The plc MSG 11:1 <strong>broadcast</strong>s the reference to all drives <strong>on</strong> address 8194 via N15:1. Therefore change<br />

the value of N15:1 between 0 to 500 = 50.0Hz.<br />

The <strong>broadcast</strong> message is a write MSG to all the drives <strong>on</strong> the network, typically used for the Logic<br />

C<strong>on</strong>trol and reference words. Other drive registers would be read <str<strong>on</strong>g>with</str<strong>on</strong>g> a single MSG ’03 Read Holding<br />

Register’ command.. The most important registers are:<br />

Address Read/Write Descripti<strong>on</strong><br />

8192 Write Logic Command<br />

8193 Write Reference 0 to 500 = 0-50.0Hz<br />

8448 Read Logic Status<br />

8449 Read Error codes<br />

8450 Read Frequency Command – Parameter 1<br />

8451 Read Output Frequency – Parameter 2<br />

Up to 8477 Read Step Logic status – Parameter 28<br />

Remember to add 1 to the address when used in the MSG setup screen.<br />

The program associated <str<strong>on</strong>g>with</str<strong>on</strong>g> this test is called<br />

MODBUS_RTU_WITH_MICROLOGIX_1100_AND_POWERFLEX_4_DRIVES_BROADCAST.RSS<br />

Distributi<strong>on</strong>: Related to:<br />

x Open x Inverter Use<br />

Rockwell Offices Opti<strong>on</strong>s Use<br />

Drives Team Applicati<strong>on</strong> Experience<br />

_________________(Name) <strong>on</strong>ly<br />

Page 6 of 6<br />

Generated by D.J.Withenshaw<br />

Date 05/09/2007<br />

Revisi<strong>on</strong> A

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!