29.11.2012 Views

FROM ISLANDING PROTECTION TO ISLANDING ... - UfE GmbH

FROM ISLANDING PROTECTION TO ISLANDING ... - UfE GmbH

FROM ISLANDING PROTECTION TO ISLANDING ... - UfE GmbH

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>FROM</strong> <strong>ISLANDING</strong> <strong>PROTECTION</strong> <strong>TO</strong> <strong>ISLANDING</strong> CONTROL<br />

10 Years of Experience with ENS Safety Interface<br />

Klaus Köln, Axel Grabitz<br />

<strong>UfE</strong> <strong>GmbH</strong><br />

18059 Rostock, Joachim-Jungius-Str. 9<br />

klaus.koeln@ufegmbh.de<br />

Purpose of the Work:<br />

The purpose is to show the progress in Islanding Control Interfaces based on Grid Impedance Step Monitoring<br />

Background:<br />

The last generation of <strong>UfE</strong> ENS (automatic disconnection device) is reaching an excellent level in safety and performance.<br />

The devices are meeting the new release of the DIN VDE 0126 prestandard. With the approved functional safety defined in<br />

the DIN VDE 0126 there is no need of repeated testing procedures.The <strong>UfE</strong> ENS is used as a separate device or integrated<br />

in inverters including Fronius, Aixcon, Mastervolt, Pairan, Philips and Xantrex.<br />

Innovation:<br />

The use of impedance step monitoring allows a lower grid frequency limit and a resulting support to grid stability without<br />

the problems of a larger Non Detection Zone (NDZ). The improvements are based on a lot of new methods like:<br />

new methods of mesurement<br />

self optimizing switching level<br />

automatic calibration and self test<br />

automatic syncronization and signal limiting in parallel connections<br />

automatic optimization of signal patterns.<br />

Results:<br />

Performance of ENS has been testet by the ISET in Kassel using 15 ENS26 Devices in parallel connection with up to 16<br />

different inverters and 15 BISI units (The BISI is deveoped in the SIDENA Project by ISET as another safety interface<br />

using Impedance Step Monitoring). The devices showed best performance even under these critical conditions.<br />

The ENS is not only used in PV-Systems but also in any other DG (Distributed Generation) systems connected to the low<br />

voltage grid. ( small wind and hydro systems, motor- , sterling- and fuell-cell CHP). The multiple use of different methods<br />

and – if neccessary different country settings- allows to meet any requirements. A new function is the automatic passive<br />

synchronization of controlled islanding inverters or synchronous machines to support back-up supply without interruption.<br />

The latest development is a three-phase ENS with integrated relais. These type of relays use permanent magnets for contact<br />

pressure. No power is needed to keep a switching state. This saves installation and wiring of external contactors and their<br />

energy consumtion.<br />

Conclusions:<br />

Many years of field experience in Germany ,Austria, Belgium, France and the ISET research shows that improved<br />

Impedance Step Monitoring is a secure method to detect uncontrolled islanding even under balanced load conditions where<br />

passive methods could fail.<br />

Background:<br />

Impedance step monitoring as a method to detect<br />

uncontrolled islanding of grid connected inverters was first<br />

used in the <strong>UfE</strong> NEG 1500 Inverter in 1992. In islandig<br />

tests this Inverter could not be forced into islanding<br />

conditions by matched load and generation.<br />

So this method was used to establish the new ENS -<br />

standard of grid monitoring for PV-inverters in Germany.<br />

Also new was a level of approved functional safety,<br />

defined in the drafts of the new standard. The typical Non<br />

Detection Zone (NDZ) known from the passive methods<br />

monitoring frequency and voltage does not accur with the<br />

new method. But there had been some problems with<br />

overreaction. Some inverters using the ENS reacted too<br />

sensible under special grid conditions like remote houses<br />

conneted with long overhead wires. There were also<br />

problems with multiple use of inverters, the ENS systems<br />

could disturbe each other. But about 98% of the<br />

installations had no problems with overreaction of the<br />

ENS. There is also in other coutries the concern of grid<br />

interference with the use of many ENS systems adding<br />

their test signals. But the main background of this concern<br />

was not the <strong>UfE</strong> ENS using a low reactive current of 50<br />

Hz but another producer of inverters using high current<br />

sharp pulses as test signals. Another problem was related<br />

to high levels of remote control signals in the grid<br />

disturbing the impedance mesurement.<br />

These problems are solved.<br />

<strong>UfE</strong> specialized in the ENS technology and developed<br />

seperate devices that could be used with any inverters.<br />

Two patents were issued on special methods of impedance<br />

measurment and ENS devices and the technology was also<br />

used in licence by other inverter producing companies.<br />

There were Fronius, Sunpower, Sunways, Sputnik<br />

Engineering, Wuseltronik, Aixcon and later Mastervolt,<br />

Pairan, Philips and Xantrex. There must be more than<br />

100,000 of Inverters running with <strong>UfE</strong>-ENS until now.<br />

The ENS was not used only in PV Systems but also in<br />

small CHP units.<br />

<strong>UfE</strong> did a lot of research and developement to solve the<br />

problems with overreaction and paralled operation. The<br />

new generation of ENS Systems (ENS26 and ENS31) is<br />

used since 4 years and is demonstrating excellent<br />

performance.<br />

Innovation:<br />

Improved methods of impedance mesurement were used:<br />

Different signal patterns, synchronisation of parallel<br />

operating ENS forming a kind of decentral pilot tone and<br />

regulation of the level of this signal according to the<br />

quantity of ENS devices and grid conditions. A new<br />

method is used to adept the switching level of impedance<br />

step monitoring to the noise of the grid without loosing<br />

safety.


Results:<br />

The ISET Institute in Kassel did some research on parallel<br />

operation of Inverters and separate islanding protection<br />

devices. Different inverters, 15 ENS26 and 15 BISI units<br />

were tested. (the BISI Bidirectional Safety Interface) is<br />

another system using impedance step monitoring. It was<br />

developed by ISET in the SIDENA Project. ISET tested<br />

up to 15 ENS or BISI devices in parallel operation<br />

connected to a single phase together with up to 16<br />

Inverters. Even under this extremly difficult conditions the<br />

ENS and also the BISI demonstrated excellent functional<br />

safety.<br />

Tests were also performed with a resonant cicuit. The<br />

results show that impedance step monitoring is easily able<br />

to pass these kind of islanding test procedures. This is the<br />

chance to discriminate between unsufficient generation in<br />

the grid and uncontrolled islanding and to support grid<br />

stability.<br />

Results from ENS Dataloggers:<br />

Each of the new ENS devices has a memory chip for<br />

datalogging integrated. The datalogger is recording one<br />

second samples of 16 classes of impedance step maxima.<br />

The sums are recorded every 8 hours and in any case of<br />

fault. Fault reasons are recorded. Because of this, there is<br />

an undervoltage record every time the power supply (grid)<br />

is switched off.Impedance step data recorded from two<br />

ENS26.<br />

Data recorded showing very low levels of impedance<br />

steps. Two ENS26 devices were recorded for 85,5 and<br />

101 days. The blue record shows data of an ENS26<br />

operated in parallel with an older ENS25. There is no<br />

synchronisation with these different devices. This might<br />

be the reason of a few recorded impedance steps of more<br />

than 0,3 Ohms. The other device was running in the <strong>UfE</strong><br />

buero.<br />

Impedance step data recorded from two ENS26<br />

Data recorded showing very low levels of impedance<br />

steps. Two ENS26 devices were recorded for 85,5 and<br />

101 days. The blue record shows data of an ENS26<br />

operated in parallel with an older ENS25. There is no<br />

synchronisation with these different devices. This might<br />

be the reason of a few recorded impedance steps of more<br />

than 0,3 Ohms.<br />

The other device was running in the <strong>UfE</strong> buero.


6250000<br />

6000000<br />

5750000<br />

5500000<br />

5250000<br />

5000000<br />

4750000<br />

4500000<br />

4250000<br />

4000000<br />

3750000<br />

3500000<br />

3250000<br />

3000000<br />

2750000<br />

2500000<br />

2250000<br />

2000000<br />

1750000<br />

1500000<br />

1250000<br />

1000000<br />

750000<br />

500000<br />

250000<br />

6000000<br />

5750000<br />

5500000<br />

5250000<br />

5000000<br />

4750000<br />

4500000<br />

4250000<br />

4000000<br />

3750000<br />

3500000<br />

3250000<br />

3000000<br />

2750000<br />

2500000<br />

2250000<br />

2000000<br />

1750000<br />

1500000<br />

1250000<br />

1000000<br />

7500 00<br />

5000 00<br />

2500 00<br />

0<br />

0<br />

Impedance<br />

Zeile 2 -0,3 -0,15 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,6 2 2,4 2,8<br />

Impedance step<br />

DR Ohms -1,6 -1,3 -1 -0,7 -0,5 -0,3 -0,2 -0,1 0 0,1 0,2 0,3 0,5 0,7 1 1,3 1,6<br />

Solarverlag<br />

Büro<br />

Solarverlag85,5d<br />

Büro 101,5d<br />

Conclusions:<br />

There are more than 10 years of field experience with<br />

ENS-Systems in PV-Inverters and also with seperate<br />

devices not only in Germay, but also in Austria, Belgium<br />

and France.<br />

There was also a lot of research and testing done with the<br />

new Islanding protection Systems. There is very good<br />

performance demonstated by the latest generation of<br />

divices.<br />

The early problems with overreaction are solved. There<br />

are no grid interferences even with massive use of ENS<br />

systems.A wider range of frequency limits is possible with<br />

the use of impedance step monitoring as a secure method<br />

to detect uncontrolled islanding.<br />

Secure methods to discriminate between uncontrolled<br />

islanding and an unsufficient balance between load and<br />

generation give the chance to support grid stability.The<br />

existing guidlines and standards for integrating<br />

Distrebuted Energy Resources (DER) into the low voltage<br />

grid are still based on the assumption of a few percent<br />

added to the conventional generated amount of Power.<br />

This is not enough to meet the requirements of the<br />

future.This future will be powered by renewable Energy.<br />

The PV-Systems of the future will be able to operate grid<br />

connected as well as in stand lone or mini grid conditions.<br />

Inverters will controll and stabilize frequency and voltage<br />

of future energy networks. Grid control technologies and<br />

standards will have to meet these challenges.<br />

THREE-PHASE ENS <strong>ISLANDING</strong> CONTROL<br />

DEVICE WITH INTEGRATED RELAYS<br />

The latest ENS development is new three-phase device<br />

with integrated relays. These are polarized trip relays that<br />

need only energy for the moments of switching (about<br />

20ms) . Contact pressure is per- formed by permanent<br />

magnets. The switching capability is up to 100A..<br />

Simplified grid connection of three phased systems:<br />

Until now a three phased ENS had to be installed together<br />

with two external contactors. Auxilary contacts had to be<br />

wired for monitoring the switching status of each of the<br />

contactors.<br />

Contactors saved:<br />

Costs for contactors and wiring are saved, also some space<br />

in the electrical cabinet. The new housing with seperated<br />

terminal box could also be installed without an electrical<br />

cabinet.<br />

Energy saved:<br />

The new ENS is saving the whole energy that would be<br />

necessary to drive two conventionell contators.With PVsystems<br />

and their EEG based high energy prices 20-60<br />

Euros per year could be saved. This will sum up to 400-<br />

1200 Euros in 20 years!<br />

Safety:<br />

The use of polarized trip relays is a novum in safety<br />

related electric applications because energy is needed to<br />

switch to a safe condition. The new ENS is storing this<br />

energy in capacitors. The capacity and charge of these<br />

capacitors are permanently monitored by microprocessors.<br />

With any fault in the system all relays are switched off<br />

instantly using this energy. For there are two sets of relays<br />

connected in series switching off is guaranteed even if a<br />

relay itself is failing.<br />

EINSPEISER<br />

1<br />

3<br />

5<br />

-K10.1<br />

R1R2R3R4<br />

RELAIS<br />

21<br />

-K10.1<br />

22<br />

<strong>UfE</strong> - ENS31<br />

2<br />

4<br />

6<br />

A1 A2<br />

21<br />

-K10.2<br />

22<br />

1<br />

3<br />

5<br />

K1 K2<br />

N L1 L2 L3<br />

KONTAKTE NETZ<br />

2<br />

4<br />

6<br />

A1 A2<br />

-K10.2<br />

N<br />

L1<br />

L2<br />

L3<br />

NETZ<br />

* * * min. 6 A<br />

max. 25 A


CONCLUSIONS<br />

There are more than 10 years of field experience with<br />

ENS-Systems in PV-Inverters and also with seperate<br />

devices not only in Germay, but also in Austria, Belgium<br />

and France.<br />

There was also a lot of research and testing done with the<br />

new Islanding protection Systems. There is very good<br />

performance demonstated by the latest generation of<br />

divices.<br />

The early problems with overreaction are solved. There<br />

are no grid interferences even with massive use of ENS<br />

systems.A wider range of frequency limits is possible with<br />

the use of impedance step monitoring as a secure method<br />

to detect uncontrolled islanding.<br />

Secure methods to discriminate between uncontrolled<br />

islanding and an unsufficient balance between load and<br />

generation give the chance to support grid stability.The<br />

existing guidlines and standards for integrating<br />

Distrebuted Energy Resources (DER) into the low voltage<br />

grid are still based on the assumption of a few percent<br />

added to the conventional generated amount of Power.<br />

This is not enough to meet the requirements of the future.<br />

This future will be powered by renewable Energy. The<br />

PV-Systems of the future will be able to operate grid<br />

connected as well as in stand lone or mini grid conditions.<br />

Inverters will controll and stabilize frequency and voltage<br />

of future energy networks. Grid control technologies and<br />

standards will have to meet these challenges.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!