Technical Databook - Belimo Actuators (Shanghai)

Technical Databook - Belimo Actuators (Shanghai)

Technical Databook - Belimo Actuators (Shanghai)

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Sontex Energy Meter<strong>Technical</strong> <strong>Databook</strong>Ver. Version 2 2.4<strong>Belimo</strong> Asia Pacific


Energy MeterThermal energy meterSuperstatic 440+Supercal 531+Temperature sensorDistributed by <strong>Belimo</strong><strong>Belimo</strong> Trade ItemNominal Pressure PN16AC 24V Power supplyBuilt-in M-Bus modulePt500 SensorEN 1434 Class 2Temp. sensor cable 3mSensor head cable 3mThreaded connection - Brass pipe (EXT-..)Model No. Nominal flow Mounting length Connection Energy unit Volume unit Sensor Pockets440M0600 1.5m 3 /h 110mm G 3/4” 0.1kWh 0.001m 3 0460R030 0460A206440M1000 2.5m 3 /h 190mm G 1” 0.1kWh 0.001m 3 0460R030 0460A206440M1600 6.0m 3 /h 260mm G 1-1/4” 1kWh 0.001m 3 0460R531 0460A207440M2000 10m 3 /h 300mm G 2” 1kWh 0.01m 3 0460R531 0460A207Flange connection - Brass pipe (EXT-..)Model No. Nominal flow Mounting length Connection Energy unit Volume unit Sensor Pockets440M2200 10m 3 /h 300mm DN40 1kWh 0.01m 3 0460R531 0460A207Flange connection - Stainless Steel pipe (EXT-..)Model No. Nominal flow Mounting length Connection Energy unit Volume unit Sensor Pockets440X2400 15m 3 /h 270mm DN50 1kWh 0.01m 3 0460R531 0460A207440X2600 25m 3 /h 300mm DN65 1kWh 0.01m 3 0460R532 0460A208440X3000 40m 3 /h 300mm DN80 0.01MWh 0.1m 3 0460R532 0460A208440X3400 60m 3 /h 360mm DN100 0.01MWh 0.1m 3 0460R532 0460A208440X3600 100m 3 /h 250mm DN125 0.01MWh 0.1m 3 0460R532 0460A208440X3800 150m 3 /h 300mm DN150 0.01MWh 0.1m 3 0460R532 0460A208440X4200 250m 3 /h 350mm DN200 0.1MWh 0.1m 3 0460R533 0460A209440X4400 400m 3 /h 450mm DN250 0.1MWh 0.1m 3 0460R533 0460A209Flange connection - Coated Steel pipe (EXT-..)Model No. Nominal flow Mounting length Connection Energy unit Volume unit Sensor Pockets440X4600 800m 3 /h 500mm DN350 0.1MWh 1m 3 *0460R852 0460A209440X5000 1500m 3 /h 500mm DN500 0.1MWh 1m 3 *0460R852 0460A209*Connection cable is not included for sensor 0460R852, cable400 can be ordered separately.The tried and tested oscillating jet principle of Superstatic flow sensors in combination with Supercal 531 integrators gurantees reliable, longtermmetering of thermal energy and flow.Thread, EN ISO 228-1Flange, DIN-EN 1092-1/DIN 2501/ISO 7005-12V2.4. 08.2011 • Subject to modifi cation


Energy MeterDistributed by <strong>Belimo</strong>Thermal energy meterSuperstatic 440+Supercal 531+Temperature sensorDesignTemperature sensor pairThe energy meter consists of a Superstatic 440 flow sensor, a Supercal 531(AC 24V) integrator and a pair of temperature sensors. Consumption valuescan be read easily on display.Supercal 531 integrators in combination with Superstatic flow sensors aresupplied as standard in Pt500 version. The temperature sensors are matchedto one another. They are always supplied in pairs and must not be separated,extended or shortened. In the case of a temperature sensor paired with acable longer than 3m, we recommend the exclusive use of screenedtemperature sensor pairs. In this case, the screening must be fitted correctly.Measurement techniqueThe Supercal 531 with AC 24V power supply records the supply and thereturn temperature every 3 seconds. The recording flow rate is dependent onthe pulse value of the flow sensor unit and is constantly updated. From themean flow rate, the temperature difference and the heat coefficient will calculatethe energy of the captured medium and display on the 8-digit LCD.Functional descriptionThe top level of Superstatic flow sensors is always the sensor level with feedbackloops. The sensor frequency/pulses are directly proportional to theflow/volume.The oscillating jet level has an acceleration section with interactive action.The oscillate frequency of the oscillating jet and the electrical signals generateddo not need any external energy source.The water inlet and outlet have a fluid input optimised for flow and anintegrated straight section, which makes an external straight section up toDN40 redundantly.V2.4. 08. 2011 . Subject to modification3


Energy MeterDistributed by <strong>Belimo</strong>Main featuresSuperstatic flow sensors are optimised for the measurement and calculationof energy consumption in cooling and heating systems. They are alsoextremely well suited to use purely as volumetric flow meters for variousmedia.- Interchangeable measuring head- Comprehensive range 1...400m 3 /h- Purchase and maintenance costs are reasonable compared with otherstatic flow sensors.- Corrosion resistant materials- Threaded and flange connection- No straight sections necessary up to DN40- No moving parts, therefore no wear- Not sensitive to dirt- Durable- Can be installed anywhere- Common spare parts 1...400m 3 /h- Dynamic range 1:50 for qp 40...400m 3 /h1:100 for qp 1...40m 3 /h- Direct pick-up of voltage pulses- Measurement irrespective of medium- Long-term, stable, accurate and reliable measurement, even if waterquality is poor.OrderingIntegratorWhen placing an order for energy meters you must indicate the normal flowused for heating or cooling and mounting place (supply or return).The Supercal 531 integrator is suitable for connection with Pt500 temperaturesensor pairs with 2- or 4-conducting wires techniques. Volume inputscan be combined with mechanical, magnetic-inductive, ultrasonic or fluidicoscillators flow sensors with a maximum nominal flow rate of 10,000m 3 /h.The factor of the pulse value is defined in the flow meter unit. The volumeinput value is defined when the unit is produced. The additional pulseinputs allow the connection of hot water, cold water, gas, oil and electricitymeters. Consumption values can be read easily on the LCD display or viathe M-bus.Power supply module The power supply of the Supercal 531- AC 24V 50/60HzCommunication moduleBuilt-in M-bus module.4V2.4. 08. 2011 . Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>Data storageIn case of power failure, the Supercal 531 has two non-volatile EEPROMfor extensive data safety storage. In both EEPROM the data is updatedevery hour. The first non-volatile memory is located inside on the printedcircuit board of the relevant calibration and measurement part of theintegrator and stores the following data:- Parameters of the integrator and configuration parameter- Cumulated energy- Cumulated volume- Customer’s specific tariff- 15 monthly values- 32 maximum values- 32 average values- Two set day- Cumulated energy or volume on the set day- Operating hours- Date and time- MET serial number (integrator upper part, calibration and measurementpart)- Pulse value of the flow meterThe second non-volatile EEPROM is located on the printed circuit boardin the integrator base part and stores the following parameters:- MIO serial number (integrator base part, printed circuit board)- Identification number and customer number- Pulse value of additional meters 1 and 2- Cumulated values of additional meters 1 and 2- Unit of additional meters 1 and 2- M-bus address- Baud rate (M-bus)- Pulse value of the pulse output- Parameter setting of the analogue outputs- Alarm and threshold valueThis EEPROM ensures a smooth exchange of the calibration andmeasurement relevant part, without a new entering of the configurationof the communication.Cumulated energyBackupTest segmentFor energy unit displayed in kWh/MWh. The maximum energy that canbe displayed is 99,999,999; the number of decimals can be set at thefactory or by an authorised calibration laboratory.For examination and safety storage of the measurement results theSupercal stores all data in a non-volatile memory once per hour. Withpower supply failure all values are automatically updated and stored.Shown on the LCD display.V2.4. 08. 2011 . Subject to modificationCumulated volumeOperating hoursDisplayed in m 3 . The maximum displayable energy is 9,999,999.9, thenumber of decimals can be set at the factory or by an authorised calibrationlaboratory.Displayed in hours.5


Energy MeterDistributed by <strong>Belimo</strong>Error timeFlow rateSupply and return temperatureTemperature differencePowerSet day valuesMonthly valuesAverage valuesMaximum valuePulse parametersIdentification numberDate and timePt500 resistance valuesPrimary address6The cumulated time, while some error was present, is indicated in minutes.The current flow rate is displayed in m 3 /h , the number of decimals can beset at the factory or by an authorised calibration laboratory.The temperature is displayed with one decimal. Temperatures under 0°Care shown with a “ - ” (minus) sign. The display range is -20...200°C.The temperature difference is displayed with two decimals. If the returntemperature is higher than the supply temperature, a “ - ” (minus) sign willbe placed in front.The standard unit displayed in kWh/MWh.The Supercal 531 has two set days. On set day the cumulated energy,volume, tariff values and auxiliary pulse inputs are stored by date.The storage date for the 15 months’ values can be set. The cumulatedenergy, volume, auxiliary pulse inputs and tariff values are stored. Thestorage date of the monthly values can be set, if the parameter settingsmode is activated.For the period of the 32 average values an integration time from 1 minuteto 45 days can be chosen. The average value for the actual power, flow,supply and return temperature, temperature difference, impulse input A1and A2 are displayed on the LCD.The precise monitoring and recording of power drops can be parameterisedin 1-hour cycles and cycles up to 1 year. The maximum values for theactual power, flow, supply and return temperature, temperature difference,impulse input A1 and A2 are displayed on the LCD.The pulse values for the flow meter, for the additional meters A1 and A2and the pulse values are displayed in the configuration menu. Values canbe changed by the program 531.The identification/customer number is displayed with 8 digits. Theidentification/customer number can be changed via the push buttons, ifthe parameter setting mode is activated.The date and time are displayed in the different menus. The date with theindex DA and the time with Hr are displayed. There is no differentiationbetween summer and winter time. Thanks to the backup function and incase of power supply loss, the date and time update themselves forseveral months. The date and the time can be changed via the pushbuttons, if the parameter setting mode is activated.The resistance value is 500 ohm at 0°C.The primary address is displayed on the LCD. The primary address can bechanged via the push buttons, if the parameter setting mode is activated.V2.4. 08. 2011 . Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>CommunicationStatus message transistor outputsSolar and cooling installationsCooling energyCommunication is displayed by means of an indicator. The indicator enablesone to recognise whether the integrator calculates or communicates from theinside or the outside.The Supercal 531 allows a locking of status messages on the transistoroutputs. The conditions of the status can be defined with the thresholdvalues. An alarm output for fast and exact external monitoring of the operatingconditions can be generated.The integrator units calibrated for water also ensure a precise measurementwith glycol mixtures, as the average mixing ratio can be customisedover the optical interface. The Supercal 531 also processes and computesnegative temperatures. The dust and splash proof water-protected housings,IP65, are especially suitable for cooling installations. For thesecustomised mixing ratios no official approvals are possible.The cooling energy is cumulated, if at the same time the two followingconditions are fulfilled:( t) temperature difference >-0.2Kas well as the supply temperature


Energy MeterDistributed by <strong>Belimo</strong>DisplayIn consideration of the person reading the LCD display of the Supercal531, the display is arranged clearly and is particularly large.index for average andmaximum valueService levelcommunication indicationindex for tariff 1 high temperature outputand tariff 2inputlow temperatureflow indicationindex for the monthly,average and maximumvaluesunitdisplay figuresframe for decimalfiguresindex for menu guidanceThe display sequences are divided into the following menus:- Main menu- Set days- 15 monthly values- 32 average values- 32 maximum values- Configuration- Service information- Test and parameter setting levelThe display sequence can be customised. The two push buttons enablesimple and customer friendly usage and readout of measurement data.Control conceptWith the command push button the different display levels or thedisplay within the display level can be selected.By pressing the enter push button a display level or one of thesubmenus can be selected. Afterwards the individual displayswithin the display level or within the submenu can be selected withthe command push button. If the command push button and theenter push button are pressed at the same time, then the displayswitches back again to the selection level of the different displaylevels.Operating mode8The integrator Supercal 531 works in principle in normal mode. The followingadditional operating modes are integrated in the integrator’s software:- Test mode (without damaging the seal)- Parameterisation mode (user seal to be removed)- Verification mode (verification seal to be removed)The integrator Supercal 531 is fully parameterised at the factory andaccording to the country specific parameter settings. Authorised laboratoriesoffices may modify the factory parameters.V2.4. 08. 2011 . Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>Error messagesThe Supercal 531 displays the Err-sign on the LCD, together with a numbercode of the occurring errors. When several errors occur at the same time thenumbers of the error code are summed up; e.g Err3=Err1+Err2.Err1Supply sensor is short circuited or disconnectedErr2Return sensor is short circuited or disconnectedErr4Flow rate too highErr8Storage error EEPROM in the integrator unit - lower part(only after the second time active)Err16 Storage error EEPROM in measuring and calibration relevantpart (only after the second time active)Err32 Configuration error EEPROM in measuring and calibrationrelevant partErr64 Configuration error EEPROM in the integrator unit - lower partErr128 Error of internal electronic, return to the manufacturerErr256 Voltage failureErr512 Defect of communication module, module location 1Err1024 Defect of communication module, module location 2Err2048 Error impulse input auxiliary meter A1Err4096 Error impulse input auxiliary meter A2Err8192 Error of internal electronic, return to the manufacturerIf an error displays for more than one hour, it is stored in the error memory withthe date it occurred, the time error comnmenced and the duration (in minutes).If an error stays less than 60 minutes, it is deleted automatically and withoutstorage.The two temperature sensor indicators are displayed as a messagewith the cumulated energy display on the main menu, indicating if:- The temperature sensors are interchanged >> this condition arises with mostinstallations during the summer time.- The temperature in the colder line is higher than in the warmer line.All error messages are deleted automatically on the LCD, 30 seconds after theerror correction.Optical interfacesCommunication optionsThe integrator Supercal 531 has an optical interface according to EN 61107.The M-Bus protocol according to EN 1434. The optical interface correspondselectrically and mechanically to the ZVEI IEC 1107 standard. Following start-upand service work, it allows:- Readout of all values- Parameterisation- TestsThe Supercal 531 differentiates between standard option possibilitiesequipped at the factory and optional plug-in communication modules. TheSupercal 531 has two plug-in spaces for all kinds of optional communicationmodules foreseen. The integrator unit recognises the optional modulesapproximately 10 seconds after plug-in. The functions are freely available.V2.4. 08. 2011 . Subject to modificationOpen collector outputsResolution of theimpulse input and outputThe Supercal 531 has as a standard two Open Collector outputs for energy,volume, tariff 1, tariff 2, alarm and threshold values. These outputs are notgalvanically separated.Optionally, two galvanically separated Open Collector output modules forstandard or high-speed impulse outputs are available. The high-speedimpulse can be used, for example, for the control of a valve. The impulse typeand pulse duration can be set over the optical interface or with the help of thecontrol push button.The set resolution as well as the unit of the impulse input and output are seenon the display menu - configuration.9


Energy MeterDistributed by <strong>Belimo</strong><strong>Technical</strong> dataFlow sensor 1.5...10m 3 /h (3/4”...2”)Model No. (EXT-..) 440M0600 440M1000 440M1600 440M2000Threaded connector 3/4” 1” 1-1/4” 2” GNominal flow qp 1.5 2.5 6.0 10 m 3 /hMaximum flow qs 3.0 5.0 12 20 m 3 /hMinimum flow qi 0.015 0.025 0.06 0.1 m 3 /hMounting length 110 190 260 300 mmWeight 1.8 2.3 1.96 6.1 kgStandardEN 1434 Class 2 (+/- 2% at qp)Nominal pressure PN 16 barPressure loss at qp 0.09 0.25 0.16 0.25 barFlow sensor10...25m 3 /h (DN40...65)Model No. (EXT-..) 440M2200 440X2400 440X2600DN 40 50 65 DNNominal flow qp 10 15 25 m 3 /hMaximum flow qs 20 30 50 m 3 /hMinimum flow qi 0.1 0.15 0.25 m 3 /hMounting length 300 270 300 mmWeight 7.0 12.2 12.8 kgStandardEN 1434 Class 2 (+/- 2% at qp)Nominal pressure PN 16 barPressure loss at qp 0.25 0.25 0.25 barFlow sensor40...100m 3 /h (DN80...125)Model No. (EXT-..) 440X3000 440X3400 440X3600DN 80 100 125 DNNominal flow qp 40 60 100 m 3 /hMaximum flow qs 80 120 200 m 3 /hMinimum flow qi 0.8 1.2 2 m 3 /hMounting length 300 260 250 mmWeight 12.2 14.6 16.0 kgStandardEN 1434 Class 2 (+/- 2% at qp)Nominal pressure PN 16 barPressure loss at qp 0.09 0.10 0.10 barFlow sensor150...1500m 3 /h (DN150...500)10Model No. (EXT-..) 440X3800 440X4200 440X4400 *440X4600 *440X5000DN 150 200 250 350 500 DNNominal flow qp 150 250 400 800 1500 m 3 /hMaximum flow qs 300 500 800 1600 3000 m 3 /hMinimum flow qi 3 5 8 32 60 m 3 /hMounting length 300 350 450 500 500 mmWeight 26.0 30.0 57.0 90.0 130.0 kgStandardEN 1434 Class 2 (+/- 2% at qp)Nominal pressure PN 16 barPressure loss at qp 0.10 0.10 0.10 0.10 0.10 bar*440X4600 and 440X5000 coated steel pipeV2.4. 08.2011 • Subject to modification


Distributed by <strong>Belimo</strong>Energy Meter<strong>Technical</strong> dataIntegrator-------------------------------------------------------------------------STANDARD VERSION-------------------------------------------------------------------------Temperature measurementPt5002 wiresAbsolute temperature range-20...180°CHomologation range2...150KTemperature resolution t 0.1KTemperature resolution Δt 0.01KMeasuring precision better than EN 1434-1 requestMeasuring cycleTemperature measurement:- 3 seconds when mains operatedVolume measurement:- Pulse volume is constantly updatedAmbient temperatureOperationStoring and transport5...55°C-25...70°C2 pulse outputsOpen collector outputs are polarised and not separatedfrom the ground. They have to be connected to external‘pull-up’ resistor.The outputs provide to an external system the possibilityto totalise the energy and volume calculated in the integratoror other values related to the configuration settings.OC class :allows connection to IB class(EN1434-2:1997prA1) inputsf max=5Hz (+60%/-20%)OD+ class:allows connection to fast inputsf max=10kHz (+60%/-20%)V2.4. 08. 2011 . Subject to modificationDisplay8 digit LCDDisplay unitsEnergykWh/MWhVolume m 3Additional pulse inputsvolume or energyTemperature°CInput voltageVoltageAC 24V 50/60HzRated currentAC 24V supplyData securityVerification and measurement relevant part EEPROMIntegrator baseEEPROM6EEPROM size8Kb, 10 writing cycleHousing protectionStandardIP54Pulse inputInput frequencyNormal modeFast modeBattery operationMains operationInput voltageVolume pulse inputsM-BusFixed or variable data structurePotential free, reverse battery proofBaud rate 300...9600 baud800mAmax. 5Hzmax. 12kHzmax. 5kHzmax. 12kHz0...30V1-10-100-1000l/pulseor 2.5-25-250-2500l/pulseU+0VOutputs531t11618171 / ft2IoutVoutElectric specifications EN1434-2 :1997prA1tmCounter 1External equipmentContactOffCounter 2t1ContactOnVout max


Energy MeterDistributed by <strong>Belimo</strong><strong>Technical</strong> data - temperature sensor 4 wire (optional)Temperature sensor 84...174mm, diameter 6mm, 4-wireStandard versions temperature sensorsSensor (EXT-..) Element Shielding Wire0460R850 Pt500 DIN 43765 4-wire0460R8510460R8520460R8530460R8540460R855Pt500 DIN plastic 4-wire8484Measuring element:Mating:Measuring range:Connection:Connection headCircuit:Material:Nominal pressure:Pocket:Pt500 platinum resistor according to DIN IEC 751Computer-paired in accordance with CEN 1434Standard version 0°C…150°C (0°C…180°C with connection head)2-wire cable or 4-wire cablePlastic, cable entry PG9 with sealable cover, IP53, or Aluminium DIN 43765 form B,cable entry PG16, IP54Standard version in 4-wire technologySensor pipe, stainless high-grade steel 1.4571Sensor PN16, protection pocket PN25Stainless high-grade steel 1.4571 with high pressure-safe squeezing ring connection2-wire connection without connection headFor this connection, the resistance of the cable is to be added to the sensor resistance. For the differential temperature measurement, bothsensor cables must be identical in length and type. The sensors are computer-matched at the factory and must not be separated. Also the suppliedsensor cables are not allowed to be cut.4-wire connection with connection headWire 1 and 2 (3 and 4) are used for constant current flow values whilst 5 and 6 (7 and 8) are for voltage changes from the Pt sensor beingmeasured. In this connection, different cable types or lengths can be used since the cable resistances have no influence on the measurement.Diagram for connections of temperature sensorshighertemperaturelowertemperaturehighertemperaturelowertemperaturehighertemperaturelowertemperaturehighertemperaturelowertemperature2-wire sensor4-wire sensor4-wire sensorfor 2-wire connection4-wire sensor12V2.4. 08.2011 • Subject to modification


Distributed by <strong>Belimo</strong>Energy Meter<strong>Technical</strong> data - temperature sensor 4 wire (optional)2-wire connectionMeasuring result=Resistance Pt500+cable resistance4-wire connectionMeasuring result=Resistance Pt500+cable resistanceThe cable resistance is not to be considered with 4-wire technologyCharacteristics of the temperature sensors according to DIN IEC7511000.0000Class B900.0000800.0000Pt100Pt500DifferenceClass AWiderstand Resistance [Ohm]700.0000600.0000500.0000400.0000300.0000200.0000100.00000.0000-100.0 -80.0 -60.0 -40.0 -20.0 0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0 160.0 180.0 200.0Temperature [°C]Insulation in accordance with SIATemperature sensor overall lengths in dependence of the pipe diameters and thickness of the thermal insulation inaccordance with SIA (Schweizerischer Ingenieur-und Architektenverein-Swiss engineer and architect association).V2.4. 08. 2011 . Subject to modificationPipeInsulation thickness Dwith temperaturedifference KWelding sleeveSensor andprotectionpocketnominallengthNominal sizeOutside K< K40- K>∅ 40°C 80°C 80°Cd lmm inch mm D mm D mm D mm inch mm mm15 1/2 21,3 30 40 50 3/8 1/2 20 31 3320 3/4 26,9 40 40 50 3/8 1/2 20 31 3325 1 33,7 40 50 --- 3/8 1/2 20 31 3325 1 33,7 --- --- 60 1/2 60 8432 1 1/4 42,4 40 50 60 1/2 60 8440 1 1/2 48,3 40 50 60 1/2 60 8450 2 60,3 50 60 60 1/2 60 8465 2 1/2 76,1 50 60 --- 1/2 60 8465 2 1/2 76,1 --- --- 80 1/2 80 13480 3 88,9 50 60 80 1/2 80 134100 4 114,8 60 80 80 1/2 80 134125 5 139,7 80 80 80 1/2 80 134150 6 165,1 80 80 100 1/2 80 174200 8 219,1 80 80 100 1/2 80 17413


Energy MeterDistributed by <strong>Belimo</strong><strong>Technical</strong> data - temperature sensor 4 wire (optional)Thermal insulationFor more accurate temperature measurement, thermal insulation should be installed.Permissible insulationThe insulation should never cover the temperature sensor cable.Installation recommendations according to EN143414V2.4. 08. 2011 . Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>Accessory - Optical ProbeEXT-531OP-UEXT-531OP-UInfra-red optical probe for meter readingDescriptionThe optical probe EXT-531OP-U enables data transfer betweendevices equipped with optical communication portconfirmed to IEC 1107 and terminals quipped with USB port.<strong>Technical</strong> DataOptical Standard EN 62056 (IEC 1107)Baud RateTransferPower SupplyCurrentDimensions50...115KHalf duplex5V by USB interfaceapprox. 30mADiameter 32mm, height 22mmCable Length 1.2mWeightMagnetisationCase Materialapprox. 65g include cable and connectorNorth pole outwards, strength approx. 15NDelrin/POMApplicationWe can change settings through the optical probe and Program 531 (which can be downloadedfrom our website).Date, time, ID number, set days, M-bus primary address, baud rate, output pulse factors, tariffsettings, customised menu......etc.Connection locationV2.4. 08.2011 • Subject to modification15


Energy MeterDistributed by <strong>Belimo</strong>Wiring diagramTEMP HTEMP L5 6 7 8TEMP H TEMP L OSCILLATOR IN1 IN2 OUT1 OU T2 M -BusAC 24V1 2 3 4 10 11 9 50 51 52 53 16 17 18 24 25LN+ _ +Vdc+ _ + _ + _ +White Green BrownPulse iutputPulse output(Energy) (Volume)AC 24VOscillatorM-Bus controller2-wireTemperature sensor(Higher side)RS 232 cable2-wireTemperature sensor(Lower side)Computer / other BMSV2.4. 08. 2011 . Subject to modification17


Energy MeterDistributed by <strong>Belimo</strong>DimensionsIntergrator (EXT-..)0531RJR119RDimensions[mm]110x138.7x45.3Sensor (EXT-..) Dimensions Wires Cable length Element [500ohm at 0°C]0460R030 ø6x33mm 2 3m Pt5000460R531 ø6x85mm 2 3m Pt5000460R532 ø6x134mm 2 3m Pt5000460R533 ø6x173mm 2 3m Pt500Plastic headAluminum head9 91732158484Sensor (EXT-..) Dimensions Wires Head Element [500ohm at 0°C]0460R850 ø6x84mm 4 Aluminium Pt5000460R851 ø6x134mm 4 Aluminium Pt5000460R852 ø6x174mm 4 Aluminium Pt5000460R853 ø6x84mm 4 Plastic Pt5000460R854 ø6x134mm 4 Plastic Pt5000460R855 ø6x174mm 4 Plastic Pt500Cable (EXT-..) Type Lengthcable400 4-wired shield cable on requestPockets (EXT-..) Dimensions0460A206 ø6x52xG 1/2”0460A207 ø6x111.5xG 1/2”0460A208 ø6x161.5xG 1/2”0460A209 ø6x201.5xG 1/2”18V2.4. 08.2011 • Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>DimensionsFlow sensor Superstatic 440Cable length 3mFig. 1 Fig. 2 Fig. 3DdHhhqp DN G PN Fig.No B[mm] H[mm] L[mm] h[mm] Bolts1.5m 3 /h - ¾” 16 1 125 79 110 - -2.5m 3 /h - 1” 16 1 125 79 190 - -6m 3 /h - 1 ¼” 16 2 78 105 260 - -10m 3 /h - 2” 16 2 78 122 300 - -10m 3 /h 40 - 16 3 150 157 300 110 M16x4LV2.4. 08.2011 • Subject to modificationqp DN PN L[mm] D[mm] d[mm] H[mm] h[mm] Bolts15m 3 /h 50 16 270 165 53 176 125 M16x425m 3 /h 65 16 300 185 69 194 176 M16x840m 3 /h 80 16 300 200 81 208 160 M16x860m 3 /h 100 16 360 220 107 231 180 M16x8100m 3 /h 125 16 250 250 132 258 210 M16x8150m 3 /h 150 16 300 285 159 290 240 M20x8250m 3 /h 200 16 350 340 207 343 295 M20x12400m 3 /h 250 16 450 405 260 402 355 M24x12800m 3 /h 350 16 500 520 510 520 470 M24x161500m 3 /h 500 16 500 715 510 715 650 M30x2019


Energy MeterDistributed by <strong>Belimo</strong>0.10.01Pressure loss [bar] ==>0.111qp1.5 & 2.5(G3/4” & 1”)10Flow [m3/h] ==>qp6(G1-1/4”)qp10(G2” & DN40)qp15(DN50)qp25(DN65)100qp40(DN80)qp60(DN100)qp100(DN125)qp150(DN150)20100010000Pressure LossSontex Superstatic 440log-logqp250(DN200)qp400(DN250)qp800(DN350)qp1500(DN500)V2.4. 08.2011 07.2011 • Subject to modification


Energy MeterDistributed by <strong>Belimo</strong>Supercal 531 Display MenuUser menu (16:32) *1) free choice *...Main menu (17:1)16) free choice ** if presentError menu (1:1) *1) Current error ** if error1) Cumulated energy2) Cumulated volume3) Cumulated energy tarif 1 *4) Cumulated volume tarif 1 *5) Cumulated energy tarif 2 *6) Cumulated volume tarif 2 *7) Cumulated value pulse input A1 *...12) Cumulated value pulse input A6 *13) Flow and return temperatures14) Delta temperature15) Actual power16) Actual flow17) Segments test* if presentSet day (13:2)1) Date set day 1..22) Cumulated energy set day 1...23) Cumulated volume set day 1...24) Cumulated energy, tarif 1, set day 1...2 *5) Cumulated volume, tarif 1, set day 1...2 *6) Cumulated energie, tarif 2, set day 1...2 *7) Cumulated volume, tarif 2, set day 1...2 *8) Pulse input A1 set day 1...2 *...13) Pulse input A6 set day 1...2 ** if presentMonthly values (13:15)1) Storage day for monthly values2) Last monthly value cumulated energy 1...153) Last monthly value cumulated volume 1...154) Last monthly value cum. energy tarif 1, 1..15 *5) Last monthly value cum. volume tarif 1, 1..15 *6) Last monthly value cum. energy tarif 2, 1..15 *7) Last monthly value cum. volume tarif 2, 1..15 *8) Last monthly value input. A1, month 1..15 *...13) Last monthly value input A6, month 1..15 ** if presentSimulation menu (7:1) §1) Start of simulation §2) Volume for simulation §3) Simulation energy4) Delta temperature5) Flow and return temperatures Average values (10:32)6) Simulation volume7) Actual flow1) Power average values 1..32§ editable2) Flow average values 1..323) Temperatures average values 1..324) Delta temperature average values 1..325) Input A1 average values 1..32 *...10) Input A6 average values 1..32 *Service (17:10)1) Custom number §* if present2) Fabrication number MET3) Fabrication number MIO4) Software version5) Hardware version6) Present options7) Temperature sensor type8) Flow type9) Running hoursConfiguration (11:6)V2.4. 08. 2011 . Subject to modification10) Days without flow11) Days without energy12) Current error13) Current error duration14) Last errors 1..1015) Last error durations 1..1016) Last error dates 1..1017) Last error times 1..10§ editable1) Date §2) Time §3) Pulse factor flowmeter4) Units of inputs A1..A6 *5) Pulse factors of inputs A1..A6 *6) Pulse factors of outputs B1..B6 *7) Averaging period8) Max. period9) Primary M-Bus address * §10) M-Bus baudrate *11) Radio adress ** if present§ editableMaximum values (10:32)1) Max. of power, values 1..322) Max. of flow, values 1..323) Max. of temperatures, values 1..324) Max. of delta temperature, values 1..325) Max. of input A1, values 1..32 *...10) Max. of input A6, values 1..32 ** if present21


Market Asia PacificASIA PACIFIC HEADQUARTERS<strong>Belimo</strong> <strong>Actuators</strong> (<strong>Shanghai</strong>) Trading Ltd.479 Chun Dong Road, Building C-2Xin Zhuang Industry Park<strong>Shanghai</strong> 201108, P.R. ChinaTel: +86 21 5483 2929Fax: +86 21 5483 2930E-mail: info.asiapacific@belimo.ch<strong>Belimo</strong> AUSTRALIAMelbourne Office:<strong>Belimo</strong> <strong>Actuators</strong> Pty. Ltd.12 Enterprise CourtMulgrave Business ParkMulgrave, VIC 3170, AustraliaTel: +61 (0)3 9545 0844Fax: +61 (0)3 9545 0855E-mail: info.australia@belimo.chSydney Office:<strong>Belimo</strong> <strong>Actuators</strong> Pty. Ltd.Suite 2.20, 32 Delhi RoadNorth Ryde, NSW 2113AustraliaTel: +61 (0)2 9805 1777Fax: +61 (0)2 9805 1722E-mail: info.australia@belimo.ch<strong>Belimo</strong> CHINA<strong>Shanghai</strong> Office:<strong>Belimo</strong> <strong>Actuators</strong> (<strong>Shanghai</strong>) Trading Ltd.479 Chun Dong Road, Building C-2Xin Zhuang Industry Park<strong>Shanghai</strong> 201108, P.R. ChinaTel: +86 21 5483 2929Fax: +86 21 5483 2930E-mail: info.shanghai@belimo.chBeijing Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.Room 605, Hai Chang Edifice44 Liang Ma Qiao RoadBeijing 100016, P.R. ChinaTel: +86 10 6462 1382Fax: +86 10 6462 1383E-mail: info.beijing@belimo.chChongqing Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.Room 4, 9th floor, Unit 7, Luoma Jiari GardenNo. 36, QingLong Road, Nan’an DistrictChongqing 400060, P.R. ChinaTel: +86 23 6275 3155Fax: +86 23 6280 3380 *519E-mail: info.chongqing@belimo.chGuangzhou Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.Room 1202, Skyline Plaza644 Tong Fu East Road, Haizhu AreaGuangzhou 510240, P.R. ChinaTel: +86 20 3435 1860Fax: +86 20 3435 1870E-mail: info.guangzhou@belimo.ch<strong>Belimo</strong> HONG KONGHong Kong Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.Room 207, 2/F, New Commerce Center19 On Sum Street, Shatin, N.T., Hong KongTel: +852 2687 1716Fax: +852 2687 1795E-mail: info.hongkong@belimo.chJapan Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.7th Floor, Honjo-Azumabashi DJ Building4-19-3, Honjo, Sumida-kuTokyo 130-0004, JapanTel: +81 3 6823 6961Fax: +81 3 3626 3911E-mail: info.japan@belimo.chMalaysia Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.12-1, Jalan PJS 10/2, Subang Indah46000 Petaling Jaya Selangor, MalaysiaTel: +603 5631 2188Fax: +603 5638 2189E-mail: info.malaysia@belimo.chSingapore Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.1 Tannery Road #08-04, One TannerySingapore 347719Tel: +65 6842 1626Fax: +65 6842 1630E-mail: info.singapore@belimo.chTaiwan Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.7F-2, No. 343, Jhonghe Road, Yonghe CityTaipei County 234, TaiwanTel: +886 2 2922 8805Fax: +886 2 2922 8806E-mail: info.taiwan@belimo.chThailand Office:<strong>Belimo</strong> <strong>Actuators</strong> Ltd.90/2 Pensiri PlaceSoi Phaholyothin 32, Phaholyothin RoadChandrakasem, JatujakBangkok 10900, ThailandTel: +662 9415582-3Fax: +662 9415584E-mail: info.thailand@belimo.ch<strong>Belimo</strong> INDIAMumbai Office:<strong>Belimo</strong> <strong>Actuators</strong> India Pvt. Ltd.23/ ABCD, Govt. Industrial Estate,Charkop, Kandivali West,Mumbai 400067, IndiaTel: +91 22 4025 4800Fax: +91 22 4025 4899E-mail: info.india@belimo.chBangalore Office:<strong>Belimo</strong> <strong>Actuators</strong> India Pvt. Ltd.Sreerama Complex,No. 13, 2nd Floor, 5th Cross Road,6th Block, Koramangala,Bangalore 560097, IndiaTel: +91 80 4090 6311Fax: +91 80 4090 6288E-mail: info.india@belimo.chNew Delhi Office:<strong>Belimo</strong> <strong>Actuators</strong> India Pvt. Ltd.Flat No. 516, DLF Tower – B,Jasola Distt. Centre, Jasola,New Delhi 110025, IndiaPhone: +91 11 4107 8501 to 4107 8507Fax: +91 11 4107 8508E-mail: info.india@belimo.chChennai Office:<strong>Belimo</strong> <strong>Actuators</strong> India Pvt. Ltd.#25, Bagavadam Street, T-NagarChennai 600017, IndiaTel: +91 44 4299 9450Fax: +91 44 4299 9451E-mail: info.india@belimo.ch


Innovation, Quality and Consultancy:A partnership for motorising HVAC actuatorswww.belimo.com<strong>Belimo</strong> regional head officesEU BELIMO Automation AGBrunnenbachstrasse 18340 Hinwil, SwitzerlandTel: +41 43 843 61 11Fax: +41 43 843 62 68E-mail: info@belimo.chAP BELIMO <strong>Actuators</strong> (<strong>Shanghai</strong>) Trading Ltd.479 Chun Dong Road, Building C-2Xin Zhuang Industry Park<strong>Shanghai</strong> 201108, P.R. ChinaTel: +86 21 5483 2929Fax: +86 21 5483 2930E-mail: info.asiapacific@belimo.chUS BELIMO Aircontrol (USA), Inc.43 Old Ridgebury RoadDanbury, CT 06813-2928, USATel: +800 543-9038 / 203 791-9915Fax: +800 228-8283 / 203 791-9919Or contact your nearest Sales Representative