30<br />

LP-<strong>Gas</strong> Regulators<br />

Indoor Installation of Regulators<br />

Regulators installed inside a building must have the bonnet vent<br />

piped away. To maintain the large vent capacity relief feature of<br />

the regulator, the vent piping should be at least as large as the vent<br />

opening on the regulator bonnet.<br />

To pipe away the LV4404B regulator, for example, remove the vent<br />

screen from the bonnet vent and install 3/4” pipe into the bonnet<br />

vent threads and pipe to the outside of building. Install vent protection<br />

on the outlet of the pipe away vent line. To utilize the vent<br />

screen and retainer supplied with the regulator, use a 3/4” NPT<br />

90º elbow. Insert screen into 3/4” F.NPT outlet of elbow. Thread<br />

retainer into outlet at least 1 turn. Install the elbow with vent screen<br />

pointing down. The vent line must be installed in a manner to prevent<br />

the entry of water, insects, or foreign material that could cause<br />

blockage. The discharge opening must be at least 3 feet from any<br />

opening below it.<br />

NOTE: Do not use regulators with over 5 PSIG inlet pressure<br />

indoors. Follow all local codes and standards as well as NFPA<br />

54 and 58.<br />

3/4” Elbow<br />

Vent Screen<br />

and Retainer<br />

To appliances<br />

From 1 st stage<br />

regulator<br />

3/4” Elbow<br />

3/4” Pipe<br />

3/4” Elbow