Polymer insulated fire-rated twisted pair<br />
cable for protection of critical fire alarm<br />
circuits.<br />
<strong>Raychem</strong> <strong>CI</strong> is a 2-hour fire-rated fire alarm<br />
cable. When installed in accordance with<br />
the requirements of the relevant U.S. and<br />
Canadian codes, <strong>Raychem</strong> <strong>CI</strong> meets the<br />
survivability requirements for fire alarm circuits<br />
as outlined in the National Fire Alarm<br />
Code (NFPA 72), Article 760 of the National<br />
Electrical Code (NFPA 70) and the Canadian<br />
National Building Code. It meets all the<br />
electrical and fire-resistive requirements of<br />
NFPA 502 and NFPA 130.<br />
<strong>Raychem</strong> <strong>CI</strong> fire alarm cables are 2-hour<br />
fire-rated to UL 2196 (and ULC S139 when<br />
installed in conduit). If installing <strong>CI</strong> in conduit,<br />
install in accordance with the details<br />
described in Electrical Circuit Protective<br />
Cable construction<br />
Unshielded cable<br />
Silicone rubber insulation<br />
Annealed solid copper conductor<br />
Low-smoke, zero-halogen<br />
polyolefin jacket<br />
<strong>Raychem</strong> <strong>CI</strong><br />
System (FHIT), System No. 22 of the UL<br />
Fire Resistance Directory.<br />
<strong>Raychem</strong> <strong>CI</strong> is:<br />
• UL Classified as 2-hour fire-resistive<br />
cable per UL 2196 (utilization voltage<br />
72 V to ground max.)<br />
• UL Listed Type FPLR-<strong>CI</strong> fire alarm<br />
cable (1)<br />
• UL Listed for wet location<br />
• ULC Listed as 2-hour fire-rated to ULC<br />
S139 (utilization voltage 72 V to ground<br />
max.)<br />
• CSA Certified as Type FAS 105<br />
• FT-4 / IEEE 1202 Vertical Flame Rating<br />
• -LS limited smoke rating<br />
(1) Other UL listings available on request –<br />
NPLF-<strong>CI</strong>, ITC, PLTC<br />
2-hour fire-rated, polymer insulated,<br />
fire alarm cable<br />
Applications include the main trunk or<br />
“backbone” of multiplex alarm systems in<br />
high-rise buildings and institutions, and<br />
from each data-gathering panel to the point<br />
they enter the notification zone being<br />
served.<br />
<strong>Raychem</strong> <strong>CI</strong> is ideal for:<br />
• High-rise buildings, for fire alarm and<br />
voice communication systems.<br />
• Hospitals and other institutions where<br />
mobility is limited, for emergency<br />
communication systems.<br />
• Tunnels and subways, for the emergency<br />
voice communication system.<br />
• Airports, stadiums, hotels, banks, etc.<br />
For additional information, contact your<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong> representative or<br />
call Tyco <strong>Thermal</strong> <strong>Controls</strong> at<br />
(800) 545-6258.<br />
Shielded cable<br />
Copper/polyester tape shield<br />
Stranded copper drain wire<br />
Silicone rubber insulation<br />
Annealed solid copper conductor<br />
Low-smoke, zero-halogen<br />
polyolefin jacket<br />
Cable Construction<br />
Conductors Annealed solid copper, designed to ensure tensile strength under fire conditions. Class “B”<br />
stranded conductor is also available. Contact Tyco <strong>Thermal</strong> <strong>Controls</strong> for more information.<br />
Insulation Conductors are insulated with a 35 mil layer of thermoset low-smoke zero-halogen silicone<br />
rubber.<br />
Circuit identification Conductor insulation is printed with “1-Black” and “2-Red”, or color coded black and red.<br />
Shielded construction Conductors are twisted together along with a flexible stranded bare copper drain<br />
wire. This assembly is helically wrapped with a laminated copper/polyester foil tape in<br />
continuous contact with the drain wire.<br />
Unshielded construction Conductors are twisted together with a helically applied polyester binder tape.<br />
Jacket The shielded cable core is covered with an extruded layer of red flame-retardant, low-smoke,<br />
zero-halogen polyolefin.<br />
Cable identification Printed on outer jacket with sequential footage markers.<br />
H57774 11/11 www.tycothermal.com 1 of 2<br />
1. Fire-Rated Cables 2. Non-Fire-Rated Cables 3. Service Entrance<br />
Cable Systems<br />
4. Zero EMI Cable<br />
Systems<br />
5. Technical Data<br />
Sheets<br />
6. Codes and Standards 6. Appendixes<br />
7. Index
<strong>Raychem</strong> <strong>CI</strong><br />
Cable Type Designation<br />
Cable Type Standard<br />
FPLR-<strong>CI</strong> UL 1666, UL 1424<br />
NPLFR-<strong>CI</strong> UL 1666, UL 1425<br />
CL3R-<strong>CI</strong>, PLTC UL 13 (Class 3 Remote Control, Signalling and Power Limited cable)<br />
ITC UL 2250<br />
CMR UL 444 /CSA C22.2 NO.214<br />
FAS 105 CSA C22.2 No. 208<br />
Cable Specifications (nominal)<br />
Conductor Insulation Jacket<br />
Number of<br />
size thickness thickness Cable diameter Weight Capacitance<br />
Product code<br />
Shielded<br />
conductors (AWG) (mils) (mils) (in) (mm) (lbs/kft) (kg/km) (pF/ft) (pF/m)<br />
<strong>CI</strong>-2C18SH 2 18 35 40 0.299 7.6 49 73 26 85<br />
<strong>CI</strong>-2C16SH 2 16 35 40 0.319 8.1 58 86 30 98<br />
<strong>CI</strong>-2C14SH<br />
Unshielded<br />
2 14 35 40 0.347 8.8 74 110 36 118<br />
<strong>CI</strong>-2C18UNSH 2 18 35 40 0.299 7.6 43 64 15 48<br />
<strong>CI</strong>-2C16UNSH 2 16 35 40 0.319 8.1 52 78 17 56<br />
<strong>CI</strong>-2C14UNSH 2 14 35 40 0.347 8.8 65 97 19 62<br />
Additional Features<br />
Approvals<br />
File No.<br />
014444_0_00<br />
<strong>Raychem</strong> <strong>CI</strong> listings in System # 22 include the following:<br />
• Pulling lubricant<br />
• 2-hour fire-rated splices<br />
• 100' vertical support spacings, 16 AWG and above<br />
• 6' spacing between supports<br />
• Minimum 1/2 steel EMT<br />
<strong>Raychem</strong> <strong>CI</strong> is also UL approved for installation in free air.<br />
E63081<br />
E135230<br />
UL Classified, 2-hour fire-resistive cable,<br />
tested to UL 2196<br />
ULC Listed, 2-hour fire-resistant cable,<br />
tested to ULC-S139-00 *<br />
* When installed in 1/2" minimum conduit<br />
2 of 2 www.tycothermal.com H57774 11/11
Worldwide Headquarters<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
7433 Harwin Drive<br />
Houston, TX 77036<br />
USA<br />
Tel: 800-545-6258<br />
Tel: 650-216-1526<br />
Fax: 800-527-5703<br />
Fax: 650-474-7711<br />
info@tycothermal.com<br />
www.tycothermal.com<br />
Canada<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
250 West St.<br />
Trenton, Ontario<br />
Canada K8V 5S2<br />
Tel: 800-545-6258<br />
Fax: 800-527-5703<br />
Latin America<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
7433 Harwin Drive<br />
Houston, TX 77036<br />
United States<br />
Tel: 713-868-4800<br />
Tel: 713-735-8645<br />
Fax: 713-868-2333<br />
Europe, Middle East, Africa (EMEA)<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
Romeinse Straat 14<br />
3001 Leuven<br />
België / Belgique<br />
Tel: +32 16 213 511<br />
Fax: +32 16 213 603<br />
Asia Pacific<br />
Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
20F, Innovation Building,<br />
1009 Yi Shan Rd,<br />
Shanghai 200233,<br />
P.R.China<br />
Tel: +86 21 2412 1688<br />
Fax: +86 21 5426 2937 / 5426 3167<br />
Tyco, Alliance Integrated Systems, AMC, AutoMatrix, AutoSol, BTV, CapaciSense, Chemelex, DHSX, DigiTrace, DigiTrace logo,<br />
DigiTrace Supervisor, Duoterm, ElectroMelt, EM2XR, FHSM, FHSC, FlexFit, FlexiClic, Flowguard, FreezeTrace, FreezGard,<br />
Frostex, Frostex Plus, Frostguard, FroStop, FSE, Gardian, HAK, Handvise, HBTV, HCCL, HotCap, HQTV, HTPG, HTPI, HWAT,<br />
HXTV, IceStop, Interlock, Isocable, Isodrum, Isoheat, Isomantle, Isopad, Isopad Frostguard, Isopad logo, Isopanel, Isotape,<br />
Isotherm, JBM, JBS, K-Flex, K-Flex logo, KHE, KHH, KHL, KHP, KTV, Labsafe, LBTV, LHC, LHFV, LHRV, Metabond, Mini<br />
WinterGard, Miser WinterGard, MoniTrace, Multi-plus, NGC, PetroTrace, PLI, PolyMatrix, Pyro CiC, PyroFLX, Pyromaster, Pyropak,<br />
Pyrosil, PyroSizer, Pyrotenax, Pyrotenax Designer, Pyrotenax logo, QTVR, QuickNet, QuickNet logo, QuickStat, QuickTerm,<br />
RayClic, RaySol, RayStat, Retro WinterGard, RHS, RHSC, RHSM, RMM2, SBF, SBV, SC, SHC, Sheathmaster, ShowerGuard, SLBTV,<br />
Smart Heat for Comfort and Safety, SnoCalc, SnoCalc logo, STS, System 500, System 1850, System 1850-SE, System 2000,<br />
System 2200, T2, T2 logo, T2Blue, T2QuickNet, T2Red, T2Reflecta, TankCalc Plus, TempBus, Thermoheat, ThermoLimit, Thermo-<br />
Line, Total Care in Heat-tracing, Touch, Trac-Loc, Trac Calc, TraceCalc Net, TraceCalc Net logo, TraceCalc Pro logo, TraceGuard 277,<br />
TraceMaster, Tracer, Tracer logo, TRACERLYNX, TRACERLYNX logo, TraceStat, TraceTek, TraceTek logo, TruckPak, VLBTV, VLKTV, VPL,<br />
We manage the heat you need, WinterGard, WinterGard logo, WinterGard Plus, WinterGard Wet, XL-ERATE, XL-ERATE logo, XL-Trace,<br />
XTV and Zero EMI are registered and/or unregistered trademarks of Tyco <strong>Thermal</strong> <strong>Controls</strong> LLC or its affiliates.<br />
All other trademarks are the property of their respective owners.<br />
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the<br />
suitability of each product for their particular application. Tyco <strong>Thermal</strong> <strong>Controls</strong> makes no warranties as to the accuracy or<br />
completeness of the information, and disclaims any liability regarding its use. Tyco <strong>Thermal</strong> <strong>Controls</strong>' only obligations are those<br />
in the Tyco <strong>Thermal</strong> <strong>Controls</strong> Standard Terms and Conditions of Sale for this product, and in no case will Tyco <strong>Thermal</strong> <strong>Controls</strong><br />
or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of<br />
the product. Specifications are subject to change without notice. In addition, Tyco <strong>Thermal</strong> <strong>Controls</strong> reserves the right to make<br />
changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.<br />
© 2011 Tyco <strong>Thermal</strong> <strong>Controls</strong> LLC