5414 654 GB<br />
Specification <strong>Vitocell</strong> 100-E (type SVP/SVPA) (cont.)<br />
TH<br />
n<br />
b<br />
m<br />
HV1/EL<br />
TR1<br />
HV2<br />
TR2<br />
TR4<br />
HR3<br />
HR4/E k<br />
l<br />
TH<br />
HV3/HR1<br />
TR3/HR2<br />
TH<br />
h<br />
g<br />
<strong>Vitocell</strong> 100-E (type SVPA, 750 and 950 litres)<br />
E Drain<br />
EL Air vent valve<br />
HR Heating water return<br />
HV Heating water flow<br />
f<br />
e<br />
d<br />
c<br />
Dimensions <strong>Vitocell</strong> 100-E<br />
Cylinder content l 750 950<br />
Length (7) a mm 1004 1004<br />
Width b mm 1060 1060<br />
Height c mm 1895 2195<br />
d mm 1777 2083<br />
e mm 1547 1853<br />
f mm 1067 1219<br />
g mm 967 1119<br />
h mm 676 752<br />
k mm 386 386<br />
l mm 155 155<br />
m mm 535 535<br />
7 excl. thermal insulation n mm 7 790 7 790<br />
o mm 140 140<br />
a<br />
b<br />
HV3/HR1<br />
o<br />
TR<br />
TH Fitting for thermometer sensor or additional sensor<br />
TR Sensor well for cylinder temperature sensor or control thermostat<br />
Pressure drop on the heating water side<br />
Pressure drop in mbar<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0.9<br />
0.8<br />
0.7<br />
0.6<br />
0.5<br />
0.4<br />
0.3<br />
0.2<br />
1000<br />
<strong>Vitocell</strong> 100-E<br />
A<br />
2000<br />
Flow rate in l/h<br />
3000<br />
B<br />
4000<br />
5000<br />
A Type SVP, 400 litre capacity<br />
B Type SVPA, 750 and 1000 litre capacity<br />
VITOCELL 100-E/140-E/160-E VIESMANN 7