1cSTHIG
1cSTHIG
1cSTHIG
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Resi9<br />
RCBO residual current<br />
circuit breaker<br />
Residual current circuit breakers<br />
High sensitivity (30 mA)<br />
Protection against electric shocks by direct contact.<br />
Use at the incoming end of several feeders:<br />
> > recommended for all power sockets.<br />
> > compulsory for all equipment in bathrooms, outdoors, etc.<br />
Medium sensitivity (300mA) TD<br />
Protection against:<br />
> > fire following an insulation fault.<br />
> > electric shocks by indirect contact.<br />
> > in the event of tripping of a high-sensitivity residual current protection device<br />
downstream, maintains power for the other circuits.<br />
Use in residential units at the incoming end of the main switchboard.<br />
Type AC Width Operating<br />
voltage<br />
Sensitivity Rating Cat. no.<br />
9 mm (V AC) (mA) (A)<br />
module<br />
2P 4 230 30 63 R9R81263<br />
30 100 R9R81291<br />
300TD 100 R9R85291<br />
Degree of pollution: 2.<br />
Degree of protection (BS EN 60529): IP20B.<br />
Connection:<br />
> > Copper cable:<br />
--<br />
rigid: Max. 35 mm²<br />
--<br />
flexible: Max. 25 mm².<br />
> > tightening torque: 3.5 N.m.<br />
Compliance with<br />
standards<br />
BS EN 61008-1<br />
35