanted tripping and<br />
optionally provides controlled<br />
tripping in the event of loss<br />
of synchronism (out of step).<br />
This function guarantees power<br />
transmission even under<br />
critical network operating<br />
conditions.<br />
Maximum Lifetime and<br />
Reliability<br />
The <strong>7SA522</strong> hardware is based<br />
on 20 years of experience<br />
by Siemens with numerical<br />
protection. State-of-theart<br />
32 bit microprocessor<br />
technology is employed.<br />
Naturally the device complies<br />
with the latest standards and<br />
techniques <strong>for</strong> electromagnetic<br />
compatibility. The overall<br />
number of electronic components<br />
is substantially reduced<br />
by using large-scale integrated<br />
circuits.<br />
The relay software is designed<br />
in accordance with high<br />
level programming language<br />
techniques. The long experience<br />
in manufacturing numerical<br />
relays provide the basis<br />
<strong>for</strong> a modern software structure.<br />
This along with modern<br />
manufacturing techniques<br />
and quality controls ensure<br />
maximum lifetime and reliability.<br />
Cost-effective power<br />
system management<br />
The <strong>SIPROTEC</strong> 4 units are<br />
numerical relays which also<br />
provide control and monitoring<br />
functions and there<strong>for</strong>e<br />
support the user in view of a<br />
cost-effective power system<br />
management. They contribute<br />
towards the reliable<br />
supply of electric power to<br />
the customers.<br />
Local operation has been designed<br />
according to ergonomic<br />
criteria. Large, easy-toread<br />
displays are a major design<br />
aim.<br />
The <strong>SIPROTEC</strong> 4 units have<br />
a uni<strong>for</strong>m design and a degree<br />
of functionality which<br />
represents a whole new<br />
level of quality in protection<br />
and control. If the application<br />
requirements change the<br />
relays may be adapted<br />
quickly by entering new settings<br />
without any additional<br />
hardware costs.<br />
The use of powerful microcontrollers<br />
and the application<br />
of digital measured value<br />
conditioning and processing<br />
largely suppresses the influence<br />
of higher-frequency<br />
transients, harmonics and<br />
DC components.<br />
Back-up protection<br />
The unit can also be used as<br />
backup distance and overcurrent<br />
protection <strong>for</strong> all types<br />
of differential protection<br />
equipment.<br />
Add-on protective<br />
functions<br />
The <strong>7SA522</strong> incorporates several<br />
protective functions<br />
usually required <strong>for</strong> transmission<br />
line protection. These<br />
are<br />
− High-resistance earth fault<br />
protection<br />
− Phase overcurrent protection<br />
− STUB bus overcurrent stage<br />
− Overvoltage protection<br />
− Automatic reclosure<br />
− Synchrocheck<br />
− Circuit breaker failure protection.<br />
Programmable logic<br />
The integrated programmable<br />
logic functions allow the<br />
user to implement his own<br />
functions <strong>for</strong> the automation<br />
of a switchgear (interlocking)<br />
or a substation via a graphic<br />
user interface. The user can<br />
also generate user-defined<br />
messages and logical combinations<br />
of internal or external<br />
signals.<br />
Local and remote<br />
communication<br />
The <strong>SIPROTEC</strong> 4 units provide<br />
several serial communication<br />
interfaces <strong>for</strong> various<br />
tasks:<br />
− Front interface <strong>for</strong> connecting<br />
a PC<br />
− IEC system interface <strong>for</strong><br />
connecting to a control<br />
system via<br />
IEC 60870-5-103 or<br />
Profibus-FMS/DP,<br />
Modbus RTU,<br />
DNP3.0<br />
− Prepared <strong>for</strong> Ethernet<br />
(UCA)<br />
− Modem interface <strong>for</strong> connecting<br />
a PC via modem<br />
and/or starcoupler<br />
− Time synchronization via<br />
IRIG-B/SCADA (DCF 77)<br />
The <strong>7SA522</strong> relay has two<br />
additional optional interfaces<br />
<strong>for</strong> communication with the<br />
remote relay or process bus.<br />
It is there<strong>for</strong>e well prepared<br />
<strong>for</strong> future communication<br />
standards.<br />
Operational indications<br />
and fault indications with<br />
time stamp<br />
The <strong>SIPROTEC</strong> 4 units provide<br />
extensive data <strong>for</strong> fault<br />
analysis as well as control.<br />
All indications listed below<br />
are protected against power<br />
supply failure.<br />
− Fault event record<br />
The last eight fault cases<br />
are always stored in the<br />
unit. All fault recordings<br />
are time stamped with a<br />
resolution of 1 ms.<br />
− Operational indications<br />
All indications that are not<br />
directly associated with<br />
the fault (e.g. operating or<br />
switching actions) are stored<br />
in the status indication<br />
buffer. The time resolution<br />
is 1 ms.<br />