3 December 2009<br />

Mr H Flototto<br />

<strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Zur Schefferei<br />

D-59821 Arnsberg<br />

Germany<br />

Dear Hubertus<br />

By post & e-mail: hf@sauerland-spanplatte.de<br />

IFC Fire Safety Advice Report <strong>FSA</strong>/<strong>9150</strong>/01<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

Review of Fire Test Evidence & Recommendations<br />

Further to your commission we write this report on our review of the fire test evidence for<br />

<strong>Sauerland</strong> Core fire resisting doorsets and to outline our recommendations for the<br />

development of these doorsets.<br />

Summaries of the tests carried out in the name of <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH are outlined<br />

in Appendices A, B and C categorised according to tubeboard core, solid core/sandwich core<br />

and routed core with moulded skin. The summaries give brief details of the tested<br />

constructions and the results of the tests. It is on the basis of these tested constructions<br />

and International Fire Consultants Ltd’s (IFC) knowledge of the test evidence of other<br />

products, which can be utilised, that this report has been prepared.<br />

1. <strong>Sauerland</strong> <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />

1.1 Test Evidence<br />

There are five tests which have been taken into account in the review of tubeboard core fire<br />

resisting doorsets. There are three tests described in this section which have been<br />

performed according to the general principles of BS476: Part 22: 1987, with the other two<br />

tests following BS EN 1634-1: 2000.<br />

These tests were carried out at Warringtonfire, utilising latched, single acting, single and double<br />

leaf doorsets. The doorsets utilised 44mm thick leaves of various core constructions with<br />

bespoke intumescent seal specifications. Two of the doorsets incorporated glazed apertures<br />

with Georgian wired glass.<br />

A summary of the tests is outlined in Appendix A.<br />

International Fire Consultants Ltd<br />

Head & Registered Office: 20 Park Street, Princes Risborough, Buckinghamshire, England HP27 9AH<br />

Tel: +44(0)1844 275500, Fax: +44(0)1844 274002, E-mail: ifc@intfire.com<br />

Registered No: 2194010 England<br />

An International Fire Consultants Group Company


1.2 Scope for Assessment<br />

A review of the five test results in the following options being available as a scope which could<br />

be included in a subsequent IFC Field of Application Report. This scope would be subject to the<br />

limitations of the report which can be commissioned following this analysis.<br />

All the doorsets utilised have demonstrated at least 30 minutes fire resistance performance.<br />

All the doorsets utilised were single acting and latched, hence both of these limitations will be<br />

incorporated into a Field of Application Report.<br />

The doorsets included single leaf and double leaf configurations, hence both of these options<br />

can be incorporated into a Field of Application Report.<br />

Two of the doorsets utilised have been tested incorporating glazed apertures with Georgian<br />

wired glass, including one on single-leaf doorset and the other on double-leaf doorset, hence<br />

options on glazed apertures can be incorporated into a Field of Application Report. We can<br />

offer a number of glasses as alternatives but if there are other glasses which you would wish to<br />

be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please let us know so that<br />

their test evidence can be reviewed.<br />

Each of the tested doorsets included a door skin on each face, hence the option of various door<br />

skins including material and thickness will be incorporated into a Field of Application Report.<br />

The maximum tested leaf size was a 2040mm high by 927mm wide for single door leaf, and a<br />

2400mm high by 1200mm wide for each leaf of double door. The size of the double leaves<br />

indicates that the possibility of enlarging the single door leaf size would be achievable.<br />

Evaluations for the maximum leaf size will be made for incorporation into a future Field of<br />

Application Report.<br />

1.3 Questions<br />

All the doorsets utilised in this section included tubeboard core, which will be included as an<br />

option on core detail in a Field of Application Report, therefore the following questions,<br />

regarding incorporation of various tubeboard core constructions, need to be confirmed:<br />

2<br />

The core construction of tubeboard 38 RF shown in the test report of WARRES No.<br />

69484/A is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />

<strong>Spanplatte</strong>. Would your confirm the core construction of tubeboard 38 RF?<br />

The core construction of tubeboard 38 RE 7 shown in the WF Test Report No. 159842<br />

(Doorset B) is not included in the Production Range of the Technical Manual of<br />

<strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm the core construction of tubeboard 38 RE 7?<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


If there are other types of tubeboard core constructions, apart from the ones included<br />

in the received test reports, which you would wish to be considered within the<br />

<strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to be<br />

reviewed.<br />

1.4 Recommendation<br />

We feel there is scope to test an unlatched specimen to supplement the test evidence available<br />

and would be pleased to discuss details with you. It is the opinion of IFC, however that there is<br />

considerable scope for inclusion in a Field of Application Report and a proposal for this could be<br />

issued on request.<br />

2. <strong>Sauerland</strong> Solid Core/Sandwich Core Fire Resisting Doorsets<br />

2.1 Test Evidence<br />

There are seven tests which have been taken into account in the review of solid<br />

core/sandwich core fire resisting doorsets. These tests described in this section have been<br />

performed according to the general principles of BS476: Part 22: 1987.<br />

Six of the seven tests were carried out at Warringtonfire whilst the other test was carried out at<br />

Chiltern. They all utilised latched, single acting, single and double leaf doorsets. These tested<br />

doorsets utilised 44mm/45mm/54mm thick leaves of various core constructions with bespoke<br />

intumescent seal specifications. Two of the doorsets incorporated glazed apertures with<br />

Georgian wired glass.<br />

A summary of the tests is outlined in Appendix B.<br />

2.2 Scope for Assessment<br />

A review of the seven test results in the following options being available as a scope which<br />

could be included in a subsequent IFC Field of Application Report. This scope would be subject<br />

to the limitations of the report which can be commissioned following this analysis.<br />

Doorsets with 44mm thick leaf<br />

All three doorsets, with 44mm thick leaves, have demonstrated at least 30 minutes fire<br />

resistance performance.<br />

All the doorsets utilised latched, single acting, single leaf configurations, hence these features<br />

can be incorporated into a Field of Application Report. There is no evidence for unlatched or<br />

double leaf configurations.<br />

There is currently no test evidence to support the use of glazed apertures for these tested<br />

doorsets, therefore this feature can not be incorporated into a Field of Application Report<br />

without additional fire test evidence.<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

3


Each of the tested doorsets included a door skin on each face, either 3mm HDF or 3mm<br />

Hardboard, hence the option of various door skins including material and thickness can be<br />

incorporated into a Field of Application Report.<br />

The maximum tested leaf size was 2040mm high by 926mm wide. This will be taken into<br />

account with any overrun in determining the maximum leaf size to be included into a Field of<br />

Application Report.<br />

Doorset with 45mm thick leaf<br />

The doorset with a 45mm thick leaf has demonstrated 63 minutes fire resistance performance.<br />

The doorset utilised latched, single acting, single leaf configuration, hence these features can be<br />

incorporated into a Field of Application Report. There is no evidence for unlatched or double<br />

leaf configurations.<br />

There is currently no test evidence to support the use of glazed apertures for this doorset,<br />

therefore this feature can not be incorporated into a Field of Application Report without<br />

additional fire test evidence.<br />

The doorset included a layer of 6mm Hardboard on each face, hence it will be incorporated into<br />

a Field of Application Report.<br />

The maximum tested leaf size was 2040mm high by 900mm wide. This will be taken into<br />

account with any overrun in determining the maximum leaf size to be included into a Field of<br />

Application Report.<br />

Doorsets with 54mm thick leaf<br />

The two tested single doorsets with a 54mm thick leaf have demonstrated 71 minutes and 75<br />

minutes fire resistance performance. The double doorset with a 54mm thick leaf achieved 59<br />

minutes fire resistance performance.<br />

All the doorsets were single acting and latched, hence both of these limitations will be<br />

incorporated into a Field of Application Report.<br />

The doorsets included single and double leaf configurations, hence both of these options can be<br />

incorporated into a Field of Application Report.<br />

Two of the doorsets utilised have been tested incorporating glazed apertures with 6mm thick<br />

Georgian wired glass, including one single-leaf doorset (achieving 71min fire resistance<br />

performance) and the other on double-leaf doorset (achieving 59min fire resistance<br />

performance). Options on glazed apertures can be incorporated into a Field of Application<br />

Report. We can offer a number of glasses as alternatives but if there are other glasses which<br />

you would wish to be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please<br />

let us know so that their test evidence can be reviewed.<br />

4<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


Each of the tested doorset included a door skin on each face, hence the option of various door<br />

skins including material and thickness will be incorporated into a Field of Application Report.<br />

The maximum leaf size achieving 60 minutes fire resistance performance was 2040mm high by<br />

928mm wide for single door leaf. The tested double-leaf doorset with different leaf size has not<br />

achieved 60 minutes fire resistance performance, however it is possible that the doorset with<br />

smaller leaves or equally sized double leaf might achieve 60 minutes fire resistance<br />

performance, therefore the maximum leaf size for single and double leaf, discussed above, will<br />

be taken into account when determining the maximum leaf size in a Field of Application Report.<br />

2.3 Questions<br />

In this section, there are five doorsets utilised solid core and two doorsets utilised sandwich<br />

core, hence the option on core construction details will be into a Field of Application Report.<br />

Therefore the following questions, regarding incorporation of various core constructions, need<br />

to be confirmed:<br />

The core construction of solidboard 38 VT5 shown in the test report of WF Test Report<br />

No. 159842 (Doorset A) is not included in the Production Range of the Technical<br />

Manual of <strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm the core construction of<br />

solidboard 38 VT5?<br />

The core construction of solidboard 42 VL shown in the WF Test Report No. 175295<br />

(Doorset A) and the WF Test Report No. 175295 (Doorset B) is not included in the<br />

Production Range of the Technical Manual of <strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm<br />

the core construction of solidboard 42 VL?<br />

If there are other types of solid core and sandwich core constructions, apart from the<br />

ones included in the received test reports, which you would wish to be considered<br />

within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to<br />

be reviewed.<br />

2.4 Recommendation<br />

In this section, there are three different thickness leaves with 44mm, 45mm and 54mm to<br />

achieve 30 minutes and 60 minutes fire resistance performance, but you may not market all of<br />

them. We would ask you to confirm which you do market.<br />

Furthermore, we feel there may be scope to test unlatched specimen and double leaves for the<br />

44mm and 45mm thick leaves to supplement the test evidence available and would be pleased<br />

to discuss details with you. It is the opinion of IFC, however, that there is considerable scope<br />

for inclusion of the FD60 doorsets with 54mm thick leaves in a Field of Application Report and a<br />

proposal for this could be issued on request.<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

5


3. <strong>Sauerland</strong> Moulded Core Fire Resisting Doorsets<br />

3.1 Test Evidence<br />

There are seven tests which have been taken into account in the review of moulded core fire<br />

resisting doorsets. There are five tests described in this section which have been performed<br />

according to the general principles of BS476: Part 22: 1987, while the other two tests<br />

following BS EN 1634-1: 2000.<br />

These tests were carried out at Warringtonfire, utilising single acting, latched and unlatched,<br />

single and double leaf doorsets. The doorsets utilised 44mm/54mm thick leaves of various core<br />

constructions with bespoke intumescent seal specifications. One of the doorsets incorporated<br />

glazed apertures with Georgian wired glass.<br />

A summary of the tests is outlined in Appendix C.<br />

3.2 Scope for Assessment<br />

A review of the seven test results in the following options being available as a scope which<br />

could be included in a subsequent IFC Field of Application Report. This scope would be subject<br />

to the limitations of the report which can be commissioned following this analysis.<br />

Doorsets with 44/45mm thick leaf<br />

The four single-leaf doorsets with 44mm thick leaf, one double-leaf doorset with 44mm thick<br />

leaf and one single-leaf doorset with 45mm thick leaf have demonstrated at least 30 minutes<br />

fire resistance performance.<br />

All the doorsets utilised were single acting, hence the feature will be incorporated into a Field of<br />

Application Report.<br />

Five single-leaf tested doorsets were latched and a double-leaf doorset was unlatched, which<br />

indicates that it is possible for single-leaf doorsets utilising unlatched leaf and double-leaf<br />

doorsets utilising latched leaf. Hence, these features can be included into a Field of Application<br />

Report.<br />

All the tested doorsets included single leaf and double leaf, hence both of these options can be<br />

incorporated into a Field of Application Report.<br />

One of the single-leaf doorsets utilised was tested incorporating glazed apertures with Georgian<br />

wired glass, hence options on glazed apertures can be incorporated into a Field of Application<br />

Report. We can offer a number of glasses as alternatives but if there are other glasses which<br />

you would wish to be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please<br />

let us know so that their test evidence can be reviewed.<br />

6<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


Each of the tested doorset included a layer of moulded hardboard on each face either 3mm<br />

thick or 3.5mm thick, hence the option of various door skins including material and thickness<br />

will be incorporated into a Field of Application Report.<br />

The maximum tested leaf size was 2040mm high by 926mm wide for single-door leaf, and<br />

1981mm high by 762mm wide for each leaf of double door. The size of the double leaves<br />

indicates that the possibility of enlarging the single door leaf size would be achievable, therefore<br />

the maximum leaf size, discussed above, will be considered in determining the maximum leaf<br />

size which can be incorporated into a Field of Application Report.<br />

Doorsets with 54mm thick leaf<br />

The single-leaf doorset with 54mm thick leaf utilised has demonstrated 60 minutes fire<br />

resistance performance.<br />

The tested doorset utilised a latched, single acting, single leaf configuration, hence these<br />

features will be incorporated into a Field of Application Report.<br />

There is currently no test evidence to support the use of glazed apertures for the tested<br />

doorset, therefore this feature can not be incorporated into a Field of Application Report without<br />

additional fire test evidence.<br />

The tested doorset included a layer of 3mm thick moulded hardboard on each face, hence the<br />

feature will be included into a Field of Application Report.<br />

The maximum tested leaf size was 1981mm high by 840mm wide for single door leaf, therefore<br />

the maximum size will be considered for incorporation into a Field of Application Report.<br />

3.3 Questions<br />

In this section, there are seven doorsets that utilised routed core with moulded skin on each<br />

face, hence this option on core construction details will be into a Field of Application Report.<br />

Therefore the following questions, regarding incorporation of various core constructions, need<br />

to be confirmed:<br />

The core construction of tubeboard 38 RF shown in the test report of WARRES No.<br />

69484 B is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />

<strong>Spanplatte</strong>. Would you confirm the core construction of tubeboard 38 RF?<br />

The core construction of solidboard 18 VL shown in the test report of WARRES No.<br />

105976 A is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />

<strong>Spanplatte</strong>. Would you confirm the core construction of solidboard 18 VL?<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

7


8<br />

If there are other types of routing core and moulded skin, apart from the ones included<br />

in the received test reports, which you would wish to be considered within the<br />

<strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to be<br />

reviewed.<br />

3.4 Recommendation<br />

The unlatched double-leaf doorset with each leaf 44mm thick has achieved 31 minutes fire<br />

resisting performance, which will be possible for IFC to incorporate a range of features for<br />

44mm thick doorsets achieving 30 minutes fire resistance into a Field of Application. There may<br />

be scope to test an unlatched specimen with 54mm thick double leaf to supplement the test<br />

evidence available and would be pleased to discuss details with you.<br />

4. Conclusion<br />

The scope of approval that could be included, if commissioned, in IFC Field of Application<br />

Reports is listed in the following table.<br />

Item Latched Unlatched<br />

44mm FD30<br />

<strong>Tubeboard</strong><br />

Core ¡<br />

44mm FD30<br />

Sandwich/<br />

Solid Core ¡<br />

45mm FD60<br />

Sandwich/<br />

Solid Core ¡<br />

54mm FD60<br />

Sandwich/<br />

Solid Core ¡<br />

44mm FD30<br />

Routed Core ¡<br />

54mm FD60<br />

Routed Core ¡<br />

×<br />

×<br />

×<br />

×<br />

¡<br />

¡<br />

¡<br />

¡<br />

Single<br />

Acting<br />

×<br />

×<br />

×<br />

×<br />

Double<br />

Acting<br />

Single<br />

Leaf<br />

Double<br />

Leaf<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

¡<br />

¡<br />

¡<br />

¡<br />

Glazed<br />

Apertures<br />

¡ ¡<br />

¡ ¡<br />

×<br />

×<br />

×<br />

×<br />

¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡<br />

× ×<br />

Note:<br />

= Can be assessed from existing received test evidence<br />

× = Not accessible with existing received test evidence<br />

¢<br />

×<br />

×


We are now in a position to forward proposals and fee estimates for some or all of the<br />

constructions listed for you to commission us to prepare Field of Application Reports. These,<br />

however, are likely to cost in the region of £2,200 - £3,500 per doorset construction to produce<br />

and so we feel that you may wish to consider them on the basis of a longer term strategy, i.e.<br />

some now and some later.<br />

We would also anticipate that you may wish to extend the potential scope for some of the door<br />

leaf types through further fire resistance testing. This could also include design features not<br />

already discussed herein. This can also be discussed as part of the ongoing programme.<br />

We would ask you to review and respond to the above information. Following your response<br />

we will produce a formal proposal and fee estimate for the next step in agreeing the scope of<br />

works.<br />

We trust this is of assistance at this time. If you have any queries please do not hesitate to<br />

contact us.<br />

Yours sincerely: Checked by:<br />

Ping Guo BEng (Hons) MSc David Cooper BEng (Hons) MIWSc<br />

Graduate Engineer Senior Engineer<br />

International Fire Consultants Ltd. (IFC) International Fire Consultants Ltd. (IFC)<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

9


10<br />

APPENDIX A<br />

Summary of Test Evidence on <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


No Test<br />

Number<br />

1<br />

2<br />

3<br />

4<br />

5<br />

WF Test Report<br />

No. 14606<br />

(Doorset B)<br />

WARRES<br />

No. 117066<br />

WARRES<br />

No. 69484/A<br />

WF Test Report<br />

No. 14606<br />

(Doorset A)<br />

WF Test Report<br />

No. 159842<br />

(Doorset B)<br />

Summary of Test Evidence on <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />

Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />

BS EN 1634-1:<br />

2000<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS EN 1634-1:<br />

2000<br />

BS 476: Part<br />

22: 1987<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Double leaf<br />

Partially insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Uninsulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

<strong>Tubeboard</strong> 38 RE<br />

<strong>Tubeboard</strong> 33 RH<br />

With glass opening<br />

300 × 1000 “Georgian<br />

wired”<br />

<strong>Tubeboard</strong> 38 RF<br />

With glass opening<br />

578 × 908× 6mm<br />

“Georgian wired<br />

plate”<br />

<strong>Tubeboard</strong> 38 RE<br />

<strong>Tubeboard</strong> 38 RE 7<br />

2.8mm<br />

MDF+ veneer<br />

5mm<br />

Hardwood<br />

3.2mm<br />

Hardboard<br />

3mm<br />

HDF+ veneer<br />

3mm<br />

Hardboard<br />

927 × 2040<br />

× 44mm<br />

2 × 1200 ×<br />

2400 ×<br />

44mm<br />

837 × 1981<br />

× 44mm<br />

927 × 2040<br />

× 44mm<br />

926 × 2040<br />

× 44mm<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

15 × 2 mm Palusol<br />

frame jambs + head<br />

15 × 2 mm Interdens<br />

base of leaf<br />

2×10× 2 mm Palusol, head<br />

frame<br />

2×10 × 2 mm Interdens,<br />

rebated meeting stile<br />

10 × 2 mm Interdens, frame<br />

jambs<br />

10 × 2mm Palusol LP1002<br />

frame jambs + head<br />

10 × 2mm Pyrostrip 300<br />

glazing seal<br />

15 × 2 mm Palusol<br />

frame jambs + head<br />

15 × 2 mm Interdens<br />

base of leaf<br />

15 × 2 mm Palusol T<br />

frame jambs + head<br />

Integrity: 33 min<br />

Insulation: 33 min<br />

Integrity: 34 min<br />

Insulation: 34 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 36 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 36 min<br />

Insulation: 36 min<br />

Integrity: 36 min<br />

Insulation:36 min<br />

11


12<br />

APPENDIX B<br />

Summary of Test Evidence on Solid Core/Sandwich Core<br />

Fire Resisting Doorsets<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


Summary of Test Evidence on Solid Core/Sandwich Core Fire Resisting Doorsets<br />

No. Test Number Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

WF Test Report<br />

No. 164432<br />

( Doorset B)<br />

WF Test Report<br />

No. 164432<br />

( Doorset A)<br />

WF Test Report<br />

No. 159842<br />

( Doorset A)<br />

Chilten/RF02009<br />

WF Test Report<br />

No. 175295<br />

( Doorset B)<br />

WF Test Report<br />

No. 175295<br />

( Doorset A)<br />

WARRES<br />

No. 105976 B<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

BS 476: Part<br />

22: 1987<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Latched<br />

Single acting<br />

Double leaf<br />

Partially insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Partially insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

<strong>Sauerland</strong><br />

Sandwich board<br />

38 S2<br />

<strong>Sauerland</strong><br />

Sandwich board<br />

38 S3K<br />

<strong>Sauerland</strong><br />

Solid board 38 VT5<br />

<strong>Sauerland</strong> 33 VL<br />

<strong>Sauerland</strong> 42 VL<br />

With glass opening<br />

6mm thick “Georgian<br />

wired polished plate”<br />

<strong>Sauerland</strong> 42 VL<br />

With glass opening<br />

6mm thick “Georgian<br />

wired polished plate”<br />

<strong>Sauerland</strong> 38 VL<br />

+ 5mm MDF<br />

3mm HDF<br />

3mm HDF<br />

3mm<br />

Hardboard<br />

6mm<br />

Hardboard<br />

5.8mm HDF<br />

5.8mm HDF<br />

3mm<br />

Hardboard<br />

926 × 2040 ×<br />

44mm<br />

926 × 2040 ×<br />

44mm<br />

926 × 2040 ×<br />

44mm<br />

900 × 2040 ×<br />

45mm<br />

Primary leaf<br />

900 × 2400 ×<br />

54mm +<br />

secondary leaf<br />

415 × 2400 ×<br />

54mm<br />

928 × 2040 ×<br />

54mm<br />

840 × 1981 ×<br />

54mm<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

15 × 2 mm Palusol T<br />

frame jambs + head<br />

15 × 2 mm Palusol T<br />

frame jambs + head<br />

15 × 2 mm Palusol T<br />

frame jambs + head<br />

2× 10 × 2 mm Palusol<br />

frame jambs + head<br />

10 × 2 mm Interdens<br />

(between core and<br />

framing)<br />

30 × 2 mm Rokustrip<br />

frame jambs + head<br />

20 × 2 mm Rokustrip / 10<br />

× 2 mm Rokustrip<br />

(meeting stile)<br />

30 × 2 mm Rokustrip<br />

frame jambs + head<br />

2× 10 × 2 mm Palusol<br />

frame jambs + head<br />

Integrity: 31 min<br />

Insulation: 31 min<br />

Integrity: 40 min<br />

Insulation: 39 min<br />

Integrity: 40 min<br />

Insulation:40 min<br />

Integrity: 63 min<br />

Insulation:63 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 59 min<br />

Insulation:59 min<br />

Integrity: 71 min<br />

Insulation:71 min<br />

Integrity: 75 min<br />

Insulation: 75 min<br />

13


14<br />

APPENDIX C<br />

Summary of Test Evidence on Routed Core with Moulded Skin<br />

Fire Resisting Doorsets<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd


Summary of Test Evidence on Routed Core with Moulded Skin Fire Resisting Doorsets<br />

No. Test Number Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

WARRES<br />

No. 105554<br />

WARRES<br />

No. 69484/B<br />

WARRES<br />

No. 67040/B<br />

WARRES<br />

No. 60270/B<br />

WF Test Report<br />

No. 145083<br />

(Doorset A)<br />

WF Test Report<br />

No. 145083<br />

(Doorset B)<br />

WARRES<br />

No. 105976/A<br />

BS 476:<br />

Part 22: 1987<br />

BS 476:<br />

Part 22: 1987<br />

BS 476:<br />

Part 22: 1987<br />

BS 476:<br />

Part 22: 1987<br />

BS EN<br />

1634 – 1:2000<br />

BS EN<br />

1634 – 1:2000<br />

BS 476:<br />

Part 22: 1987<br />

Single acting<br />

Double leaf<br />

Fully insulated<br />

Unlatched<br />

Single acting<br />

Single leaf<br />

Uninsulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Single acting<br />

Single leaf<br />

Fully insulated<br />

Latched<br />

Solid board 38 PV<br />

With moulding<br />

<strong>Tubeboard</strong> 38 RF<br />

With glass opening<br />

578 × 908 × 6mm<br />

“Georgian Wired ”<br />

Solid board 38 PV<br />

With moulding<br />

Solid board 38 PV<br />

(chipboard core)<br />

With moulding<br />

Solid board 38 PV<br />

With moulding<br />

Solid board 38 PV<br />

With moulding<br />

Solid board 18VL<br />

3mm Moulded<br />

hardboard<br />

(MASONITE)<br />

3mm Moulded<br />

Hardboard<br />

(MASONITE)<br />

3.5mm Moulded<br />

hardboard<br />

(MASONITE)<br />

3mm Moulded<br />

hardboard<br />

(MASONITE)<br />

3mm Moulded<br />

hardboard<br />

(MASONITE)<br />

3mm Moulded<br />

hardboard<br />

(MASONITE)<br />

3mm Moulded<br />

hardboard<br />

(MASONITE)<br />

2 ×762 × 1981<br />

× 44mm<br />

837 × 1981<br />

× 44mm<br />

824 × 1985<br />

× 45mm<br />

820 × 1980<br />

× 44mm<br />

926 × 2040<br />

× 44mm<br />

926 × 2040<br />

× 44mm<br />

840 × 1981<br />

× 54mm<br />

IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />

Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />

International Fire Consultants Ltd<br />

10× 2 mm Palusol<br />

top rail<br />

10 × 2 mm Interdens<br />

rebated meeting stile +<br />

leaf james + bottom rail<br />

10 × 2mm Palusol LP1002<br />

(frame jambs + head)<br />

10 × 2mm Pyrostrip 300<br />

(glazing seal)<br />

10 × 2mm Palusol LP1002<br />

in top edge of door leaf<br />

10 × 4mm Palusol LP1004<br />

frame jambs + head<br />

15× 2 mm Palusol<br />

head + frame james<br />

15× 2 mm Palusol<br />

head + frame james<br />

10 × 2 mm Interdens, bottom<br />

rail<br />

2× 10 × 2 mm Palusol<br />

frame jambs + head<br />

Integrity: 31 min<br />

Insulation: 31 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 32 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 33 min<br />

Insulation: 33 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 34 min<br />

Insulation: 34 min<br />

( opening towards<br />

the furnace)<br />

Integrity: 36 min<br />

Insulation:32 min<br />

Integrity: 37 min<br />

Insulation:35 min<br />

Integrity: 60 min<br />

Insulation: 60 min<br />