IFC Fire Safety Advice Report <strong>FSA</strong>/<strong>9150</strong>/01<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
Review of Fire Test Evidence & Recommendations<br />
Further to your commission we write this report on our review of the fire test evidence for<br />
<strong>Sauerland</strong> Core fire resisting doorsets and to outline our recommendations for the<br />
development of these doorsets.<br />
Summaries of the tests carried out in the name of <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH are outlined<br />
in Appendices A, B and C categorised according to tubeboard core, solid core/sandwich core<br />
and routed core with moulded skin. The summaries give brief details of the tested<br />
constructions and the results of the tests. It is on the basis of these tested constructions<br />
and International Fire Consultants Ltd’s (IFC) knowledge of the test evidence of other<br />
products, which can be utilised, that this report has been prepared.<br />
1. <strong>Sauerland</strong> <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />
1.1 Test Evidence<br />
There are five tests which have been taken into account in the review of tubeboard core fire<br />
resisting doorsets. There are three tests described in this section which have been<br />
performed according to the general principles of BS476: Part 22: 1987, with the other two<br />
tests following BS EN 1634-1: 2000.<br />
These tests were carried out at Warringtonfire, utilising latched, single acting, single and double<br />
leaf doorsets. The doorsets utilised 44mm thick leaves of various core constructions with<br />
bespoke intumescent seal specifications. Two of the doorsets incorporated glazed apertures<br />
with Georgian wired glass.<br />
A summary of the tests is outlined in Appendix A.<br />
International Fire Consultants Ltd<br />
Head & Registered Office: 20 Park Street, Princes Risborough, Buckinghamshire, England HP27 9AH<br />
Tel: +44(0)1844 275500, Fax: +44(0)1844 274002, E-mail: ifc@intfire.com<br />
Registered No: 2194010 England<br />
An International Fire Consultants Group Company
1.2 Scope for Assessment<br />
A review of the five test results in the following options being available as a scope which could<br />
be included in a subsequent IFC Field of Application Report. This scope would be subject to the<br />
limitations of the report which can be commissioned following this analysis.<br />
All the doorsets utilised have demonstrated at least 30 minutes fire resistance performance.<br />
All the doorsets utilised were single acting and latched, hence both of these limitations will be<br />
incorporated into a Field of Application Report.<br />
The doorsets included single leaf and double leaf configurations, hence both of these options<br />
can be incorporated into a Field of Application Report.<br />
Two of the doorsets utilised have been tested incorporating glazed apertures with Georgian<br />
wired glass, including one on single-leaf doorset and the other on double-leaf doorset, hence<br />
options on glazed apertures can be incorporated into a Field of Application Report. We can<br />
offer a number of glasses as alternatives but if there are other glasses which you would wish to<br />
be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please let us know so that<br />
their test evidence can be reviewed.<br />
Each of the tested doorsets included a door skin on each face, hence the option of various door<br />
skins including material and thickness will be incorporated into a Field of Application Report.<br />
The maximum tested leaf size was a 2040mm high by 927mm wide for single door leaf, and a<br />
2400mm high by 1200mm wide for each leaf of double door. The size of the double leaves<br />
indicates that the possibility of enlarging the single door leaf size would be achievable.<br />
Evaluations for the maximum leaf size will be made for incorporation into a future Field of<br />
Application Report.<br />
1.3 Questions<br />
All the doorsets utilised in this section included tubeboard core, which will be included as an<br />
option on core detail in a Field of Application Report, therefore the following questions,<br />
regarding incorporation of various tubeboard core constructions, need to be confirmed:<br />
2<br />
The core construction of tubeboard 38 RF shown in the test report of WARRES No.<br />
69484/A is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />
<strong>Spanplatte</strong>. Would your confirm the core construction of tubeboard 38 RF?<br />
The core construction of tubeboard 38 RE 7 shown in the WF Test Report No. 159842<br />
(Doorset B) is not included in the Production Range of the Technical Manual of<br />
<strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm the core construction of tubeboard 38 RE 7?<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
If there are other types of tubeboard core constructions, apart from the ones included<br />
in the received test reports, which you would wish to be considered within the<br />
<strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to be<br />
reviewed.<br />
1.4 Recommendation<br />
We feel there is scope to test an unlatched specimen to supplement the test evidence available<br />
and would be pleased to discuss details with you. It is the opinion of IFC, however that there is<br />
considerable scope for inclusion in a Field of Application Report and a proposal for this could be<br />
issued on request.<br />
2. <strong>Sauerland</strong> Solid Core/Sandwich Core Fire Resisting Doorsets<br />
2.1 Test Evidence<br />
There are seven tests which have been taken into account in the review of solid<br />
core/sandwich core fire resisting doorsets. These tests described in this section have been<br />
performed according to the general principles of BS476: Part 22: 1987.<br />
Six of the seven tests were carried out at Warringtonfire whilst the other test was carried out at<br />
Chiltern. They all utilised latched, single acting, single and double leaf doorsets. These tested<br />
doorsets utilised 44mm/45mm/54mm thick leaves of various core constructions with bespoke<br />
intumescent seal specifications. Two of the doorsets incorporated glazed apertures with<br />
Georgian wired glass.<br />
A summary of the tests is outlined in Appendix B.<br />
2.2 Scope for Assessment<br />
A review of the seven test results in the following options being available as a scope which<br />
could be included in a subsequent IFC Field of Application Report. This scope would be subject<br />
to the limitations of the report which can be commissioned following this analysis.<br />
Doorsets with 44mm thick leaf<br />
All three doorsets, with 44mm thick leaves, have demonstrated at least 30 minutes fire<br />
resistance performance.<br />
All the doorsets utilised latched, single acting, single leaf configurations, hence these features<br />
can be incorporated into a Field of Application Report. There is no evidence for unlatched or<br />
double leaf configurations.<br />
There is currently no test evidence to support the use of glazed apertures for these tested<br />
doorsets, therefore this feature can not be incorporated into a Field of Application Report<br />
without additional fire test evidence.<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
3
Each of the tested doorsets included a door skin on each face, either 3mm HDF or 3mm<br />
Hardboard, hence the option of various door skins including material and thickness can be<br />
incorporated into a Field of Application Report.<br />
The maximum tested leaf size was 2040mm high by 926mm wide. This will be taken into<br />
account with any overrun in determining the maximum leaf size to be included into a Field of<br />
Application Report.<br />
Doorset with 45mm thick leaf<br />
The doorset with a 45mm thick leaf has demonstrated 63 minutes fire resistance performance.<br />
The doorset utilised latched, single acting, single leaf configuration, hence these features can be<br />
incorporated into a Field of Application Report. There is no evidence for unlatched or double<br />
leaf configurations.<br />
There is currently no test evidence to support the use of glazed apertures for this doorset,<br />
therefore this feature can not be incorporated into a Field of Application Report without<br />
additional fire test evidence.<br />
The doorset included a layer of 6mm Hardboard on each face, hence it will be incorporated into<br />
a Field of Application Report.<br />
The maximum tested leaf size was 2040mm high by 900mm wide. This will be taken into<br />
account with any overrun in determining the maximum leaf size to be included into a Field of<br />
Application Report.<br />
Doorsets with 54mm thick leaf<br />
The two tested single doorsets with a 54mm thick leaf have demonstrated 71 minutes and 75<br />
minutes fire resistance performance. The double doorset with a 54mm thick leaf achieved 59<br />
minutes fire resistance performance.<br />
All the doorsets were single acting and latched, hence both of these limitations will be<br />
incorporated into a Field of Application Report.<br />
The doorsets included single and double leaf configurations, hence both of these options can be<br />
incorporated into a Field of Application Report.<br />
Two of the doorsets utilised have been tested incorporating glazed apertures with 6mm thick<br />
Georgian wired glass, including one single-leaf doorset (achieving 71min fire resistance<br />
performance) and the other on double-leaf doorset (achieving 59min fire resistance<br />
performance). Options on glazed apertures can be incorporated into a Field of Application<br />
Report. We can offer a number of glasses as alternatives but if there are other glasses which<br />
you would wish to be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please<br />
let us know so that their test evidence can be reviewed.<br />
4<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
Each of the tested doorset included a door skin on each face, hence the option of various door<br />
skins including material and thickness will be incorporated into a Field of Application Report.<br />
The maximum leaf size achieving 60 minutes fire resistance performance was 2040mm high by<br />
928mm wide for single door leaf. The tested double-leaf doorset with different leaf size has not<br />
achieved 60 minutes fire resistance performance, however it is possible that the doorset with<br />
smaller leaves or equally sized double leaf might achieve 60 minutes fire resistance<br />
performance, therefore the maximum leaf size for single and double leaf, discussed above, will<br />
be taken into account when determining the maximum leaf size in a Field of Application Report.<br />
2.3 Questions<br />
In this section, there are five doorsets utilised solid core and two doorsets utilised sandwich<br />
core, hence the option on core construction details will be into a Field of Application Report.<br />
Therefore the following questions, regarding incorporation of various core constructions, need<br />
to be confirmed:<br />
The core construction of solidboard 38 VT5 shown in the test report of WF Test Report<br />
No. 159842 (Doorset A) is not included in the Production Range of the Technical<br />
Manual of <strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm the core construction of<br />
solidboard 38 VT5?<br />
The core construction of solidboard 42 VL shown in the WF Test Report No. 175295<br />
(Doorset A) and the WF Test Report No. 175295 (Doorset B) is not included in the<br />
Production Range of the Technical Manual of <strong>Sauerland</strong> <strong>Spanplatte</strong>. Would you confirm<br />
the core construction of solidboard 42 VL?<br />
If there are other types of solid core and sandwich core constructions, apart from the<br />
ones included in the received test reports, which you would wish to be considered<br />
within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to<br />
be reviewed.<br />
2.4 Recommendation<br />
In this section, there are three different thickness leaves with 44mm, 45mm and 54mm to<br />
achieve 30 minutes and 60 minutes fire resistance performance, but you may not market all of<br />
them. We would ask you to confirm which you do market.<br />
Furthermore, we feel there may be scope to test unlatched specimen and double leaves for the<br />
44mm and 45mm thick leaves to supplement the test evidence available and would be pleased<br />
to discuss details with you. It is the opinion of IFC, however, that there is considerable scope<br />
for inclusion of the FD60 doorsets with 54mm thick leaves in a Field of Application Report and a<br />
proposal for this could be issued on request.<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
5
3. <strong>Sauerland</strong> Moulded Core Fire Resisting Doorsets<br />
3.1 Test Evidence<br />
There are seven tests which have been taken into account in the review of moulded core fire<br />
resisting doorsets. There are five tests described in this section which have been performed<br />
according to the general principles of BS476: Part 22: 1987, while the other two tests<br />
following BS EN 1634-1: 2000.<br />
These tests were carried out at Warringtonfire, utilising single acting, latched and unlatched,<br />
single and double leaf doorsets. The doorsets utilised 44mm/54mm thick leaves of various core<br />
constructions with bespoke intumescent seal specifications. One of the doorsets incorporated<br />
glazed apertures with Georgian wired glass.<br />
A summary of the tests is outlined in Appendix C.<br />
3.2 Scope for Assessment<br />
A review of the seven test results in the following options being available as a scope which<br />
could be included in a subsequent IFC Field of Application Report. This scope would be subject<br />
to the limitations of the report which can be commissioned following this analysis.<br />
Doorsets with 44/45mm thick leaf<br />
The four single-leaf doorsets with 44mm thick leaf, one double-leaf doorset with 44mm thick<br />
leaf and one single-leaf doorset with 45mm thick leaf have demonstrated at least 30 minutes<br />
fire resistance performance.<br />
All the doorsets utilised were single acting, hence the feature will be incorporated into a Field of<br />
Application Report.<br />
Five single-leaf tested doorsets were latched and a double-leaf doorset was unlatched, which<br />
indicates that it is possible for single-leaf doorsets utilising unlatched leaf and double-leaf<br />
doorsets utilising latched leaf. Hence, these features can be included into a Field of Application<br />
Report.<br />
All the tested doorsets included single leaf and double leaf, hence both of these options can be<br />
incorporated into a Field of Application Report.<br />
One of the single-leaf doorsets utilised was tested incorporating glazed apertures with Georgian<br />
wired glass, hence options on glazed apertures can be incorporated into a Field of Application<br />
Report. We can offer a number of glasses as alternatives but if there are other glasses which<br />
you would wish to be considered within the <strong>Sauerland</strong> Core Fire Resisting Doorsets then please<br />
let us know so that their test evidence can be reviewed.<br />
6<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
Each of the tested doorset included a layer of moulded hardboard on each face either 3mm<br />
thick or 3.5mm thick, hence the option of various door skins including material and thickness<br />
will be incorporated into a Field of Application Report.<br />
The maximum tested leaf size was 2040mm high by 926mm wide for single-door leaf, and<br />
1981mm high by 762mm wide for each leaf of double door. The size of the double leaves<br />
indicates that the possibility of enlarging the single door leaf size would be achievable, therefore<br />
the maximum leaf size, discussed above, will be considered in determining the maximum leaf<br />
size which can be incorporated into a Field of Application Report.<br />
Doorsets with 54mm thick leaf<br />
The single-leaf doorset with 54mm thick leaf utilised has demonstrated 60 minutes fire<br />
resistance performance.<br />
The tested doorset utilised a latched, single acting, single leaf configuration, hence these<br />
features will be incorporated into a Field of Application Report.<br />
There is currently no test evidence to support the use of glazed apertures for the tested<br />
doorset, therefore this feature can not be incorporated into a Field of Application Report without<br />
additional fire test evidence.<br />
The tested doorset included a layer of 3mm thick moulded hardboard on each face, hence the<br />
feature will be included into a Field of Application Report.<br />
The maximum tested leaf size was 1981mm high by 840mm wide for single door leaf, therefore<br />
the maximum size will be considered for incorporation into a Field of Application Report.<br />
3.3 Questions<br />
In this section, there are seven doorsets that utilised routed core with moulded skin on each<br />
face, hence this option on core construction details will be into a Field of Application Report.<br />
Therefore the following questions, regarding incorporation of various core constructions, need<br />
to be confirmed:<br />
The core construction of tubeboard 38 RF shown in the test report of WARRES No.<br />
69484 B is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />
<strong>Spanplatte</strong>. Would you confirm the core construction of tubeboard 38 RF?<br />
The core construction of solidboard 18 VL shown in the test report of WARRES No.<br />
105976 A is not included in the Production Range of the Technical Manual of <strong>Sauerland</strong><br />
<strong>Spanplatte</strong>. Would you confirm the core construction of solidboard 18 VL?<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
7
8<br />
If there are other types of routing core and moulded skin, apart from the ones included<br />
in the received test reports, which you would wish to be considered within the<br />
<strong>Sauerland</strong> Core Fire Resisting Doorsets then their test evidence will have to be<br />
reviewed.<br />
3.4 Recommendation<br />
The unlatched double-leaf doorset with each leaf 44mm thick has achieved 31 minutes fire<br />
resisting performance, which will be possible for IFC to incorporate a range of features for<br />
44mm thick doorsets achieving 30 minutes fire resistance into a Field of Application. There may<br />
be scope to test an unlatched specimen with 54mm thick double leaf to supplement the test<br />
evidence available and would be pleased to discuss details with you.<br />
4. Conclusion<br />
The scope of approval that could be included, if commissioned, in IFC Field of Application<br />
Reports is listed in the following table.<br />
Item Latched Unlatched<br />
44mm FD30<br />
<strong>Tubeboard</strong><br />
Core ¡<br />
44mm FD30<br />
Sandwich/<br />
Solid Core ¡<br />
45mm FD60<br />
Sandwich/<br />
Solid Core ¡<br />
54mm FD60<br />
Sandwich/<br />
Solid Core ¡<br />
44mm FD30<br />
Routed Core ¡<br />
54mm FD60<br />
Routed Core ¡<br />
×<br />
×<br />
×<br />
×<br />
¡<br />
¡<br />
¡<br />
¡<br />
Single<br />
Acting<br />
×<br />
×<br />
×<br />
×<br />
Double<br />
Acting<br />
Single<br />
Leaf<br />
Double<br />
Leaf<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
¡<br />
¡<br />
¡<br />
¡<br />
Glazed<br />
Apertures<br />
¡ ¡<br />
¡ ¡<br />
×<br />
×<br />
×<br />
×<br />
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡<br />
× ×<br />
Note:<br />
= Can be assessed from existing received test evidence<br />
× = Not accessible with existing received test evidence<br />
¢<br />
×<br />
×
We are now in a position to forward proposals and fee estimates for some or all of the<br />
constructions listed for you to commission us to prepare Field of Application Reports. These,<br />
however, are likely to cost in the region of £2,200 - £3,500 per doorset construction to produce<br />
and so we feel that you may wish to consider them on the basis of a longer term strategy, i.e.<br />
some now and some later.<br />
We would also anticipate that you may wish to extend the potential scope for some of the door<br />
leaf types through further fire resistance testing. This could also include design features not<br />
already discussed herein. This can also be discussed as part of the ongoing programme.<br />
We would ask you to review and respond to the above information. Following your response<br />
we will produce a formal proposal and fee estimate for the next step in agreeing the scope of<br />
works.<br />
We trust this is of assistance at this time. If you have any queries please do not hesitate to<br />
contact us.<br />
Yours sincerely: Checked by:<br />
Ping Guo BEng (Hons) MSc David Cooper BEng (Hons) MIWSc<br />
Graduate Engineer Senior Engineer<br />
International Fire Consultants Ltd. (IFC) International Fire Consultants Ltd. (IFC)<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
9
10<br />
APPENDIX A<br />
Summary of Test Evidence on <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
No Test<br />
Number<br />
1<br />
2<br />
3<br />
4<br />
5<br />
WF Test Report<br />
No. 14606<br />
(Doorset B)<br />
WARRES<br />
No. 117066<br />
WARRES<br />
No. 69484/A<br />
WF Test Report<br />
No. 14606<br />
(Doorset A)<br />
WF Test Report<br />
No. 159842<br />
(Doorset B)<br />
Summary of Test Evidence on <strong>Tubeboard</strong> Core Fire Resisting Doorsets<br />
Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />
BS EN 1634-1:<br />
2000<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS EN 1634-1:<br />
2000<br />
BS 476: Part<br />
22: 1987<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Double leaf<br />
Partially insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Uninsulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
<strong>Tubeboard</strong> 38 RE<br />
<strong>Tubeboard</strong> 33 RH<br />
With glass opening<br />
300 × 1000 “Georgian<br />
wired”<br />
<strong>Tubeboard</strong> 38 RF<br />
With glass opening<br />
578 × 908× 6mm<br />
“Georgian wired<br />
plate”<br />
<strong>Tubeboard</strong> 38 RE<br />
<strong>Tubeboard</strong> 38 RE 7<br />
2.8mm<br />
MDF+ veneer<br />
5mm<br />
Hardwood<br />
3.2mm<br />
Hardboard<br />
3mm<br />
HDF+ veneer<br />
3mm<br />
Hardboard<br />
927 × 2040<br />
× 44mm<br />
2 × 1200 ×<br />
2400 ×<br />
44mm<br />
837 × 1981<br />
× 44mm<br />
927 × 2040<br />
× 44mm<br />
926 × 2040<br />
× 44mm<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
15 × 2 mm Palusol<br />
frame jambs + head<br />
15 × 2 mm Interdens<br />
base of leaf<br />
2×10× 2 mm Palusol, head<br />
frame<br />
2×10 × 2 mm Interdens,<br />
rebated meeting stile<br />
10 × 2 mm Interdens, frame<br />
jambs<br />
10 × 2mm Palusol LP1002<br />
frame jambs + head<br />
10 × 2mm Pyrostrip 300<br />
glazing seal<br />
15 × 2 mm Palusol<br />
frame jambs + head<br />
15 × 2 mm Interdens<br />
base of leaf<br />
15 × 2 mm Palusol T<br />
frame jambs + head<br />
Integrity: 33 min<br />
Insulation: 33 min<br />
Integrity: 34 min<br />
Insulation: 34 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 36 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 36 min<br />
Insulation: 36 min<br />
Integrity: 36 min<br />
Insulation:36 min<br />
11
12<br />
APPENDIX B<br />
Summary of Test Evidence on Solid Core/Sandwich Core<br />
Fire Resisting Doorsets<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
Summary of Test Evidence on Solid Core/Sandwich Core Fire Resisting Doorsets<br />
No. Test Number Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
WF Test Report<br />
No. 164432<br />
( Doorset B)<br />
WF Test Report<br />
No. 164432<br />
( Doorset A)<br />
WF Test Report<br />
No. 159842<br />
( Doorset A)<br />
Chilten/RF02009<br />
WF Test Report<br />
No. 175295<br />
( Doorset B)<br />
WF Test Report<br />
No. 175295<br />
( Doorset A)<br />
WARRES<br />
No. 105976 B<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
BS 476: Part<br />
22: 1987<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Latched<br />
Single acting<br />
Double leaf<br />
Partially insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Partially insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
<strong>Sauerland</strong><br />
Sandwich board<br />
38 S2<br />
<strong>Sauerland</strong><br />
Sandwich board<br />
38 S3K<br />
<strong>Sauerland</strong><br />
Solid board 38 VT5<br />
<strong>Sauerland</strong> 33 VL<br />
<strong>Sauerland</strong> 42 VL<br />
With glass opening<br />
6mm thick “Georgian<br />
wired polished plate”<br />
<strong>Sauerland</strong> 42 VL<br />
With glass opening<br />
6mm thick “Georgian<br />
wired polished plate”<br />
<strong>Sauerland</strong> 38 VL<br />
+ 5mm MDF<br />
3mm HDF<br />
3mm HDF<br />
3mm<br />
Hardboard<br />
6mm<br />
Hardboard<br />
5.8mm HDF<br />
5.8mm HDF<br />
3mm<br />
Hardboard<br />
926 × 2040 ×<br />
44mm<br />
926 × 2040 ×<br />
44mm<br />
926 × 2040 ×<br />
44mm<br />
900 × 2040 ×<br />
45mm<br />
Primary leaf<br />
900 × 2400 ×<br />
54mm +<br />
secondary leaf<br />
415 × 2400 ×<br />
54mm<br />
928 × 2040 ×<br />
54mm<br />
840 × 1981 ×<br />
54mm<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
15 × 2 mm Palusol T<br />
frame jambs + head<br />
15 × 2 mm Palusol T<br />
frame jambs + head<br />
15 × 2 mm Palusol T<br />
frame jambs + head<br />
2× 10 × 2 mm Palusol<br />
frame jambs + head<br />
10 × 2 mm Interdens<br />
(between core and<br />
framing)<br />
30 × 2 mm Rokustrip<br />
frame jambs + head<br />
20 × 2 mm Rokustrip / 10<br />
× 2 mm Rokustrip<br />
(meeting stile)<br />
30 × 2 mm Rokustrip<br />
frame jambs + head<br />
2× 10 × 2 mm Palusol<br />
frame jambs + head<br />
Integrity: 31 min<br />
Insulation: 31 min<br />
Integrity: 40 min<br />
Insulation: 39 min<br />
Integrity: 40 min<br />
Insulation:40 min<br />
Integrity: 63 min<br />
Insulation:63 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 59 min<br />
Insulation:59 min<br />
Integrity: 71 min<br />
Insulation:71 min<br />
Integrity: 75 min<br />
Insulation: 75 min<br />
13
14<br />
APPENDIX C<br />
Summary of Test Evidence on Routed Core with Moulded Skin<br />
Fire Resisting Doorsets<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd
Summary of Test Evidence on Routed Core with Moulded Skin Fire Resisting Doorsets<br />
No. Test Number Standard Configuration Core detail Skin Leaf size Intumescent seal Result<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
WARRES<br />
No. 105554<br />
WARRES<br />
No. 69484/B<br />
WARRES<br />
No. 67040/B<br />
WARRES<br />
No. 60270/B<br />
WF Test Report<br />
No. 145083<br />
(Doorset A)<br />
WF Test Report<br />
No. 145083<br />
(Doorset B)<br />
WARRES<br />
No. 105976/A<br />
BS 476:<br />
Part 22: 1987<br />
BS 476:<br />
Part 22: 1987<br />
BS 476:<br />
Part 22: 1987<br />
BS 476:<br />
Part 22: 1987<br />
BS EN<br />
1634 – 1:2000<br />
BS EN<br />
1634 – 1:2000<br />
BS 476:<br />
Part 22: 1987<br />
Single acting<br />
Double leaf<br />
Fully insulated<br />
Unlatched<br />
Single acting<br />
Single leaf<br />
Uninsulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Single acting<br />
Single leaf<br />
Fully insulated<br />
Latched<br />
Solid board 38 PV<br />
With moulding<br />
<strong>Tubeboard</strong> 38 RF<br />
With glass opening<br />
578 × 908 × 6mm<br />
“Georgian Wired ”<br />
Solid board 38 PV<br />
With moulding<br />
Solid board 38 PV<br />
(chipboard core)<br />
With moulding<br />
Solid board 38 PV<br />
With moulding<br />
Solid board 38 PV<br />
With moulding<br />
Solid board 18VL<br />
3mm Moulded<br />
hardboard<br />
(MASONITE)<br />
3mm Moulded<br />
Hardboard<br />
(MASONITE)<br />
3.5mm Moulded<br />
hardboard<br />
(MASONITE)<br />
3mm Moulded<br />
hardboard<br />
(MASONITE)<br />
3mm Moulded<br />
hardboard<br />
(MASONITE)<br />
3mm Moulded<br />
hardboard<br />
(MASONITE)<br />
3mm Moulded<br />
hardboard<br />
(MASONITE)<br />
2 ×762 × 1981<br />
× 44mm<br />
837 × 1981<br />
× 44mm<br />
824 × 1985<br />
× 45mm<br />
820 × 1980<br />
× 44mm<br />
926 × 2040<br />
× 44mm<br />
926 × 2040<br />
× 44mm<br />
840 × 1981<br />
× 54mm<br />
IFC Fire Safety Advice <strong>FSA</strong>/<strong>9150</strong>/01 – <strong>Sauerland</strong> <strong>Spanplatte</strong> GmbH & Co KG<br />
Development of <strong>Sauerland</strong> Core Fire Resisting Doorsets<br />
International Fire Consultants Ltd<br />
10× 2 mm Palusol<br />
top rail<br />
10 × 2 mm Interdens<br />
rebated meeting stile +<br />
leaf james + bottom rail<br />
10 × 2mm Palusol LP1002<br />
(frame jambs + head)<br />
10 × 2mm Pyrostrip 300<br />
(glazing seal)<br />
10 × 2mm Palusol LP1002<br />
in top edge of door leaf<br />
10 × 4mm Palusol LP1004<br />
frame jambs + head<br />
15× 2 mm Palusol<br />
head + frame james<br />
15× 2 mm Palusol<br />
head + frame james<br />
10 × 2 mm Interdens, bottom<br />
rail<br />
2× 10 × 2 mm Palusol<br />
frame jambs + head<br />
Integrity: 31 min<br />
Insulation: 31 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 32 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 33 min<br />
Insulation: 33 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 34 min<br />
Insulation: 34 min<br />
( opening towards<br />
the furnace)<br />
Integrity: 36 min<br />
Insulation:32 min<br />
Integrity: 37 min<br />
Insulation:35 min<br />
Integrity: 60 min<br />
Insulation: 60 min<br />
15