Audico Avec ADA 8x8 datasheet english.pub
Audico Avec ADA 8x8 datasheet english.pub
Audico Avec ADA 8x8 datasheet english.pub
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>ADA</strong> <strong>8x8</strong> Central Unit
Notes<br />
AUDICO SYSTEMS OY<br />
P.O.Box 39<br />
Ruunikkokatu 2<br />
Fi 20381 Turku<br />
Finland<br />
Tel. + 358 –2 – 415 5400<br />
Fax. + 358 –2 – 415 5450<br />
audico@audico.fi<br />
www.audico.fi
The real heart of the digital <strong>Audico</strong> <strong>Avec</strong>, Public Address<br />
and Voice Evacuation system, is the <strong>Audico</strong><br />
<strong>ADA</strong> <strong>8x8</strong> central unit.<br />
The <strong>ADA</strong> <strong>8x8</strong> is a very effective and compact unit. It<br />
has versatile analog and digital audio inputs, effective<br />
digital signal processing circuitry and matrix, built-in<br />
prerecorded spoken message player and even 8 digital<br />
150W power amplifiers. The <strong>Audico</strong> <strong>Avec</strong> accommodates<br />
also system surveillance according to EN<br />
60849 standard. It’s certified by authorized certification<br />
body.<br />
All this in a single 2U high 19” device.<br />
<strong>Audico</strong> <strong>Avec</strong> digital Public Address and Voice Evacuation system<br />
AUDICO <strong>ADA</strong> <strong>8x8</strong> CENTRAL UNIT<br />
<strong>Audico</strong> <strong>Avec</strong> is configured using intuitive and easy to use <strong>Avec</strong> software, the file is finally downloaded to the <strong>ADA</strong> <strong>8x8</strong><br />
V 1.01<br />
• EN 60849 certified Voice Evacuation system<br />
• 8 independent 150W @ 8 Ohms amplifiers<br />
• Digital matrix 7x8<br />
• 7 analog audio inputs, mic/line level<br />
• 2 digital SPDIF inputs<br />
• Built-in message/advertisement player<br />
• Messages in USB-memory-stick<br />
• Calendar and timer functions<br />
• Phantom voltage for microphones<br />
• 8 control contact inputs<br />
• 8 control contact output<br />
• System bus for top hierachy level devices<br />
• Local bus for lower hierachy devices<br />
• Efficient signal processing (DSP)<br />
• Volume and source controls on users’ panel<br />
• RS 232 serial input for external control
MAINS INLET AND FUSES<br />
<strong>ADA</strong> <strong>8x8</strong> is connected to 230V operation voltage<br />
using standard mains plug.<br />
<strong>ADA</strong> <strong>8x8</strong> contains two separate parallel low voltage<br />
power units. Both power supplies have dedicated<br />
fuse at the rear panel.<br />
<strong>ADA</strong> <strong>8x8</strong> must be equipped with external UPS device<br />
when erecting a system according to the EN 60849<br />
standard.<br />
Fuse size is 3,15AT<br />
SPEAKER OUTPUTS<br />
<strong>ADA</strong> <strong>8x8</strong> contains 8 pcs 150W digital power amplifiers.<br />
8 Ohms loudspeakers may be connected directly to<br />
the speaker outputs. When 50-70-100V speakers<br />
are used the <strong>ADA</strong> <strong>8x8</strong> must be equipped with ALT<br />
<strong>8x8</strong> line transfer unit. It converts the 8 Ohms outputs<br />
to desired line voltage.<br />
The ALT <strong>8x8</strong> provides also priority voltage outputs,<br />
individually for each line (24VDC).<br />
RS-232 INTERFACE<br />
The RS232 interface at the rear is used for monitoring<br />
the running of the <strong>ADA</strong> <strong>8x8</strong>’s operation system.<br />
Suitable software is for example Windows Hyperterminal.<br />
<strong>ADA</strong> <strong>8x8</strong> can be controlled thru USB port<br />
using special RS232/USB adapter.<br />
24VDC OPERATION VOLTAGE OUTPUT<br />
The 24DC power output is used to supply power to<br />
the ALT <strong>8x8</strong> line transfer unit. The same voltage is<br />
used also for priority voltage. Priority voltage is used<br />
to bypass possible attenuators in rooms during paging<br />
or alarm to ensure the message is heard everywhere<br />
in the building.<br />
DIGITAL OPTICAL INPUTS AND OUTPUTS<br />
(SPDIF)<br />
<strong>ADA</strong> <strong>8x8</strong> can handle digital audio signals directly.<br />
Digital audio is brought to <strong>ADA</strong> <strong>8x8</strong> by using optical<br />
SPDIF-cable.<br />
The optical inputs are activated by configuration software,<br />
the corresponding analog inputs must be disabled.<br />
SPDIF input 1 is parallel to analog inputs 1 and 2,<br />
SPDIF 2 is parallel to analog inputs 5 and 6.<br />
FAN<br />
The <strong>ADA</strong> <strong>8x8</strong> is equipped with a fan. The rotation of<br />
fan is also monitored and any fault is reported to surveillance<br />
system.
SYSTEM & LOCAL OVERRIDE AUDIO OUT<br />
Both paging and alarm signals can be configured to<br />
these outputs. The outputs are mainly intended to<br />
feed paging audio to external amplifers or other systems.<br />
CTRL ALT <strong>8x8</strong> CONTROL DATA TO ALT <strong>8x8</strong><br />
The ALT <strong>8x8</strong> delivers priority voltage to wanted lines<br />
according the data from <strong>ADA</strong> <strong>8x8</strong>.<br />
DEVICE ADDRESS DIP-SWITCH<br />
Every <strong>ADA</strong> <strong>8x8</strong> in a system must have own individual<br />
device address in the same order as they appear on<br />
the configuration software. The first main unit has<br />
address one, then two etc.<br />
CONTROL OUTPUTS<br />
The control outputs may be configured to activate on<br />
diverse situations, like paging, alarm, fault-indication,<br />
firebell muting etc. The output is open-collector type.<br />
CONTROL INPUTS<br />
The control inputs may be used to active different<br />
<strong>ADA</strong> <strong>8x8</strong> actions like activate a paging, change preset,<br />
play message, alarm etc.<br />
MIC/LINE INPUTS<br />
7 pcs microphone/line inputs.The connector is removable<br />
3-pins plug. Each input has own input sensitivity<br />
trimmer. The mic/line selection is done using the<br />
configuration software.<br />
SYSTEM BUS & LINK<br />
<strong>Audico</strong> <strong>Avec</strong> devices are connected together using<br />
either system or local bus. The devices connected to<br />
the system bus can be used to control all <strong>ADA</strong> <strong>8x8</strong>’s<br />
in a single installation. Maximum number of devices<br />
in a single bus is 32.<br />
LOCAL BUS<br />
The local bus is used to connect devices that are<br />
intended to be used only locally within the cover area<br />
of a single <strong>ADA</strong> <strong>8x8</strong>. Typically local paging unit and<br />
volume controllers are such locally operated devices.<br />
USB-MEMORY STICK CONNECTOR<br />
The alarm and other messages are stored in wavformat<br />
to a USB-memory stick. The stored sound files<br />
can be played as chime, alarm or information message<br />
triggered by timer, paging, control input or a fault<br />
etc.<br />
There is another USB - jack inside the <strong>ADA</strong> <strong>8x8</strong> for<br />
non-removable messages.
<strong>ADA</strong> <strong>8x8</strong> simplified block diagram
<strong>ADA</strong> <strong>8x8</strong> CENTRAL UNIT<br />
<strong>Audico</strong> code 30010<br />
EAN code 6430029190019<br />
Signal processing and routing characteristics<br />
8 digital power 150W @ 8 Ohms amplifiers<br />
7 analog audio inputs, configurable either to mic or line level<br />
Phantom-voltage for electret microphones<br />
2 SPDIF digital stereo inputs<br />
2 SPDIF digital stereo outputs<br />
Internal message player, security messages in internal memory,<br />
unlimited number of messages in USB memory stick. (wav)<br />
Input channels digital signal processing (DSP), 7 channels<br />
Input level, mic or line<br />
Type of signal: digital/analog<br />
Parametric equalizer, 3 band<br />
Digital routing<br />
Level control<br />
Output channels digital signal processing (DSP), 8 channels<br />
Tone control<br />
Parametric equalizer, 5 band<br />
High pass filter, frequency freely selectable<br />
12 or 24 dB/octave, filter: Butterworth, Linkwitz- Riley or<br />
Bessel<br />
Delay max 4ms<br />
Compressor /limiter<br />
Volume control<br />
Connection buses and I/O’s<br />
Local bus (CAT5) for paging and control devices operational within<br />
one <strong>ADA</strong> <strong>8x8</strong> only<br />
System bus (CAT5) for paging and control devices operational over<br />
whole system, max 32 devices<br />
System bus link connector for chaining to next <strong>ADA</strong> <strong>8x8</strong><br />
Front panel USB connector for configuration file down/upload<br />
Rear panel and internal USB jacks for message memory sticks<br />
8 control contact inputs, operation configurable<br />
8 control contact outputs, operation configurable<br />
Priority data for controlling the ALT <strong>8x8</strong> line transfer unit<br />
System operation<br />
System is expandable by adding required number of <strong>ADA</strong> <strong>8x8</strong> units.<br />
Up to 256 speaker lines / paging zones<br />
Possibility to use local programme sources in any <strong>ADA</strong> <strong>8x8</strong>.<br />
System surveillance:<br />
Device and system monitoring according to EN-60849 standard<br />
Automatic switch-over to a another <strong>ADA</strong> <strong>8x8</strong> if master <strong>ADA</strong> fails<br />
Power supply voltage and temperature monitoring<br />
Fan rotation monitoring<br />
Requirement for Voice Evacuation System’s Main<br />
User<br />
Standard EN-60849 sets also guidelines for the user<br />
of the installed system. The main user must take care<br />
of system maintenance, testing, keep the logbook<br />
and ensure all other users are well trained to use the<br />
system.<br />
We have prepared a booklet guiding the user as well<br />
the installation and service companies to set-up and<br />
run a system according the EN standard.<br />
V 1.01<br />
<strong>Audico</strong> <strong>Avec</strong> digital Public Address and Voice Evacuation system<br />
TECHNICAL CHARACTERISTICS<br />
Operation voltage 230VAC<br />
Max power 950W<br />
Required maximum alarm-on UPS capacity is 1kVA<br />
Required ready-state UPS capacity is 200VA<br />
(system on but no audio signal)<br />
Analog audio inputs 7 pcs<br />
Control I/O’s 8 / 8 pcs (open-collector)<br />
SPDIF in/out 2 pcs<br />
System bus max 32 device, CAT 5<br />
Local bus max 32 device, CAT 5<br />
Outputs 8 pcs each 150W@8 Ohms<br />
The <strong>ADA</strong> <strong>8x8</strong> is Rohs-compliant, it is tested according<br />
all relevant safety and electromagnetic compatibility<br />
standards (EMC).<br />
The <strong>Audico</strong> <strong>Avec</strong> product family is certified according<br />
to EN-60849 standard (Sound System for Emergency<br />
Purposes).<br />
Dimensions<br />
W x H x D 483 x 88 x 380 mm<br />
Carton W x H x D 540 x 460 x 170 mm<br />
Volume 0,042m 3<br />
Weight / net 8,5 kg<br />
Weight / gross 9 kg<br />
Accessories<br />
- mains cable with Schuko-plug<br />
- USB A-B cable for downloading<br />
- 1 GB USB memory stick<br />
- installation and operation manuals<br />
- configuration manual
AUDICO AVEC ACCESSORIES<br />
ALT <strong>8x8</strong> Transformer unit<br />
• Used to convert <strong>ADA</strong> <strong>8x8</strong>’s low impedance<br />
outputs to 50-70-100V lines<br />
• Supplies also 24VDC priority voltage<br />
AAE 800 Paging and control unit<br />
• Paging<br />
• Programme selection and volume control<br />
• Preset activation<br />
AAE 804 Fireman’s microphone<br />
• High priority paging<br />
• Prerecorded evacuation message play buttons<br />
<strong>Audico</strong> <strong>Avec</strong> configuration software<br />
• Used to set-up the system<br />
• Runs in a standard Windows PC<br />
• Requires USB-port<br />
• Requires installation of a USB gadget-driver<br />
AUDICO SYSTEMS OY<br />
P.O. Box. 39 (Ruunikkokatu 2)<br />
20381 Turku, Finland<br />
Tel. +358- 2- 415 5400<br />
Fax: +358- 2- 415 5450<br />
VAT FI 0982651-1<br />
AAE 806 Paging and control unit<br />
• Paging<br />
• Programme selection and volume control<br />
• Preset activation<br />
• 6 buttons to play prerecorded messages<br />
AAI 800 Preset buttons and audio input<br />
• 3 Preset activation buttons<br />
• Audio input with level control<br />
ASV 800 Programme and volume control<br />
• Up-down buttons to choose channel<br />
• Up-down buttons to set volume<br />
AEU 100 Line end unit<br />
• Improves line monitoring performance<br />
• Installed to end of each monitored speakerline<br />
www.audico.fi<br />
audico@audico.fi