Electrical freeze protection and process<br />

temperature maintenance for both nonhazardous<br />

and hazardous locations with a<br />

flexible cold lead.<br />

Pyrotenax mineral insulated (<strong>MI</strong>) heating<br />

cable with the PyroFLX cold lead option<br />

offers all of the long standing benefits of a<br />

metal sheathed, Alloy 825 <strong>MI</strong> heating cable,<br />

along with the added advantages of a flexible,<br />

easy-to-install cold lead section. This<br />

feature is achieved by utilizing a section of<br />

Flexible polymeric<br />

tray cable cold lead<br />

<strong>MI</strong> to polymeric<br />

tray cable transition<br />

cold-weather capable, highly impact resistant,<br />

flexible polymeric tray cable, integrated<br />

to a short segment of traditional <strong>MI</strong><br />

cold lead. Installations of PyroFLX can be<br />

performed without excessive cold lead<br />

shaping and forming, minimizing expensive<br />

on-site labour costs. Additionally, since the<br />

tray cable can be easily routed in the field,<br />

junction boxes and cable-to-cable connections<br />

can be extended to make them easily<br />

accessible for maintenance purposes,<br />

Traditional <strong>MI</strong> cold lead<br />

Available with or without quick connector<br />

(field-attachable connector shown)<br />

avoiding costly scaffolding and maintenance<br />

troubleshooting time.<br />

Pyrotenax PyroFLX cables are constructed<br />

and approved for use in nonhazardous and<br />

CID2 and Zone 2 hazardous locations.<br />

For additional information, contact your<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong> representative or<br />

call Tyco <strong>Thermal</strong> <strong>Controls</strong> at<br />

(800) 545-6258.<br />

<strong>MI</strong> cable heated portion<br />

Application Reduced installation costs for series-connected cables, and where extended cold lead runs are<br />

required for power supply connections, for freeze protection and process temperature maintenance<br />

in hazardous and nonhazardous areas.<br />

PyroFLX Cold Lead Length<br />

<strong>MI</strong> cold lead segment* 5 ft (1.5 m) standard<br />

Flexible tray cable* 3 ft (0.9 m) standard<br />

*Longer lengths available<br />

Visit www.tycothermal.com<br />

for more information on our<br />

ten-year extended warranty.<br />

<strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> — Alloy<br />

825 with PyroFLX Cold Lead<br />

Optional polymeric flexible cold lead for Alloy<br />

825 sheathed mineral insulated heating cable<br />

H58737 2/11 www.tycothermal.com 1 of 4<br />

1. Self-<br />

Regulating<br />

<strong>Cable</strong>s<br />

2. Power-<br />

Limiting<br />

<strong>Cable</strong>s<br />

3. Mineral<br />

Insulated<br />

<strong>Cable</strong>s<br />

4. Longline<br />

<strong>Heating</strong><br />

5. Tubing<br />

Bundles<br />

6. Tank<br />

<strong>Heating</strong><br />

7. Snow and<br />

Ice<br />

8. Control and<br />

Monitoring<br />

9. Heat-Trace<br />

Panels<br />

10.Engineered<br />

Products<br />

11.Steam-<br />

Tracing<br />

Systems<br />

12.Technical<br />

Data<br />

Sheets<br />

13.Appendixes 14.Index


<strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> — Alloy 825 with PyroFLX Cold Lead<br />

Connector Options<br />

There are three options for connection configurations on the PyroFLX cold lead.<br />

1) Molded quick connector<br />

– Factory installed<br />

– Permanently molded to tray cable (not removable in the field)<br />

– Available in both male and female configurations<br />

2) Field-attachable quick connector<br />

– Installed standard at the factory<br />

– Mechanically attached to tray cable (can be installed or replaced in the field)<br />

– Available in both male and female configurations<br />

3) No connector<br />

– Tray cable only for attachment into junction box<br />

– Customer to supply approved junction box connector<br />

Temperature Rating<br />

Maximum exposure temperature 1200°F (650°C) <strong>MI</strong> heating cable and cold lead<br />

1022°F (550°C) <strong>MI</strong> cable splices and end cap<br />

194°F (90°C) Flexible polymeric PyroFLX cold lead<br />

Approvals<br />

Nonhazardous and Hazardous Locations<br />

Class I, Div. 2, Groups A, B, C, D<br />

Class II, Div. 2, Groups E, F, G<br />

Class III<br />

Zone 2<br />

Basic <strong>Heating</strong> <strong>Cable</strong> Design Configurations <strong>Heating</strong> cables with the PyroFLX cold lead option are supplied as complete factory-fabricated<br />

assemblies consisting of a <strong>MI</strong> heated section joined to a short segment of <strong>MI</strong> non-heating cold<br />

lead, which transitions into a flexible, polymeric tray cable by means of a molded splice.<br />

PyroFLX cold leads are designed for use with Alloy 825 sheathed <strong>MI</strong> heating cables. Refer to<br />

design and technical information on H56870, <strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> – Alloy 825 data sheet.<br />

2 of 4 www.tycothermal.com H58737 2/11


Design A Design B<br />

Design D<br />

Heated<br />

length<br />

Design A: Single conductor cable (61 series only) Design B: Single conductor cable (61 series only)<br />

Heated<br />

length<br />

PyroFLX (End A)<br />

PyroFLX (End A)<br />

Design D: Dual conductor cable (32, 62 series only) Design E: Dual conductor cable (32, 62 series only)<br />

<strong>MI</strong> cold<br />

lead segment<br />

PyroFLX<br />

PyroFLX<br />

transition<br />

<strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> — Alloy 825 with PyroFLX Cold Lead<br />

PyroFLX (End A)<br />

Heated<br />

length<br />

PyroFLX (End B)<br />

Heated<br />

PyroFLX (End A) length<br />

PyroFLX (End B)<br />

<strong>Heating</strong> <strong>Cable</strong> Catalog Number To order an <strong>MI</strong> heating cable with the PyroFLX cold lead option, it is important to understand the<br />

format of our catalog number.<br />

E/32SP4583/40/1800/68.1/5-7/LS23A/X/T8-10/RLFM<br />

Design E<br />

Flexible polymeric<br />

tray cable<br />

Quick connector<br />

(also available<br />

without connector)<br />

End B; F = Female connector; M = Male connector<br />

(use only with Design B and Design E cables)<br />

End A; F = Female connector; M = Male connector<br />

L = Molded connector; K = Field-attachable connector<br />

PyroFLX cold lead<br />

Length of tray cable; End A - End B (feet)<br />

Hot/cold joint type, “X” (stainless steel) is standard for Alloy 825 cables<br />

Standard <strong>MI</strong> cold lead code(see Table 1)<br />

Length of standard <strong>MI</strong> cold lead; End A - End B (feet)<br />

<strong>Heating</strong> cable voltage<br />

<strong>Heating</strong> cable wattage<br />

<strong>Heating</strong> cable length (in feet)<br />

<strong>Heating</strong> cable reference (see Tables 3, 4, 5 in<br />

H56870, <strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> - Alloy 825 data sheet)<br />

<strong>Heating</strong> cable design configuration (A, B, D, E)<br />

In the above heating cable catalog number, the length of the heated section, standard <strong>MI</strong> cold<br />

lead and the PyroFLX cold lead are in feet. For metric lengths, the heating cable catalog number<br />

would include a suffix “M” after the length, as follows: E/32SP4583/12.2M/1800/68.1/1.5-<br />

2.1M/LS23A/X/T2.4-3.0M/RLFM<br />

Conversion from English to Metric units is: L(ft) x 0.3048 = L(m)<br />

Conversion from Metric to English units is: L(m) x 3.2808 = L(ft)<br />

For Hazardous areas, specify approval required (see above Approvals section).<br />

H58737 2/11 www.tycothermal.com 3 of 4<br />

1. Self-<br />

Regulating<br />

<strong>Cable</strong>s<br />

2. Power-<br />

Limiting<br />

<strong>Cable</strong>s<br />

3. Mineral<br />

Insulated<br />

<strong>Cable</strong>s<br />

4. Longline<br />

<strong>Heating</strong><br />

5. Tubing<br />

Bundles<br />

6. Tank<br />

<strong>Heating</strong><br />

7. Snow and<br />

Ice<br />

8. Control and<br />

Monitoring<br />

9. Heat-Trace<br />

Panels<br />

10.Engineered<br />

Products<br />

11.Steam-<br />

Tracing<br />

Systems<br />

12.Technical<br />

Data<br />

Sheets<br />

13.Appendixes 14.Index


<strong>MI</strong> <strong>Heating</strong> <strong>Cable</strong> — Alloy 825 with PyroFLX Cold Lead<br />

Examples<br />

D/62SQ3100/200/9920/480/5/S25A/X/T3/RLM<br />

• <strong>Heating</strong> cable configuration is Design D<br />

• 600-V rated dual conductor cable, resistance<br />

at 20°C is 0.100 Ω/ft (0.328 Ω/m)<br />

• <strong>Heating</strong> cable length is 200 ft (61 m)<br />

• <strong>Heating</strong> cable wattage is 9920 W at 480 V<br />

• Standard <strong>MI</strong> cold lead portion length is 5 ft<br />

(1.5 m)<br />

• Standard <strong>MI</strong> cold lead code is S25A<br />

• Standard stainless steel 'X' hot/cold joint<br />

• Tray cable cold lead length is 3 ft (0.9 m)<br />

• PyroFLX cold lead option with molded<br />

male quick connector<br />

E/32SQ3200/25.0M/870/120/2.1-<br />

4.1M/LS23A/X/T5-10M/RKFM<br />

• <strong>Heating</strong> cable configuration is Design E<br />

• 300-V rated dual conductor cable, resistance<br />

at 20°C is 0.2 Ω/ft (0.656 Ω/m)<br />

• <strong>Heating</strong> cable length is 25 m (82 ft)<br />

• <strong>Heating</strong> cable wattage is 870 W at 120 V<br />

• Standard <strong>MI</strong> cold lead portion length is 2.1<br />

m (7 ft) on end A and 4.1 m (13 ft) on end<br />

B<br />

• Standard <strong>MI</strong> cold lead code is LS23A<br />

• Standard stainless steel 'X' hot/cold joint<br />

• Tray cable cold lead length is 5 m (16 ft) on<br />

end A and 10 m (33 ft) on end B<br />

• PyroFLX cold lead option with field attachable<br />

female quick connector on end A and<br />

field attachable male quick connector on<br />

end B<br />

Table 1 PyroFLX Cold Leads<br />

Design A, D, E Design B<br />

Cold lead reference Maximum voltage (V) Maximum current (A) Cold lead reference Maximum voltage (V) Maximum current (A)<br />

LS23A 300 23 S29A 600 29<br />

S25A 600 25 S40A 600 30<br />

S34A 600 30<br />

Ground-Fault Protection<br />

To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or<br />

improperly installed, and to comply with the requirements of Tyco <strong>Thermal</strong> <strong>Controls</strong>, agency certifications,<br />

and national electrical codes, ground-fault equipment protection must be used on<br />

each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.<br />

Many DigiTrace control and monitoring systems meet the ground-fault protection requirement.<br />

4 of 4 www.tycothermal.com H58737 2/11


Worldwide Headquarters<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

7433 Harwin Drive<br />

Houston, TX 77036<br />

USA<br />

Tel: 800-545-6258<br />

Tel: 650-216-1526<br />

Fax: 800-527-5703<br />

Fax: 650-474-7711<br />

info@tycothermal.com<br />

www.tycothermal.com<br />

Canada<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

250 West St.<br />

Trenton, Ontario<br />

Canada K8V 5S2<br />

Tel: 800-545-6258<br />

Fax: 800-527-5703<br />

Latin America<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

7433 Harwin Drive<br />

Houston, TX 77036<br />

United States<br />

Tel: 713-868-4800<br />

Tel: 713-735-8645<br />

Fax: 713-868-2333<br />

Europe, Middle East, Africa (EMEA)<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

Romeinse Straat 14<br />

3001 Leuven<br />

België / Belgique<br />

Tel: +32 16 213 511<br />

Fax: +32 16 213 603<br />

Asia Pacific<br />

Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

20F, Innovation Building,<br />

1009 Yi Shan Rd,<br />

Shanghai 200233,<br />

P.R.China<br />

Tel: +86 21 2412 1688<br />

Fax: +86 21 5426 2937 / 5426 3167<br />

Tyco, Alliance Integrated Systems, AMC, AutoMatrix, AutoSol, BTV, CapaciSense, Chemelex, DHSX, DigiTrace, DigiTrace logo,<br />

DigiTrace Supervisor, Duoterm, ElectroMelt, EM2XR, FHSM, FHSC, FlexFit, FlexiClic, Flowguard, FreezeTrace, FreezGard,<br />

Frostex, Flostex Plus, Frostguard, FroStop, FSE, Gardian, HAK, Handvise, HBTV, HCCL, HotCap, HQTV, HTPG, HTPI, HWAT,<br />

HXTV, IceStop, Interlock, Isocable, Isodrum, Isoheat, Isomantle, Isopad, Isopad Frostguard, Isopad logo, Isopanel, Isotape,<br />

Isotherm, JBM, JBS, K-Flex, K-Flex logo, KHE, KHH, KHL, KHP, KTV, Labsafe, LBTV, LHC, LHFV, LHRV, Metabond, Mini<br />

WinterGard, Miser WinterGard, MoniTrace, Multi-plus, NGC, PetroTrace, PLI, PolyMatrix, Pyro CiC, PyroFLX, Pyromaster, Pyropak,<br />

Pyrosil, PyroSizer, Pyrotenax, Pyrotenax Designer, Pyrotenax logo, QTVR, QuickNet, QuickNet logo, QuickStat, QuickTerm,<br />

RayClic, RaySol, RayStat, Retro WinterGard, RHS, RHSC, RHSM, RMM2, SBF, SBV, SC, SHC, Sheathmaster, ShowerGuard,<br />

ShrinkCap, ShrinkSeal, ShrinkSystems, ShrinkTool, ShrinkTube, SLBTV, SnoCalc, SnoCalc logo, STS, System 500, System 1850,<br />

System 1850-SE, System 2000, System 2200, T2, T2 logo, T2Blue, T2QuickNet, T2Red, T2Reflecta, TankCalc Plus, TempBus, Thermoheat,<br />

ThermoLimit, ThermoLine, Touch, Trac-Loc, TraceCalc, TraceCalc Net, TraceCalc Net logo, TraceCalc Pro logo, TraceGard 277,<br />

TraceMaster, Tracer, Tracer logo, TracerLynx, TracerLynx logo, TraceStat, TraceTek, TraceTek logo, TruckPak, VLBTV, VLKTV, VPL,<br />

We manage the heat you need, WinterGard, WinterGard logo, WinterGard Plus, WinterGard Wet, XL-Trace, XTV and Zero E<strong>MI</strong> are<br />

registered and/or unregistered trademarks of Tyco <strong>Thermal</strong> <strong>Controls</strong> LLC or its affiliates.<br />

All other trademarks are the property of their respective owners.<br />

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the<br />

suitability of each product for their particular application. Tyco <strong>Thermal</strong> <strong>Controls</strong> makes no warranties as to the accuracy or<br />

completeness of the information, and disclaims any liability regarding its use. Tyco <strong>Thermal</strong> <strong>Controls</strong>' only obligations are those<br />

in the Tyco <strong>Thermal</strong> <strong>Controls</strong> Standard Terms and Conditions of Sale for this product, and in no case will Tyco <strong>Thermal</strong> <strong>Controls</strong><br />

or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of<br />

the product. Specifications are subject to change without notice. In addition, Tyco <strong>Thermal</strong> <strong>Controls</strong> reserves the right to make<br />

changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.<br />