Easy9 & Resi9<br />

Affordable circuit protection<br />

you can depend on<br />

Compliant<br />

metal consumer unit<br />

BS 7671:2008<br />

Amendment 3 (2015)


Schneider Electric is a global specialist<br />

in energy management. Established as a<br />

circuit breaker designer and manufacturer<br />

in France since 1920, Schneider Electric<br />

are the worldwide leader of electrical<br />

protection technologies, present in more<br />

than 100 countries.<br />

Domestic Circuit Protection BS7671 Amendment 3<br />

Regulation 421.1.201 – What is it and when does it<br />

come into force?<br />

> From January 2015 Amendment No. 3 to BS7671 IET Wiring Regulations prescribes<br />

that within domestic (household) premises, consumer units and similar switchgear<br />

assemblies shall have their enclosures manufactured from non-combustible material,<br />

or be enclosed in a cabinet or enclosure constructed of non-combustible material and<br />

comply with product standard BS EN 61439-3.<br />

> Although regulation 421.1.201 will appear in BS7671 from January 2015, it is<br />

expected that the implementation date for this regulation with be 1st January<br />

2016, however this does not preclude compliance particularly in terms of design and<br />

specification prior to this date.<br />

What is the intention behind this change to BS7671?<br />

> As far as it is reasonably practical, to contain any fire within the<br />

enclosure and minimise flames from escaping, caused mainly as a<br />

result of poorly installed connections.<br />

What is a non-combustible enclosure?<br />

> At the time of this publication it is expected that regulation 421.1.201 will advise<br />

that an example of a non combustible materials is a ferrous metal e.g. steel. Therefore<br />

a non combustible enclosure includes base, cover, door and any components e.g.<br />

hinges necessary to contain the fire. Blanks and devices are contained within the non<br />

combustible enclosure.<br />

1


Easy9<br />

Affordable circuit protection<br />

you can depend on<br />

Introduction<br />

A complete range of modular devices...................................................................................... p.3<br />

New Easy9 circuit protection provides long-lasting protection.................................................. p.5<br />

Product information<br />

Metal enclosures..................................................................................................................... p.9<br />

Switch-disconnectors............................................................................................................ p.10<br />

RCCB residual current circuit breakers.................................................................................. p.11<br />

Miniature circuit breaker ........................................................................................................ p.12<br />

RCBO residual current devices.............................................................................................. p.13<br />

Product selector.................................................................................................................... p.14<br />

Technical<br />

Technical information ............................................................................................................ p.17<br />

Resi9<br />

The complete residential<br />

circuit protection offer<br />

Introduction<br />

Resi9 Consumer Units........................................................................................................... p.28<br />

Features & benefits................................................................................................................ p.29<br />

Resi9 overview...................................................................................................................... p.30<br />

Resi9 overview diagram......................................................................................................... p.31<br />

Product information<br />

Resi9...................................................................................................................................... p33<br />

Switch-disconnector.............................................................................................................. p.34<br />

RCCB Residual Current Circuit Breaker................................................................................. p.35<br />

RCBO Residual Current Device............................................................................................. p.36<br />

Miniature Circuit Breaker......................................................................................................... p37<br />

Terminal Block....................................................................................................................... p.38<br />

Quick Selector<br />

Select consumer unit............................................................................................................. p.40<br />

Select devices....................................................................................................................... p.41<br />

Technical Guide<br />

Resi9 - metal unit dimensions................................................................................................ p.43<br />

2


Easy9<br />

Affordable circuit protection<br />

you can depend on<br />

A complete range of modular<br />

devices<br />

Just what you need from circuit protection<br />

We work closely with electricians worldwide to help bring safe<br />

electricity to homes and buildings around the globe. Now you can<br />

take pride in delivering to your customers the enhanced safety<br />

and peace of mind they deserve.<br />

3


“I would recommend Easy9<br />

to anyone”<br />

New, robust circuit protection<br />

from a brand you trust<br />

The new Easy9 range better supports your<br />

business as an electrician, helping you to be<br />

more effective through:<br />

> A high-quality, user-friendly design<br />

> Availability when and where you need it<br />

> Reliability you can count on<br />

4


Easy9<br />

Affordable circuit protection<br />

you can depend on<br />

New Easy9 circuit protection<br />

provides long-lasting protection<br />

Easy9 brings you the quality, peace of mind, and reliability of<br />

a high-end device at a mid-range price. Thanks to consistent<br />

design and high manufacturing standards, Easy9 is a durable<br />

range you can be proud to install.<br />

> Guaranteed compliance to product standards<br />

> Certification by independent authorities<br />

Since<br />

1920<br />

Leader in electrical<br />

switchgear<br />

5


Quality<br />

- 100% designed and manufactured by Schneider Electric<br />

- All sites with ISO 9000 certification<br />

- Brand selected everywhere for industry, hospitals and airports<br />

Availability<br />

- Always available at your distributor<br />

- Complete coverage of protection features<br />

- Large assortment of ratings<br />

Customer satisfaction<br />

- Highly reliable and safe circuit protection<br />

- Dependable power supply<br />

Safety<br />

- Protection from electric shocks, overloads and short circuits<br />

- Compliance to standards<br />

Time saving<br />

- Consistent design and connection features<br />

- One-stop shopping for all parts<br />

- Proven robustness to withstand wear and tear<br />

6


Easy9<br />

Easy 9 at a glance<br />

Affordable circuit protection<br />

you can depend on<br />

Schneider Electric warranty<br />

Comprehensive range<br />

Full compliance<br />

with international<br />

IEC standards 3rd<br />

party certification<br />

Installer-friendly wiring<br />

with only 1 screwdriver<br />

7


Class II front face<br />

Full range coherence<br />

Compliant<br />

metal consumer unit<br />

BS 7671:2008<br />

Amendment 3 (2015)<br />

<br />

Clear and visible<br />

production information.<br />

Whatever the toggle<br />

position<br />

Full trip indication on<br />

the front panel by<br />

position of handle<br />

On-Off engraved<br />

Neutral terminal<br />

identification engraved<br />

8


Easy9<br />

Metal enclosures<br />

BS7671 Amendment 3 Compliant<br />

Description<br />

The surface mounting enclosure consists of:<br />

■■<br />

Metal surface mounting enclosure with:<br />

■■<br />

Multiple cable entry points and rear knock out slots<br />

■■<br />

Secure fixed DIN rail<br />

■■<br />

Earth terminal block and a neutral terminal blocks fitted as standard<br />

■■<br />

Secure busbar shield<br />

■■<br />

Standard consumer units up to 20 usable ways<br />

■■<br />

Earthed cover<br />

■■<br />

Enclosure colour: White RAL 9003.<br />

Compliant<br />

metal consumer unit<br />

BS 7671:2008<br />

Amendment 3 (2015)<br />

<br />

Consumer Unit<br />

Reference Description No. Usable Ways<br />

EZ92MCUL EZ9 2 Way Metal CU 2<br />

EZ94MCUL EZ9 4 Way Metal CU 4<br />

EZ96MCUL EZ9 6 Way Metal CU 6<br />

EZ98MCUL EZ9 8 Way Metal CU 8<br />

EZ912MCUL EZ9 12 Way Metal CU 12<br />

EZ916MCUL EZ9 16 Way Metal CU 16<br />

EZ920MCUL EZ9 20 Way Metal CU 20<br />

Consumer unit with switch/RCDs fitted<br />

Reference Description No. Usable Ways<br />

EZ9R4R4MCUL EZ9 4+4W 100A Sw, 63A RCCBx2 Metal 4+4 dual RCCB<br />

EZ9R6R6MCUL EZ9 6+6W 100A Sw, 63A RCCBx2 Metal 6+6 dual RCCB<br />

EZ9R6R6DMCUL EZ9 6+6W 100A Sw, 80A RCCBx2 Metal 6+6 dual RCCB<br />

EZ9R8R8DMCUL EZ9 8+8W 100A Sw, 80A RCCBx2 Metal 8+8 dual RCCB<br />

EZ9S2R5R5DMCUL EZ9 2+5+5 100A Sw, 80A RCCBx2 Metal cw 2 unprotected ways 2,5,5 dual RCCB<br />

EZ9S2R7R7DMCUL EZ9 2+7+7 100A Sw, 80A RCCBx2 Metal cw 2 unprotected ways 2,7,7 dual RCCB<br />

Consumer unit with switch/RCDs fitted<br />

Reference Description No. Usable Ways<br />

Flexible Split Consumer Unit Including Incomers<br />

EZ9FS12MCUL<br />

EZ9 12 Way FS 100A Sw, 80A RCCBx2 Metal<br />

up to 4 unprotected ways with max splits of 4/7/7<br />

EZ9FS16MCUL<br />

EZ9 16 Way FS 100A Sw, 80A RCCBx2 Metal<br />

up to 4 unprotected ways with max splits of 4/9/9<br />

Populated consumer unit with switch/RCDs/MCBs fitted<br />

12 way flex split<br />

16 way flex split<br />

Reference Description No. Usable Ways<br />

EZ9R6R6MREL EZ9 6+6 Kitbox cw 8 MCB Metal 6+6 dual RCCB<br />

EZ9S2R5R5DMREL EZ9 2+5+5 Kitbox cw 8 MCB Metal Metal cw 2 unprotected ways 2,5,5 dual RCCB<br />

Garage consumer unit<br />

Reference Description No. Usable Ways<br />

EZ9GARAGE63L EZ9 garage unit cw 63A RCCB and 6 & 16A mcbs 2<br />

9


Easy9<br />

Switch-disconnectors<br />

Functions<br />

The switch-disconnectors are used for:<br />

■■<br />

Control (opening and closing of circuits under load).<br />

■■<br />

Disconnection of on-load electrical circuits already protected against overloads<br />

and short-circuits.<br />

2P<br />

Easy9 control switches<br />

Rating (Ie)<br />

63 A EZ9S16263<br />

100 A EZ9S16291<br />

Voltage rating (Ue)<br />

400 V, 50/60 Hz<br />

Width in 9-mm modules 4<br />

Certified compliant BSEN60947-3<br />

Connection<br />

6.5 mm<br />

PZ2<br />

Rigid copper cables<br />

y 50 mm 2<br />

Flexible copper cables<br />

y 35 mm 2<br />

Tightening torque: 3.5 Nm<br />

Tightening torque: 3.5 Nm<br />

20 mm<br />

10


Easy9<br />

RCCB residual current circuit<br />

breakers<br />

Functions<br />

■■<br />

Tripping in case of leakage current only.<br />

■■<br />

One RCCB protects several circuits when fitted upstream of a group of<br />

circuit breakers.<br />

2P<br />

Residual current circuit breakers AC<br />

Rating (In)<br />

30 mA<br />

63 A EZ9R33263<br />

80 A EZ9R33280<br />

Voltage rating (Ue)<br />

127 - 230 V, 50/60 Hz<br />

Width in 9-mm modules 4<br />

Certified compliant BSEN61008-1<br />

Additional feature<br />

Endurance (O-C) Electrical 2000 cycles<br />

Mechanical<br />

5000 cycles<br />

Conditional rated short With fuse<br />

3000 A<br />

circuit current (Inc/IDc) With Easy9 MCB<br />

3000 A<br />

Operating temperature<br />

-5°C to +60°C<br />

Storage temperature<br />

-40°C to +85°C<br />

Electrical feeding<br />

By the top and the bottom<br />

Connection<br />

DB406037<br />

6.5 mm<br />

PZ2<br />

Rigid copper cables<br />

1 to 35 mm 2 Tightening torque: 3.5 Nm<br />

Flexible copper cables<br />

1 to 25 mm 2 Tightening torque: 3.5 Nm<br />

16 mm<br />

11


Easy9<br />

Miniature circuit breaker<br />

1P<br />

Circuit breakers<br />

Rating (In) Curve B Curve C<br />

3 A EZ9F16103 -<br />

6 A EZ9F16106 EZ9F66106<br />

10 A EZ9F16110 EZ9F66110<br />

16 A EZ9F16116 EZ9F66116<br />

20 A EZ9F16120 EZ9F66120<br />

25 A EZ9F16125 -<br />

32 A EZ9F16132 EZ9F66132<br />

40 A EZ9F16140 EZ9F66140<br />

50 A EZ9F16150 EZ9F66150<br />

Width in 9-mm modules 2<br />

Certified compliant BS EN 60898-1<br />

Additional feature<br />

According to EN 60898-1<br />

Breaking capacity (Icn)<br />

Ph/N 230 V AC 6000 A<br />

Additional characteristics<br />

Endurance (O-C) Electrical 4,000 cycles<br />

Mechanical<br />

10,000 cycles<br />

Operating temperature<br />

-5°C to +60°C<br />

Storage temperature<br />

-40°C to +85°C<br />

Connection<br />

6.5 mm<br />

PZ2<br />

Rigid copper cables<br />

3 to 25 A 1 to 25 mm 2 Tightening torque: 2 Nm<br />

32 to 50 A 1 to 35 mm 2 Tightening torque: 3.5 Nm<br />

16 mm<br />

Flexible copper cables<br />

3 to 25 A 1 to 16 mm 2 Tightening torque: 2 Nm<br />

32 to 50 A 1 to 25 mm 2 Tightening torque: 3.5 Nm<br />

12


Easy9<br />

RCBO residual current devices<br />

Functions<br />

■■<br />

Protection from short-circuits.<br />

■■<br />

Protection of cable from overloads.<br />

■■<br />

Protection of persons from electric shocks by direct contact (30 mA sensitivity)<br />

■■<br />

Can be fitted instead of a miniature circuit breaker for complete protection of one<br />

circuit.<br />

The Earth Reference Cable "FE": enables RCD to protect users from electric shocks,<br />

even in case of supply neutral loss, neutral conductor breakage or supply voltage<br />

drop (FE= Functional Earth).<br />

1P+N<br />

Easy9 RCBO type A 30 mA<br />

Rating (In)<br />

B curve<br />

6 A EZ9D16806<br />

10 A EZ9D16810<br />

16 A EZ9D16816<br />

20 A EZ9D16820<br />

25 A EZ9D16825<br />

32 A EZ9D16832<br />

40 A EZ9D16840<br />

50 A EZ9D16850<br />

Voltage rating (Ue)<br />

230 V AC, 50 Hz<br />

Width in 9-mm modules 2<br />

Certified compliant BS EN 61009-1<br />

Connection<br />

5.5 mm<br />

PZ2<br />

Rigid copper cables<br />

L in 1 to 25 mm 2 Tightening torque: 2 Nm<br />

L and N out 1 to 16 mm 2 Tightening torque: 2 Nm<br />

14 mm<br />

16 mm<br />

Flexible copper cables<br />

L in 1 to 16 mm 2 Tightening torque: 2 Nm<br />

L and N out 1 to 10 mm 2 Tightening torque: 2 Nm<br />

13


Easy9<br />

Product selector<br />

Consumer Unit<br />

Reference Description No Ways<br />

EZ92MCUL EZ9 2 Way Metal CU 2<br />

EZ94MCUL EZ9 4 Way Metal CU 4<br />

EZ96MCUL EZ9 6 Way Metal CU 6<br />

EZ98MCUL EZ9 8 Way Metal CU 8<br />

EZ912MCUL EZ9 12 Way Metal CU 12<br />

EZ916MCUL EZ9 16 Way Metal CU 16<br />

EZ920MCUL EZ9 20 Way Metal CU 20<br />

Incoming Devices<br />

Reference Device Rating Description<br />

EZ9S16263 Switch 63A EZ9 Switch Disconnector 2P 63A 400V<br />

EZ9S16291 Switch 100A EZ9 Switch Disconnector 2P 100A 400V<br />

EZ9R33263 RCCB 63A, 30mA EZ9 RCCB 2P 63A 30mA AC-type 230V<br />

Residual Current Circuit Breaker<br />

EZ9R33280 RCCB 80A, 30mA EZ9 RCCB 2P 80A 30mA AC-type 230V<br />

Residual Current Circuit Breaker<br />

For split load applications select a split load kit<br />

Reference Description Rating<br />

EZ963R30KIT2 RCCB and cables 63A 30mA<br />

EZ980R30KIT2 RCCB and cables 80A 30mA<br />

OR<br />

Select consumer units with switch/RCD’s fitted<br />

Reference Description Total ways Un/P ways RCD1 ways RCD2 ways<br />

EZ9R4R4MCUL EZ9 4+4W 100A Sw, 63A RCCBx2 Metal 8 4 4<br />

EZ9R6R6MCUL EZ9 6+6W 100A Sw, 63A RCCBx2 Metal 12 6 6<br />

EZ9R6R6DMCUL EZ9 6+6W 100A Sw, 80A RCCBx2 Metal 12 6 6<br />

EZ9R8R8DMCUL EZ9 8+8W 100A Sw, 80A RCCBx2 Metal 16 8 8<br />

EZ9S2R5R5DMCUL EZ9 2+5+5 100A Sw, 80A RCCBx2 Metal 12 2 5 5<br />

EZ9S2R7R7DMCUL EZ9 2+7+7 100A Sw, 80A RCCBx2 Metal 16 2 7 7<br />

Flexible Split Consumer Unit Including Incomers Total ways Max Un/P ways Max RCD1 ways Max RCD2 ways<br />

EZ9FS12MCUL EZ9 12 Way FS 100A Sw, 80A RCCBx2 Metal 12 4 7 7<br />

EZ9FS16MCUL EZ9 16 Way FS 100A Sw, 80A RCCBx2 Metal 16 4 9 9<br />

Amendment 3 metal populated consumer unit with switch/RCDs/MCBs fitted Total ways Max Un/P ways Max RCD1 ways Max RCD2 ways<br />

EZ9R6R6MREL EZ9 6+6 Kitbox cw 8 MCB Metal 12 6 6<br />

EZ9S2R5R5DMREL EZ9 2+5+5 Kitbox cw 8 MCB Metal 12 2 5 5<br />

EZ9GARAGE63L Garage unit cw 63A RCCB and 6 & 16A mcbs 2 - 2 -<br />

14


Easy9<br />

Product selector<br />

Select devices and accessories<br />

Select outgoing devices or accessories<br />

SP 6kA MCBs (B curve)<br />

Reference Description Current Rating<br />

EZ9F16103 MCB (B curve) 3A<br />

EZ9F16106 MCB (B curve) 6A<br />

EZ9F16110 MCB (B curve) 10A<br />

EZ9F16116 MCB (B curve) 16A<br />

EZ9F16120 MCB (B curve) 20A<br />

EZ9F16125 MCB (B curve) 25A<br />

EZ9F16132 MCB (B curve) 32A<br />

EZ9F16140 MCB (B curve) 40A<br />

EZ9F16150 MCB (B curve) 50A<br />

SP 6kA MCBs (C curve)<br />

Reference Description Current Rating<br />

EZ9F66106 MCB (C curve) 6A<br />

EZ9F66110 MCB (C curve) 10A<br />

EZ9F66116 MCB (C curve) 16A<br />

EZ9F66120 MCB (C curve) 20A<br />

EZ9F66132 MCB (C curve) 32A<br />

EZ9F66140 MCB (C curve) 40A<br />

EZ9F66150 MCB (C curve) 50A<br />

SP 6kA 1 module RCBO (B curve)<br />

Reference Description Current rating<br />

EZ9D16806 RCBO 30mA 1 Module 1P&N 6A<br />

EZ9D16810 RCBO 30mA 1 Module 1P&N 10A<br />

EZ9D16816 RCBO 30mA 1 Module 1P&N 16A<br />

EZ9D16820 RCBO 30mA 1 Module 1P&N 20A<br />

EZ9D16825 RCBO 30mA 1 Module 1P&N 25A<br />

EZ9D16832 RCBO 30mA 1 Module 1P&N 32A<br />

EZ9D16840 RCBO 30mA 1 Module 1P&N 40A<br />

EZ9D16850 RCBO 30mA 1 Module 1P&N 50A<br />

Accessories<br />

Reference<br />

EZ9LKITL<br />

EZ9EARTHKIT<br />

EZ916BKIT<br />

SEDNBP3<br />

Description<br />

Door lock kit (for amendment 3 metal enclosure only)<br />

Additional earth terminals for clean earth or high integrity earthing<br />

Replacement/spare main busbar<br />

3 module blanking plate<br />

15


Easy9<br />

Technical<br />

information<br />

16


Easy9<br />

Technical information<br />

Metal Units<br />

Ref No. Type No Ways Height (mm) Width (mm) Depth (mm)<br />

EZ92MCUL Standard 2 247 186 100<br />

EZ94MCUL Standard 4 247 222 100<br />

EZ96MCUL Standard 6 247 258 100<br />

EZ98MCUL Standard 8 247 294 100<br />

EZ912MCUL Standard 12 247 366 100<br />

EZ916MCUL Standard 16 247 438 100<br />

EZ920MCUL Standard 20 247 510 100<br />

EZ9R4R4MCUL Split 8 247 366 100<br />

EZ9R6R6MCUL Split 12 247 438 100<br />

EZ9R6R6DMCUL Split 12 247 438 100<br />

EZ9R8R8DMCUL Split 16 247 510 100<br />

EZ9S2R5R5DMCUL Multiple 12 247 438 100<br />

EZ9S2R7R7DMCUL Multiple 16 247 510 100<br />

EZ9FS12MCUL Flex Split 12 247 438 100<br />

EZ9FS16MCUL Flex Split 16 247 510 100<br />

EZ9R6R6MREL Multiple 12 247 438 100<br />

EZ9S2R5R5DMREL Multiple 12 247 438 100<br />

EZ9GARAGE63L garage 2 247 186 100<br />

G<br />

86<br />

G<br />

G<br />

F<br />

D<br />

F<br />

29 41<br />

20 B<br />

20<br />

A<br />

Note: Incoming and outgoing devices must be<br />

selected separately from the devices section -<br />

only applies to EZ9**MCUL<br />

Incoming devices available<br />

• Switch disconnector 63A & 100A<br />

• RCCB’s 63A/30mA 80A/30mA<br />

Max. busbar splits - for split load<br />

8 way 2+4 to 4+2<br />

12 way 4+6 to 6+4<br />

16 way 6+8 to 8+6<br />

F<br />

D<br />

G<br />

E<br />

80<br />

G<br />

30<br />

21<br />

36<br />

200<br />

No. Of knockouts<br />

Dimensions (mm)<br />

25 x<br />

90mm<br />

32mm 25mm 20mm 18mm<br />

Ref No. A B D E F G<br />

EZ92MCUL 180 140 - 2* - 2 -<br />

EZ94MCUL 217 176 1 1 1 2 -<br />

EZ96MCUL 253 212 1 1 1 3 -<br />

EZ98MCUL 289 248 1 1 2 3 -<br />

EZ912MCUL 361 320 2 1 3 4 -<br />

EZ916MCUL 433 392 2 1 3 5 -<br />

EZ920MCUL 505 464 2 1 3 5 1<br />

EZ9S2R5R5DMREL 433 392 2 1 3 5 -<br />

EZ9S2R5R5DMCUL 433 392 2 1 3 5 -<br />

EZ9S2R7R7DMCUL 505 464 2 1 3 5 1<br />

EZ9R8R8DMCUL 505 464 2 1 3 5 1<br />

EZ9R5R5DMCUL 433 392 2 1 3 5 -<br />

EZ9R6R6DMCUL 433 392 2 1 3 5 -<br />

EZ9R6R6MCUL 433 392 2 1 3 5 -<br />

EZ9R6R6MREL 433 392 2 1 3 5 -<br />

EZ9R4R4MCUL 361 320 2 1 3 4 -<br />

EZ9FS12MCUL 433 392 2 1 3 5 -<br />

EZ9FS16MCUL 505 464 2 1 3 5 1<br />

EZ9GARAGE63L 180 140 - 2* - 2 -<br />

* 2W Version only, 1 x 32mm K/O in upper wall, 1 x K/O in back of box.<br />

Technical data<br />

Max. busbar current (A) 100A<br />

Max. operating voltage 230/240V @ 50Hz<br />

Max. cable capacity 25 mm2 (earth and neutral bars)<br />

Certification BS EN 61439-3<br />

17


Easy9<br />

Switch-disconnectors<br />

Position contact<br />

indication<br />

Suitable for isolation<br />

according to<br />

BSEN 60947-3 standard<br />

Manual control on front<br />

face by O-I lever<br />

Characteristics<br />

Main characteristics<br />

Operating category<br />

AC-22 A<br />

Permissible rated short-time withstand current (Icw) 12 Ie, 1 second<br />

Conditional rated short-circuit current (Inc) 5000 A<br />

Rated short-circuit closing current (Icm)<br />

15 Ie<br />

Additional characteristics<br />

Degree of protection<br />

(IEC 60529)<br />

Device only<br />

IP20<br />

Endurance (O-C) Mechanical 40 -100 A 8500 cycles<br />

Electrical 40-100 A 1500 cycles<br />

Operating temperature<br />

-5°C to +55°C<br />

Storage temperature<br />

-5°C to +70°C<br />

Tropicalisation (IEC 60068-1) Treatment 2<br />

(relative humidity 95 % to 55°C)<br />

Dimensions (mm)<br />

2P<br />

36<br />

5.5<br />

73<br />

61<br />

45<br />

82<br />

45<br />

3<br />

Weight (g)<br />

Type<br />

Easy9 switch-disconnector<br />

2P 175<br />

18


Easy9<br />

RCCB residual current circuit<br />

breakers<br />

Positive contact<br />

indication.<br />

Fault tripping indication<br />

on the front panel by<br />

the position of the<br />

handle (O - I engraved)<br />

Characteristics<br />

Main characteristics<br />

Rated impulse withstand voltage (Uimp)<br />

According to IEC 61008-1<br />

Making and breaking capacity (Im/IDm)<br />

4 kV<br />

500 A<br />

Additional characteristics<br />

Degree of protection<br />

(IEC 60529)<br />

Hazardous substances<br />

Tropicalisation (IEC 60068-1)<br />

Device only<br />

IP20<br />

RoHS 2003 compliant<br />

Treatment 2 (relative humidity 95 % to 55°C)<br />

Dimensions (mm)<br />

36<br />

2P<br />

5.5<br />

68<br />

61<br />

45<br />

82<br />

45<br />

7<br />

62<br />

Weight (g)<br />

Type<br />

Easy9 RCCB<br />

2P 195<br />

19


Easy9<br />

Miniature circuit breaker<br />

6 kA<br />

Easy9 circuit breakers combine the following<br />

functions:<br />

Circuit protection against short-circuit<br />

currents.<br />

Circuit protection against overload<br />

currents.<br />

Fault tripping indication<br />

on the front panel by the<br />

position of the handle<br />

(O - I engraved)<br />

Characteristics<br />

Main characteristics<br />

Voltage rating (Ue)<br />

Operating frequency<br />

Electrical feeding<br />

230/400 V AC<br />

50/60 Hz<br />

By the top and bottom<br />

Additional characteristics<br />

Degree of protection<br />

(IEC 60529)<br />

Hazardous substances<br />

Tropicalisation (IEC 60068-1)<br />

Device only<br />

IP20<br />

RoHS 2003 compliant<br />

Treatment 2 (relative<br />

humidity 95 % to 55°C)<br />

Dimensions (mm)<br />

1P<br />

18<br />

5.5<br />

72<br />

61<br />

45<br />

82<br />

45<br />

5<br />

70<br />

Weight (g)<br />

Type<br />

Easy9 MCB<br />

1P 100<br />

20


Easy9<br />

RCBO residual current devices<br />

6 kA<br />

Certified compliant BS EN 61009-1<br />

Test "T"<br />

Operating test button,<br />

on the front panel<br />

Fault tripping indication<br />

on the front panel by the<br />

position of the handle<br />

(O - I engraved)<br />

Cable length<br />

1000 mm<br />

Characteristics<br />

Main characteristics<br />

Endurance (O-C) Electrical 4000 cycles<br />

Mechanical<br />

10000 cycles<br />

Additional characteristics<br />

Degree of protection Device only IP20<br />

Overvoltage category (IEC 60364)<br />

IV<br />

Operating temperature<br />

-15°C to +60°C<br />

Storage temperature<br />

-40°C to +85°C<br />

Hazardous substances<br />

RoHS 2003 compliant<br />

Tropicalisation (IEC 60068-1)<br />

Treatment 2 (relative<br />

humidity 95 % to 55°C)<br />

Dimensions (mm)<br />

18<br />

5.5<br />

72<br />

61<br />

50<br />

110<br />

45<br />

5<br />

44<br />

Weight (g)<br />

Type<br />

Easy9 RCBO<br />

1P+N 180<br />

21


Easy9<br />

Miniature circuit breakers<br />

Selection<br />

Time current tripping curves<br />

MCB selection chart for household appliances<br />

1000<br />

100<br />

10<br />

t(s)<br />

Appliance Capacity MCB rating (A) Tripping<br />

curves<br />

Air conditioner 1 ton 16 "C"<br />

1.5 ton 20<br />

2 ton 20<br />

3 ton 25<br />

Refrigerator 165 litres 2<br />

285 litres 2<br />

1<br />

Water heater 1 kW 6 "B"<br />

3 kW 16<br />

0,1<br />

B<br />

C<br />

Electric kettle 1.5 kW 10<br />

0,01<br />

1<br />

3...5 6.4...9.6<br />

I / In<br />

Food processor<br />

(50 % load)<br />

200 W 1 "C"<br />

Vacuum cleaner 50 W 0.5<br />

Toaster 1.2 kW 6 "B"<br />

Cooking range 750 W 4<br />

2 kW 10<br />

4.5 kW 25<br />

Room heater 1 kW 6<br />

2 kW 10<br />

Washing<br />

machine<br />

300 W 2 "C"<br />

1.3 kW 10<br />

Electric iron 750 W 6 "B"<br />

1.25 kW 6<br />

22


Easy9<br />

Circuit protection<br />

Miniature circuit breakers<br />

Function<br />

■■<br />

Protection from short-circuits.<br />

■■<br />

Protection of cable from overload.<br />

MCB current rating<br />

Single-phase circuit<br />

Selection of circuit breakers according to the cables<br />

to be protected (BS 7671)<br />

■■<br />

PVC-insulated, copper, flexible or rigid cable.<br />

■■<br />

Ambient temperature:<br />

■■<br />

30°C in the open air (methods A, B, C, E)<br />

■■<br />

20°C if buried (method D),<br />

■■<br />

For other situations, refer to BS 7671standard (or UK wiring regulations).<br />

Cable cross section (in mm 2 ) 1.5 2.5 4 6 10 16 25 35<br />

Type of installation<br />

Maximum rating of the circuit breaker used there (in Ampere)<br />

A: in conduit or directly in thermally insulated wall, moulding, architrave, window frame<br />

Single core 10 16 25 32 40 50 80 80<br />

Multicore 10 16 25 32 40 50 70 80<br />

B: in conduit in a wall, in conduit trunking or cable duct on a wall, in building cavity<br />

Single core 16 20 32 40 50 70 100 125<br />

Multicore 16 20 25 32 50 50 80 80<br />

C: direct on a wall, suspended from ceilings, on unperforated cable tray, in masonry wall<br />

Single core or<br />

multicore<br />

16 25 32 40 63 80 100 125<br />

D: in conduit in the ground<br />

Multicore or<br />

single core<br />

20 25 32 40 50 70 80 80<br />

D: directly in the ground<br />

Multicore or<br />

single core<br />

20 25 32 40 63 80 100 125<br />

E: in free-air, on cable ladder, on perforated cable tray<br />

Multicore u 0.3 d 20 25 40 40 70 80 100 125<br />

d<br />

23


Easy9<br />

Residual current devices<br />

Function<br />

■■<br />

Protection of persons against electric shock by direct contact (30 mA).<br />

■■<br />

Protection of installations against the risk of fire (300 mA).<br />

■■<br />

Protection of persons against electric shock by indirect contact<br />

(100 mA to 300 mA).<br />

Operating principle<br />

Protection from electric shocks by direct contact:<br />

10 mA<br />

40 mA<br />

0.5 mA<br />

Muscular<br />

contraction<br />

Burns<br />

respiratory<br />

Severe burns<br />

ventricular<br />

fibrilation<br />

80 mA<br />

16 A<br />

RCD<br />

30 mA<br />

30 mA<br />

Perception<br />

Cardiac arrest<br />

1 A<br />

Research worldwide shows that the intensity of current flowing<br />

through the body determines the extent and severity of an<br />

electric shock.<br />

■■<br />

Injuries become serious when currents exceed 40 to<br />

50 mA during one second.<br />

■■<br />

Theoretically, a 150 mA current flows through the<br />

body when a person touches a 230 V energised<br />

conductor under dry conditions.<br />

By measuring the intensity difference between live and neutral conductors,<br />

RCDs actually detect the current flowing through the human body.<br />

If this current reaches the 30 mA limit, the RCD trips within a few milliseconds,<br />

so preventing injury or worse.<br />

Check RCDs regularly<br />

Test<br />

Testing the RCD every<br />

3 months enables<br />

detection of any event<br />

that may have impaired<br />

its operation<br />

24


Easy9<br />

Residual current devices<br />

Selection guide<br />

Selection<br />

Residual current sensitivity<br />

Protection from Residential Non-residential Sensitivity<br />

Electric shocks by direct contact<br />

bb<br />

Mandatory protection for all socket<br />

outlets<br />

bb<br />

Mandatory protection for all electrical<br />

equipment in bathroom<br />

bb<br />

Recommended for lighting circuits<br />

bb<br />

Mandatory protection for all<br />

socket outlets<br />

bb<br />

Mandatory protection for all<br />

equipement located<br />

bb<br />

Close to water points<br />

bb<br />

30 mA<br />

bb<br />

10 mA for all applications<br />

where required by the<br />

standard (e.g.: jacuzzi,<br />

swimming pools, etc.)<br />

Fire ignited by leakage current<br />

bb<br />

Recommended in old buildings<br />

(presence of dust or moisture)<br />

bb<br />

Mandatory in all locations under<br />

risk of fire or explosion<br />

bb<br />

Recommended in all premises<br />

under presence of dust, moisture,<br />

chemical agents…<br />

bb<br />

300 mA<br />

Electric shock by indirect contact<br />

bb<br />

All circuits in case of "TT" earthing<br />

system<br />

bb<br />

All circuits in case of "TT"<br />

earthing system<br />

bb<br />

100 mA or 300 mA<br />

Current rating: shall not be<br />

in excess of upstream MCB<br />

current rating<br />

Requirements from wiring regulation (411.3.3)<br />

Protection by means of a residual current protective device (RCD),<br />

shall be provided for:<br />

■■<br />

Socket outlets with a rated current not exceeding 20 A, that are for ordinary<br />

persons and intended for general use, mobile equipment with a current rating not<br />

exceeding 32 A for use outdoors.<br />

■■<br />

In rooms containing a bath or a shower.<br />

Bathroom<br />

25


Easy9<br />

Notes<br />

26


Resi9<br />

The complete residential<br />

circuit protection offer


Resi9 consumer units<br />

The Resi9 range of consumer units provides arguably the highest levels of residential<br />

circuit protection safety. With a wide range of switch disconnectors, RCDs and MCBs,<br />

complimented by a single pole RCBO.<br />

Providing speed of installation with safety in mind.<br />

All outgoing devices can be connected in seconds and with no incoming terminal to<br />

tighten, the correct mechanical connection force is guaranteed every time. For unused<br />

ways, Resi9’s unique fully encapsulated busbar system means that the highest levels of<br />

installer and end user protection are always guaranteed.<br />

Even with the front cover of the enclosure removed, the main busbar is protected to IP2X,<br />

meaning it remains finger safe but allows access with test probes by the installer. For<br />

energy management and safety, Resi9 can also accept a wide range of control devices.<br />

“What really sets Resi9 apart is the plug-on breaker concept<br />

and fully encapsulated busbars.”


Compliant<br />

metal consumer unit<br />

BS 7671:2008<br />

Amendment 3 (2015)<br />

Features and benefits<br />

Unique MCB/RCBO fixing system.<br />

Provides complete finger safety to IP2XB, bringing<br />

increased levels of safety to consumer unit design<br />

Tested in accordance with BS EN 61439-3<br />

Unrestricted cable entry can be made from any side<br />

Totally encapsulated busbar system<br />

Incoming devices can be ordered separately giving<br />

a multitude of combinations<br />

Type A single pole RCBO<br />

Increased levels of user safety with Class II device front faces<br />

Retains plug-on philosophy for speed of installation and<br />

guaranteed connections<br />

Insulated safety pull up shuttered terminals limit incorrect<br />

cable insertion<br />

Control devices may be installed on any outgoing way<br />

No extra mounting accessories required<br />

Lockable cover option also available


Resi9<br />

Option 1<br />

Incoming switch disconnector and outgoing<br />

RCBO’s<br />

Option 2<br />

Split load consumer unit using RCBO’s<br />

Option 3<br />

Incoming switch disconnector supplying two<br />

RCD protected sections<br />

Option 4<br />

Incoming switch disconnector with RCBO<br />

ways and two RCD protected sections<br />

30


Resi9<br />

The complete solution<br />

Insulated, safety pull up shuttered<br />

terminals<br />

Finger touch proof terminals (FTPT)<br />

Class II Front face<br />

Guaranteed plug-on connections<br />

Clear and visible product information<br />

whatever the toggle position<br />

31


Unique plug on system<br />

Quick and easy to install<br />

Type A RCBO devices<br />

50% less connections to torque test<br />

BS7671 compliant enclosures<br />

Guaranteed compliance to standards<br />

32


Resi9<br />

The complete residential circuit protection offer<br />

33


Resi9<br />

Switch-disconnector<br />

ON/OFF<br />

Switch-disconnector<br />

To ensure:<br />

> > control and disconnection of loaded electrical circuits.<br />

It must be protected:<br />

--<br />

against short circuits occurring downstream<br />

--<br />

against overloads; its rating must be at least equal to the rating of the upstream<br />

circuit breaker.<br />

Type Width Operating<br />

voltage<br />

Rating<br />

Cat. no.<br />

9 mm (V AC) (A)<br />

module<br />

2P 4 400 100 R9S87291<br />

1 3<br />

2 4<br />

Degree of pollution: 2.<br />

Degree of protection (BS EN 60529): IP20B.<br />

Connection:<br />

> > copper cable:<br />

--<br />

rigid: Max. 50 mm²<br />

--<br />

flexible: Max. 35 mm².<br />

> > tightening torque: 3.5 N.m.<br />

Compliance with standards BS EN 60947-3-1<br />

34


Resi9<br />

RCBO residual current<br />

circuit breaker<br />

Residual current circuit breakers<br />

High sensitivity (30 mA)<br />

Protection against electric shocks by direct contact.<br />

Use at the incoming end of several feeders:<br />

> > recommended for all power sockets.<br />

> > compulsory for all equipment in bathrooms, outdoors, etc.<br />

Medium sensitivity (300mA) TD<br />

Protection against:<br />

> > fire following an insulation fault.<br />

> > electric shocks by indirect contact.<br />

> > in the event of tripping of a high-sensitivity residual current protection device<br />

downstream, maintains power for the other circuits.<br />

Use in residential units at the incoming end of the main switchboard.<br />

Type AC Width Operating<br />

voltage<br />

Sensitivity Rating Cat. no.<br />

9 mm (V AC) (mA) (A)<br />

module<br />

2P 4 230 30 63 R9R81263<br />

30 100 R9R81291<br />

300TD 100 R9R85291<br />

Degree of pollution: 2.<br />

Degree of protection (BS EN 60529): IP20B.<br />

Connection:<br />

> > Copper cable:<br />

--<br />

rigid: Max. 35 mm²<br />

--<br />

flexible: Max. 25 mm².<br />

> > tightening torque: 3.5 N.m.<br />

Compliance with<br />

standards<br />

BS EN 61008-1<br />

35


Resi9<br />

RCBO Residual current device<br />

Residual current devices<br />

Protection against:<br />

> > cable overloads.<br />

> > short circuits.<br />

> > electric shocks by direct contact.<br />

Use in place of a circuit breaker, for circuits requiring protection against direct contacts:<br />

> > recommended for all power sockets.<br />

> > compulsory for all equipment in bathrooms, outdoors, etc.<br />

Type A Width Operating<br />

voltage<br />

Sensitivity Rating Cat. no.<br />

9 mm (V AC) (mA) (A) B curve<br />

module<br />

1P+N 2 230 30 6 R9D87806<br />

L in<br />

10 R9D87810<br />

I Δ<br />

16 R9D87816<br />

20 R9D87820<br />

FE N in<br />

N out L out<br />

32 R9D87832<br />

40 R9D87840<br />

50 R9D87850<br />

Class Type A<br />

Breaking capacity: 6000 A.<br />

Degree of pollution: 2.<br />

Degree of protection (BS EN 60529): IP20B.<br />

Connection:<br />

> > copper cable:<br />

--<br />

rigid: Max. 25 mm²<br />

--<br />

flexible: Max. 16 mm².<br />

> > tightening torque: 2 N.m.<br />

Compliance with<br />

standards<br />

BS EN 61009-1<br />

36


Resi9<br />

Circuit breaker<br />

Circuit breakers<br />

Protection against:<br />

> > cable overloads.<br />

> > short circuits.<br />

Type Width Operating Rating Cat. no.<br />

voltage<br />

9 mm (V AC) (A) B curve C curve<br />

module<br />

1P 2 230 3 R9F87103 R9F64103<br />

1<br />

6 R9F87106 R9F64106<br />

10 R9F87110 R9F64110<br />

16 R9F87116 R9F64116<br />

2<br />

20 R9F87120 R9F64120<br />

25 R9F87125 R9F64125<br />

32 R9F87132 R9F64132<br />

40 R9F87140 R9F64140<br />

50 R9F87150 R9F64150<br />

63 R9F87163 R9F64163<br />

--<br />

Breaking capacity: 6000 A.<br />

--<br />

Degree of pollution: 2.<br />

--<br />

Degree of protection (BS EN 60529): IP20B.<br />

--<br />

Type C MCB’s denoted by grey appearance<br />

--<br />

Connection:<br />

--<br />

> copper cable:<br />

--<br />

- rigid: ≤ 25 A: Max. 25 mm2, ≥ 32 A: Max. 35 mm2<br />

--<br />

- flexible: ≤ 25 A: Max. 16 mm2, ≥ 32 A: Max. 25 mm2.<br />

--<br />

> tightening torque:<br />

--<br />

- ≤ 25 A: 2 N.m.<br />

--<br />

- ≥ 32 A: 3.5 N.m.<br />

Compliance with<br />

standards<br />

BS EN 60898-1<br />

37


Resi9<br />

Terminal block<br />

Terminal block<br />

> > Distribution and sub-distribution of the electric<br />

> > power supply.<br />

Terminal block Width Cat. no.<br />

1P<br />

100 A 18 mm SE1100L<br />

Degree of protection (BS EN 60529): IP20B.<br />

Compliance with<br />

standards<br />

BS EN 60998-1<br />

38


Easy9<br />

Quick selector<br />

Quick selector<br />

39


Select Consumer Unit<br />

Compliant<br />

metal consumer unit<br />

BS 7671:2008<br />

Amendment 3 (2015)<br />

<br />

The surface mounting enclosure consists of:<br />

> > Metal surface mounting enclosure with:<br />

> > Multiple cable entry points and rear knock out slots<br />

> > Secure fixed plug on assembly<br />

> > Fully encapsulated bus bar assembly<br />

> > Earth terminal block and neutral blocks fitted as standard<br />

> > Standard consumer units up to 24 ways<br />

> > Earthed cover<br />

> > Enclosure colour: White RAL 9003<br />

Consumer Unit<br />

Reference Description No of ways<br />

R9BM2L 2 Way Resi9 metal CU 2<br />

R9BM4L 4 Way Resi9 metal CU 4<br />

R9BM6L 6 Way Resi9 metal CU 6<br />

R9BM8L 8 Way Resi9 metal CU 8<br />

R9BM12L 12 Way Resi9 metal CU 12<br />

R9BM16L 16 Way Resi9 metal CU 16<br />

Dual bank<br />

Reference Description No of ways<br />

R9BM24L 24 Way Resi9 metal CU 24<br />

Split Load<br />

Reference Description No of ways<br />

R9BMS4R6L 4+6 Resi9 metal CU 4+6 split load<br />

R9BMS6R4L 6+4 Resi9 metal CU 6+4 split load<br />

R9BMS5R5L 5+5 Resi9 metal CU 4+4 split load<br />

R9BMS7R7L 7+7 Resi9 metal CU 7+7 split load<br />

Dual RCCB - Including Incomers<br />

Reference Description No of ways<br />

R9BMSR6R6L 6+6 Resi9 metal CU inc 100a Sw & 2 x 63a RCCBs 6+6 dual split<br />

R9BMS2R5R5L 2+5+5 Resi9 metal CU inc 100a Sw & 2 x 63a RCCBs cw 2 unprotected ways 2,5,5, multiple split<br />

R9BMDS2R5R5L 2+5+5 Resi9 metal CU inc 100a Sw & 2 x 100a RCCBs cw 2 unprotected ways 2,5,5, multiple split<br />

40


Select devices<br />

Incoming Devices<br />

R9R81263<br />

R9R81291<br />

R9R85291<br />

R9S87291<br />

SE1100L<br />

63A/30mA RCCB<br />

100A/30mA RCCB<br />

100A/300mA RCCB TD<br />

100A Switch Disconnector<br />

100A 1P Terminal Block<br />

Outgoing Device<br />

MCB’s type B<br />

MCB’s type C<br />

R9F87103 Single Pole 3A Type B MCB 6kA R9F64103 Single Pole 3A Type C MCB 6kA<br />

R9F87106 Single Pole 6A Type B MCB 6kA R9F64106 Single Pole 6A Type C MCB 6kA<br />

R9F87110 Single Pole 10A Type B MCB 6kA R9F64110 Single Pole 10A Type C MCB 6kA<br />

R9F87116 Single Pole 16A Type B MCB 6kA R9F64116 Single Pole 16A Type C MCB 6kA<br />

R9F87120 Single Pole 20A Type B MCB 6kA R9F64120 Single Pole 20A Type C MCB 6kA<br />

R9F87125 Single Pole 25A Type B MCB 6kA R9F64125 Single Pole 25A Type C MCB 6kA<br />

R9F87132 Single Pole 32A Type B MCB 6kA R9F64132 Single Pole 32A Type C MCB 6kA<br />

R9F87140 Single Pole 40A Type B MCB 6kA R9F64140 Single Pole 40A Type C MCB 6kA<br />

R9F87150 Single Pole 50A Type B MCB 6kA R9F64150 Single Pole 50A Type C MCB 6kA<br />

R9F87163 Single Pole 63A Type B MCB 6kA R9F64163 Single Pole 63A Type C MCB 6kA<br />

RCBO’s - Type A<br />

R9D87806<br />

R9D87810<br />

R9D87816<br />

R9D87820<br />

R9D87825<br />

R9D87832<br />

R9D87840<br />

R9D87850<br />

Single Pole 6A/30mA B Curve RCBO<br />

Single Pole 10A/30mA B Curve RCBO<br />

Single Pole 16A/30mA B Curve RCBO<br />

Single Pole 20A/30mA B Curve RCBO<br />

Single Pole 25A/30mA B Curve RCBO<br />

Single Pole 32A/30mA B Curve RCBO<br />

Single Pole 40A/30mA B Curve RCBO<br />

Single Pole 50A/30mA B Curve RCBO<br />

Control devices and accessories<br />

A9C20732<br />

ICT 25A 2NO 230...240VAC 50HZ Contactor<br />

A9C20834<br />

ICT 25A 4NO 220...240VAC 50HZ Contactor<br />

A9C20842<br />

ICT 40A 2NO 220...240VAC 50HZ Contactor<br />

A9C20843<br />

ICT 40A 3NO 220...240VAC 50HZ Contactor<br />

A9C20844<br />

ICT 40A 4NO 220...240VAC 50HZ Contactor<br />

A9C20863<br />

ICT 63A 3NO 220...240VAC 50HZ Contactor<br />

A9C30811 ITL16A 1NO 230/240VAC 110VDC 50-60<br />

A9C30812<br />

ITL16A 2NO 230/240VAC 50-60HZ 110V<br />

A9E15535 CHANGEOVER RELAY IRLI 10A 2P UC 230V-240<br />

A9A15321<br />

ISO BELL 8 12V<br />

A9A15214<br />

BELL TRANSFORMER 4VA 230VCA 8VCA<br />

A9A15323<br />

BUZZER 8..12 VCA 70DBA 50..60HZ<br />

CCT15368<br />

IC2000 light sensitive switch<br />

15336 24HR analogue time switch with reserve<br />

CCT15720<br />

1 Channel IHP program time switch<br />

CCT15722<br />

2 Channel IHP program time switch<br />

15363 MIN time switch 1-7mins (delayed off)<br />

A9A27062<br />

5X Spacer 9MM - 1/2 module blank<br />

SEPLMCB<br />

MCB Padlock attachment (pk10) MCB<br />

SEPLRCBO<br />

RCBO Padlock attachment (pk10) RCBO<br />

SEPL<br />

Padlock (can be used with MCB or RCBO attachment)<br />

EZ9LKITL<br />

Door lock kit (for AMD3 metal enclosure only)<br />

SEDNBP3<br />

3 module blanking plate module<br />

Control devices<br />

May be installed at any outgoing point on the RCD protected or unprotected side<br />

41


Easy9<br />

Technical guide<br />

Technical guide<br />

42


Resi9 - metal unit dimensions<br />

Metal Units<br />

Ref No. Type Useable No Ways Height (mm) Width (mm) Depth (mm)<br />

R9BM2L Standard 2 247 186 112<br />

Metal R9BM4L units Standard 4 247 Dimensions (mm) 222 No. 112of knockouts<br />

Reference R9BM6L number Standard No. of 6 ways Type 247 A B 258 D E 112 F G H<br />

R9BM8L Standard 8 247 294 112<br />

25 x 89 30mm 25mm 20mm<br />

R9BM12L Standard 12 247 366 112<br />

R9BM2 2 Standard 181 119 – 2 2 8 –<br />

R9BM4 R9BM16L Standard 4 16 Standard 247 222 155 4382 2 112 2 8 –<br />

R9BM6 R9BM24L R9BM6SG Standard 6 24 Standard 487 258 191 366– 2 112 4 8 –<br />

R9BM8 R9BMS4R6L R9BM8SG Split 8 10 Standard 247 294 227 366– 2 112 4 10 2<br />

R9BM12 R9BM12SG 12 Standard 366 299 4 4 4 12 –<br />

R9BMS6R4L Split 10 247 366 112<br />

R9BM16 16 Standard 438 371 4 4 4 16 –<br />

R9BM24<br />

R9BMS5R5L Split<br />

24<br />

10<br />

Standard<br />

247<br />

366 299<br />

366<br />

6 4<br />

112<br />

4 8 –<br />

R9BMS4R6 R9BMSR6R6L Split 4+6 12 Split 247 378 299 4384 4 112 4 12 –<br />

R9BMS5R5 R9BMS7R7L Split 5+5 14 Split 247 378 299 4384 4 112 4 12 –<br />

R9BMS6R4 R9BMS2R5R5L Multiple 6+4 12 Split 247 378 299 4384 4 112 4 12 –<br />

R9BMS7R7 7+7 Split 450 371 4 4 4 16 –<br />

R9BMDS2R5R5L Multiple 12 247 438 112<br />

R9BMSR6R6 R9BMSR6R6SG 6+6 Multiple 450 371 4 4 4 16 –<br />

R9BMDS2R5R5 R9BMDS2R5R5SG 2+5+5 Multiple 450 371 4 4 4 16 –<br />

R9BMS2R5R5 R9BMS2R5R5SG 2+5+5 Multiple 450 371 4 4 4 16 –<br />

Note: Rear of enclosure = 242mm high<br />

Incoming and outgoing devices must be selected separately from the Resi9 devices section.<br />

The following ref’s are supplied with switch disconnector and RCDs fitted:- R9BMSR6R6L, R9BMDS2R5R5L, R9BMS2R5R5L<br />

Cable entry sizes (mm)<br />

Height 247mm<br />

Depth 111mm<br />

5.5Ø<br />

63<br />

D<br />

2 WAY ONLY<br />

H<br />

F<br />

D<br />

116<br />

111<br />

86<br />

9.5Ø<br />

61<br />

54<br />

180<br />

247 (surface)<br />

259 (flush)<br />

5.5Ø 73<br />

D<br />

H<br />

F<br />

D<br />

31 B<br />

A<br />

Dotted line<br />

indicates cover<br />

39<br />

27<br />

(all dimensions in mm)<br />

44 54<br />

43<br />

27<br />

G<br />

E<br />

E<br />

F<br />

F<br />

G<br />

G<br />

G<br />

G<br />

G<br />

27<br />

12 & 16 Way only<br />

6 to 16 Way only<br />

4 to 16 Way only<br />

43


Technical data<br />

Metal<br />

Max. busbar current rating (A) 100<br />

Max. operating voltage (V) 240<br />

Operating frequency (Hz) 50<br />

Max. incoming cable capacity mm2 (phase and neutral) 50<br />

Max. outgoing cable capacity mm2 25<br />

Certification BS EN 61439-3<br />

IP rating BS EN 60529 (internal)<br />

IP2XB<br />

No. Of knockouts<br />

Dimensions (mm)<br />

25 x<br />

90mm<br />

32mm 25mm 20mm<br />

Ref No. A B D E F G<br />

R9BM2L 181 119 - 2 2 8<br />

R9BM4L 217 155 2 2 2 8<br />

R9BM6L 253 191 2 2 4 8<br />

R9BM8L 289 227 2 2 4 10<br />

R9BM12L 361 299 4 4 4 12<br />

R9BM16L 433 371 4 4 4 16<br />

R9BM24L 361 299 6 4 4 8<br />

R9BMS4R6L 361 299 4 4 4 12<br />

R9BMS6R4L 361 299 4 4 4 12<br />

R9BMS5R5L 361 299 4 4 4 12<br />

R9BMSR6R6L 433 371 4 4 4 16<br />

R9BMS7R7L 433 371 4 4 4 16<br />

R9BMDS2R5R5L 433 371 4 4 4 16<br />

R9BMS2R5R5L 433 371 4 4 4 16<br />

For short circuit back-up protection, maximum fuse rating:-<br />

Residual current breakers<br />

Reference number Description Cable capacity Dimensions Weight<br />

mm2 Height Width Depth kg<br />

SED25032 25A RCCB 30mA trip 2 pole 35 81 36 75 0.227<br />

SED25302 25A RCCB 300mA trip 2 pole 35 81 36 75 0.227<br />

SED40032 40A RCCB 30mA trip 2 pole 35 81 36 75 0.227<br />

SED40102 40A RCCB 100mA trip 2 pole 35 81 36 75 0.227<br />

SED40302 40A RCCB 300mA trip 2 pole 35 81 36 75 0.227<br />

SED63032 63A RCCB 30mA trip 2 pole 35 81 36 75 0.227<br />

SED63102 63A RCCB 100mA trip 2 pole 35 81 36 75 0.227<br />

SED63302 63A RCCB 300mA trip 2 pole 35 81 36 75 0.227<br />

SED80032 80A RCCB 30mA trip 2 pole 50 81 36 75 0.227<br />

SED100032 100A RCCB 30mA trip 2 pole 50 81 36 75 0.227<br />

SED100102 100A RCCB 100mA trip 2 pole 50 81 36 75 0.227<br />

44


UK contact details -<br />

0870 608 8 608<br />

Fax 0870 608 8 606<br />

Ireland contact details -<br />

01 601 2200<br />

Fax 01 601 2201<br />

As the global specialist in energy management with operations in more<br />

than 100 countries, Schneider Electric offers integrated solutions across<br />

multiple market segments, including leadership positions in energy<br />

and infrastructure, industrial processes, building automation, and data<br />

centres/networks, as well as a broad presence in residential applications.<br />

Schneider Electric is dedicated to making individuals’ and organisations’<br />

energy safe, reliable, efficient, productive and green from Power Plant to<br />

Plug TM .<br />

We are changing our brand names and becoming one Schneider Electric.<br />

You’ll get the same great quality products, but from one name you can remember and<br />

trust. This provides you and your customers with the reassurance associated with<br />

Schneider Electric.<br />

Some of our market leading brands have already become Schneider Electric including<br />

Merlin Gerin, Telemecanique, Square D, GET, Mita, Sarel, Himel, Thorsman,<br />

Tower and TAC.<br />

Working as one Schneider Electric makes it clearer that our ranges are highly compatible<br />

for integrated solutions.<br />

Schneider Electric Ltd<br />

United Kingdom<br />

Stafford Park 5,<br />

Telford<br />

Shropshire<br />

TF3 3BL<br />

Tel: 0870 608 8 608<br />

Fax: 0870 608 8 606<br />

www.schneider-electric.com/uk<br />

Ireland<br />

Head office,<br />

Block a<br />

Maynooth Business Campus<br />

Maynooth, Co. Kildare<br />

Tel: (01) 601 2200<br />

Fax: (01) 601 2201<br />

www.schneider-electric.com/ie<br />

Schneider Electric Limited is a company registered in England and Wales.<br />

Registered number: 1407228. Registered office: Stafford Park 5, Telford, Shropshire TF3 3BL.<br />

© 2014 Schneider Electric. All Rights Reserved. Schneider Electric, Active Energy Management,<br />

Compact, EcoStruxure, ION Enterprise, iRIO, Make the most of your energy, Masterpact,<br />

Micrologic, Power Plant To Plug, Modbus, and PowerLogic are owned by Schneider Electric<br />

Industries SAS, or its affiliated companies in the United States and other countries.<br />

As standards, specifications and designs change from time to time, please ask for confirmation<br />

of the information given in this publication.<br />

SE8899 FEB 2015<br />