AUTOMATIC MAINS FAILURE PANEL : SEQUENCE LOGICFollowing sequence logic should be followed while designing the logic <strong>for</strong>AMF Panel:1.Automatic starting of diesel generating <strong>set</strong> in the event of mains voltage belowpre<strong>set</strong> value / total failure.2.On restoration of mains supply, it's quality will be monitored <strong>for</strong> a pre<strong>set</strong> timeand then load is automatically transferred on the mains and diesel engine isshutdown after a pre<strong>set</strong> idle running period.3.In the event of failure of diesel engine to start on failure of mains supply on firstattempt, two more attempts are made automatically. If, engine still fails to start dueto some defect, it will get locked automatically and necessary audiovisual signalshall be given.4.In the manual mode the DG Set can be started <strong>by</strong> the operator <strong>by</strong> pressing thestart button and stopped <strong>by</strong> stop button irrespective of the mains condition.5.In the test-mode, mains failure condition is simulated. However, the load will notbe transferred on the DG Set.