light, thus ensuring that the lightingconforms with the data set out in theCIBSE lighting guide for hospitals. Asstandard the light modules use highfrequency, quick start ballasts which canbe dimmed locally for use as the nightlight.Adjustable Arm Lighting<strong>MEDISYS</strong> <strong>integra</strong> also has theability to provide bedheadreading/observation or examinationlighting via one or more ‘anglepoise’-type lamps, which are fitted to the front of the trunkingby a special bedlight bracket. We can supply theselamps from a variety of manufacturers or alternativelythey can easily be site-fitted by the installing contractor.All assembly fixings are hidden from view, ensuring aneasy to clean and aesthetically pleasing finish.EMC CertificationProtecting electronic components from ElectromagneticInterference and Radio Frequency Interference is ofparamount importance, especially within a healthcareenvironment. <strong>MEDISYS</strong> <strong>integra</strong> has been designedspecifically to ensure that each chamber, and in turneach individual compartment, controls both the emissionand reception of Electromagnetic and Radio FrequencyInterference.By specifying <strong>MEDISYS</strong> <strong>integra</strong> you can be satisfiedthat the EMC elements of the Medical Devices Directivehave been complied with, and have been tested for byBSI with all of the nurse call system in operation.All metallic sections have an extruded earthingprovision, therefore the system components can simplybe earthed in accordance with the latest IEE WiringRegulations (BS7671). This has been designed andtested to ensure that all discharged static is dissipatedaway without causing any effect to sensitive nurse callor other ancillary components within the trunking and itsenvironment. This has specificimportance when considering the buildupof static within a patient or memberof the nursing staff, which could easilybe discharged through the trunkingwhen they come into direct contact.A ground equalisation socket isavailable so that items whereelectrostatic discharge may occur (suchas bed frames) can be attached withminimal fuss.Engraved Text and LegendsDue to the specific nature of individual accessory lids inhospital applications, it is essential that legends andusage instructions are clearly evident to the user. Weadopt a policy of engraving all text and legends on oursystems thus ensuring a greater life span for thecomponent and making it easy for the user to identifythe relevant service.Module Construction<strong>MEDISYS</strong> <strong>integra</strong> is factory assembled with alloutlets pre-configured. The module can then be fitted onsite as a second or third fix item and, if required, we canpre-wire and pre-pipe prior to despatch, all with testcertification. The <strong>integra</strong>l lighting systems are alwayspre-wired.This method of production reduces costs by benefitingfrom lower labour rates for off-site assembly, andspeeds up the general site installation time whilsthelping to eliminate the risk of on-site damage totrunking and abuse by other trades during theconstruction phases.Medical Equipment RailWhile some systems have an <strong>integra</strong>l Medical EquipmentRail, our review of this concept has concluded it is an illconceivedfailure. Its inclusion invariably obstructs othertrunking-mounted outlets and the forces exerted on therail can cause the extrusions to buckle.Issue: A May 2004 Page 5 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


Instead we manufacture a separate Medical-Rail to EN12218 which is independently wall mounted (separatedatasheet available)Vertical RisersWe recognise the need to keep the visual effect of thetrunking to a minimum and have developed a slimtrunking section to tee into the system for the supply ofall services.The overall size of this riser is 180 x 45mm but can bedoubled up if a larger volume of services are to beaccommodated.InstallationEach module is secured directly to the wall surface usingsuitable fixings (refer to installation instructions). Theuse of proprietary mounting plates is not recommendedwith such a system. All wall deviations should be filledWe have recognised the need of some clients to procurea total package from a specialist manufacturer.Our experienced Contracts Department specialises in theinstallation of our trunking systems, a major factor insatisfying this requirement.Our in-house installation technicians are trained to thehighest standards, to achieve the best possible resultwhen our products and their services are co-ordinated.By equipping them with the latest machinery and tools,they are able to complete installations quickly andefficiently and our expert product knowledge assists inensuring a successful conclusion to any contract.Further information about this service can be obtainedby contacting our Sales Team who will be pleased toprovide you with a costing on your specific applicationfor installation or machine hire.using a suitable caulk or mastic.Issue: A May 2004 Page 6 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


Technical SpecificationInternational Standards:Material:Surface Finish:Service Entry:Installation:End Caps:See back pagesExtruded Aluminium (A MgS:0.5)Powder coated* / AnodisedCan be either back-fed or fed via a purpose designed riser section withcorresponding features.Supplied as a factory pre-built module. TECHNOTRUNK <strong>MEDISYS</strong> <strong>integra</strong>is generally secured directly to the wall above the head of a bed in accordancewith HTM 2015.Supplied in steel, either open or closed depending on requirements<strong>integra</strong> M10 <strong>integra</strong> M10-U <strong>integra</strong> M10-D104mm 104mm 104mm237mm210mm196mmCapacitiesMax. No. of electrical compartments: 3Max. No. of pipes: 2Compartment capacity (gross)mm²:1 1034 (2151 with downlight only)2 6173 1588Issue: A May 2004 Page 7 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M20 <strong>integra</strong> M20-U <strong>integra</strong> M20-D104mm 104mm 104mm270mm244mm230mmCapacitiesMax. No. of electrical compartments: 4Max. No. of pipes: 4Compartment capacity (gross)mm²:1 1675 (3014 with downlight only)2 6173 6524 2289Issue: A May 2004 Page 8 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M13 <strong>integra</strong> M13-U <strong>integra</strong> M13-D104mm 104mm 104mm360mm322mm322mmCapacitiesMax. No. of electrical compartments: 3Max. No. of pipes: 4Compartment capacity (gross)mm²:1 1034 (2151 with downlight only)2 6173 1588Issue: A May 2004 Page 9 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M14 <strong>integra</strong> M14-U <strong>integra</strong> M14-D104mm 104mm 104mm394mm356mm356mmCapacitiesMax. No. of electrical compartments: 3Max. No. of pipes: 5Compartment capacity (gross)mm²:1 1034 (2151 with downlight only)2 6173 1588Issue: A May 2004 Page 10 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M23 <strong>integra</strong> M23-U <strong>integra</strong> M23-D104mm 104mm 104mm394mm356mm356mmCapacitiesMax. No. of electrical compartments: 4Max. No. of pipes: 4Compartment capacity (gross)mm²:1 1675 (3014 with downlight only)2 6173 6524 2289Issue: A May 2004 Page 11 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M24 <strong>integra</strong> M24-U <strong>integra</strong> M24-D104mm 104mm 104mm427mm389mm389mmCapacitiesMax. No. of electrical compartments: 4Max. No. of pipes: 6Compartment capacity (gross)mm²:1 1675 (3014 with downlight only)2 6173 6524 2289Issue: A May 2004 Page 12 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M132 <strong>integra</strong> M132-U <strong>integra</strong> M132-D104mm 104mm 104mm519mm481mm481mmCapacitiesMax. No. of electrical compartments: 4Max. No. of pipes: 5Compartment capacity (gross)mm²:1 1034 (2151 with downlight only)2 6173 15884 3985Issue: A May 2004 Page 13 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


<strong>integra</strong> M142 <strong>integra</strong> M142-U <strong>integra</strong> M142-D104mm 104mm 104mm552mm514mm514mmCapacitiesMax. No. of electrical compartments: 4Max. No. of pipes: 6Compartment capacity (gross)mm²:1 1034 (2151 with downlight only)2 6173 15884 7719Issue: A May 2004 Page 14 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


Applicable StandardsDocument ReferenceBS 196BS 476BS 1363-2BS 2754BS 3676-1 & BS EN 60669-1BS 4533BS 4662BS 5266BS 5394Document DescriptionNon-reversible Plugs and Socket Outlet Up to 250 VoltsFire Tests on Building Materials and Structures13A Switched and Unswitched Socket OutletsConstruction of Electrical Equipment for Protection against Electric ShockSwitches for Fixed Electrical InstallationsGeneral Requirements for LuminairesElectrical Accessory BoxesEmergency Lighting SystemsRadio Interference Characteristics of Fluorescent LampsBS 5490 Degrees of Protection Provided by Enclosures (EN 60 529)BS 5733BS 6496BS 6701BS 6972General Requirements of Electrical Equipment and EnclosuresPowder Coating to Metal EnclosuresCode of Practice for Installation of Apparatus Intended for Connection to CertainTelecommunication SystemsSpecification for General Requirements for Luminaire Supporting Couplers forDomestic, Light Industrial and Commercial useBS 7671 IEE Wiring Regulations (EN 60 364)BS EN 737-1BS EN 737-4BS EN 793BS EN 12464-1BS EN 13032-2BS EN 50081BS EN 50082BS EN 50083BS EN 50085BS EN 60439BS EN 60598-1BS EN 60601-1BS EN 60601-1-2IEC 60364-7-710CIECIBSE LG:2CIBSE LG:3HTM 1HTM 17HTM 2007Medical Gas Pipeline Systems. Terminal Units for Compressed Medical Gases andVacuumMedical Gas Pipeline Systems. Terminal Units for Anaesthetic Gas Scavenging SystemsParticular Requirements for Safety of Medical Supply UnitsLight and Lighting – Lighting of indoor workplacesLight and Lighting – PhotometricEMC Generic Emission StandardEMC Generic Immunity StandardCabled Distribution Systems for Television and Sound SignalsCable Trunking and Cable Ducting Systems for Electrical InstallationsSpecification for Low-Voltage Switchgear and Controlgear AssembliesGeneral Requirements for LuminairesMedical electrical equipment. General requirements for safetyCollateral standard. Electromagnetic compatibility. Requirements and testsIEC Wiring regulations – Medical LocationsEuropean Lighting GuideLighting Guide – Medical Installations and Hospital BuildingsLighting Guide – General EnvironmentsAnti-static PrecautionsHealth Building Engineering InstallationsElectrical Services Supply and DistributionIssue: A May 2004 Page 15 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com


HTM 2011HTM 2014HTM 2015HTM 2020HTM 2022HBN 40NHS SPEC C4972/23/EEC89/336/EEC93/42/EECEmergency Electrical ServicesAbatement of Electrical InterferenceBedhead ServicesElectrical Safety Code for Low Voltage SystemsPiped Medical Gas InstallationThe Patient Environment – Common Activity SpacesPatient Call SystemsLow Voltage DirectiveEMC DirectiveMedical Devices DirectiveThis product is designed and where applicable tested and certified in accordance with the aforementioned documents.Cableflow International LimitedWindsor HouseAbbey Barn RoadHigh WycombeBuckinghamshireHP11 1NNUnited KingdomMade in UKIssue: A May 2004 Page 16 of 16Phone: +44 (0) 1494 528811Fax: +44 (0) 1494 531188E-mail: sales@cableflow.comWeb: www.cableflow.com