02.12.2012 Views

Electric Service Standards - CenterPoint Energy

Electric Service Standards - CenterPoint Energy

Electric Service Standards - CenterPoint Energy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Changes in the 08/23/2012 Revision of the CNP <strong>Service</strong> <strong>Standards</strong> Book<br />

1. Changed date of last revision to 08/23/2012 (Page 1).<br />

2. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 405, Page 25).<br />

Revised 1,000 KCMIL to “2‐1,000 KCMIL ”<br />

“When the total cross‐sectional area of all <strong>Service</strong> Entrance Conductors at a service outlet<br />

location exceed 2‐1,000 KCMIL per phase, a bus bar type weatherhead must be used.”<br />

3. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 423, Page 49)<br />

Revised “<strong>Electric</strong> Engineering” to “Company Personnel”.<br />

“For all new services, Company personnel must be able to verify that the main disconnect is<br />

open before energizing service.”<br />

4. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec513.6, Page 67).<br />

Revised 1,000 KCMIL to “2‐1,000 KCMIL ”<br />

Revised “<strong>Electric</strong> Engineering” to “Company Personnel”.<br />

“When the service entrance requires conductors greater than 2‐1000 KCMIL per phase, a bus<br />

bar type weatherhead must be used. If the service entrance requires conductors less than or<br />

equal to 2‐1,000 KCMIL per phase, then the Customer may utilize either a bus bar type<br />

weatherhead or a conventional type weatherhead installation (See Illustration 26 –<br />

Weatherhead Arrangement for Outdoor Metering, page 59) with outdoor current transformers.<br />

See ARTICLE 513.7 – 514.2 for outdoor current transformer installation. Typical details of a bus<br />

bar type weatherhead are shown in the Illustrations 27‐30, on pages 68‐71. All bus bar<br />

weatherheads must be approved by Company personnel.”<br />

5. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 513.7, Page 72)<br />

Corrected “500 KCMIL” to “1,000 KCMIL”.<br />

“<strong>Service</strong> Entrance Phase Conductors for outdoor metering transformer installations may be<br />

made up of one wire (600 KCMIL through 1,000 KCMIL conductor) or two identical wires per<br />

phase (300 KCMIL through 1,000 KCMIL conductors).”<br />

Revised 1,000 KCMIL (2‐500 KCMIL) to “2,000 KCMIL (2‐1,000 KCMIL)”<br />

“Conductors may not be paralleled where the total combined area per phase is less than 600<br />

KCMIL (2‐300 KCMIL) or greater than 2,000 KCMIL (2‐1,000 KCMIL).”<br />

6. Revised/Corrected <strong>Service</strong> <strong>Standards</strong> wording (Sec 517, Page 75)<br />

a) Revised “Company personnel” to “<strong>Electric</strong> Engineering”.<br />

“REQUESTS FOR THE INSTALLATION OF A DISCONNECTING MEANS ON THE LINE SIDE OF A<br />

REMOTE METERING GUTTER MUST BE REFERRED TO ELECTRIC ENGINEERING FOR<br />

APPROVAL OF THE ARRANGEMENT DURING EARLY DESIGN STAGES, PRIOR TO<br />

INSTALLATION OF EQUIPMENT.”<br />

b) Revised “<strong>Electric</strong> Engineering” to “Company personnel”.<br />

“For all new services, Company personnel must be able to verify that the main disconnect is<br />

open before energizing service.”

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!