32<br />

LP-<strong>Gas</strong> Regulators<br />

Underground Installations<br />

In underground installations the vent tube opening must be above<br />

the maximum water table and kept free from water, insects, and<br />

foreign material. NOTE: if the water mark in the dome of an<br />

underground tank is above the regulator vent tube end or regulator<br />

vent opening, the regulator should be replaced and the situation<br />

corrected.<br />

Grade ground downward and<br />

away around housing dome.<br />

This prevents water collecting<br />

and running into or standing<br />

around dome.<br />

Regulator adjustment closure<br />

cap must be tight.<br />

6 inches minimum<br />

(24 inches minimum if<br />

subject to vehicular traffic).<br />

End of regulator vent tube<br />

located at top inside of<br />

housing dome cover.<br />

2 to 6 inches<br />

minimum.<br />

Reading a Regulator Performance Chart<br />

Refer to the capacity chart for the size and type regulator which fits<br />

your particular application. Check the performance of this regulator<br />

with your actual load at the inlet pressure corresponding to your<br />

lowest winter temperatures (as shown on Page 3).<br />

Example for a Two Stage System<br />

Selecting the First Stage Regulator<br />

1. Assume a load of 500,000 BTUs per hour<br />

2. Assume a minimum delivery pressure of 9.5 psig.