SYSTEM BSRATED VOLTAGE~ 240VCHARACTERISTICSCorrection factor for converting the power dissipation for percentage loadLoad( %)Correction factor10 0,00520 0,02530 0,06340 0.12250 0,20460 0,3170 0,44280 0,690 0,785100 1Power dissipation, pre-arcing Joule Integral and Operating Joule Integral for Ultra Quick BS8, BS17, BS38, BS38TULTRA QUICKSize I nPowerdissipationBS8BS17BS38BS38TPre-arcingJoule integralI 2 t (1ms)OperatingJoule IntegralI 2 t ~ 120VOperatingJoule IntegralI 2 t ~ 240VA W A 2 s A 2 s A 2 s6 1 2 6 910 2,5 3,8 12 2212 2,5 7 22 3216 2,5 20 50 10020 4 25 80 16025 4 18 120 25032 5 32 200 45035 5 50 320 60050 7 100 500 1.40063 9 180 1.100 2.20080 10 300 1.900 3.800100 10 600 3.800 7.500125 16 600 3.800 7.500160 20 1.100 7.000 16.000180 21 1.600 12.000 29.000160 17 1.100 7.000 16.000200 28 1.500 10.000 20.000250 28 3.200 20.000 40.000315 35 6.000 35.000 75.000355 35 8.000 50.000 100.000400 40 14.000 70.000 160.000450 42 18.000 100.000 220.000400 60 6.000 35.000 80.000500 64 14.000 80.000 170.000630 75 24.000 150.000 300.000710 77 32.000 200.000 460.000800 82 52.000 300.000 600.00056