<strong>Series</strong> <strong>400</strong> <strong>400</strong> <strong>Amp</strong> <strong>Disconnect</strong> Specifications<br />

The <strong>PRG</strong> <strong>Series</strong> <strong>400</strong> <strong>400</strong> <strong>Amp</strong> <strong>Disconnect</strong> shall be mounted in a Rolling Rack with two removable<br />

covers exposing the connector and control panels of the unit. Two locking casters shall keep the<br />

unit in place when connected.<br />

Solid copper bus bars shall be used in all high - current circuitry, reducing losses and internal heating.<br />

Two thermostatically controlled cooling fans shall be mounted within the enclosure and shall turn on<br />

when internal bus bar temperatures reach 55°C. Replaceable metal air filters shall cover fan inlets.<br />

Six Cam-Lok <strong>Series</strong> E1016 high current connections shall be provided for input power. Double<br />

Neutral connectors shall handle excessive neutral currents generated by low power factor loads.<br />

Neon lamps shall indicate when the cable feeding the <strong>Disconnect</strong> is energized. Twelve Cam-Lok<br />

<strong>Series</strong> E1016 high-current connectors shall be provided for output power. Safety covers shall be<br />

provided for all outputs.<br />

A thermal-magnetic Main Breaker shall protect circuit wiring so that long term operation at currents<br />

in excess of rated will cause it to trip, while magnetic elements respond quickly to overloads resulting<br />

from fault current surges. The Main Breaker shall tolerate momentary overcurrent conditions caused<br />

by inrush currents to prevent nuisance tripping when such loads are energized with full line voltage.<br />

The inrush limit shall be adjustable from 2000 to <strong>400</strong>0 <strong>Amp</strong>s by a slider control.<br />

A green LED Pilot Light shall indicate when the Main Breaker is ON. Operation of the LED may be<br />

checked when the Main Breaker is OFF by pushing in on the lens cap causing the LED to light. Seven<br />

digital LED meters shall monitor the power flowing through the <strong>Disconnect</strong>. Three voltmeters shall<br />

measure phase voltages present at the input to the Main Breaker. A rocker switch shall allow connection<br />

of the meters between the three phases (Ø-Ø) or between each phase and neutral (Ø-N).<br />

Four current meters shall measure the current flowing in each phase and in the neutral circuit. The<br />

current meters shall be isolated from the AC line by current transformers. The meters shall display<br />

a full-wave averaging, RMS calibrated value.<br />

Five color coded, insulated test points shall be provided for metering the output voltages after the<br />

Main Breaker. Local convenience outlets shall provide protected branch circuits: <strong>One</strong> 120V, 15 <strong>Amp</strong><br />

single phase circuit serving two Edison outlets; <strong>One</strong> 208V, 15 <strong>Amp</strong> single phase circuit serving two<br />

Neutrik® PowerCon® outlets; <strong>One</strong> 208V, 20 <strong>Amp</strong> single phase circuit serving one NEMA L6-20R<br />

outlet; and one 120V/208V, 30 <strong>Amp</strong> 3-phase, 5-wire circuit serving two NEMA L21-30R outlets.<br />

The <strong>Series</strong> <strong>400</strong> <strong>Disconnect</strong> shall be approved for use in the U.S. and Canada, or in any locality with<br />

a 5-wire, 120/208V power grid. The unit is also suitable for use with portable power sources (generators)<br />

as long as its ratings are not exceeded and an adequate Earth ground has been established.<br />

The unit shall conform to UL Standard 1640, be certified to Canadian Standard CAN/CSA STD C22.2<br />

No. 29, and shall carry the Intertek ETL safety mark. The unit shall be used in dry locations only and<br />

may be operated with the front rack cover in place, if desired.<br />

Ordering Information<br />

20.9680.0200 <strong>Series</strong> <strong>400</strong> <strong>400</strong> <strong>Amp</strong> <strong>Disconnect</strong><br />

XØ VOLTS YØ VOLTS ZØ VOLTS<br />

MAIN<br />

BR EAKER<br />

ON<br />

PUSH<br />

TO<br />

TES T<br />

SWITCH TO OFF<br />

POSITION TO<br />

RESET BREAKER<br />

INPUT VOLTAGES<br />

<strong>400</strong> AMP<br />

MAIN BREAKER<br />

ON<br />

Type 1Enclosure<br />

For use in DryLocations<br />

50 C MaxAmbient<br />

For Use in Areas Not Readily Accessible bythe General Public<br />

FOR USE BY QUALIFIED PERSONNEL ONLY<br />

WARNING - Risk of ElectricShock.<br />

OFF<br />

2000A 3000A <strong>400</strong>0A<br />

INRUSH LIMIT<br />

SETTING<br />

ARC MIXE D T U NGSTEN<br />

L OADS LOADS L OADS<br />

Conforms to:<br />

ProductionResourceGroup<br />

UL STD 1640<br />

8617AmbassadorRow<br />

Suite 120<br />

Certified to:<br />

Dallas, TX 75247<br />

CAN/CSASTDC22.2<br />

Made inUSA<br />

No.29<br />

XXXXX<br />

S-<strong>400</strong><br />

<strong>400</strong> AMP DISCONNECT<br />

MODEL 23-9680-0200<br />

Ø -Ø<br />

Ø -N<br />

600A MAX<br />

NEUT AMPS<br />

120/208V<br />

3ØY/30 A<br />

Production Resource Group<br />

XØ AMPS<br />

XØ<br />

GROUND<br />

FOR BRANCH CIRCUIT USE ONLY<br />

120V / 15A 208V / 15A 208V / 20A<br />

120/208V<br />

3ØY/30 A<br />

<strong>400</strong>A MAX<br />

YØ AMPS<br />

YØ<br />

NEUTRAL<br />

120/208V<br />

3ØY/30 A<br />

ZØ AMPS<br />

ZØ<br />

OUTPUT<br />

VOLTAGES<br />

TEST POINT<br />

FUSES<br />

1A / 250V<br />

AGC1<br />

RATINGS and AMPACITY<br />

Voltage Rating: 120/208V 3-phase wye with Neutral and<br />

Ground<br />

Line Frequency: 50 - 60 Hz<br />

Current Rating, Phases: <strong>400</strong> <strong>Amp</strong>s per phase continuous<br />

Current Rating, Neutral: 600 <strong>Amp</strong>s continuous<br />

Current Rating, Ground: <strong>400</strong> <strong>Amp</strong>s<br />

Fault Current Interrupting Capacity: 42,000 <strong>Amp</strong>s<br />

Fault Current Interrupt Time: Circuit clears in less than<br />

one line cycle<br />

MAIN BREAKER<br />

Type: Thermal-Magnetic, Square D Model LAL36<strong>400</strong><br />

Number of Poles: 3<br />

Voltage Rating: 600V AC<br />

Current Rating: <strong>400</strong> <strong>Amp</strong>s<br />

Inrush Overload Limit: Adjustable from 2000A to <strong>400</strong>0A<br />

DIGITAL LED METERS (7)<br />

Update Rate: 2.5 samples/sec.<br />

Display: 3-digit reading<br />

INPUT VOLTMETERS (3)<br />

Accuracy: ± 1 Volt<br />

Input Range: 85 - 264 Volts AC<br />

Overload Protection: 300V AC<br />

OUTPUT AMMETERS (4)<br />

Phase Current Meters full scale reading: <strong>400</strong> <strong>Amp</strong>s<br />

Neutral Current Meter full scale reading: 600 <strong>Amp</strong>s<br />

Overcurrent Rating: 1.5X rated full scale reading<br />

Accuracy (sine wave): ±0.15% of full scale or ±6 counts<br />

ENVIRONMENTAL<br />

Operational Temperature Range: -20° C to +50° C<br />

Cooling: Two thermostatically controlled fans<br />

For Dry Locations Only<br />

DIMENSIONS and WEIGHT<br />

Unit in Rolling Rack: 22.5”(L) x 22.5”(W) x 30.5”(H)<br />

Stand-Alone Panel w/o Rack: 8.5”(D) x 19”(W) x 23.5”(H)<br />

Weight: 153 lbs. with Rack / 79 lbs. w/o Rack<br />

D W<br />

S-<strong>400</strong><br />

<strong>400</strong> AMP<br />

DISCONNECT<br />

INPUT CONNECTIONS<br />

MUST BE MADE<br />

IN THE FOLLOWI NG<br />

ORDER:<br />

1) CONNECT GROUND<br />

2) CONNECT NEUTRAL<br />

3) CONNECT PHASES<br />

DISCONNECT IN<br />

REVERSE ORDER<br />

GND<br />

GND<br />

GND<br />

120/208V 3Ø OUTPUTS <strong>400</strong>A PER Ø MAX<br />

NEUT<br />

NEUT<br />

NEUT XØ<br />

YØ<br />

YØ<br />

120/208V 3Ø INPUTS <strong>400</strong>A PER Ø MAX<br />

NEUT<br />

NEUT<br />

NEUT<br />

XØ<br />

X Ø YØ<br />

FRONT SIDE BACK<br />

Atlanta 404-214-4800 | Chicago 847-227-5171 | Dallas 214-630-1963 | Denver 303-341-4848<br />

Detroit 248-526-5290 | Las Vegas 702-942-4774 | Las Vegas / Henderson 702-294-4805<br />

Los Angeles 818-252-2600 | Mount Vernon 914-662-3540 | Nashville 615-834-3190 | New Windsor 845-567-5700<br />

New York 212-589-5<strong>400</strong> | North Bergen 201-758-<strong>400</strong>0 | Orlando 407-855-8060 | Toronto 905-270-9050<br />

<strong>PRG</strong> <strong>Series</strong> <strong>400</strong> and Virtuoso® are trademarks of Production Resource Group, LLC. Neutrik® and PowerCon® are registered trademarks of Neutrik AG.<br />

©2008 Production Resource Group, LLC. All Rights Reserved. Specifications are subject to change without notice. Version: August 2008<br />