Electric Service Standards - CenterPoint Energy
Electric Service Standards - CenterPoint Energy
Electric Service Standards - CenterPoint Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Changes in the 08/23/2012 Revision of the CNP <strong>Service</strong> <strong>Standards</strong> Book<br />
1. Changed date of last revision to 08/23/2012 (Page 1).<br />
2. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 405, Page 25).<br />
Revised 1,000 KCMIL to “2‐1,000 KCMIL ”<br />
“When the total cross‐sectional area of all <strong>Service</strong> Entrance Conductors at a service outlet<br />
location exceed 2‐1,000 KCMIL per phase, a bus bar type weatherhead must be used.”<br />
3. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 423, Page 49)<br />
Revised “<strong>Electric</strong> Engineering” to “Company Personnel”.<br />
“For all new services, Company personnel must be able to verify that the main disconnect is<br />
open before energizing service.”<br />
4. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec513.6, Page 67).<br />
Revised 1,000 KCMIL to “2‐1,000 KCMIL ”<br />
Revised “<strong>Electric</strong> Engineering” to “Company Personnel”.<br />
“When the service entrance requires conductors greater than 2‐1000 KCMIL per phase, a bus<br />
bar type weatherhead must be used. If the service entrance requires conductors less than or<br />
equal to 2‐1,000 KCMIL per phase, then the Customer may utilize either a bus bar type<br />
weatherhead or a conventional type weatherhead installation (See Illustration 26 –<br />
Weatherhead Arrangement for Outdoor Metering, page 59) with outdoor current transformers.<br />
See ARTICLE 513.7 – 514.2 for outdoor current transformer installation. Typical details of a bus<br />
bar type weatherhead are shown in the Illustrations 27‐30, on pages 68‐71. All bus bar<br />
weatherheads must be approved by Company personnel.”<br />
5. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 513.7, Page 72)<br />
Corrected “500 KCMIL” to “1,000 KCMIL”.<br />
“<strong>Service</strong> Entrance Phase Conductors for outdoor metering transformer installations may be<br />
made up of one wire (600 KCMIL through 1,000 KCMIL conductor) or two identical wires per<br />
phase (300 KCMIL through 1,000 KCMIL conductors).”<br />
Revised 1,000 KCMIL (2‐500 KCMIL) to “2,000 KCMIL (2‐1,000 KCMIL)”<br />
“Conductors may not be paralleled where the total combined area per phase is less than 600<br />
KCMIL (2‐300 KCMIL) or greater than 2,000 KCMIL (2‐1,000 KCMIL).”<br />
6. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 517, Page 75)<br />
a) Revised “Company personnel” to “<strong>Electric</strong> Engineering”.<br />
“REQUESTS FOR THE INSTALLATION OF A DISCONNECTING MEANS ON THE LINE SIDE OF A<br />
REMOTE METERING GUTTER MUST BE REFERRED TO ELECTRIC ENGINEERING FOR<br />
APPROVAL OF THE ARRANGEMENT DURING EARLY DESIGN STAGES, PRIOR TO<br />
INSTALLATION OF EQUIPMENT.”<br />
b) Revised “<strong>Electric</strong> Engineering” to “Company personnel”.<br />
“For all new services, Company personnel must be able to verify that the main disconnect is<br />
open before energizing service.”