• Wall mounted unit • FXAQ20-63MVE<br />

2 Specifications<br />

2-1 Technical specifications<br />

FXAQ-MVE 20 25 32 40 50 63<br />

COOLING CAPACITY (1) kW 2.2 2.8 3.6 4.5 5.6 7.1<br />

HEATING CAPACITY (2) kW 2.5 3.2 4.0 5.0 6.3 8.0<br />

NOMINAL INPUT Cooling W 16 22 27 20 27 50<br />

Heating W 24 27 32 20 32 60<br />

DIMENSIONS HxWxD mm 290x795x230 290x1,050x230<br />

WEIGHT kg 11 14<br />

COLOUR white (10Y9/0.5) white (B-272)<br />

SOUND LEVEL Sound pressure high dBA 35 36 37 39 42 46<br />

low dBA 29 29 29 34 36 39<br />

Sound power dBA * * * * * *<br />

FAN Air flow rate high m 3 /h 450 480 540 720 900 1,140<br />

low m 3 /h 270 300 330 540 720 840<br />

Type<br />

cross flow fan<br />

Motor output W 40 43<br />

Drive<br />

direct drive<br />

HEAT EXCHANGER Rows x stages x fin pitch mm 2x14x1.4<br />

Face area m 2 0.161<br />

AIR FILTER<br />

resin net (washable)<br />

REFRIGERANT CONTROL<br />

electronic expansion valve<br />

TEMPERATURE CONTROL<br />

microprocessor thermostat for cooling and heating<br />

PIPING CONNECTIONS Liquid flare mm ø 6.4 ø 9.5<br />

Gas flare mm ø 12.7 ø 15.9<br />

Drain mm VP13, external diameter 18, internal diameter 14<br />

Sound absorbing insulation material<br />

foamed polystyrene / foamed polyethylene<br />

3D039370<br />

NOTES<br />

1 Nominal cooling capacities are based on:<br />

• Indoor temperature: 27°CDB, 19°CWB<br />

• Outdoor temperature: 35°CDB<br />

• Equivalent refrigerant piping: 5m (horizontal)<br />

2 Nominal heating capacities are based on:<br />

• Indoor temperature: 20°CDB<br />

• Outdoor temperature: 7°CDB, 6°CWB<br />

• Equivalent refrigerant piping: 5m (horizontal)<br />

3 Capacities are net including a deduction for cooling (an addition for<br />

heating) for indoor fan motor heat.<br />

* <strong>data</strong> were not available at the time of publication<br />

2<br />

2-2 Electrical specifications<br />

FXAQ-MVE 20 25 32 40 50 63<br />

CURRENT Minimum circuit amps (MCA) A 0.3 0.4 0.4 0.4 0.4 0.6<br />

Maximum fuse amps (MFA) (5) A 15<br />

POWER SUPPLY V1 1 ~, 50Hz, 220-240V<br />

VOLTAGE RANGE Min~max V 198/264<br />

INDOOR FAN MOTOR Fan motor rated output W 40 43<br />

Full load amps (FLA) A 0.2 0.3 0.3 0.3 0.3 0.5<br />

4D034907B<br />

NOTES<br />

1 Voltage range: units are suitable for use on electrical systems where<br />

voltage supplied to unit terminals is not below or above listed range limits.<br />

2 Maximum allowable voltage range variation between phases is 2%.<br />

3 MCA/MFA:<br />

MCA = 1.25 x FLA<br />

MFA ≤ 4 x FLA<br />

next lower standard fuse rating minimum 15A.<br />

4 Select wire size based on the MCA.<br />

5 Instead of a fuse, use a circuit breaker<br />

6 For more details concerning conditional connections, see<br />

http://www.daikineurope.com/extranet, select "Daikin<br />

Documentation" and select "conditional connection", "the<br />

requested product type" and "English" from the drop down lists,<br />

click the search button.<br />

Finally, click on the document title of your choice.<br />

• Systems • Indoor Units 3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!