Case Study<br />
Circuit Breaker<br />
CB controlled by XCBR: “Warning” state <strong>for</strong> health (i.e. Warning<br />
state <strong>for</strong> the EE<strong>Health</strong> data <strong>of</strong> XCBR)<br />
The impact <strong>of</strong> this health status on the per<strong>for</strong>mance <strong>of</strong> the<br />
generic GAPC control function:<br />
XCBR → GAPC<br />
XCBR → CILO (Bay) → CILO (Station) → GAPC<br />
XCBR → CSWI → CILO (Bay) → CILO (St.) → GAPC<br />
The total effect <strong>of</strong> the Warning health status <strong>of</strong> the CB on the<br />
GAPC is determined as:<br />
max{ min(M) + min(V.H, M, M) + min(V.H, V.H, M, M) }<br />
= Medium<br />
© ABB Group<br />
March 3, 2011 | Slide 17