Resi9<br />

RCBO residual current<br />

circuit breaker<br />

Residual current circuit breakers<br />

High sensitivity (30 mA)<br />

Protection against electric shocks by direct contact.<br />

Use at the incoming end of several feeders:<br />

> > recommended for all power sockets.<br />

> > compulsory for all equipment in bathrooms, outdoors, etc.<br />

Medium sensitivity (300mA) TD<br />

Protection against:<br />

> > fire following an insulation fault.<br />

> > electric shocks by indirect contact.<br />

> > in the event of tripping of a high-sensitivity residual current protection device<br />

downstream, maintains power for the other circuits.<br />

Use in residential units at the incoming end of the main switchboard.<br />

Type AC Width Operating<br />

voltage<br />

Sensitivity Rating Cat. no.<br />

9 mm (V AC) (mA) (A)<br />

module<br />

2P 4 230 30 63 R9R81263<br />

30 100 R9R81291<br />

300TD 100 R9R85291<br />

Degree of pollution: 2.<br />

Degree of protection (BS EN 60529): IP20B.<br />

Connection:<br />

> > Copper cable:<br />

--<br />

rigid: Max. 35 mm²<br />

--<br />

flexible: Max. 25 mm².<br />

> > tightening torque: 3.5 N.m.<br />

Compliance with<br />

standards<br />

BS EN 61008-1<br />

35