<strong>SIPROTEC</strong> 4 – <strong>7SA522</strong><br />

<strong>Distance</strong> <strong>Protection</strong> <strong>Relay</strong> <strong>for</strong> <strong>Transmission</strong> Lines<br />

Typical connections<br />

Typical connection of<br />

current and voltage<br />

trans<strong>for</strong>mers<br />

The typical AC connection has<br />

3 phase current trans<strong>for</strong>mers<br />

and 3 phase-ground (earth)<br />

voltage trans<strong>for</strong>mers. The<br />

neutral (residual) current (I N =<br />

3I 0 ) is measured via the I4-<br />

current trans<strong>for</strong>mer as the<br />

sum of the three phase currents.<br />

The zero sequence voltage<br />

3V 0 is not measured externally<br />

but calculated by the<br />

microprocessor.<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

52<br />

Circuit<br />

breaker<br />

I N<br />

V N<br />

Flush mounting<br />

Q1<br />

Q2<br />

Q3<br />

Q4<br />

Q5<br />

Q6<br />

Q7<br />

Q8<br />

R15<br />

R16<br />

R17<br />

R18<br />

Busbar<br />

I A(L1)<br />

I B(L2)<br />

I C(L3)<br />

V A(L1)<br />

V B(L2)<br />

I 4<br />

V 4<br />

V C(L3)<br />

R13<br />

R14<br />

Line<br />

Figure 26<br />

Voltage trans<strong>for</strong>mer connections:<br />

Separate open<br />

delta trans<strong>for</strong>mer<br />

The three phase-to-ground<br />

(earth) voltage trans<strong>for</strong>mers<br />

are typically connected as illustrated.<br />

The V4 voltage<br />

trans<strong>for</strong>mer measures the<br />

zero sequence voltage 3V 0<br />

(Ven) via a separate VT (open<br />

delta connection). This ensures<br />

an additional voltage supervision.<br />

The V4 trans<strong>for</strong>mer can also<br />

be connected to a separate<br />

voltage trans<strong>for</strong>mer <strong>for</strong> free<br />

assignable voltage measurement<br />

(Vx).<br />

A (L1)<br />

B (L2)<br />

C (L3)<br />

Circuit<br />

breaker<br />

52<br />

R15<br />

R16<br />

R17<br />

R18<br />

R13<br />

R14<br />

V A(L1)<br />

V B(L2)<br />

V C(L3)<br />

V 4<br />

Busbar<br />

Line<br />

Figure 27<br />

18 Siemens SIP 4.2 · 08/99