F IGURE 87:<br />

G RAPHICS S CREEN<br />

S HOWING Z ONE ID FOR<br />

R ESET D RIVERS<br />

X154X FAN TYPE, SIZE AND CONTROL<br />

This indicates that <strong>VAV</strong> box<br />

20 has the highest cooling<br />

loop output<br />

Field Experience with Static Pressure, Supply Air Temperature Reset and Other<br />

Demand-Based Reset Sequences<br />

Appendix 14 describes several buildings where trend data was collected to see how<br />

successfully supply air temperature setpoint reset, static pressure setpoint reset and demand<br />

controlled ventilation sequences had been implemented. Trend data was collected on<br />

approximately 15 air handling systems. Figure 88 summarizes the static pressure reset results<br />

presented in Appendix 14. As this figure shows the average pressure setpoint was<br />

approximately halfway between the maximum and minimum setpoints, which means that<br />

these systems are achieving considerable fan energy savings compared to a fixed setpoint<br />

scheme.